Fire-Water Pumps
for CPI Facilities FIGURE 1 Fire-water pump assem-
blies are typically skid-mounted to ease
installation and operation. Shown here
Follow this guidance to improve the selection, design is an example of a skid-mounted, diesel-
engine-driven, ire-water pump package
and operation of pumps handling water for fire-
ent guidelines have been used to
fighting and related systems estimate the ideal water volume
and flow requirements for CPI fire
Amin Almasi around 2035% of the insurance- cases, depending on plant specifics,
Consultant deficiency rating points for a CPI applicable codes, regulations and
plant are related to inadequate fire- fire-fighting methods. As a result,

F
ire-water pumps are criti- water pumping systems. On aver- these specifications will vary based
cal machines that save lives age, 510% of all fire-water pumping on whether the plant is using fire
and prevent chemical pro- systems in CPI plants have failed to control, fire suppression, exposure
cess industries (CPI) facili- provide satisfactory services at the cooling and so on.
ties from damage more so than time required (as evidenced during Fire-water demands are usually
any other plant components. Fire- actual fire cases or drill-type exer- calculated based on the maximum
water pumps are nearly always cen- cises). Thus, it is critical to design, rate of water that will be required for
trifugal pumps with capacity from implement, operate and maintain a worst-case scenario typically a
around 203,000 m3/h. Specific re- these critical systems beyond the potential scenario involving a large,
quirements for fire-water pumps minimum requirements set forth in single-fire incident. The most remote
are briefly noted in fire codes (such published fire codes. unit(s) from the fire-water pumps, or
as NFPA 20 [1]), but this may not the largest unit(s), are typically exam-
be sufficient for specifying high- Fire-water system ined to identify the worse possible fire
performance fire-water pumps in Fire-protection efforts are categorized scenario(s). The potential scenario of
a way that ensures good reliability as passive or active. The primary a vast fire in the largest unit should
and operation as well as optimum passive measures for fire protection be used to define the capacity of fire-
price. This article provides practi- include efforts to ensure sufficient water system. The most-remote fire
cal notes on fire-water pumps to ex- clearances, install protective barri- unit(s) should be used to define maxi-
pand upon the information that can ers, limit and protect fuel sources, mum rated pressure of the fire-water
be found in existing fire codes. and other steps designed to reduce pump.
Various styles and configurations fire risks (such as the use of less CPI fire cases can be very differ-
of fire-water pumps are available hazardous materials, processes and ent, considering the different types
at different prices. In addition to equipment). By comparison, active of materials handled and the types
proper selection, fire-water pumps fire-protection systems are designed of operations carried out at differ-
must be properly integrated into to detect and apply fire-protection ent facilities. Today, computerized
the overall fire-water system, as an measures, which usually rely on some simulations play a critical role in
integral part of the CPI facility. effort to actually extinguish the fire. identifying and modeling potential
Figure 1 shows an example of Commonly used system components fire scenarios, validating fire-fight-
a skid-mounted, diesel-engine- include fire hydrants, monitors, hose ing methodologies, and estimating
driven fire-water pump package. reels, water-spray systems, deluge- the required water capacity.
