PETUNJUK TEKNIS

Petunjuk teknis penggunaan SNI 1729


Spesifikasi untuk bangunan gedung baja
struktural
Daftar Isi
Daftar Isi ................................................................................................................................ i
Prakata .................................................................................................................................vi
Bab A Ketentuan Umum ..................................................................................................... 1
A1. RUANG LINGKUP ................................................................................................................... 1
A2. SPESIFIKASI, TATA CARA DAN STANDAR YANG DIACU ............................................................ 1
A3. MATERIAL .............................................................................................................................. 1
REFERENSI BAB A ........................................................................................................................... 1
Bab B Persyaratan Desain .................................................................................................. 2
B1. KETENTUAN UMUM ............................................................................................................... 2
B2. BEBAN DAN KOMBINASI BEBAN ............................................................................................. 2
B3. DASAR DESAIN ....................................................................................................................... 2
B4. PROPERTI KOMPONEN STRUKTUR.......................................................................................... 2
REFERENSI BAB B ........................................................................................................................... 2
Bab C Desain untuk Stabilitas ............................................................................................. 3
C1. PERSYARATAN STABILITAS UMUM ......................................................................................... 3
C2. PERHITUNGAN KEKUATAN PERLU .......................................................................................... 3
CONTOH C.1A DESAIN RANGKA PENAHAN MOMEN DENGAN METODE ANALISIS LANGSUNG ........ 4
CONTOH C.1B DESAIN RANGKA PENAHAN MOMEN DENGAN METODE PANJANG EFEKTIF ........... 10
CONTOH C.1C DESAIN RANGKA PENAHAN MOMEN DENGAN METODE ORDE PERTAMA ............. 18
Ringkasan beban-beban untuk analisis Rangka Penahan Momen ................................................. 20
Bab D Desain dari Komponen Struktur untuk Tarik ........................................................... 22
D1. PEMBATASAN KELANGSINGAN ............................................................................................ 22
D2. KEKUATAN TARIK ................................................................................................................. 22
D3. LUAS NETO EFEKTIF ............................................................................................................. 22
D4. KOMPONEN STRUKTUR TERSUSUN ...................................................................................... 22
D5. KOMPONEN STRUKTUR TERSAMBUNG-SENDI...................................................................... 22
D6. EYEBAR ................................................................................................................................ 22
CONTOH D.1 BATANG TARIK DENGAN PROFIL WF ....................................................................... 23
CONTOH D.2 BATANG TARIK PROFIL SIKU .................................................................................. 26
CONTOH D.3 BATANG TARIK PROFIL T ......................................................................................... 29
CONTOH D.4 BATANG TARIK PROFIL TABUNG PERSEGI PANJANG ................................................ 32
CONTOH D.5 BATANG TARIK PIPA ................................................................................................ 35
CONTOH D.6 BATANG TARIK PROFIL SIKU GANDA ...................................................................... 38
CONTOH D.7 BATANG TARIK TERHUBUNG-SENDI ........................................................................ 41

