MATERIAL TAKE-OFF

.NO DESCRIPTION UNIT QTY UNIT PRICE TOTAL PRICE


(S.R.) (S.R.)

ELECTRICAL INSTALLATIONS:-
1
INCLUDE FOR THE COMPLETE INSTALLATION AS
DESCRIBED IN THE SPECIFICATION AND AS SHOWN
ON DRAWING TO GIVE ACOMPLETE SYSTEM THAT
IS ACCEPTABLE TO THE ENGINEER AND LOCAL
AUTHORITIES THE QUANTITIES MENTIONED IN THE
BOQ ARE INDICATIVE FOR THE WORKS INVOLVED
THE TENDERED SHALL ALLOW FOR ALL ITEMS
REQUIRED TO COMPLETE THE WORK TO THE
SATISFACTION OF THE ENGINEER AND LOCAL
AUTHORITIES LIAISE WITH SAUDI ELECTRICAL
COMPANY (SEC) FOR SUPPLYING INCULDING
CONNECTING TO EXISTING ELECTRIC
GRID,CABLES,DUCT BANKS,MANHOLES,ANY CIVIL
WORK,EXCAVATIONS,FINISHING, AND
INSTALLATION OF
MV 13.8/0.4 KV,TRANSFORMER,RMU,AND INCLUDE LOT 1
FOR CONNECTION OF SEC SUPPLIED CABLES TO
1.1 METER CABINET INCLUDING TERMINATION

TRANSFORMER 13.8/0.4 KV ,1000 KVA

2 ELECTRICAL POWER DUCT BANK INCULDING LOT 1


ALL CIVIL WORK AS PER DRAWING AND
SPECIFICATIONS FOR :-

3 ELECTRICAL POWER MANHOLES INCULDING LOT 1


ALL CIVIL WORK AS PER DRAWING AND
SPECIFICATIONS

4 GROUNDING SYSTEM:-

EXECUTION COMPLETE GROUND SYSTEM


FOR THE WORKSHOP INCULDING ALL CIVIL
WORK, AS PER DRAWING AND
SPECIFICATIONS.
1. COPPER GRD.ROD 2440 MM LONGX 20 MM
DIAM.
BARE COPPER SOFT DRAWN CABLE SIZE
120 MM2.
THERMAL WELDING. LOT 1
CONCRETE GRD.INSPECTION PIT AS PER
DRAWING.

TOTAL
Page 1 OF 8
MATERIAL TAKE-OFF

5 LIGHTING FIXTURES AND SWITCHES:-

SUPPLY,INSTALL, CONNECT AND TEST


THE FOLLOWING LIGHTING FIXTURES
ALL ACCORDING TO DRAWING AND ,
SPECIFICATION THE ITEM INCLUDING
CONDUCTING,EMT PIPES,LIGHTING
FIXTURES, WIRRING,CABLES, INCULDING
ANY CIVIL WORK AND ALL FIXING
ACCESSORIES THAT NEEDEDTO PROVIDE
5.1 .PERFECT OPERATION CONDITION
EA 23
FLUORESCENT LAMP , 4 X 20 WATT ,
5.2 220 VOLT, 60 HZ.

METAL HALIDE LAMP 400 WATT , 220 V , 60 EA 87


HZ , TYPE AS PER DRAWING
5.3
DOWN LIGHT 60 W, 220V, 60HZ,. EA 8
WEATHERPROOF WITH COVER.

5.4 FLUO.EXIT SIGN, 1X 20 WATT , EMERGENCY EA 11


BACK-UP FOR 3 HR , TYPE AS PER DRAWING ,
220 VOLTS

5.5 EMERGENCY LIGHTING 2X50 W WITH BACK- EA 12


UP FOR 3H

5.6 WALL MOUNTED LAMP FIXTURE, WEATHER


PROOF, 250W,.H.P.S. LAMP , 220 V.IP65. EA 18

5.7 1 GANG 1-WAY LIGHTING SWITCH. EA 2

5.8 2 GANG 1-WAY LIGHTING SWITCH.. EA 8

Page 2 OF 8
MATERIAL TAKE-OFF
:POWER OUTLETS& SWITCHES
6
RATE AND PRICE SHALL BE SUPPLY AND
INSTALL THE FOLLOWING POWER
OUTLETS INCLUDING WIRING,
CABLES,PIPES EMT,OUTLETS,CONDUITS,
BOXES, PVC OR STEEL, JUNCTION BOXES,
CONNECTORS,CABLES TRAY, ANY CIVIL
WORK ,HANGER/SUPPORTS, ALL
FITTINGS,END BELL, TESTING ,
COMMISSIONING, AND EVERYTHING
REQUIRED FOR A COMPLETE SYSTEM
ACCORDING TO DRAWINGS AND
SPECIFICATIONS.
6.1 EA 20
RECESSED DUPLEX RECEPTACLE ,
220 VOLT, 20 AMP. WITH CONTROL SWITCH 20
AMP.
6.2 EA 1
AS ABOVE BUT GFCI TYPE.

