Está en la página 1de 9

INNOVENTIONS MILLENNIUM

INNOVENTIONS
WEST CENTRAL
EAST

BID & CONSTRUCT


WORLD
SHOWPLACE

06/07/17
1
GLOBE

ILLUMINATIONS

PROJECT
LOCATION

TOTAL SHEET COUNT: 7


INDEX OF DRAWINGS
SHEET ISSUE LAST REVISION SHEET SHEET ISSUE LAST REVISION SHEET SHEET ISSUE LAST REVISION SHEET
NUMBER DATE REV. ISSUE TITLE NUMBER DATE REV. ISSUE TITLE NUMBER DATE REV. ISSUE TITLE

CIVIL ENGINEERING LEAD:


INDEX

A. DAO
A. DAO
DISCIPLINE SHEET COUNT: 1
ID-110 6/17/17 COVER, DRAWING INDEX SITE LOCATION MAP

CIVIL
DISCIPLINE SHEET COUNT: 6
XC-101 6/17/17 EXISTING CONDITIONS
XC-102 6/17/17 DEMOLITION PLAN & EROSION CONTROL PLAN
C-111 6/17/17 SITE PLAN
C-211 6/17/17 GRADING & DRAINAGE PLAN
C-221 6/17/17 POND ENLARGEMENT AND DETAILS
C-401 6/17/17 DETAILS
C-402 6/17/17 DETAILS
C-404 6/17/17 DETAILS

BACK OF HOUSE MODIFICATIONS


Heery InternationalInc.
100 East Pine St.,
Suite 300
Orlando, Florida 32801
design 407.992.6300
EB 0005176
AA 0002293
PROJECT #

FRANCE
EPCOT
Reason: I have reviewed this
document
Contact Info: kklueh@heery.com
Date: 2017.06.20 15:00:38-04'00'
Location: Printed copies of this C WFR09-04
document are not considered
signed and sealed and the
signature must be verified on any
electronic copies.
BID & CONSTRUCT
06/07/17
1
CIVIL ENGINEERING LEAD:
A. DAO
A. DAO

BACK OF HOUSE MODIFICATIONS


Heery InternationalInc.
100 East Pine Street,
Suite 300,
Orlando, Florida 32801
design 407.992.6300
EB 0005176
AA 0002293
PROJECT #

FRANCE
EPCOT
C WFR09-04
LEGEND:
LIMIT OF WORK

REMOVE EX. FENCING.


SILT FENCE (SINGLE OR DOUBLE
ROW, SEE PLAN), SEE 1/ XC-203

TURBIDITY CURTAIN, SEE 2/ XC-203


PROPOSED GRADES. SEE SHEET C-211

GUARD POST OR TUBULAR MARKERS


X TO BE REMOVED
SNOW FENCING FOR TREE CLUSTER
PROTECTION
TREES TO BE PROTECTED

TREES TO BE REMOVED

SILT FENCE INLET PROTECTION,


SEE 2/ C-402

LIGHT POLE TO BE REMOVED.


REMOVE CIRCUIT AND CONDUIT
TO PANEL

PAVEMENT IN THIS AREA


TO BE DEMOLISHED

WORK IN THIS AREA REPRESENTS FUTURE


SCOPE UNDER THIS PACKAGE, EXISTING
PAVING TO REMAIN

NOTES:
5
1. CONTRACTOR SHALL COORDINATE PHASING AND SEQUENCING OF THE WORK
WITH WDW REPRESENTATIVES.

2. FDOT TYPE III SILT FENCE SHALL BE CONSTRUCTED PRIOR TO EARTH MOVING
ACTIVITIES. THE SILT FENCE SHALL ENCOMPASS ALL DISTURBED AREAS AND
6 5 REMAIN IN PLACE UNTIL ALL CONSTRUCTION HAS CEASED AND DISTURBED
AREAS STABILIZED.

BID & CONSTRUCT


3. ALL SURFACE WATER DISCHARGE FROM THIS SITE, INCLUDING DEWATERING
DISCHARGE SHALL MEET STATE WATER QUALITY STANDARDS (LESS THAN 29 NTU
ABOVE BACKGROUND) PRIOR TO REACHING ANY WATERS OF THE STATE
INCLUDING WETLANDS.