i
CONTOH D.8 BATANG TARIK EYEBAR ........................................................................................... 45
CONTOH D.9 PELAT DENGAN BAUT BERSELING ........................................................................... 47
Bab E Desain Komponen Struktur untuk Tekan ................................................................ 49
E1. KETENTUAN UMUM ............................................................................................................. 49
E2. PANJANG EFEKTIF ................................................................................................................ 49
E3. TEKUK LENTUR KOMPONEN STRUKTUR TANPA ELEMEN PENAMPANG LANGSING ................ 49
E4. TEKUK TORSI DAN TEKUK TORSI LENTUR KOMPONEN STRUKTUR TANPA ELEMEN LANGSING 50
E5. KOMPONEN STRUKTUR TEKAN SIKU TUNGGAL .................................................................... 50
E6. KOMPONEN STRUKTUR TERSUSUN ........................................................................................ 50
E7. KOMPONEN STRUKTUR DENGAN ELEMEN LANGSING .......................................................... 50
CONTOH E.1. PERHITUNGAN KUAT TEKAN PROFIL WF ................................................................. 51
CONTOH E.2. KOLOM TERSUSUN DENGAN BADAN LANGSING .................................................. 53
CONTOH E.3. KOLOM TERSUSUN DENGAN SAYAP LANGSING ...................................................... 57
CONTOH E.4. BATANG TEKAN SIKU GANDA DENGAN ELEMEN TIDAK LANGSING ....................... 61
CONTOH E.5. BATANG TEKAN SIKU GANDA DENGAN ELEMEN LANGSING .................................. 65
CONTOH E.6. BATANG TEKAN PROFIL WT TANPA ELEMEN LANGSING ........................................ 69
CONTOH E.7. BATANG TEKAN PROFIL WT DENGAN ELEMEN LANGSING ..................................... 73
CONTOH E.8. PERHITUNGAN KUAT TEKAN PROFIL PSB .............................................................. 77
CONTOH E.9. PERHITUNGAN KUAT TEKAN PROFIL PSB DENGAN ELEMEN LANGSING ................... 79
CONTOH E.10. PERHITUNGAN KUAT TEKAN PROFIL PIPA ............................................................. 82
CONTOH E.11. KOLOM I TERSUSUN DENGAN UKURAN SAYAP BERBEDA .................................... 84
Bab F Desain Komponen-komponen struktur untuk lentur ............................................... 89
PENDAHULUAN ........................................................................................................................... 89
F1. KETENTUAN UMUM ............................................................................................................. 89
F2. KOMPONEN STRUKTUR KOMPAK SIMETRIS GANDA PROFIL I DAN KANAL MELENTUR DI SUMBU
MAJOR ........................................................................................................................................ 89
F3. KOMPONEN STRUKTUR PROFIL I SIMETRIS GANDA DENGAN BADAN KOMPAK DAN
NONKOMPAK ATAU SAYAP LANGSING MELENGKUNG DI SUMBU MAJOR .................................... 91
F4. KOMPONEN STRUKTUR PROFIL I LAIN DENGAN BADAN KOMPAK ATAU NONKOMPAK
MELENTUR DI SUMBU MAJOR ..................................................................................................... 91
F5. KOMPONEN STRUKTUR PROFIL I SIMETRIS GANDA DAN SIMETRIS TUNGGAL DENGAN BADAN
LANGSING MELENTUR DI SUMBU MAJOR .................................................................................... 91
F6. KOMPONEN STRUKTUR PROFIL I DAN KANAL MELENTUR DI SUMBU MINOR ........................ 91
F7. KOMPONEN STRUKTUR PSB PERSEGI DAN PERSEGI PANJANG SERTA KOMPONEN STRUKTUR
BERBENTUK BOKS ........................................................................................................................ 92

ii
F8. PSB BUNDAR ........................................................................................................................ 92
F9. PROFIL T DAN SIKU GANDA YANG DIBEBANI DALAM BIDANG SIMETRI ................................. 92
F10. SIKU TUNGGAL ................................................................................................................... 92
F11. BATANG TULANGAN PERSEGI PANJANG DAN BUNDAR ........................................................ 92
F12. PROFIL-PROFIL TIDAK SIMETRIS .......................................................................................... 93
F13. PROPORSI BALOK DAN GELAGAR ........................................................................................ 93
CONTOH F.1-1 PERENCANAAN KOMPONEN STRUKTUR LENTUR PROFIL WF TERHADAP SUMBU
KUAT (TERSOKONG PENUH DALAM ARAH LATERAL) .................................................................... 97
CONTOH F.1-2 PERENCANAAN KOMPONEN STRUKTUR LENTUR PROFIL WF TERHADAP SUMBU
KUAT (TERSOKONG LATERAL DI TITIK SEPERTIGA BENTANG)........................................................ 99
CONTOH F.1-3 PERENCANAAN KOMPONEN STRUKTUR LENTUR PROFIL WF TERHADAP SUMBU
KUAT (TERSOKONG DI TITIK SETENGAH BENTANG) .................................................................... 103
CONTOH F.2-1 BALOK KANAL PENAMPANG KOMPAK TERSOKONG PENUH DALAM ARAH LATERAL
.................................................................................................................................................. 106
CONTOH F.2-2 BALOK KANAL PENAMPANG KOMPAK TERSOKONG DALAM ARAH LATERAL DI
SETIAP SEPERLIMA BENTANG .................................................................................................... 111
CONTOH F.3 BALOK WF DENGAN SAYAP NON-KOMPAK YANG MENGALAMI LENTUR TERHADAP
SUMBU KUAT ............................................................................................................................ 113
CONTOH F.4 PERANCANGAN BALOK PROFIL WF BERDASARKAN MOMEN INERSIA TERHADAP
SUMBU KUAT ............................................................................................................................ 115
CONTOH F.5 BALOK PROFIL WF YANG MENGALAMI LENTUR TERHADAP SUMBU LEMAH .......... 117
CONTOH F.6 BALOK PSB DENGAN SAYAP KOMPAK .................................................................. 119
CONTOH F.7 BALOK PSB DENGAN SAYAP NONKOMPAK............................................................. 121
CONTOH F.8 BALOK PSB DENGAN SAYAP LANGSING .................................................................. 124
CONTOH F.9 BALOK PROFIL PIPA LINGKARAN ............................................................................ 127
CONTOH F.10 BALOK PROFIL T ................................................................................................... 129
CONTOH F.11A BALOK PROFIL SIKU TUNGGAL ........................................................................... 132
CONTOH F.11B BALOK PROFIL SIKU TUNGGAL ........................................................................... 135
CONTOH F.11C BALOK PROFIL SIKU TUNGGAL ........................................................................... 138
CONTOH F.12 BATANG TULANGAN PERSEGI PANJANG .............................................................. 144
CONTOH F.13 BATANG TULANGAN BUNDAR ............................................................................. 146
Bab G Desain Komponen Struktur untuk Geser .............................................................. 148
PENDAHULUAN ......................................................................................................................... 148
G1. KETENTUAN UMUM ............................................................................................................ 148
G2. KOMPONEN STRUKTUR DENGAN BADAN TIDAK DIPERKAKU ATAU BADAN DIPERKAKU ..... 148
G3. AKSI MEDAN TARIK ............................................................................................................ 148

