Está en la página 1de 11

Moulded Case Circuit Breakers

NM7
2. Type designation
N M 7 /

Types of quadrupole circuit breakers:


A-N pole with no over-current
release component,
N pole always on;
B-N pole with no over-current
release component,
N pole to be closed and opened
NM7 together with the other three poles
(N pole closed first and then opened);
Moulded Case Circuit Breaker C-N pole with over-current release
component,
1. General
N pole to be closed and opened
After successively developing NM8 and NM6, our company together with other three poles
launched another new product, the NM7 series moulded (N pole closed first and then opened);
case circuit breaker upgraded from the NM1 series, by
further taking the structural features and design style of the Codes for applications: nothing for
NM1 series products, modifying the accessories, wiring distribution; 2 for motor protection
mode, appearance and the like in an individualization way,
allowing the product not only to be set by the manufacturer Release (of a mechanical switching device)
before delivery but also replaced by users themselves, which mode and accessory code (see table 1)
is really an improvement, and integrating the up-to-date
design concept to make the product more people-oriented. Number of poles

Certificate: KEMA, CE.


Rated operation range 10A~1600A. Breaking capacity codes:
Several modes available: 3P, 4P, fixed type, C economic type, S standard type
plug-in type, H relatively high type, R current limiting type
front connection, rear connection.
The product can be installed vertically or horizontally. Frame size rated current
Isolating function is available.
This product meets the requirements in
S:Intelligent stype,blank:thermal magnetic
IEC 60947-2.

Design serial number

Moulded case circuit breaker

Company code

67 >> Empower the World


Moulded Case Circuit Breakers
NM7
3. Operating conditions
3.1 Ambient air temperature
3.2 The upper limit for the ambient air temperature is+40,
lower limit -5, and the average temperature is not higher
than+35 within 24 hours. Ambient temperature

3.3 Altitude: not higher than 2000m for the installation site.
3.4 Atmospheric conditions:
When the ambient air temperature is +40, the relative
humidity of the air shall not be higher than 50%; a higher

2000m
relative humidity is allowed at a lower temperature;
Altitude
for the wettest month, the maximum relative humidity
averaged shall be 90% while the lowest temperature
averaged in that month 25, and the condensation
produced due to temperature change shall be taken into
consideration.
3.5 Class of pollution: 3 No Pollution

Table 1
Accessory code Accessory installation and mode of wirings

Accessory name Compound NM7-125 NM7-250 NM7-400, 630 NM7-800 NM7(S)-1600


release
3P 4P 3P 4P 3P 4P 3P 4P 3P 4P

No accessories 300

Alarm contact 308

Shunt release 310

Auxiliary contact 320

Under voltage release 330

Shunt release,
340
auxiliary contact

Shunt release,
350
under voltage release
Two groups of
360
auxiliary contacts

Auxiliary contact,
370
under voltage release

Shunt release,
318
alarm contact

Auxiliary contact,
328
alarm contact

Under voltage release,


338
alarm contact

Shunt release, auxiliary


348
contact, alarm contact

Two groups of auxiliary


368
contacts, alarm contact

Auxiliary contact, under


378
voltage release, alarm contact

Note: a. 200 for the breaker body only with the magnetic release;
300 for thermal release + magnetic release body;
000 for the breaker body with no release and inner accessory.
b. alarm contact; auxiliary contact; shunt release; under voltage release.

Empower the World >> 68


Moulded Case Circuit Breakers
NM7
4. Technical data

NM7 NM7-125
Rated currentIn(A) 16,20,25,32,40,50,63,80,100,125
Rated insulation voltage Ui(V) 800
Rated impulse withstand voltage Uimp(kV) 8
Rated operational voltage Ue(V) 380/400/415

Appearance

Breaking capacity feature code S


Number of poles 3 4
Rated ultimate short circuit breaking AC380/400/415V 35 35
capacityIcu(kA) AC690V - -
Rated service short circuit breaking AC380/400/415V 17.5 17.5
capacityIcs(kA) - -
AC690V
Service life Mechanical 25000
(C-O cycle) Electric 8000
Usage category

Overall dimensions 3P(LWH) 1559074


(mm) 4P(LWH) 15512074
Isolating function
Front connection panel
Rear connection panel *
Cage type connection terminal *
Plug-in type *
Draw-out type *
Rotary manual operating handle
Motor driven operating handle
Shunt, under voltage release
Auxiliary, alarm contact
Terminal cover *

Note: Standard configuration Selected configuration; the one with * is unconfiguration.

