Documentos de Académico
Documentos de Profesional
Documentos de Cultura
REFRIGERANT
REFRIGERANT
R410A HEATPUMP
1. Precaution................................................................................................................................................. 3
2. Function .................................................................................................................................................... 6
3. Product Specification .............................................................................................................................. 7
4. Dimension ................................................................................................................................................ 11
5. Performance data ................................................................................................................................... 17
6. Refrigerant Cycle Diagram .................................................................................................................... 25
7. Wiring diagram ....................................................................................................................................... 26
8. Installation Details.................................................................................................................................. 30
9. Operation Characteristics ..................................................................................................................... 37
10. Electronic function ................................................................................................................................ 38
11. Troubleshooting ..................................................................................................................................... 46
12. Exploded view and spare part list ........................................................................................................ 64
PRECAUTION
There is risk of electric shock or fire. Keep level even when installing the
Stop operation and close the window product.
in storm or hurricane. If possible, remove It can avoid vibration of water leakage.
the product from the window before the Do not install the product where the
hurricane arrives. noise or hot air from the outdoor unit could
There is risk of property damage, failure of damage the neighborhoods.
product, or electric shock. It may cause a problem for your neighbors.
Do not open the inlet grill of the Use two or more people to lift and
product during operation. (Do not touch the transport the product.
electrostatic filter, if the unit is so equipped.) Do not install the product where it will
There is risk of physical injury, electric shock, be exposed to sea wind (salt spray) directly.
or product failure. It may cause corrosion on the product.
When the product is soaked, contact Corrosion, particularly on the condenser and
an authorized service center. evaporator fins, could cause product
There is risk of fire or electric shock. malfunction or inefficient operation.
Be caution that water could not enter
the product. Operational
There is risk of fire, electric shock, or product Do not expose the skin directly to
damage. cool air for long time. (Do not sit in the
Ventilate the product from time to draft).
time when operating it together with a stove Do not use the product for special
etc. purposes, such as preserving foods, works
There is risk of fire or electric shock. of art etc. It is a consumer air conditioner,
Turn the main power off when not a precision refrigerant system.
cleaning or maintaining the product. There is risk of damage or loss of property.
There is risk of electric shock. Do not block the inlet or outlet of air
When the product is not be used for a flow.
long time, disconnect the power supply plug Use a soft cloth to clean. Do not use
or turn off the breaker. harsh detergents, solvents, etc.
There is risk of product damage or failure, or There is risk of fire, electric shock, or damage
unintended operation. to the plastic parts of the product.
Take care to ensure that nobody Do not touch the metal parts of the
could step on or fall onto the outdoor unit. product when removing the air filter. They
This could result in personal injury and are very sharp.
product damage. Do not step on or put anything on the
product. (outdoor units)
CAUTION Always insert the filter securely.
Always check for gas (refrigerant) Clean the filter every two weeks or more
leakage after installation or repair of often if necessary.
product. A dirty filter reduces the efficiency of the air
Low refrigerant levels may cause failure of conditioner and could cause product
product. malfunction or damage.
Install the drain hose to ensure that Do not insert hands or other objects
water is drained away properly. through air inlet or outlet while the product
A bad connection may cause water leakage. is operated.
