Está en la página 1de 13

Available online at www.sciencedirect.

com

ScienceDirect
Solar Energy 97 (2013) 155167
www.elsevier.com/locate/solener

An eective passive islanding detection method for PV single-phase


grid-connected inverter
Ku Nurul Edhura Ku Ahmad , Nasrudin Abd Rahim, Jeyraj Selvaraj, Ahmad Rivai,
Krismadinata Chaniago
UM Power Energy Dedicated Advanced Centre (UMPEDAC), Level 4, Wisma R&D University of Malaya, Jalan Lembah Pantai, 59990 Kuala
Lumpur, Malaysia

Received 4 December 2012; received in revised form 31 July 2013; accepted 12 August 2013
Available online 12 September 2013

Communicated by: Associate Editor Nicola Romeo

Abstract

This paper presented a low cost and eective passive islanding detection method for single-phase photovoltaic grid-connected invert-
ers. An analog circuit for over/under voltage protection is developed to ensure fast detection and no delay to system. An under/over
frequency circuit is also developed, for accurate and fast frequency detection with minimal external components. A new algorithm is
developed in a low-cost PIC18F4550. An improved disconnection time in the proposed method compared with that in the previously
developed method is an attractive solution for single phase grid connected inverters. The low cost, eective and minimal external com-
ponent count are the advantages. A prototype is developed and tested to demonstrate the performance and feasibility of the proposed
method. The experiment results veried that the proposed islanding detection method able to detect islanding operation eectively under
various load types, inverter output powers and quality factors.
2013 Elsevier Ltd. All rights reserved.

Keywords: Passive islanding; Distributed generation; Inverter

1. Introduction a portion of utility system that contains both load and dis-
tributed resources remains energized while it is isolated
Development for renewable energy sources produce low from the remainder of the utility system. Such an undesir-
pollution compared to the fossil fuels and nuclear genera- able event could potentially occur due to the circuit
tion system (Yu et al., 2008). The new paradigm of distrib- tripping, accidental disconnection of the utility due to
uted generation (DG) thus gains technical importance and equipment failure, human error, temporary disconnection
creates business opportunities (Chowdhury et al., 2009). In (for maintenance services) or uncommon network recong-
principle distribution generation is a small scale generation uration (Chowdhury et al., 2009; Yu et al., 2010). Integrat-
unit that need to be installed to the load and also connected ing DG into utility is a major challenge to researchers. DG
to the grid for selling or buying energy purposes. One of could still be supplying local load demand while network is
the most important criteria that need to be considered is already isolated from the main system. Existing methods
the islanding issue (Yu et al., 2010). The islanding are still lacking, hence successful detection of islanding is
condition as specied in Recommended Practice for Utility an ongoing challenge.
Interface of Photovoltaic (PV) Systems (2000), occurs when Two factors must be highlighted to better understand
the islanding phenomenon. The rst one is the available
Corresponding author. Tel.: +60 3 22463246; fax: +60 3 22463257. standards that have been established for the grid connected
E-mail address: edhura@gmail.com (K.N.E.K. Ahmad). system. These standards addressed the issue of islanding as

0038-092X/$ - see front matter 2013 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.solener.2013.08.011
156 K.N.E.K. Ahmad et al. / Solar Energy 97 (2013) 155167

Nomenclature

PV photovoltaic APS active phase shift


DG distributed generation SFS Sandia frequency shift
NDZ none detection zone AFD active frequency drift
PCC point of common coupling RPEED reactive power export error detection
Qf quality factor PLCC power line carrier communication
LPS load parameter space T transmitter
PMS power mismatch space R receiver
In,a negative sequence current SPD signal produced by disconnect
OV/UV over and under voltage SCADA supervisory control and data acquisition
OF/UF over and under frequency Vpcc voltage at point of common coupling
PJD phase jump detection RMS root mean square
ROCOP rate of change of power output LED light-emitting diode
ROCOF rate of change of frequency IGBT insulated gate bipolar transistor
SMS sliding mode frequency shift DFT digital Fourier transformation
PWM pulse width modulation V grid voltage
MPPT maximum power point tracking f grid frequency
R resistor C capacitance
L inductance Qf quality factor