The performance and reliability of type fire-protection systems or water- When evaluating a potential
a fire-water pumping system is an exposure cooling systems. The fire-wa- fire-fighting scenario, additional
important issue, and details of the ter pump plays an important role in pressure (a safety margin to the
fire-water pumping system are usu- most active fire-protection systems. calculated head) should be added
ally a part of risk studies, HAZOP to maintain the fire-water pres-
and inspection activities. System design and sizing sure in all remote units and critical
Fire-water pumps are important There have been different sets of fire-fighting systems; this is nec-
to different stakeholders, including rules to define the required flow essary to ensure that a fire-water
clients, investors in the CPI plant, and head of fire-water pumps. In stream with adequate pressure can
and insurance providers. Usually other words, a variety of differ- be maintained to support all appli-
CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM DECEMBER 2014 53
Environmental Manager

cable fire-fighting systems should The control of a fire event usu-


there be a fire in a unit. ally requires variable amount
Fire-water and utility-water sys- of water at a relatively constant
tems have sometimes been com- pressure
bined in non-critical plants. In the Fire-water pumps are typically
event of a fire, the connected util- operated in parallel. A relatively
ity water system would be tripped. flat curve ensures troublefree
However, these combined systems parallel operation
are always risky. Various fire codes Sometimes, a large amount of
recommend that no utility-water water can be required by the fire- FIGURE 2. Shown here are several
connections be made to the fire-wa- water system to battle a vast fire; examples of ire-water pumps; an identi-
ter system. In some special cases, in those cases, the required water cal spare pump is commonly used to in-
the fire-water system may be used could be considerably larger than crease the reliability of ire-water pump-
ing systems
for emergency process-cooling re- the rated flow of the pump. In
quirements, but only as the second- this regard, the fire-water pump ing and power-density exceed a cer-
ary (reserve) supply. overload point (the end operating tain level. As a rough indication,
Fresh (treated) water is always point at the right side of the pump this limit could be 400 kW.
preferred (over seawater, brackish curve) should demonstrate a capac- As noted, the fire-water pumps in-
or untreated water, for instance) for ity of more that 150% of the rated stalled at any given facility should
fire-water systems in all onshore capacity at a head more than 70% be able to operate in parallel. How-
plants. Untreated or brackish water of the rated point. In other words, ever, there are some challenges
can cause many issues such as cor- operation point could move to the and issues in ensuring parallel op-
rosion, which can potentially wreak far right side of the rated point and eration. Even in certain conditions,
havoc on the system components. that point should offer sufficient pumps designed to operate in paral-
In general, engineers should pur- flow and head. lel could be subject to overheating
chase or construct the fire-water A steep pump curve should al- or damage. A well-known danger is
pumping system and the fire-water ways be avoided. As a rough indica- one pump operating at higher flow,
distribution system using proper tion, the average slope of a fire-wa- forcing another pump to operate at
materials (for instance, selecting ter pump curve should preferably lower flow; operation at lower flow
suitable corrosion-resistant mate- be around 1020% (for instance, an can be damaging to the pump.
rials or proper protective coatings), average slope of 1/10 up to 1/5). When fire-water pumps are oper-
because untreated raw water (such Fire-water pumps can idle ated in parallel, the pump with the
as seawater) could be used as the against closed valves for a short lowest head may work at a reduced
secondary source for extra fire-wa- period of time. In other words, for a flowrate. In this way, the pump
ter capacity, in the case of an unex- short time, the pump should be able could work far from the best effi-
pected fire event. If this happens, to operate in a closed water system ciency point with a very low effi-
the fire-water system should be without any fire-water application. ciency, high friction and heat gener-
flushed with treated water after the Check valves should be provided ation, which can result in damage.
incident, to remove residual traces at both the discharge and the suc- Even in identical fire-water pumps,
of untreated source water. tion. The rated pressure of a fire- pumps that have been in use for
water pump could be 430 barg. more hours (and thus has probably
Selecting fire-water pumps Single-impeller centrifugal pumps been subjected to more wear), pumps
Centrifugal pumps with a rela- (for applications that require pres- with minor defects, and pumps with
tively flat characteristic perfor- sure below roughly 12 barg), and slightly lower speed could all be
mance curve (a graph of head ver- multi-impeller centrifugal pumps subjected to a reduced flow, which
sus flowrate) are generally selected (for higher-pressure systems) are can create problems during an ac-
for fire-water pumps. Ideally, the also commonly used. tual fire event. Because of this ef-
head should rise continuously from The differential pressure of a fect, operators should rotate pumps
the rated point to the shutoff point, pump is proportional to both the over time, so that each pump works
with only a small increase of head square of the rotating speed and as the main fire-water pump for
(say, a 915% rise of the head from the square of the impeller diameter. some period of time; this can help to
rated point to shutoff point). These A discharge pressure of around 10 ensure even wear patterns among
pumps can provide a steady, stable barg can be obtained by a relatively identical pumps in service. Individ-
flow of water at a relatively uniform large, single-impeller pump (with a ual protection against the minimum
pressure over a wide range of re- suitable speed). flow (to ensure a minimum flow for
quired fire-water flowrates. Overhung (OH) pumps have been each pump) is recommended.