69 >> Empower the World


Moulded Case Circuit Breakers
NM7

NM7-250
100,125,160,180,200,225,250
800
8
380/400/415

S
3 4
35 35
- -
17.5 17.5
- -
20000
2500
A
16510574
16514074


*
*
*
*




*

Empower the World >> 70


Moulded Case Circuit Breakers
NM7

NM7 NM7-400
Rated currentIn(A) 250,315,350,400
Rated insulation voltage Ui(V) 800
Rated impulse withstand voltage Uimp(kV) 8
Rated operational voltage Ue(V) 380/400/415/690

Appearance

Breaking capacity feature code S H


Number of poles 3 4 3 4
Rated ultimate short circuit breaking AC380/400/415V 50 50 65 65
capacityIcu(kA) AC690V - - 12 12
Rated service short circuit breaking AC380/400/415V 25 25 32.5 32.5
capacityIcs(kA) - - 6 6
AC690V
Service life Mechanical 4000
(C-O cycle) Electric 1000
Usage category A
Overall dimensions 3P(LWH) 257150107
(mm) 4P(LWH) 257198107
Isolating function
Front connection panel
Rear connection panel *
Cage type connection terminal *
Plug-in type *
Draw-out type
Rotary manual operating handle
Motor driven operating handle
Shunt, under voltage release
Auxiliary, alarm contact
Terminal cover *

Note: Standard configuration Selected configuration; the one with * is unconfiguration

71 >> Empower the World


Moulded Case Circuit Breakers
NM7

NM7-630 NM7-800 NM7(S)-1600


400,500,630 500,630,700,800 800,1000,1250,1600
800 800 800
8 8 8
380/400/415/690 380/400/415/690 380/400/415/690

S H S H S H
3 4 3 4 3 4 3 4 3,4
50 50 65 65 50 50 75 75 50 65
- - 15 15 - - 15 15 - 20
25 25 32.5 32.5 25 25 37.5 37.5 37.5 50
- - 7.5 7.5 - - 10 10 - 20
4000 2500 2500
1000 500 500
A A A
280182112 275210112 406210146
280240112 275280112 406280146


* *
* *
*
*




* * *

Empower the World >> 72


Moulded Case Circuit Breakers
NM7
5. Inverse-time overcurrent protection curve for the
breaker for distribution (see Fig. 1 10)
Fig.1 NM7-125(16A~32A) operation characteristic curve Fig.2 NM7-125(16A~32A) temperature compensation curve
10000
7200
3600 130
1200
600 120
300
Tripping time(S)

Rated current(%)
120
60 110
30
20
100
10
5
2 90
1
0.5
0.2 80
0.1
0.05
0.02
-5 0 10 20 30 40 50 60

1 2 3 4 5 78 12 20 Ambient temperature ()
Rated current times

Fig.3 NM7-125(40A~125A) operation characteristic curve Fig.4 NM7-125(40A~125A) temperature compensation curve
10000
7200
3600 130
1200
600 120
300
Tripping time(S)

Rated current(%)
120
60 110
30
20 100
10
5
2 90
1
0.5
0.2 80
0.1
0.05
0.02 -5 0 10 20 30 40 50 60

1 2 3 4 5 78 12 20 Ambient temperature ()
Rated current times

Fig.5 NM7-250 operation characteristic curve Fig.6 NM7-250 temperature compensation curve
10000
7200 130
3600
1200 120
600
Rated current(%)

300
Tripping time(S)

120 110
60
30
100
20
10
5 90
2
1
0.5 80
0.2
0.1
0.05
-5 0 10 20 30 40 50 60
0.02

Ambient temperature ()
1 2 3 4 5 78 12 20
Rated current times

Fig.7 NM7-400 operation characteristic curve Fig.8 NM7-400 temperature compensation curve

