Está en la página 1de 5

CONTROL DE COLOCACION DE CONCRETO EN OBRA

NUMERO
NUMERO DE HORA SALIDA HORA LLEGADA HORA INICIO HORA FINAL DISEO
FECHA DE COLOCACIN M3 SLUMP DESCRIPCION
PRECINTO PLANTA OBRA VACEADO VACEADO Kg/CM2
PLACA GUIA

001 3/10/2017 ALA-809 0007465 8:01 AM 9:40 AM 10:14 AM 11:40 AM 8 4" 280 Parrarayos 1,2,3,4,5, Transformador de Tension 1,2,3

002 3/16/2017 ALA-809 0007514 8:21 AM 9:30 AM 9:40 AM 10:35 AM 8 6" 280 Interruptor de Potencia Tripolar 1,2,3

003 3/16/2017 ALA-809 0007521 12:05:00 p.m . 1:28 AM 1:40 PM 2:06 PM 8 5.5" 280 Transforma. De Corriente 1,2,3 Aislador Pedestal1,2 Parrarayo 6

004 3/17/2017 ALA-809 0007529 9:53:00 a.m . 11:12 AM 11:20 AM 12:40 PM 8 6.5" 280 Parrarayo 1,2,3 Trasformador de Tension 1,2,3

005 3/17/2017 ALA-809 0007534 2:23:00 p.m . 3:40 PM 3:50 PM 5:00 PM 8 7" 280 Transformador de corriente 4,5,6 Parrarayo 4,5 parrarayo 8,9

006 3/18/2017 ALA-809 0007547 8:55:00 a.m . 10:10 AM 10:20 AM 10:40 PM 8 6" 280 Interruptor de potencia Tripolar 4,5,6

007 3/20/2017 ALA-809 0007554 9:47:00 a.m . 10:57 AM 11:06 AM 12:00 PM 8 6.5" 280 Transformador de corriente8,9 Interruptor de potencia Tripolar 8,9

008 3/20/2017 ALA-809 0007555 2:01:00 p.m . 3:20 PM 3:37 PM 4:50 PM 4 6.5" 280 Parrarayos 6 Interruptor de P. Tripolar 3 Transformador de tencion 6

009 3/21/2017 ALA-809 0007560 8:35:00 a.m . 9:50 AM 10:00 AM 11:26 AM 8 5" 280 Transform. De Tencion 4,5 Transform. De Corriente 3 Interru. De P Trip.

010 3/21/2017 ALA-809 0007565 1:49:00 p.m . 2:50 PM 3:05 PM 4:00 PM 4 3.5" 280 Transformador de Corriente 1,2

011 3/22/2017 ALA-809 0007575 9:19:00 a.m . 10:30 AM 10:41 AM 11:42 AM 8 5" 280 Aislador Pedestal 1,2 Transfom. De Corriente 4,5,6

012 3/23/2017 ALA-809 0007593 1:12:00 p.m . 2:35 PM 2:40 PM 4:20 PM 8 6" 280 pararrayos 9 rmador de corriente 8,9 Interruptor de potencia 8,9

013 3/24/2017 ALA-809 0007614 11:22:00 a.m . observado 13:20:00 p. m. 2:50 PM 8 4" 280 Interruptor de Potencia Tripolar 4,5,6 Pararrayos 8 Trasformador de Tenc

014 3/25/2017 ALA-809 0007614 8:30:00 a.m . 9:40 a.m. 10:10 AM 11:00 PM 8 5.5" 280 Portico de Barras 3,4 Pararrayos 7 Trasformador de tencion 5
OCACION DE CONCRETO EN OBRA

TEMP.
ESTRUCTURA TEMP. CONCRETO OBSERVACIONES
AMBIENTE

Se moldeo 6
Zapata 27.8 26.2
Probetas
Se moldeo 6
Zapata 27.5 25
Probetas
Se moldeo 6
Zapata 24 26.1
Probetas
Se moldeo 6
Pedestal 29.5 27.2
Probetas
Se moldeo 6
Zapata Pedestal 24.1 27.1
Probetas
Se moldeo 6
Zapata 25.2 26.1
Probetas
Se moldeo 6
Zapata 25.5 27.7
Probetas
Se moldeo 6
Zapata Pedestal 24.4 27.6
Probetas
Se moldeo 6
Zapata Pedestal 24.5 26.8
Probetas
Se moldeo 6
Pedestal 24.2 26.9
Probetas
Se moldeo 6
Pedestal 27.6 28.5
Probetas
Se moldeo 6
Pedestal 25.5 27.2
Probetas
Se moldeo 6
Pedestal 26.7 27.3
Probetas
Se moldeo 6
Zapata Pedestal 25.8 25.6
Probetas
CONTROL DE COLOCACIN DE CONCRETO EN OBRA