A relatively flat performance used for small- and medium-sized Monitoring of the differential
curve is always encouraged for cen- fire-water pumps. Users should temperature of each pump can pro-
trifugal fire pumps for the following consider the between-bearing (BB) vide valuable insight for estimating
reasons: pump design when size, power rat- the parallel operation issue (the re-
54 CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM DECEMBER 2014
Environmental Manager

duced-flow problem) and resulting ing details. However, in this au- be considered for pumps above the
inefficient operation (overheat). In thors view, NFPA 20 should be con- 350-kW range.
case of reduced flow, the differential sidered as a minimum requirement
temperature (the discharge temper- for a fire-water pump. For critical Fire-water pump arrangement
ature minus the suction tempera- fire pumps, the well-known API- The location for fire-water pumps
ture) would rise and could indicate 610 pump standard [2] is addition- should be selected carefully to mini-
such a malfunction. ally applied. mize various risks and potential
Because of small leakage and hazard situations. Explosions or
small consumption of fire water, the API-610 fire-water pumps high-hazard fires are major con-
pressure in a fire-water network The API-610 pump standard is used cerns, which can disable fire-water
could decrease slightly. Fire-water to ensure the reliable operation of pumps. Ideally, there should be
pump systems are usually designed high-performance pumps, mainly in 4080 m of clearance between fire-
in a way that spare pumps should the oil-and-gas, petroleum refinery water pumps and a hydrocarbon
be started if fire-water pressure and petrochemical sectors. The API- or chemical process unit or storage
dropped below a certain level. How- 610 is usually considered to be the area. This limit should also be re-
ever, a slight pressure drop should minimum specification for pumps spected for some utility areas, such
not lead always to the startup of a that handle hazardous, flammable, as a power-generation units, gas-
large fire pump, as this could result toxic and explosive liquids since compression units, oxygen-genera-
in many unnecessary on-off oper- any reliability issue associated with tion units, and similar.
ating cycles of the main fire water these pumps could result in a poten- The possibility of an unconfined
pump (Figure 2). tial disaster. API-610 pumps are also vapor-cloud explosion is one of the
On the other hand, small pres- very popular in applications with main concerns, as this could disrupt
sure changes resulting from varia- extreme temperatures, including utilities, damage major support fa-
tions in fire-water consumption pumps for both high-temperature cilities, and damage the fire-water
during a fire incident can result in service (such as boiler-feed-water, or pumping system. Generally, there
an unstable operation of the main BFW, pumps) and low-temperature is a great possibility of the electri-
fire-water pump(s). For instance, applications (for example, pumps cal network or the steam-distribu-
this may lead to unnecessary fast used in liquid petroleum gas (LPG) tion system failing in the event of
changing of the operating point of a liquefied oxygen, and liquefied natu- a major explosion or extensive fire
large pump, which can result in per- ral gas (LNG) service). For critical event. This underscores the critical
formance and reliability issues. (high-risk) CPI units, fire-water role of independent, diesel-engine-
Smaller-capacity pumps (known as pumps are usually specified to com- driven fire-water pumps. Fire-wa-
jockey pumps) are usually employed ply with the API-610, to ensure that ter diesel engines should generally
in conjunction with the main pump(s) they are able to achieve a high re- comply with NFPA 37 [3].