5 4. INSPECT ALL EROSION AND SEDIMENTATION CONTROL STRUCTURES AT LEAST


ONCE A WEEK AND WITHIN 24 HOURS AFTER THE END OF A STORM EVENT THAT IS
0.50 INCHES OR GREATER. COMPLETE A STORMWATER POLLUTION PREVENTION

06/07/17
PLAN INSPECTION AND MAINTENANCE FORM AFTER EVERY INSPECTION.

5. CONSTRUCTION VEHICLE PATHS, WHICH ARE USED REGULARLY, WILL BE


STABILIZED TO MINIMIZE TRANSPORT OF SEDIMENTS BY VEHICLES.

1
11 6. ALL EXCESS MATERIAL IS TO BE REMOVED FROM THE SITE AND PROPERLY
DISPOSED BY THE CONTRACTOR.
5
7. ALL ON-SITE STORAGE OF MATERIALS IS SUBJECT TO THE APPROVAL OF THE SITE
CONSTRUCTION MANAGER.
EX. 9
SUBSTATION 3 8. PROTECT EXISTING INLETS DURING CONSTRUCTION. MAINTAIN DRAINAGE ON THE
SITE AT ALL TIMES DURING CONSTRUCTION.
8
9. GUARD POSTS, FENCE POSTS, BOLLARDS AND THEIR FOOTINGS SHALL BE
4 REMOVED COMPLETELY.
7
10. VENTS, MANHOLES, VAULTS, ETC. SHALL BE DISPOSED OF AS DIRECTED.

11. CLEAN OUTS, WATER VALVES, ETC. SHALL REMAIN AND PROTECTED.
6
12. ALL ABOVE GROUND UTILITIES, ELECTRIC PANELS, ETC. PRESENTLY SERVICING
EQUIPMENT TO BE REMOVED OR RELOCATED SHALL ALSO BE REMOVED AND
RELOCATED.
1 13. PROTECT OTHER ABOVE GROUND UTILITIES THAT ARE TO REMAIN DURING
CONSTRUCTION.
2
1. CONEX CONTAINERS TO BE REMOVED BY OTHERS PRIOR TO
6 CONSTRUCTION.
2. SHED TO BE REMOVED BY OTHERS PRIOR TO CONSTRUCTION.
10 3. ENTERTAINMENT TRAILER REMOVED AND RELOCATED TO THE NORTH.
4. EXISTING SWITCHGEAR TO BE RELOCATED COORDINATE WITH RCES.
5. TRAILERS AND SHEDS TO REMOVED AND REPLACED SOUTH OF
MOROCCO AS SHOWN.
6. CONEXES TO BE RELOCATED SOUTH OF MOROCCO.
7. RELOCATE DUMPSTERS AND RECYCLED BIN.
8. RELOCATE BAILER.
9. RELOCATE COMPACTOR
1 10. TRAILERS TO BE REMOVED BY OTHERS PRIOR TO CONSTRUCTION
11. EXISTING PAVING MAY REMAIN BUT WILL REQUIRE TRENCHING FOR
UTILITY RELOCATION AND DEMOLITION. SEE SHEET XC-103 AND C-301

CIVIL ENGINEERING LEAD:


A. DAO
A. DAO

BACK OF HOUSE MODIFICATIONS


Heery InternationalInc.
100 East Pine Street,
Suite 300,
Orlando, Florida 32801
design 407.992.6300
EB 0005176
AA 0002293
PROJECT #

FRANCE
EPCOT
C WFR09-04
LEGEND:

PAVING-DRIVEWAY,
SIDEWALKS ETC.

PROPOSED GRAVEL
PARKING AREA

FUTURE WORK UNDER


SEPARATE PACKAGE

NOTES:
1. SCOPE TO INCLUDE TEMPORARY
PAVING OF ALL FIRE ACCESS AND
DELIVERY ROADS. SEE DETAIL 8/C401.