6.3 WATER HEATER OUTLET AND SWITCH. EA 1

6.4 OUTLET ( 32 ) AMP FOR AUTOMATIC DOOR EA 3


SUPPLY , 220 VOLT

6.5 (160) AMP SWITCH, 3 PH., 380 VOLT. FOR A.C EA 8


PU. INCULDING CABLES ,CABLES TRAY,EMT
PIPES,WEATHERPROOF.IP65.

6.6 (32) AMP SWITCH, 3 PH. , 380 VOLT. FOR AIR EA 6


CURTAIN FAN.

6.7 OUTLET AND SWITCH FOR EXHAUST FAN EA 1

6.8 COMBINATION SOCKET 60A ,IP55, INCULDING EA 23


WIRING,CABLES ,CABLES TRAY,EMT PIPES AS
PER DRAWING AND SPECIFICATION

6.9 ELECTRICAL CABLES TRAY , AS PER


DRAWING AND SPECIFICATION, AND LOT 1
EVERYTHING REQUIRED FOR A COMPLETE
SYSTEM ACCORDING TO DRAWINGS AND
SPECIFICATIONS.

Page 3 OF 8
MATERIAL TAKE-OFF
7
:DISTRIBUTION PANELS

RATE AND PRICE SHALL BE SUPPLY AND


INSTALL THE FOLLOWING PANEL
BOARDS INCLUDING SCREW, WASHERS,
NUTS, CLAMPS,BOXES,CONNECTORS,
HANGER/SUPPORTS,DUCT
BANKS,MANHOLES,SLEEVES,EMT
PIPES,CABLES TRAY,ANY CIVIL WORK,
ALL FITTINGS,END BELL, ALL CIVIL
WORK SUCH AS EXCAVATION, DRILLING,
BACK FILLING, CONCRETE AND ANY
ACCESSORIES,
TESTING,COMMISSIONING,AND
EVERYTHING REQUIRED FO A COMPLETE
SYSTEM ACCORDING TO DRAWINGS AND
SPECIFICATIONS.
7.1
CIRCUIT BREAKERS :- LOT 1
MAIN C. BR. ( 1600 ) AMP INSIDE NEMA 1R
ENCLOSURE.IP65.
7.2
MDB:-
EA 1
MAIN BREAKER 1600 AMP / 2000 AF , 3PH , 4
WIRE, 60 HZ, FLUSH OR SURFACE MOUNTED,
BRANCHES :-
800/ 800AMP 3P 1 NOS
400/ 400AMP 3P 1 NOS
300/ 400AMP 3P 1 NOS
200/ 250AMP 3P 2 NOS
160/ 250AMP 3P 1 NOS
100/ 100AMP 3P 1 NOS

7.3
PB-VAC:-
EA 1
MAIN BREAKER 800 AMP / 800 AF , 3PH , 4
WIRE, 60 HZ, FLUSH OR SURFACE MOUNTED,
BRANCHES :-
160 AMP 3P 11 NOS
60AMP 3P 1NOS
7.4
PB-PS:-

MAIN BREAKER 300 AMP / 400 AF , 3PH , 4


WIRE, 60 HZ, FLUSH OR SURFACE MOUNTED,
BRANCHES :-
60 AMP 3 P 30 NOS

7.5
PB-M:-
EA 1
MAIN BREAKER 400 AMP / 400 AF , 3PH , 4
WIRE, 60 HZ, FLUSH OR SURFACE MOUNTED,
BRANCHES :-
100 AMP 3P 3 NOS
Page 4 OF 8
MATERIAL TAKE-OFF
60AMP 3P 7NOS

