by V. Ganapathy, ABCO Industries, Abilene, Texas
Introduction
In any heat transfer equipment such as a boiler or Heat Recovery Steam Generator (HRSG), the
exit gas temperature determines the amount of energy recovered from the flue gas stream, which
is indicative of efficiency. Hence efforts are often made to lower this temperature as much as
possible taking into consideration cost effectiveness and low temperature corrosion concerns. In
a conventional steam generator such as a package boiler, the exit gas temperature is
independent of steam pressure. With say a 230 F feed water temperature, an exit gas
temperature of about 300 F can be easily achieved using an economizer as the heat recovery
equipment. However in a gas turbine HRSG, due to thermodynamic reasons, the exit gas
temperature is a function of inlet gas temperature, feed-water temperature and steam pressure.
The low exhaust gas temperature from gas turbines, typically ranging from 900 to 1050F,
generates less steam on unit gas mass basis in the HRSG evaporator compared to a package
boiler. On the other hand, in a steam generator or package boiler, the flue gas stream is cooled
from adiabatic combustion temperature of 3300 F and hence generates a large amount of steam
on unit gas mass basis. Table 1 shows the gas/steam ratio of HRSGs and steam generators.
The small ratio of steam to gas flow in a HRSG is not adequate to cool the exhaust gases in the
economizer, resulting in a high exit gas temperature. Also it can be shown that higher the steam
pressure, higher the exit gas temperature and vice versa. However various options are available
for lowering the exit gas temperature, which improves the HRSG efficiency and these are
examined in this article.
Table 1: Gas inlet temperature vs Steam generation in HRSGs and steam generatorsType of HRSG gas
inlet temp Gas/steam
Unfired 850-1000 7 to 5.5
Supplemenatry fired 1000-1700 5.5 to 2.5
Furnace fired HRSG 1700-3200 2.5 to 1.2
Steam generator* 3300-3400 1.2 to 1.3
[* typical oil or gas fired steam generator]
Pinch point is the difference between the gas temperature leaving the evaporator and saturation
temperature=Tg3-ts
Fig 1: HRSG temperature profiles
Approach point is the difference between saturation temperature and feed water temperature
entering the evaporator= ts -tw2.
Pinch and approach points cannot be arbitrarily selected. In an unfired HRSG, minimum pinch
and approach points range from 10 to 20 F depending on economic considerations. A low pinch
or approach point naturally increases the surface area required for the evaporator and
economizer and thus the HRSG cost. A large value for these variables decreases the amount of
energy recovered and hence a balance has to be struck.
Neglecting variations in gas specific heats we have from the above equations:
(Tg1-Tg3)/(Tg1-Tg4)=(hs2-hw2)/(hs2-hw1)=X
where X is a function of steam parameters. For steam generation to occur, two conditions must
be satisfied: Tg3>ts and Tg4>tw1
If the pinch point is arbitrarily selected, then it is likely that Tg4 can be lower than tw1; if the
approach point is arbitrarily selected, then it is likely that Tg3 can be lower than ts. These
situations are referred to as temperature cross conditions from thermodynamic view point.
Thus one cannot assume an exit gas temperature and determine the steam generation. A
temperature profile analysis must be done in the unfired mode as shown below.
Solution: Assume 10 psi pressure drop in the superheater. The drum pressure is 610 psig and
the saturation temperature is 492 F. The gas temperature leaving the evaporator=492+25=517 F.
The feed water temperature entering evaporator or leaving economizer is 492-20=472 F.
The energy absorbed by superheater and evaporator= 160,000 x 0.27 x 0.98 x (950-517)=18.33
MM Btu/h. In this expression, 0.98 refers to the 2 % heat loss in the HRSG system and 0.27 the
specific heat of the gas at the average temperature of 734 F.
The enthalpy absorbed by steam=(1378.9-455.4) Btu/lb, where 1378.9 and 455.4 refer to
enthalpies of steam at 600 psig, 750 F and at water at 472 F. Neglecting blow down, we have the
steam production as: 18.33x106/(1378.9-455.4)=19,850 lb/h
It may be seen that the exit gas temperature is rather high. With lower pinch and approach
points, we could bring it down a little to around 370 F but not to 300 F range. Thus unfired single
pressure HRSGs are not very efficient particularly at high steam pressures. The exit gas
temperature will be higher at higher steam pressures. Table 1 shows the results of calculations
for various steam pressures.
(based on 15 F approach point,20 F pinch point and 900 F gas inlet temperature and no blow down. Feed
water temperature=230 F)
It can be easily seen that higher the steam pressure, higher the exit gas temperature.
This is due to the fact that higher the steam pressure, higher the saturation temperature
of steam and higher the gas temperature leaving the evaporator. Hence less energy is
available between the gas inlet temperature and gas temperature leaving the evaporator
and the resulting flow through the economizer is not adequate to cool the exit gas
temperature to a low level.
Higher the steam temperature, higher the exit gas temperature. This is again due to the
fact that less steam is generated if it is superheated (due to the higher enthalpy absorbed
by steam) and the resulting low flow through the economizer is not adequate to cool the
exhaust gases to a low exit gas temperature.
