LS C&S Busduct System E-series~BTMS

Busduct System

LS C&S Busduct System E-series~BTMS


2014 LS Cable & System, Ltd. All right reserved
E-series, Mini-way, LT-way, BTMS

Aug. 2014
Gre a te r Va l u e To g e t h e r

LS Busduct System
136 LS-ro, Dongan-gu, Anyang-si, Gyeonggi-do, 431-831, Korea
Tel. 031-428-4147 Fax. 031-428-4281
About LS Cable & System
Since the separation from LG Electronics in 2003, LS Group has specialized in industrial energy, electronic energy, and industrial materials.
LNG, CNG
Thus, LS Group has achieved specialized global competitiveness in these fields. LS Group is a parent company of 40 subsidiary companies,
including LS Cable & System, LSIS, LS Nikko Copper, LS Mtron, Gaon Cable, E1 and Yesco. LS Cable & System holds the unrivaled position of the
top cable maker in Korea, and it provides total solutions for electronic power and telecommunication industries.

LS Cable & System has strived to become a global leader in the industry by implementing constant innovation since the establishment of the company.
While providing high-quality solutions to help our clients, LS Cable & System is accelerating efforts to be the top player of the global cable industry by securing
the top technologies in submarine cables and superconducting cables, as well as focusing on green business. Under the company vision
Your No.1 Creative Partner, LS Cable & System dedicates its best effort to deliver only the top technology and service to its clients.

Superior Essex

Supply of LPG for residential&commercial,


transportation,industrial and petrochemical uses in domestic market.
Import & Export of LPG etc.

LS Cable & System E1 Global Cable


LSIS Yesco Incorporated
LS Nikko Copper Superior Essex
Gaon Cable

LS Global
Pountek Components, Machinery

LG Electronics LG Display
LG Chemical LG Telecom

Electrolytic Copper Cathode, Gold, Silver, Chemicals Product etc.

GS Caltex GS Retail
GS Engineering & Construction GS Homeshopping
Power equipment, Power supply & transmission, Industrial IT,
Automation equipment, Electric Power Tools, RFID etc.

A New Beginning as a Total Solution Provider for Electric Power and Telecommunications Standing Tall as the Third Largest Cable Maker in the Global Cable Industry
History was made when LS Cable & System, the de facto holding company of LS Group, transformed into LS Holding Company in July 2008 and started as a new In August 2008, LS Cable & System acquired Super Essex, the largest cable maker in North America, making LS Cable & System the third largest cable maker
total-solution provider specialized in electric power and telecommunications. It was the optimized business decision to increase management efficiency of the in the global cable industry. By incorporating the staple product line of coils and communication wires of Superior Essex to the existing business structure
constantly expending business segments and to strengthen the responsible management system to foster a new growth engine to drive our business. of power cables, optical fiber cables, and wires of the company, LS Cable & System has built an ideal cable product line. Securing the extensive experience
By separating investment and business segments, LS Holdings was able to discover a new growth engine to propel the group into a new phase of growth. The new of production and distribution network of Superior Essex in the markets of North America and Europe has led to LS Cable & Systems emergence as a true
change of business provided an opportunity to the subsidiary companies to focus on their own operations and to strengthen their respective business expertise, global enterprise.
as well as successfully enhancing the competitiveness in the industry. LS Cable & System, as the holding company, is committed to providing continued support to Superior Essex In 1999, Superior Cable, which back then was a communication cable producer, made an acquisition of Essex Wire, a magnet wire producer,
the subsidiary companies, while practicing responsible management.LS Cable & System endeavor to focus on our core business while strengthening its business and the combination formed Superior Essex. The company is the worlds largest maker of magnet wires and the largest maker of communication cables in
expertise and competitiveness as a global company. North America. The company is headquartered in Atlanta, Georgia, USA, where they manage 24 factories in a total of 9 countries, including the United States,
Canada, Mexico, Germany, the UK, Italy, and China.
LS Cable & System
Busduct System Solution
Buildings
The LS C&S Busbuct system is easy to install, and ensures large capacity of
energy transmission while providing space efficiency which makes the bus
duct system ideal for high-rise buildings, office buildings, data centers and
apartment complexes.

Plants
The full lineup is consisting of NSPB, CAST RESIN and SIB that can cover up
to 27kv, and the lineup thus enables us to provide our clients customized
designs. The system is suitable for electrical rooms and power lines, and it
features a real time monitoring system using the temperature and power
monitoring system.

Data Center
The flexibility and expandability as well as easy maintenance property
of the busduct system provides the best alternative to improve the existing
problems of the conventional power cable system of data centers,
which requires constant extension, reinstallation and capacity
modification of loads.

Apartment Buildings
Although the demands for more electricity for families are growing,
the space for EPS area has reduced. Due to the change,
the need for busducts and multi boxes have increased.

Hospitals
The stability of the power supply in the hospitals is perhaps the most vital element,
because its failure could threaten the safety of patients.
The Busduct system distributes larger capacity of electric power, and provides
stability of the loads which make it an ideal choice to satisfy the requirements of
systematization of hospital complexes and larger hospital equipments.

Airports
In order to secure the stable power supply of the airport, the busduct system
provides the best customized solutions by installing high voltage busducts
at the transmission, transformation and power distribution lines, and by
installing low voltage busducts at the cargo, the control tower and general
commercial buildings.

Stadiums
The needs for a busducts system has been growing for its benefit such as
large capacity of power transmission, providing a stable power supply for
various loads and an eco friendly property as well as economical quality.

Marine & Wind


The compact and light weight design of the busduct satisfies the demands of the clients,
and comes with an outstanding quack resistance property. The busduct provides stability
to the operation of the facilities through a real-time monitoring system using
a temperature and power monitoring system. As the needs for renewable energy grows,
the demand for our busduct has been increasing teadily.
LS Cable & System Busduct Product The LS Cable & System Busducts are available in a wide range of products from low current capacity LT-way (25A~63A) to large current
capacity (630A~7500A), and the products enable the supply of proper capacity of power for factories and the distribution system. Our
products such as the air insulated bus conducts with enhanced safety property and the cast resin busducts with resistance for high

Line-up
temperature, humidity and dusty environment will satisfy various application needs and provide a customized engineering service.

Ez/Ex/Ef-way
1 Sandwich Type (PET Film, Epoxy Coating, MICA)/AL
Extrusion Housing/Standard IP54/Joint Kit
Riser Part - Designed for low voltage products below AC 1000V, and between
630A to 7500A.
End Closer
- The most widely used conventional model.

End Closer
Mini-way
Spring Hanger
2 Air Insulated Type/AL Extrusion Housing/Standard IP54/Joint Kit
- Designed for low voltage products below AC 1000V, and between
Spring Hanger 160A and 800A.
Plug in Unit - Ideal for small distribution system with multi distribution loads
(Vertical areas of buildings, data centers, assemble factories)
Plug-in Box
Spring Hanger Horizontal Part
Plug in Unit
LT-way
Spring Hanger Plug-in Box
3
Rigid Hanger 3 Plug in Unit
Flat Wire Type/Copper Conductor with PVC Extruded Insulation/AL
Extrusion Housing/Various Plug Types/Joint Brush
(It can be installed with a live wire.)
- Designed for low voltage products below AC 690V, and between 25A and 63A
Rigid Hanger - Suitable for Light bulbs, FFU and distribution for small equipments
1
Plug-in Box
1 MS/Wind-way
2 4 Air Insulated Type/ Compact NSPB Type / One-Bolting Type
Plug-in Box Designed for low voltage products below AC 1000V, and between
1000A and 5000A
- A Hybrid incorporating NSPB and sandwich type
2 - Ideal for ships, wind towers and chemical plants where stability is required.

7 NSPB-LV/MV
4 5 Air Insulated Type/Insulated conductors separated by phase/AL,
STS and Steel Housing (optional)/Indoor Type/Outdoor Type
6 - NSPB-LV : Designed for low voltage products below AC 1000V,and below 4000A
- NSPB-MV: Designed for high voltage products below AC 27kV, and below 4000A
- Suitable for plants where high stability is required.
5 Switchgear

CR-LV/MV
6 - Cast Resin Type/IP 68/Epoxy Molding between Conductors
Indoor - CR-LV: Designed for low voltage products below AC 1000V, and between
TR Flanged
End Box Switchgear 630A and7500A.
- CR-MV: Designed for high voltage products below AC 27KV,
and below 5000A.
- The most safe bus duct suitable for plants where high stability is required.
Transformer TR Flanged End Box

7 SIB
Transformer Epoxy Vacuum impregnated insulation Products/Suitable for phase
separation system
- Designed for high voltage products below AC 27kV and below 7500A
- Small space , bending area
Outdoor Transformer - Suitable for high voltage products.
Why Busduct?
Easy Distribution of Loads Adaptability to various installation
When supplying power using cables, each load has to be connected individually to cables which waste space, environment with convenience
and an additional distribution panel is also required.
The busduct system is a power distribution system and can
On the other hand, busducts are separated from a single line at a plug box which simplifies the electric power system.
be applied to various complex routes. The busduct system
A MCCB can be installed at the plug box to effectively shut off fault current.
comes with various fittings such as elbow, off-set and tee,
and can transmit high capacity currents without electrical
Cable Wiring System Busduct Wiring System
and mechanical loss.
P-x P-x L-x L-x P-x P-x L-x L-x

P-... P-... L-... L-... P-... P-... L-... L-...

P-3 P-3 L-3 L-3 P-3 P-3 L-3 L-3

P-2 P-2 L-2 L-2 P-2 P-2 L-2 L-2 Excellent short circuit
P-1 P-1 L-1 L-1 P-1 P-1 L-1 L-1 The busduct system has a high tolerance for short circuit.
Its stability and reliability make it perfect for a high capacity
ACB ACBMCCB ACB
MCCB ACB ACB ACB
ACB ACB energy transmission system.
One to-one correspondence of power One to-many correspondence of power
supply and loads supply for specific power supply
Additional lines are needed in case of a Additional lines are not necessary in case
load change of a load change

ACB : Air Circuit Breaker, MCCB : Molded Case Circuit Breaker

High current density


Labor Hours
Cables are connected directly to electric loads using racks.
Easy Installation 800
0.2 0.6 1.0 1.4 1.8 2.2 2.6 3.0 3.4 3.8
Its maximum allowable current ampacity limit is 1000A, and
Pulling and cable tray installation for cables can be difficult, and requires additional lines for a higher current. Each line of
1000
requires a longer construction period, therefore increases the the busduct system can transmit up to 7500A, and provides
1500
cost. On the other hand, the busducts use a simple installation high current density.
2000
method to connect specific length of products, which requires a 2500
shorter installation period, and is economically friendly. 3000
4000
Cable
Ampere Busduct

Easy maintenance
The design of the busduct system makes it easy to detect
abnormalities during installations, and ensures easy main-
Compact tenance. When humidity or dust causes a malfunction on
the system, the easy-to -maintain design allows replacing
The compact design of the busduct system provides high space efficiency at up to 50% compared to the cables. only the damaged part.
While cables require larger space to install multi lines as well as additional space for coiling areas, the busducts use
proper fittings to maximize space efficiency.

The space
R
Cable required reduces S

by 50%
T
Outstanding features of
EMC and EMI
Unlike cables, the busduct system does not require a shield,
Cable Tray instead Busduct, the housing itself performs as a shield
which enhances the features of EMC and EMI.
Why LS Cable &System Busduct
Total Solution
Global Top Tier Once PJT launches, our engineer will participate to guide the clients from the initial period in order to produce the best
LS Cable & System has been a long-time leading Busduct provider in korea. With extensive experience and product line com- system for our clients, and to respond quickly when the system is changed.
petitiveness, the company provides total solutions for each application to satisfy the needs of its clients. Using its expertise in Our engineers from each department provide full support in design, production, installation and testing at in-bound to
the electronic markets of large LCD monitors and semiconductors in Korea, the company has obtained PJT sales records in 50 satisfy our clients.
countries worldwide in Asia, the Middle East, CIS, and America. We operate the CS Team, a task force for the busduct system, to make sure efficient after-sale service and maintenance
service.

Process

PJT Kick O Provide technical support


Desi
gn
les an for the clients

Sa
Product development

dD
eve
System design

lopm
LS Cable & System

ent
Busduct

Installa
Total Solution

tion

on
Customer Service ua

/Q

cti
lity d u
Product test and / CS Pro
installation support
Full Line up PJT management
Production

LS Cable & System is the only global company that provides a full line-up of busducts, from low to high voltage and from low
to high capacity, to satisfy every need of its clients and provide an optimized solution for each PJT.