7.6
EA 1
PB-L:-

MAIN BREAKER 160 AMP / 250 AF , 3PH , 4


WIRE, 60 HZ, 48 WAY FLUSH OR SURFACE
MOUNTED,
BRANCHES :-
7.7 32 AMP 1 P 48NOS

PB-O:-
EA 1
MAIN BREAKER 100 AMP / 100 AF , 3PH , 4
WIRE, 60 HZ, 30 WAY FLUSH OR SURFACE
MOUNTED,
BRANCHES :-

32AMP 3P 1 NOS
32AMP 1P 5 NOS
20AMP 1P 16 NOS

Page 5 OF 8
MATERIAL TAKE-OFF

8
:CABLES & ACCESSORIES
RATE AND PRICE SHALL BE SUPPLY AND
INSTALL THE FOLLOWING CABLES
INCLUDING DUCT BANKS, LUGS ,
GALANDS ,CONDUITS, BOXES, PVC OR
STEEL, JUNCTION BOXES, CONNECTORS,
ALL FITTINGS,END BELL, TESTING ,
COMMISSIONING, , ALL CIVIL WORK
SUCH AS EXCAVATION, DRILLING, BACK
FILLING, CONCRETE AND ANY CIVIL
WORK, AND EVERYTHING REQUIRED FOR
A COMPLETE SYSTEM ACCORDING TO
.DRAWINGS AND SPECIFICATIONS
:NOTES
The contractor must check the length in the site
8.1 LM 40
before supply.
8.2 LM 20
7 1/C x 630 MM2 + 120 MM2 GR
8.3 LM 20
4 x 300 MM2 + 120 MM2 GR
8.4 LM 20
4 x 240 MM2 + 120 MM2 GR
8.5 4 x 185 MM2 + 70 MM2 GR LM 20
4 x 70 MM2 + 35MM2 GR
8.6 LM 30
4 x 35 MM2 + 10MM2 GR

Page 6 OF 8
MATERIAL TAKE-OFF
FIRE ALARM SYSTEM :-
COMPLETE SYSTEM AS PER DRAWING AND
9 EXISTING FIRE ALARM SYSTEM IN THE SITE, ,
RISER DIAGRAM, ANY CIVIL WORK, AND
SPECIFICATIONS BY USING :-

FIRE ALARM CONTROL PANEL WITH


9.1 BATTERY BACK-UP AND BATTERY
CHARGER RELAYS
EA 1
SMOKE DETECTOR.
9.2 1. EA 69
HEAT DETECTOR.
9.3 2. EA 5
MANUAL BREAK GLASS STATION.
9.4 EA 4
ALARM BELL. 6.
9.5 EA 5
WEATHER PROOF ALARM BELL WITH
9.6 FLASHING LIGHT. EA 3

TELEPHONE SYSTEM :-
10 COMPLETE SYSTEM ACCORDING TO
CAMERON REQUIREMENTS, ANY CIVIL
WORK, AS PER DRAWING AND LOT
SPECIFICATION.

11 PUBLIC ADDRESS SYSTEM :-


COMPLETE SYSTEM ACCORDING TO
CAMERON REQUIREMENTS, ANY CIVIL LOT
WORK, AS PER DRAWING AND
SPECIFICATION.

DATA SYSTEM :-
12 COMPLETE SYSTEM ACCORDING TO
CAMERON REQUIREMENTS, ANY CIVIL
WORK, AS PER DRAWING AND
SPECIFICATION.

TOTAL PRICE

ELECTRICAL NOTES

1 Contractor must check the quantities according to the drawings before


Bidding and shall be responsible for his price without additional cost.
Page 7 OF 8
MATERIAL TAKE-OFF
2 Supply, Installation, Testing & commissioning of all electrical works
As per drawing, schedules and specification are included.

3 Wiring, Sleeves, Manholes, Cables tray, Duct banks, Conduits, Boxes,


Main Junction Boxes, Hangers/Supports, Fitting
For a complete system are included

4 Exposed run conduit will be EMT (Electrical metallic tube) complete with
all accessories screw type, flexible liquid tight metal if required and
Concealed conduit in wall or incased on concrete will be PVC NEMA TC 2
Or TC 8, EPT-A , SAPPCO or approved equal.

5 Exposed conduit inside Electric & Mechanical rooms shall be galvanized


Rigid steel conduit.

6 Building wire THWN / Riyadh, Jeddah wire or Middle East Co.

7 Panel board GE, Electra type or Mitsubishi. Made in Japan.

8 Any civil work such as excavation, drilling, back-filling, red tiles, fine sand,
Concrete, manhole or hand hole are included, shall be done by
Electromechanical contractor.

9 Disconnect switches will be Esq. Type or G.E. or approved equal.

10 Cable tray and ladder 1.5mm thickness mill galvanized steel with cover.

11 Wiring devices shall be Legrand Pass & Seymour type, U.S.A made.
or approved equal.

12 Fire alarm system will be conventional pyrotronics type or simplex


or notifier.type OR as existing in site.

13 Telephone cables & devices shall be orthotics products


or approved equal.

14 Small hand hole 50 x 50 x 80cm are included for the outdoor lighting
And site works.

15 Outdoor lighting cable shall be type XLPE ins., P.V.C sheathed single
or Multi core.

16 Feeder cable type shall be Riyadh,Jeddah cable XLPE / PVC


1 KV/0.6 KV or approved equal.

Page 8 OF 8