Protection IED
Technical Manual
VersionV1.00
Doc. CodeF0SF.451.089(E)
Issued Date2010.09
Copyright owner: Beijing Sifang Automation Co., Ltd
Note: the company keeps the right to perfect the instruction. If equipments do not agree with
the instruction at anywhere, please contact our company in time. We will provide you with
corresponding service.
is registered trademark of Beijing Sifang Automation Co., Ltd.
We reserve all rights to this document, even in the event that a patent is issued and a different
commercial proprietary right is registered. Improper use, in particular reproduction and
dissemination to third parties, is not permitted.
This document has been carefully checked. If the user nevertheless detects any errors, he is
asked to notify us as soon as possible.
The data contained in this manual is intended solely for the IED description and is not to be
deemed to be a statement of guaranteed properties. In the interests of our customers, we
constantly seek to ensure that our products are developed to the latest technological standards
as a result; it is possible that there may be some differences between the hardware/software
product and this information product.
Manufacturer:
Beijing Sifang Automation Co., Ltd.
Tel: +86-10-62961515
Fax: +86-10-62981900
Internet: http://www.sf-auto.com
Add: No.9, Shangdi 4th Street, Haidian District, Beijing, P.R.C.100085
CSC-101 Line Distance Protection IED Technical Manual
Important notes
Restricted liability
Device operation
The user is responsible for checking that the rated characteristics of the device are
suitable for its application. The user is responsible for reading and following the
devices operating and installation instructions before attempting to commission or
maintain it. Failure to follow these instructions can affect device operation and
constitute a hazard for people and property.
Please use the testing instruments which comply with the relevant standards for test
and detection as well.
To prevent damage from equipment, dont hot-plug and hot-unplug any module of the
relay; touching the chips and components in printed circuit board is inhibited.
Operation password
The operation password is: 8888, the system setup password is: 7777.
Protective grounding
The user is responsible for compliance with all the existing international and national
electrical codes concerning protective grounding of any device.
~I~
CSC-101 Line Distance Protection IED Technical Manual
Safety instructions
Read these instructions carefully and look at the protective relay to become familiar
with the device before trying to install, operate, service or maintain it. The following
special messages may appear throughout this bulletin or on the IED to warn of
potential hazards or to call attention to information that clarifies or simplifies a
procedure.
Safety alert
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, could
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, could
NOTE
NOTE indicates matters need attention regarding a certain special application,
~ II ~
CSC-101 Line Distance Protection IED Technical Manual
CONTENTS
IMPORTANT NOTES .........................................................................................................I
SAFETY INSTRUCTIONS ............................................................................................... II
1 INTRODUCTION ........................................................................................................ 1
1.1 OVERVIEW .............................................................................................................. 1
1.2 FEATURES................................................................................................................ 1
2 TECHNICAL DATA .................................................................................................... 3
2.1 BASIC DATA ............................................................................................................. 3
2.2 BINARY INPUTS AND OUTPUTS ........................................................................ 4
2.3 PROTECTION FUNCTIONS ................................................................................. 4
2.4 STATION COMMUNICATION.............................................................................. 5
2.5 TYPE TESTS ACCORDING TO STANDARDS ................................................... 6
3 HARDWARE ................................................................................................................ 9
3.1 PRODUCT STRUCTURE ....................................................................................... 9
3.2 MODULES ARRANGEMENT ............................................................................. 10
3.3 TRANSFORMER INPUT MODULE ( TIM ) ..................................................... 10
3.4 CPU MODULE ( CPU ).......................................................................................... 10
3.5 COMMUNICATION MODULE ( COM )............................................................ 11
3.6 BINARY INPUT MODULE ( BIM ) ..................................................................... 11
3.7 BINARY OUTPUT MODULE ( BOM ) ............................................................... 11
3.8 POWER SUPPLY MODULE ( PSM ) .................................................................. 11
3.9 HUMAN-MACHINE INTERFACE ( HMI )........................................................ 12
4 PROTECTION FUNCTION ..................................................................................... 13
4.1 WHOLE STRUCTURE OF PROTECTION PROGRAM ................................. 13
4.2 THE PROTECTION BASIC ELEMENTS .......................................................... 13
4.3 SELF-TESTING FUNCTION AND OTHER CRITERIA ................................. 23
4.4 PILOT PROTECTION .......................................................................................... 31
4.5 THREE ZONES DISTANCE PROTECTION ..................................................... 35
4.6 DISTANCE PROTECTION LOGIC BLOCK..................................................... 38
4.7 DESCRIPTION OF ZERO-SEQUENCE FUNCTION ...................................... 40
4.8 ZERO-SEQUENCE PROTECTION LOGIC BLOCK ...................................... 42
CSC-101 Line Distance Protection IED Technical Manual
1 Introduction
1.1 Overview
The CSC-101 line distance protection IED is used for the protection of overhead lines
and cables in all types of networks up to the highest voltage levels. It is suitable for
the protection of heavily loaded lines and multi- terminal lines where the requirement
for tripping is one, and/or three pole. It can be adopted for double bus arrangement,
1 breaker arrangement and etc.
The IED consists of line pilot protection, 3 zones distance protection, 4 stages earth
fault overcurrent protection, STUB protection, and etc.
Earth Fault
STUB
Type Pilot protection Distance overcurrent
Protection
Protection
CSC-101A
1.2 Features
1.2.1 High performance hardware
-1 -
CSC-101 Line Distance Protection IED Technical Manual
-2 -
CSC-101 Line Distance Protection IED Technical Manual
2 Technical data
2.1 Basic data
-3 -
CSC-101 Line Distance Protection IED Technical Manual
Environment conditions
Ambient temperature -10C+55C IEC 60255-6: 1988;
Extreme range of ambient -25C~+70C GB/T 14047-1993, IDT
temperature
Atmospheric pressure 80~110kPa
Relative humidity 95%
Storage temperature -25~70
-4 -
CSC-101 Line Distance Protection IED Technical Manual
-5 -
CSC-101 Line Distance Protection IED Technical Manual
-6 -
CSC-101 Line Distance Protection IED Technical Manual
-7 -
CSC-101 Line Distance Protection IED Technical Manual
-8 -
CSC-101 Line Distance Protection IED Technical Manual
3 Hardware
3.1 Product Structure
The CSC-101 relays are housed in 19-inch height, 4U width case which meets IEC
60297-3 standard, with unitary faceplate and the withdrawal/insertion function
modules locked by ejector/inserter clips. All function modules are embedded in the
case, and all wiring terminals are designed at rear panel. The current/voltage
connector can be expanded and combined at random because of their same
configurations and sizes. A case size is shown in Fig.2-1, and the relay outline is
shown in Fig.2-2.
-9 -
CSC-101 Line Distance Protection IED Technical Manual
1 2 3 4 5 6 7 8 9 10
TIM CPU CPU COM BIM BOM BOM BOM BOM PSM
-10 -
CSC-101 Line Distance Protection IED Technical Manual
performs sampling, A/D transform, upward transmission analog data and input
information, judgment of the protection criteria, fault recorder and software and
hardware self-testing etc. CPU2, which is called startup CPU module, performs the
protection startup and block etc.
In order to backup data and test A/D by the protection itself, every AC analog circuit is
devided to two channels to be sampled two analog quantities such as Ia and IaR for
the current of phase A, Ib and IbR for the current of phase B. The analog quantities
with postfix capital R are used to backup and test by the protection itself.
Each of binary input modules has two groups input circuits and self-testing circuits, so
all input circuits can be performed real time self-testing.
Output modules mainly provide tripping contacts that can be output directly from
modules with great performance against interference. The definitions of all contacts
can be referenced in part of rear panel wiring terminals explanation.
-11 -
CSC-101 Line Distance Protection IED Technical Manual
+ 24V two groups provided: power for inputs and outputs module
It is fixed on the front panel of the equipment and includes LCD, keys, reset buttons
-12 -
CSC-101 Line Distance Protection IED Technical Manual
4 Protection function
4.1 Whole structure of protection program
Software modularized design in the protection system ensures the same function
module has the same program module in different type system. The following
introduces the modularized design according to various modules classed as software
whole structure, elements of relay protection and operating logic.
For the general alarm signals (Run Alarm), only the signal is sent out to clue the
operator to examine and repair. For the serious alarm signal threatening the
protection security and reliability (Relay Alarm), once the signal is sent out, the
protection output circuit is blocked.
When fault occurs in power system, fault dealt program does not return to the main
program until it has finished all relevant protection functions to reach to meet the
conditions of the whole reset.
Startup element mainly implements to detect fault, start the protection relay and
energize positive power supply for the output relay. Once startup element operates, it
does not reset until the protection relays fully return.
-13 -
CSC-101 Line Distance Protection IED Technical Manual
Sudden-change current differential element is the main startup element that can
sensitively detect most of faults. Its criterion is as follows:
i>IQD
or 3i0>IQD
To ensure the protection right operation in the loss of static stability state, the static
stability breakage detector is settled.
(1) All currents of phase A, B and C are greater than the current setting value
I_PowerSwing, and the sudden-change current elements have not operated.
(2) All impedances of phase-to-phase AB, BC and CA enter into zone III of distance
relay, and the sudden-change current elements have not operated.
Any of the above conditions has been validated for 30ms, power system is regarded
as the loss of static stability state, then, the startup element operates, the protection
program is switched to power swing blocking module, at the same time, Z Startup or
I_PS Startup and Relay Startup are reported.
-14 -
CSC-101 Line Distance Protection IED Technical Manual
When one end of the protected line is weak-source system, lower voltage can be
used to startup protection for permission mode. Its criterion: Single-phase voltage is
less than 30V or phase-to-phase voltage is less than 50V and the relay receives
signal.
Using various phase selecting principles to detect various fault types, phase selector
can pick out fault phase to meet single-phase tripping.
The protection flexibly makes use of various principles of phase selection for different
fault cases. Sudden-change-current phase selector is employed at the beginning of
fault after sudden-change current startup, later, sequence fault components phase
selector is used. Both sudden-change-current phase selector and sequence fault
components phase selector are not applicable to weak-source system and feeder
terminal line where low voltage phase selector is employed.
The amplitude of phase-to-phase differential current IAB, IBC and ICA at different
faults are shown in Tab.4-1 below.Where + means the bigger one++ the more
bigger one means the smaller one
Table 4-1
Phase
A B C AB BC CA ABC
Selected
I
IAB
IBC
ICA
IAB, IBC and ICA can be sorted into the biggest, the bigger and the smaller, then
the fault selection result can be implemented according to Tab.2.
Steady sequence fault components phase selector mainly uses the angle relation of
zero- and negative- sequence current to detect the fault phase with an additional
method based on phase-to-phase ejection.
-15 -
CSC-101 Line Distance Protection IED Technical Manual
Theoretical analysis have demonstrated that, compared with phasor I0a, I2a locates
at area of -30+30when A-phase earth fault occurs or BC-phase earth fault does
with a smaller arc resistance, furthermore, I2a lags behind I0a close to 90with the
resistance increasing. Six phasor areas can be devided according to the angle
relation of I2a/I0a as shown in Fig.4-1.
I0a
0 0
+30 AN,BCN -30
ABN BCN
0 0
+90 -90
CN,ABN BN,CAN
0 0
+150 CAN -150
Corresponding phase-to-phase faults are affirmed directly in the above areas of (2),
(4) and (6). On the other hand, in phasor areas of (1), (3) and (5), there are
single-phase and phase-to-phase both fault types which are always independent to
each other and can be differentiated by phase-to-phase impedance calculation. If
phase-to-phase impedance is greater than its setting value, then phase-to-phase
fault is impossible whereas single-phase-to-ground fault can be confirmed, otherwise
phase-to-phase fault will be done.