Technical Excellence
LT-way Unparalleled Reliability Total Engineering Technology
Provides standardized design, and owns numerous certifications Provide the optimal design by experienced engineers
MS/Wind-way such as UL Certification, Quack Proof Certification, and Impact Design following analysis and inspection of CAE
Resistance Certification Unique and exclusive design program for the busduct system
The CS team, a task force for the busduct system, Design based on structure stability inspection
provides efficient after-sale service
The excellent heat radiating property of the aluminum housing, which
Safe use in hazardous zones ensures large capacity of power transmission
Manage the system using a unique temperature Low Weight & Low cost
Mini-way monitor sensor
Easy installation
Semi-permanent service life
Deployable where access is difficult
Ez / Ex / Ef-way Used qualified insulation such as epoxy and PET film
Automated epoxy insulation facility
for efficient insulation
Unique joint kit connections
CR-LV/MV Reduce electromagnetic
Eco friendly
BPMS (Busduct Power Monitoring system)
Fully recyclable
BTMS (Busduct Temperature Monitoring system)
Halogen free
SIB (MV) Does not contain RoHS 6 hazardous substance
No toxicity in fire & Fire-Retardant
NSPB -LV/MV Non Explosive
The Busduct Temperature Monitoring System
Ez/Ex/Ef-way
LS C&S Busbuct System Catalogue
(BTMS : Busduct Temperature Monitoring System)
The busduct is a large capacity power distribution system. The insulation of the duct has to stay stable when the Joule lines
01 of 08
occur during a power supply of the conductor. The rated current will be set by the insulation type and the temperature rises.
These properties of the busduct make it possible to monitor and manage abnormalities of the system by checking the
temperature of specific areas of the system.

The temperature monitoring system uses various temperature sensors such as optical fiber cable, IC electric chips and
thermo-graphic cameras. Specific areas like the entire system line, joints, plug-in boxes and cable connection can be
monitored at the central monitor room using various methods on request.

Contents
I. Introduction
- Overview 14
- Application 15
The Busduct Power Monitoring System
(BPMS : Busduct Power Monitoring System) II. General Data 16
III. Component
The ongoing trends of the busduct system are more than a simple power supplying system. The growing trend is; 1) the stability of
the power system, 2) unmanned system,3)cost cutting, and 4)green and smart grid. While the SCADA system monitors and controls - Feeder 22
the power of the main system, the BMS monitors low loads of the sub system. The frequency of the resent electrical accidents is - Flanged End 23
higher at the sub system than at the main system. Therefore, the preference for the BMS system has been increasing.
- Fittings 26
Smart box - Hanger 29
- Plug-In Unit 31
- Etc 33
IV. Technical Data
Communication Unit
- Impedance 35
- Voltage Drop 35
Ethernet Optical Ethernet RS-485 - Temperature Rise 37
Communication
V. Install Information
- Joint Connection 38
VI. Certification & Specification 39

<Monitor Program>
I. Introduction 06 / 07

Overview Application
The E-Series Electrical Rooms

E-series
The LS C&S E-Series Busducts are designed to carry voltage range below AC 1000V, and to carry the current range of 630A to 7500A.
The busduct can be installed both horizontally and vertically
Joint kit connections provide more space to connect which reduce the contact resistance to its minimum while connecting products. at the electrical room.
LS C&S E-series Busduct comes with a standard IP54rating; however, it can be upgraded to an indoor or outdoor IP65 rating on request. The maximized safety features are seismic-proof and
Depending on each insulation property, the system comes in three types; Ez-way when polyester film is used, explosion-proof.
Ef-way when mica film is used and Ex-way is used when epoxy powder is used. Provides excellent space efficiency and easy installation
compared to cables.

Compact Size
LS C&S E-Series Busduct uses an effective heat radiating housing profile which allows the size of the conductors to be smaller
than the existing Busduct models. The light weight of the Busduct also allows easier installation and requires less space.

Economical and Easy Installation


LS C&S E-Series Busduct uses aluminum housing and joint kit Commercial / Housing Building etc.
connections which enable easy installation with less time and low cost.
Provides excellent space efficiency.
The busducts can be applied to high-rise buildings,
office buildings, and data centers.
Multi-box can be applied on request.
Easy Distribution of Loads
LSC&S E-Series Busduct can directly distribute the loads at the
plug-in box using a single line, and thus simplifies the power
supply system. The MCCB can be installed in the plug-in box
on request to effectively shut off the faulty current.

Factory / Plant etc.


The busducts can be applied to a vast range of industries such as
semiconductor, display and petrochemical plants.
The temperature and the power supply monitoring system allows
easy maintenance.
The busducts provides high space efficiency, and allows
a significantly reduced installation period.

14 E-series LS C&S-Busway System E-series LS C&S-Busway System 15


. General Data 06 / 07

End Cap
Plug-in Box
Offset

E-series
Elbow Connection
Joint Cover Option I : Joint Kit

Option I I : One Bolting

Flanged End
Feed in Unit

High Current Density Eco - Friendly Conductors Housing


The busduct has a compact design compared to the The LS C&S Busbucts acquired RoHS certification, The E-Series uses either copper conductors with The E-Series uses an effective heatradiating
existing models by using an effective heat-radiating and only uses components without hazardous conductivity over 99%, or aluminum conductors aluminum housing profile which produces an
housing profile and can carry from 630A up to 7500A substances such as lead, cadmium, mercury, with conductivity over 61%. excellent mechanical strength and heat radiation.
with reduced loss of electric power. It is an ideal power chrome, PBBs and PBDEs. The aluminum housing can be used as a protective
distribution system that provides high efficiency, The connection of the conductors is tin-plated in conductor(PE) due to its high level conductivity and
stability, economy-friendliness and convenience. The order to reduce contact resistance and to prevent cross sectional areas. An optional optical fiber tem-
design of the conductor allows flexibility to extend corrosion of the connection. (A silver plated option perature sensor can be installed at the housing.
and relocate depending on the environment. is available.)

Low Voltage Drop and High Standard Insulation Properties Connection


Short Circuit Strength IEC 61439-1 [(previous standard)IEC 60439-1]
o
An insulator of thermal class rating Class B (130 C ) or Kit : DH (dual head) bolts and Visible-label (Redtag)
Power Switch gear and Control gear Assemblies more is applied to the E-Series. Other insulation Check for installation using the contact
Thanks to the optimum design, power can be options such as Epoxy, PET and MICA (Fire proof To exert a uniform force on the entire connection can Disc
transmitted with the greatest possible efficiency, IEC 61439-6 [(previous standard)IEC 60439-2] o
Busbar Trunking Systems up to 1200 C) are also available. FRP (Fiber Reinforced Spring A structure. (Assembly Torque 800 ~ 1000kgf.cm)
and the resultant voltage drop is low due to extremely Plastic) with high dielectric property is used as
NSEN 60439 Busways One-bolting : One-bolting without a Feeder Kit Part
low impedance. In addition, the LS C&S Busducts is insulation at the connection which performs as of the structure is directly connected to the conductor,
designed to have very high short circuit strength. NEMA BU 1.1 Busways insulation between phases and housing. Kit with the same DH (dual head) bolts and Visible-label
(Red-tag) to Check for the installation and use of all
contacts Connection can apply a uniform force to
the Disc Spring A structure. (Assembly Torque 800 ~
Permissible Operating Temperature Service Condition 1000kgf.cm)
o o
The cross sectional areas of the conductor and Ambient Temperature : -15 C ~ 55 C
housing profile are designed to meet the standard Relative Humidity : 95% or below
permissible operating temperature of IEC 61439-1 (When the service condition of the environment
and 6. Therefore the temperature rise limit of does not meet the requirements listed above, please
the housing is within 55K or less of the ambient contact our design team.)
temperature.

16 E-series LS C&S-Busway System E-series LS C&S-Busway System 17


. General Data 06 / 07

General Specifications Joint Connection


E-series Busduct uses insulation with a thermal class rating over130 oC for each phase. A sandwich type design is applied to Feature
the Busduct to protect the aluminum housing, and it can be used at the voltage range of AC 1000V or less, and the current
Both joint plates of the joint kit and the conductors are tin plated. (A silver plated option is available.)
range between 630A to 7500A. It is designed to use a joint kit connection and general IP54 rating. It prevents the joint plate from discoloration and corrosion. In order to ensure easy maintenance

E-series
and reliability, double-headed bolts and visible labels are used to check the application,
and a disc spring allows even connection of the contact surface.

Extruded Aluminum housing coated with paint Double Headed Bolts


Double-headed bolts are used to ensure a proper torque level when installing the joint kit.
Fastening Bolt & Washer If a torque wrench applies a pressure of 800 to 1000kgfcm to the outer bolt head,
the head of the outer bolt and the tag attached to it will be sheared off automatically.
Conductor(Copper / Aluminum) Thus, it allows visual inspection for the proper application of the bolts at the connection.
The remaining bolt head can be re-used when tightened to 800kgf . cm using a torque wrench.

Insulation
- Ex-way by EPOXY <Option : Joint Kit> <Option : One Bolting>
(Class B 130oC / Class F 155oC)
- Ez-way by PET
(Class B 130oC / Class F 155oC)
- Ef-way by MICA (1200oC)

Number of Double headed bolts


Number of
1 2 4 6
D.H bolts
630, 800, 1000, 2500, 3200,
CU 5000 6300, 7500
1250, 1600, 2000 3600, 4000
Ampere
(A) 630, 800, 1600, 3200,
AL 5000, 6300
1000, 1250 2000, 2500 3600, 4000

! Precaution
Be sure to clean the interior of the connections prior to installation. Use caution not to twist the joint kit while inserting it, and after it is inserted.
An excessive pressure during installation may break the kit.
Make sure that the double-headed bolts and the red tags are intact.
If proper torqueses are not applied at the connection, it may cause heat during operation.

18 E-series LS C&S-Busway System E-series LS C&S-Busway System 19


. General Data 06 / 07

Grounding and Harmonics IP Code (Degree of Protection)


E-Series Busduct comes with aluminum housing, and the cross-section area of the housing is over 100% of each International protection degree codes provided by IEC 60529(Degree of Protection Provided by Enclosure-IP Code)
phase conductor. Therefore, the aluminum housing alone works as 100% or more of ground bar, and the housing also
improves the heat radiation of the conductors. NEMA STANDARD : IP54=NEMA 12, 12K, 13 IP55=NEMA 3, 3X, 3S, 3SX IP66=NEMA 4.4X IP67=NEMA 6

E-series
* As the standard differs, it is a similar substitution, not 1:1 substitution.

The degree of protection against water of the LS C&S E-Series is a standard IP54; however, it can be adjusted from IP42
The 200%N type Busduct is used for a nonlinear load that generates harmonic current. Lately, the needs for non-linear loads at the power distribution
to IP65 depending on the environment and on request.
system of buildings are increasing due to the increase of office automation and computer facilities. The harmonic current produced by the system can

IP
flow up to 200% of over current at phase N. The LS C&S 200% N type busduct is safe to be used at the distribution system where the harmonic current
can be generated.

Solid Particle Protection Liquid Ingress Protection


0 No Protection 0 No Protection

1 Protection against 50mm 1 Protection against 5 Protection against


diameter solid particles. falling drops of water. low pressure jets of water
(back of a hand) from all directions.
2 Protection against 12mm
solid particles. (fingers) 2 Protection against falling 6 Protection against
[3W+GE] [4W+GE] [4W(200%N)+GE] drops of water with an strong jets of water
enclosure tilted at a 15degree from all directions.
3 Protection against 2.4mm
angle from a vertical line
solid particles.
(tools or thick wires)
4 Protection against 1mm 3 Protection against
1m
15cmmin.
7 Protection against the effects
spray sat a 60degree of immersion between
solid particles.
angle from a vertical line 15.0 centimeters and 1.0 meter.
(tools or most wires)
5 Protection against dust.
1m
4 Protection against 8 Protection against
water splashed from longer periods of immersion
6 Complete protection all directions. under pressure.
against dust.

Degree of Protection IP54 / IP55 Degree of Protection IP65 / IP66


IP54 is applied to the feeder, plug-in and tap-off, and can be With the IP65 rating, the busduct is ideal for corrosive environments.
[3W+50%E, 100%E] [4W+50%E, 100%E] [4W(200%N) + 50%E]
used during water leakages and near sprinklers. The special sealing between the housing sections seals off water,
dust and gasses.

Plating/Coating
Indoor and Outdoor Type Indoor Type Outdoor Type
Plating Coating
Standard tin plating is applied at taps, plugs and connections In order to improve heat radiation and to prevent corrosion, as
of conductors using an electroplating method to maintain the well as to fit in with the surroundings, we apply polyester-epoxy
electrical characteristics and to prevent corrosion. Silver plating is (hybrid) power coating after treating the surface. A wide range of IP Code
available on request. color is available to meet the needs of our clients.
Degree of Protection
Busbucts Construction Type
(IP)
IP54 / IP55 Feeder, Plug-in, Riser Drip-proof / Splash-proof
IP65 / IP66 Feeder Water Jet-proof
*Outdoor applications require advanced discussion with the design team.