2. Function
O: optional function
3. Product Specification
3.1 ELSI-JKD009-N11 / ELAU-VKD009-H11
MODEL INDOOR UNIT ELSI-JKD009-N11
Model Outdoor Unit ELAU-VKD009-H11
Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Average Warm Cold
Capacity (1) kW 2.65(1.2-3.3) 2.8(0.85-3.7)
Pdesign kW 2.65 2.4 2.8 3
SEER /SCOP (2) W/W 6.9 4 5.1 3.3
Energy efficiency class A++ A+ A+++ B
Annual energy consumption kWh 135 840 769 1910
oC
Tbiv N/A -7 2 -15
oC
Tol N/A -15
Power supply V/Ph/Hz 220-240V/Single/50Hz
Circuit breaker rating A 10
Fan type & quantity Cross flow fan x1
Fan speeds H/M/L/VL RPM 1150 / 1000 / 800
Air flow (3) H/M/L/VL m3/hr 430/380/320/230
External static pressure Min-Max Pa 0
Sound power level (4) H/M/L dB(A) 54
INDOOR
Weight kg 26.6
Package dimensions LxWxH mm 900x345x585
Packaged weight kg 29
Stacking height Units 4
Refrigerant type R410A
Refrigerant charge (standard connecting tubing length) kg(5m) 0.8
Additional charge per 1 meter gr / 1m 15
Connections between units Liquid line In.(mm) 1/4
Suction line In.(mm) 3/8
Max.tubing length m. 25
Max.height difference m. 10
Operation control type Remote control
Heating elements kW NA
Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2) SEER / SCOP calculation accordance with EN14825.
Weight kg 29.1
Package dimensions LxWxH mm 920x390x615
Packaged weight kg 31.9
Stacking height Units 4
Refrigerant type R410A
Refrigerant charge (standard connecting tubing length) kg(5m) 0.95
Additional charge per 1 meter gr / 1m 15
Liquid line In.(mm) 1/4
Suction line In.(mm) 3/8
Connections between units
Max.tubing length m. 25
Max.height difference m. 10
Operation control type Remote control
Heating elements kW NA
Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2) SEER / SCOP calculation accordance with EN14825.
Weight kg 37.8
Package dimensions LxWxH mm 920x390x615
Packaged weight kg 40.5
Stacking height Units 4
Refrigerant type R410A
Refrigerant charge (standard connecting tubing length) kg(5m) 1.48
Additional charge per 1 meter gr / 1m 15
Liquid line In.(mm) 1/4
Suction line In.(mm) 1/2
Connections between units
Max.tubing length m. 30
Max.height difference m. 20
Operation control type Remote control
Heating elements kW NA
Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2) SEER / SCOP calculation accordance with EN14825.
Weight kg 48.4
Package dimensions LxWxH mm 965x395x755
Packaged weight kg 51.6
Stacking height Units 3
Refrigerant type R410A
Refrigerant charge (standard connecting tubing length) kg(5m) 2
Additional charge per 1 meter gr / 1m 30
Liquid line In.(mm) 3/8"
Suction line In.(mm) 5/8"
Connections between units
Max.tubing length m. 50
Max.height difference m. 25
Operation control type Remote control
Heating elements kW NA
Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2) SEER / SCOP calculation accordance with EN14825.
4. Dimension
4.1 Indoor Unit
W D
Model W D H
ELSI-JKD009-N11 715 188 250
ELSI-JKD012-N11 800 188 275
ELSI-JKD018-N11 940 205 275
ELSI-JKD024-N11 1045 235 315
For ELSI-JKD012-N11
For ELSI-JKD018-N11
For ELSI-JKD024-N11
For ELAU-VKD009-H11
779 W3
555
H
12
487 W1
300 D 770 W
70 W2
25 B1
90 B2
D2 D3
286
298
322
D1
61.5 A2
60
H1
93
H2
R6
12 A1
815 W3
554
H
12.0
333 D 514 W1
800 W 70 W2
62 B1
106 B2
D2 D3
340
365
311
D1
85.5 60
H1
H2
R2
0 20 A1
R6
61.6 A2
For ELAU-VKD024-H11
JKD DCI 15 Version - 1
DIMENSIONS
5. Performance data
5.1 ELSI-JKD009-N11 / ELAU-VKD009-H11
1) Cooling
ID COIL ENTERING AIR DB/WB TEMPERATURE [C0]
OD COIL ENTERING AIR DB DATA 22/15 24/17 27/19 29/21 32/23
TEMPERATURE [C0]
TC 80 - 110 % of nominal
-10 - 20
SC 80 - 105 % of nominal
(protection range)
PI 25 - 50 % of nominal
TC 2.56 2.73 2.90 3.06 3.23
25 SC 1.98 2.02 2.06 2.10 2.14
PI 0.61 0.62 0.63 0.64 0.66
TC 2.44 2.61 2.77 2.94 3.11
30 SC 1.93 1.97 2.01 2.05 2.09
PI 0.68 0.69 0.70 0.72 0.73
TC 2.32 2.48 2.65 2.82 2.98
35 SC 1.88 1.92 1.96 2.00 2.04
PI 0.75 0.76 0.78 0.79 0.80
TC 2.19 2.36 2.53 2.69 2.86
40 SC 1.83 1.87 1.91 1.95 1.99
PI 0.82 0.83 0.85 0.86 0.87
TC 2.04 2.21 2.38 2.55 2.71
46 SC 1.77 1.81 1.85 1.89 1.93
PI 0.91 0.92 0.93 0.94 0.96
Legend:
TC - Total Cooling Capacity [kW] SC - Sensible Capacity [kW]
PI - Power Input [kW] WB - Wet Bulb Temperature
DB - Dry Bulb Temperature ID - Indoor
OD - Outdoor
2) Heating
ID COIL ENTERING AIR DB TEMPERATURE [C0]
OD COIL ENTERING
AIR DB/WB DATA 15 20 25
TEMPERATURE [C0]
TC 1.78 1.66 1.53
-15/-16
PI 0.43 0.48 0.52
TC 1.98 1.86 1.73
-10/-12
PI 0.52 0.56 0.61
TC 2.14 2.01 1.89
-7/-8
PI 0.59 0.63 0.68
TC 2.21 2.09 1.96
-1/-2
PI 0.62 0.66 0.71
TC 2.26 2.14 2.01
2/1
PI 0.64 0.69 0.73
TC 2.92 2.80 2.68
7/6
PI 0.68 0.72 0.76
TC 3.09 2.96 2.84
10/9
PI 0.72 0.76 0.80
TC 3.25 3.12 3.00
15/12
PI 0.76 0.80 0.84
15-24 TC 85 - 105 % of nominal
(Protection Range) PI 80 - 120 % of nominal
Legend
TC - Total Capacity [kW] PI - Power Input [kW]
WB -Wet Bulb Temperature DB -Dry Bulb Temperature
ID - Indoor OD Outdoor
Legend:
TC - Total Cooling Capacity [kW] SC - Sensible Capacity [kW]
PI - Power Input [kW] WB - Wet Bulb Temperature
DB - Dry Bulb Temperature ID - Indoor
OD - Outdoor
2) Heating
ID COIL ENTERING AIR DB TEMPERATURE [C0]
OD COIL ENTERING
AIR DB/WB DATA 15 20 25
TEMPERATURE [C0]
TC 2.23 2.07 1.92
-15/-16
PI 0.56 0.62 0.68
TC 2.48 2.32 2.17
-10/-12
PI 0.68 0.74 0.79
TC 2.67 2.51 2.36
-7/-8
PI 0.77 0.82 0.88
TC 2.76 2.61 2.45
-1/-2
PI 0.81 0.87 0.92
TC 2.83 2.67 2.51
2/1
PI 0.84 0.90 0.95
TC 3.66 3.50 3.34
7/6
PI 0.88 0.94 1.00
TC 3.86 3.70 3.55
10/9
PI 0.94 0.99 1.05
TC 4.06 3.90 3.75
15/12
PI 0.99 1.05 1.10
15-24 TC 85 - 105 % of nominal
(Protection Range) PI 80 - 120 % of nominal