Temperatura Temperatura DISEO


ITEM Descripcin Estructura Edad (Das) Fecha Vaceado Fecha de Rotura Slump (Pg) AREA KN KG F^C(Kg/cm2) % Resistencia OBSERVACIONES
Ambiente de Concreto Kg/CM2

001 7 3/10/2017 3/17/2017 27.8 26.2 280 4" 181 323 32959 182.1 65.0

002 7 3/10/2017 3/17/2017 27.8 26.2 280 4" 181 209.16 21343 117.9 42.1
003 Pararrayos 1,2,3,4,5 y 3/10/2017 4/7/2017 27.8 26.2 280 4" 181 0 0.0 0.0
Transformador de Tensin Zapata 28 6 Probetas
004 1,2,3 28 3/10/2017 4/7/2017 27.8 26.2 280 4" 181 0 0.0 0.0
005 Reserva 3/10/2017 #VALUE! 27.8 26.2 280 4" 0 0 #DIV/0! #DIV/0!
006 Reserva 3/10/2017 #VALUE! 27.8 26.2 280 4" 0 0 #DIV/0! #DIV/0!

007 7 3/16/2017 3/23/2017 27.5 25 280 6" 181 261.42 26676 147.4 52.6

008 7 3/16/2017 3/23/2017 27.5 25 280 6" 181 247.2 25224 139.4 49.8

009 3/16/2017 4/13/2017 27.5 25 280 6" 181 0 0.0 0.0


Interruptpr de Potencia 28
Zapata 6 Probetas
Tripolar 1,2,3
010 3/16/2017 4/13/2017 27.5 25 280 6" 181 0 0.0 0.0
28
011 3/16/2017 #VALUE! 27.5 25 280 6" 0 0 #DIV/0! #DIV/0!
Reserva
012 3/16/2017 #VALUE! 27.5 25 280 6" 0 0 #DIV/0! #DIV/0!
Reserva
013 7 3/16/2017 3/23/2017 24 26.1 280 5.5" 181 428.18 43692 241.4 86.2

014 7 3/16/2017 3/23/2017 24 26.1 280 5.5" 181 438.68 44763 247.3 88.3

015 Trasformador de Corriente 3/16/2017 4/13/2017 24 26.1 280 5.5" 181 0 0.0 0.0
28
1,2,3 Aislador Pedestal 1,2 Zapata 6 Probetas
016 Parrarayos 6 3/16/2017 4/13/2017 24 26.1 280 5.5" 181 0 0.0 0.0
28
017 3/16/2017 #VALUE! 24 26.1 280 5.5" 0 0 #DIV/0! #DIV/0!
Reserva
018 3/16/2017 #VALUE! 24 26.1 280 5.5" 0 0 #DIV/0! #DIV/0!
Reserva
019 7 3/17/2017 3/24/2017 29.5 27.2 280 6.5" 181 515.86 52639 290.8 103.9

020 7 3/17/2017 3/24/2017 29.5 27.2 280 6.5" 181 499.12 50931 281.4 100.5

021 Parrarayos 1,2,3 3/17/2017 4/14/2017 29.5 27.2 280 6.5" 181 0 0.0 0.0
Transformador de Tension Pedestal 28 6 Probetas
022 1,2,3 3/17/2017 4/14/2017 29.5 27.2 280 6.5" 181 0 0.0 0.0
28
023 Reserva 3/17/2017 #VALUE! 29.5 27.2 280 6.5" 0 0 #DIV/0! #DIV/0!