to maintain a relatively constant fire- liability level the same as other Regarding the diesel fuel-tank ca-
water pressure. Jockey pumps usu- pumps in the unit. pacity, typically, a 12-h duration is
ally initiate operation after a rela- Engineers often struggle with specified as the minimum require-
tively small pressure drop (say 0.51 whether or not to use API-610- ment. However, some critical CPI
bar) in a fire-water system. compliant fire-water pumps for plants require 24-h-capacity fuel
Main fire-water pumps are typi- a CPI plant. This decision would tanks for each fire-water pump-die-
cally electrically driven and the depend on the application, pump sel engine.
spare (backup or reserve) fire-water head, power rating, capacity, pump Meanwhile, each diesel engine
pumps are typically driven by die- speed and expected reliability. The should be provided with independent
sel engine. A commonly used ar- main variable is CPI service (the auxiliaries and accessories, includ-
rangement for critical CPI facilities CPI plant and expected reliability). ing a dedicated fuel system and fuel
is to install six fire-water pumps, For instance, for critical units han- tank. The startup of the engine is
including two electric-motor-driven dling flammable liquids and gases, commonly managed by a battery sys-
pumps, two diesel-engine-driven API-610-compliant fire-water pumps tem (with two independent barriers).
pumps and two jockey pumps. Fire- are often preferred. The failure of a diesel engine is
water pumps are nearly always pro- For a fire-water pump with dif- usually the result of a problem with
vided on a prefabricated skid. This ferential pressure more than 20 one of the auxiliary systems. Major
packaging concept can help to ease bar, API-610 is usually specified. reasons for such a failure include
the alignment and installation is- The pump power rating is a bit fuel-system issues, a lubrication-
sues and ensure high reliability. tricky, since there are many non- system problem, a starting issue,
As noted earlier, the fire code API fire-water pumps available a wiring problem or component fa-
NFPA 20 is dedicated to fire-water (with successful references) that tigue. Only clean, high-quality die-
pumps. It specifies proper require- are intended for high power ranges sel fuel should be used, and special
ments for pump tests, pump per- in a wide array of industry applica- attention is required for the lubri-
formance curves, pump accessories tions. As a general rule of thumb cation oil selection and supply.
and auxiliaries, and some packag- for many CPI plants, API-610 can Proper overhauls and repairs
CHEMICAL ENGINEERING WWW.CHEMENGONLINE.COM DECEMBER 2014 55
Environmental Manager

are required, just like for any other dition to the conventional fire-water tightening) is to install dial indica-
properly designed combustion en- pumps to supply seawater (for tors (or other types of indicators)
gines. Experience has shown that CPI plants located at the coastal re- that monitor movements in critical
the diesel-engine-driven, fire-water gions) or other sources of untreated parts of the machinery train. Usu-
pump is the most reliable option raw water (such as untreated water ally, two dial indicators are used to
currently available for severe loss from a lake or water wells), to observe movement in each machin-
incidents in a CPI plant. The reli- quickly supply additional capacity ery component (such as the driver,
ability and availability of micro- to the plants fire-water network. the fire-water pump and the gear
turbines (small gas turbines in the For a seawater-based emergency unit, if any) compared to the base-
50400 kW range) could be higher fire-water pumping system, the plate or foundation (the main pur-
than diesel engines, but their ef- pumps are usually submerged in pose is to identify improper support
ficiencies are relatively lower (in seawater. For some locations, the of machinery, called soft-foot).
