Está en la página 1de 1

Mediumvoltage11000v&Above

PaPeR insulated Mains caBles PVc 11000V


COPPER CONDUCTOR
Plain annealed copper conductors, paper insulated, paper belted, semi-conducting carbon paper
tape bedding, lead sheathed, textile compound bedding, galvanised steel wire armour, PVC outer
sheath - Red. 6350/11000 volts grade to BS6480/88. Flame propagation to BS EN 60332. Red
outer sheath can be prone to fading when exposed to U.V rays.
CCC Conductor Stranding No. Of Weight Overall Nylon
Code Size (mm) Cores (Kg/Km) Diameter Cleat
(mm2) (mm) Size
PILC3X25RD 25 7/2.14 3 5230 43.6 1.8 Temperaturelimits:
PILC3X35RD 35 19/1.53 3 5890 42.3 2.0 upto65C.
PILC3X50RD 50 19/1.78 3 6620 45.6 2.0
PILC3X70RD 70 19/2.14 3 7820 49.7 2.0 *Bendingradius:
PILC3X95RD 95 19/2.52 3 9240 53.3 TC9 13xoveralldiameter.
PILC3X120RD 120 37/2.03 3 10400 56.2 TC9
PILC3X150RD 150 37/2.25 3 11770 59.2 TC10
Coreidentification:
PILC3X185RD 185 37/2.52 3 13550 62.8 TC10 Whiteprintednumberson
PILC3X240RD 240 61/2.25 3 16390 67.8 TC11 insulatingpapers.
PILC3X300RD 300 61/2.52 3 19870 73.6 TC12
Shouldnotbeinstalledat
PILC3X400RD 400 61/2.85 3 23700 79.4 TC14
temperaturesbelow0Cor
above+60C.

ALUMINIUM CONDUCTOR
Plain aluminium stranded conductors, paper insulated, paper belted, semi-conducting carbon paper
tape bedding, lead sheathed, textile compound bedding, galvanised steel wire armour, PVC outer
sheath - Red. 6350/11000 volts grade to BS6480/88. Flame propagation to BS EN 60332.
Red outer sheath can be prone to fading when exposed to U.V rays.
CCC Conductor Stranding No. Of Weight Overall Nylon
Code Size (mm) Cores (Kg/Km) Diameter Cleat Temperaturelimits:upto65C.
(mm2) (mm) Size
10100RD 95 19/2.52 3 7115 53.2 TC9 *Bendingradius:13xoverall
10103RD 185 37/2.52 3 9521 63.5 TC11 diameter.
10105RD 300 61/2.52 3 13403 71.5 TC12
Coreidentification:Whiteprinted
numbersoninsulatingpapers.
Shouldnotbeinstalledat
temperaturesbelow0Cor
above+60C.

Pleasenotethatglandandcleatsizesareintendedtobeindicativeandmayvaryaccordingtodifferentmanufacturerstolerances.
*Allbendingradiishownareindicativeonlyaseachindividualmanufacturerhastheirowncriteriafortheirproduct.Specificationoftheminimumbending
42 radius(MBR)ofcablesisnotreferredtoincablestandards.Thisisamanufacturerdeclaration,basedontheirownjudgementandexperienceofthe
capabilitiesoftheircable,itisnotaspecificationdefinedinstandards.