Low voltage phase selector mainly meets phase selection of the relay fixed at
weak-source end where both of the above phase selectors cannot select faulted
phase. If VT circuit does not open, low voltage phase selector can be put into
operation. Its criterion is as below.
a) Any one of phase voltage is less than 0.5Un, and other two phases voltage are
larger than 0.8Unthen the single phase with lower voltage is faulted.
-16 -
CSC-101 Line Distance Protection IED Technical Manual
Where XDZ is set according to the protected range and RDZ is set according to
avoiding load impedance (under general instance), which meets different
requirements to enhance the resistive tolerance to high path fault resistance for short
line and to improve the ability of avoiding load impedance for long line. The reactance
as shown in Fig.4-2 to enhance
line of polygon is inclined to an obliquitous angle 7
the ability to prevent the relay from overreaching at forward external faults.
When fault occurs after reclose or manual close, based on the characteristics shown
in Fig.4-2, the impedance operating characteristics is added a small rectangle area
including center of coordinates as shown in Fig.4-3. This is called impedance-offset
characteristics that can ensure that faults near the bus can be reliably cleared. Zone
3 of distance relay has offset characteristics when three-phase fault occurs.
Fig.4-2 Fig.4-3
Fig.4-2 Operating characteristics of polygonal distance protection
The values in the small rectangle operation area are shown in Tab.4-2.
-17 -
CSC-101 Line Distance Protection IED Technical Manual
Tab.4-2
d ( I K X 3I 0 )
UL * dt +R *(I+Kr3I0)= A, B, C.
dI
For phase-to-phase impedance: UL dt + RI=AB, BC, CA.
Special directional elements are set to resolve dead zone for distance protection
when fault occurs near the bus. For symmetric fault, the memory voltage that is two
cycles of pre-fault voltage is used to compare phasor with post-fault current to detect
direction. For asymmetric fault near the bus, negative-sequence directional element
is taken as directional element of distance relay. The operating conditions for distance
relay are as below: The forward directional element operates, and measuring
impedance lies within the setting polygon area.
-18 -
CSC-101 Line Distance Protection IED Technical Manual
. .
Area of forward directional element is 18arg3 I 0/3 U 0180
. .
Area of reverse directional element is -162arg3 I 0/3 U 00
lm
forward
81 81
18
3U0
reverse
Directional element lies in the forward directional operation area and 3I0>3I0DZ.
Where 3I0DZ is the setting value of zero-sequence current setting 3I0 of pilot
protection, the setting Iset of inverse time zero-sequence current, and the setting
values of stage IIV of zero-sequence current I01, I02, I03 and I04.
-19 -
CSC-101 Line Distance Protection IED Technical Manual
lm
forward
81 81
18
3U2
reverse
Power system is impossible to begin swing within 150ms after sudden-charge current
startup element operating, therefore, during this time, all distance relays are settled to
take on action but power swing block need not be enabled. After 150ms or the
protection startup by loss of static stability or zero-sequence current, the distance
relay must be enabled by fault detector to prevent mal-operation during power swing.
Fault detectors of power swing blocking are different for asymmetric faults and
three-phase fault.
Zero- and negative-sequence current can distinguish fault from swing. The criterion is
described as below.
|I0|>m1|I1| or I 2>m2|I 1|
Where m1 and m2 ensure that, during power swing, the mal-operation of the distance
protection is not caused when external fault occurs under the most disadvantageous
conditions of power system but asymmetric faults detection element can be operates
when internal asymmetric fault occurs.
When power swing happens, I0 and I 2 are close to zero, it is impossible for the
above formula to come into being. When power swing and external fault occur, the
smaller fault component current at the relay location cant meet the above formula.
When power swing and internal fault occur, I0 and I 2 will be big enough to meet the
above formula. To keep the protection from mal-operation caused by the imbalance
output of zero- and negative-sequence current when the external fault is removed,
the protection has to operate in a certain short time delay.
-20 -
CSC-101 Line Distance Protection IED Technical Manual
element dR/dt
4.2.6.2.1 During power swing, measuring resistance or measuring impedance at the relay
location is continuously changing with time, and sometimes the change is slow,
sometimes the change is intensive, the change rate is decided by swing period and
the machine angle . Curve 1 and curve 2 in Fig.5-6-(a) are the trajectories of
measuring resistance changing with time, where Rf is load resistance component and
Tz is swing period. Whether the trajectory of measuring impedance is a line or a
circular arc on R-X plane during power swing, is decided by electromotive force of
both terminals equivalent system, as shown in Fig.5-6-(b).
Rm(t)
1 2 jX
Rf
t Zm
0
R
0
Tz
a b
(a) measuring resistance Rm changing with time (b) the track of measuring
impedance on R-X plane
Fig.4-6 The trajectory of measuring impedance during power swing
Rm(t)
Rf
Rk
O t
t1 t2 t3
-21 -
CSC-101 Line Distance Protection IED Technical Manual
4.2.6.2.2 When fault occurs on the protected line, resistance component of measuring
impedance maybe changes due to electric arc elongated, but analysis and calculation
show that changing rate of arc resistance is far less than that of resistance
corresponding to the possibly biggest swing period noted up to the present. After
short circuit, measuring resistance is resistance RK of short circuit, whose value
hardly changes or almost keeps invariability, as shown in Fig.5-7. The rule of
measuring impedance is also similar.
Contrasting Fig.5-6 with Fig.5-7, it can be seen that power system is determined to be
in the swing state if measuring resistance is always changing and exceeds a
threshold value in a period of time. Therefore, the least change of resistance is
looked over during power swing. It can be known from analyzing Fig.5-6 that the
instance of the least change of measuring resistance occurs in the following
conditions.
1) near 180
And then, enlarge this part track of resistance change to be shown in Fig.11.
Rm
180
Rmin
t
/2
Rmin180TZMAX )
is obtained corresponding to a time , in this way, for any
Therefore, consider error and protection margin, take the following formula as
criterion detecting swing.
R K Rmin180TZMAX )
(1)
Reliable coefficient K is a less than 1. Surely, also consider equivalent system
-22 -
CSC-101 Line Distance Protection IED Technical Manual
Concluding the above analysis, we can reason the method distinguishing fault from
power swing:
When fault occurs, it is possible that formula (1) is satisfied due to time
too small, however, can be increased to relax the restrained condition
gradually.
4.2.6.2.3 When fault suddenly occurs on the protected line, if the angles between two sources
do not reach 180, or three-phase fault occurs outside the swing center, the
magnitude and angle of pre- or post-fault impedance must have great sudden change.
Based on this character, distance element can be enabled quickly when three-phase
fault occurs in power system without serious swing or under the conditions that swing
does not occur after protection pickup for 150ms.
Two criteria are set to detect VT circuit opened and both of them have delay time.
Only under normal operation and without any element startupthey are put into
operating. Hardly does the circuit-opened detector stop operating when any startup
element operates, and it is not enabled until all system reset.
When TV is connected to line, if any phase voltage Ua, Ub or Uc is less than 8V,
-23 -
CSC-101 Line Distance Protection IED Technical Manual
and any phase current is larger than 0.04In or CB is in the closed state (detect
tripping state input)TV circuit can be also confirmed to be broken.
When TV circuit is opened, TV Fail is reported, and all distance unit, negative
sequence directional unit and zero current unit with direction are forbidden to operate,
while current differential pilot protection not being affected by TV opened continues to
work. TV voltage will be continuously supervised in order that each element can be
automatically put into the operation again as soon as the voltage returns to the
normal.
Relay startup
Binary of
VT Fail
NO DICB
OPEN
1
OR1
1
VT_bus OR2
& &
Relay test AND3 AND5
Ia(b,c) >
0.04In
&
AND4
Ua(b,c) < 8V
-24 -
CSC-101 Line Distance Protection IED Technical Manual
To prevent the relay from wrong trip, interruptions in the secondary circuits of current
transformers is detected and reported by the device. When the zero-sequence
current is always larger than the setting value of 3I0_Startup for 12s, CT Fail will be
reported and each zone of zero-sequence current protection will be blocked.
. . .
I
By comparing amplitude and phase of self-producing 3I0 ( I A + B + I C ) with that of
3I0 external connectedwhether the polarity of external 3I0 is connected in reverse or
not can be differentiated, if it is in reverse,3I0 Reverse will be reported.
If the third harmonic voltage exceeds, Harmonic3 Alarm will be reported with delay
timebut the protection is not blocked.
If there is input signal of auxiliary tripping contact of CB, and corresponding phase
has current, which is confirmed with 2s delay time, CB Open_A (B,C) DI Err is
reported.
The system supervises load flow on real time. If all three-phase current are always
greater than the setting current of loss of static stability for 30s, Overload is
reported.
-25 -
CSC-101 Line Distance Protection IED Technical Manual
4.3.1.9.1 CPU module self-testing. CPU module performs self-tests to its memories, analog
channels and program areas during power-up, parts of the above are checked by
itself in real time during the system running. If any of them is confirmed to be failure,
alarm will be given, and the protection will be blocked. (If an alarm is given for
hardware damaged, it still exists after reset. If serious alarm exists, the current
differential relay at remote end of the line reports Offsid Relay Off. If local damaged
hardware is restored, the remote relay reports Offside Relay On.)
4.3.1.9.2 The sampled data can be checked with each other in real time due to the redundancy
set of double A/D channel for one analog quality. If the difference between two
channels exceeds the setting limit, one of the double channels is regarded as fault
one.
4.3.1.9.3 Each I/O plug-in module performs self-testing during power-up and real-time
self-testing. Self-testing checks input channel, output channel, memories and code
areas etc. Self-testing of input channel is performed by bit changing simulation.
Self-testing of output channel is performed by coil tests. The tests are very thorough
with wide range, if any failure is confirmed, alarm is given.
4.3.1.9.5 Communication module performs self tests at power-up and real-time self tests which
verify and check memories, program areas and relevant communication with the
outside. If any abnormal event is detected, alarm will be given.
The input of auxiliary tripping contact of CB lasts 10s, later I operates, and then the
system regards this condition as manual closure of the CB. If no fault is detected,
delay time 1s later, the whole system resets. If fault is detected, instantaneous trip
function put into operation.
Distance relay use impedance element to detect fault, zero-current relay operates
with 100ms delay, when fault occurs during switch-on-to-fault.
When switch-on-to-fault line occurs, if the binary setting of distance relay is enabled,
the distance relay will accelerate to operate. Six loops of impedance will be calculated,
if any of them is located in the area of operating characteristics with offset region. The
-26 -
CSC-101 Line Distance Protection IED Technical Manual
DI CB
OPEN A-
PHASE
DI CB
&
OPEN B- AND1 10s
PHASE
DI CB
OPEN B-
PHASE
Distance
operation
1
OR1
1s Relay reset
100ms
Zero-
sequence
operation
&
No fault AND4
If the fault still exists after automatic reclosure, then the protective elements will re-trip
the circuit breaker.
When the equipment has detected CB opened, and the fault phase current is larger
than 0.1In(single phase reclose mode) or any phase current is larger than 0.1In(three
phase reclose mode) or the input of auxiliary tripping contact disappears, the
equipment think that line has reclosed. Distance protection acceleration function is
enabled according to the control word setting. The acceleration starts up only 500ms
after reclose.