iii
G4. SIKU TUNGGAL .................................................................................................................. 149
G5. PSB PERSEGI PANJANG DAN KOMPONEN STRUKTUR BERBENTUK BOKS ............................ 149
G6. PSB BUNDAR...................................................................................................................... 149
G7. GESER SUMBU LEMAH PADA PROFIL SIMETRIS GANDA DAN TUNGGAL ............................... 149
G8. BALOK DAN GELAGAR DENGAN BUKAAN BADAN................................................................. 149
CONTOH G.1 BALOK PROFIL WF YANG MENGALAMI GESER TERHADAP SUMBU KUAT ............... 150
CONTOH G.2 BALOK PROFIL KANAL YANG MENGALAMI GESER TERHADAP SUMBU KUAT .......... 152
CONTOH G.3 BALOK PROFIL SIKU YANG MENGALAMI GESER .................................................. 154
CONTOH G.4 BALOK PROFIL PSB PERSEGI PANJANG YANG MENGALAMI GESER ......................... 156
CONTOH G.5 BALOK PROFIL PIPA YANG MENGALAMI GESER ..................................................... 158
CONTOH G.6 BALOK PROFIL SIMETRI GANDA YANG MENGALAMI GESER TERHADAP SUMBU
LEMAH ...................................................................................................................................... 160
G7. GESER SUMBU LEMAH PADA PROFIL SIMETRIS GANDA DAN TUNGGAL ............................... 162
CONTOH G.7 BALOK PROFIL SIMETRI TUNGGAL YANG MENGALAMI GESER TERHADAP SUMBU
LEMAH ...................................................................................................................................... 162
CONTOH G.8 BALOK PROFIL TERSUSUN DENGAN PENGAKU TRANSVERSAL ............................... 164
Bab H Desain Komponen Struktur untuk Kombinasi Gaya-gaya dan Torsi ................................. 170
CONTOH H.1 .............................................................................................................................. 171
CONTOH H.2. ............................................................................................................................. 175
CONTOH H.3 a. KEKUATAN TORSIONAL PENAMPANG PSB ...................................................... 181
CONTOH H.3 b. KEKUATAN TORSIONAL PENAMPANG PIPA ...................................................... 182
CONTOH H.3 c. KOMBINASI KEKUATAN LENTUR DAN TORSIONAL PENAMPANG PSB ............... 183
Bab I Desain Komponen Struktur Komposit .................................................................... 188
I1. KETENTUAN UMUM ............................................................................................................ 188
I2. GAYA AKSIAL ....................................................................................................................... 188
I3. LENTUR ............................................................................................................................... 188
I4. GESER ................................................................................................................................. 189
I5. KOMBINASI LENTUR DAN GAYA AKSIAL................................................................................. 189
I6. TRANSFER BEBAN ................................................................................................................ 189
I7. DIAFRAGMA KOMPOSIT DAN BALOK KOLEKTOR .................................................................. 190
I8. ANGKUR BAJA ..................................................................................................................... 190
CONTOH I.1 DESAIN BALOK INDUK KOMPOSIT ........................................................................... 196
CONTOH I.2 BATANG TEKAN TERISI BETON KOMPOSIT .............................................................. 208
CONTOH I.4 BATANG KOMPOSIT TERISI YANG MENAHAN GAYA TEKAN, MOMEN LENTUR DAN
GESER ........................................................................................................................................ 214