2. SCOPE DOES NOT INCLUDE SIDEWALK


ENTERTAINMENT TRAILER TO REPLACE CONSTRUCTION AND TRAILER, SHED &
FRANCE EXISTING TRAILER CONNEX LAYOUT WHICH WILL BE
ACCOMPLISHED UNDER SEPARATE
PACKAGE
EER TO REMAIN
THREE WALK IN COOLERS TO REMAIN

PROJECT LIMIT OF WORK

BID & CONSTRUCT


GRAVEL PARKING AREA #3
(FUTURE)

NEW LOCATION FOR


RELOCATED RECYCLE BINS
GRAVEL PARKING AREA #1

06/07/17
(APPROX. 26 SPACES)
FI

EXISTING ENTERTAINMENT TRAILER


RE

(W217) TO REMAIN IN PLACE


NEW LOCATION FOR
AC

RELOCATED BAILER
CE

1
S
S

NEW LOCATION FOR


RO

RELOCATED COMPACTOR
AD

CONTRACTOR TO FIELD VERIFY NEW LOCATION FOR


EXISTING PAVING TO DETERMINE RELOCATED DUMPSTER
EX.
EXTENT THAT CAN REMAIN IN THIS
SUBSTATION
PHASE

RELOCATED SWITCH GEAR


EXISTING ELECTRICAL SUBSTATION PROJECT LIMIT OF WORK
GRAVEL PARKING AREA #2
(APPROX. 175 SPACES) NEW LOCATION FOR RELOCATED TRAILER.

EXISTING ENTERTAINMENT TRAILER


(W168) TO BE REPLACED.

D
AD AN
RO SS
SS CE
CE AC
AC RY
RE E
FI LIV
MOROCCO

DE
REORIENT EXISTING TRAILERS AS SHOWN.
RECONNECT ALL UTILITIES

CIVIL ENGINEERING LEAD:


EXISTING COMPACTOR TO REMAIN.

A. DAO
A. DAO
DRY DETENTION POND #1
SEE C-221

MERCH. SHED, CAST BREAK ROOM AND


DRY DETENTION POND #2 OPERATOR TRAILER TO REPLACE EXISTING.
SEE C-221

BACK OF HOUSE MODIFICATIONS


Heery InternationalInc.
100 East Pine Street,
Suite 300,
Orlando, Florida 32801
design 407.992.6300
EB 0005176
AA 0002293
PROJECT #

FRANCE
EPCOT
C WFR09-04
LEGEND

PROPOSED CONTOURS
99.05 PROPOSED SPOT ELEVATION
BS BOTTOM OF SWALE
ST INLET #1 ME MATCH EXISTING GRADE
GRATE 104.50 FUTURE WORK UNDER
I.E. 102.00 SEPARATE PACKAGE M.E.S. MITERED END SECTION
40 LF 10" DIA HP HIGH POINT
ST @ 0.50%
MATCH EX FUTURE WORK UNDER
ELEV 104.60 SEPARATE PACKAGE
104.60 +
ST INLET #2 MATCH EX
+
GRATE 104.50 ELEV 104.77
+
I.E. 101.80
36 LF 10" DIA + EX FFE 104.89
ST @ 0.50% MATCH EX
ST INLET #3 ELEV 104.60
GRATE 104.40 +
I.E. 101.62

70 LF 12" DIA MATCH EX


ST @ 1.7% ELEV 104.60
ST INLET #4 +
GRATE 103.80 MATCH EX ELEV 103.68 EX FFE 101.48 +
I.E. 99.00 50 LF 10" DIA
N: 45375.33 + ST @ 0.50%
E: 21964.44 + FFE 104.97 ST INLET #5
GRATE 103.60
I.E. 99.25
90 LF 15" DIA N: 45354.95
ST @ 0.55% EX FFE 101.53 +
E: 22012.72
ST INLET #6
GRATE 103.60 EX FFE 105.01 +
I.E. 99.43 ST INLET #7
ST INLET #12 36 LF 10" DIA N: 45325.03 MATCH EXISTING
GRATE 102.38
GRATE 102.80

BID & CONSTRUCT


ST @ 0.50% E: 22037.96 I.E. 99.68 ELEV 100.85
I.E. 98.50 +
N: 45300.01
N: 45323.95
E: 22077.68
E: 21907.09 MATCH EX.
ELEV 100.90
45 LF 8" DIA PROPOSED FFE
ST @ 0.55% + 103.20