20 E-series LS C&S-Busway System E-series LS C&S-Busway System 21


. Component 06 / 07

Feeder Flanged End


Sectional View Flanged end is connected to either a transformer or panel. Dimension details are listed below.

AA AA
Flanged End(GE) Flanged End(50%, 100%E)

E-series
Flange(AL 4t) Flange(AL 4t) Flange(AL 4t) Flange(AL 4t)
WW WW
Flange(AL 4t) Flange(AL 4t) Flange(AL 4t) Flange(AL 4t)

3434

H
HH

H
t
tt

t
[Fig. E1-1] [Fig. E1-2]
A [Fig. E2-1]
A

W
W
34 34

H
34 34

H
t
t
[Fig. E1-3] [Fig. E2-2] [Fig. E2-3] [Fig. E2-4] [Fig. E2-5]

Dimension(mm) Weight(kg/m) Dimension(mm)


Ampere(A) Fig. Ampere(A) Fig.
t W A 3W 4W 4W+50%E 4W+100%E t W A B
630 41 107 7.58 8.43 8.79 9.15 630 41 ~
E2-2
800 62 128 8.83 10.09 10.63 11.17 800 62 ~
1,000 86 152 10.92 12.14 12.89 13.64 1,000 86 40
E1-1 100 E2-3
1,250 108 174 13.40 15.42 16.36 17.30 1,250 108 50
1,600 164 230 19.57 20.61 22.08 23.55 1,600 164 60
E2-5
2,000 210 276 23.08 26.23 28.14 30.09 2,000 210 70
AL 6.35 AL 6.35
2,500 (2)126 352 28.94 33.18 35.38 37.58 2,500 (2)126 40 E2-4
3,200 (2)164 428 34.86 42.44 45.29 48.14 3,200 (2)164 60
E1-2
3,600 (2)184 468 38.31 45.40 48.59 51.78 3,600 (2)184 60
130
4,000 (2)210 520 41.81 50.10 53.75 57.40 4,000 (2)210 70 E2-5
5,000 (3)184 686 57.74 68.43 73.22 78.01 5,000 (3)184 60
E1-3
6,300 (3)210 764 64.03 73.61 81.51 89.41 6,300 (3)210 70
630 41 107 11.91 14.44 15.65 16.86 630 41 ~
800 41 107 11.91 14.44 15.65 16.86 800 41 ~ E2-2
1,000 57 123 14.65 18.25 20.58 22.91 1,000 57 ~
1,250 73 139 17.65 22.04 24.60 27.16 E1-1 1,250 73 40 100
E2-3
1,600 108 174 26.74 31.00 36.47 41.94 1,600 108 50
2,000 145 211 31.69 37.39 44.76 52.13 2,000 145 50 E2-4
CU 2,500 6.35 195 261 42.69 54.59 60.25 65.91 CU 2,500 6.35 195 70 E2-5
3,200 (2)108 316 50.16 63.60 69.87 76.14 3,200 (2)108 50 E2-3
3,600 (2)126 352 57.55 73.16 80.41 87.66 3,600 (2)126 40
E1-2 E2-4
4,000 (2)145 390 64.82 82.72 91.17 99.62 4,000 (2)145 50
130
5,000 (2)195 490 85.26 109.14 121.08 133.02 5,000 (2)195 70
6,300 (3)164 626 108.91 139.27 154.65 168.02 6,300 (3)164 60 E2-5
E1-3
7,500 (3)195 719 126.89 162.81 179.83 196.85 7,500 (3)195 70
* H : 107.5(3W+GE, 3W+50%E) / 115(4W+GE, 4W+50%E) / 125(4W+100%E) *T: Conductor thickness

22 E-series LS C&S-Busway System E-series LS C&S-Busway System 23


. Component 06 / 07

Flanged End
Drilling Pattern for Flanged End Flanged End Box / Feed in Box

E-series
A

B D [Fig. E4-1]
A D

B D D
D

C1 25 25 C2 C1 25 25 C2 C1 25 25 C2

[Fig. E3-1] [Fig. E3-2] [Fig. E3-3] [Fig. E4-2]

3W Dimension(mm) 4W Dimension(mm) 4W+50%E, 100% E Dimension(mm) 3W Dimension(mm) 4W Dimension(mm) 4W+50%E, 100% E Dimension(mm)
Ampere(A) Fig. Ampere(A)
A B C1, C2 D A B C1, C2 D A B C1 C2 D A B C D L A B C D L A B C D1 D2 L
630 240 122 110 152 340 122 160 152 410 122 230 160 152 630 347 297 410 180X2 270 347 297 510 230X2 270 347 297 580 300 230 270
800 240 143 110 173 340 143 160 173 410 143 230 160 173 800 368 318 410 180X2 270 368 318 510 230X2 270 368 318 580 300 230 270
1,000 240 167 110 197 340 167 160 197 410 167 230 160 197 1,000 392 342 410 180X2 270 392 342 510 230X2 270 392 342 580 300 230 270
E3-1
1,250 240 189 110 219 340 189 160 219 410 189 230 160 219 1,250 414 364 410 180X2 270 414 364 510 230X2 270 414 364 580 300 230 270
1,600 240 245 110 275 340 245 160 275 410 245 230 160 275 1,600 470 420 410 180X2 270 470 420 510 230X2 270 470 420 580 300 230 270
2,000 240 291 110 321 340 291 160 321 410 291 230 160 321 2,000 516 466 410 180X2 270 516 466 510 230X2 270 516 466 580 300 230 270
AL AL
2,500 300 367 140 199 430 367 205 199 500 367 275 205 199 2,500 592 542 470 210X2 270 592 542 600 275X2 270 592 542 670 345 275 270
3,200 300 443 140 237 430 443 205 237 500 443 275 205 237 3,200 668 618 470 210X2 270 668 618 600 275X2 270 668 618 670 345 275 270
E3-2
3,600 300 483 140 257 430 483 205 257 500 483 275 205 257 3,600 708 658 470 210X2 270 708 658 600 275X2 270 708 658 670 345 275 270
4,000 300 535 140 283 430 535 205 283 500 535 275 205 283 4,000 760 710 470 210X2 270 760 710 600 275X2 270 760 710 670 345 275 270
5,000 300 701 140 244 430 701 205 244 500 701 275 205 244 5,000 926 876 470 210X2 270 926 876 600 275X2 270 926 876 670 345 275 270
E3-3
6,300 300 779 140 270 430 779 205 270 500 779 275 205 270 6,300 1004 954 470 210X2 270 1004 954 600 275X2 270 1004 954 670 345 275 270
630 240 122 110 152 340 122 160 152 410 122 230 160 152 630 347 297 410 180X2 270 347 297 510 230X2 270 347 297 580 300 230 270
800 240 122 110 152 340 122 160 152 410 122 230 160 152 800 347 297 410 180X2 270 347 297 510 230X2 270 347 297 580 300 230 270
1,000 240 138 110 168 340 138 160 168 410 138 230 160 168 1,000 363 313 410 180X2 270 363 313 510 230X2 270 363 313 580 300 230 270
1,250 240 154 110 184 340 154 160 184 410 154 230 160 184 E3-1 1,250 379 329 410 180X2 270 379 329 510 230X2 270 379 329 580 300 230 270
1,600 240 189 110 219 340 189 160 219 410 189 230 160 219 1,600 414 364 410 180X2 270 414 364 510 230X2 270 414 364 580 300 230 270
2,000 240 226 110 256 340 226 160 256 410 226 230 160 256 2,000 451 401 410 180X2 270 451 401 510 230X2 270 451 401 580 300 230 270
CU 2,500 240 276 110 306 340 276 160 306 410 276 230 160 306 CU 2,500 501 451 410 180X2 270 501 451 510 230X2 270 501 451 580 300 230 270
3,200 300 331 140 181 430 331 205 181 500 331 275 205 181 3,200 556 506 470 210X2 270 556 506 600 275X2 270 556 506 670 345 275 270
3,600 300 367 140 199 430 367 205 199 500 367 275 205 199 3,600 592 542 470 210X2 270 592 542 600 275X2 270 592 542 670 345 275 270
E3-2
4,000 300 405 140 218 430 405 205 218 500 405 275 205 218 4,000 630 580 470 210X2 270 630 580 600 275X2 270 630 580 670 345 275 270
5,000 300 505 140 268 430 505 205 268 500 505 275 205 268 5,000 730 680 470 210X2 270 730 680 600 275X2 270 730 680 670 345 275 270
6,300 300 641 140 224 430 641 205 224 500 641 275 205 224 6,300 866 816 470 210X2 270 866 816 600 275X2 270 866 816 670 345 275 270
E3-3
7,500 300 734 140 255 430 734 205 255 500 734 275 205 255 7,500 959 909 470 210X2 270 959 909 600 275X2 270 959 909 670 345 275 270

24 E-series LS C&S-Busway System E-series LS C&S-Busway System 25


. Component 06 / 07

Fittings
E-Series Busduct has a wide range of fittings to satisfy any layout of buildings. Elbow angles other than 90 o are also available. Combination
Fitting designs are shown in the following figures, and they consist of the source-side and the load-side. Offset or
combination elbows can be used where standard elbows are not feasible. Dimension(mm)

E-series
Ampere(A)
(Dimensions for each fitting are shown in the following figures. Contact our design team for a minimum dimension.) X Y Z
630~1,250 500 500 500
1,600~3,200 600 600 600
AL
3,600~4,000 700 700 700
Elbow Offset 5,000~6,300 800 800 800
[Horizontal] [Horizontal]
630~2,000 500 500 500
3,000~4,000 600 600 600
CU
5,000~6,300 700 700 700
7,500 800 800 800

Tee
[Vertical] [Vertical] [Horizontal] [Vertical]
600 600
600
600 600 600
600
600

600 600
600 600

Vertical Elbow Vertical Offset Vertical Tee


Dimension(mm) Dimension(mm) Dimension(mm)
Ampere(A) Ampere(A) Ampere(A)
X Y X Y Z X Y Z
630~1,250 500 500 630~1,250 500 150 500 630~1,250 500 500 500
1,600~3,200 600 600 1,600~3,200 600 150 600 1,600~3,200 600 600 600
AL AL AL
3,600~4,000 700 700 3,600~4,000 700 150 700 3,600~4,000 700 700 700
5,000~6,300 800 800 5,000~6,300 800 150 800 5,000~6,300 800 800 800
630~2,000 500 500 630~2,000 500 150 500 630~2,000 500 500 500
2,500~4,000 600 600 3,000~4,000 600 150 600 3,000~4,000 600 600 600
CU CU CU
5,000~6,300 700 700 5,000~6,300 700 150 700 5,000~6,300 700 700 700
7,500 800 800 7,500 800 150 800 7,500 800 800 800

26 E-series LS C&S-Busway System E-series LS C&S-Busway System 27


. Component 06 / 07

Fittings Hanger
Expansion Vertical Mounting Hangers
The fitting is designed to allow a 60mm extension of a straight line. Spring hangers are used to support the busducts between floors. The number of springs depends on the weight of the installed busduct and plug-in
boxes. A medium hanger should be installed if the height between the floors exceeds 4.5 meters, and the height of the installed spring hangers can be

E-series
easily adjusted. Rigid hangers (no spring type) are used on the lowest floor, and they can be used instead of spring hangers depending on the set up
Dimension(mm)
Ampere(A) design.
X Y
630~7,500 1,500 360

Reducer
A reducer is used to connect a large capacity busduct to a small capacity busduct.
It can be used for an economical setup to distribute loads. [Rigid Hanger] [Spring Hanger]

Ampere(A) Dimension(mm)
Primary Secondary X Rigid Hanger
1,000 630~800
1,250 800~1,000
1,600 1,000~1,250
2,000 1,250~1,600
2,500 1,600~2,000
1,000
3,200 2,000~2,500
4,000 2,500~3,200
5,000 3,200~4,000
6,300 4,000~5,000
[1 Row] [2 Row] [Side View]
7,500 5,000~6,300

*Any change made to load distribution or to capacities follows inner line regulations. An overcurrent circuit
breaker can be installed on request. Spring Hanger

Phase Transposition Feeder


A phase transposition feeder is used when the setup transforms
the phase.

[1 Row] [2 Row] [Side View]

* Hangers with more than 2 rows depending on the installation environment are also available on request.
Please contact the design team for further information.