iv
CONTOH I.5 KOLOM BOKS KOMPOSIT TERISI BETON DENGAN ELEMEN LANGSING .................... 226
CONTOH I.6 KOLOM TEKAN KOMPOSIT TERISI BETON DAN PROFIL WF ................................... 234
CONTOH I.7 KOLOM KOMPOSIT TERISI BETON DAN PROFIL WF MENAHAN TARIK ..................... 240
CONTOH I.8 BATANG KOMPOSIT WF TERBUNGKUS BETON YANG MENAHAN GAYA TEKAN,
MOMEN LENTUR DAN GESER .................................................................................................... 242
Bab J Desain Sambungan............................................................................................... 258
CONTOH J.1 LAS SUDUT YANG MENGALAMI GESER LONGITUDINAL .......................................... 259
CONTOH J.2 LAS SUDUT YANG DIBEBANI DALAM ARAH MIRING ................................................ 262
CONTOH J.3 KOMBINASI TARIK DAN GESER PADA SAMBUNGAN TIPE TUMPU ........................... 264
CONTOH J.4A SAMBUNGAN SLIP-KRITIS DENGAN LUBANG SLOT PENDEK ................................ 266
CONTOH J.4B SAMBUNGAN SLIP-KRITIS DENGAN LUBANG SLOT PANJANG .............................. 267
CONTOH J.5 KOMBINASI TARIK DAN GESER PADA SAMBUNGAN SLIP-KRITIS ............................. 269
CONTOH J.6 KEKUATAN TUMPU PADA LUBANG DIBOR.............................................................. 272
CONTOH J.7 KEKUATAN TUMPU PELAT DASAR KOLOM PADA BETON ........................................ 273
Bab K Desain Sambungan Komponen Struktur PSB dan Boks .................................................... 277
CONTOH K.1 PELAT TRANSVERSAL YANG DIBEBANI TEGAK LURUS PSB PERSEGI........................ 278
Kondisi batas lain....................................................................................................................... 280
CONTOH K.2 PELAT LONGITUDINAL YANG DIBEBANI TEGAK LURUS PSB BUNDAR ...................... 281

v
Prakata

Informasi yang disajikan dalam petunjuk teknis ini telah disiapkan sesuai dengan prinsip-
prinsip teknik yang diakui dan hanya merupakan informasi umum saja. Meskipun diyakini
cukup akurat, informasi ini tidak boleh digunakan atau diandalkan untuk aplikasi tertentu
tanpa pemeriksaan secara professional, kompeten dan verifikasi keakuratan, kesesuaian,
dan penerapannya oleh seorang insinyur berlisensi profesional, desainer, atau arsitek.
Publikasi material yang terkandung di sini tidak dimaksudkan sebagai representasi atau
garansi pada bagian dari SNI 1729 atau dari orang lain yang tercantum disini, bahwa
informasi ini cocok sebagai informasi umum atau khusus atau bebas dari pelanggaran paten
atau hak paten. Siapa pun yang memanfaatkan informasi ini dianggap memenuhi semua
kewajiban yang timbul dari penggunaan tersebut.

Perhatian harus dilakukan bila mengandalkan spesifikasi lain dan peraturan yang
dikembangkan oleh badan-badan lain dan disusun sebagai referensi karena material
tersebut dapat dimodifikasi atau diubah dari waktu ke waktu setelah pencetakan edisi ini.
Penerbit tidak bertanggung jawab atas material tersebut selain untuk merujuk dan
menggabungkan sebagai referensi pada saat publikasi awal edisi ini.

vi
Bab A Ketentuan Umum

A1. RUANG LINGKUP

Petunjuk teknis ini berisi contoh-contoh desain ini dimaksudkan untuk menggambarkan
aplikasi SNI 1729, Spesifikasi untuk bangunan gedung baja struktural dalam aplikasi seismik
rendah. Untuk informasi pada aplikasi desain yang membutuhkan pendetailan seismik, lihat
AISC Seismic Design Manual.

A2. SPESIFIKASI, TATA CARA DAN STANDAR YANG DIACU

Pasal A2 mencakup daftar spesifikasi, tata cara dan standar terdetail yang diacu di seluruh
SNI 1729, Spesifikasi untuk bangunan gedung baja struktural.

A3. MATERIAL

Pasal A3 meliputi daftar material baja yang disetujui untuk digunakan dalam SNI 1729,
Spesifikasi untuk bangunan gedung baja struktural. Standar ASTM lengkap untuk material
baja yang paling umum digunakan dapat ditemukan di Selected ASTM Standards for
Structural Steel Fabrication (ASTM, 2011).

A4. GAMBAR DESAIN STRUKTURAL DAN SPESIFIKASI

Pasal A4 SNI 1729, Spesifikasi untuk bangunan gedung baja struktural mensyaratkan
bahwa gambar desain struktural dan spesifikasi memenuhi persyaratan AISC Code of
Standard Practice for Steel Buildings and Bridges (AISC, 2010b).

REFERENSI BAB A

SNI 1729, Spesifikasi untuk bangunan gedung baja struktural.


AISC (2010b), Code of Standard Practice for Steel Buildings and Bridges, American Institute
for Steel Construction, Chicago, IL.
AISC (2011), Steel Construction Manual, 14th Ed., American Institute for Steel Construction,
Chicago, IL.
ASTM (2011), Selected ASTM Standards for Structural Steel Fabrication, ASTM
International, West Conshohocken, PA.