Legend
TC - Total Capacity [kW] PI - Power Input [kW]
WB -Wet Bulb Temperature DB -Dry Bulb Temperature
ID - Indoor OD Outdoor
Legend:
TC - Total Cooling Capacity [kW] SC - Sensible Capacity [kW]
PI - Power Input [kW] WB - Wet Bulb Temperature
DB - Dry Bulb Temperature ID - Indoor
OD - Outdoor
2) Heating
ID COIL ENTERING AIR DB TEMPERATURE [C0]
OD COIL ENTERING
AIR DB/WB DATA 15 20 25
TEMPERATURE [C0]
TC 3.18 2.96 2.74
-15/-16
PI 0.81 0.89 0.97
TC 3.54 3.32 3.10
-10/-12
PI 0.98 1.06 1.14
TC 3.81 3.59 3.37
-7/-8
PI 1.10 1.18 1.27
TC 3.95 3.73 3.50
-1/-2
PI 1.16 1.25 1.33
TC 4.04 3.82 3.59
2/1
PI 1.21 1.29 1.37
TC 5.22 5.00 4.78
7/6
PI 1.27 1.35 1.43
TC 5.51 5.29 5.07
10/9
PI 1.34 1.43 1.51
TC 5.80 5.58 5.35
15/12
PI 1.42 1.50 1.58
15-24 TC 85 - 105 % of nominal
(Protection Range) PI 80 - 120 % of nominal
Legend
TC - Total Capacity [kW] PI - Power Input [kW]
WB -Wet Bulb Temperature DB -Dry Bulb Temperature
ID - Indoor OD Outdoor
Legend:
TC - Total Cooling Capacity [kW] SC - Sensible Capacity [kW]
PI - Power Input [kW] WB - Wet Bulb Temperature
DB - Dry Bulb Temperature ID - Indoor
OD - Outdoor
2) Heating
ID COIL ENTERING AIR DB TEMPERATURE [C0]
OD COIL ENTERING
AIR DB/WB DATA 15 20 25
TEMPERATURE [C0]
TC 4.77 4.44 4.11
-15/-16
PI 1.40 1.55 1.69
TC 5.31 4.98 4.65
-10/-12
PI 1.69 1.84 1.98
TC 5.72 5.39 5.05
-7/-8
PI 1.91 2.05 2.19
TC 5.92 5.59 5.25
-1/-2
PI 2.02 2.16 2.30
TC 6.06 5.72 5.39
2/1
PI 2.09 2.23 2.37
TC 7.83 7.50 7.17
7/6
PI 2.20 2.34 2.48
TC 8.27 7.93 7.60
10/9
PI 2.33 2.47 2.61
TC 8.70 8.36 8.03
15/12
PI 2.46 2.60 2.75
15-24 TC 85 - 105 % of nominal
(Protection Range) PI 80 - 120 % of nominal
Legend
TC - Total Capacity [kW] PI - Power Input [kW]
WB -Wet Bulb Temperature DB -Dry Bulb Temperature
ID - Indoor OD Outdoor
INDOOR OUTDOOR
CHECK VALVE
LIQUID SIDE (Heating Model only)
HEAT
EXCHANGE
(EVAPORATOR) HEAT
T1 Room temp. T4 Ambient EXCHANGE
sensor temp. sensor (CONDENSER)
T2 Evaporator
temp. sensor
GAS SIDE
4-WAY VALVE
COOLING
HEATING
7. Wiring diagram
7.1 Indoor unit : ELSI-JKD009-N11, ELSI-JKD012-N11, ELSI-JKD018-N11, ELSI-JKD024-N11
BLUE
1 L 2(N) S L N
Y/G
Y/G
INDOOR UNIT
4-WAY
BLUE CRANKCASE
HEATER
RED
PAN
HEATER
BLACK
CAPACITOR
U V W
CN 25
AC-FAN
Y/G
Y/G
CN 7
CONDENSER TEMP. SENSOR
OPTIONAL:
DC-FAN
Y/G
8. Installation Details
8.1 Wrench torque sheet for installation
Outside diameter Torque Additional tightening torque
mm inch N.cm N.cm
6.35 1/4 1500(153kgf.cm) 1600(163kgf.cm)
9.52 3/8 2500(255kgf.cm) 2600(265kgf.cm)
12.7 1/2 3500(357kgf.cm) 3600(367kgf.cm)
15.9 5/8 4500(459kgf.cm) 4700(479kgf.cm)
19 3/4 6500(663kgf.cm) 6700(683kgf.cm)
on the nameplate which located on the side panel of the unit. Please refer to the nameplate before
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the
system reliability.