28 E-series LS C&S-Busway System E-series LS C&S-Busway System 29


. Component 06 / 07

Hanger Plug-in Unit


Horizontal Hangers Straight Lengths: Plug-in/Tap-off Intervals
This busdust comes with an overcurrent blocking device (MCCB, fuse) in order to protect the wires while distributing loads.
General Hangers

E-series
The required minimum intervals of a plug-in(800A or less)and a tap-off(1000A, 1250A) are shown below. A length longer than
The standard installation method for these hangers is to install them horizontally at 1.5 meters intervals. They generally require 12mm diameter stud bolts. the required minimum intervals can be predestinated on request.

[Flatwise] [Edgewise]
Hanger Rod Hanger Rod
Plug-in Feeder
MCCB Frame Plug-in Hole Intervals(P)
(AF) (mm)
50, 65, 100 650
Hanger Clamp 250 650
Hanger Clamp 400 900 W
630, 800 1000
1000, 1250 1300
D
Spring Nut Spring Nut

Plug-in Box H

Hole Pitch (P)


Dimensions(mm)
MCCB Frame
W Fig.
(AF) D H
3W 4W
Wall Bracket 50, 65, 100 200 250 220 450
Wall brackets can be installed on a wall where general hangers are not feasible. 250 200 250 220 450
E5-2
400 250 300 220 750
630, 800 350 400 220 800
[Flatwise] [Edgewise] 1000, 1250 400 450 220 1200 E5-3
[Fig. E5-1]

[Fig. E5-2] [Fig. E5-3]

30 E-series LS C&S-Busway System E-series LS C&S-Busway System 31


. Component 06 / 07

Plug-in Unit Etc.


Plug-in Box Attachments Wall Flange
Attachments such as CT, TD and PT can be installed in a plug-in box to control and to supervise the current, A wall flange is used to seal the gaps produced during installation of busducts at the walls, ceilings and floor. The standard
voltage and wattage remotely. dimensions of a wall opening should be 30mm larger than the external dimensions of the E-Series Busduct.

E-series
Door Types of the Plug-in Unit Wall Flange Wall Flange

Various design of doors for the plug-in box is available to satisfy the demands of our clients. Glass Wool(out of scope)
The available types are shown below.
Fire Foam(out of scope)

External handle Push Button External lever interlock

Floor Openings
The standard dimensions of a floor opening should be 30mm larger than the external dimensions of the E-Series Busduct.

Bolt Fastening Key Lock Outlet

32 E-series LS C&S-Busway System E-series LS C&S-Busway System 33


Component . Technical Data 06 / 07

Etc. Technical Data


The Required Minimum Distances from a Wall for Heat Dissipation Impedance and Voltage Drop
The required minimum distances between a busduct and a wall, or a ceiling are shown below. The formula to measure the voltage drop of a busduct is shown below. The impedance and voltage drop values for aluminum
and copper conductors are shown in the table below.

E-series
The values listed are measured between upper and middle lines at 60Hz. For a 50Hz installation, multiply the reactance (X) by 0.83.
wall , ceiling wall , ceiling ceiling wall

250mm BEAM 100mm


200mm
100mm Vd = I x 3(R cos + X sin)
Vd = voltage drop[V] I = rated road amperes[A] R = resistance[] X = reactance[] / cos = power factor / sim = reactive factor
wall wall wall

100mm Actual load current Actual length of the line (m)


Actual voltage Drop = x Vd x x
100mm 100mm Rated load current 100m
joint
(Load Constant) = 1, concentrated load
(a place such as an electrical room) F F
= 0.5, Distributed load F : Flanged End (panel connections)
(a place such as a vertical section) F P P P P P P : Plug-in Unit

The required minimum distances between busducts


The required minimum distances between busducts are shown below.
10-3 /100m, 60Hz Voltage Drop(V/100m)
Ampere(A)
joint joint
R X Z 0.7 0.8 0.9 1
630 13.98 4.07 14.56 13.85 14.87 15.66 15.25
800 7.97 2.62 8.39 10.32 11.01 11.52 11.04
1,000 6.83 2.21 7.18 11.02 11.77 12.32 11.84
P2 P1 P3
1,250 5.55 1.82 5.84 11.22 11.97 12.52 12.01
1,600 3.82 1.23 4.02 9.85 10.52 11.02 10.60
2,000 3.08 1.00 3.24 9.96 10.63 11.12 10.67
200 AL
2,500 2.40 0.80 2.53 9.74 10.39 10.86 10.40
joint joint 3,200 1.91 0.61 2.00 9.82 10.48 10.98 10.56
3,600 1.72 0.55 1.81 9.99 10.67 11.18 10.74
4,000 1.54 0.50 1.62 9.93 10.60 11.09 10.64
100 5,000 1.15 0.37 1.21 9.24 9.87 10.34 9.94
100
6,300 1.02 0.33 1.08 10.41 11.11 11.63 11.16
630 7.49 4.07 8.53 8.90 9.21 9.30 8.18
800 7.49 3.84 8.42 11.07 11.50 11.67 10.38
200 1,000 5.49 2.99 6.25 10.35 10.72 10.82 9.52
1,250 4.39 2.45 5.03 10.44 10.78 10.86 9.50
1,600 3.10 1.71 3.54 9.40 9.72 9.80 8.60
Standard Dimension (mm) 200
2,000 2.40 1.35 2.76 9.17 9.46 9.53 8.32
3W and 3W 3W and 4W 4W and 4W
CU 2,500 1.86 1.05 2.13 8.87 9.16 9.22 8.06
P1 110 135 130
3,200 1.54 0.85 1.76 9.34 9.66 9.75 8.55
P2 150 175 180 3,600 1.35 0.74 1.54 9.20 9.51 9.60 8.42
P3 190 215 230 4,000 1.20 0.67 1.37 9.13 9.42 9.49 8.29
5,000 0.93 0.52 1.06 8.84 9.13 9.19 8.03
*Outdoor installation requires a further discussion with our design team about proper distance.
6,300 0.73 0.39 0.83 8.62 8.93 9.02 7.97
7,500 0.62 0.35 0.71 8.83 9.12 9.18 8.02

34 E-series LS C&S-Busway System E-series LS C&S-Busway System 35


. Technical Data 06 / 07

Technical Data
Short Circuit Strength Temperature Rise
LS C&S Busduct has been tested under actual short circuit conditions according to IEC 61439-1 and 6 [(previous standard) IEC 60439-1 and 2] The temperature rise limit is an important property which determines the performance of busducts. The temperature rise limit of the busduct is
at KEMA and ASTA. The result and the graph are shown below. designed that when a busduct is operated with a rated current , the temperature limit values of the housing are within 55K as specified

E-series
in IEC61439-1 and 6 [(previous standard) IEC 60439-1 and 2].

Phase to Phase Short Circuit Ratings


AL (kA) CU (kA)
Ampere(A)
1 sec 3 sec 1 sec 3 sec
630 24 14 36 21
800 42 24 36 21
1,000 50 29 51 29
1,250 62 36 65 37
1,600 95 55 95 55
2,000 121 70 129 75
2,500 132 76 150 107
3,200 169 97 191 110
4,000 200 140 200 149
5,000 200 150 200 200
6,300 200 150 200 200
7,500 - - 200 200

1 2 3 4 5

7 8

-Joint- 6

80

70
2
60 3

Temperature()
1

50

40 4
7 8
30 5 6
9
20

10

0 1 2 3 4 5 6 7 8
Time(hr)

Classification 1 2 3 4 5 6 7 8 9
Ambient
Sensor Location Connection Conductor Housing
Temperature
Temperature Rise
58K 64K 60K 40K 32K 31K 31K 31K 24
Value

36 E-series LS C&S-Busway System E-series LS C&S-Busway System 37


V. Install Information VI. Certification & Specification 06 / 07

Joint Connection Certification & Specification

E-series
Both parts should be aligned at the top and the bottom and the left and Using a torque wrench, slowly tighten the exposed bolt head of a double
the right as well as horizontally and vertically. (This also applies to the joint headed bolt. The head of the double headed bolt is designed to break off at ASTA Certification (Ez-way) ASTA Certification (Ex-way) KEMA Certification (Ex-way)
connection of the horizontal and vertical ducts.) Make sure that the joint kit 800~1000Kgf cm. Continue tightening the exposed head until it breaks off.
is not tilted. (We recommend a jig tool for the installation.)

Once the exposed head and the red tag attached to it have been cut off, a red line should be visible, which means they are properly connected. Be sure
to check the distance from the housing, and the gaps between the conductors at the kit after the installation.
KS Certification(E-series) UL Certification (Ex-way) CCC Certification(E-series)

Transparent cap

Before applying the connection cover, check the space between the Perform the last inspection of the connection.
end block and the holes of the connection cover. The red line should be
visible through the transparent cap.
Dust and Water Proof Certification Fire Proof Certification (Ef-way) Fire Sprinkler Certification (Ef-way)
(E-series)

38 E-series LS C&S-Busway System E-series LS C&S-Busway System 39


VI. Certification & Specification 06 / 07

Certification & Specification


Mini- way
LS C&S Busduct System Catalogue
02 of 08

Quake Proof TUV Eco Friendly Certification ISO9001


(SEISMIC ZONE/E-series) (Ef-way)

Contents
I. Introduction
- Overview 42
- Application 43
II. General Data 44
III. Component
- Feeder 49
ISO14001 OHSAS18001 - Flanged End 50
- Fittings 52
- Hanger 54
- Plug-In Unit 55
- Etc 56
IV. Technical Data
- Impedance 57
- Voltage Drop 57
- Temperature Rise 58
V. Install Information
- Joint Connection 59
VI. Certification & Specification 60

40 E-series LS C&S-Busway System E-series LSC&S-Busway System Certification & Specification 41


I. Introduction 06 / 07

Overview Application
Mini-way Data Center etc.
LSC&S Mini-way is an air insulation type bare conductor busduct, and designed for low currents at AC 1000V or less or between 160A and 800A.
Each conductor is compounded with a class B rating insulating material (thermal class 130 oC) and using a joint kit system Supply power to computer equipments at each rack in the
at the joint connections provides easy installation of feeders. server room.
Distribution boards or modular racks are not necessary.
The Mini-way comes with an IP54 rating and is water proof which reduces malfunction during operation caused by water leakage.
Consist of two lines of general use and emergency use.

Safe and Efficient Distribution System


LS C&S Mini-way is suitable for lager modern structures such as apartment complexes,
factories, shopping malls, and data center server rooms because of easy load distribution,
extension and installation. Our highly experienced and well-trained professionals can design

Mini-way
highly efficient products which will harmonize with surroundings and other equipments.

Easy Installation Apartments and Housing etc.


The light weight of LS C&S Mini-way enables easy trans-
Vertical Busducts can be installed at the EPS room.
portation and installation, and employing the joint kit
Provides better space efficiency than cables
system provides easy installation of the feeders. Multi-box can be applied

Excellent Performance
LS C&S Mini-way follows the IEC standard, and has
designed the cross-section, conductor support and hous-
ing shape according to the regulations of temperature.
Therefore it has efficient voltage drop and high short
circuit strength.

Shopping Centers / Air Port etc


Can be applied at the low capacity lines of department stores,
supermarkets and shopping malls
Provides better space efficiency than cables

42 Introduction
Mini-way LS C&S-Busway
E-series
System
LSC&S-Busway System E-series LSC&S-Busway
Mini-way
System Introduction
LS C&S-Busway System 43
. General Data 06 / 07

Elbow

Feeder

Joint Kit
Plug-in Hole

Plug-in Box Joint Cover

Mini-way
Joint Kit

Weight Eco Friendly Conductors Housing


The wonderfully light weight of the Mini-way was The LS C&S Busducts acquired RoHS certification, and The Mini-way uses either copper conductors with The Mini-way uses an effective heat radiating
possible due to aluminum housing, optimizing the only uses components without hazardous substances conductivity over 99%, or aluminum conductors aluminum housing profile which produces an
cross sectional areas and light weight components. such as lead, cadmium, mercury, chrome, PBBs and with conductivity over 61%. The connection of the excellent mechanical strength and heat radiation.
PBDEs. conductors is tin-plated in order to reduce contact The aluminum housing can be used as a protective
resistance and to prevent to corrosion of the conductor (PE) due to its high level conductivity
connection. (A silver plated option is available.) and cross sectional areas.

