Está en la página 1de 23

DATOS PRINCIPALES

VOLTAJE DE LINEA (KV) 220


VOLTAJE DE FASE (KV) 127.02
DISTANCIA DE LINEA (Km) 221.16
TEMPERATURA (c) 15
LONGITUD DE VANO (m) 330

TIPO DE TORRE # DE TORRES # DE CADENAS DE AISLADORES POR TORRE


ESTRUCTURA DE INICIO 1 12
ESTRUCTURA DE FIN 1 12
ESTRUCTURA DE ALINEACION 490 3
ESTRUCTURA DE ANCLAJE 134 12
ESTRUCTURA ESPECIAL 2 12
ESTRUCTURA DE ANGULO 42 6
TOTAL 670
670
TRAMO DISTANCIA Km
1 2.88
2 3.42
3 2.81
4 7.69
5 3.45
6 4.52
7 5.87
8 7.14
9 1.49
10 1.95
11 5.7
12 6.56
13 14.6
14 12.7
15 3.11
16 1.62
17 5.35
18 3.17
19 8.65
20 2.65
21 2.73
22 1.42
23 4.64
24 3.5
25 2.33
26 6.99
27 19.6
28 3.52
29 2
30 2.93
31 1.61
32 1.62
33 2.43
34 5.94
35 11.7
36 3.66
37 2.99
38 8.1
39 4.78
40 6.44
41 6.95
42 4.67
43 3.12
TOTAL 219
DATOS PRINCIPALES
CADENA DE AISLADORES EN SUSPENSION
CADENA DE AISLADORES DE AMARRE
FRECUENCIA Hz
TENSION MAS ELEVADA REGLAMENTO LIN.
POTENCIA (MVA)

#AISLADORES X CADENA
16
16
15
16
16
16

EFECTO CORONA

ALTURA
0 - 100
100 - 200
200 - 300
300 - 400

TIEMPO
seco
humedo

T1
T2
T3
T4

T1
T2
T3
T4

T1
T2
T3
T4
TOTAL

PER

PERDIDAS TOTALES EN LA LINEA


PERDIDAS TOTALES EN AISLADORES (KW)
PERDIDAS TOTALES EFECTO CORONA (KW)
TOTAL (KW)

PERDIDAS TRIFASICAS KILOMETRICAS EN LA LINEA (KW/Km)


PERDIDAS POR KILOMETRO EN AISLADORES (KW/Km)
PERDIDAS KILOMETRICAS POR EFECTO CORONA (KW/Km)
TOTAL (KW/Km)

RENDIMIENTO
0.0065812701
DATOS PRINCIPALES
15 ELEMENTOS CADA UNO
16 ELEMENTOS CADA UNO
60
245
180

CANTIDAD DE AISLADORES TOTALES


192
192
22050
25728
384
4032
52578

CALCULOS

W
TIEMPO
TEMPERATURA SECA 3

TEMPERATURA HUMEDA 20

Gkf CONDUCTANCIA KILOMETRICA POR FASE (S/Km) Gkt CONDUCTANCIA KILOMET

9.82385887185374E-08 2.9471576615561

TRAMOS TOTAL
3 - 10 - 11 - 15- 16 -29 - 30 - 31 - 32 - 33 - 34 - 43 12
1 - 2 - 5 - 8 - 9 - 13 - 14 - 17 - 19 - 20 - 24 - 28 - 35 - 38 - 40 - 41 - 42 17
4 - 6 - 7 - 12 - 18 - 21 - 25 - 26 - 27 - 37 - 39 11
22 - 23 - 36 3
43

mt r RADIO DEL COND (cm)


1
0.8 1.5189

TEMPERATURA (C) h
15 75.1
15 74.2
15 73.3
15 72.4

SECO PERDIDA EF. CORONA (KW/Km)


Vc TENSION CRITICA EFICAZ (KV) p
308.496 10.942
304.799 9.823
301.102 8.752
297.405 7.731

P.EF. COR. TRIF. (KW/Km) P. EF. COR. TOTAL (KW)


3p
0.03 5.82
0.01 2.45
0.14 31.29
0.42 93.51
0.60 133.07

PERDIDAS TOTALES LINEA L2216

DAS TOTALES EN LA LINEA


1051.56
133.069
1184.629

AS KILOMETRICAS EN LA LINEA (KW/Km)