8.4 Installation for the first time connection to the vacuum pump.
Air and moisture in the refrigerant system have 4) Fully open the handle Lo of the manifold
undesirable effects as below: valve.
Pressure in the system rises. 5) Operate the vacuum pump to evacuate.
Operating current rises. 6) Make evacuation for 30 minutes and check
Cooling or heating efficiency drops. whether the compound meter indicates
Moisture in the refrigerant circuit may -0.1Mpa. If the meter does not indicate
freeze and block capillary tubing. -0.1Mpa after pumping 30 minutes, it
Water may lead to corrosion of parts in the should be pumped 20 minutes more. If the
refrigerant system. pressure cant achieve -0.1Mpa after
Therefore, the indoor units and the pipes pumping 50 minutes, please check if there
between indoor and outdoor units must be leak are some leakage points.
tested and evacuated to remove gas and Fully close the handle Lo valve of the manifold
moisture from the system. valve and stop the operation of the vacuum
Gas leak check (Soap water method): pump. Confirm that the gauge needle does not
Apply soap water or a liquid neutral move (approximately 5 minutes after turning off
detergent on the indoor unit connections or the vacuum pump).
outdoor unit connections by a soft brush to 7) Turn the flare nut of the 3-way valves about
check for leakage of the connecting points of 45 counterclockwise for 6 or 7seconds
the piping. If bubbles come out, the pipes have after the gas
leakage. Coming out, then tighten the flare nut again.
8.4.1 Air purging with vacuum pump Make sure the pressure display in the pressure
indicator is a little higher than the atmosphere
pressure. Then remove the charge hose from
the 3 way valve.
8) Fully open the 2 way valve and 3 way valve
and securely tighten the cap of the 3 way
valve.
8.4.2 Air purging by refrigerant
cylinder to the service port of the 3-way valve. refrigerant is R410A, make the cylinder bottom
3). Air purging. up to ensure the liquid charge.
Open the valves on the charging cylinder and the 2). Purge the air from the charge hose.
charge set. Purge the air by loosening the flare Open the valve at the bottom of the cylinder
nut on the 2-way valve approximately 45 for 3 and press the check valve on the charge set to
seconds then closing it for 1 minute; repeat 3 purge the air (be careful of the liquid
times. refrigerant).
After purging the air, use a torque wrench to 3) Put the charging cylinder onto the electronic
tighten the flare nut on the 2-way valve. scale and record the weight.
4). Check the gas leakage. 4) Operate the air conditioner at the cooling
Check the flare connections for gas leakage. mode.
5). Discharge the refrigerant. 5) Open the valves (Low side) on the charge set
Close the valve on the charging cylinder and and charge the system with liquid refrigerant.
discharge the refrigerant by loosening the flare 6).When the electronic scale displays the proper
nut on the 2-way valve approximately 45 until the weight (refer to the table), disconnect the charge
gauge indicates 0.3 to 0.5 Mpa. hose from the 3-way valves service port
6). Disconnect the charge set and the charging immediately and turn off the air conditioner before
cylinder, and set the 2-way and 3-way valves to disconnecting the hose.
the open position. 7). Mount the valve stem caps and the service
Be sure to use a hexagonal wrench to operate the port
valve stems. Use torque wrench to tighten the service port
7). Mount the valve stems nuts and the service cap to a torque of 18N.m.
port cap. Be sure to check for gas leakage.
Be sure to use a torque wrench to tighten the 8.5 Adding the refrigerant after running the
service port cap to a torque 18Nm. system for many years
Be sure to check the gas leakage.
8.4.3 Adding the refrigerant if the pipe
length >5m
Procedure:
1). Connect the charge hose to the 3-way service
port, open the 2-way valve and the 3-way valve.