well as procedure for testing and qualifying DG system Active techniques developed include impedance measure-
(Chiang et al., 2010). The second feature is associated with ment (IM), sliding mode frequency shift (SMS) or active
the so called Non-detection zone (NDZ) which can be phase shift (APS), sandia frequency shift (SFS) or active
dened as the zone for which an islanding detection frequency drift with positive feedback, and reactive power
method would fail to operate in time. NDZ is an evaluating export error detection (RPEED) Chowdhury et al., 2009;
criterion of islanding detection methods. In principle, islan- Mohamad et al., 2011; Lopes and Huili, 2006. AFD
ding detection monitors changes in inverter output param- method varies the output current frequency through posi-
eter or other system parameters that indicate islanding. tive feedback. This method will inject a current with
There are two types of anti islanding methods which are slightly distorted in frequency into the PCC. Upon grid dis-
the local and remote methods. The local methods can be connection, the phase error between the PCC voltage and
divided into passive and active. Passive islanding detection the inverter current will be detected by the inverter, which
detects changes in electrical parameters to determine the then tries to compensate by increasing the frequency of the
occurrence of islanding (Chiang et al., 2010). The advanta- injected current until it exceeds the OF/UF limits. How-
ges of these passive techniques are their easy implementa- ever, the performance of this conventional AFD method
tion (no additional controller), no degradation of PV is inecient and researchers are facing diculty in choos-
inverter power quality, and their inexpensiveness. The pri- ing the suitable chopping fraction (cf) value to meet the
mary drawbacks are a relatively large NDZ and ineective- limit of harmonics. Hence, a novel AFD method (Jung
ness in multi-PV inverter systems (Syamsuddin et al., and Yu, 2007) with a periodic chopping fraction that devi-
2009). The most commonly used passive technique for ates from the frequency in an instant way from nominal
islanding detection are under/over voltage and under/over was proposed. Remote islanding detection techniques are
frequency (OV/UV & OF/UF), phase jump detection based on communication between utilities and PV inverter
(PJD), voltage harmonic monitoring, current harmonic units (Syamsuddin et al., 2009). This technique do not have
monitoring, rate of change of power output (ROCOP) the NDZ, do not degrade PV inverter power quality, are
and rate of change of frequency (ROCOF) Yu et al., eective in multi-PV-inverter systems, but are expensive
2010; Llaria et al., 2011; De Mango et al., 2006; Freitas to implement (especially in small systems), and have a com-
et al., 2005; Redfern et al., 1993. Active techniques inject plicated communication technique for multi-PV inverter
a small disturbance at the PV inverter output to detect systems. Common techniques that are communication-
islanding. The main advantage of these techniques is their based include power line carrier communication (PLCC),
relatively smaller NDZ than that of passive methods. Their signal produced by disconnect (SPD), and supervisory con-
main drawbacks are the possibly deteriorated output trol and data acquisition (SCADA). In application, each
power quality causing instability to the PV inverter and method has advantages and drawbacks. Among popular
normally require additional controllers which increased reference standards for islanding are IEEE 929-2000, IEC
the complexity of the method (Syamsuddin et al., 2009). 62116, IEE 1547, VDE 0126-1-1, and AS 4777.3-2005.
K.N.E.K. Ahmad et al. / Solar Energy 97 (2013) 155167 157

Table 1
Existing anti-islanding standards.
Quality factor, Qf Required islanding Normal frequency range, Normal voltage range,
detection time, t f (nominal frequency f0) V (% of nominal voltage V0)
IEC 62116 1 t<2s f 0  1:5 Hz 6 f and 85% 6 V 6 115%
f 6 f 0 1:5 Hz
IEEE 1547 1 t<2s 59:3 Hz 6 f 6 60:5 Hz 88% 6 V 6 110%
IEEE 929-2000 2.5 t<2s 59:3 Hz 6 f 6 60:5 Hz 88% 6 V 6 110%
Japanese standard 0 (+rotating Passive: t < 0.5 s active: Setting value Setting value
machinery) 0:5 s < t < 1 s
Korean standard 1 t < 0.5 s 59:3 Hz 6 f 6 60:5 Hz 88% 6 V 6 110%
VDE 0126-1-1 2 t < 0.2 s 47:5 Hz 6 f 6 50:2 Hz 80% 6 V 6 115%
AS4777.3-2005 1 t<2s Setting value Setting value