10000 130
7200
3600
1200 120
Rated current(%)

600
300
120 110
Tripping time(S)

60
30
20 100
10
5
2 90
1
0.5
0.2 80
0.1
0.05
0.02
-5 0 10 20 30 40 50 60
1 2 3 4 5 78 12 20
Ambient temperature ()
Rated current times

73 >> Empower the World


Moulded Case Circuit Breakers
NM7

Fig.9 NM7-630 operation characteristic curve Fig.10 NM7-630 temperature compensation curve
10000
7200
3600 130
1200
600 120
300

Rated current(%)
120
Tripping time(S)

60 110
30
20
10 100
5
2 90
1
0.5
0.2
80
0.1
0.05
0.02
-5 0 10 20 30 40 50 60
1 2 3 4 5 7 8 12 20
Ambient temperature ()
Rated current times

Fig.11 NM7-800 operation characteristic curve Fig.12 NM7-800 temperature compensation curve
10000
7200 130
3600
1200
600 120

Rated current(%)
300
Tripping time(S)

120 110
60
20 100
10
5
2 90
1
0.5
0.2 80
0.1
0.05
0.02
-5 0 10 20 30 40 50 60
1 2 3 4 5 7 8 12 20
Ambient temperature ()
Rated current times

Fig.13 NM7-1600 operation characteristic curve Fig.14 NM7-1600 temperature compensation curve

10000
7200
3600 130
1200
Rated current(%)

600 120
300
Tripping time(S)

120
60 110
30
20
100
10
5
2 90
1
0.5
0.2 80
0.1
0.05
0.02 0 10 20 30 40 50 60 70

Ambient temperature ()
1 2 3 4 5 7 8 12 20
Rated current times

Empower the World >> 74


Moulded Case Circuit Breakers
NM7
Fig.15 NM7S-1600 tripping characteristic curve

10000

5000

IR=0.4~1In
1000
500
200

TR=3~18S
50
20
0
t(s) 30
5 Isd=1.5~8In

2
1

0.5
0.2
0.2 0.15
0.1 0.1
0.06 Ii=2~12In
0.05

0.02
0.01
0.05 0.1 0.3 0.5 1 2 3 4 56 8 10 30 50 80 200 300
0.2 0.4 40 60 100
I/In xln

6. Overall and mounting dimensions


NM7-125

96
74
120(4P) 70
90(3P) 61.5
30 30 30 24.5

1 3 5 N

23
102
155
135

132
45

29

2 4 6 N

30(3P)
60(4P)

NM7-250

96
74
140(4P) 70
105(3P) 61.5
35 35 35 24.5

1 3 5 N

22 29
102

126
165
145

50

2 4 6 N

35(3P)
70(4P)

75 >> Empower the World


Moulded Case Circuit Breakers
NM7
NM7-400

160
200(4P) 107
150(3P) 106
98.5
52.5 48 52.5
48

1 3 5 N

150
90

194
311
257
225

50

2 4 6 N

28 44(3P)
45.5
94(4P)

NM7-630
165
112
240(4P)
182(3P) 110
103
58 58 58
52

1 3 5
160
92
280
245
405

210

50

2 4 6

50 58(3P)
116(4P)

NM7-800

169
112
280(4P) 105.5
210(3P) 95
70 70 70 41.5

1 3 5 N
329.5

240.5

221

243
275

88

67

2 4 6 N

70(3P)
140(4P)

Empower the World >> 76


Moulded Case Circuit Breakers
NM7
NM7(S)-1600

280(4P)
210(3P) 210
146
70 70
11 172 37

81

378
201
406
545

690
468
100

35
22

46
70(3P)
50 22 140(4P)
37

140

7. Ordering information
Users shall order goods in the following way:
Product type + rated current + code of the inner accessory (00 for no inner accessories) + application code + operation mode + (word
description, accessory voltage, type and the like to be described in detail).
Order Sample: 10 pcs of NM7250S, 250A, three poles, shunt release (AC230V), for motor protection, power operating mechanism
(DC220V), plug-in type.10 pcs of NM7250S/250/3310 2 D (shunt AC230V, power operating mechanism DC220V, plug-in type).

77 >> Empower the World