Está en la página 1de 16

Type MBCH 12, 13, 16

Biased Differential Protection for


Transformers, Generators and
Generator Transformers
Type MBCH 12, 13, 16
Biased Differential Protection for Transformers,
Generators and Generator Transformers

Figure 1:
Relay Type MBCH 16
withdrawn from case

Features
Independent single phase relays
suitable for single or three phase
transformer protection schemes
Fast operating times, typically
10ms to 25ms
Dual slope percentage bias
restraint characteristic with
adjustable basic threshold setting
of 10% to 50% In, selectable in
10% steps Application controlling each winding, as in
mesh or one and a half circuit-
High stability during through The type MBCH 12, 13 and 16 are breaker busbar arrangements.
faults even under conditions of CT high-speed, single phase, biased Typical applications are shown in
saturation and with up to 20% differential relays suitable for the Figures 2 to 8.
ratio imbalance resulting from the protection of two- or three-winding
effects of tap changing and CT power transformers, auto- As a general low impedance biased
errors transformers, or generator- differential relay, the MBCH may
transformer units. Up to six biased also be regarded as an alternative
Magnetising inrush restraint over-
current inputs can be provided to to the high impedance type relay for
excitation (over-fluxing) restraint
cater for power transformers with the protection of reactors, motors
Up to six biased inputs more than two windings and/or and generators.
Transformer phase group and line more than one circuit-breaker
CT ratio correction by means of
separate tapped interposing
transformers where required Models Available
Two isolated change-over tripping Type Designation No. of Bias Application
contacts plus one isolated Circuits
normally open latching alarm
MBCH 12 2 Two-winding power transformer
contact. The individual phase
elements can be interconnected MBCH 13 3 Generally 3 winding power transformer,
to provide six isolated change- where bias is required from each of the 3
over tripping contacts for three groups of CTs
phase schemes MBCH 16 6 For all applications requiring 4, 5 or 6
bias circuits
Light emitting diode (led) fault
indication.