1 dari 282
Bab B Persyaratan Desain

B1. KETENTUAN UMUM

B2. BEBAN DAN KOMBINASI BEBAN

Dengan tidak adanya peraturan bangunan gedung yang berlaku, kombinasi standar beban
yang akan digunakan dengan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
ini adalah yang berasal dari SNI 1727, Beban minimum untuk perancangan bangunan
gedung dan struktur lain.

B3. DASAR DESAIN

Bab B SNI 1729, Spesifikasi untuk bangunan gedung baja struktural menjelaskan dasar dari
desain, baik untuk DFBK maupun DKI.

Pasal ini membahas tiga tipe dasar dari sambungan: sambungan sederhana, sambungan
momen Tertahan Penuh (TP), dan sambungan momen Tertahan Sebagian (TS).

Informasi pada aplikasi dari ketentuan kemampuan layan dan genangan air dapat ditemukan
masing-masing dalam SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
Lampiran 2, dan penjelasan yang terkait. Contoh-contoh desain dan informasi lain yang
berguna mengenai topik ini diberikan dalam AISC Design Guide 3, Serviceability Design
Considerations for Steel Buildings, Edisi ke dua (West et al., 2003).

Informasi pada aplikasi dari ketentuan desain kebakaran dapat ditemukan pada SNI 1729,
Spesifikasi untuk bangunan gedung baja struktural Lampiran 4 dan penjelasan yang terkait.
Contoh-contoh desain dan informasi lain yang berguna mengenai topik ini diberikan dalam
AISC Design Guide 19, Fire Resistance of Structural Steel Framing (Ruddy et al., 2003).

B4. PROPERTI KOMPONEN STRUKTUR

SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Tabel B4.1a dan B4.1b
memberikan daftar lengkap pembatasan rasio lebar-terhadap-tebal untuk semua komponen
struktur tekan dan lentur.

REFERENSI BAB B

SNI 1727, Beban minimum untuk perancangan bangunan gedung dan struktur lain.
West, M., Fisher, J. and Griffis, L.G. (2003), Serviceability Design Considerations for Steel
Buildings, Design Guide 3, 2nd Ed., AISC, Chicago, IL.
Ruddy, J.L., Marlo, J.P., Ioannides, S.A. and Alfawakhiri, F. (2003), Fire Resistance of
Structural Steel Framing, Design Guide 19, AISC, Chicago, IL.

2 dari 282
Bab C Desain untuk Stabilitas

C1. PERSYARATAN STABILITAS UMUM

SNI 1729, Spesifikasi untuk bangunan gedung baja struktural mensyaratkan bahwa
perancang untuk menghitung stabilitas dari sistem struktural secara keseluruhan, dan
stabilitas elemen-elemen individu. Dengan demikian, analisis lateral yang digunakan untuk
menilai stabilitas harus mencakup pertimbangan dari efek kombinasi beban gravitasi dan
lateral, serta inelastisitas komponen struktur, keluar-dari-ketegak lurusan, keluar-dari-
kelurusan dan efek orde kedua yang dihasilkan P dan P . Efek dari "kolom yang
tidak menjamin stabilitas struktur" juga harus diperhatikan, seperti digambarkan dalam
contoh dalam bab ini.

Efek P dan P dijelaskan dalam penjelasan SNI 1729, Spesifikasi untuk bangunan
gedung baja struktural Gambar C-C2.1. Metode untuk menangani stabilitas, mencakup efek
P dan P , tersedia dalam SNI 1729, Spesifikasi untuk bangunan gedung baja
struktural Pasal C2 dan Lampiran 7.

C2. PERHITUNGAN KEKUATAN PERLU

Perhitungan kekuatan perlu diilustrasikan pada contoh dalam bab ini.

3 dari 282
CONTOH C.1A DESAIN RANGKA PENAHAN MOMEN DENGAN METODE ANALISIS
LANGSUNG

Tentukan kekuatan perlu dan faktor panjang efektif kolom-kolom pada Rangka kaku seperti
gambar di bawah ini untuk kombinasi pembebanan gravitasi maksimum, menggunakan
DFBK. Gunakan metode analisis langsung. Seluruh komponen struktur terbuat dari material
baja Fy = 250 MPa.

Kolom-kolom tidak terbreis antara tumpuan dan atap pada sumbu x dan y serta diasumsikan
memiliki tumpuan sendi.

Solusi:

wD = 4 kN/m wL = 12 kN/m

Lspan = 8 m

Fy = 250 MPa

WF 300x300x10x15 memiliki Ag = 119,8 cm2

Balok-balok pada bentang A-B, C-D, dan D-E memiliki ujung sendi dan tidak berkontribusi
terhadap stabilitas lateral portal. Pengaruh P pada balok-balok tersebut tidak
diperhitungkan dan direncanakan memiliki K = 1,0.

