Standard Technical Features of BTG System for Supercritical 660/800 MW Thermal Units
The insulation shall have sufficient dielectric
strength to withstand rated phase to earth voltage in slot portion and phase to phase voltage in end windings. The insulation material shall not have any tendency for plastic deformation even under extreme operating condition like the conductor temperature, mechanical forces, vibrations etc. The cooling circuit shall be provided with asuitable device to guard against any rise in pressure. Power & instrumentation leads shall be taken out of the motor through water tight sealing glands & shall be run in flexible metal conduits or metal cable sheathing along the length of the pump body. The design of the seals shall allow for effects of differential expansion between insulation conductor and pressure casing, over the entire range of operating temperature. 4. Cooling One number external high pressure cooler for system each motor rated for 100% duty shall be provided to remove the heat generated by the motor and bearings during operation. The temperature of high pressure cooling water leaving the motor cavity to the cooler shall not exceed 600C. The cooler shall be adequately sized to reduce this temperature to 500C. The design shall be such that during hot standby service of the pumping unit, sufficient cooling effect is provided by natural circulation of the coolant so as to prevent over heating of the motor. 6.5.6 Superheaters & reheaters i) Superheaters and reheaters shall be designed, suitably sectionalized and positioned to comply with the following, for the specified load(s), coal(s) and for normal, upset, most adverse and other operating conditions: a) Rated steam temperature As indicated at clause 6.2 above. b) Maximum average flue 10 m/sec (maximum localized velocity gas velocity in section/ across the cross-section not to exceed tube banks with 12 m/sec) transverse tube pitching For high GCV low ash (say 10% and of 600 mm or less and below) coals: 12 m/sec (maximum with 25% excess air at localized velocity across the cross- economizer outlet section not to exceed 14 m/sec) 37