Está en la página 1de 2

704

DEEP SEA ELECTRONICS PLC Auto Mains


Failure

Issue 7
VH 28/08/02

DESCRIPTION

The 704 is an Automatic Mains Failure Issues such as environmental compliance


module with generator monitoring, and EMC have been carefully engineered
protection and start facilities. It utilises into the design. Advanced features such
advanced surface mount construction as Protected Solid State Outputs mean
techniques to provide a compact yet that there are no moving parts or contacts
highly specified module. to burn out.
Operation of the module is via three OPERATION
pushbuttons mounted on the front panel
with STOP, MANUAL and AUTO Stop mode - This is used to stop the
positions. Selection of the ‘Auto’ mode is engine when it is running and to cancel
confirmed by LED indicator, and monitors ‘Auto’ mode. It is also used to reset any
SPECIFICATION
the incoming mains supply (3 phase or Shutdown alarm conditions.
single phase). Should the incoming AC DC Supply:
mains supply fall below a configurable 8 to 35 V Continuous.
Manual mode - This is used to manually
pre-set limit (180V default), the generator Cranking Dropouts:
start and run the engine. It can be stopped
will be started, and load transferred to the Able to survive 0 V for 50 mS,
by pressing the Stop button.
gen-set. providing supply was at least 10 V
before dropout and supply recovers
Auto mode - This selects the automatic
When the AC mains supply returns to to 5V. This is achieved without the
mode of operation, in which the module will
within limits, the module will wait for a need for internal batteries.
await a mains failure. Once detected, the
configurable, pre-set stabilisation period, Max. Current:
module will initiate its pre-configured start
and then transfer load back to the mains. Operating 50mA
sequence, observing the Start Delay Timer
The engine will be instructed to stop after Standby 10mA
before starting the engine. When the
a cool-down period. Alternator Input Range:
mains supply returns, the module will 75(ph-N) to 277(ph-N) 3 Phase
The module’s microprocessor provides a initiate its pre-configured stopping 4wire AC (+20%)
comprehensive list of timers and sequence. Alternator Input Frequency:
functions, and access to the settings is 50 - 60 Hz at rated engine speed
via a small Configuration Switch on the FEATURES (Minimum: 75V AC Ph-N) (Crank
rear of the module. Parameter settings Disconnect from 15V Ph-N @ 20Hz)
can be adjusted using the front panel Overspeed +14% (+24% overshoot)
Ø Micro-processor based design
pushbuttons once in Configuration Mode. Underspeed –20%
Ø Automatic Engine Starting and
The module monitors the engine and Stopping Start Output:
provides the following functions: Ø Automatic Shutdown on Fault 1.2 Amp DC at supply voltage.
Condition Fuel Output:
Ø Automatic Start with 3 start attempts Ø Configurable via front panel 1.2 Amp DC at supply voltage.
and Automatic Crank Disconnect - Ø Simple pushbutton controlled Auxiliary Outputs:
with adjustable Start and Stop operation 1.2 Amp DC at supply voltage.
Timers and Fail to Start indication. Ø Configurable Digital Inputs Dimensions:
Ø Configurable Pre-heat and Energise Ø Configurable Solid State Outputs 125 X 165 X 28 mm
to Stop functions. Ø Configurable Timer Settings Charge Fail:
Ø Low Oil Pressure and High Engine Ø Solid State Fuel and Crank Outputs 12V = 8V CF 24V = 16V CF
Temperature Shutdown. Ø External Remote Start Input Operating Temperature Range:
Ø Overspeed and Underspeed Ø LED Alarm indication -30 to + 700C
(frequency) protection. Ø Start/Stop Delay Timer
Ø Charge Fail alarm Ø Warm-up/Cooling Timer Ø Compliant with BS EN 60950
Ø Two fully configurable auxiliary Ø Energise to Stop Timer Low Voltage Directive
inputs. Ø Single/Three phase mains sensing Ø Compliant with BS EN 50081-2
Ø Adjustable Warming and cooling Ø Load contactor control Solid State EMC Directive
timers Outputs Ø Compliant with BS EN 50082-2
Ø Adjustable Mains Fail voltage level Ø Pre-heat Timer EMC Directive
Ø Change-over contactor control. Ø Over Speed Shutdown
Ø Optional Underspeed Protection The 700 series modules have been
All alarms are indicated by high visibility Ø Low Oil Pressure Shutdown designed for front panel mounting.
red LED’s. Ø High Engine Temp Shutdown The module is fitted into the cut-out,
Ø Optional Crank Disconnect from Oil and screw holes are provided for
Pressure
secure fixing.
Deep Sea Electronics plc reserve the right to change
specification without notice.
CONFIGURATION
Configuration Mode is selected by operation of a small switch on the rear, left-hand edge of the PCB. This is partially hidden to
prevent accidental operation. See figs 1 and 2

Fig. 1 Once Configuration Mode is selected, the ‘Auto’ LED will commence rapid flashing. When in
Configuration Mode all normal operation is suspended.
Normal The ‘Stop’ pushbutton can be used to select the LED ‘code’ that corresponds to the required
function. The 5 left hand LED’s will form the code.
The ‘Manual’ pushbutton will allow the user to change the function parameters. The 3 right-hand
LED’s inform the user of the current setting for the chosen function.
Configuration
When the required parameters are displayed, pressing the ‘Auto’ button will save the
new setting. The process is repeated for each function change.
When configuration is complete, the Configuration Mode Selector Switch should be returned to the
‘Normal’ position.
A key to configuration options is provided with the Installation Instructions supplied with module.

Fig. 2 Reverse of 704


Fig. 3 Dimensions (mm)
Mechanical Interlock

Typical Connections Load

Alternator Output Mains / Utility supply


L3 L3

L2 L2

L1 L1

N N
Electrical Interlock SSO = Solid state outputs

G M
F 2A FUSES 2A = External 'Automotive' or 'Plug-in' type relays
Normally open
NOTE * Normally closed

* Close mains relay must be normally closed


to ensure fail safe operation
+ Close gen relay Close mains relay
+
21 20 14 13 16 17 18 19
SSO
SSO

Close Gen output Close mains output 15

Fuel output Start output Auxiliary Outputs


SSO SSO SSO SSO Auxiliary Alarm
Inputs
1 2 3 4 5 6 7 8 9 10 11 12
Engine temperature

Remote Start
Oil Pressure

+ + + +

F2A F

+ Crank
Fuel Starter Charge
Battery motor alt

Deep Sea Electronics plc


Highfield House, Hunmanby Industrial Estate, North Yorkshire, YO14 0PH, England
Tel: +44 (0) 1723 890099 Fax: +44 (0) 1723 893303 E-mail sales@deepseaplc.com