-27 -
CSC-101 Line Distance Protection IED Technical Manual
When all the following conditions have been meet for 5s, the whole relay resets from
fault dealt program.
All three-phase currents are less than the setting I_PS of loss of static
stability.
After tripping commands sent out, the current of tripping phase is in the supervision.
When tripping phase has not current, the protection system considers that CB has
been opened. If tripping phase always has current, the system output three-phase trip
signal with 250ms delay. That is to say, if tripping phase always has current during
250ms after single-phase trip signal output, which indicates CB not tripping, then,
three-phase trip signal is output. After this, if any phase current lasts 250ms,
three-phase final tripping command is issued. Later, if CB still in close state lasts 5s,
three-phase final tripping failure alarm will be sent out, and the whole relay will reset.
Trip command will be withdrawal as soon as fault is cleared. To ensure that CB trips
reliably, withdrawal command is impossible to be considered within 40ms after trip
command sent out.
When there is no current flowing for 5s after the output of trip command, the program
routine jumps to the whole relay reset.
After tripping command output, the sending signal command does not return until
tripping command has been withdrawal for 200ms in order to ensure the pilot
protection of both terminals to operate reliably.
-28 -
CSC-101 Line Distance Protection IED Technical Manual
relay.
If forward element has acted, pilot protection sends out permissive signal, and if
permissive signal from the remote terminal, tripping command will be sent.
If reverse element operates, pilot protection sends out blocking signal, therefore, after
one phase trip, it is impossible for this protection to trip three phases mistakenly when
faults occurs on adjacent line.
Notice that the settings of impedance of two terminals of a line must be same when
the relay is set to blocking mode.
Pilot protection send signal with Tw_reverse delay time when the directional
elements change from reverse direction to forward direction. It prevents relay
wrong tripping when zero- or negative- sequence power reversing flow during
external faults cleared.
In the protection logic for weak-source system, only all the forward and
reverse directional elements do not operate, the send signal element using
low-voltage could be put into operation.
If one side of the line is feeder, when forward fault for the relay at feeder side occurs,
the fault characters are no longer same as that of two side source system. To perform
selective tripping function for a line with feeder, feeder tripping of pilot protection must
be put into operation.
When internal faults occur, the local relay sends out permissive signal in order that
the relay at power source side trips quickly. The relay at weak-source side can
-29 -
CSC-101 Line Distance Protection IED Technical Manual
Phase selector of the relay at weak-source end can meet the phase-selection
requirements for line faults, and the relay can correctly perform selective trip. Even if
faults occur on load terminal line, the relay can either send out tripping command
quickly and exactly or select fault phase correctly.
When sudden-change current startup element does not pick up, if feeder function is
enabled, relay starts up under the following conditions.
Receiving signal.
After pickup, the feeder relay will send signal quickly and extend the signal 200ms to
ensure the relay at power source side to trip quickly.
At feeder side, if the relay have picked up and the following conditions are satisfied,
the relay of permissive mode sends permissive signal. If the setting of the relay at
feeder is enabled, the relay can trip after confirming permissive signal.
Not receiving blocking signal for 25ms or receiving permissive signal for 5ms.
Relay will give the event report of weak send signal for permissive mode.
Directional elements of pilot protection send signal with Tw_reverse delay time and
confirms to trip when the directional elements change from reverse direction to
forward direction to prevent wrong tripping caused by zero- or negative- sequence
power reversing flow during external faults cleared.
The high arc resistance fault, pilot relay meet the condition that send signal on the
one side, But pilot relay dont meet the condition the other side. So the first stage of
zero-sequence or zone I of phase to earth distance near the fault will first act, and the
pilot relay protection on the other side will meet the condition that send signal after
the breaker because the current change subsequently. The relay will send the signal
-30 -
CSC-101 Line Distance Protection IED Technical Manual
CSC-101 pilot distance protection logic for overreach permissive mode is shown in
Fig.4-11-a. CSC-101 pilot zero sequence current protection logic is shown in
Fig.4-11-b.
When internal fault occurs, the startup elements and pilot distance can operate,
permissive signal is sent out to the remote to permit the remote trip. If it is external
fault that occurs on line, the forward directional element of one end of the line
operates and does not receive permissive signal while that of another end of the line
does not operate and receive permissive signal, therefore, both ends cant trip.
Pilot distance operates that permissive signal is sent out to the remote.
Because the directional element near fault detects reverse direction, it does not send
permissive signal to the remote. Although the remote relay can send signal, it cannot
receive the remote permissive signal, therefore, both of two sides do not trip.
The method to resolve this problem for the relay is that the relay sends signal with
Tw_reverse delay time when the directional element operates from the reverse to
the forward to avoid the period in which both sides are forward direction, and then
both sides trip after sending signal is confirmed with 15ms delay when internal fault
occurs again.
-31 -
CSC-101 Line Distance Protection IED Technical Manual
For feeder end, sudden-change current startup element cannot operates, the
logic of the low voltage is startup.
If the relay at feeder end receives the remote permissive signal and <low
voltage element> operates, relay startup.
Within 200ms after protection pickup, if <low voltage element> operates, both
the forward and reverse directional element at feeder end do not operate,
and the permissive signal has been received for 5ms, sending signal
lasted for 150ms to ensure the relay at power source end trips quickly. feeder
end can also trip.
4.4.1.1.5 The protection is not picked up, receives the remote signal < CARR RECIEVED >
and there are < CB OPEN A(B,C)-PHASE >, send signal can be done for 200ms
to ensure the remote pilot protection operates reliably.
Relay
startup
&
AND-1
Single fault
& Trip three
Multiphase AND-7 phase
fault
Muti_ph trip Permenent
no_ARis
&
enabled AND-8 trip
& |0 150|
AND-9
Low voltage
CB OPEN A-
PHASE OR-1
&
CB OPEN B- & AND- |0 200|
AND- 11
PHASE 10
CB OPEN C-
PHASE
-32 -
CSC-101 Line Distance Protection IED Technical Manual
When internal fault occurs, the startup elements and pilot zero sequence current can
operate, permissive signal is sent out to the remote to permit the remote trip. If it is
external fault that occurs on line, the forward directional element of one end of the line
operates and does not receive permissive signal while that of another end of the line
does not operate and receive permissive signal, therefore, both ends cant trip.
Because the directional element near fault detects reverse direction, it does
not send permissive signal to the remote. Although the remote relay can send
signal, it cannot receive the remote permissive signal, therefore, both of two
sides do not trip.
Relay
startup
&
AND-1
Relay reset
& CARR (DEF)
Pilot zero AND-3 Send
operation
POR Enabled 1
OR-1 & |0 T0| Pilot trip
PUR Enabled AND-4
CSC-101 pilot protection logic for under reach permissive mode is shown in Fig.4-12.
When internal fault occurs, the startup elements and zone 1 can operate, permissive
-33 -
CSC-101 Line Distance Protection IED Technical Manual
signal is sent out to the remote to permit the remote trip. If it is external fault that
occurs on line, the forward directional element of one end of the line operates and
does not receive permissive signal while that of another end of the line does not
operate and receive permissive signal, therefore, both ends cant trip.
Because the directional element near fault detects reverse direction, it does not send
permissive signal to the remote. Although the remote relay can send signal, it cannot
receive the remote permissive signal, therefore, both of two sides do not trip.
This function doesnt consider power flow reversing for external fault.
For feeder end, sudden-change current startup element cannot operates, the
logic of the low voltage is startup.
If the relay at feeder end receives the remote permissive signal and <low
voltage element> operates, relay startup.
Within 200ms after protection pickup, if <low voltage element> operates, both
the forward and reverse directional element at feeder end do not operate,
and the permissive signal has been received for 5ms, sending signal
lasted for 150ms to ensure the relay at power source end trips quickly.
Feeder end can also trip.
4.4.1.2.5 The protection is not picked up, receives the remote signal < CARR RECIEVED >
and there are < CB OPEN A(B,C)-PHASE >,send signal can be done for 200ms
to ensure the remote pilot protection operates reliably.
-34 -
CSC-101 Line Distance Protection IED Technical Manual
Relay
startup
&
AND-1
Single fault
& Trip three
Multiphase AND-7 phase
fault
Muti_ph trip Permenent
no_ARis
&
enabled AND-8 trip
& |0 150|
AND-9
Low voltage
CB OPEN A-
PHASE OR-1
&
CB OPEN B- & AND- |0 200|
AND- 11
PHASE 10
CB OPEN C-
PHASE
Fig.4-12 CSC-101 pilot protection for under reach permission mode logic
Zone of distance relay and zone or zone of distance relay are controlled
respectively to be on or off by the binary settings of zone and that of zone or
zone of distance relay.
After the sudden-change current startup element operates the protection system
-35 -
CSC-101 Line Distance Protection IED Technical Manual
switches the executing program to the fault processed part, the distance
measurement element is instantaneously opened for 150ms. Within 150ms, zone 1,
zone 2 , zone 3 of distance relay are fixedly put into operation. In 150ms after the
sudden-change current startup element operates, or when the loss of static steady
startup element or zero-current startup element operates, the executing program will
directly go into the logic part of power swing blocking. In this period, zone 1, zone 2
and zone 3 of distance relay must be enabled by fault detector of power swing
blocking, that is, asymmetry faults are detected by asymmetry fault detector, three
phase fault is detected by the impedance change rate detectordR/dt.
Zone 1, zone 2 and zone 3 of distance relay are respectively controlled by different
binary settings to be selected whether they are blocked during power swing blocking.
If the control bit is set on, zone 1 or zone 2 or Zone 3 of distance relay is put into
operation without blocking element after the protection starts.
During power swing, there is a special program module to detect whether power
swing quiets down or not, that is, if all zero-current detection element, the loss of
static stability detection element and six impedance of zone 3 of distance relay dont
operate, after 5s, the whole system resets.
In the logic after one phase trip, if the following conditions are satisfied, zone 1 of
distance relay will output tripping command
If the following conditions are satisfied, zone 2 of distance relay will output tripping
command
When manual close to a fault line occurs, the distance relay will accelerate zone 1,
-36 -
CSC-101 Line Distance Protection IED Technical Manual
zone 2 and zone 3 to operate. Six kinds of impedance will be calculated, if any of
them is located in the area of operating characteristics with offset region, the distance
relay operates.
Accelerated zone 3 with 1.5s delay to avoid power swing, this function is fixed
to put into operation without control word to be on or off.
When TV circuit is open, the distance relay exits, and at the same time, the voltage of
TV is monitored continually. Once the voltage comes to the normal for 500ms, the
distance relay will be automatically put into operation again. In the event of VT Fail
condition, all distance units are blocked to operate., one definite and one inverse
stage phase overcurrent, and one definite and one inverse stage zero current
protection can be used. Their setting and delay time can be set independently.
Tab. 4-5
Control word of
Zone 1 of Blocked /
Z1_FUNC Single
phase-to-earth unblocked
tripping
-37 -
CSC-101 Line Distance Protection IED Technical Manual
0s On /Off
Blocked / Three trip / Control word of
Zone 3 Fixed to run
unblocked Final trip Z3_FUNC
with 1.5s delay
Control word of OC VT
OC VT FAIL Final trip /exit
FAIL
4.6.1 The start component IQD acts and the measurement components will be open for a
short time within 150ms. Via computation and determination, namely < I zone>-JLI
-Y22-Y32-H21-single trip.