Short Circuit Strength Standard Insulation Properties Joint Kit


Thanks to the optimum design of the conductor IEC 61439-1 [(previous standard)IEC 60439-1] The Mini-way uses the air insulation system. The The Mini-way uses joint kit to connect the bus
o
shapes, and predestinated space between support Power Switchgear and Controlgear Assemblies insulation of thermal rating Class B (130 C) provides ducts. In order to ensure easy maintenance and
insulations, the Mini-way can withstand mechanical IEC 61439-6 [(previous standard)IEC 60439-2] high insulation performance between conductors reliability, double-headed bolts and visible labels
and thermal stress when a short circuit occurs. Busbar Trunking Systems and between conductors and housing. In order to (red tags) are used to check the application, and a
NSEN 60439 Busways secure the stability of conductor support and high disc spring allows even connection of the contact
NEMA BU 1.1 Busways short circuit performance, the design is following surface.(Connecting torque 800~1000kgf.cm)
CAE (Computer Aided Engineering) instructions. The joint plate of the joint kit is tin plated in order to
prevent discoloration and corrosion.(A silver plated
option is available.)
Permissible Operating Temperature Service Condition
The cross sectional areas of the conductor and Ambient Temperature : -15 ~ 55
housing profile are designed to meet the standard Relative Humidity : 95% or below
permissible operating temperature of IEC 61439-1 (When the service condition of the environment
and 6. Therefore the temperature rise limit of the does not meet the requirements listed above,
housing is within 55K or less of the ambient tem- please contact our design team.)
perature.

44 General Data
Mini-way LS C&S-Busway
E-series
System
LSC&S-Busway System E-series LSC&S-Busway
Mini-way
System General
LS C&S-Busway Data
System 45
. General Data 06 / 07

General Concept Grounding Capacity


LSC&S Mini-way is an air insulation type bare conductor busduct, and it supports each phase with Class B rating insulating The aluminum housing of the Mini-way is designed to perform as a grounding conductor within the rated current. In
material (thermal class 130 oC). It is designed for AC 1000V or less or between 160A and 800A. It also comes with a joint kit case 50~100% more grounding capacity is needed, an internal grounding conductor can be added without changing
system and standard IP54 rating. the existing design.

Housing

Configration

Mini-way
[General Earth]

[3W+GE] [4W+GE] Housing

50% Earth

[50% Earth]
[3W+50%E] [4W+50%E]
Housing 50% Earth

50% Earth

[3W+100%E] [4W+100%E]
[100% Earth]

*Special capacity such as 4W(200%N)+100%E at [Cu 160~400A] can be produced on request.


Note
The aluminum housing itself acts as a grounding conductor and improves heat-radiation of conductors. The light weight of the Mini-way was possible thanks
to the innovated design to reduce the weight.

46 Mini-way LS C&S-Busway System Mini-way LS C&S-Busway System 47


. General Data . Component 06 / 07

IP Code (Degree of Protection) Feeder


IP Code is an international protection degree code provided by IEC 60529(Degree of Protection Provided by Enclosure-IP Code) Although the standard length of the Mini-way is 3 meters, it can be adjusted to the installation
environment on request.
NEMA STANDARD: IP54=NEMA 12, 12K, 13 IP55=NEMA 3, 3X, 3S, 3SX IP66=NEMA 4.4X IP67=NEMA 6
* As the standard differs, it is a similar substitution, nota 1:1 substitution.

The degree of protection against water of the Mini-way is a standard IP54; however, it can be adjusted up to IP65.
An additional sealing using high strength silicon is also available at the joint connections between the housing and the
connection cover on request.

IP

Mini-way
Solid Particle Protection Liquid Ingress Protection

0 No Protection 0 No Protection

1 Protection against 50mm 1 Protection against 5 Protection against


diameter solid particles. falling drops of water. low pressure jets of water A A
(back of a hand) from all directions.

2 Protection against 12mm t t


solid particles. (fingers) 2 Protection against falling 6 Protection against
drops of water with an strong jets of water
3 Protection against 2.4mm enclosure tilted at a 15degree from all directions.
solid particles. angle from a vertical line
(tools or thick wires)

W
W

H
4 Protection against 1mm 3 Protection against
1m
15cmmin.
7 Protection against the effects
solid particles. spray sat a 60degree of immersion between
(tools or most wires) angle from a vertical line 15.0 centimeters and 1.0 meter.

5 Protection against dust.


1m
4 Protection against 8 Protection against
[3W] [4W]
water splashed from longer periods of immersion
6 Complete protection all directions. under pressure.
against dust.
Dimension (mm) Weight (kg/m)
Ampere(A)
t W A H 3W 4W 4W + 50%E 4W + 100%E
160 20 87 5.3 5.6 5.8 5.9
250 30 87 5.8 6.3 6.5 6.7
AL 400 6.35 50 165 107 6.9 7.7 8.1 8.4
630 70 127 7.9 9.1 9.6 10.1

Plating and Coating 800


160
95
20
152
87
9.2
5.8
10.9
6.3
11.5
6.8
12.2
7.2
250 30 87 6.8 7.6 8.3 9.1
Plating Coating
CU 400 6.35 50 165 107 8.1 9.4 10.6 11.9
Standard tin plating is applied at taps, plugs and connections In order to improve the heat radiation and to prevent corrosion, as
of conductors using an electroplating method to maintain the well as to fit in with the surroundings, we apply polyester-epoxy 630 50 107 12.8 15.6 16.9 18.1
electrical characteristics and to prevent corrosion. Silver plating is (hybrid) power coating after treating the surface. A wide range of 800 70 127 16.2 20.1 21.9 23.7
available on request. color is available to meet the needs of our clients.

48 Mini-way LS C&S-Busway System Mini-way LS C&S-Busway System 49


. Component 06 / 07

Flanged End
The flanged end is connected to either a transformer or a panel. Drilling Pattern for Flanged
Dimension details are shown below.

C
50

50
A

50
200

200
150

12

150
C

40

Mini-way
A A
A A A

20
W D
[3W+GE] [4W+GE] [side]

Dimension(mm) Dimension(mm)
Ampere(A) Ampere(A)
A B C D A B C D
160 200 70 160 200 70
50

250 200 70 250 200 70


50

AL 400 220 340 80 370 CU 400 220 340 80 370


200

12
200

150
150

40 630 240 100 630 220 80


800 265 125 800 240 100
20

70 A A A W
70 A A
[3W+50%E] [4W+50%E] [side]

Flanged End Box


Dimension(mm) Dimension(mm)
Ampere(A)
Ampere(A) A t W A B C D L
t w
3W 4W 500
160 20 190 130
160 20 L 250 30 200 140
250 30
AL 400 6.35 50 220 160 510 450 270
AL 400 6.35 50
630 70 240 180
630 70 B A
800 95 800 95 265 205
100 100
160 20 160 20 190 130
250 30 250 30 200 140
CU 400 6.35 50 D CU 400 6.35 50 220 160 510 450 270
630 50 C 630 50 220 160
800 70
800 70 240 180
*t : thickness of a conductor

50 Component
Mini-way LS C&S-Busway
E-series
System
LSC&S-Busway System E-series LSC&S-Busway
Mini-way
System Component
LS C&S-Busway System 51
. Component 06 / 07

Fittings
Mini - way Busduct has a wide range of fittings to satisfy any layout of buildings. Elbow angles other than 90 oC are also Tee
available. Fitting designs are shown in the following figures, and they consist of the source-side and the load-side.
[Vertical] [Horizontal]
Offset or combination elbows can be used where standard elbows are not feasible.
(Dimensions for each fitting are shown in the following figures. Contact our design team for a minimum dimension.) Z
Z
Z Z
Elbow Z
[Vertical] [Horizontal] Z
Y Z
Y X X
Y Y Z
Y H H
Y Y Y
Y X
Y Y
X X X
Y X Y H X
Y
Y H
Y

Mini-way
X X
X X
X Z Z X
Dimension(mm) Dimension(mm)
Ampere(A) Z Ampere(A)
X X Y Z Z X Z Y Z
X Z
160 ~ 800 500 500 500 160 ~ 800 500 500 500

Y Y X Z
X Y Y Y Z
Y Y Y
X X
Dimension(mm) X
Dimension(mm) Y Dimension(mm) H Dimension(mm)
Ampere(A) Ampere(A) Y Ampere(A) Y H Ampere(A) Y
Y Y
X Y X Y X Y Z H H_AL H_CU
X X Y Y
Z
160 ~ 800 500 500 Y 160Y ~ 800 500 500 Y 160 ~ 800 500 500 500 160 134 134
X Y Y X Z X
X X
X Y X X 250 X144 144
X
X
Y 400 164 164
X X X Z
Y Z
630 184 164
X X
Offset X Combination 800 209 184
Z Z
Z
[Vertical] [Horizontal] Z

Z
Y Y Z Z
Z
X Y Y Y Z
X
X Y
X X
Y Y
X
Y
X X
X
Z Z
Z

Z Z
Z

Dimension(mm) Dimension(mm) Dimension(mm)


Ampere(A) Ampere(A) Ampere(A)
X Y Z X Y Z X Y Z
160 ~ 800 500 500 500 160 ~ 800 500 500 500 160 ~ 800 500 500 500

52 Mini-way LS C&S-Busway System Mini-way LS C&S-Busway System 53


. Component 06 / 07

Hanger Plug-in Unit


Busducts installed on the ceilings, floors, walls and beams are usually supported by stud bolts, system channels, angles and The position of the plug-in distribution location will be decided according to the installation environment and on
channels. Various types of hangers are available depending on the installation condition or environment. request. The standard length of the feeders is 3 meters, and a maximum of 8 plug-in holes can be made on a 3 meter
(Please contact our design team for further information about hanger types and installation.) feeder. In order to secure the smooth access between the plug-in brushes and feeders, a guide pin has been attached

Horizontal Hangers

[Flatwise] Hanger Rod 12 [Edgewise] Hanger Rod 12

Guide Pin

Guide Pin Hole

Mini-way
Plug-in Box
Hanger Clamp Hanger Clamp Attachments such as CT, TD and PT can be installed in a plug-in box to control and to supervise current, voltage and wattage remotely.

Door Types of the Plug-in Box


Vertical Hangers Various design of doors for the plug-in box is available to satisfy the demands of our clients.
The available types are shown below.
[Rigid Hanger]

Base Channel

- Front Type - - Side Type -

External handle Push Button External lever interlock


[Spring Hanger]

Base Channel

- Front Type - - Side Type -

Bolt Fastening Key Lock Outlet

54 Mini-way LS C&S-Busway System Mini-way LS C&S-Busway System 55


. Component . Technical Data 06 / 07

Etc. Technical Data


Wall Flange Floor Opening Impedance and Voltage Drop
The formula to measure the voltage drop of a Busduct is shown below. The impedance and voltage drop values for aluminum
Wall Open Size Wall Flange Fire Foam and copper conductors are shown in the table below.
Cut Out (out of scope) Floor Opening Size The values listed are measured between the upper and middle lines at 60Hz. For a 50Hz installation, multiply the reactance (X) by 0.83.
W+160 Cut Out
W+60
W+60 30 W 30 Vd = I x 3(R cos + X sin)
W+10 30
Vd = voltage drop[V] I = rated road amperes[A] R = resistance[] X = reactance[] / cos = power factor / sim = reactive factor
H+160
H+10
H+60

H H+60 Actual load current Actual length of the line (m)


Actual voltage Drop = x Vd x x
Rated load current 100m
30
Glass Wool
(out of scope) (Load Constant) = 1, concentrated load
(a place such as an electrical room) F F

Mini-way
A wall flange is used to seal the gaps produced during installation of Busducts at the walls, W : The width of the product (165mm)
ceilings and floors. H : The height of the product = 0.5, Distributed load F : Flanged End (panel connections)
(It is decided by a rated current.) (a place such as a vertical section) F P P P P P P : Plug-in Unit
W : The width of the product (165mm)
H : The height of the product (It is decided by a rated current.)
10-3 /100m, 60Hz Voltage Drop(V/100m)
Ampere(A)
R X Z 0.7 0.8 0.9 1.0
160 66.4 18.1 68.8 8.72 9.15 9.40 8.82
250 32 15.1 35.4 9.15 9.42 9.44 8.13
AL 400 15.3 13.8 20.6 10.74 10.76 10.42 8.19

The Required Minimum Distances from a Wall for Heat Dissipation 630
800
6.7
5.0
8.0
6.5
10.5
8.2
11.38
11.28
11.11
10.95
10.41
10.16
7.32
6.92
160 82.2 20.9 84.8 9.17 9.56 9.73 8.75
wall , ceiling
wall , ceiling 250 35.1 17.6 36.3 9.64 9.80 9.68 8.04
wall ,, ceiling
wall ceiling wall ,wall , ceiling
ceiling CU 400 17.6 13.7 22.3 11.24 11.34 11.10 8.96
250mm Beam wall , ceiling
wall , ceiling
250mm Beam 630 5.9 9.8 11.4 12.14 11.56 10.44 6.42
100100

250mm Beam
100

250mm Beam 800 4.4 8.1 9.2 12.25 11.57 10.33 6.05
100

wall wall
wall Wall,ceiling Short Circuit Strength
wall
LS C&S Busduct has been tested under actual short circuit conditions according to IEC 61439-1 and 6 [(previous standard) IEC 60439-1 and 2] at KEMA.
The result and the graph are shown below. Phase to Phase Short Circuit Ratings
100 100
Joint
Joint Point
Point
100
100
JointPoint
Joint Point
ceiling
ceiling wall wall
ceiling
ceiling wallwall
100
100100
200
200200

100

100 100
200

wallwall 100
wall wall100
wall 100
wall 100 wall
wall
100
100 AL(kA) CU(kA)
Ampere (A)
1 sec. 3 sec. 1 sec. 3 sec.
160 10 6 10 6
250 10 6 10 6
400 25 15 25 15
630 30 17 30 17
800 40 23 40 23

56 Mini-way LS C&S-Busway System E-series LSC&S-Busway


Mini-way Technical
SystemLS C&S-Busway Data
System 57
. Technical Data . Install Information 06 / 07

Technical Data Joint Connection


Temperature Rise
The temperature rise limit is an important property which determines the performance of Busducts. The temperature rise 1 2
limit of the Busduct is designed so that when a busduct is operated with a rated current, the temperature limit values of the
housing are within 55K as specified in IEC61439-1 and 6 [(previous standard) IEC 60439-1 and 2].

