VSC Rectifier
Chunyi Guo, Chengyong Zhao Xiuyu Chen
School of Electrical and Electronic Engineering Dept. of Electrical and Computer Engineering
North China Electric Power University University of Manitoba
Beijing, China Winnipeg, Canada
chunyiguo@gmail.com, chengyongzhao@ncepu.edu.cn cxy.ncepu@gmail.com
AbstractA dual-infeed HVDC with LCC inverter and VSC but not at the same busbar. References [7]-[8] studied the
rectifier at the same busbar is investigated. The impact of VSC interaction between LCC inverter and LCC rectifier in the
rectifier on LCC inverter is quantified by the Apparent multi-infeed HVDC system, and the results show that the
Increase in Short Circuit Ratio or AISCR index. Then, steady rectifier will help inverter to improve its maximum available
state and transient aspects, such as the maximum available
power and immunity to commutation failure. In this paper, a
power (MAP), temporary over-voltage (TOV), "Commutation
Failure Immunity Index" (CFII), and fault recovery dual-infeed HVDC with LCC inverter and VSC rectifier at
performance are considered in the system performance analysis. the same busbar will be investigated. In China, a 5-terminal
The results show that, the VSC rectifier has the ability to VSC-HVDC system will be commissioned in Zhejiang
improve the maximum available power, regulate the ac voltage, Province by State Grid Corporation of China (SGCC) in 2014.
and enhance commutation failure immunity of LCC inverter. One of its VSC converters locates close to the inverter of
Moreover, compared with the dual-infeed HVDC with VSC and Luchaogang-Shengsi LCC-HVDC project, as shown in
LCC both inverters, the VSC rectifier provides more Figure 1. The real power between Shengsi-island and
contribution to the performance improvement of LCC converter. Qushan-island can be bidirectional, thus it is meaningful to
Index Terms-- Apparent Increase in Short Circuit Ratio; Dual-
analyze the interaction between LCC inverter and VSC
Infeed HVDC; Line Commutated Converter; Voltage Source rectifier.
Converter
LuchaoGang
I. INTRODUCTION
Line Commutated Converter High Voltage Direct
Current (LCC-HVDC) has been wildly used in many areas, Shengsi
such as asynchronous ac grid connection, long distance bulk Island
Yangshan
power transmission, etc.. However, if the short circuit ratio Island
(SCR) of ac network is low, the LCC-HVDC system would
have poor voltage regulation ability and be susceptible to Qushan
Island
commutation failure [1].
Nowadays, Voltage Source Converter based High Daishan
Voltage Direct Current (VSC-HVDC) have been developing Island
rapidly because of its advantages, including independent and
fast control of active and reactive power, no need for reactive
power support, ability to feed power into passive networks, Zhoushan
Island
and so on[2]-[3].
In previous work, a dual-infeed HVDC system with
LCC inverter and VSC inverter infeeds on the same busbar
are analyzed, and an effective index called Apparent Figure 1. One example of dual-infeed HVDC system
Increase in Short Circuit Ratio (AISCR) was proposed to
In this paper, the dual-infeed HVDC system(one is LCC
quantify the impact of VSC inverter on LCC inverter[4]. One
inverter, and the other is VSC rectifier) is studied. And the
of the examples is the Skagerrak 4 VSC-HVDC link, between
impact of VSC rectifier on LCC inverter is evaluated by the
Norway and Denmark [5]. Reference [6] focused on the
AISCR index. Then the maximum available power (MAP),
situation that VSC inverter is located close to LCC inverter
temporary over-voltage (TOV), "Commutation Failure
1.4
1.2
1.1
Figure 2. Dual-infeed HVDC scheme with VSC rectifier and LCC inverter 1
Ud,Id: DC voltage and DC current of LCC-HVDC; Figure 3. MAPs of LCC with varying SCR
U : Line to line voltage at Ac busbar;
XT: Transformer leakage reactance of LCC-HVDC;
3.2 MAP of LCC with VSC rectifier infeed
T: Transformer turns ratio of LCC-HVDC;
Bc,Qc: Equivalent admittance and Reactive power of the When the real power absorbed by 328 MVA VSC-HVDC
filters and compensator for LCC-HVDC; varies from 0 to 0.328 pu (full load), the MAP values of
Ud2, Id2: DC voltage and DC current of VSC-HVDC; 1000MW LCC-HVDC system can be obtained as in Figure 4,
Pd2, Qd2: DC real and reactive powers of VSC-HVDC; by solving the equations presented in Appendix. For
T2: Transformer turns ratio of VSC-HVDC; validation purposes, the results from electromagnetic
Z: System equivalent impedance; transient (EMT) simulation are also presented indicated by
E0 : System electromotive force (emf). the dark squares. The good agreement validates the analytical
In the Figure 2, the LCC-HVDC system is rated at 1000 calculations.