The control word KG6 control the system swing. If the KG6 is set to 0, no system
swing occurs and H8 directly opens the gate Y23 and Y24; If KG6 is set to 1, the
system swing occurs and H2-Y19-H7-H8 opens the gate Y23 and Y24.
the control word KG6 controls the system swing. If KG6 is set to 0, no system swing
occurs and H9 directly opens the gate Y25 and Y26; If KG6 is set to 1, the
-38 -
CSC-101 Line Distance Protection IED Technical Manual
oscillation lock occurs and H2-Y19-H7-H9 opens the gate Y25 and Y26.
The control word KG16 controls the system swing. If KG6 is set to 0, no system
swing occurs
4.6.5 For VT fail, the gates Y3Y8 and Y22 are locked- and the distance protection for all
zones exits; TV fail over-current or TV fail zero-current starts up,Y20-T1L-H29-
permanent trip.
4.6.6 SOTF: if any impedance is within, and zone, the exit will instantly trip and
the gate H6-Y11-H29permanently trip.
trip;
permanent trip;
If KG11 does not operate, III zone is accelerated with avoidance delay and
permanent trip.
-39 -
CSC-101 Line Distance Protection IED Technical Manual
or
KG20:Z2 And 3I02 NO_A/R
delay T2 reset
Permanent
Z3 PS_Block
1_Phase
3_Phase
Z PS_Block
Trip
Z3 Speed
Z2 Speed
Trip
Trip
and
Note
.5s 0
0
1
1
0
0
0
0
0
Speed after AR
I_power swing
NEG POS DIR
3i0 startup
MEM POS DIR
Overcurrent
open swing
3_PH Fault
Speed
1PH OR 2PH
VT Fail
I_abrupt
z1_pep
Fault
z2_pe
z2_pp
z3_pe
z3_pp
z1_pe
Fault
SOTF
-40 -
CSC-101 Line Distance Protection IED Technical Manual
After the abrupt startup or zero-sequence current startup, the zero-sequence I, II, III
and IV zone and the reverse stage zero-sequence protection startup. After the
zero-sequence I, II and III zone act, a phase will be selected to trip (II and III zone can
make a permanent trip). After the zero-sequence IV zone acts, there is a permanent
trip or three phase trip. After the zero-sequence reverse time limit action, there is a
permanent trip or three phase trip.
During a period of time, all the zero-sequence zones dont meet the action condition,
protection will be reset.
K
T Ts
Id R
( ) 1
Iset
Wherein: Id short circuit current
Ts Zero-sequence reverse time limit delay setting, meeting the requirement of the
reverse stage zero-sequence.
R=2 and K=80 Different reverse time limit curve such as extreme reverse time
limit
-41 -
CSC-101 Line Distance Protection IED Technical Manual
The self-generated 3U0 is used for the protection. Namely the software adds three
phase voltages to get 3U0 for a direction determination. When VT fail, the
zero-sequence protection with direction will exit and the zero-sequence zone without
direction will be reserved.
4.7.3.2 CT fail
Zero-sequence IV zone (action time is T04-500ms) after one phase trip is used to
eliminate the secondary fault in a non full phase operation. Note: if the VT is on the
line side, the zero-sequence voltage of the non full phase secondary fault is not the
true fault zero-sequence voltage. So the zero-sequence IV zone with a delay (T04
500ms, longer than single reclose time) is not set with a direction.
If the zero-sequence protection of the IED is determined as the manual close and
speedup will operate through the control word of 3I0 Speed, and it has a 0.06s delay
and make a permanent trip action. Direction is not determined upon manual close.
The manual close stage have a 0.06s delay in order to avoid the three phase
discordance of the breaker.
After the break start component or zero-sequence auxiliary start component start, and
enter into the fault processing procedure, the zero-sequence zone (I01I04)
and reverse stage zero-sequence protection operate in the full phase operation. The
I01I04 zone is locked in the non full phase operation. The I04 short time zone
operate.
4.8.1 The zone-sequence I zone will include automatic direction. The reverse stage
-42 -
CSC-101 Line Distance Protection IED Technical Manual
zones direction are separately controlled by their own control words, namely KG26
When CT fail, the feature that no zero-sequence voltage exists when VT disconnects
is used to make the possible mistaken protection action have a direction and the
current exists for a long time, <CT fail> will send alarm signals after 12s and all
the zero-sequence zones are blocked, namely the gate Y11Y14 are blocked.
4.8.2 The self-produced 3U0 and 3I0 are used by the zero-sequence direction module for
direction determination. When VT is fail, the zero-sequence protection will without
direction.
To the line fault, start component acts. While the component entre into the fault
processing procedure, the fault selection phase is made.
The gate Y4-Y11-Y22- H5 will output. If the protection <selects single phase>, the
gate Y26zero-sequence single trip; if the protection <selects inter-phase>, the
gate Y27KG21 (set to 1) H10-zero-sequence permanent trip, or KG21 (set
to 0) H2-zero-sequence three trip;
If the protection <select three trip>, the gate Y28 KG21 (set to 1) H10-
zero-sequence permanent trip, or KG21 (set to 0) H2-zero-sequence three
trip.
The trip can be enabled or disabled under control of the control words and the
selective trip or permanent trip command is controlled under the control of the control
words. The KG14-Y5-Y12-T02 (KG15-Y6-Y13-T03) -H6-KG20 (set to 0) -H5
outputs; if the protection <select single phase>, the gate Y26zero-sequence
single trip; if the protection <selects inter-phase>, the gate Y27KG21 (set to 1)
H10-zero-sequence permanent trip, or KG21 (set to 0) H2-zero-sequence
three trip; if the protection <selects three phase> the gate Y28KG21 (set to 1)
H10-zero-sequence permanent trip, or KG21 (set to 0) H2-zero-sequence
three trip. If KG20 is set to1-H8-H10-zero-sequence permanent trip.
The trip is controlled by the control word to transmit three trip command or permanent
-43 -
CSC-101 Line Distance Protection IED Technical Manual
4.8.4 For the non full phase, the block can easily make all zones act by mistake, namely
the gate Y4-7 closes I01 -I04;
Zero-sequence IV zone:
Voltage is connected with the line VT : the zero-sequence IV zone does not include a
permanent trip;
The voltage is connected with the bus VT: IV zone includes a direction and
-44 -
3PH Fault
PH-PH Fault
DIR
1
JUDGE
3U0
3I01 Stage 1
0
0
1
0 1
3I02 Stage
1
0
0
-45 -
3I03 Stage
1
1
0
Trip NO
1
3I04 Stage
AR
1
3PH Trip
Run
3 Phase Run Alarm
CB CB
CT
3 CT 6
G G
1 8
1 3
CB CB
2
CT CT 5
CT CT
7
G 2 G
3 6
2 4
STUB
CT CT
CB CB
fault
4 5
1 4
BUS I
-46 -
CSC-101 Line Distance Protection IED Technical Manual
OC1_STUB FUNC
Ia(b,c)>IOC
1_STUB
Ia(b,c)>IOC OC2_STUB FUNC
TOC2_STUB OR-1
2_STUB Permenent
&
AND-1 trip
STUB PROT
ENABLE
-47 -
CSC-101 Line Distance Protection IED Technical Manual
Tab.5-1
No. Setting name Unit Setting range
1 CT_PRIMARY A 1~9999
2 CT_SECONDARY A 1~5
3 U_PRIMARY kV 1~1200
4 U_ SECONDARY V 100~120
Tab.5-2
No. Name Unit Setting range
1. I_abrupt A 0.220(0.044)
2. 3I0_Startup A 0.220(0.044)
3. I_PowerSwing A 0.5100(0.120)
4. 3I0_Pilot A 0.05100.012
5. X_Pilot 0.01120(0.05600)
6. R_Pilot 0.01120(0.05600)
7. T0_Pilot s 0.0110
8. Tw_reverse ms 0100
9. R1_line 0.01120(0.05600)
10. X1_line 0.01120(0.05600)
11. KX -0.3310
12. KR -0.3310
13. Line length km 0655.4
14. R1_PE 0.01120(0.05600)
15. X1_PE 0.01120(0.05600)
16. R2_PE 0.01120(0.05600)
17. X2_PE 0.01120(0.05600)
-48 -
CSC-101 Line Distance Protection IED Technical Manual
-49 -
CSC-101 Line Distance Protection IED Technical Manual
Tab.5-3
NO. Setting name
1. Pilot DIST Enable
2. Pilot DEF Enable
3. Weak Infeed
4. POTT
5. PUTT
6. Z PS_Block
7. Z1_FUNC
8. Z2_FUNC
9. Z3_FUNC
10. Z2 Speed
11. Z3 Speed
12. Z3 PS_Block
13. OC VT FAIL
14. OC_INV VT FAIL
15. EF VT FAIL
16. EF_INV VT FAIL
17. OC1_STUB FUNC
18. OC2_STUB FUNC
19. 3PH Trip Mode
20. Z2 And 3I02 NO_A/R
21. Muti_PH Trip NO_A/R
22. 3I01_FUNC
23. 3I02_FUNC
24. 3I03_FUNC
25. 3I04_FUNC
26. 3I0_2 Direction
27. 3I0_3 Direction
28. 3I0_4 Direction
29. 3I0_Speed FUNC
30. 3I0_Speed DIR
31. 3I0_INV FUNC
5.1.3.1 U_PRIMARY Set to be actual rated primary voltage of TV, unit is kV.
5.1.3.3 CT_PRIMARY, CT_SECONDARY: Set to be the rated primary current whose unit
is kA. There are two specifications of rated secondary current, 1A or 5A.
-50 -
CSC-101 Line Distance Protection IED Technical Manual
5.1.3.4 The setting values are all secondary values if there is no special note. Impedance
setting is set according to positive impedance of line. All zero-sequence current is
3I0.
5.1.3.8 3I0_Pilot: Setting of pilot zero-sequence current relay, relay sends signal if
zero-sequence forward direction and zero current more than this setting.
5.1.3.9 X_Pilot and R_Pilot: Pilot reactance setting and resistance setting, if POTP
function is enabled, distance relay send signal if the direction is forward and
impedance calculate within the reactance setting and resistance setting.
5.1.3.10 T0_Pilot: Delay time Setting of pilot zero-sequence current, relay trip delay time the
setting from receiving signal.
5.1.3.11 Tw_reverse: the delay time of power from reverse to forward, this setting need
consider the delay time of the channel.
5.1.3.12 KXCalculated based on the actual line parameters, setting value ought to be less
than or close to calculation value.
KX = (X0-X1 ) / 3X1
5.1.3.13 KRCalculated based on the actual line parameters, setting value ought to be less
than or close to calculation value.
KR = (R0-R1 ) / 3R1
5.1.3.14 X1_line, R1_line Set according to secondary values of actual line parameters.
5.1.3.16 R1_PE, R2_PE, R3_PE resistance setting of 1st, 2nd, 3rd zone ground
distance relay, set to avoid load impedance. As the setting range of ground resistance
component is usually set to be rather large due to avoiding load impedance,
Reactance:
-51 -
CSC-101 Line Distance Protection IED Technical Manual
XDZ
ZZD
d RDZ
XDZ(Sindtg7Cosd)|ZZD|
Tab.5-5
d 90 85 80 76 73 72 70
Zzd - XDZ
*100% 0 0.68% 0.61% 0 0.79% 1.11% 1.87
XDZ
5.1.3.17 X1_PE according to 0.80.85 times of positive reactance of full line, it must be
lessened properly for lines with mutual inductance.
5.1.3.18 X2_PE, T2_PESet to be satisfied with sensitivity and the matched requirement
for terminal fault of current line.