Both parts should be aligned at the top and the bottom and the left and Using a torque wrench, slowly tighten the exposed bolt head of a double

Mini-way
the right as well as horizontally and vertically. (This also applies to the joint headed bolt. The head of the double headed bolt is designed to break
connection of the horizontal and vertical ducts.) Make sure that the joint off at 800~1000Kgfcm. Continue tightening the exposed head until it
kit is not tilted. (We recommend a jig tool for the installation.) breaks off.

3 4
1 2 3 4 5

7 8

-Joint- 6

80 2 3
1
70
4
Once the exposed head and the red tag attached to it have been cut off, Be sure to check the distance from the housing, and the gaps between the
60
Temperature()

they are properly connected. conductors at the kit after the installation.
7 8
50

40 5
5 6
6
30
9
20

10

0 1 2 3 4 5 6 7 8
Time(hr)

Classification 1 2 3 4 5 6 7 8 9
Ambient
Censer Location Connection Conductor Housing Before applying the connection cover, check the space between the end Perform the last inspection of the connection. (Follow the instruction of
Temperature
block and the holes of the connection cover. the installation manual for additional sealing according to the IP Code)
Temperature Rise
75K 79K 80K 61K 39K 32K 52K 53K 23
Value

58 TechnicalLS
Mini-way Data
C&S-Busway
E-series
SystemLSC&S-Busway System E-series LSC&S-Busway System Install Information
Mini-way LS C&S-Busway System 59
VI. Certification & Specification 06 / 07

Certification & Specification


LT- way
LS C&S Busduct System Catalogue
03 of 08

Fire proof Certification Dust and Water proof TUV Eco Friendly Certification
Certification

Contents
I. Introduction
- Overview 62
- Application 63
II. General Data 64
III. Component
- Feeder 67
KEMA Certification KEMA Certification KEMA Certification - Feed in Unit 70
- Flexible Fitting 71
- End Cover 72
- Hanger 72
- Plug in Unit 73
IV. Technical Data
- Impedance 74
- Voltage Drop 74
- Temperature Rise 75
V. Install Information
- Joint Connection 76
- Plug-in Unit Installation 76
VI. Certification & Specification 77
ISO9001 ISO14001 OHSAS18001

60 Certification
Mini-way & Specification
LS C&S-Busway System E-series LSC&S-Busway System E-series LSC&S-Busway System Certification & Specification 61
I. Introduction 06 / 07

Overview Application
About LT-way Supermarkets / Shopping Mall etc.
LS C&S LT-way is designed for small capacity loads of 25 to 63A such as lamp circuits. It is also designed to blend in well with the existing facilities, while
providing the optimum power supply system. The LT-way comes with the optimized cross sectional areas as well as stable design of conductors and Can be used as lighting system in the store.
housing, which provide efficient heat-radiating property specified in IEC heat regulations. The LT-way also comes with a high degree of protection with
standard IP54. The design can be applied in a special environment such as greenhouses and clean-rooms. Its adaptability to frequent alterations of a
layout makes it a perfect product.

Safe and Efficient Distribution System


LS C&S LT-way is designed for small lines or lamp circuits at buildings, factories and shopping malls.
The plug and the outlet attached to the LT-way provide easy management of load distribution.

Eco-Friendly
The LS C&S LT-way is an environmentally friendly product following the
RoHS regulation, and only uses components without hazardous substances.
Factory etc.

Can be used as lighting system for production lines.

Easy Installation Excellent flexibility and adaptability to layout changes.

The light weight of LS C&S LT-way enables easy transportation


and installation, and employing the joint brush system makes
it easy to take apart and assemble. The plug-in load distribution
provides easier maintenance and installation compare to cables.

LT-way
Basement Parking etc.
Can be used as lighting system for basement parking space of
large buildings, apartments and commercial complexes.

62 Introduction
LT-way LS C&S-Busway
E-series
SystemLSC&S-Busway System E-series LSC&S-Busway
LT-way
System Introduction
LS C&S-Busway System 63
. General Data 06 / 07

Plug-in Unit

Plug-in Hole

Feeder

Feed-in Unit Flexible Fitting


Plug-in Unit

Weight Eco Friendly Conductors Housing

LT-way
The compact and light weight design of extruded The LS C&S Busducts acquired RoHS certification, and The conductor uses over 99 percent pure copper flat The high strength aluminum housing can be used
aluminum housing is suitable for low capacity power only uses components without hazardous substances wire consisting of 2 or 4 fibers. Elongated marks have as a protective conductor (PE) due to its high level
lines between 25 to 63A. such as lead, cadmium, mercury, chrome, PBBs and been etched in order to prevent slips when pressed. conductivity and mechanical strength. Variety of
PBDEs. The LT-way comes with high molecule insulation of coating options for the housing is available on request.
a fire proof grade A rating. The intervals between
insulations have been designed for the optimum
functionality as specified in CAE (Computer Aided
Engineering).

Easy Load Distribution Standard Insulation Joint Brush


Each feeder (3 meters) can have a maximum 10 load IEC 61439-1 [(previous standard)IEC 60439-1] Other than the connections and the PH, the conductor The Joint brush can be safely and easily connected
distributions installed, and provide them easily. Power Switchgear and Controlgear Assemblies has been insulated which prevent accidents caused by with a live wire. Optional double cover is available.
IEC 61439-6 [(previous standard)IEC 60439-2] impacts. The insulation uses PVC which has the fire proof The double enhances the strength against impacts.
Busbar Trunking Systems grade A rating (105) according to IEC regulations.

Permissible Operating Temperature Service Condition


The cross sectional areas of the conductor and housing Ambient Temperature : -15 ~55
profile are designed to meet the standard permissible Relative Humidity : 95% or below
operating temperature of IEC 61439-1 and 6. Therefore (When the service condition of the environment does
the temperature rise limit of the housing is within 55K not meet the requirements listed above, please contact
or less of the ambient temperature. our design team.)

64 GeneralLSData
LT-way C&S-BuswayE-series
SystemLSC&S-Busway System E-series LSC&S-Busway
LT-way
System General
LS C&S-Busway Data
System 65
. General Data . Component 06 / 07

Basic Structure Feeder


LT-way comes with flat-wire, and suitable for small loads or lamp loads of 690V 25 to 63A. Each phase has been wrapped The standard length of feeders is either 3 meters or 1.5 meters,
with PVC, an electric insulation with an A rating (fire proof grade 105 oC) or higher, and the same rating insulation supports and 5 plug-in holes can be applied on each side of a
them. 3 meter feeder (maximum 10 holes).
For a 1.5 meter feeder, 3 plug-in holes can be applied
on each side (maximum 6 holes).
Configration

Phase : (PH + N + PE) Phase : (3PH + N + PE)


Wire : 2 (PH + N + PE)
Tier : 1 Wire : 6 1500

Tier : 2 250 500 500 250

H
1500
375 750 375

W
Phase : (3PH + N + PE) Phase : (3PH + N + PE) x 2
3000

LT-way
Wire : 4 Wire : 8
Tier : 1 Tier : 2 300 600 600 600 600 300

3000
500 1000 1000 500

Phase : (PH + N + PE) x 2 Phase : (3PH + N + PE) 3000


Wire : 4 Wire : 4 750 1500 750
Tier : 2 Tier : 2
*It only applies to the special capacity (63A).

Dimension(mm)
Ampere(A)
H W
25 1.8
CU 40 30 50
2.8
63

66 LT-way LS C&S-Busway System LT-way LS C&S-Busway System 67


. Component 06 / 07

Feeder
A single housing can handle two lines (R, S, T, N X 2), and the 3-phase 4-wire system supplies larger capacity than a single
phase which decrease the line imbalance.

Ampere Wire Tier Length Plug-in hole Weight Cat No. Ampere Wire Tier Length Plug-in hole Weight Cat No.
Configuratian Configuratian
A W Tier mm EA g/m No. A W Tier mm EA g/m No.
25 2 1 3000 0 LSLT F252130 25 6 2 3000 0 LSLT F256230

25 2 1 3000 2 LSLT F252132 25 6 2 3000 2 LSLT F256232


2615
2355 25 6 2 3000 3 LSLT F256233
25 2 1 3000 3 LSLT F252133
25 6 2 3000 5 LSLT F256235
25 2 1 3000 5 LSLT F252135
25 6 2 1500 2 LSLT F256212
25 2 1 1500 2 LSLT F252112 1390
STD. Feeder 25 6 2 1500 3 LSLT F256213
1260
STD. Feeder 2 2 1 1500 3 LSLT F252113 (Ph + N + PE) x 2 40 6 2 3000 0 LSLT F406230
(Ph + N + PE) 40 2 1 3000 0 LSLT F402130 40 6 2 3000 2 LSLT F406232
2970
40 2 1 3000 2 LSLT F402132 40 6 2 3000 3 LSLT F406233
2520 40 6 2 3000 5 LSLT F406235
40 2 1 3000 3 LSLT F402133
40 6 2 1500 2 LSLT F406212
40 2 1 3000 5 LSLT F402135 1565
40 6 2 1500 3 LSLT F406213
40 2 1 1500 2 LSLT F402112 25 6 2 3000 0 LSLT F256230
1340
40 2 1 1500 3 LSLT F402113 25 6 2 3000 2 LSLT F256232
2890
25 4 1 3000 0 LSLT F254130 25 6 2 3000 3 LSLT F256233
25 4 1 3000 2 LSLT F254132 25 6 2 3000 5 LSLT F256235
2615 25 6 2 1500 2 LSLT F256212
25 4 1 3000 3 LSLT F254133 1525
STD. Feeder 25 6 2 1500 3 LSLT F256213
25 4 1 3000 5 LSLT F254135

LT-way
(3Ph + N + PE)(Ph + N + PE) 40 6 2 3000 0 LSLT F406230
25 4 1 1500 2 LSLT F254112
1390 40 6 2 3000 2 LSLT F406232
3415
25 4 1 1500 3 LSLT F254113 40 6 2 3000 3 LSLT F406233
STD. Feeder
40 4 1 3000 0 LSLT F404130 40 6 2 3000 5 LSLT F406235
(3Ph + N + PE)
40 4 1 3000 2 LSLT F404132 40 6 2 1500 2 LSLT F406212
1790
40 6 2 1500 3 LSLT F406213
40 4 1 3000 3 2970 LSLT F404133
25 8 2 3000 0 LSLT F258230
40 4 1 3000 4 LSLT F404134
25 8 2 3000 2 LSLT F258232
40 4 1 3000 5 LSLT F404135 3175
25 8 2 3000 3 LSLT F258233
40 4 1 1500 2 LSLT F404112 25 8 2 3000 5 LSLT F258235
1565
40 4 1 1500 3 LSLT F404113 25 8 2 1500 2 LSLT F258212
1670
63 4 1 3000 0 LSLTF634130 STD. Feeder 25 8 2 1500 3 LSLT F258213
(3Ph + N + PE) x 2 40 8 2 3000 0 LSLT F408230
63 4 1 3000 2 LSLTF634132
3860 40 8 2 3000 2 LSLT F408232
STD.Feeder 63 4 1 3000 3 LSLTF634133 3860
40 8 2 3000 3 LSLT F408233
(3Ph+N+PE) 63 4 1 1500 5 LSLTF634135
40 8 2 3000 5 LSLT F408235
63 4 1 1500 2 LSLTF634112 40 8 2 1500 2 LSLT F408212
2010 2010
63 4 1 3000 3 LSLTF634113 40 8 2 1500 3 LSLT F408213

68 LT-way LS C&S-Busway System LT-way LS C&S-Busway System 69


. Component 06 / 07

Feed in Unit Flexible Fitting


The feed in unit connects cables and the LT-way. It can connect a maximum 10mm2 and is The flexible fitting rotates 180 and is used to adjust the height or bypass a route.
used at the opening and ending points of source and load system. The fixing method is the same as the feeder and the standard length is 0.5m and 1m.