2
Description be used where necessary for power The output from T1 is rectified and
transformer phase shift correction. combined with the bias voltage to
The relay is extremely stable during produce a signal which is applied
through faults and provides high- For some applications, no phase
to the amplitude comparator. The
speed operation on internal faults, shift correction is necessary, but a
comparator output is in the form of
even when energised via line zero sequence current trap is
pulses which vary in width
current transformers of only required to prevent zero sequence
depending on the amplitude of the
moderate output. Immunity to false currents, due to external earth faults
combined bias and difference
tripping due to large inrush currents being seen by the differential relay.
voltages. Where the measurement
on energisation of the power Two secondary windings are
of the interval between these pulses
transformer, and also during provided on the interposing
indicates less than a preset time, an
overfluxing conditions, is provided transformer to allow the creation of
internal fault is indicated and a trip
by the use of a novel feature not an isolated delta connection for this
signal, initiated after a short delay
involving harmonic filter circuits and purpose.
( 1 s), level set by the bias. If, during
f
their associated delay. Each relay case incorporates a the above mentioned delay, the
It can be beneficial to supplement terminal block, for external instantaneous value of differential
the differential protection by a connections, into which the module current falls below the threshold and
restricted earth fault relay, is plugged. Removal of the module remains below for longer than a
1
especially where the neutral point of from the case automatically causes further preset time, ( 4f s) as it would
the power transformer is earthed the incoming line current transformer during transformer magnetising
via a current limiting resistor. The connections to be short-circuited, inrush conditions, the trip timer is
restricted earth fault relay (type followed by the open circuiting of reset and operation of the relay
MCAG 14 or MFAC 14) may be the relay tripping circuit. blocked.
connected into the differential Setting adjustment is by means of An unrestrained high-set circuit,
circuitry, in association with a frontplate mounted switches. which monitors the differential
current transformer in the neutral Indication of relay operation is current, will override the amplitude
connection of the power provided by an led, also mounted comparator circuit and operate the
transformer, as indicated in Figures on the relay frontplate, and which is relay output element when the
3 and 6. Additional line current resettable by a push button operable difference current is above the high-
transformers are not required. with the relay cover in position. The set setting.
For optimum performance, the output elements consist of auxiliary
attracted armature relays, the Variable percentage bias
differential scheme should be
contacts of which are capable of restraint
arranged so that the relay will see
rated current when full load current circuit-breaker tripping. Three Even under normal operating
flows in the protected circuit. This electrically independent contacts, conditions, unbalanced currents
may be achieved either by comprising two self-resetting change- (spill current), may appear. The
appropriate choice of main line over contacts and one hand reset, magnitude of the spill current
current transformers, or the use of normally open contact are provided depends largely on the effect of tap
interposing current transformers. per pole, for circuit breaker tripping changing. During through faults the
and alarm purposes respectively. By level of spill current will rise as a
When protecting a power interconnecting relays as shown in function of the fault current level. In
transformer, the differential setting Figure 9, up to six self-resetting order to avoid unwanted operation
should not be less than 20% relay change-over contacts can be due to spill current and yet maintain
rated current, to give stability for provided for the three-phase tripping high sensitivity for internal faults,
moderate transient overfluxing. The of up to six circuit-breakers. when the difference current may be
maximum spill current with through
relatively small, the variable
load current should generally be Functional Description percentage bias restraint
kept below 20% of the relay rated
The differential transformer characteristic shown in Figure 11 is
current, allowing for CT mismatch
protection measuring circuit is based used. The setting Is is defined as the
and possible tap changer
on the well known Merz-Price minimum current, fed into one of the
operation. Where higher levels of
circulating current principle. bias inputs and the differential
spill current exist, the relay setting
Figure 10 shows the relay functional circuit, to cause operation. This is
may need to be increased.
block diagram. The outputs from adjustable between 10% and 50%
A tapped interposing transformer is of rated current.
each bias restraint transformer T3 to
available for ratio matching of the
T5, proportional to the appropriate The initial bias slope is 20% from
main current transformers. The taps
primary line currents, are rectified zero to rated current. This ensures
are spaced at intervals of 4% and
and summed to produce a bias sensitivity to faults whilst allowing a
better, allowing matching to well
restraint voltage. Any resulting 15% current transformer ratio
within 2% in most cases. The same
difference current is circulated mismatch when the power
interposing transformers may also
through transformers T1 and T2.