Procedure: Connect the charge hose to the valve at the
1). Connect the charge hose to the charging bottom of the cylinder. If the refrigerant is
cylinder, open the 2-way valve and the 3-way R410A, make the cylinder bottom up to ensure
valve. liquid charge.
Connect the charge hose which you 2). Purge the air from the charge hose.
disconnected from the vacuum pump to the Open the valve at the bottom of the cylinder
valve at the bottom of the cylinder. If the and press the check valve on the charge set to
Procedure:
1). Confirm that both the 2-way and 3-way valves
are set to the closed position.
2). Connect the charge set and a charging
cylinder to the service port of the 3-way valve
Leave the valve on the charging cylinder closed.
3). Air purging.
Open the valves on the charging cylinder and the
charge set. Purge the air by loosening the flare
Procedure nut on the 2-way valve approximately 45 for 3
1). Confirm that both the 2-way and 3-way valves seconds then closing it for 1 minute; repeat 3
are set to the opened position times.
Remove the valve stem caps and confirm that the After purging the air, use a torque wrench to
valve stems are in the opened position. tighten the flare nut on the 2-way valve.
Be sure to use a hexagonal wrench to operate the 4). Check the gas leakage
valve stems. Check the flare connections for gas leakage.
2). Connect the charge hose with the push pin of 5). Discharge the refrigerant.
handle lo to the 3-way valves gas service port. Close the valve on the charging cylinder and
3). Air purging of the charge hose. discharge the refrigerant by loosening the flare
Open the handle Lo valve of the manifold valve nut on the 2-way valve approximately 45 until the
slightly to purge air from the charge hose for 5 gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging 8.7.2 Refrigerant charging
cylinder, and set the 2-way and 3-way valves to
the open position
Be sure to use a hexagonal wrench to operate the
valve stems.
7). Mount the valve stems nuts and the service
port cap
Be sure to use a torque wrench to tighten the
service port cap to a torque 18N.m.
Be sure to check the gas leakage.
8.7 Re-installation while the outdoor unit
need to be repaired Procedure:
8.7.1 Evacuation for the whole system 1). Connect the charge hose to the charging
cylinder, open the 2-way valve and the 3-way
valve
Connect the charge hose which you
disconnected from the vacuum pump to the
valve at the bottom of the cylinder. If the
refrigerant is R410A, make the cylinder bottom
up to ensure liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder
and press the check valve on the charge set to
purge the air (be careful of the liquid
Procedure: refrigerant).
1). Confirm that both the 2-way and 3-way 3) Put the charging cylinder onto the electronic
valves are set to the opened position. scale and record the weight.
2). Connect the vacuum pump to 3-way valves 4). Open the valves (Low side) on the charge set
service port. and charge the system with liquid refrigerant
3). Evacuation for approximately one hour. If the system cannot be charge with the specified
Confirm that the compound meter indicates amount of refrigerant, or can be charged with a
-0.1Mpa. little at a time (approximately 150g each time) ,
4). Close the valve (Low side) on the charge set, operating the air conditioner in the cooling cycle;
turn off the vacuum pump, and confirm that the however, one time is not sufficient, wait
gauge needle does not move (approximately 5 approximately 1 minute and then repeat the
minutes after turning off the vacuum pump). procedure.
5). Disconnect the charge hose from the vacuum 5).When the electronic scale displays the proper
pump. weight, disconnect the charge hose from the
3-way valves service port immediately
If the system has been charged with liquid
refrigerant while operating the air conditioner,
turn off the air conditioner before disconnecting
the hose.
6). Mounted the valve stem caps and the service
port
9. Operation Characteristics
Temperature
Cooling operation Heating operation Drying operation
Mode
Room temperature 17 30 10
050
Outdoor temperature
-1550
-1530 050
(For the models with
low temperature
cooling system)
CAUTION:
1. If the air conditioner is used beyond the above conditions, certain safety protection features
may come into operation and cause the unit to operate abnormally.