4.755
0.60
5.356

%
0.6581270064
RESISTENCIA ELECTRICA (OHM/KM)
0.02985

CALCULOS

PERDIDA DE POTENCIA EN LOS AISLADORES (W)

157734

1051560

Gkt CONDUCTANCIA KILOMETRICA TOTAL(S/Km)

2.94715766155612E-07

CLASIFICACION DE LOS TRAMOS SEGN ALTURA


TOTAL Km
34.84
107.21
67.23
9.72
219

TIPO HILO
hilo superficie lisa
hilos oxidados o rugosos
cables


1.022
1.010
0.998
0.986

CONDUCTANCIA KILOMETRICA
Gk (S/Km)
3.44922828042295E-07
3.17194120526004E-07
2.89596794568359E-07
2.62227794254425E-07

CONDUCTANCIA 3 CONDUC.
3Gk (S/Km)
1.29522521532747E-09
5.59915458706594E-10
7.31407184181243E-09
2.24081490407617E-08
3.15773615566082E-08

S LINEA L2216

CONDUCTANCIA TOTAL EN LA LINEA


CONDUCTANCIA TOTAL EN AISLADORES (S)
CONDUCTANCIA TOTAL EFECTO CORONA (S)
TOTAL (S)

CONDUCTANCIA KILOMETRICA EN LA LINEA (S/Km)


CONDUCTANCIA POR KILOMETRO EN AISLADORES (S/Km)
CONDUCTANCIA KILOMETRICAS POR EFECTO CORONA (S/Km)
TOTAL (S/Km)
REACTANCIA DE AUTOINDUCCION (OHM/KM) SUSCEPTANCIA (S/km) PERDITANCIA (S/km)
0.2506693278 6.55812960855487E-06 7.46938301358722E-09
MODULO
ANGULO

PERDIDA DE POTENCIA EN LOS AISLADORES POTENCIA POR FASE (KW) POR FASE KILOMETRICO (KW/Km)
(KW)

157.734 52.578 0.2377373847

1051.56 350.52 1.584915898

Gt CONDUCTANCIA TOTAL (S)

6.51793388429752E-05

URA
VEL DEL VIENTO (m/s) TEMPERATURA (C)
T1 2 15
T2 2 15
T3 3 15
T4 3 15

mc distancias entre fases (m)


1 d12 7.3
0.955 d23 7.3
0.85 d13 14.6

SECO EFECTO CORONA PERDIDA EF. CORONA (KW/Km)


Vc TENSION CRITICA EFICAZ (KV) <245 p
308.50 SI HAY EF. CORONA 10.942
304.80 SI HAY EF. CORONA 9.823
301.10 SI HAY EF. CORONA 8.752
297.41 SI HAY EF. CORONA 7.731

CONDUCTANCIA 3 CONDUC. CONDUCTANCIA TOTAL HUMEDO


3Gk (S/Km) G (S) Vc TENSION CRITICA EFICAZ (KV)
1.03476848412689E-06 0.0002288494 246.797
9.51582361578012E-07 0.000210452 243.840
8.68790383705078E-07 0.0001921417 240.882
7.86683382763274E-07 0.0001739829 237.924

CONDUCTANCIA TOTAL
G (S)
0.00000
0.00000
0.00000
0.00000
0.00001

EN LA LINEA
6.51793E-05
6.98365E-06
7.21630E-05

EN LA LINEA (S/Km)
0.00000029
0.00000003
0.00000033
IMPEDANCIA (OHM/KM) ADMITANCIA IMPEDANCIA CARACTERISTICA
0.02985+0.250669327772771i 7.46938301358722E-09+6.55812960855487E-06i
0.2524403581 6.55813386218112E-06 196.1955963052
83.2089346761 89.9345326828 -3.3627990033

h
75.1 1.022
74.2 1.010
73.3 0.998
72.4 0.986

diametro equivalente D (cm)

920

P.EF. COR. TRIF. (KW/Km) P. EF. COR. TOTAL (KW) HUMEDO


3p Vc TENSION CRITICA EFICAZ (KV)
32.826 7259.871 246.80
29.468 6517.185 243.84
26.256 5806.692 240.88
23.194 5129.594 237.92