3
transformer is at the limit of its tap restraint a new technique has been currents are possible it is
range, plus 5% for CT ratio error. developed to recognise magnetising recommended that an over-fluxing
Above rated current, extra errors inrush current and restrain the relay relay, responsive to V/Hz, should
may be gradually introduced as a during such periods. be used. Such relays are designed
result of CT saturation. The bias to operate after a time delay of
In practice the magnetising inrush
slope is therefore, increased to 80% several seconds
current waveform is characterised
to compensate for this.
by a period during each cycle when
At the inception of a through fault little or no current flows, as shown in High-set
the bias is increased to more than Figure 12. By measuring this An unrestrained instantaneous high-
100%. It then falls exponentially to characteristic zero period, the relay set feature is incorporated to
the steady state characteristic shown is able to determine whether the provide extremely fast clearance of
in Figure 11. This transient bias difference current is due to heavy internal faults. This
matches the transient differential magnetising inrush current or to instantaneous feature has an auto-
currents that result from CT genuine fault current and thereby ranging setting, normally low at
saturation during through faults, so inhibit operation only during the normal load through-put, but
ensuring stability. inrush condition. This new automatically rising to a higher
measurement technique ensures that value under heavy through fault
However, during internal faults this
operating times remain unaffected conditions. Furthermore, immunity
transient bias is suppressed to
even during periods of significant to magnetising current inrush is
ensure that no additional delay in
line CT saturation. guaranteed provided the first peak
operation is caused.
of the waveform is no greater than
The transient bias circuits of the Transformer over-excitation 12 times the rated rms current. The
three phases are externally problem relating to choice of a
interconnected to ensure optimum When a large section of system
high-set threshold which avoids
stability of the protection during load is suddenly disconnected from
tripping on magnetising current
through faults. a power transformer the voltage at
inrush does not, therefore, occur
the input terminals of the transformer
and no user adjustment is required.
Magnetising inrush restraint may rise by 10-20% of rated value
giving rise to an appreciable Auxiliary interposing
Particularly high inrush currents may
increase in transformer steady state transformer
occur on transformer energisation
exciting current. The resulting
depending on the point on wave of Auxiliary interposing transformers
exciting current may rise to a value
switching as well as on the are available as single or triple unit
high enough to operate the
magnetic state of the transformer assemblies as illustrated in Figure
differential protection relay, since
core. 15.
this current is seen by the input line
Since the inrush current flows only in current transformers only. Exciting A comprehensive tap adjustment
the energised winding the protection currents of this order are due to the range is available as indicated by
relay sees this current as difference input voltage exceeding the knee the details of turns per tap shown in
current. To avoid unwanted tripping point voltage of the power Table 2. All line CT connections
of the power transformer it has been transformer resulting in a should be made to the terminal strip
customary to incorporate second magnetising current wave shape as marked S1 S2 S3 S4 P1 P2.
harmonic restraint to block the shown in Figure 13. By detecting
protection relay. Practice has shown the periods when the current Selection of appropriate primary
that this technique may result in remains close to or at zero, in a taps is made using the flexible
significantly slower operating times similar manner to that used to jumper leads connected to terminals
for internal faults when second identify magnetising inrush current, P1 and P2. See Figure 16. The
harmonics are introduced into the the relay is able to detect and tertiary winding S3-S4 must be
current waveform by core saturation remain insensitive to substantial used in series with winding S1-S2
of line CTs. over-excitation current. where a delta output winding is
required to ensure correct operation
In order to overcome the problems Where extremely large and
of the differential scheme.
associated with second harmonic potentially damaging over-exciting

4
DY1
A A
B B
C C

23 25 27
MBCH 12 12
24 26 28

23 25 27
MBCH 12 12
24 26 28

23 25 27
12
MBCH 12

24 26 28

Figure 2:
Application diagram: relay type MBCH 12 with two biased inputs

DY1
A

Restricted E/F
relay

23 25 27
Phase 'A' 12
Relay MBCH 12
24 26 28

23 25 27
Phase 'B' 12
Relay MBCH 12
24 26 28

23 25 27

Phase 'C' 12
Relay

24 26 28 MBCH 12

Figure 3:
Typical connection diagram for MBCH 12 relays protecting a DY 1 transformer
with integral restricted earth fault relay

5
A

23 25 27

24 26 28

23 25 27

24 26 28

23 25 27

24 26 28

Figure 4:
Typical connection diagram for MBCH relays protecting a YD 11 transformer
on a phase by phase basis

23 25 27
12
24 26 28

23 25 27
12
24 26 28

23 25 27
12
24 26 28

Figure 5:
Typical connection diagram for MBCH 12 relays protecting a series reactor

6
Y(d1) YO
A

Restricted
E/F relay

21 23 25 27
MBCH 13
12
22 24 26 28

21 23 25 27

MBCH 13
22 24 26 28 12

21 23 25 27
12

22 24 26 28 MBCH 13

Figure 6:
Typical connection diagram for MBCH 13 relays protecting a Y(d) YO transformer with integral restricted earth fault relay

Y(d)YO

21 23 25 27
MBCH 13
12
22 24 26 28

21 23 25 27
MBCH 13
12
22 24 26 28

21 23 25 27
12

MBCH 13
22 24 26 28

Figure 7:
Typical connection diagram for MBCH 13 relays protecting a Y(d) YO transformer supplied from a mesh busbar

7
Generator

21 23 25 27 12
MBCH 13
22 24 26 28
N.E.R.
Unit
Transformer
21 23 25 27 12
MBCH 13
22 24 26 28

21 23 25 27
MBCH 13
22 24 26 28 12

Figure 8:
Typical connection diagram for MBCH 13 relays protecting a generator/transformer unit

13 1
+
Vx 3
14
5
Phase 'A'
12 2

10 4

13 1

14 3 All output contacts shown are


instantaneously initiated for any
5 internal fault condition when
12
Phase 'B' terminals No. 10 on each phase
2 unit are connected together
as shown.
10 4
Correct phase indication
6 is maintained.