MW, operated in constant current control mode at the rectifier Generally, the MAP of the LCC decreases, as the
side and constant extinction angle control mode at the inverter absorbed active power by VSC is increased. However, it is
side. The data is as in the First CIGRE HVDC Benchmark interesting that slight MAP increase of LCC can be observed
model[9]. The VSC-HVDC system is rated at 300 MW at the VSC real power range of 0-0.05p.u.. There are two
(328MVA), operated in constant DC voltage control and ac factors affecting MAP of LCC, 1) remaining reactive power
voltage control modes at the inverter side, and constant real
of VSC-HVDC, 2) the amount of absorbed active power by
power control and constant ac voltage control modes at the
VSC-HVDC from receiving AC system. If VSC-HVDC
rectifier side. With the VSC-HVDC link blocked, the SCR at
the receiving ac system is 2.5 based on 1000MW rated absorbs more power from receiving AC system, it will
capacity. apparently reduce the active power supplied by LCC-HVDC
to AC system, and increase the MAP of LCC-HVDC
III. INVESTIGATION OF APPARENT INCRASE IN SCR indirectly. Thus, these two factors have opposite effects
resulting in the slight MAP increase of LCC at the PVSC range
The Apparent increase in SCR (AISCR) is a measure of
of 0-0.05p.u..
the increase in short circuit ratio (SCR) for the LCC-HVDC
3) with VSC rectifier. The results are shown in Table 1. With
1.28
VSC inverter or rectifier infeeds, TOV at the common busbar
1.26 are both suppressed. Meanwhile, the reduction in TOV is
1.24 particularly improved with VSC rectifier (1.08 pu) than with
VSC inverter (1.15 pu).
1.22
MAP of LCC-HVDC(p.u.)
Qd = P d tan (4)
cos + cos( + )
cos = (5)
2
Pac = 1 Z U 2 cos EU cos( + ) (6)
Qac = 1 Z U 2 sin EU sin( + ) (7)
Figure 6. Fault recovery performance of LCC inverter unfer single-line to
ground fault Qc = BcU 2 (8)
Pd Pac = 0 (9)
Qd + Qac Qc = 0 (10)
Pd Pd 2 Pac = 0 (11)
Real Power (p.u.)
Qd + Qac Qc Qd 2 = 0 (12)
2 2 2
Pd 2 + Qd 2 (U I max ) (13)
Where, Imax is the maximum current through the VSC
converter corresponding to the MVA capacity.
REFERENCES
[1] E. Rahimi, A. M. Gole, J. B. Davies, I. T. Fernandot, and K. L. Kent,
Commutation failure in single- and multi-infeed HVDC systems, in
Figure 7. Fault recovery performance of LCC inverter under three-phase to Proc. 2006 IEE International Conference on AC and DC Power
ground fault Transmission, pp. 182-186.
[2] N. Flourentzou, V. G. Agelidis, and G. D. Demetriades, "VSC-Based
HVDC Power Transmission Systems: An Overview," IEEE Trans. on
V. CONCLUSIONS Power Electronics, vol. 24, no. 3, pp. 592-602, Mar. 2009.
In this paper, the operation characteristics of the dual- [3] C. Du, E. Agneholm, and G. Olsson, Comparison of Different
infeed HVDC with LCC inverter and VSC rectifier infeeds on Frequency Controllers for a VSC-HVDC Supplied System, IEEE
Trans. on Power Delivery, vol. 23, no 4, pp. 22242232, Oct. 2008.
the same busbar are analyzed. The AISCR index is then [4] Chunyi Guo, Yi Zhang, A.M. Gole, and Chengyong Zhao, Analysis of
adopted to evaluate the impact of VSC rectifier on LCC Dual-Infeed HVDC with LCC-HVDC and VSC-HVDC, IEEE Trans.
inverter. Then, the MAP, TOV, CFII and fault recovery on Power Delivery, vol. 27, no.3, pp. 1529 - 1537, Jul. 2012.
performance are considered to further investigate the [5] ABB Group. Skagerrak HVDC Interconnections [Online]. Available:
http://www.abb.com/industries/ap/db0003db004333/448A5ECA0D6E1
operation performances of the dual-infeed HVDC with VSC 5D3C12578310031E3A7.aspx, (2011).
rectifier and LCC inverter. From the results, we can get the [6] Chunyi Guo, Chengyong Zhao, Ani Gole and Xiuyu Chen, Apparent
following conclusions: Increase in Short Circuit Ratio (AISCR) as a measure of the impact of
a) Both VSC inverter and VSC rectifier infeeds have VSC converters on LCC converters in Multi-Infeed HVDC systems
with VSC and LCC infeeds, in Proc. 2012 International Conference
positive impact on LCC inverters. on AC and DC Power Transmission, pp.1-4.
b) If the VSC rectifier absorbs more real power from the [7] Chen X, Gole A M, and Han M, Analysis of Mixed Inverter/Rectifier
terminated ac system, the LCC infeed can get larger MAP Multi-Infeed HVDC Systems, IEEE Trans. on Power Delivery, vol.
value, thus the larger AISCR can be obtained. 27, no.3, pp. 1565-1573, Jul. 2012.
[8] Xiuyu Chen, Ani Gole and Chunyi Guo, Multi-infeed HVDC system
c) In the dual-infeed HVDC system, VSC as a rectifier with inverter and rectifier infeeds, in Proc. 2012 International
can provide more contribution for the performance Conference on AC and DC Power Transmission, pp.1-4
improvement of LCC converter than VSC as an inverter. [9] M. Szechtman, T. Wess and C.V. Thio, A benchmark model for
d) With VSC infeeds, the recovery performance LCC HVDC system studies, in Proc. International Conference on AC and
DC Power Transmission, pp. 374-378, 1991.
converter from faults is not improved obviously. However,
the commutation failure immunity of LCC inverter can be
improved.