5.1.3.19 X3_PE, T3_PESet to be satisfied with sensitivity and the matched requirement
for terminal fault of current line.
5.1.3.20 R1_PP, R2_PP, R3_PP resistance setting of 1st, 2nd, 3rd zone phase-phase
distance relay, set to avoid load impedance. As the setting range of ph-ph resistance
component is usually set to be rather large due to avoiding load impedance,
5.1.3.21 X1_PP according to 0.80.85 times of positive reactance of full line, it must be
lessened properly for lines with mutual inductance.
5.1.3.22 X2_PP, T2_PPSet to be satisfied with sensitivity and the matched requirement
for terminal fault of current line.
5.1.3.23 X3_PP, T3_PPSet to be satisfied with sensitivity and the matched requirement
for terminal fault of current line.
5.1.3.24 I_OC VT failOnly used after TV broken, set by single phase current to avoid load
current and be satisfied with sensitivity for terminal fault.
-52 -
CSC-101 Line Distance Protection IED Technical Manual
5.1.3.25 T_OC VT fail: Delay setting of overcurrent and zero-sequence overcurrent for TV
broken.
5.1.3.26 I_EF VT fail: Only used after TV broken, set to be satisfied with sensitivity for
terminal fault.
5.1.3.28 3I0_1Set to avoid the maximum zero-current at ground fault of current line end.
5.1.3.29 3I0_2, T0_2, 3I0_3, T0_3, 3I0_4, T0_4: According to the matched
requirements. 4th stage zero-current need not be disenabled during open-phase
operation but its delay is lessened 0.5s than the delay time setting of 4th stage
zero-current relay (noticethis delay must be larger than the delay of single-phase
reclosure).
5.1.4.2 Pilot DEF Enable: pilot zero sequence direction function is enabled.
5.1.4.3 Weak Infeed: if the one side is weak source, the setting is enabled on this side, but
the other side must not be enabled.
5.1.4.4 Z PS_Block :1st and 2nd zone distance relay with power swing blocking, When it is
set to 1, 1st or 2nd zone distance relay must be enabled by power swing blocking
elements after sudden-change current startup element has been operating for 150ms
or loss of stability detector operates. If it is set to 0, 1st or 2nd zone distance relay is
enabled from startup to whole system reset. 3rd zone distance relay is enabled from
startup to whole system reset, it is fixed.
5.1.4.6 Z2 Speed and Z3 Speed: instantaneous accelerated 2nd zone distance relay enabled
and instantaneous accelerated 3rd zone distance relay enabled. All control bits about
acceleration are depended on acceleration after autoreclosure.
-53 -
CSC-101 Line Distance Protection IED Technical Manual
5.1.4.8 3PH Trip Mode: relay trip three phase for single phase fault.
5.1.4.9 Z2 And 3I02 NO_A/R: 2nd zone distance and 2nd & 3rd stage zero current relay
permanent trip enabled, it is set to 1, 2nd zone distance relay and 2nd & 3rd stage
zero current relay will operate to perform permanent tripping. Set to 0, 2nd zone
distance relay and 2nd & 3rd stage zero current relay will operate to perform selective
tripping or three-phase tripping. 3rd zone distance relay will operate to perform
permanent tripping, it is fixed. 4th stage zero relay will operate to perform permanent
tripping, it is fixed.
5.1.4.10 Muti_PH Trip NO_A/R: Enabled if this bit is set to 1, permanent trip command
(blocking autoreclosure) will be sent out for all phase-phase faults (including
three-phase faults). Disenabled if it is set to 0, then three-pole trip command will be
sent out for ph-ph faults.
5.1.4.11 OC1_STUB FUNC and OC2_STUB FUNC: 1st and 2nd stage overcurrent function is
enabled for STUB.
5.1.4.13 3I0_2 Direction, 3I0_3 Direction,3I0_4 Direction: Zero-sequence II, III and IV stage
operation with direction: upon operation, when the zero-sequence direction is
determined as the positive direction, the corresponding zone can act. The
zero-sequence I zone will automatically carry a direction.
5.1.4.15 3I0_Speed DIR: Acceleration zero-sequence zone direction, it are only indicates the
reclose post acceleration; if it is set to 1 , Acceleration zero-sequence can trip as the
positive direction for the reclose speed. For SOTF speedup zero-sequence can trip
for the fault . For acceleration after reclose and SOTF, the zero-sequence speed up
zone makes a fixing operation with 60ms delay.
-54 -
CSC-101 Line Distance Protection IED Technical Manual
Tab.5-6
No. Paramet Range Setup method Remark
er
01 Current 0132 Use and Current number of
setting keys on faceplate to setting zone
zone modify current setting
number
02 Equipme 10ABH Enter into menu system Address range 10
nt setupcommunication ABH
address addressLon network
and 485 address
03 Baud rate 9600 Means that baud rate of 9600,192000 and
of series RS485 is 9600 (cannot 38400 can be set for
port be set below version V2.03 and above
2.03)
04 Line Set actual line name by CSPC program or ISN Character numbers of
name on faceplate line name can not be
larger than 30
05 Type of B2H Enter into menu system function code of
103 setup103 function CSC-101 is B2H
type to set
IEC60870-5-103
function code
06 Time Network mode, Enter into menu system Optional network mode,
synchroni minute pulse and setuptiming mode pulse mode based on
zation second pulse mode GPS IRIG-B
07 Protocol Communication Enter into menu system CSC-2000 protocol can
type protocol V1.20 setupprotocol option be selected for LON net
Communication or Ethernet. This option
protocol V1.10 need not be disposed
when information of
IEC60870-5-103
protocol are output from
port 485.
08 SOE Manual reset, Enter into menu system Optional manual reset
reset automatic reset setupSOE reset (receive reset
command to reset
SOE) or automatic
-55 -
CSC-101 Line Distance Protection IED Technical Manual
-56 -
CSC-101 Line Distance Protection IED Technical Manual
6 Reports
6.1 Overview
The IED provides quick, complete and reliable information about disturbances in the
system, and about the operation and state of the IED. This information is important to
used for different purposes for operators and engineers in the short term (e.g.
corrective actions) and in the long term (e.g. Functional Analysis).
event report;
Initiating report;
Alarm report;
Operation report;
Tab.6-1
No. Report No. Report
1 Relay Startup 30 Z Send Signal
2 Z Startup 31 3I0 Send Signal
3 3I0 Startup 32 Abpt Send Signal
4 I_PS Startup 33 Trip Send Signal
5 Z2 Speed Trip 34 CBO Send Signal
6 Z3 Speed Trip 35 Weak Send Signal
7 Z Trip_SOTF 36 3PH Trip
8 Z Speed Trip 37 3I0_INV Trip
9 RE_Trip NO AR 38 3I0 Speed Trip
10 3P Trip(1T_Fail) 39 To 3_PH Trip
11 Z1 Trip EVOL 40 3_PH Trip
12 Z2 Trip EVOL 41 A_PH Trip
13 Fault Location 42 B_PH Trip
14 Z Location 43 C_PH Trip
15 3I01 Trip 44 Z1_pe Trip
16 3I02 Trip 45 Z2_pe Trip
17 3I03 Trip 46 Z3_pe Trip
18 3I04 Trip 47 Z1_pp Trip
19 3I0 Trip_SOTF 48 Z2_pp Trip
-57 -
CSC-101 Line Distance Protection IED Technical Manual
Tab. 6-2-1
No. Report Causes and solutions
1 Sampling Err Check DC power supply, replace CPU module of
protection
2 EquipPara Err Solidify system parameter again, if failure, replace CPU
module
3 ROM Verify Err Check CPU module or replace CPU module
4 Setting Err Solidify setting and system parameter again, otherwise,
replace CPU module
5 Set Group Err Switch setting group, if failure, replace CPU module
6 DO Breakdown Make sure whether alarm I occurs to result in losing 24V
or nototherwise replace corresponding output module
7 DO No Response Fail to drive output but feedback is detected, means that
certain dynatron or optical isolator has been struck
through, ought to replace output module
8 DO EEPROM Err Replace corresponding output module
Tab. 6-2-2
No. Report Causes and solutions
1. DI Comm Fail Make sure input module is inserted tightly, replace input module
2. DO Comm
Make sure output module is inserted tightly, replace output module
Fail
3. Test DO
Not reset after output driving, press reset button
Un_reset
-58 -
CSC-101 Line Distance Protection IED Technical Manual
Tab. 6-3
-59 -
CSC-101 Line Distance Protection IED Technical Manual
Tab.6-4
No. Report No. Report
1 SwSetGroup OK 2 ClrConfig OK
3 Write Set OK 4 Test DO OK
5 WriteEquipParaOK 6 DI Change
7 WriteConfig OK 8 AdjDrift OK
9 AdjScale OK 10 VT OK
The event reports can be searched and read conveniently on the HMI or by CSPC
software tool, and can be printed automatically if the IED is connected with a printer,
and can be transmit to the substation automation system automatically through
dedicated network.
-60 -
CSC-101 Line Distance Protection IED Technical Manual
1st row:
Number of IED;
2nd row:
Type of IED;
Version of Software;
The type of reports;
3rd row:
Bay name;
Network address of IED;
Date and time when report is output.
4th ~ 6th row:
protection action events sequence with relative time tag in ms; The events consist of:
-61 -
CSC-101 Line Distance Protection IED Technical Manual
The Disturbance Recorder function acquires sampled data from all selected analogue
input and binary signals connected and can record the data of whole period of the
fault, from 140ms before fault takes place to 150 ms after the state of the last binary
input changes. The sample rate is 24 times per cycle, equal to 0.694ms between two
samples. At least 24 whole period fault records can be saved in the IED.
Note: If the test mode control linker is on, the new disturbance record report will not
be saved or uploaded.
First part:
Protection action events sequence, which is same as the action event report
presented in previous chapter, Event Report of IED
Second part:
The part shows the waveform of analogue inputs and time sequence diagrams of
binary inputs and outputs. Its format is shown below:
Text Section:
st
1 row:
-62 -
CSC-101 Line Distance Protection IED Technical Manual
Number of IED;
2nd row:
Last row:
Diagram Section:
X-ordinate:
They are waveforms of analogue inputs and time sequence lines of binary inputs and
outputs, illustrated from left to right. The line represented the binary input or output,
will become thick when the input or output is present.
First part:
Protection action events sequence, which is same as the action event report
presented in previous chapter, Event Report of IED
Second part:
The sampling value of analogue input and bit data of binary inputs or outputs. Its
format is shown below:
Text Section:
st
1 row:
Number of IED;
2nd row:
Sampling rate;
-63 -
CSC-101 Line Distance Protection IED Technical Manual
Sampling times;
The designations of bit in the word, which represent the state of binary inputs
and outputs;
Data Section:
X-ordinate:
Y-ordinate:
Data:
They are real-time sample values of analogue inputs and word of state of binary
inputs and outputs. The bit will be 1 when the represented binary input or output is
present.
-64 -
CSC-101 Line Distance Protection IED Technical Manual
8 Operation
8.1 Human-Machine Interface ( HMI )
8.1.1 Overview
The human-machine interface is simple and easy to understand the whole front
plate is divided into zones, each of them with a well-defined functionality:
8.1.2 Keypad
The keypad is used to monitor and operate the IED. The keypad has the same look
and feel in all IEDs in the CSC series. LCD screens and other details may differ but
the way the keys function is identical. The keys used to operate the IED are described
below in table 8-1.
-65 -
CSC-101 Line Distance Protection IED Technical Manual
Up arrow key:
Moves up in menu
Page up between screens
Increases value of setting.