53
69

33
500
90 347
[Load] 105

1000
69

605

90 271
[Source]

Ampere Wire Tier Source/Load Weight Cat No. Ampere Wire Tier Length Weight Cat No.
Configuration Configuration
A W Tier Source/Load g/m No. A W Tier mm g/m No.
25 2 1 Source 500 LSLT U2521S 25 2 1 500 585 LSLT X25210

STD. Feeder 25 2 1 Load 600 LSLT U2521L STD. Feeder 25 2 1 1000 1010 LSLT X25211
(Ph + N +PE) 40 2 1 Source 515 LSLT U4021S (Ph + N +PE) 40 2 1 500 610 LSLT X40210
Load

LT-way
40 2 1 515 LSLT U4021L 40 2 1 1000 1060 LSLT X40211
25 4 1 Source 515 LSLT U2541S 25 4 1 500 630 LSLT X25410
25 4 1 Load 515 LSLT U2541L 25 4 1 1000 1100 LSLT X25411

STD. Feeder 40 4 1 Source 550 LSLT U4041S STD. Feeder 40 4 1 500 615 LSLT X40410
(3Ph + N +PE) 40 4 1 Load 550 LSLT U4041L (3Ph + N +PE) 40 4 1 1000 1195 LSLT X40411
63 4 1 Source 615 LSLTU6341S 63 4 1 500 815 LSLTX63410
63 4 1 Load 615 LSLTU6341L 63 4 1 1000 1465 LSLTU63411
25 4 2 Source 515 LSLT U2542S 25 4 2 500 630 LSLT X25420

STD. Feeder 25 4 2 Load 515 LSLT U2542L STD. Feeder 25 4 2 1000 1110 LSLT X25421
(Ph + N +PE) x 2 40 4 2 Source 550 LSLT U4042S (Ph + N +PE) x 2 40 4 2 500 615 LSLT X40420
40 4 2 Load 550 LSLT U4042L 40 4 2 1000 1195 LSLT X40421
25 6 2 Source 530 LSLT U2562S 25 6 2 500 675 LSLT X25620
STD. Feeder 25 6 2 Load 530 LSLT U2562L STD. Feeder 25 6 2 1000 1185 LSLT X25621
(3Ph + N +PE) (3Ph + N +PE)
(Ph + N + PE) 40 6 2 Source 580 LSLT U4062S (Ph + N + PE) 40 6 2 500 745 LSLT X40620
40 6 2 Load 580 LSLT U4062L 40 6 2 1000 1330 LSLT X40621
25 8 2 Source 545 LSLT U2582S 25 8 2 500 720 LSLT X25820

STD. Feeder 25 8 2 Load 545 LSLT U2582L STD. Feeder 25 8 2 1000 1275 LSLT X25821
(3Ph + N +PE) x 2 40 8 2 Source 615 LSLT U4082S (3Ph + N +PE) x 2 40 8 2 500 815 LSLT X40820
40 8 2 Load 615 LSLT U4082L 40 8 2 1000 1465 LSLT X40821

70 Component
LT-way LS C&S-Busway
E-series
SystemLSC&S-Busway System E-series LSC&S-Busway
LT-way
System Component
LS C&S-Busway System 71
. Component 06 / 07

End Cover Plug-in Unit


The end cover is applied at the end of a rail, The load distribution system can be either installed or removed with a live line. The unit is a double-sided
and is the same for all capacities. clamp to connect a conductor, and incombustible materials have been used for the insulation and plastic

Product Capacity(A) Phase Cat No. (No)


Phase Joint Type
Phase L1+N LSLT P10F1
It is usually used for single phase products,
Joint 10/16A L2+N LSLT P10F2
and the design maximizes the convenience.
53

Type L3+N LSLT P10F3


L1+N LSLT P10S1
L2+N LSLT P10S2
33 24
Phase L3+N LSLT P10S3
Capacity Source/Load Cat No.
Selection 10/16A L1+L2 LSLT P10S12
A Source / Load No. Type L1+L3 LSLT P10S13
25 Source LSLT ES L2+L3 LSLT P10S23
53

25 Load LSLT EL L1+L2+L3+N LSLT P10S4


40 Source LSLT ES L1+N LSLT P10FU1
40 Load LSLT EL L2+N LSLT P10FU2
33 93
L3+N LSLT P10FU3
63 Source LSLT ES Fuse
10/16A L1+L2 LSLT P10FU12
63 Load LSLT EL Type
L1+L3 LSLT P10FU13
L2+L3 LSLT P10FU23

Hanger L1+L2+L3+N LSLT P10FU4

Phase Selection Type Fuse Type


General Type Direct Type The adaptability of this type provides options to select a suitable phase It is the same type as the phase selection type; however, the fuse type
depending on the condition of the installation site. The internal process comes with a fuse for each phase to protect faulty current and overcurrent
of the type can be checked through the transparent cover. caused by load distribution.

LT-way
Plug-in Type Product Capacity(A) Phase Cat No.(No)
It is designed for low capacity products (63A or less). Easy to use and a L1+N LSLT P10S1
1-outlet or 3-outlet plug-in is available. L2+N LSLT P10S2
Maximum The hangers are used to install the busducts at buildings.
Load L3+N LSLT P10S3
Product Install Method They can be either installed directly to the ceiling, or at the hanger rods.
kg 1 outlet 10/16 L1+L2 LSLT P10S12
The standard installation interval between hangers is 1.5 meters.
L1+L3 LSLT P10S13
It is installed at the Caution) When the hangers are used to fix lamps, avoid the positions of
General Type 60 L2+L3 LSLT P10S23
hanging bolt. the joint connection.
It is installed at the L1+L2+L3+N LSLT P10S4
Direct Type 60
fixing band. L1+N LSLT P10FU1
L2+N LSLT P10FU2
L3+N LSLT P10FU3
3 outlet 10/16 L1+L2 LSLT P10FU12
Note L1+L3 LSLT P10FU13
Please contact out design team if a special type of hangers (Tee or Reducer) are required due to the installation environment. 1 outlet 3 outlet L2+L3 LSLT P10FU23
L1+L2+L3+N LSLT P10FU4

72 LT-way LS C&S-Busway System LT-way LS C&S-Busway System 73


. Technical Data 06 / 07

Technical Data
Impedance and Voltage Drop Temperature rise
The formula to measure the voltage drop of a Busduct is shown below. The impedance and voltage drop values for aluminum and The temperature rise limit is an important property which determines the performance of busducts. The temperature rise limit of the Busduct is
copper conductors are shown in the table below. designed so that when a Busduct is operated with a rated current , the temperature limit values of the housing are within 55K as specified
The values listed are measured between the upper and middle lines at 60Hz. For a 50Hz installation, multiply the reactance (X) by 0.83. in IEC61439-1 and 6 [(previous standard) IEC 60439-1 and 2].

Vd = I x 3(R cos + X sin)


Vd = voltage drop[V] I = rated road amperes[A] R = resistance[] X = reactance[] / cos = power factor / sim = reactive factor

Actual load current Actual length of the line (m)


Actual voltage Drop = x Vd x x
Rated load current 100m

(Load Constant) = 1, concentrated load


(a place such as an electrical room) F F
= 0.5, Distributed load F : Flanged End (panel connections)
(a place such as a vertical section) F P P P P P P : Plug-in Unit
1 2 3 4 5

7 8

10-3 /100m, 60Hz Voltage Drop(V/100m) -Joint- 6


Ampere(A)
R X Z 0.7 0.8 0.9 1

25 8.1 0.2 8.1 0.25 0.29 0.32 0.35

LT-way
CU 40 3.35 0.167 3.4 0.17 0.19 0.21 0.23
80
63 1.67 0.141 1.7 0.14 0.16 0.17 0.18 70

60

Temperature()
50 2
3 1
40 4

Short Circuit Strength 30

LT-way has been tested under actual short circuit conditions according to IEC 61439-1 and 6 [(previous standard) 20 7 5
8 6
IEC 60439-1 and 2]. 10 9

Copper(kA)
Ampere(A) 0 1 2 3 4 5 6 7 8
1 sec. 3 sec. Time(hr)
25 0.6 0.34
40 1.4 0.8
63 1.4 0.8
Classification 1 2 3 4 5 6 7 8 9
Ambient
Censer Location Connection Conductor Housing
Temperature
Temperature Rise
46K 49K 46K 40K 15K 14K 15K 14K 12
Value

74 Technical
LT-way Data
LS C&S-Busway E-series
System LSC&S-Busway System E-series LSC&S-BuswayLT-way Technical
SystemLS C&S-Busway Data
System 75
. Install Information VI. Certification & Specification 06 / 07

Joint Connection Certification & Specification


1) Check the condition of the joint, and loosen the cross heads 2) Insert the end into the other as shown in the image below,
of the protection cover. and tighten the cross heads.

Caution) Dont loosen the hexagon bolts for they fix the
products in place.

(O) (X)

(X)

(O)
Temperature Rise Test KERI Temperature Rise Test KERI Heat Resistant Performance
Certification Certification Certification

! Caution
Make sure to clean the parts of the joint before installation. Proceed with caution since the joint can be damaged by impacts.
Be sure to keep them straight and steady to connect.

Plug-in Unit Installation

LT-way
Open the plug cover as shown below, and insert an appropriate plug-in unit or an outlet plug.

TUV Environmentally Friendly ISO 14001 ISO 9001


Certification

! Caution
Make sure the plug-in holes are clean before inserting the plug-in unit. Be sure to check the phase of unit and the plug.
OHSAS 18001

76 Install Information
LT-way LS C&S-Busway System
E-series LSC&S-Busway System E-series LSC&S-Busway System Certification
LT-way & Specification
LS C&S-Busway System 77
06 / 07

Memo
BTMS(Temperature
Monitoring System)
(DTS, MPTS, IR-Ts)
08 of 08

Contents
I. Introduction
- Overview 80
- Application 81

II. Component
- DTS 82
- MPTS 85
- IR-Ts 88

78 Certification & Specification


LT-way LS C&S-Busway System E-series LSC&S-Busway System E-series LSC&S-Busway System Certification & Specification 79
I. Introduction 06 / 07

Overview Application
About BTMS
The temperature sensors of the Busduct Temperature Monitoring System (BTMS) measure busduct temperatures in real time to check the abnormality
of the lines to prevent accidents. Therefore, the BTMS is the optimum monitoring system for busducts. S
DTS (Optical Fiber Cable Sensor)
MPTS (Digital Temperature Sensor)
Why BTMS? S
The standard evaluation method to check the stability of the busduct and other power distribution system is the evaluation of a permissible tempera-
ture and temperature change of the insulation materials. The permissible temperature is also used by international standards such as IEC to evaluate the
stability. Therefore, any abnormality of a product can be detected just by checking the temperature change. S

BTMS Benefit S

1) Easy Maintenance: Real time monitoring of the entire system including inaccessible areas
2) Unmanned Monitoring System: Minimize the size of the supervision staff for periodic inspection
S

S
S
BTMS Measuring Principles S

01 Fixed Temperature Measurement Temperature() Alarm


S
(Comparison to the Standard Temperature) IR-Ts (Infrared Temperature Sensor)
Detect abnormalities if the temperature increases over the set value of the
standard temperature.
Ex. Set at 60 C : A pre-alarm will be set off at 50 C
An alarm will be set off at 60 C Distance(m)
Feature DTS (Optical Fiber Cable Sensor) MPTS (Digital Temperature Sensor) IR-Ts (Infrared Temperature Sensor)

02 Differential Temperature Measurement Temperature()


- Sequential temperatures
(Comparison to Time and Temperature) - Measure temperatures at multiple points - Measure temperature at a specific point
- Measure temperature by conducting
Alarm Monitoring - Proximity measurement of the points - Direct or proximity measurement
Detect abnormality if the temperature increases over the set value of the properties
- Identify the variation using data log - High-speed response
temperature during a certain period of time. T - High-speed response
Ex. When the system is set for one minute, and the temperature variation is set
for 7C, an alarm will be set off if the temperature increases over the set value Distance(m) Maximum - Measure temperatures at specific points only
within the scheduled time period. - Repeaterless measurement between - Measure a specific point only
Measurement (up to 80 points can be measured on a single
1 to 12km. (single point for each line).
Section line).
03 Proportional Differential Temperature Measurement Temperature()
Alarm
(Comparison to Temperature Variations) -Suitable for long-distance sensor installation. -Economical due to temperature sensors and -Suitable for local or small-scale installation.