Rangka penahan momen antara grid B dan C adalah komponen pendukung stabilitas lateral
sehingga harus direncanakan berdasarkan Pasal C SNI 1729, Spesifikasi untuk bangunan
gedung baja struktural. Walaupun kolom-kolom pada grid A, D, dan E tidak berkontribusi
terhadap stabilitas lateral, gaya-gaya stabilitas kolom-kolom tersebut harus diperhitungkan
dalam analisis. Untuk analisis, seluruh Rangka dapat dimodelkan seperti gambar di bawah
ini. Beban-beban stabilitas kolom yang tidak menjamin stabilitas konstruksi (leaning
columns) digabung pada satu kolom.

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kombinasi pembebanan gravitasi maksimum:

kN
Metode DFBK: wu = 1,2wD + 1,6wL = 24
m
kN
Metode DKI: wa = wD + wL = 16
m

4 dari 282
Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal C2.1,
untuk DFBK analisis orde kedua dan pemeriksaan kekuatan dilakukan dengan kombinasi
pembebanan DFBK.

Pembebanan Gravitasi untuk Analisis Struktur Rangka

Beban gravitasi seragam untuk analisis orde kedua pada balok B-C adalah:

kN
Metode DFBK: wu = 24
m

kN
Metode DKI: wa = 1,6wa = 25,6
m

Beban-beban gravitasi terpusat untuk analisis orde kedua kolom di grid B dan C yang
diperoleh dari balok-balok di sebelahnya adalah:

Lspan
Metode DFBK: Pu = wu = 96 kN
2

Lspan
Metode DKI: Pa = wa = 102,4 kN
2

Beban-beban gravitasi terpusat pada kolom yang tidak menjamin stabilitas konstruksi palsu

Pembebanan pada kolom tersebut memperhitungkan seluruh beban gravitasi yang juga
ditahan oleh Rangka penahan momen namun secara tidak langsung pada rangka adalah:

Metode DFBK: PuL = 2 Lspan wu = 384 kN

Metode DKI: PaL = 2 Lspan wa = 409,6 kN

Pembebanan Notional untuk Analisis Struktur Portal

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal C2.2,
ketidakvertikalan kolom harus diperhitungkan secara eksplisit pada pemodelan atau dengan
mengaplikasikan beban notional. Pada contoh ini dipergunakan beban notional.

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Persamaan
C2.1, besar beban notional tersebut adalah:

Ni = 0,002 Yi
dengan

= 1,0 (DFBK); = 1,6 (DKI)


Ni = beban notional yang digunakan pada level i, kN

Yi = beban gravitasi yang digunakan pada level i dari kombinasi beban DFBK atau
kombinasi beban DKI, yang sesuai kN

5 dari 282
Metode DFBK: LRFD 1,0
Yi.LRFD = 4Lspan wu = 768 kN

Ni.LRFD = 0,002 LRFD Yi.LRFD = 1,536 kN

Ringkasan beban-beban untuk analisis portal

Metode DKI: ASD 1,6

Yi.ASD = 4Lspan wa = 512 kN

Ni.ASD = 0,002 ASD Yi.ASD = 1,638 kN

Ringkasan beban-beban untuk analisis portal

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal C2.3,
analisis dilakukan dengan mereduksi kekakuan nominal menjadi sebesar 80% untuk

6 dari 282
memperhitungkan pengaruh inelastisitas. Asumsikan (dengan verifikasi) Pr/Py tidak lebih
dari pada 0,5, sehingga kekakuan tidak perlu direduksi lebih besar.

50% beban gravitasi dipikul oleh kolom-kolom pada rangka penahan momen. Karena beban
gravitasi yang ditahan oleh Rangka penahan momen melebihi sepertiga beban gravitasi total
yang ditahan struktur, berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja
struktural Pasal C2.1, pengaruh P pada P harus diperhitungkan dalam analisis
struktur. Jika program yang digunakan tidak menghitung pengaruh P , perlu dilakukan
penambahan titik pada kolom di antara tumpuan dan balok.

Menggunakan program analisis struktur yang memperhitungkan P dan P , diperoleh


hasil sebagai berikut:

Metode DFBK:

Hasil analisis orde pertama:

1st = 2,79 mm

Hasil analisis orde kedua:

2nd = 3,62 mm

2nd
= 1,297
1st

Periksa apakah asumsi Pr/Py 0,5 terpenuhi, b = 1,0

7 dari 282
dengan

Pr = kekuatan tekan aksial perlu menggunakan kombinasi beban DFBK atau DKI, kN

Py = kekuatan leleh aksial (= Fy Ag), kN

Py = Fy Ag = 2,995 x 103 kN

Pr = 72,6 kN

LRFD Pr
= 0,024 < 0,5
Py

Asumsi terpenuhi, sehingga b = 1,0 dapat digunakan

Metode DKI:

Hasil analisis orde pertama:

1st 2,975 mm

Hasil analisis orde kedua:

2nd 3,943 mm

2nd
1,325
1st

8 dari 282
Periksa apakah asumsi Pr/Py 0,5 terpenuhi, b = 1,0

Py = Fy Ag = 2,995 103 kN

Pr = 72,6 kN

ASDPr
0,039 < 0,5
Py

Asumsi terpenuhi, sehingga b = 1,0 dapat digunakan

Walaupun faktor perbesaran goyangan orde kedua sekitar 1.3, perubahan momen lentur
relatif kecil karena momen bergoyang hanya diakibatkan oleh beban notional yang bernilai
kecil. Untuk kombinasi-kombinasi beban dengan pembebanan gravitasi dan lateral yang
signifikan, peningkatan momen lentur akan lebih besar.