Down arrow key
Moves down in menu
Page down between screens
Decreases the value of setting.
RESET key:
Reset LEDs
Return to normal scrolling display mode directly
RESET
The shortcut keys and functional keys are below the LCD on the front panel. These
keys are designated to execute the frequent menu operations for users convenience.
The keys used to operate the IED are described below in table 8-2
Table 8-2: Shortcut keys and functional keys on the front of the IED
Key function
Report Report key:
Print the latest operation report
Set Setting key:
Print setting of current setting group
Sample Sample key:
Print current sampled data
Version Version key:
Print protection version information and current operating status
+ Plus key:
Switch next setting group forward as active setting group meaning
8.1.4 LED
There are 8 LEDs on the left side of the LCD. The information that the LEDs indicate
is pre-defined and described in table 8-3
-66 -
CSC-101 Line Distance Protection IED Technical Manual
Not used
Not used
8.1.5 LCD
The LCD on the HMI can display 8 lines with up to 28 characters per line, with blue
background.
The back light will turn on automatically, when one key is pressed or an alarm is
reported, until a set time delay after the last operation or alarm.
8.2 Menu
8.2.1 Introduction
Operating mode
Configuring mode
-67 -
CSC-101 Line Distance Protection IED Technical Manual
During the normal service without any operation, the LCD display scrolling the
information listed below:
Magnitude of P, Q;
Linkers enabled,
To Press SET to enter into main menu during Normal display mode.
This mode is only for manufacturer to complete final configuration of IED before
delivery.
-68 -
CSC-101 Line Distance Protection IED Technical Manual
-69 -
CSC-101 Line Distance Protection IED Technical Manual
-70 -
CSC-101 Line Distance Protection IED Technical Manual
Notes
In the IED test mode ( when the RELAY TEST binary input is present )
operating reports are neither transported nor saved, just are printed or
displayed on PC. If disturbance record report need to be printed, but without
PC, only disturbance record data reports can be printed.
It is convenient to check the accuracy of measuring analogue values by
comparing the actual analogue values injected by tester with the
corresponding values displayed in the menuStatus/measure/. Especially, in
the IED test mode, the displayed values are refreshed so quickly that they
are accurate to keep up with the change of the actual analogue value
injected.
Input bay name on HMI, see appendix.
-71 -
CSC-101 Line Distance Protection IED Technical Manual
9.1.3 Check that all items are included in accordance with the delivery documents. Once
the IED has been started make sure that the software functions ordered have been
included in the delivery.
If transport damage is discovered appropriate action must be taken against the latest
carrier and the nearest Sifang office or representative should be informed. Sifang or
his partner should be notified immediately if there are any discrepancies in relation to
the delivery documents.
9.1.5 If the IED is repacked for transport again, the storage packing of the IED must provide
the proper degree of protection against various possible damages, in accordance
with IEC 60255-21-1 class 2 and IEC 60255-21-2 class 1.
9.2 Installation
9.2.1 Insert the IED into the opening (cut-out) in the panel. The bottom of the IED should be
supported on the frame of the panel.
9.2.2 Fix the IED by tightening all four screws against the panel. The IED ought to be fixed
on panel (tank), and every connection screws of the IED must be firmed.
9.2.3 Connect the earthing screw on the rear of the IED unit to the closest possible earthing
point in the cubicle. Electrical codes and standards require that protective earth
cables are green/yellow conductors with a cross section area of at least 2.5 mm2.
The cubicle must be properly connected to the station earthing system. Use a
conductor with a core cross section area of at least 4 mm2.
The wiring from the cubicle terminal block to the IED terminals must be made in
accordance with the established guidelines for this type of IED. The wires from binary
inputs and outputs and the auxiliary supply must be routed separated from the current
transformer cables between the terminal blocks of the cubicle and the IEDs
connections. The connections are made on connector X10. Connection diagram is
shown on the rear plate of the IED.
-72 -
CSC-101 Line Distance Protection IED Technical Manual
CTs and VTs are connected to the connector of the Transformer input module on the
rear side of the IED. Connection diagram is shown on the rear plate of the IED.
Use a solid conductor with a cross section area between 2.5-6 mm2 (AWG14-10) or a
stranded conductor with a cross section area between 2.5-4 mm2 (AWG14-12). The
screws used to fasten the conductors should be tightened.
Auxiliary power and signals are connected using female connectors. Signal wires are
connected to a female connector, which is then plugged into the corresponding male
connector, located at the rear of the IED. Connection diagrams are shown on the rear
plate of the IED.
Check the protective earthing conductors of IED are connected reliably in accordance
with the related standards and Codes.
Check that the wiring is in strict accordance with the supplied connection diagram.
The CTs must be connected in accordance with the circuit diagram provided with the
IED, both with regards to phases and polarity.
Check that the auxiliary supply voltage remains within the permissible input voltage
range under all operating conditions. Check that the polarity is correct.
Preferably, disconnect the binary input connector from the binary input cards. Check
all connected signals so that both input level and polarity are in accordance with the
IEDs specifications.
-73 -
CSC-101 Line Distance Protection IED Technical Manual
Preferably, disconnect the binary output connector from the binary output cards.
Check all connected signals so that both load and polarity are in accordance with IED
specifications.
9.3.7.1 Each module should be in the correct slot and be locked reliably to ensure the
connection between the male connector of the module and the female connector
welded on the main back board.
9.3.7.2 The IED is provided with current terminals with automatically operating contacts for
short-circuiting the CT secondary circuits when the transformer input module is
withdrawn from its connector. The short-circuiting contact should be opened when the
transformer input module is inserted into the connector.
9.3.7.3 The jumpers and short-circuiting wires of each module is set correctly.
There are four groups jumper and needle AD3, AD2, AD1 and AD0 near CPU1 or
CPU2 ejector/inserter clips, whose tag H and L represents high potential and low
potential respectively. Setup four jumpers AD3, AD2, AD1 and AD0 to high potential
or low potential to form CPU address as shown in Tab.11. CPU1 address can be
expressed as 0000 (value is 0) with four binary bits, and CPU2 address is 0001 (value
is 1). In the same way, I/O address can be set as shown in Tab.9-1.
Tab.9-1
Module Coding Remark Module Coding Remark
address address
CPU1 0000 Value 0 Output 1 0000 Value 0
CPU2 0001 Value 1 Output 2 0001 Value 1
Input 1 000 Value 0 Output 3 0010 Value 2
Output 4 0011 Value 3
-74 -
CSC-101 Line Distance Protection IED Technical Manual
According to table 9-3 as below, use a rotating meter inducing 500V to test insulation
resistance in turn between analog circuits and ground, and the circuits to each other.
Every resistance must not be less than 100 M. And the lasting time for resistance
test is not less than 5s to ensure that the value of insulation resistance is read in a
steady state. The ground terminal is X10-32.
Tab.9-3
Tested circuits Terminals
AC current inputs X1-1,2,3,4
AC voltage inputs X1-9,10
DC voltage X10-2,4,8,10,12,14,16,20,222628
Output contacts and centre signals Terminals of X6,X7,X8 and X9
Input contacts Terminals of X4
9.4.1.1 Energize DC power supply, the relay for loss of power alarm ought to be excited
reliably, and its contacts as X10-c16 and X10-a16 must be opened reliably.
9.4.1.2 check the self startup performance of powerWhen the value of DC power supply is
modified gradually from 0 to 80% rating, contacts of the relay for loss of power alarm
must change from closed state to opened state supervised by versatile meter. Then,
when DC power supply is from off to on, the versatile meter operates as the same
results.
9.4.1.3 Testing of voltage output value and its stability: Every class output voltage must be
maintained stably as shown in Tab.9-4 when the input voltage of DC power supply is
UN.
Tab. 9-4
Test Point X-c14-c12 X-c4-c2 X-a4-a2 X-c26-c24 X10-c2-c8
Rating voltage of DC 5V +12V -12V 24V R24V
outputs
Permissive error 0~+3 -20~0 -20~0 0~+5 0~+8
range 5.0~5.15 9.6~12.0 -12.0~-9.6 24.0~25.2 24.0~25.92
9.4.1.4 Testing of DC power on and off rapidly: Power on and off rapidly for three times, no
abnormal case occurs for the IED.
9.4.2 Set
9.4.2.1 Under the circumstance of power off, insert all plug-in units into the corresponding
-75 -
CSC-101 Line Distance Protection IED Technical Manual
slot of the IED according to the configuration figure in the guide book, and connect
the flat cable between faceplate and communication module.
9.4.2.2 Switch on DC power supply; the setting steps are described as follows to initialize
CPU.
Press QUIT and SET at the same time, enter into debugging menu. Then enter
into the menu of CPU setup, enable all CPU1 and CPU2press the key of SET to
save. And energize the IED once again.
9.4.2.3 Setting
9.4.2.3.1 Enter MainMenu-Set Timeuse square keyboard to set clock to current time. Then
return to the normal display of LCD, observe whether the running clock is normal or
not. Cut off DC power supply for 5 min, then switch on, check the time and date
displayed in LCD to conform that the clock is running and nicety during power turnoff.
Set the address of Lon network and RS-485 port whose range is 10HABHthe
address of our equipment can not be repeated.
Examine that the address of Ethernet 1 and that of Ethernet 2are not set to be 0.
9.4.2.3.5 Enter into MainMenuSetupBayNameinput the actual name and serial number of
line by means of ISN(internal statement number)(as shown at appendix) on faceplate
or directly input by CSPC program.
Select CPU
CSC101A
Press SET to display the following:
-76 -
CSC-101 Line Distance Protection IED Technical Manual
Tab. 9-5-1
Ia
Ib
Ic
3I 0
Ua
Ub
Uc
Ia R
Ib R
Ic R
3 I0 R
Tab. 9-5-2
CB Open A_PH
CB Open B_PH
CB Open C_PH
Z Send Signal
3I0 Send Signal
Z RECV Signal
3I0 RECV Signal
-77 -
CSC-101 Line Distance Protection IED Technical Manual
The recommended setup is Print record automatically, Print control word and
Print format of record data set to wave. If the protection operating results have some
questions, suggest that set Print format of record data to data at first, then, print a
record wave againor use shortcut key F1 to directly print the latest one of record
data, after that, equipment testing can be followed. This can avoid losing data, and
causing disadvantage for furthermore analysis.
9.6.2 MainMenuPrintReport Enter into this menu, select report or operation record to
print, the printer ought to print correctly.
9.6.4 Testing print function of shortcut key: Use shortcut key on the faceplate to print, the
printer ought to print normally.
-78 -
CSC-101 Line Distance Protection IED Technical Manual
Connect +24V with the following terminals shown in Tab.9-6 as bellow, the
corresponding inputs displayed on the faceplate are valid. If certain input is error,
check the corresponding optical isolator, resistance etc are false welded, welded in
reverse, or damaged.
Tab. 9-6
Name of input Terminals
RESET X4:a8
CB OPEN A_PHASE X4:c4
CB OPEN B_PHASE X4:c6
CB OPEN C_PHASE X4:c8
CAR RECV(DIST) X4:c10
CAR RECV(DEF) X4:c12
VT_MCB X4:c22
STUB PROT ENABLE X4:c18
REM ACCESS BLK X4:a2
RELAY TEST X4:a4
Tab. 9-7
No. Item Contactors light Display on HMI
X9:c22-a22 X9:c24-a24 Run lamp
flash Test DO OK
Relay Alarm
Alarm Relay Alarm
1
lamp flash
Equipment X9:c22-a22 Alarm
power-on after off light flash
X9:c26-a26 X9:c28-a28 Run lamp
flash Test DO OK
Run Alarm
2 Alarm Run Alarm
lamp light
Equipment X9:c26-a26 Alarm
-79 -
CSC-101 Line Distance Protection IED Technical Manual
-80 -
CSC-101 Line Distance Protection IED Technical Manual
Before the IED leaves factory, zero drift and calibration have been regulated, only
examination needs in locale. To examine calibration, enter into measuring quantities
or analog quantities menu at first, then enter into analog quantities menu to do it. If
they dont meet requirements, regulate them according to the following methods.