PERDIDA EF. CORONA (KW/Km) CONDUCTANCIA KILOMETRICA CONDUCTANCIA 3 CONDUC.


p Gk (S/Km) 3Gk (S/Km)
0.009 4.31741738442491E-10 1.29522521532747E-09
0.004 1.86638486235531E-10 5.59915458706594E-10
0.047 2.43802394727081E-09 7.31407184181243E-09
0.141 7.46938301358722E-09 2.24081490407617E-08
ANGULO CARACTERISTICO POTENCIA CARACTERISTICA POTENCIA CARACTERISTICA MW
0.0170154424045297+0.284052304339693i 246692591.023863 246.6925910239
0.2845614817
86.5717336794
TETTA' 0.0170154424
TETTA'' 0.2840523043
A 1.04076548986216+0.00489877076681157i
B 56.5971768394 83.1177947592
C
D 1.04076548986216+0.00489877076681157i
EFECTO CORONA PERDIDA EF. CORONA (KW/Km) P.EF. COR. TRIF. (KW/Km)
<245 p 3p
SI HAY EF. CORONA 0.009 0.026
SI HAY EF. CORONA 0.004 0.011
SI HAY EF. CORONA 0.047 0.141
SI HAY EF. CORONA 0.141 0.423

CONDUCTANCIA TOTAL
G (S)
0.00000
0.00000
0.00000
0.00000
RACTERISTICA MW

52.8331904773701-20.2951819448549i
P. EF. COR. TOTAL (KW)

5.816
2.454
31.286
93.512
SENH (TETTA) 0.0177073763713204+0.287929247672217i
MODULO 0.2884732273
ANGULO 86.4805937625
DATOS PRINCIPALES
VOLTAJE DE LINEA (KV) 220
VOLTAJE DE FASE (KV) 127.02
DISTANCIA DE LINEA (Km) 221.16
TEMPERATURA (c) 15
LONGITUD DE VANO (m) 330
OPCION 1
radio conductor mm 15.189
TIPO CABLE CARDENAL
RESISTENCIA DEL CABLE (OHM/KM) 0.0597
CONFIGURACIN 2 TERNAS SIMPLEX
D (mm) 9200
PARAMETROS FUNDAMENTALES MODULO
RK RESISTENCIA ELECTRICA (OHM/KM) 0.02985
LK INDUCTANCIA ELECTRICA (H/KM) 0.0006649195
CK CAPACIDAD (F/KM) 1.73959383980426E-08
GK CONDUCTANCIA (S/KM) 0.00000033
XK REACTANCIA DE AUTOINDUCCION (OHM/KM 0.2506693278
BK SUSEPTANCIA (S/KM) 6.55812960855487E-06
ZK IMPEDANCIA (OHM/KM) 0.02985+0.250669327772771i 0.25244036
YK ADMITANCIA(S/KM) 3.2629312771222E-07+6.55812960855487E-06i 6.5662E-06
IMPEDANCIA CARACTERISTICA 195.95839303934-6.7446153678242i 196.074429
ANGULO CARACTERISTICO 0.0239233059647296+0.283730546902999i 0.28473733
TETTA' 0.023923306
TETTA'' 0.2837305469
POTENCIA CARACTERISTICA MW 246.845038846
A 0.960292529494087+0.0066977046951033i
B 6.38958748838034+54.7171741702783i
C 0.0000679498767455404+0.00143131091683571i
D 0.960292529494087+0.0066977046951033i

0.922116882953969+0.0128635115669303i -0.07788311704603+0.0128635115669303i 0.999999999999999


DATOS PRINCIPALES
CADENA DE AISLADORES EN SUSPENSION 15 ELEMENTOS CADA UNO
CADENA DE AISLADORES DE AMARRE 16 ELEMENTOS CADA UNO
FRECUENCIA Hz 60
TENSION MAS ELEVADA REGLAMENTO LIN. 245
POTENCIA (MVA) 180

ANGULO PARAMETROS NO KIL


6.601626
0.1470535941
3.8472857361111E-06
0.000072163
55.4380285302
0.0014503959
83.209 1.452 55.830 6.601626+55.438028530226i
87.151 1.521 0.001452 0.0000721629881248345+0.00145039594422799i
-1.971
85.1801929487

.999999999999999

También podría gustarte