2. The room relative humidity should be less than 80%. If the air conditioner operates beyond this
figure, the surface of the air conditioner may attract condensation. Please set the vertical air flow
louver to its maximum angle (vertically to the floor), and set HIGH fan mode.
3. The optimum performance will be achieved during this operating temperature zone.
ION INDICATOR
(optional)
Lights up when ionizer or plasma function is activated.
DEFROSTING
INDICATOR Lights up when the unit is under defrosting operation or when the anti-cold
air function is activated.
RUN INDICATOR
Lights up when the unit is in operation.
TIMER INDICATOR
Lights up when TIMER function is activated.
A+ Off
Decrease
A
B Hold
Resume
C
E
When condenser temperature temp. is more
than setting value, the compressor will stop.
H
A H=H When the AC run in mute mode, the
B
C
H-H-=H-G) compressor will run with low frequency.
M+(M+=M+Z) When the current is more than setting value,
D M(M=M)
M
E
the current protection function will be activated
M-(M-=M-Z)
F and the compressor will stop.
L+(L+=L+D)
G L(L=L)
L
H
L-(L-=L-D) 10.4.3.2 Outdoor fan running rules
I
The outdoor unit will be run at different fan
The auto fan acts as below rules:
speed according to T4.
T1
For different outdoor units, the fan speeds are
different
a T4
b E
c
D
d
e C
A+
L-(L-=L-D)
Hold
L
L(L=L)
L+(L+=L+D)
- Resume
10.4.4 Auto-mode
This mode can be chosen with remote
controller and the setting temperature can be
changed between 17C~30C
In auto mode, the machine will choose cooling,
heating or fan-only mode according to T (T
=T1-Ts).
times in ten seconds, the buzzer will keep ring for two seconds. The air conditioner will enter into the
information enquiry status. You can press the Light button to check the next items information.
When the AC enter the information enquiry status, it will display the code name in 2 seconds, the
When the AC enter into the information enquiry status, it will display the code value in the next 25s, the
11. Troubleshooting
Safety
Electricity power is still kept in capacitors even the power supply is shut off. Do not forget to discharge the electricity
power in capacitor.
Electrolytic Capacitors
(HIGH VOLTAGE! CAUTION!)
For other models, please connect discharge resistance (approx.100 40W) or soldering iron (plug) between +, -
terminals of the electrolytic capacitor on the contrary side of the outdoor PCB.
Note: The picture above is only for reference. The plug of your side may be different.
Malfunction decision Indoor or outdoor PCB main chip does not receive feedback
conditions from EEPROM chip.
Supposed causes Installation mistake
PCB faulty
Trouble shooting:
Yes
EEPROM: a read-only memory whose contents can be erased and reprogrammed using a pulsed
voltage. For the location of EEPROM chip, please refer to the below photos.
Indoor PCB
Outdoor PCB
Note: The two photos above are only for reference, its may be not same totally with the ones
on your side.
Malfunction decision Indoor unit does not receive the feedback from outdoor unit during
conditions 110 seconds and this condition happens four times continuously.
Supposed causes Wiring mistake
Indoor or outdoor PCB faulty
Trouble shooting:
Power
Power off,
off, then
then restart
restart the
the unit
unit 22 minutes
minutes later
later
Yes
Measure
Measure Vs, Vs, is
is itit positive
positive fluctuation?
fluctuation?
(Vs
(Vs is
is the
the voltage
voltage between
between S S and
and N
N of
of No
outdoor
outdoor unit.
unit. Red
Red pan-S,
pan-S, Black
Black pan-N)
pan-N)
Yes
Check
Check the
the outdoor
outdoor wiring
wiring connection
connection
Yes Check
Check the
the indoor
indoor wiring
wiring connection
connection
Yes
Check
Check whether
whether reactor
reactor
Replace
Replace the
the reactor
reactor No
is
is normal?
normal? Replace
Replace the
the indoor
indoor main
main PCB.