Notice to increase the setting value of startup elements.
To regulate zero drift, disconnect the IED with testing instrument or standard source
to ensure not any input in AC terminal of the IED. Enter into Main
MenuTestingAdjDrift, select all, and confirm it, then zero drift regulation can be
performed. If regulation succeeds, report zero drift regulation success. After this,
select Main MenuTestingViewDrift,, current channel must be less than 0.1A
(rated value of TA 5A) or 0.02A (rated value of TA 1A), voltage channel must be less
than 0.1V.
Connect input terminals of voltage UA, UB, UC, employ testing instrument with grade
0.5 and the above whose outputs UA and UN are connected to protection terminals
-81 -
CSC-101 Line Distance Protection IED Technical Manual
After finishing calibration and zero drift regulation, measure linear error using testing
instrument with grade 0.5 and the above, and write down testing result. Requirements:
For secondary rated current 5A of TA, input currents 25A, 10A (the lasting time of the
above two is not allowed to exceed 10s), 2A, 1A and 0.4A respectively. For secondary
rated current 1A of TA, input currents 5A, 2A, 0.5A, 0.2A and 0.08A. Supply voltage
60V, 30V, 5V, 1V and 0.4V respectively. Observe LCD display or enter into Main
MenuTestingViewScale, ask that the difference between LCD display value and
external meter is less than 0.1V for 0.4V and 1V of voltage channel, the others are
less than 2.5, and current channel error is less than 0.02In for 0.08In and 0.2In, the
others are less than 2.5.
Short b1b4 of AC module X1, IA, IB, IC and IN outputs of testing instrument are
connected to terminals X1-a1, X1-a2, X1-a3 and X1-a4 of the IED, input rated current
and three-phase symmetry voltage 50 via a10, a9, b9 and b10 of X1 respectively,
each phase voltage leads each phase current phase angle 60respectively, check
LCD loop display or enter into MainMenuStatusmeasure to view, phase
difference of A-, B-, and C-phase voltage must be 120, and phase difference of A-,
B-, and C-phase current must be 120. One phase current must lag the
corresponding phase voltage 60(angle error 3). Otherwise, check the IED of AC
module connection.
Input three-phase symmetry voltage 50V, and rated current only to phase A which
lags phase A voltage 60, observe the display of amplitude and angle of 3I0 which
must be the same as IA, otherwise, check the IED of AC module connection.
For a single equipment, wiring can be connected as shown in Fig.9-1, and connect
trip A, tripB, trip C and common terminal to the testing instrument if necessary.
-82 -
CSC-101 Line Distance Protection IED Technical Manual
Testor
a1 b1 Equipment
Ia
a2 b2
Ib
Ic a3 b3
In a4 b4
X1
Ua a10
Ub a9
Uc b9
Un b10
Input settings according to the setting advice note or typical settings and solidify them
to certain zone at first. Then make pilot differential relay (self-looping state), distance
relay and zero-sequence current relay test, as shown in Tab.9-8.
During testing, notice that signal lights on panel and reports are correct. For new
installed protection system, and check the operating results are correct.
Tab.9-8
Protection
SN Fault type Correct report on panel Light
Function
Phase ABR=0 Trip A,
1. Pilot X=0.95 setting Relay StartupPilot Trip B,C light
values shine
distance
Phase ABR=0
2. protection X=1.05 setting Relay Startup N/A
values
Phase B I=1.05* Trip B
3. Pilot Relay StartupPilot Trip
setting values light shine
distance
protection Phase B, I=0.95*
4. Relay Startup N/A
setting values
Phase ABR=0 Trip A,
5. X=0.95 setting Relay StartupZ1_pp Trip B,C light
values shine
Phase ABR=0
6. X=1.05 setting Relay Startup N/A
Phase to values
phase Phase BCR=0 Trip A,
7. X=0.95 setting Relay StartupZ1_pp Trip B,C light
distance values shine
zone I Phase BCR=0
8. X=1.05 setting Relay Startup N/A
values
Phase CAR=0 Trip A,
9. X=0.95 setting Relay StartupZ1_pp Trip B,C light
values shine
-83 -
CSC-101 Line Distance Protection IED Technical Manual
Protection
SN Fault type Correct report on panel Light
Function
Phase CAR=0
10. X=1.05 setting Relay Startup N/A
values
Phase ABR=0 Trip A,
11. Phase to X=0.95 setting Relay StartupZ2_pp Trip B,C light
phase values shine
distance Phase ABR=0
12. zone II X=1.05 setting Relay Startup N/A
values
Phase BCR=0 Trip A,
13. Phase to X=0.95 setting Relay StartupZ3_pp Trip B,C light
phase values shine
distance Phase BCR=0
14. zone III X=1.05 setting Relay Startup N/A
values
Phase AR=0
Trip A,
15. X=0.95 setting Relay StartupZ1_pe Trip
light shine
values
Phase AR=0
16. X=1.05 setting Relay Startup N/A
values
Phase BR=0
Trip B
17. Phase to X=0.95 setting Relay StartupZ1_pe Trip
light shine
earth values
distance Phase BR=0
18. zone I X=1.05 setting Relay Startup N/A
values
Phase CR=0
Trip C
19. X=0.95 setting Relay StartupZ1_pe Trip
light shine
values
Phase CR=0
20. X=1.05 setting Relay Startup N/A
values
Phase BR=0
Trip B
21. Phase to X=0.95 setting Relay StartupZ2_pe Trip
light shine
earth values
distance Phase BR=0
22. zone II X=1.05 setting Relay Startup N/A
values
Phase CR=0 Trip A,
23. Phase to X=0.95 setting Relay StartupZ3_pe Trip B,C light
earth values shine
distance Phase CR=0
24. zone III X=1.05 setting Relay Startup N/A
values
Inverse Phase BR=0
25. direction X=-0.7 setting Relay Startup N/A
fault values
Phase B
Trip B
26. zero I=1.05 setting Relay Startup3I02 Trip
light shine
sequence values
stage II Phase B
27. Relay Startup N/A
I=0.95 setting
-84 -
CSC-101 Line Distance Protection IED Technical Manual
Protection
SN Fault type Correct report on panel Light
Function
values
Phase C
Trip C
28. zero I=1.05 setting Relay Startup3I03 Trip
light shine
values
sequence
Phase C
29. stage III I=0.95 setting Relay Startup N/A
values
Phase A Trip A,
30. I=1.05 setting Relay StartupOC_VT Fail Trip B,C light
Over current values shine
of TV fail Phase A
31. I=0.95 setting Relay Startup N/A
values
Note
the fault current I for testing must be larger than 0.2In while fault voltage is
less than threshold value.
U U
XD RD
I KX * 3I 0 90 I KR * 3I 0 0.
U U
X R
I 90 I 0
9.11.1 After turning on DC power supply, the LED <Run> is lit steadily in green, rest of the
LEDs should be extinguished.
9.11.3 After setting the date and time of IED, turn on and off the DC power supply of five
times in short time, and then check the tolerance of the date and time is limited in
-85 -
CSC-101 Line Distance Protection IED Technical Manual
permissive scope.
9.11.5 Check, record and Print (if a printer is connected) the protection settings item by item
of each group which are possibly employed in the actual operating modes.
9.11.6 Check and record the state of all binary inputs. Particularly ensure that the IED is not
in test mode, meaning there is not a hand type icon displayed at the upright corner of
the LCD, and the binary input, relay test, is not present.
9.11.7 Inject system currents (load current must be larger than 0.08In) and voltages into the
IED, and then check whether the magnitude, phase angle, polarity and phase
sequence of each measuring analog value are correct or not.
9.11.8 Print information and operating condition with the version shortcut key if the IED
have been connected with a printer.
-86 -
CSC-101 Line Distance Protection IED Technical Manual
10 Maintenance
WARNING
Never disconnect the secondary connection of a current
transformer circuit without short-circuiting the transformers
secondary winding. Operating a current transformer with the
secondary winding open will cause a massive potential build up
that may damage the transformer and may cause injuries to
humans.
CAUTION
Never connect or disconnect a wire and/or a connector to or from
a IED during normal service. Hazardous voltages and currents are
present that may be lethal. Operation may be disrupted and IED
and measuring circuitry may be damaged.
NOTE
Instructions from the power network company and other
maintenance directives valid for maintenance of the power
system must be followed. The following items are only for
reference.
NOTE
a) During operation, these manual operations listed below are
forbidden:
Touch the live parts of the IED
Insert in or draw out the modules
Some manual operations in the menu of HMI, they are:
Test contacts of output relay;
Modify setting
Write setting;
Set system parameters
Change the IED address in the communication network.
b) If the whole IED need be out of service, Switch off all external
tripping linkers firstly, and then turn off the DC power supply of
the IED.
-87 -
CSC-101 Line Distance Protection IED Technical Manual
CAUTION
Most electronic components are sensitive to electrostatic
discharge and latent damage may occur. Please observe usual
procedures for handling electronics and also use an ESD wrist
strap. A semi-conducting layer must be placed on the workbench
and connected to earth.
-88 -
CSC-101 Line Distance Protection IED Technical Manual
CAUTION
When a printed circuit board is sent to Sifang, it must always be
placed in a metallic, ESD-proof, protection bag.
The IED is self-supervised. It is easy to identify the faulty module according the alarm
messenger.
When a module is in fault, It should be replaced with the backup module. And send
the faulty module to Sifang for repair.
10.4.1.1 Firstly, confirm the address jumper to be right on CPU module, input and write setting;
10.4.1.2 Check the version and CRC code of CPU module software;
10.4.1.3 After updating or replacing, if alarm setting zone error or setting error is present,
the setting should be written again and the active setting group should be set again.
10.4.1.4 After updating or replacing, if alarm logical Linker error or linker error is present,
the setting should be written again and the active setting group should be set again.
-89 -
CSC-101 Line Distance Protection IED Technical Manual
10.4.2.2 Configure again according to the former configuration, or write the former
configuration of communication again.
10.4.2.5 Print and check any reports and disturbance record reports
10.4.2.6 Test some binary inputs or outputs to confirm the menu operation can be done well.
Test all inputs or outputs on the module and relative external secondary
circuits before IED in service.
10.5 Others
There are one test male connector at the up left corner of rear plate, The
connector can be used to test 24V(output), 12V 5V and perform
auto-testing by connection with the internal CAN net.
There are three ways to input settings(1) Keypad on front panel, (2) employ
CSPC software tool (3) Substation automation system.
-90 -
CSC-101 Line Distance Protection IED Technical Manual
Use LON net to connect printer via the CSN 010 interface casethe terminal
wiring of printer and cable must be changed.
Connect printer directly with the print series ports of the IED through special
printer cable. If several equipments (the maximum is 4) need use one printer
in common, a CSN-4 interface case is needed.
Except AC terminals, all the other rear plate terminals are located on the female
connectors. If it is necessary to modify their wiresthe female connector must be draw
out, then modify the wire of terminals on the connector. Except AC terminal, prohibit
inserting or withdrawing terminal wires without pulling out the female connector, in
order to prevent connecting wires from bad connection.