Verifikasi kekuatan kolom menggunakan gaya-gaya dalam orde kedua, dengan panjang
efektif sebagai berikut (perhitungan tidak ditampilkan)

Kolom:

Gunakan KLx = 6 m KLy = 6 m

9 dari 282
CONTOH C.1B DESAIN RANGKA PENAHAN MOMEN DENGAN METODE PANJANG
EFEKTIF

Ulangi Contoh C.1A dengan metode panjang efektif.

Tentukan kekuatan perlu dan faktor panjang efektif kolom-kolom pada Rangka kaku seperti
gambar di bawah ini untuk kombinasi pembebanan gravitasi maksimum, menggunakan
DFBK. Gunakan metode panjang efektif. Seluruh komponen struktur terbuat dari baja Fy =
250 MPa .
Kolom-kolom tidak terbreis antara tumpuan dan atap pada sumbu x dan y serta diasumsikan
memiliki tumpuan sendi.

Solusi:

kN kN
wD = 4 wL = 12
m m

Lspan = 8 m Lcol = 6 m

Fy = 250 MPa E = 200 000 MPa

WF 300x300x10x15 memiliki Ag = 119,8 cm2 Ix = 20 400 cm4

Balok-balok pada bentang A-B, C-D, dan D-E memiliki ujung sendi dan tidak berkontribusi
terhadap stabilitas lateral portal. Pengaruh P pada balok-balok tersebut tidak
diperhitungkan dan direncanakan memiliki K = 1,0.

Rangka penahan momen antara grid B dan C adalah komponen pendukung stabilitas lateral
sehingga harus direncanakan berdasarkan Pasal C SNI 1729, Spesifikasi untuk bangunan
gedung baja struktural. Walaupun kolom-kolom pada grid A, D, dan E tidak berkontribusi
terhadap stabilitas lateral, gaya-gaya stabilitas kolom-kolom tersebut harus diperhitungkan
dalam analisis. Untuk analisis, seluruh rangka dapat dimodelkan seperti gambar di bawah
ini. beban-beban stabilitas kolom yang tidak menjamin stabilitas konstruksi (leaning column)
digabung pada satu kolom.

10 dari 282
Periksa batasan-batasan penggunaan metode panjang efektif berdasarkan Lampiran 7,
Pasal 7.2.1:

(1) Struktur menahan beban-beban gravitasi melalui kolom-kolom vertikal.

(2) Rasio simpangan maksimum orde kedua terhadap simpangan maksimum orde pertama
diasumsikan tidak lebih dari pada 1,5, dan perlu dilakukan verifikasi.

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kombinasi pembebanan gravitasi maksimum:

kN
Metode DFBK: wu = 1,2 wD + 1,6 wL = 24
m

kN
Metode DKI: wa = wD + wL = 16
m

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Lampiran 7,
Pasal 7.2.1, analisis sesuai dengan SNI 1729 Pasal C2.1, dengan pengecualian faktor
reduksi kekuatan yang disyaratkan pada Pasal C2.3.

Pembebanan Gravitasi untuk Analisis Struktur Portal.

Beban gravitasi seragam untuk analisis orde kedua pada balok B-C adalah:

kN
Metode DFBK: wu = 24
m

kN
Metode DKI: wa' =1,6 wa = 25,6
m

Beban-beban gravitasi terpusat untuk analisis orde kedua kolom di grid B dan C yang
diperoleh dari balok-balok di sebelahnya adalah:

Lspan
Metode DFBK: Pu = wu = 96 kN
2

Lspan
Metode DKI: Pa = wa' = 102,4 kN
2

Beban-beban gravitasi terpusat pada kolom yang tidak menjamin stabilitas konstruksi palsu.

Pembebanan pada kolom tersebut memperhitungkan seluruh beban gravitasi yang juga
ditahan oleh rangka penahan momen namun secara tidak langsung pada rangka adalah:

Metode DFBK: PuL = 2 Lspan wu = 384 kN

Metode DKI: PaL = 2 Lspan wa' = 409,6 kN

11 dari 282
Pembebanan Notional untuk Analisis Struktur Rangka

Berdasarkan SNI 1729, Spesifikasi untuk gedung baja struktural Lampiran 7 Pasal 7.2.2,
ketidakvertikalan kolom harus diperhitungkan secara eksplisit pada pemodelan atau dengan
mengaplikasikan beban notional sesuai Pasal C2.2b.