Table 1 shows all the standards having their own quality from the variable ac supply, and (2) reading of the
factor (Q) value, the required islanding disconnection time, over/under voltage or over/under frequency values at
and range of operational frequency and voltage (Yu et al., which disconnection occurred. A criteria of acceptance
2010). According to IEEE929-2000 standard the quality for over/under voltage is that the value at step (2) should
factor Q is equals to; equal an under-voltage set point of 5 V; for frequency,
the value should equal an under-frequency set point of
Q tanarccosinepf 1 0.1 Hz.
The primary objective of this paper is to propose a new
The selected Q = 2.5 is equals to a power factor of 0.37.
low cost and eective passive method for islanding detec-
As the power factor increases, Q decreases. Thus according
tion of single-phase grid-connected PV inverter and to
to IEEE929-2000, the test requirement that sets Q = 2.5
compare between the proposed algorithm and existing
equals lines with uncorrected power factors from 0.37 to
algorithm.
unity and seems to cover all reasonable distribution line
congurations (Recommended Practice for Utility Inter-
face of Photovoltaic (PV) Systems, 2000). Meanwhile, Jap- 2. Research methodology
anese standard are proposing Q = 0 based on adding
rotating machinery while islanding test is being conducted 2.1. PV inverter system connected to grid
(Yu et al., 2010). Other than quality factor, disconnection
time is also important. The German VDE0126-1-1 stan- Fig. 1 is the block diagram of a typical single-phase grid-
dard has the strictest disconnection time limit which is less connected PV inverter; here, it has PV arrays, DCDC
than 0.2 s. Normal frequency and voltage range also are boost converter connected to two capacitors in series
crucial to determining islanding detection capability. (and functioning as maximum power point (MPP) tracker),
Australian standard AS4777.3-2005 requires nominal four switching devices connected in full bridge congura-
frequency and voltage range to be set by manufacturer. tion (S1S4) and presented as ideal switches, and a lter
Steps to obtaining tripping values are: (1) determination inductor (Lf) ltering the current injected into the grid.
of under/over voltage and under/over frequency values The power produced by the system is transferred directly
through gradual increase or decrease of voltage and to the grid. Since grid voltage is uncontrollable, the sim-
frequency until the device tested (the inverter) disconnects plest way of controlling system operation is by controlling

Fig. 1. Single-phase grid-connected PV inverter.


158 K.N.E.K. Ahmad et al. / Solar Energy 97 (2013) 155167

Fig. 2. The grid-connected PV inverter system with PIC 18F4550 microcontroller.

15V

R3
R1

LED
+
C1 R2 To Port
Grid RD6
- R1
Op
R1 Amp1
2W06 LM311

15V

R3

R1 LED
+
To Port
RD7
- R1
Op
Amp2
LM311

Fig. 3. Under/over voltage circuit.

the current owing into the grid. The injected current must
be sinusoidal and have low harmonic distortion (Rahim
et al., 2011; Rahim and Selvaraj, 2010).

2.2. Overall block diagram of the grid-connected PV inverter


with the proposed method +

Fig. 2 is the block diagram of the grid-connected PV


inverter system with PIC 18F4550 microcontroller for
islanding detection integrated with the main controller
for the inverter system. In this paper, the proposed low cost
and eective passive method is developed using microcon- Fig. 4. Zero-crossing detector circuit for under/over frequency detection.
troller PIC 18F4550. The controller handles the proposed
passive islanding of under/over voltage and under/over fre-
quency detection before the signals are sent to the main voltage circuit and send the signals as input to PIC18F4550
controller of the single-phase grid-connected inverter. The for under/over voltage detection. For under/over fre-
proposed method takes the grid voltage to the under/over quency, the proposed method detects zero crossing
K.N.E.K. Ahmad et al. / Solar Energy 97 (2013) 155167 159

