Está en la página 1de 1

Performance Summary for FCU-5

Project: jpmc 05/12/2017


Prepared By: 10:13AM

42GW Cassette Fan Coil with Variable Speed Motor


System Operation: 2 Pipe Cooling Only

Selection Conditions 42GW709CC----


Cooling Mode
Room Air Temperature (db): 26.1 C
Room Air Relative Humidity: 44.2 %
Entering Fluid Temperature: 6.0 C
Fluid Delta T: 6.0 K
Fluid Type: Water

Sound Attenuation
Room Attenuations: 9.00 dB

Performance 42GW709CC----

Fan Speed Low Medium High


Speed Speed Speed
Cooling
Variable Speed V 2.0 2.0 4.0 6.0 8.0 10.0
Air Flow Rate m3/h 601 601 839 1080 1339 1598
Cooling Mode
Total Capacity kW 3.66 3.66 4.80 5.98 7.38 8.99
Sensible Capacity kW 3.03 3.03 4.01 5.02 6.20 7.52
Supply Air Temperature C 11.9 11.9 12.6 13.0 13.1 12.9
Fluid flow rate m3/h 0.52 0.52 0.69 0.86 1.06 1.29
Fluid Pressure Drop kPa 3 3 4 7 10 15
Electric Motor Consumption W 11 11 25 40 77 115
FCEER Class A
Noise level
Lw:Sound power level dB(A) 40 40 46 52 57 61
Lp:Sound pressure level dB(A) 31 31 37 43 48 52
NC level dB(A) 23 23 30 36 41 45
NR level dB(A) 25 25 32 38 43 47
Dimensions (HxWxD) mm 302x822x879

Note:
Sound Power Levels according to ISO 3741. Sound pressure level, NR and NC are based upon hypothetical acoustic attenuation for the room and air diffusion sub-
system.
The accuracy of the above data is +/-2dB(A). All dimensions include Water valve factory fitted as maximum unit dimensions, for installation safety.
If the product is supplied without a Carrier control device, verification of EMC conformity is the responsibility of the installer or control integrator.

CARRIER participates in the ECP program for Fan Coil Units (Ducted and non Ducted). Check ongoing validity of certificate: http://www.eurovent-
certification.com

EMEA Fan Coil Builder 3.05 Page 1 of 1