Está en la página 1de 3

CALCULO DE TUBERIA - INSTALACION INTERIOR A 140 mbar

1.7 Densidad del GLP Presin Man (bar) 0.140


27.5 P.C.S. Pre.Atm.La Paz (bar) 0.673

Long Real Long eq CAUDAL Dimetro Dimetro p1 abs p1^2 - p2^2 p2 abs p2 man p prom cada de P
TRAMO Pot (kW) p1 man [bar] Vel [m/seg] Relacin Q/D
[M] [M] [M3/HR] [pulg] [mm] [bar] [bar^2] [bar] [bar] [bar] [mbar]

O-A 0.60 0.72 20.92 0.76 1 19.45 0.14000 0.81280 0.00001 0.81280 0.14000 0.81280 0.87581 0.00497 0.03911
A-B 10.98 13.18 17.52 0.64 1 5.62 0.14000 0.81280 0.04253 0.78619 0.11339 0.79957 8.93051 26.60010 0.11336
A-C 4.35 5.22 1.05 0.04 1/2 2.58 0.11339 0.78619 0.00428 0.78347 0.11067 0.78483 2.58728 2.72813 0.01480
A-D 1.07 1.28 2.35 0.09 1/2 4.09 0.11067 0.78347 0.00050 0.78315 0.11035 0.78331 2.30865 0.31614 0.02089
MEDIDOR PARA UN CAUDAL 70 m3/h

REGULADOR 1 PARA UN CAUDAL 80 m3/h

REGULADOR 2 PARA UN CAUDAL 25 m3/h