Table 2
Parameters of the single-phase grid-connected PV inverter prototype.
Parameter Value
D1 RHRP30120 VRR = 1200 V, I = 30 A
S1S4 IGBT IRG4PH50UD VCE = 1200, Ic = 24 A
Filter inductor (Lf) 5 mH
Switching frequency 20 kHz

The islanding detection algorithm output from PIC


18F4550 is input to the main inverter controller through
GPI0A11, the input then used as a signal to turn o the
relay, disconnecting the inverter from the grid (see Figs. 3
Fig. 5. Falling edge of a square wave signal with the triggered interrupt. and 4).

2.3. The proposed under-voltage and over-voltage circuit


detection pulses and sends the signal as interrupt input to
PIC18F4550. These signals are used as conditional PIC 18F4550 was designed to read analog signals
detection in the islanding detection algorithm developed. between 0 V and 5 V, hence the under/over voltage circuit

Fig. 6. Flowchart of islanding detection.


160 K.N.E.K. Ahmad et al. / Solar Energy 97 (2013) 155167

Table 3 Table 4
Load parameters of the simulation and experiment at Q = 2.5, and Load parameters of the simulation and experiment at Q = 1, 2, 2.5, and
P = 1 kW. P = 1 kW.
Types R (O) L C Quality factor R (O) L (mH) C (lF)
Pure resistor load 57.6 1 57.6 183.35 55.26
Resistorinductor load 57.6 73.33 mH 2 57.6 91.67 110.52
Resistorcapacitor load 57.6 138.13 lF 2.5 57.6 73.33 138.13
Resistorinductor-capacitor load 57.6 73.33 mH 138.13 lF

was designed to not exceed that range. In this work, a 240


6 V transformer was connected to the utility source. A rec- forces the voltage down. Resistor pair R2 is a voltage divi-
tier transforms the lower AC voltage into DC. Through der, producing 2.5 V as reference voltage to Op Amp
the addition of resistor R2 parallel with capacitor C1, this LM311. The circuit output connects to RB0. Capacitor
circuit can convert a high voltage signal into a very stable C1 connects to the Op Amp output to act as noise lter
low DC voltage signal. The stable DC signal then act as that gives the possibility to prevent noise in a simple and
input to the under-voltage circuit which used the OpAmp1. cost eective way. It improves triggering of the interrupt
A 10 kO potentiometer is used as tuner for reference volt- by reducing the noise in the low-voltage square-wave sig-
age Vref1. The DC voltage and reference voltage Vref1 are nals. As the square-wave signal is in phase with the grid
compared, with OpAmp1 acting as comparator. OpAmp1 voltage, the falling edge will indicate very accurately where
output is fed to RD6 as input signal to the microcontroller. the zero crossing is. This square wave signal will be the
The same concept is applied to the over voltage circuit, input to interrupt routine INT0, making possible the
except that the location of the reference voltage is now at design of a zero-crossing-detection routine in an interrupt
the positive side of OpAmp2 and the stable DC voltage routine and automatically making the detection fully inter-
now connects to the negative input of OpAmp2. This cir- rupt-driven. Fig. 5 shows a square-wave input signal and
cuit was developed for accurate and fast detection of the triggered interrupt.
under/over voltage without continuous calculation of the
grid voltage RMS as in the past method. Not only does
2.5. Islanding algorithm
detection become very fast, there is no added delay.
Fig. 6 shows the control algorithm of the proposed pas-
2.4. The proposed under-frequency and over-frequency sive islanding detection, applied in PIC18F4550, which
circuit processes the algorithm through C programming language.
PIC18F4550 collects analog inputs data from the under/
This circuit is to ensure accurate and fast frequency over voltage circuit through RD7 and RD6. There is a lter
detection with minimal external components. Resistor R1 in the programming algorithm to meet AS 4777.3-2005

Voltage sensor
PM6000
Current sensor
LAN Area
LeCroy
Oscilloscope

PC for PV Array Simulator PC for PM6000

R C L Inverter PV Array
Simulator
Programmable
AC source
GPIB and serial USB

(a)