13 1

3
14
5
Phase 'C'
12 2

10 4

Figure 9:
Connection for six change-over tripping contacts for three phase tripping of
up to six circuit breakers showing correct connection of the screened lead on
a three phase scheme

8
21 1
RL1-1 3
I3
5
22 T5
23 RL1 2 Trip output
2 RL1-2 4
I2
6
24 T4 Output
25 circuits
I1 10
Case earth Trip other phase
26 T3
1 2
13
3 4 +
Input
5 6 14 Vx
circuits
7 8
12
9 10 Bias
11 12 see note 2
Reset
13 14 T2
15 16 9
27 Operate RL2 RL2-1 11 Alarm
17 18 1
IDIFF
19 20
28 T1
21 22
Protective
23 24 safety
earth
25 26

27 28
Note 1: Note 2:
(a) C.T. shorting links make Terminal 12 on each phase assembly should be
before (b) & (c) disconnect interconnected by a screened lead GJO153 001
Module terminal with the screen connected to terminal 14.
block viewed (b) short terminals break before (c)
from rear

Figure 10:
Block diagram: Biased differential protection relay type MBCH 13 with three biased inputs

2
Differential current (xIn) Operate
pe
Figure 11: = I1 +I2 +I3 +I4 +I5 +I6 Slo Restrain
%
Typical percentage bias 80
characteristic 1
le
Setting Allowab or
ra ti o err
range pe 20%
(0.1-0.5) 20% Slo

0 1 2 3 4
Effective bias (xIn) = I1 +I2 +I3 +I4 +I5 +I6
2

Figure 12:
B
Typical magnetising
inrush waveforms

9
Figure 13:
Magnetising current with 0
transformer overfluxed

Operating time (cycles)


2

Figure 14:
Typical operating time
characteristic

Setting range

0
0.1 0.2 0.5 1 2 5 10 20 50 100
Fault current (xIn)

119 (1) 4 off M5


83.5 (1) clearance
holes

1 2 3 4 5 6 X 7 8 9 1 2 3 4 5 6 X 7 8 9 1 2 3 4 5 6 X 7 8 9
Primary taps

145 117 Earth


S1 S2 S3 S4 P1 P2 S1 S2 S3 S4 P1 P2 S1 S2 S3 S4 P1 P2

11,5
310 (3)
145
343 (3)

M4 terminal screws

Figure 15:
Outline details of single and triple unit auxiliary interposing transformer assembly

1 2 3 4 5 6 X 7 8 9
Flexible
jumper
Output leads
to relay

Figure 16: S1 S2 S3 S4 P1 P2
Winding arrangement of
single pole of auxiliary
interposing transformer
Input from
line CT's

10
Technical Data

Ratings
AC Current (In) 1A or 5A
Frequency 50Hz or 60Hz
Auxiliary dc supply (Vx) Voltage Rating Operating
(Vdc) range (Vdc)
30 - 34 24 - 41
48 - 54 37.5 - 65
110 - 125 87.5 - 150
220 - 250 175 - 300

Minimum basic setting


Biased feature 10%, 20%, 30%, 40%, 50% In
High-set feature 4In up to through bias currents of 9In,
thereafter increasing gradually to 8In
at through bias currents of 14In

High-set operation Immunity to magnetising current


inrush is guaranteed provided the first
peak of the waveform is no greater
than 12 times the rated rms current.
Accuracy 10%

Operating characteristic Dual slope, 20% up to In,


80% above In.

