Está en la página 1de 2

Project Location: Sheet

Initial Date Amorato Stadium, Don Alejandro Roces Avenue, Quezon City Proj.no 11
Raised by 3 Scale
(100m )
Designed MJRI 7/20/2017 Description: Rev. No 0
Checked VVCJr 7/20/2017 MANILA WATER EMERGENCY RESERVOIR PROJECT Dwg/Calc No.
Approved
Calculation Procedure

Seismic Design Parameters: (NSCP 2015 7th Edition, Volume 1)


Soi Profile Type, SC Very Dense Soil and Soft Rock
Seismic Zone Zone 4
Distance to known Seismic Source (see Figure 1) 5.8 km
Near Source Factor: Na (from linear interpolation) 1.160
Near Source Factor: Nv 1.000
Seismic Coeffiecient, Ca (0.4N a ) 0.464 (PGA)
Seismic Coeffiecient, Cv (0.56N v ) 0.56

Estimate the expected free-field ground strains (NCHRP Report 611)


Seismic Consideration - Seismic propagates perpendicularly to the structures
max = max/Gm

where: max = (PGA/g) v Rd


maximum earthquake-induced shearing stress
2
= 87120.47 lb/ft
PGA = 0.464g peak ground acceleration
2
g = 9.81 m/s gravitational constant

v = s(H + D) total vertical overburden pressure at the depth


2 corresponding to the invert of the vessel
= 1893 lb/ft (90.58) kPa
3
d = 114.680 lb/ft (18) kN/m^3 unit weight of fill
H = 6.560 ft (2000) mm height of fill above the top of vessel
D = 9.945 ft (3032) mm vessel oustide diameter
Rd = 1.0 - 0.00233*z for z < 30ft
depth-dependent stress reduction factor
= 1.174 - 0.00814*z for 30ft < z < 75ft
Rd = 0.973
z = 11.532 ft (3516) mm depth to the midpoint of the vessel
Gm = Vs effective, strain compatible shear modulus of
2
= 4969309.349 lb/ft the ground surrounding the vessel

= d/g

= 3.564 lb-s2/ft4 unit mass of soil


2
g = 32.18 ft/s gravitational constant

Vs = 1180.8 ft/s (360) m/s shear wave velocity (see Figue 2)

max = 0.018
maximum earthquake-induced shearing stress

Maximum free field diameter change


DEQ-FF = 0.5 max D
= 1.046 in (26.571) mm diameter change in ground
Alllow Ovality = 5%D
= 5.97 in
Capacity of section is safe against ovality from seismic load.
Project Location: Sheet
Initial Date Amorato Stadium, Don Alejandro Roces Avenue, Quezon City Proj.no 11
Raised by 3 Scale
(100m )
Designed MJRI 7/20/2017 Description: Rev. No 0
Checked VVCJr 7/20/2017 MANILA WATER EMERGENCY RESERVOIR PROJECT Dwg/Calc No.
Approved
Calculation Procedure

Figure 1. Showing the distance of Structure from the Nearest Fault Line

Figure 2. Soil Profile Types