Computer
PM6000

Oscilloscope
under and over
voltage circuit

under and over


frequency circuit

Inverter
RLC load

(b)
Fig. 7. (a) Islanding test and (b) the laboratory test equipment with the proposed passive islanding detection method.
K.N.E.K. Ahmad et al. / Solar Energy 97 (2013) 155167 161

Fig. 8. Simulation model of the islanding test circuit.

standard reconnection time. For frequency calculation, a Fig. 7 shows the PV grid-connected inverter hardware
simple zero-crossing circuit is utilized. The square wave prototype controller interface with the islanding detection,
produced by the zero-crossing detector has the same fre- implemented on PIC 18F4550 to validate the performance
quency as the grid. By feeding the produced signal into of the proposed passive islanding detection algorithm.
the RB0 of the PIC18F4550, the microcontroller is pro- Table 2 lists the prototype parameters of the single phase
grammed to be a very accurate zero-crossing detector with grid-connected PV inverter. The hardware was tested under
an interrupt-driven code. various load conditions. Equipment such as PV array

Vgrid Vgrid
400 400
200 200
0 0
-200 -200
-400 -400
Vpcc Vpcc
400 400
200 200
0 0
-200 -200
-400 -400
Iinv*10 Iinv*10
100 100
50 50
0 0
-50 -50
-100 -100
0 0.2 0.4 0.6 0.8 1 1.2 0 0.2 0.4 0.6 0.8 1 1.2
Time (s) Time (s)

(a) (b)
Vgrid
400
200
0
-200
-400
Vpcc
400
200
0
-200
-400
Iinv*10
100
50
0
-50
-100
0 0.2 0.4 0.6 0.8 1 1.2
Time (s)
(c)
Fig. 9. Simulation result for islanding detection, at (a) Q = 1, (b) Q = 2, and (c) Q = 2.5.
162 K.N.E.K. Ahmad et al. / Solar Energy 97 (2013) 155167

 2
simulator, resistor-inductor-capacitor (RLC) load, pro- Qf
grammable AC source, PM6000, and LeCroy Oscilloscope C L 4
R
were used. The test was conducted from 500 W to 2 kW
power output. In the following experiments, the grid-con- Fig. 8 is a diagram of the PSIM model of the islanding
nected inverter was controlled to generate balanced real circuit.
power with the load. Various load types were used to verify
the proposed islanding detection method. Table 3 lists the 3. Results and discussion
load parameters of the experiments. The parameters of
the resistorinductorcapacitor (RLC) load were as 3.1. Disconnection time for dierent method and algorithm
specied by the IEEE Std. 929-2000 (Recommended Prac-
tice for Utility Interface of Photovoltaic (PV) Systems, To prove that the proposed passive islanding detection
2000) for testing islanding operation performance. IEEE has advantages over the implemented algorithm in
Std. 929-2000 states that a non-islanding inverter must shut TMS320F2812 DSP in terms of disconnection times, the
down within 2 s of grid disconnection for loads with a qual- corresponding comparisons were made on both passive
ity factor (Qf) equals to or lower than 2.5. The values for L islanding methods. Low cost PIC 18F4550, compared with
and C are calculated through this formula: ATMEGA and TMS320F2812 DSP with under/over volt-
age and under/over frequency islanding detection algo-
V2 rithms, were compared. The circuit connections and
P 2 algorithms of the past methods are as in Syamsuddin
R
et al. (2009). The prototype of both methods monitored
R grid voltage and grid frequency at PCC (see Table 4).
L 3
Qf  x

Vpcc

400

200

-200

-400
Iinv*10

100

50

-50

-100

0 0.2 0.4 0.6 0.8 1 1.2


Time (s)

(a)
Vpcc

400

200

-200

-400
Iinv*10

100

50

-50

-100

0 0.2 0.4 0.6 0.8 1 1.2


Time (s)

(b)
Fig. 10. Simulation result for (a) RL load (b) RC load under islanding operation with Q = 2.5 and P = 1 kW.
K.N.E.K. Ahmad et al. / Solar Energy 97 (2013) 155167 163

