Está en la página 1de 1

TABLE 1 - EFFECTS OF VERY FAST TRANSIENTS [17]

EQUIPMENT VFT EFFECTS MITIGATION TECHNIQUES


Direct connected transformers can experience Transformers can withstand the stress built up by steep front waves. In critical cases, it might
- an extremely nonlinear voltage distribution along the high voltage winding, be necessary to install varistors to protect tap changers against very high frequency transient
TRANSFORMERS connected to the oil-SF6 bushings, due to steep fronted wave impulses oscillations.
- extremely high part-winding resonance voltages due to transient oscillations
generated within the GIS.

The insulation system of breakers and loadbreak switches is not endangered by VFT The development of a ground fault by branching of the leader discharge during a
overvoltages generated in adjacent GIS equipment. disconnector operation can be avoided by a proper disconnector design.
DISCONNECTORS Ground faults induced by VFTO have been observed in disconnectors operations, as
& BREAKERS residual leader branches can be activated by enhanced field gradient to ground and by
feeding them with GIS-generated VFTO.

Breakdown caused by VFT overvoltages is improbable in a well-designed GIS insulation


system during normal operations. However, breakdown values can be reduced by
SF6 INSULATION insulation irregularities like edges and fissures.
The breakdown probability is very low for low VFTO amplitudes, it increases with the
frequency of the oscillations and the degree of the field homogeneity.

TEV can cause sparking across insulated flanges and to insulated busbars of CTs, and TEVs can be minimized
puncture of insulation which is intended to limit the spread of circulating currents within - by a proper design and arrangement of substation mats
the enclosure. - by keeping ground leads as short and straight as possible in order to minimize the
ENCLOSURE inductance
- by increasing the number of connections to ground
- by introducing shielding to prevent internally generated VFT from reaching the
outside of the enclosure
- by installing voltage limiting varistors where spacers must be employed.

BUSHINGS SF6 insulated bushings can be affected as other SF6 equipment. Avoid high impedance in the connection of the last graded layer to the enclosure.
Very few problems have been reported with capacitively graded bushings.

CABLES No problems have been experienced on the main insulation. Grounding connections must be modified to eliminate troubles.
VFT effects appear always in grounded circuits and are originated by TEVs.

TEV may interfere with secondary equipment or damage sensitive circuits Correct cable connection procedures may minimize interference. The coupling of radiated
- by raising the housing potential if they are directly connected energy may be reduced
SECONDARY - or via cable shields to GIS enclosure by emitting free radiation which may - by mounting control cables closely along the enclosure supports and other
EQUIPMENT induce currents and voltages in adjacent equipment. grounded structures
- by grounding cable shields at both ends by leads as short as possible
- by using optical coupling services.
Voltage limiting devices may have to be installed.

TABLE 2 - GIS COMPONENT MODELS [17]

También podría gustarte