terms of lower operating duration seawater level may fluctuate from Two dial indicators can be used
with the same amount of fuel). Cur- 7 m to +16 m. Considering that to monitor critical bearing housing
rently they are not popular for fire- there is often a long distance from movements in the fire-water pump
water pump systems. the sea to the CPI facility, these fire- (usually in x and y directions). Ac-
Fire-water pumps are typically water pumps should be designed ceptable movements should be
arranged for both manual and au- to produce a relatively high head. below 0.04 mm (40 micrometers) to
tomatic startup. Automatic startup These special fire-water pumps are ensure a proper piping-pump con-
is expected to happen rapidly, in a usually multi-impeller pumps. Prop- nection. A similar limit should be
very reliable manner, once a fire erly designed highly reliable pumps applied to movements in all critical
event has been detected. Fire-water are always specified for such com- pump train locations (such as bear-
pumps are usually stopped manu- plex service. Electric-motor-driven ing housing, coupling, machinery
ally at the pumps local control submersible pumps, or sometimes support and others), and suction and
panel. In other words, operator in- hydraulic-driven pumps are used discharge nozzle flanges (in terms
tervention is usually used to turn for these special applications. These of limiting deformations in all direc-
off the pump, once the situation has are usually down-hole, vertical tur- tions). For special fire-water pumps,
stabilized and the fire is out. bine-type pumps. depending on the machinery design,
A suitable enclosure (or building) In some cases, local regulations speed, power rating and applica-
should be provided for fire-water or plant specifications require three tions, a limit higher or lower than
pumps. Sufficient reinforcement dedicated fire-water pumps (as the the above-mentioned (0.04 mm)
should be considered for the fire- minimum) for special CPI applica- may be specified. n
pump enclosure. This is very im- tions (such as CPI plants that han- Edited by Suzanne Shelley
portant. For example, in the case dle highly explosive or highly flam-
of a major earthquake, fire-water mable materials). In such cases, one References
pumping systems need to be fully of the main concerns is personnel 1 NFPA 20, Standard for the Installation of Sta-
tionary Pumps for Fire Protection, National
operational to respond to fire events safety during a major fire case and Fire Protection Assn. (NFPA), 2013.
resulting from the earthquake. An provisions must be made to ensure 2 API 610, Centrifugal Pumps, American Petro-
open-sided shelter is not recom- a safe personnel evacuation. leum Inst. (API), 2009.
3 NFPA 37, Standard for the Installation and
mended. And, fire-water pumps Use of Stationary Combustion Engines and
should be located at a higher eleva- Installation and commissioning Gas Turbines, National Fire Protection Assn.
(NFPA), 2014.
tion than the majority of the CPI The piping installation and connec-
facility and upwind of it. tion to a fire-water pump can lead
Author
To provide another layer of protec- to relatively high loads on the pump Amin Almasi is a rotating-
tion (in order to avoid common fail- nozzles and to the pump trains sen- equipment consultant in Aus-
tralia (Email: amin.almasi@
ures), the main fire-water pumps, sitive components, such as bearings, ymail.com). He previously
and any other reserve or support- coupling and rotating assemblies. worked at Worley Parsons Ser-
vices Pty Ltd. (Brisbane, Aus-
ing fire-water pumps should not be The fire-water pumps are often tralia), Technicas Reunidas
located immediately next to each left on standby, therefore any high (Madrid, Spain) and Fluor
Corp. (various offices). He
other. Locating fire-water pumps at nozzle loads or misalignment might holds a chartered professional
two separate locations can improve be left unchecked. This can poten- engineer license from Engi-
neers Australia (MIEAust
both the fire-water system reliabil- tially wreck the pump in the first CPEng Mechanical), a chartered engineer cer-
tificate from IMechE (CEng MIMechE), RPEQ
ity and overall fire-water network hours of operation in the event of (registered professional engineer in Queensland)
hydraulic behavior. fire. Periodic checks are important. and he also holds M.S. and B.S. degrees in me-
chanical engineering. He specializes in rotating
A well-known method to monitor machines including centrifugal, screw and recip-
Special fire-water pumps the movements and deformations of rocating compressors, gas and steam turbines,
pumps, condition monitoring and reliability. Al-
For critical CPI plants, additional critical machinery components dur- masi is an active member of Engineers Australia,
emergency (or reserve) firewater ing the piping connection (piping IMechE, ASME, Vibration Institute, SPE, IEEE,
and IDGTE. He has authored more than 60 pa-
pumps should be provided in ad- flange and machinery flange bolt pers and articles dealing with rotating machines.