Table 5
Disconnection times of the two methods.
Under voltage Over voltage Under frequency Over frequency
disconnection time (s) disconnection time (s) disconnection time (s) disconnection time (s)
ATMEGA and DSP based Could not be determined 1.2 2.1 52.5
algorithm
PIC 18F4550 algorithm 0.6 0.6 0.6 0.6

Fig. 11. Experiment results for R load under islanding operation, for (a) 25% (500 W), (b) 50% (1 kW), (c) 75% (1.5 kW), and (d) 100% (2 kW) inverter
output, with (M1) Vgrid, (M2) Vpcc, (M3) the inverter output current and (M4) load current.

The disconnection time of PIC18F4550 was much faster for under/over voltage disconnection. This may add some
than that of ATMEGA and TMS320F2812. The cost of lagging to the systems when detecting under/over voltage.
design and implementation for the proposed method were The proposed circuit and algorithm aim to correct the
also much less. The disconnection times were validated problem.
according to AS 4777.3-2005 standard. Table 5 compares
the disconnection times. 3.2. Simulation results
As the table shows, the proposed method is much faster
and more stable than the past method (very unstable). Simulations were performed using PSIM system. The
Although over-voltage disconnection time of the past DC voltage source was 400 V, the grid voltage 240 V, the
method passed the less-than-2-s standard, the proposed grid frequency 50 Hz, and the output lter inductance
method enabled much faster disconnection. From Syam- 5mH. The inverter was designed for 1.4 kW power output.
suddin et al. (2009), this method used TMS320F2812 The RMS current injected into the grid was 6 A. The main
DSP for reading the grid voltage at the sensor signal parameters of the simulation were as those of the experi-
through the ADC and calculates the RMS voltage value ments. The inverter was loaded by a parallel RLC circuit
164 K.N.E.K. Ahmad et al. / Solar Energy 97 (2013) 155167

with quality factors 1, 2, and 2.5. Fig. 9 shows the point of the simulation result for RC under islanding operation
common coupling voltage Vpcc, the inverter current and with 1 kW inverter output power. The Vpcc voltage is
voltage, and grid current and voltage ideally when the almost the same for both simulation and experiment results
inverter is tripped o. (see Fig. 10(b) and 12(b)). From the simulation result for
Fig. 10(a) shows the simulation result for RL under RC load under islanding condition, the value of Vpcc volt-
islanding operation with 1 kW inverter output power. age before inverter is tripped o is 160 V and 216 V from
The inverter output current is almost the same for both the experiment (see Fig. 12(b)).
simulation and experiment results (see Fig. 10(a) and see
Fig. 12(a)). From the simulation result for RL load under 3.3. Experiment results
islanding condition, the value of the maximum inverter
output current before inverter is tripped o is 7.08 A and The grid system was rst connected to the inverter and
5.7 A from the experiment (see Fig. 12(a)). Fig. 10(b) shows then removed to create islanding. Fig. 11 gives the dierent

Fig. 12. Experiment results for (a) RL load, and (b) RC load under islanding operation, with (M1) Vgrid, (M2) Vpcc, (M3) the inverter output current
and (M4) load current.
K.N.E.K. Ahmad et al. / Solar Energy 97 (2013) 155167 165

Fig. 13. Experiment results for RLC load under islanding operation, at (a) Q = 1, (b) Q = 2, and (c) Q = 2.5, with (M1) Vgrid, (M2) Vpcc, (M3) the
inverter output current and (M4) load current.

Fig. 14. Experiment results for RLC load under islanding operation, at Q = 2.5 with (M2) the inverter output current, (M3) load current.
166 K.N.E.K. Ahmad et al. / Solar Energy 97 (2013) 155167

Watt Inverter starts to deliver power


Inverter power

Load power

load
power
grid
power
inverter
power
Grid power
seconds

Fig. 15. The inverter comes on-line and gradually increases its output to 1 kW.