Operating time Typically 10ms to 25ms

Number of current inputs MBCH 12 - 2 biased inputs


MBCH 13 - 3 biased inputs
MBCH 16 - 6 biased inputs
AC thermal rating
Continuous MBCH 13,16: 4In
MBCH 12: 2In
Short time, all versions 100In for 1s with a
maximum of 400A

DC burden
With output H/A not picked up
DC voltage Burden at upper
rating (V) voltage rating (W)
30 - 34 Approx 3
48 - 54 Approx 3
110 - 125 Approx 4
220 - 250 Approx 8
With output H/A picked up
DC voltage Burden at upper
rating (V) voltage rating (W)
30 - 34 Approx 4
48 - 54 Approx 4
110 - 125 Approx 7
220 - 250 Approx 12
AC burden
Through current only
(per bias circuit) Approx 0.15VA (In = 1A)
Ithro - 1 x In Approx 0.30VA (In = 5A)
Bias and differential circuit only Approx 2.80VA (In = 1A)
Idiff = 1 x In Approx 3.20VA (In = 5A)

11
Contacts Two change-over self-reset tripping
contacts per relay. (For 3 phase
schemes relays can be interconnected
as shown in Figure 9 to provide
instantaneous operation of all three
sets of change-over tripping contacts.)
One normally open latching contact
per relay.

Make and carry: 7500VA for 0.2s


with maxima of 30A and 300V ac or dc.
Carry continuously: 5A ac or dc
Break: 1250VA ac or 50W dc resistive,
25W, L/R = 0.04s.
Subject to maxima of 5A and 300V.

Durability
Loaded contact 10,000 operations minimum
Unloaded contact 100,000 operations minimum
Operation indicator Light emitting diode (red), hand reset
Line current transformer requirements
Application Knee Point Voltage Vk Through Fault Stability
Note: Values to be as given
below, with minima of 60
In
for star-connected CTs and
100 for delta connected CTs

In X/R If
Transformers Vk  NM 24 In [Rct+2Rl+Rt] 40 15In
Generators
Generator
transformers Vk  24In [Rct+2Rl+Rt] 40 15In
Overall generator-
transformer/units Vk  48In [Rct+2Rl+Rt] 120 15In
Motors
Shunt reactors
Series Reactors
also Transformers
connected to a
Mesh Corner Vk  24In [Rct+2Rl+Rt] 40 15In
having two sets of
CTs each
supplying separate
relay inputs
Note: CTs should
Vk  48In [Rct+2Rl+Rt]
{ 40

120
40In

15In
be of equal ratio
and magnetisation
characteristic

Where:
In = Rated line CT secondary current (1A or 5A).
Rct = Resistance of line CT secondary winding.
Rl = Resistance of a single lead from line CT to relay.
Rt = Effective resistance of interposing CT where used.
X/R = Maximum value of primary system reactance/resistance ratio.
f = Maximum value of through fault current.
Table 1: Current Transformer requirements.

12
Auxiliary interposing transformers
Nominal secondary current rating, In 1A or 5A
Nominal current ratios selectable in 0.58 - 1.73/1
4% In steps see Table 1 2.89 - 8.66/1
2.89 - 8.66/5
Note: Higher primary currents can be
catered for. Refer to publication
R-6077
Rated frequency 50/60Hz
Thermal withstand 4 x In continuous
30 x In for 10s
100 x In for 1s with 400A maximum
Effective resistance Rt 2.0 for 0.58 - 1.73/1ratio
0.2 for 2.89 - 8.66/5 ratio
0.15 for 2.89 - 8.66/1ratio
Insulation test voltage 2kV rms 1 minute, 50Hz
Maximum terminal block wire size 84 strand, 0.3mm
Dimensions Outline drawings for single and triple
group shown in Figure 15
Weight 4kg single unit
12kg triple unit
Number of turns

Primary top Transformer rating


terminals 1/1A 5/1A 5/5A
12 5 1 1
23 5 1 1
34 5 1 1
45 5 1 1
56 125 25 25
X7 25 5 5
78 25 5 5
89 25 5 5
S1 S2 125 125 25
S3 S4 90 90 18
Table 2: Interposing CTs: number of turns per tap.