1%
106 LF 15" DIA

06/07/17
EXISTING FFE
ST @ 1.0% 103.20
MATCH EX.
+ ELEV 100.4
+
100.70 + 0.5% +

1%

1
ST INLET #13 BEGIN SWALE, +101.22
GRATE 101.20 ELEV 100.1
I.E. 97.45 MATCH EX. +
N: 45229.95 ELEV 101.1
EX. HIGH POINT
E: 21963.05
SUBSTATION 100.90 101.16 +
SWALE @ 0.5% 0.5 102.00
65 LF 15" DIA TO INLET %
ST @ 2.1% +
ST INLET #14 HIGH POINT +
GRATE 99.00 100.60 101.8
I.E. 96.00 4%
N: 45179.71 +
E: 22010.07 + DM #3

0.5
%
HIGH POINT

3%
85 LF 15" DIA 100.30
ST @ 1.15%

BOTTOM OF
ST INLET #32
+ SWALE,
GRATE 97.50
ELEV 99.1
I.E. 95.19 SWALE @ 0.5%
ST INLET #15 N: 45109.37 91 LF 12" DIA ST @ 0.50% TO INLET
GRATE 97.70 E: 22032.33
I.E. 95.00
N: 45099.68 ST INLET #31
E: 21970.44 GRATE 97.50

%
CONTROL STRUCTURE #1 BOTTOM OF

0.5
I.E. 94.73
SEE C-221 60 LF 15" DIA N: 45047.39 SWALE,
N: 45026.75 ST @ 1.0% E: 22104.14 ELEV 98.60
E: 21928.06 ST MANHOLE
RIM 97.70
I.E. 94.40 +
66 LF 15" DIA ST @ 0.5%
N: 45045.39
E: 22015.92
CROSSING UTILITIES

CIVIL ENGINEERING LEAD:


CH TOP OF PIPE 95
COMM TOP OF DUCT 95.5
62 LF 15" DIA
%

ST @ 1.0% BOTTOM OF
0.5

A. DAO
A. DAO
C- 21

M.E.S. SWALE,
4

ST INLET #5
40

I.E. 93.70 ELEV 98.60


GRATE 97.90
N: 44994.02 I.E. 94.40
E: 21971.31 N: 44952.46
5%

CONTROL
1.2

STRUCTURE #3 E: 22214.52
SEE C-221 + MATCH EX.
ELEV. 98.25
0.5% FFE
DRY DETENTION 99.25
POND #2.
SEE C-221
94.25 H.P.
DRY DETENTION
POND #1. SEE C-221
+ 1%
50 LF 15" DIA FFE
@ 0.40% 70 LF 15" DIA 101.5
@ 0.40%
99.05

M.E.S.
I.E. 93.90
N: 44852.50
E: 22139.99

BACK OF HOUSE MODIFICATIONS


FFE
99.25
ST MANHOLE #4
RIM 97.5
I.E. 94.10
N: 44892.93
E: 22172.27
CONTROL STRUCTURE #2
SEE C-221
N: 44806.71
C- 0
4
2

E: 22189.27
40

Heery InternationalInc.
100 East Pine Street,
Suite 300,
Orlando, Florida 32801
design 407.992.6300
EB 0005176
AA 0002293
PROJECT #

FRANCE
EPCOT
C WFR09-04
TOP OF BERM ELEV. 98.50

CORE DRILL OPENING 30 LF 12" DIA


IN EXISTING ST @ 1.0% CONTROL STRUCTURE #1
STORM MH, I.E. 91.70 FDOT TYPE D INLET
SEE DETAIL 4 SHEET C-401 GRATE 97.00
I..E (SE) 93.50 3" (DIA ORIFICE)
I.E. (NW) 92.00 (12" DIA STORM)
SEE DETAIL 22 SHEET C-404.

0.5
0%
M.E.S. I.E. 93.70

TOP OF BERM ELEV. 98.50

BID & CONSTRUCT


CONTROL STRUCTURE #3
BRICK UP EXISTING INLET TO
ELEVATION 95.50 AND INSTALL
SKIMMER. SEE DETAIL 23 SHEET C-404.