Table 6 grid values. It has been proved that the larger the power
Detection times for the RLC load with Q = 2, as taken by PM6000 imbalance (DP and DQ in local generation and consump-
Universal Power Analyzer.
tion in the islanded system prior to grid disconnection),
Timestamp Channel Arms Watt the larger the variations are in the frequency of the voltage
20130130155137.30 B Load 5.00 1091.88 and voltage at the PCC. Therefore, standard under/over
20130130155137.30 C Grid 2.51 182.38 frequency and under/over voltage protections are success-
20130130155137.30 D Inverter 5.35 1283.13
20130130155137.60 B Load 0.00 0.00
ful in preventing islanding in system with large enough
20130130155137.60 C Grid 0.00 0.00 power imbalances. The islanding condition for the experi-
20130130155137.60 D Inverter 0.00 0.00 ments conducted was made to have the smallest power
imbalance possible, i.e., the worst-case scenario. Fig. 13
shows the experiment results for RLC load under islan-
Table 7
ding, at Q = 1, Q = 2, and Q = 2.5. In the following exper-
Detection times for the dierent quality factors.
iments, the grid-connected inverter will be tripped o
Capacity inverter Quality factor of the RLC Detection
21.25 ms (Q = 1), 24.8 ms (Q = 2) and 55.7 ms (Q = 2.5)
output Load time
after the grid is disconnected. From all the following exper-
1 kW 1 21.25 ms
iments (see Fig. 13), the inverter (Vpcc) briey swings up to
1 kW 2 24.8 ms
1 kW 2.5 55.7 ms slightly more than + and  400 volt peak after the grid is
disconnected, and then shuts down. The detection time of
islanding operation may be dierent under dierent loads
Table 8 and dierent quality factors of RLC load. As Fig. 14
Response to abnormal voltages.
shows, (M2) and (M3), at inverter output 1 kW and R
Voltage (at PCC) Maximum trip time LC load with Q = 2.5, the inverter output current was
V < 120 (V < 50%) 6 cycles almost identical with the load current. This indicates the
120 6 V < 211 (50% 6 V < 88%) 120 cycles worst case for islanding detection, where the power-ow
211 6 V 6 264 (88% 6 V 6 110%) Normal operation
between the grid-connected inverter and the local load is
264 < V < 329 (110% < V < 137%) 120 cycles
329 6 V (137% 6 V) 2 cycles balanced.
Table 6 lists the disconnection times for when the grid
was disconnected until the inverter was tripped o. As
shown in Table 6 the disconnection time is 0.3 s (24.8 ms)
inverter outputs: 25%, 50%, 75% and 100% with pure resis- for RLC load with Q = 2. PM6000 Universal Power
tive load under islanding condition. The results allow con- analyzer was set to the minimum time setting available
clusion that the ratio of the inverters output and load for data recording (every 0.3 s). The detection time satises
consumption can aect the amplitude of the load voltage. the IEEE 929-2000 control standard, verifying that the pro-
Fig. 12 shows the experiment results for the RL and R posed islanding method is able to detect islanding eec-
C loads under islanding operation. In the following exper- tively. As shown in Table 6, the inverter current value
iments, the grid-connected inverter will be tripped o when immediately zeros out after the grid is disconnected (see
islanding is detected. Table 7).
Under islanding conditions, the magnitude and fre- According to IEEE Std. 929-2000 standard, the relation-
quency of the voltage at PCC tend to slide from the rated ship between the amplitude of the load voltage and the
K.N.E.K. Ahmad et al. / Solar Energy 97 (2013) 155167 167