High Voltage withstand


Dielectric withstand
IEC 60255-5: 1977 2kV rms for 1 minute between all
terminals and case earth.
2kV rms for 1 minute between all
terminals of independent circuits, with
terminals on each independent circuit
connected together.
1 kV rms for 1 minute across normally
open contacts.

High voltage impulse


IEC 60255-5: 1977 Three positive and three negative
impulses of 5kV peak, 1.2/50s, 0.5J
between all terminals of the same
circuit (except output contacts),
between independent circuits, and
between all terminals connected
together and case earth.

13
Electrical environment
DC supply interruption
IEC 60255-11: 1979 The unit will withstand a 10ms
interruption in the auxiliary supply,
under normal operating conditions,
without de-energising.
AC ripple on DC supply The unit will withstand 12% ac ripple
IEC 60255-11: 1979 on the dc supply

High frequency disturbance


IEC 60255-22-1: 1988 Class III 2.5kV peak between independent
circuits and case.
1.0kV peak across terminals of the
same circuit.
Fast transient disturbance
IEC 60255-22-4: 1992 Class IV 4.0kV, 2.5kHz applied directly to
auxiliary supply.
4.0kV, 2.5kHz applied directly to all
inputs.
Surge immunity
IEC 61000-4-5: 1995 Level 3 2.0kV peak, 1.2/50s between all
groups and case earth.
2.0kV peak, 1.2/50s between
terminals of each group.
EMC compliance
89\336\EEC Compliance with the European
Commission Directive on EMC is
claimed via the Technical Construction
File route.
EN5008-2: 1994 Generic Standards were used to
EN5008-2: 1995 establish conformity.
Product safety
73/23/EEC Compliance with the European
Commission Low Voltage Directive.

EN 61010-1: 1993/A2: 1995 Compliance is demonstrated by


EN 60950: 1992 All: 1997 reference to generic safety standards.

Atmospheric environment
Temperature
IEC 60255-6: 1988 Storage and transit -25C to + 70C
Operating -25C to +55C
IEC 60068-2-1: 1990 Cold
IEC 60068-2-2: 1974 Dry heat

Humidity
IEC 60068-2-3 56 days at 93% RH and 40C
Enclosure protection
IEC 60529: 1989 IP50 (dust protected)

Mechanical environment
Vibration
IEC 60255-21-1: 1988 Response Class 1
Seismic
IEC 60255-21-3: 1993 Class 2

14
Cases
52
Relays type MBCH are housed in 4 holes 4.4
97 23.5
size 4 cases as shown in Figure 17.

168 159

Push button
projection 10 max. 99
Panel cut-out:
Flush mounting fixing details

32 212 25 min.

177 157 max.

Reset

77 Flush mounting 11
All dimensions in mm

Figure 17:
Case outline size 4

Information required with order


Note: 3 single-phase MBCH relays are required for a 3-phase scheme. Please
state total number of single-phase relays required.
Rated current In
Rated frequency
Auxiliary dc supply voltage Vx
Number of current bias inputs:
MBCH 12: 2 input
MBCH 13: 3 input
MBCH 16: 6 input

Auxiliary interposing transformer


Rated current In
Current ratio
Mounting: single or triple unit

Associated Publications
Interposing matching CTs for use with MBCH relays R6077
MIDOS system R6001
MMLG/MMLB test block/test plug R6004

15
ALSTOM T&D Protection & Control Ltd St Leonards Works, Stafford, ST17 4LX England
Tel: 44 (0) 1785 223251 Fax: 44 (0) 1785 212232 Email: enquiries@pcs.alstom.co.uk Internet: www.alstom.com
1998 ALSTOM T&D Protection & Control Ltd

Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should
only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
ALSTOM T&D Protection & Control Ltd cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.

Publication R-6070L 060010 Printed in England.

También podría gustarte