Documentos de Académico
Documentos de Profesional
Documentos de Cultura
ASHRAE HANDBOOK
This report includes additional information, and technical errors Table 2 Values
found between June 15, 2010, and April 1, 2013, in the inch-pound (2010 Refrigeration, Chapter 11, p. 23)
(I-P) editions of the 2010, 2011, and 2012 ASHRAE Handbook Refrigerant f
volumes. Occasional typographical errors and nonstandard symbol
labels will be corrected in future volumes. The most current list of On the low side of a limited-charge cascade system:
Handbook additions and corrections is on the ASHRAE web site R-13, R-13B1, R-503 2.0 (0.163)
(www.ashrae.org). R-14 2.5 (0.203)
R-23, R-170, R-508A, R-508B, R-744, R-1150 1.0 (0.082)
The authors and editor encourage you to notify them if you
find other technical errors. Please send corrections to: Handbook Other applications:
Editor, ASHRAE, 1791 Tullie Circle NE, Atlanta, GA 30329, or R-11, R-32, R-113, R-123, R-142b, R-152a, R-290, R- 1.0 (0.082)
e-mail mowen@ashrae.org. 600, R-600a, R-764
R-12, R-22, R-114, R-124, R-134a, R-401A, R-401B, (0.131)
R-401C, R-405A, R-406A, R-407C, R-407D, R-407E,
2010 Refrigeration R-409A, R-409B, R-411A, R-411B, R-411C, R-412A,
R-414A, R-414B, R-500, R-1270
Licensed for single user. 2013 ASHRAE, Inc.
Ch. 1. All existing references to Table 19 should be to Table 20. All R-115, R-402A, R-403B, R-404A, R-407B, R-410A, 2.5 (0.203)
existing references to Table 20 should be to Table 19. R-410B, R-502, R-507A, R-509A
R-143a, R-402B, R-403A, R-407A, R-408A, R-413A 2.0 (0.163)
p. 10.4, Table 3. Replace the table with the following. R-717 0.5 (0.041)
Table 3 Cellular Glass Insulation Thickness for R-718 0.2 (0.016)
Indoor Design Conditions
(90F Ambient Temperature, 80% Relative Humidity, 0.9 Emittance, p. 50.4, Horsepower entry. The value for horsepower should be
0 mph Wind Velocity) 550 ftlbf /s2, not 500.
(2010 Refrigeration, Chapter 10, p. 4)
Nominal
2011 HVAC Applications
Pipe Operating Temperature, F
Pipe Size, (CD only) Table of Contents, p. 2. Replace the second instance of
in. 40 20 0 20 40 60 80 100 Building Operations and Management with General Applica-
0.50 1.0 1.0 1.5 1.5 2.0 2.0 2.0 2.5 tions.
0.75 1.0 1.5 1.5 2.0 2.0 2.0 2.5 2.5 Contributors List. For Chapter 4, add Dennis Wessel, Karpinski
1.00 1.0 1.5 1.5 2.0 2.0 2.0 2.5 2.5
Engineering.
1.50 1.0 1.5 1.5 2.0 2.5 2.5 3.0 3.0
2.00 1.0 1.5 1.5 2.0 2.5 2.5 3.0 3.0 p. 28.8, 1st col. Under U.S. Evolutionary Power Reactor (USEPR),
2.50 1.0 1.5 2.0 2.5 2.5 3.0 3.0 3.0 delete (30 Pa).
3.00 1.0 1.5 2.0 2.5 2.5 3.0 3.0 3.0
4.00 1.0 1.5 2.0 2.5 2.5 3.0 3.0 3.5 p. 35.4, end of 2nd para. It should be = for all conditions.
5.00 1.5 1.5 2.0 2.5 2.5 3.0 3.0 3.5
p. 35.5, Eq. (17). The equation should be Fsg = (1 cos ) /2.
6.00 1.5 2.0 2.0 2.5 3.0 3.0 3.5 3.5
8.00 1.5 2.0 2.0 2.5 3.0 3.0 3.5 3.5 p. 35.10, 2nd col., 3rd para. from bottom. The slope should be
10.00 1.5 2.0 2.0 2.5 3.0 3.5 3.5 4.0 0.82 /0.69 = 1.19.
12.00 1.5 2.0 2.0 2.5 3.0 3.5 3.5 4.0
14.00 1.5 2.0 2.5 3.0 3.0 3.5 4.0 4.0 p. 35.22, Example 7, Solution. The load collector ratio should use
16.00 1.5 2.0 2.5 3.0 3.5 3.5 4.0 4.5 Eq. (41).
18.00 1.5 2.0 2.5 3.0 3.5 3.5 4.0 4.5
p. 35.23, 2nd col., last para. The average wind load on a tilted
20.00 1.5 2.0 2.5 3.0 3.5 3.5 4.0 4.5
24.00 1.5 2.0 2.5 3.0 3.5 4.0 4.0 4.5
roof should be 25 lb/ft2.
28.00 1.5 2.0 2.5 3.0 3.5 4.0 4.0 4.5 p. 35.27, Symbols. Delete the second definition for Aap .
30.00 1.5 2.0 2.5 3.0 3.5 4.0 4.0 4.5
36.00 1.5 2.0 2.5 3.0 3.5 4.0 4.5 4.5 p. 36.9, Table 4. Replace the table with the one on p. A.3.
Notes:
1. Insulation thickness is chosen either to prevent or minimize condensation on outside
p. 48.20, 2nd col. For frequency range #1, consult Table 13 for A f.
jacket surface or to limit heat gain to 8 Btu/hft2, whichever thickness is greater. In definitions for Eq. (10), refer to Table 12 for a .
2. All thicknesses are in inches.
3. Values do not include safety or aging factor. Actual operating conditions may vary. p. 48.45, Table 47. Deflection values for cooling towers should be
Consult a design engineer for appropriate recommendation for your specific system.
4. Data calculated using NAIMA 3E Plus program.
Floor Span
Slab on
p. 11.23, Table 2. Amend the table values as shown above right. Equipment Type Grade Up to 20 ft 20 to 30 ft 30 to 40 ft
p. 19.2, Eq. (4). Change two to xwo. Cooling Towers 0.25 3.5 3.5 3.5
0.25 2.5 2.5 2.5
p. 19.7, Eq. (10). Change to t to (to t) 2. 0.25 0.75 0.75 1.5
pp. 55.12-13, Eqs. (27), (28), (30), and (31). For all four equations, p. 41.3, Fig. 3. Replace parts B and C of the graphic with the hori-
the denominators of the last two terms should be b and a, not 2b and zontal polymer tube shown above right.
2a. Also, for Eq. (31), change the first + sign to a sign.
p. 44.8, Table 1. In both equations for flow and head, change the
p. 60.9, Fig. 9. Replace the figure with the one above left. minuses to equals signs.
This file is licensed to Rabee Taleb (rabee_t@hotmail.com). Publication Date: 6/1/2013