maximum trip time for determining the islanding condition References


are shown in Table 8. All the experiment results show the
amplitudes of the local load (Vpcc) to have passed the fol- Chiang, W.-J., Jou, H.-L., Wu, J.-C., Wu, K.-D., Feng, Y.-T., 2010.
lowing requirement. Active islanding detection method for the grid-connected photovoltaic
generation system. Electric Power Systems Research 80, 372379.
The proposed method is shown to eectively and eort- Chowdhury, S.P., Chowdhury, S., Crossley, P.A., 2009. Islanding
lessly detect islanding operation under dierent load types protection of active distribution networks with renewable distributed
and quality factors. As Fig. 15 shows, the inverter comes generators: a comprehensive survey. Electric Power Systems Research
on-line and gradually increases its output power to 79, 984992.
1300 W. Fig. 15 shows the transition as the inverter power De Mango, F., Liserre, M., Aquila, A.D., Pigazo, A., 2006. Overview of
Anti-Islanding Algorithms for PV Systems. Part I: Passive Methods.
increases and the grid transitions from delivering the load In: Power Electronics and Motion Control Conference. EPE-PEMC
power to negative. Note that the load power stays constant 2006. 12th International, pp. 18781883.
during the transition period. Freitas, W., Wilsun, X., Aonso, C.M., Zhenyu, H., 2005. Comparative
analysis between ROCOF and vector surge relays for distributed
generation applications. Power Delivery, IEEE Transactions 20, 1315
4. Conclusions
1324.
Youngseok Jung, J.C., Yu, Gwonjong., 2007. A novel active anti-islanding
A low cost and eective passive method for islanding method for grid-connected photovoltaic inverter. Journal of Power
detection of single-phase grid-connected inverter is pro- Electronics.
posed. An analog circuit for under/over voltage protection Llaria, A., Curea, O., Jimenez, J., Camblong, H., 2011. Survey on
has been developed, to ensure fast detection with no added microgrids: unplanned islanding and related inverter control tech-
niques. Renewable Energy 36, 20522061.
delay. An under/over frequency circuit has also been devel- Lopes, L.A.C., Huili, S., 2006. Performance assessment of active
oped, for accurate and fast frequency detection and with frequency drifting islanding detection methods. Energy Conversion,
minimal external components. A new algorithm is devel- IEEE Transactions 21, 171180.
oped in a low cost PIC18F4550. The circuit topology, con- Mohamad, H., Mokhlis, H., Bakar, A.H.A., Ping, H.W., 2011. A review
trol algorithm, and operational principle of the proposed on islanding operation and control for distribution network connected
with small hydro power plant. Renewable and Sustainable Energy
method have been presented. PIC18F4550 optimized the Reviews 15, 39523962.
methods performance, which has improved the disconnec- Rahim, N.A., Selvaraj, J., 2010. Multistring ve-level inverter with novel
tion time of a past method. The inexpensiveness, eective- PWM control scheme for PV application. Industrial Electronics, IEEE
ness, and minimal external component count are the Transactions 57, 21112123.
Rahim, N.A., Chaniago, K., Selvaraj, J., 2011. Single-phase seven-level
proposed methods advantages. Its performance and feasi-
grid-connected inverter for photovoltaic system. Industrial Electronics,
bility has been tested and proven by a purpose-developed IEEE Transactions 58, 24352443.
prototype. The main improvements are the disconnection IEEE Recommended Practice for Utility Interface of Photovoltaic (PV)
times, eectiveness in detecting islanding under various Systems, 2000. IEEE Std 9292000, i.
load types, inverter output powers and quality factors Redfern, M.A., Usta, O., Fielding, G., 1993. Protection against loss of
and also cost down of the end product. utility grid supply for a dispersed storage and generation unit. Power
Delivery, IEEE Transactions 8, 948954.
Syamsuddin, S., Rahim, N.A., Krismadinata, Selvaraj, J., 2009. Imple-
Acknowledgments mentation of TMS320F2812 in islanding detection for photovoltaic
grid connected inverter. In: Technical Postgraduates (TECHPOS),
This work was supported by UMPEDAC (University of 2009 International Conference for, pp. 15.
Malaya Power Energy Dedicated Advanced Centre), a ag- Yu, B., Matsui, M., So, J., Yu, G., 2008. A high power quality anti-
islanding method using eective power variation. Solar Energy 82,
ship HICoE (Higher Institution Centre of Excellence) of the 368378.
Ministry of Higher Education, Malaysia and HIR Grant H- Yu, B., Matsui, M., Yu, G., 2010. A review of current anti-islanding
16001-00-0000032 Campus Network Smart Grid System for methods for photovoltaic power system. Solar Energy 84, 745754.
Energy Security. The authors thank all concerned.

También podría gustarte