06/07/17
0.5
0%

1
0.50%

0.5
0%

+ 3H : 1V

+ 94.25

0.5
0%
3H : 1V

TOP OF BERM ELEV. 98.50


15'-0" MAINTENANCE EASEMENT

CIVIL ENGINEERING LEAD:


A. DAO
A. DAO
0.5
0%
M.E.S. I.E. 93.75
TOP OF BERM ELEV. 98.50
8H : 1V
END OF MAINTENANCE
EASEMENT ELEV. 96.60
3H : 1V

61 LF 12" DIA ST @ 1.0%

3H : 1V
0.50%

0.5
0%

TOP OF BERM ELEV. 98.50

BACK OF HOUSE MODIFICATIONS


TOP OF BERM ELEV. 98.50

Heery InternationalInc.
100 East Pine Street,
Suite 300,
Orlando, Florida 32801
design 407.992.6300
EB 0005176
AA 0002293
PROJECT #

FRANCE
CORE DRILL OPENING IN EXISTING

EPCOT
INLET, I.E. 89.40

CONTROL STRUCTURE #2
FDOT TYPE D INLET
GRATE 97.00
I..E (NW) 93.50 3" (DIA ORIFICE) C WFR09-04
I.E. (NW) 90.00 (12" DIA STORM)
SEE DETAIL 22 SHEET C-404.
6" DIA. GALVANIZED STEEL
POST FILLED W/ CONC.
COLOR TO BE SELECTED
BY OWNER

3'-6"
FINISH GRADE

ASPHALT CONCRETE

4'-0"
#5 REBAR, TYP. CONCRETE FOOTING

BID & CONSTRUCT


4"
16"
AGGREGATE BASE
NOTES:
O.D.
1. BOLLARDS TO BE PAINTED SAFETY YELLOW EXCEPT BOLLARDS NEAR
FIRE HYDRANTS TO BE PAINTED RED.

06/07/17
1
1 1 2" SUPERPAVE TYPE SP 12.5

6" GRADED AGGREGATE OR CRUSHED


CONCRETE BASE COURSE, LBR OF 100%

12" SUBGRADE COMPACTED TO AT LEAST


95% OF THE MODIFIED PROCTOR MAXIMUM
DRY DENSITY

CIVIL ENGINEERING LEAD:


A. DAO
A. DAO

BACK OF HOUSE MODIFICATIONS


Heery InternationalInc.
100 East Pine Street,
Suite 300,
Orlando, Florida 32801
design 407.992.6300
EB 0005176
AA 0002293
PROJECT #

FRANCE
EPCOT
C WFR09-04
TRAFFIC FLOW

30'
-0"
MIN
.
FDOT #4 COARSE
AGGREGATE FILTERED WATER
STAKES (2x4 WOOD) MAX.
SPACING 3'-0" O.C.
6" U.V. RESISTANT BLACK
FILTER FABRIC
U.V. RESISTANT RUNOFF WATER

16"
BLACK FILTER FABRIC WITH SEDIMENT
DROP INLET
. WITH GRATE
MIN
-0"
20' OVER GEOTEXTILE BURIED FILTER FABRIC
SEPARATION 8" MIN. (4"x4" TRENCH)
FABRIC PLAN VIEW
CROSS-SECTION

LEGEND AND NOTES:

NOTES:

BID & CONSTRUCT


1. ALL EROSION CONTROL MEASURES SHOWN ON THIS PLAN ARE PART
OF THE BASE BID.

06/07/17
1
CIVIL ENGINEERING LEAD:
A. DAO
A. DAO

BACK OF HOUSE MODIFICATIONS


Heery InternationalInc.
100 East Pine Street,
Suite 300,
Orlando, Florida 32801
design 407.992.6300
EB 0005176
AA 0002293
PROJECT #

FRANCE
EPCOT
C WFR09-04
BID & CONSTRUCT
06/07/17
1
CIVIL ENGINEERING LEAD:
A. DAO
A. DAO

BACK OF HOUSE MODIFICATIONS


Heery InternationalInc.
100 East Pine Street,
Suite 300,
Orlando, Florida 32801
design 407.992.6300
EB 0005176
AA 0002293
PROJECT #

FRANCE
EPCOT
C WFR09-04