BTMS
T
Economical -The cost of a measuring device is higher for communication modules. -The cost can be high, depending on the
Detect abnormalities based on temperature variations between one Efficiency the optical fiber. -Harness module sensor type.
measuring point and the other.
Ex. An alarm will be set off when the temperature of a measuring point A is
higher than the temperatures of four locations before and after A. Distance(m)
- Additional repeaters and lines are
- Maintenance for optical fiber cable routing is
Installation - Connectors between the modules ensure necessary when transmitting power
required since optical attenuation can occur
Temperature() and easy installation for multiple lines.
04 Proportional Measurement when cable bends.
Alarm T Maintenance - Easy maintenance
- High-voltage line effect - Due to the single point for each line
(Comparison to Temperature Differences) system, high maintenance is required.

For busducts with two or more stacks, an alarm will be set off if the temperature
- Small-sized equipment facilities
differences of the stacks are higher than the set value. - Power Plant, Oil & Gas - Ex. Distribution panel+
Application (electrical rooms)
Ex. A-stsck : 55, B-stack : 65 Distance(m)
- Display, Semi-conductor Ex) Busduct routes busduct joint connections
- Ex. joint connection of busducts

80 Introduction
BTMS LS C&S-BuswayE-series
SystemLSC&S-Busway System E-series LSC&S-Busway
BTMS
System Introduction
LS C&S-Busway System 81
. Component 06 / 07

DTS
(Distributed Temperature System)
DTS Overview Features of DTS
1) Optical fibers are used as the temperature sensor for the DTS. DTS
Compact and light weight By channels (1,2,4,6ch) and distances (2,4,8,10,12km)
The DTS does not get affected by EMC and EMI. Temperature sensing distance(1m) , Accuracy
Economical
2) Measure and monitor temperature of long distance section.
Industrial Computer
3) A self-diagnosis system as well as an auto adjusting system for optical attenuation of optical fibers.
Stability of industrial PC
4) The DTS collects and manages the temperature data. The computer based system ensures easy management of HMI and data.
Fast and stable monitoring and data management
High capacity HDD with 1 terabyte
Principles of Distance Measurement
The distance of the point where the temperature has been measured is calculated using the process speed of the laser UPS (Optional)
pulse within the optical fibers. Provide stable power supply in case of power failure
Protect power supply of computer equipment
x = c x t/2 Fiber is the distributed sensor
and peripheral devices
DTS
Laser Laser Pulse

Detector Backscattered Light GUI


Objective and convenient screen layout
Self data backup and organization system
(data analysis-detect, manage and predict problems)

Principles of Temperature Measurement


Relay and Warning light
Various back scattering laser lights return when the laser pulse has been discharged. One of the back scattering laser lights is
a Raman scattering light, and its wavelength change and scattering strength are used to measure the temperature. Interlocked with the computer and can manage up to 8 signals
Semi-permanent LED warning lights

Ias hav
(- )
kT DTS

Is Monitoring PC

Optical Fiber
Directional
Coupler
Optical Fiber Sensor
las : The illumination level Luminous

BTMS
of the anti-stoke light Source
la : The illumination level of Raman Scattering Laser Light
the stoke light
Rayleigh Band
h : Planck constant
k : Boltzmann constant
Anti-Stokes Raman Stokes Raman
General Function
c : The speed of light Band Band Monitoring temperature profile: Temperature vs. Distance graph
v : Frequency of incident Signal Processing
Monitoring by zones, lines and loads: Up to 500 pre-designated points and statistical information
light Auto detection and warning system (when bidirectional measurement was applied) of optical attenuation and fiber cut
T : Temperature Warning system: Data prints based on real time temperature measurement
Warning signals can be interlocked with other systems
(Ex. Interlocking with fire signal)

82 General
BTMS LSData
C&S-BuswayE-series
System LSC&S-Busway System E-series LSC&S-Busway
BTMS
System General
LS C&S-Busway Data
System 83
. Component 06 / 07

MPTS
(Multi-Point Temperature System)
DTS Application MPTS Preview
The MPTS measures temperature of a specific point by installing a digital temperature sensor at a specific point including the joint
connection of a busduct.
Each sensor is linked to a communication system to transmit the measured temperature in real time.
Up to 80 points can be linked to a single communication line.

Principles of the Digital Temperature Sensor


Principles
[SMS Transmission Screen] The temperature is set by the size of the vibration energy of subtle displacement of atoms and molecules. The resistance values of metallic lines or
semiconductors change by temperature. An electromotive force can occur if the connecting point of dissimilar metals is heated. The digital temperature
sensor measures the resistance or the electromotive force to measure the temperature.
Feature
The system prints out measured temperature vales in digitalized signals. Therefore, data management is easier, and it also prevents degradation caused
by noise. The sensor is energy efficient, and suitable for measuring temperature in wide areas.

The Structure of the Temperature Sensor


Temperature Sensor Module Amplifying Circuit Digital Converting Circuit
[ Factory ]
[DTS Configuration Example] [Trend screen]

Digital Temperature Sensor


Temperature Sensor Module
- The current voltage characteristic changes in accordance with the temperature
variation at the P-N connecting point.

Amplifier Circuit
- In order to amplify the weak signal of the sensor data, an amplifier circuit has been
installed in the sensor.
- Potential exterior noise during signal amplifications has been eliminated.

Digital Converting Circuit

BTMS
- Digitalized temperature value output
- Easy data management and prevention of the degradation caused by noise

[GUI Configuration Example]

84 BTMS LS C&S-Busway System BTMS LS C&S-Busway System 85


. Component 06 / 07

MPTS
The data collected by the sensor is gathered and saved at the data collection system, and monitored by a surveillance PC.

MPTS Application
Drawing up a draft plane is easier thanks to the graphic configuration of HMI, and managing the points using the remote observation system
MPTS Setup reduces the work loads.

Main Screen Location Screen


Displays the temperature monitoring points Displays the locations of the temperature monitoring points

Configuration
No. Specifics Feature
1 Sensor Module Digital temperature sensor module with communication function

BTMS
2 Data Collection Device Collecting and transmitting of the temperature data of the sensor module

3 Power Supply Device Supply power using the sensor module


Alarm Screen Trend Screen
Monitoring measure values through HMI Displays the abnormalities, details and location - Displays the temperature variation trend
4 Monitoring PC
(data set-up, measuring, data log and information reference function)

86 BTMS LS C&S-Busway System BTMS LS C&S-Busway System 87


. Component 06 / 07

IR-Ts
IR-Ts Preview IR-Ts Configuration
The IR-Ts uses an infrared light noncontact temperature sensor to
measure and monitor the heat released from objects. The system is
suitable for dangerous environments including high voltage areas, or
areas where contact sensors are not feasible. Temperature Sensors Data Collection Device

IR-Ts : Infrared Camera

Feature
1) Compact and light weight
2) Can be installed at all directions *
3) Applicable Temperature Range: -20C~ 200C *
4) Real time temperature variation measurement and video (CCTV Camera) *
5) Wire or wireless communication network system

IR-Ts (CCTV) *
: Infrared Camera + CCTV *
*

Installation
(Exterior image of the distribution board)
- PC-
*
*
*

BTMS
Photographic Measuring - 16EA -

1) Infrared Camera(IR Cam) 2) CCTV 3) Composite photograph of IR+CCTV

88 BTMS LS C&S-Busway System BTMS LS C&S-Busway System 89


Global Network

LSCD (New Delhi, India) LSCA (Atlanta, USA)

Yichang, China

Branches
Sydney Office Houston Office
Level 35, Suite 35.02 Northpoint 100 Miller St. North Sydney, NSW 2060 Australia 22126 Manor Estates Dr. Katy, TX77449, USA
Tel. +61-2-9460-0255 Tel: +1-713-202-8003

Manila Office Peru Office


S-1903 B, West Tower, Philippine Stock Exchange Centre Exchange Rd. Av. Dos de mayo No.516 Oficina 307 Miraflores Lima 18 Peru LSCV(Hochiminh) Korea Operations
Ortigas Center, Pasig City, Philippines Tel : +51-1-221-9786
Nhon Trach Il-Lockhang IZ, Nhon Trach Dt. Dong Nai province, Hochiminh, Vietnam
Tel: +63-2-6875028 Headquarters
Tel. +84-61-356-9037
Production : MV/LV Cable, Data Cable LS Tower, 1026-6 Hogye-dong, Dongan-gu, Anyang-si, Gyeonggi-do 431-830 Korea
Jakarta Office Tel. +82-2-2189-9114
Graha Mustika Ratu, 11th Fl. Jl.Jenderal Gatot Subroto Kav.74-75, Subsidiaries
Jakarta Selatan 12870 Indonesia LSCM(Penang)
Tel. +62-21-830-6733 LSCW Lot 1192, Mukim 14, Permatang Tinggi, 1400 Bukit Mertajam, Penang, Malaysia Anyang Plant
Tel. +60-4-588-9609(Ext.34) 555 Hogye-dong, Dongan-gu, Anyang-si, Gyeonggi-do 431-830 Korea
LS Industrial Park, Xin Mei Rd. National High-tech Industrial Development Zone
Singapore Office Wuxi, Jiangsu Province 214028 China Production : Magent Wire Tel. +82-31-428-4114
300 Beach Rd. #25-07 The Concourse Singapore 199555 Production : Automotive Wire, Tube Components, HV Cable & Connectors,
Tel. +65-6342-9162~3 Tel : +86-510-8534-5943
LSCI(Haryana) Bus Duct, Flooring System
Production : Automotive Wire & Cable, Bus Duct, Electroncic Wire & Cable, Tube, ACF,
Accessories for EHV Cable System #101, 1st Fl. Park Center, Sector-30, Gurgaon, Haryana 122002. India
Abu Dhabi Office Tel : +91-124-4285800~4 Gumi Plant
#133, Al Bateen Towers C6, Bainunah St.34, Al Bateen, 190 Gongdan-dong, Gumi-si, Gyengsangbuk-do 730-708 Korea
P.O.Box 113 100, Abu Dhabi, U.A.E LSCT Production : RF Feeder Cable, Power Cable, OPGW
Tel. +82-54-469-7114
Tel : +971-2-406-9856 East of Jing-jin Express, Yixingbu Entrance, Beichen Tianjin, China
Tel : +86-22-2699-7618 LSCD : Marketing and sales Production : Power Cable up to 500kV, OHTL, OPGW, Data Cable,
12th Fl. IFCI Tower 61 Nehru Place, 110019 New Delhi, India RF Feeder System, Copper Rod, Magnet Wire
Riyadh Office Production : Magnet Wire
#7, 2nd Fl. Olaya St. B/D #28, Riyadh, Saudi Arabia Tel : +91-4167-1588
Tel : +966-1-201-3515 China R&D Center(Yichang) Indong Plant
#1 Tanjiahe Rd. Dianjun District, Yi-Chang City, Hubei Province 443004 China LSCA : Marketing and sales 643 Jinpyeong-dong, Gumi-si, Gyengsangbuk-do 730-735 Korea
Cairo Office Tel. 070-8650-2188 6120 Powers Ferry Road, Atlanta, GA 30339, USA Tel. +82-54-469-7763
#36, El-Zeini Tower, 25 Misr Helwan Rd. Maadi, Cairo, Egypt Tel. +1-770-657-6141 Production : Industrial Cable & Module, Optical Cable, Aluminum Materials
Tel. +20-19-966-2810 LSHQ
#1 Tanjiahe Rd. Dianjun District, Yi-Chang City, Hubei Province 443004 China LSCU : Marketing and sales Donghae Plant
Johannesburg Office 1377 Songjeong-dong, Donghae-si, Gangwon-do 240-806 Korea
3rd Fl. South Tower at Nelson Mandela Square,Corner 5th Ave. and +86-717-667-7777 #109, Building 3, Chiswick Busuness Park 566 Chiswick High Rd.
Production : Power Cable, Submarine Cable, Industrial Specialty Cable London, W4 5YA, UK Tel. +82-33-820-3114
Maude St. Sandton, Johannesburg, South Africa
Tel. +44-20-8899-6671 Production : Submarine Cable, Industrial Specialty Cable
Tel. +27-11-783-6320
LS-VINA(Haiphong)
Moscow Office South of Binh Bridge St. So Dau Precinct, Hong Bang Dt. Haiphong, Vietnam LSCJ : Marketing and sales R&D Center
Park Place Tower E711, 113/1 Leninsky Prospect, Moscow 117198 Russia Tel. +84-31-540750 E 16th Fl. Akasaka Twin Tower 17-22, 2-Chome Akasaka, Minato-ku, Japan 200 Dangjeong-dong, Gunpo-si, Gyeonggi-do 431-831 Korea
Tel : +7-495-662-3811~14 Production : EHV Power Cable, ACSR, OPGW, SCR Tel. +81-3-3582-9129 Tel : +82-31-450-8114