-91 -
CSC-101 Line Distance Protection IED Technical Manual
Shown in Tab.11-1.
Tab.11-1
Terminals Description Remark
a1-b1 Current of phase A,IA polar terminal, IA not Analog
a2-b2 Current of phase B,IB polar terminal, IB not quantities input,
a3-b3 Current of phase C,IC polar terminal, IC not practical wiring
a4-b4 Current of 3I0, IN polar terminal, IN not diagram is
a9 Voltage of phase B, UB input shown in
b9 Voltage of phase C, UC input Fig.9-1
Shown in Tab.11-2
-92 -
CSC-101 Line Distance Protection IED Technical Manual
Tab.11-2
X3(MASTER)
A group terminal of GPS time synchronization, two
Not Uesd 1
group terminals of 485, two group terminals of
Print Transmit 2
Print Receive 3
LonWorks, series print terminal, two group terminals
Print GND 4 of electric Ethernettwo group terminals of optic
485-2B 5 Ethernet. Configure the above according to user
485-2A 6
Ethernet
requirements.
485-1B 7
485-1A 8
GPS 9
GPSGND 10
LON-2A 11
LON-2B 12
LONGND 13
LON-1A 14
LON-1B 15
Not Used 16
Shown in Tab.11-3.
Tab.11-3
Terminals Description
a2a28 The a2 has been already installed an input of 24V at the interior of the IED, and
a28 has been already installed an input of 24V earthing. So the connection
exterior is not allowed.
a4 Remote access block-onWhen the input is 24V, the controls must be on site.
That means only the local commands can be executed. All the non-local
commands will not be executed, such as the remote switching connector, setting
group, and writing the settings.
a6 Relay testThe relays will be test, when signal DI is given into this terminal.
When test the protections, the IED wont send the report, and wont execute the
remote commands. While the IED operating, the input of this terminal must be
cancel.
a8 Signal resetused to reset the signal of flash on the front panel
a12 DIFF PROT EN. The differential protection is enabled or disabled, it is 125V
input.
c2c28 Wirings of these terminals is not allowed for equipment with supply 125V.
c4c6 Connect separately with CB position A,B,C. For a semi-connection mode, the
c8 split-phase CB positions of edge relay and middle relay should be input. Its
function are: 1) VT fail alarm. At the condition of that all the three phases have no
-93 -
CSC-101 Line Distance Protection IED Technical Manual
voltages, if there are three CB positions, the protection will not alarm, if not give
the VT fail alarm. 2) If there are CB positions, and the corresponding phase has
no current, the IED will consider that the switch of that phase should trip, and the
protection enter into the logic of full phase and non-full phase according to the
condition of switching. 3) Used to speed-up the distinguishing after the manual
close or the speed reclose.
c10 Input of distance signal
c12 Input of zero_def signal
C18 STUB PROT ENABLE: STUB function is enabled input.
c20 DI_DTT
c22 VT_MCB
Shown in Tab.11-4.
Tab.11-4
Terminals Description Remark
a2 Segregated phase tripping 1(+) Positive power
c2 Segregated phase tripping 2(+) of output
a4 Three-phase tripping 1(+)
c4 Three-phase tripping 2(+)
a6 Segregated phase tripping 3(+)
c6 Segregated phase tripping 4(+)
a10a12a14 Belong to trip A1, trip B1 and trip C1 respectively Output of
segregated
c10c12c14 Belong to trip A2, trip B2 and trip C2 respectively
phase tripping
Shown in Tab.11-5.
Tab.11-5
-94 -
CSC-101 Line Distance Protection IED Technical Manual
Shown in Tab.11-6.
Tab.11-6
Terminals Description Remark
c2-a2 CARR SEND (DIST) Fast output
c4-a4 CARR SEND (DIST)
c6-a6 CARR SEND (DEF)
c8-a8 CARR SEND (DEF)
c10-a10 Not Used
c12-a12 Not Used
c14-a14 Not Used
c16-a16 Not Used
c18-a18 CARR FAIL ALARM 11
c20-a20 CARR FAIL ALARM 12
c22-a22 Protection operating signal 1holding signal
c24-a24 For
Protection operating signal 2not holding
remote signal of protection operation
c26-a26 Backup (holding
c28-a28 Backup (not holding
c30-a30 Backup (holding
c32-a32 Backup (not holding)
Shown in Tab.11-7.
Tab.11-7
Terminals Description Remark
c2-a2 Backup Output contacts
c4-a4 Backup
c6-a6 Backup
c8-a8 Backup
c10-a10 Protection operating signal 2not holdingFor remote
signal of protection operation
-95 -
CSC-101 Line Distance Protection IED Technical Manual
Shown in Tab.11-8.
Tab.11-8
Terminals Description Remark
ca2, ca4 24V+ output terminal
ca8, ca10, ca12 24V- output terminal
c14-a14 Contact of DC input Signal of DC input
c16-a16 Contact of loss of DC power supply Signal of loss
c18-a18 power
ca20ca22 1: input terminal of positive power Input for external
ca26ca28 2: input terminal of negative power power supply
ca32 Shielded ground of equipment Connected
reliably to the grounding of substation
-96 -
CSC-101 Line Distance Protection IED Technical Manual
12.2 Transportation
The IED can be transported by all means of conveyance such as car, train and ship
etc, but ought to prevent it from rain, snow, vibration, Shock and bump, in order to
ensure perfect performance of the IED.
-97 -
CSC-101 Line Distance Protection IED Technical Manual
13 Ordering
Manufactured type, name, and quantities
Optical channel:
Single-channel or double-channel.
-98 -
CSC-101 Line Distance Protection IED Technical Manual
14 Appendix
14.1 Terminal diagram
10/100M BASE-T
232-GND 4
8 CB OPEN C_PHASE RESET 485-2B 5 3 IC'(CT OUT) IC(CT IN)
10 CAR RECV(DIST) 485-2A 6
12 CAR RECV(DEF) PILOT PROT EN 4 IN'(CT OUT) IN(CT IN)
485-1B 7
14 NOT USED NOT USED 5
485-1A 8
16 NOT USED NOT USED
GPS 9 6
18 NOT USED A
20 NOT USED GPSGND 10 RX
NOT USED A 7
LON-2A 11 TX A
22 VT_MCB NOT USED
LON-2B 12 B B 8
24 NOT USED NOT USED RX
26 NOT USED LONGND 13 B 9 UC UB
TX
28 KM- R24V- INPUT LON-1A 14
10 UN UA
30 NOT USED NOT USED LON-1B 15
32 NOT USED NOT USED NOT USED 16 11
OUTPUT
SIGNAL
-99 -
CSC-101 Line Distance Protection IED Technical Manual
This port introduces the data modeling, communication principles that are used in the
IEDs. The purpose of supporting IEC61850 series is to provide interoperability
between devices from different venders.
For some advanced applications, the reader should have intensive knowledge about
IEC61850.
The communication between substation level and bay level uses mainstream
technology, which is an ISO/OSI stack consisting of Ethernet (layers 1 and 2), TCP/IP
(layers 3 and 4) and MMS (layers 5-7). The object models and their communication
services are mapped to the application layer of MMS (layer 7).
Note:
-100 -
CSC-101 Line Distance Protection IED Technical Manual
-101 -
CSC-101 Line Distance Protection IED Technical Manual
It is introduced in this part, the layout of the Logical Device, Logical Nodes and Data
Objects. The IEC61850 device model begins with a physical device. There are
several logical devices within each physical device. And there are at least 3 logical
nodes within each logical device.
Note:
There are No vender specific Logical Node Class and Common Data Class in CSC
series devices.
-102 -
CSC-101 Line Distance Protection IED Technical Manual
-103 -
CSC-101 Line Distance Protection IED Technical Manual
M4 Data set C5 C5 Y
M5 Substitution O O N
Reporting
M7 Buffered report control O O Y
M7-1 sequence-number Y Y Y
M7-2 report-time-stamp Y Y Y
M7-3 reason-for-inclusion Y Y Y
M7-4 data-set-name Y Y Y
M7-5 data-reference Y Y Y
M7-6 buffer-overflow Y Y Y
M7-7 entryID Y Y Y
M7-8 BufTm Y Y Y
M7-9 IntgPd N Y Y
M7-10 GI Y Y Y
M8 Unbuffered report control M M Y
M8-1 sequence-number Y Y Y
M8-2 report-time-stamp Y Y Y
M8-3 reason-for-inclusion Y Y Y
M8-4 data-set-name Y Y Y
M8-5 data-reference Y Y Y
M8-6 BufTm Y Y Y
M8-7 IntgPd N Y Y
M8-8 GI N Y Y
Logging
M9 Log control O O N
M9-1 IntgPd N N N
M10 Log O O N
GSE
M12 GOOSE O O N
M13 GSSE O O N
M14 Multicast SVC O O N
M15 Unicast SVC O O N
M16 Time M M Y
M17 File Transfer O O Y
-104 -
CSC-101 Line Distance Protection IED Technical Manual
IED
Server
S1 ServerDirectory - M Y
Application association
S2 Associate M M Y
S3 Abort M M Y
S4 Release M M Y
Logical device
S5 LogicalDeviceDirectory M M Y
Logical node
S6 LogicalNodeDirectory M M Y
S7 GetAllDataValues O M Y
Data
S8 GetDataValues M M Y
S9 SetDataValues O O Y
S10 GetDataDirectory O M Y
S11 GetDataDefinition O M Y
Data set
S12 GetDataSetValues O M Y
S13 SetDataSetValues O O Y
S14 CreateDataSet O O Y
S15 DeleteDataSet O O Y
S16 GetDataSetDirectory O O Y
Substitution
S17 SetDataValues M M N
Setting group control
S18 SelectActiveSG O O Y
S19 SelectEditSG O O Y
S20 SetSGValues O O Y
S21 ConfirmEditSGValues O O Y
S22 GetSGValues O O Y
S23 GetSGCBValues O O Y
Reporting
Buffered report control block (BRCB)
S24 Report C6 C6 Y
S24-1 data-change (dchg) C6 C6 Y
S24-2 qchg-change (qchg) C6 C6 Y
S24-3 data-update (dupd) C6 C6 Y
S25 GetBRCBValues C6 C6 Y
S26 SetBRCBValues C6 C6 Y
-105 -
CSC-101 Line Distance Protection IED Technical Manual
-106 -
CSC-101 Line Distance Protection IED Technical Manual
S51 Select M M N
S52 SelectWithValue M M N
S53 Cancel O M N
S54 Operate M M Y
S55 Command-Termination M M N
S56 TimeActivated-Operate O O N
File transfer
S57 GetFile O M Y
S58 SetFile O O Y
S59 DeleteFile O O Y
S60 GetFileAttributeValues O M Y
Time
SNTP O
server
SNTP Y
client
T1 Time resolution of internal T1
clock
T2 Time accuracy of internal T0
clock
T3 Supported Timestamp 10
resolution
-107 -
CSC-101 Line Distance Protection IED Technical Manual
Address
Building 9, Fourth Avenue, Shangdi Information Industry Base,
Haidian District, Beijing, P.R.China
Zip 100085
Tel +8610-62961515,
+8610-62985012 (Marketing Department)
+8610-62986668(Technical Support)
Fax +8610-62981004
+8610-62978952 (Marketing Department)
E-mail: webinfo@sf-auto.com
Web Site: http://www.sf-auto.com
-108 -