PCB.
Power
Power on.
on. IsIs the
the error
error
extinguished?
extinguished?
Yes No
Replace
Replace the
the outdoor
outdoor main
main PCB.
PCB.
Power
Power on.
on. Is
Is the
the error
error Replace
Replace the
the outdoor
outdoor main
main PCB.
PCB.
extinguished?
extinguished?
No
Replace
Replace the
the indoor
indoor main
main PCB.
PCB.
11.2.3 Fan speed has been out of control diagnosis and solution (E3)
Error Code E3/F5
Malfunction decision When indoor fan speed keeps too low (300RPM) for certain time,
conditions the unit will stop and the LED will display the failure.
Supposed causes Wiring mistake
Fan assy faulty
Fan motor faulty
PCB faulty
Trouble shooting:
Yes
Shut off the power supply, Find out the cause and have
No
Rotate the fan by hand. it solved
Yes
Yes
Yes
Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor
connector. If the value of the voltage is not in the range showing in below table, the PCB must has
Power on ,and check if the fan can run normally, if the fan can run normally, the PCB must has
problems and need to be replaced, If the fan cant run normally, measure the resistance of each two
pins. If the resistance is not equal to each other, the fan motor must have problems and need to be
replaced, otherwise the PCB must has problems and need to be replaced.
Power on and set the unit running in fan mode at high fan speed. After running for 15 seconds,
measure the voltage of pin1 and pin2. If the value of the voltage is less than 100V (208~240V power
supply) or 50V (115V power supply), the PCB must has problems and need to be replaced.
11.2.4 Open circuit or short circuit of temperature sensor diagnosis and solution (E5)
Error Code E4/E5/F1/F2/F3
Malfunction decision If the sampling voltage is lower than 0.06V or higher than 4.94V,
conditions the LED will display the failure.
Supposed causes Wiring mistake
Sensor faulty
Trouble shooting: PCB faulty
Yes
Yes
Malfunction decision Define the evaporator coil temp.T2 of the compressor just starts
conditions running as Tcool.
In the beginning 5 minutes after the compressor starts up, if T2
Tcool2 does not keep continuous 4 seconds and this
situation happens 3 times, the display area will show EC and
AC will turn off.
Yes
No Yes
No
Yes
Repair the leakage and
recharge the refrigerant.
check blockIng of system and
clear the blocking
Yes
Yes
Yes
Yes
Yes
Malfunction decision When the voltage signal that IPM send to compressor drive chip
conditions is abnormal, the display LED will show P0 and AC will turn off.
Supposed causes Wiring mistake
IPM malfunction
Outdoor fan assy faulty
Compressor malfunction
Outdoor PCB faulty
Trouble shooting:
Check the wiring between main PCB Correct the connection or replace
Yes
and compressor the wires and connectors.
No
Yes
Yes
Yes
Yes
Yes
Yes
Malfunction decision If the sampling voltage is not 5V, the LED will display the failure.
conditions
Supposed causes Power supply problems.
System leakage or block
PCB faulty
Trouble shooting:
Check the air flow system Clear up the air inlet and outlet or the heat
Yes
of indoor and outdoor units exchanger of indoor and outdoor units.
No
Yes
Yes
Yes
Yes
Check the wiring between main PCB Correct the connection or replace
Yes
and compressor the wires and connectors.
No
Yes
Yes
Yes
Temperature Sensors.
Room temp. (T1) sensor,
Indoor coil temp. (T2) sensor,
Outdoor coil temp. (T3) sensor,
Outlook ambiant tempo. (T4) seor,
Compressor discharge temp. (T5) sensor.
Measure the resistance value of each winding by using the multi-meter.
12.2 ELSI-JKD012-N11
12.3 ELSI-JKD018-N11
12.4 ELSI-JKD024-N11
12.5 ELAU-VKD009-H11
12.6 ELAU-VKD012-H11
12.7 ELAU-VKD018-H11
12.8 ELAU-VKD024-H11