024 Reserva 3/17/2017 #VALUE! 29.5 27.2 280 6.5" 0 0 #DIV/0! #DIV/0!

025 7 3/17/2017 3/24/2017 24.1 27.1 280 7" 181 399.95 40811 225.5 80.5

026 7 3/17/2017 3/24/2017 24.1 27.1 280 7" 181 451 46020 254.3 90.8

027 Transformador de Corriente 28 3/17/2017 4/14/2017 24.1 27.1 280 7" 181 0 0.0 0.0
4,5,6 Pararrayos4,5 Pararrayos Pedestal 6 Probetas
028 8,9 28 3/17/2017 4/14/2017 24.1 27.1 280 7" 181 0 0.0 0.0

029 Reserva 3/17/2017 #VALUE! 24.1 27.1 280 7" 0 0 #DIV/0! #DIV/0!

030 Reserva 3/17/2017 #VALUE! 24.1 27.1 280 7" 0 0 #DIV/0! #DIV/0!

031 7 3/18/2017 3/25/2017 25.2 26.1 280 6" 181 0 0.0 0.0

032 7 3/18/2017 3/25/2017 25.2 26.1 280 6" 181 0 0.0 0.0

033 28 3/18/2017 4/15/2017 25.2 26.1 280 6" 181 0 0.0 0.0
Interruptor de potencia Tripolar
Zapata 6 Probetas
4,5,6
034 28 3/18/2017 4/15/2017 25.2 26.1 280 6" 181 0 0.0 0.0

035 Reserva 3/18/2017 #VALUE! 25.2 26.1 280 6" 0 0 #DIV/0! #DIV/0!

036 Reserva 3/18/2017 #VALUE! 25.2 26.1 280 6" 0 0 #DIV/0! #DIV/0!

037 7 3/20/2017 3/27/2017 25.5 27.7 280 6.5" 181 0 0.0 0.0

038 7 3/20/2017 3/27/2017 25.5 27.7 280 6.5" 181 0 0.0 0.0

039 Interruptor de potencia Tripolar 28 3/20/2017 4/17/2017 25.5 27.7 280 6.5" 181 0 0.0 0.0
8,9 / Transformador de Zapata 6 Probetas
040 corriente 8,9 28 3/20/2017 4/17/2017 25.5 27.7 280 6.5" 181 0 0.0 0.0

041 Reserva 3/20/2017 #VALUE! 25.5 27.7 280 6.5" 0 0 #DIV/0! #DIV/0!

042 Reserva 3/20/2017 #VALUE! 25.5 27.7 280 6.5" 0 0 #DIV/0! #DIV/0!

043 7 3/20/2017 3/27/2017 24.4 27.6 280 6.5" 181 0 0.0 0.0

044 7 3/20/2017 3/27/2017 24.4 27.6 280 6.5" 181 0 0.0 0.0

045 Pararrayos 6 (P) Interruptor de 28 3/20/2017 4/17/2017 24.4 27.6 280 6.5" 181 0 0.0 0.0
potencia 3 (P), Transformador Pedestal Zapata 6 Probetas
046 de tencion 6 (Z) 28 3/20/2017 4/17/2017 24.4 27.6 280 6.5" 181 0 0.0 0.0

047 Reserva 3/20/2017 #VALUE! 24.4 27.6 280 6.5" 0 0 #DIV/0! #DIV/0!

048 Reserva 3/20/2017 #VALUE! 24.4 27.6 280 6.5" 0 0 #DIV/0! #DIV/0!

049 7 3/21/2017 3/28/2017 24.5 26.8 280 5" 181 0 0.0 0.0

050 7 3/21/2017 3/28/2017 24.5 26.8 280 5" 181 0 0.0 0.0
Transformador de tencion4,5
051 28 3/21/2017 4/18/2017 24.5 26.8 280 5" 181 0 0.0 0.0
Transformador de corriente 3
Pedestal Zapata 6 Probetas
Interruptor de potencia Tripolar
052 28 3/21/2017 4/18/2017 24.5 26.8 280 5" 181 0 0.0 0.0
1,2
053 Reserva 3/21/2017 #VALUE! 24.5 26.8 280 5" 0 0 #DIV/0! #DIV/0!