Higher the gas inlet temperature, lower will be exit gas temperature. For example, if the
inlet temperature is 1000 F instead of 900 F, the exit gas temperature for the case of 600
psig, 750 F steam is: 1000-(1000-512)/.7728=369 F versus 398 F. This is due to the
simple fact that more energy is available between the gas temperatures entering the
HRSG and leaving the evaporator, which generates more steam, which in turn results in
more water flow through the economizer; the larger heat sink at the economizer can cool
the gases further. It may be shown similarly that lower the gas inlet temperature, higher
the exit gas temperature from the HRSG. This is one of the reasons that part load
operation of gas turbines is not generally a good idea.
Lower the feed water temperature, lower will be exit gas temperature. However one can
to consider condensation of water vapor on economizer surfaces if the inlet temperature
is below the water dew point.
We mentioned earlier that the exit gas temperature and pinch and approach points cannot be
arbitrarily selected and an analysis similar to that above should be done to establish temperature
profiles else there will be temperature crossings. To illustrate this point, a few examples are
given.
Example: Can we obtain a stack temperature of 300 F with 900 F gas inlet temperature and with
steam parameters of 600 psig,750 F and 230 F feed water?
We note from Table 1 that 398 F is the exit gas temperature. With minor improvements in pinch
and approach points, the exit gas temperature can be lowered slightly but not to 300 F level. Let
us see what happens if we did so.
Example: Can we have a pinch point of 20 F when the gas inlet temperature is say 1500 F?
Tg3=512 F at 600 psig. (1500-512)/(1500-Tg4)=0.7728 or Tg4=221 F, which falls below the feed
water temperature. Hence a large pinch point and a large approach point is associated with high
inlet gas temperatures.
Predicting off-design performanceIn order to evaluate the temperature profiles in the fired mode or
other off-design cases, a HRSG simulation analysis should be done[1]. This analysis estimates
the (UA) value of each surface and corrects it for the off-design or fired conditions for the effects
of gas flow, gas analysis and temperature.[U=overall heat transfer coefficient and A=surface
area].Then using the NTU (Number of Transfer Units)method, one arrives at the performance. In
the off-design mode the pinch and approach points fall in place. There is only one design mode
analysis but there can be numerous off-design cases.A software is required to perform this
complex analysis, particularly if the HRSG has multiple pressure levels and has a complex
arrangement of heating surfaces. Note that simulation analysis does not require the physical
design of the HRSG as UA is taken as a single entity, which can be obtained from the equation
Q=UADT, where Q=energy transferred to the surface and DT is the log-mean temperature
difference.
Once we have the HRSG performance in various modes of operation such as unfired, fired, part
load etc, the next question is: How can we improve the efficiency of a HRSG or lower the exit gas
temperature?
Auxilliary firing
Using low pinch and approach points for the HRSG evaporator
Auxilliary firing
Auxilliary firing of turbine exhaust gases is the simplest way to improve the efficiency of a HRSG.
In a gas turbine, unlike a steam generator, the exhaust gas flow remains constant and adding
fuel alone without adding air increases the exhaust gas temperature. The exhaust gas typically
has 14 % volume of oxygen and hence is capable of being fired to about 3000 F without
additional air. The relation between oxygen consumption and fuel input to a HRSG is given by
the simple relation [1]: Q=58.4WO
Let the exhaust gas flow=100,000 lb/h at 900 F with the following analysis:
CO2=3,H2O=7,N2=75 and O2=15 by volume. If the gas inlet temperature is 900 F and is raised
to 3000 F, the fuel required can be shown to be 74 MM Btu/h. This lowers the oxygen content by
about 12.3 % and hence 2.7 % oxygen still remains in the exhaust gases. Thus a lot of energy
can be added to the exhaust gases, which in turn generates steam in the HRSG. The exit gas
temperature is also lowered due to the larger heat sink in the form of economizer. In fact, it can
be shown that the efficiency of fuel input is nearly 100 % or all of the fuel goes into generating
steam. In a conventional boiler, it is a well known fact that increasing the excess air decreases
the boiler efficiency. In a HRSG,the excess air is decreased by addition of fuel, which increases
the efficiency. Also, we have a lower exit gas temperature, which also contributes to the
efficiency improvement.
Conclusion
Efficiency of an unfired single pressure HRSG is low and can be improved using several
methods as discussed above. Though the cost of the HRSG increases, the payback is quick and
well worth consideration, particularly when the fuel cost is on the rise. HRSG simulation is a
valuable tool that may be used to evaluate the performance of HRSGs in various modes of
operation to determine if the HRSG design can be optimized. It also helps to arrive at the
gas/steam temperature profiles in a HRSG, which is basic to understanding and improving the
HRSG performance.
References
1.V.Ganapathy, Waste Heat Boiler Deskbook, Fairmont Press
2.V.Ganapathy, HRSGs-Understanding the basics, Chemical Engineering Progress, Aug 1996.
3.V.Ganapathy, Efficiently generate steam from cogeneration plants, Chemical Engineering,
May 1997
Author Information
V.Ganapathy is a Heat Transfer Specialist with ABCO industries, Abilene, Texas, where he is
responsible for process engineering of package boilers and heat recovery boilers. He holds a
Bachelors and Masters degree in Mechanical Engineering. Ganapathy is the author of over 200
articles and papers on boilers, heat recovery and steam generation and has authored four books.
He has also contributed several chapters to the Encyclopedia of Chemical Processing and
Design. He can be reached at vganapathy@abcoboilers.com