054 Reserva 3/21/2017 #VALUE! 24.5 26.8 280 5" 0 0 #DIV/0! #DIV/0!

055 7 3/21/2017 3/28/2017 24.2 26.9 280 3.5" 181 0 0.0 0.0

056 7 3/21/2017 3/28/2017 24.2 26.9 280 3.5" 181 0 0.0 0.0

057 28 3/21/2017 4/18/2017 24.2 26.9 280 3.5" 181 0 0.0 0.0
Transformador de Corriente
Pedestal 6 Probetas
1,2
058 28 3/21/2017 4/18/2017 24.2 26.9 280 3.5" 181 0 0.0 0.0

059 Reserva 3/21/2017 #VALUE! 24.2 26.9 280 3.5" 0 0 #DIV/0! #DIV/0!

060 Reserva 3/21/2017 #VALUE! 24.2 26.9 280 3.5" 0 0 #DIV/0! #DIV/0!

061 7 3/22/2017 3/29/2017 27.6 28.5 280 5" 181 0 0.0 0.0

062 7 3/22/2017 3/29/2017 27.6 28.5 280 5" 181 0 0.0 0.0

063 Aislador pedestal 1,2 28 3/22/2017 4/19/2017 27.6 28.5 280 5" 181 0 0.0 0.0
Transformador de corriente Pedestal 6 Probetas
064 4,5,6 28 3/22/2017 4/19/2017 27.6 28.5 280 5" 181 0 0.0 0.0

065 Reserva 3/22/2017 #VALUE! 27.6 28.5 280 5" 0 0 #DIV/0! #DIV/0!

066 Reserva 3/22/2017 #VALUE! 27.6 28.5 280 5" 0 0 #DIV/0! #DIV/0!

067 7 3/23/2017 3/30/2017 25.5 27.2 280 6" 181 0 0.0 0.0

068 7 3/23/2017 3/30/2017 25.5 27.2 280 6" 181 0 0.0 0.0

069 Pararrayo 9 Trasformador de 28 3/23/2017 4/20/2017 25.5 27.2 280 6" 181 0 0.0 0.0
corriente 8,9 Interruptor dre Pedestal 6 Probetas
070 potencia 8,9 28 3/23/2017 4/20/2017 25.5 27.2 280 6" 181 0 0.0 0.0

071 Reserva 3/23/2017 #VALUE! 25.5 27.2 280 6" 0 0 #DIV/0! #DIV/0!

072 Reserva 3/23/2017 #VALUE! 25.5 27.2 280 6" 0 0 #DIV/0! #DIV/0!

073 7 3/24/2017 3/31/2017 26.7 27.3 280 4" 181 0 0.0 0.0

074 7 3/24/2017 3/31/2017 26.7 27.3 280 4" 181 0 0.0 0.0

075 Interruptor de potencia tripolar 28 3/24/2017 4/21/2017 26.7 27.3 280 4" 181 0 0.0 0.0
4,5,6 Pararrayos 8 Pedestal 6 Probetas
076 Transformador de tencion 4 28 3/24/2017 4/21/2017 26.7 27.3 280 4" 181 0 0.0 0.0

077 Reserva 3/24/2017 #VALUE! 26.7 27.3 280 4" 0 0 #DIV/0! #DIV/0!

078 Reserva 3/24/2017 #VALUE! 26.7 27.3 280 4" 0 0 #DIV/0! #DIV/0!

079 7 3/25/2017 4/1/2017 25.8 25.6 280 5.5" 181 0 0.0 0.0

080 7 3/25/2017 4/1/2017 25.8 25.6 280 5.5" 181 0 0.0 0.0

081 Portico de Barras 3,4 28 3/25/2017 4/22/2017 25.8 25.6 280 5.5" 181 0 0.0 0.0
Pararrarayos 7 Trasformador Zapata Pedestal 6 Probetas
082 de Tension 5 28 3/25/2017 4/22/2017 25.8 25.6 280 5.5" 181 0 0.0 0.0

083 Reserva 3/25/2017 #VALUE! 25.8 25.6 280 5.5" 0 0 #DIV/0! #DIV/0!

084 Reserva 3/25/2017 #VALUE! 25.8 25.6 280 5.5" 0 0 #DIV/0! #DIV/0!
CONTROL DE COLOCACIN DE CONCRETO EN OBRA

Temperatura Temperatura DISEO


ITEM Descripcin Estructura Edad (Das) Fecha Vaceado Fecha de Rotura Slump (Pg) AREA KN KG F^C(Kg/cm2) % Resistencia OBSERVACIONES
Ambiente de Concreto Kg/CM2
CONTROL DE COLOCACIN DE CONCRETO EN OBRA

Temperatura Temperatura DISEO


ITEM Descripcin Estructura Edad (Das) Fecha Vaceado Fecha de Rotura Slump (Pg) AREA KN KG F^C(Kg/cm2) % Resistencia OBSERVACIONES
Ambiente de Concreto Kg/CM2