Berdasarkan SNI 1729 Persamaan C2.1, beban notional tersebut adalah:

Metode DFBK:

LRFD = 1,0

Yi.LRFD = 4Lspan wu = 768 kN

Ni.LRFD = 0,002 LRFD Yi.LRFD = 1,536 kN

Ringkasan beban-beban untuk analisis rangka

Metode DKI:

ASD = 1,6

Yi.ASD = 4Lspan wa = 512 kN

Ni.ASD = 0,002 ASD Yi.ASD = 1,638 kN

12 dari 282
Ringkasan beban-beban untuk analisis rangka

Berdasarkan SNI 1729, Spesifikasi untuk gedung baja struktural Lampiran 7 Pasal 7.2.2,
analisis dilakukan dengan kekakuan nominal penuh.

50% beban gravitasi dipikul oleh kolom-kolom pada rangka penahan momen. Karena beban
gravitasi yang ditahan oleh rangka penahan momen melebihi sepertiga beban gravitasi total
yang ditahan struktur, berdasarkan SNI 1729 Pasal C2.1, pengaruh P pada P
harus diperhitungkan dalam analisis struktur. Jika program yang digunakan tidak
menghitung pengaruh P , perlu dilakukan penambahan titik pada kolom di antara
tumpuan dan balok.

Menggunakan program analisis struktur yang memperhitungkan P dan P , diperoleh


hasil sebagai berikut:

Metode DFBK:

Hasil analisis orde pertama:

1st.LRFD = 2,24 mm

13 dari 282
Hasil analisis orde kedua:

2nd.LRFD = 2,76 mm

2nd.LRFD
=1,232
1st.LRFD

Untuk rangka penahan momen: Pr1.LRFD = 190,8 kN Pr2.LRFD = 193,2 kN

Metode DKI:

Hasil analisis orde pertama:

1st.ASD = 2,39 mm

Hasil analisis orde kedua: (sebelum dibagi 1,6)

2nd.ASD = 2,99 mm

2nd.ASD
=1,251
1st.ASD

14 dari 282
203,6 kN
Untuk rangka penahan momen: Pr1.ASD = =127,25 = 127,25 kN
1,6

206,0 kN
Pr2.ASD = =128,75 = 128.75 kN
1,6
Rasio simpangan maksimum orde kedua terhadap simpangan maksimum orde pertama
tidak lebih dari pada 1,5; sehingga metode panjang efektif dapat diterapkan.

Walaupun faktor perbesaran goyangan orde kedua sekitar 1,25, perubahan momen lentur
relatif kecil karena momen bergoyang hanya diakibatkan oleh beban notional yang bernilai
kecil. Untuk kombinasi-kombinasi beban dengan pembebanan gravitasi dan lateral yang
signifikan, peningkatan momen lentur akan lebih besar.

Hitunglah faktor panjang efektif pada bidang, Kx, menggunakan story stiffness method dan
Persamaan C-A-7-5 yang terdapat pada Penjelasan Lampiran 7, Pasal 7.2.

Gunakan Kx = K2

P r 2 E I H

2 E I H
0,85 + 0,15RL Pr L2 H L
K x = K2 =
L2 1,7 H L

Hitunglah beban total yang dipikul seluruh kolom, P r

Metode DFBK: P r.LRFD wu 4Lspan 768 kN

Metode DKI: P r.ASD wa 4Lspan 512 kN

Hitunglah rasio beban pada kolom yang tidak menjamin stabilitas konstruksi terhadap beban
total, RL

Metode DFBK: P r.moment_frame.LRFD Pr 1.LRFD + Pr 2.LRFD 384 kN

15 dari 282
RL.LRFD
P r.LRFD Pr.moment_frame.LRFD
= 0,5
P r.LRFD

Metode DKI: P r.moment_frame.ASD Pr 1.ASD + Pr 2.ASD 256 kN

RL.ASD
P r.ASD Pr.moment_frame.ASD
= 0,5
P r.ASD

Hitunglah beban tekuk Euler satu kolom:

2EI x
11185,552 kN
L2col

Hitunglah rasio simpangan menggunakan hasil analisis orde pertama dengan beban
notional.

1st.LRFD mm
Metode DFBK: 0,000373
Lcol mm

1st.ASD mm
Metode DKI: 0,000398
Lcol mm

Untuk kolom pada grid C:

Metode DFBK:

PrC.LRFD = 193,2 kN HC.LRFD = 14.2 kN

K x.LRFD =
P r.LRFD 2 E I x 1st.LRFD
2 3,418
0,85 + 0,15RL.LRFD PrC.LRFD Lcol Ni.LRFDLcol
2 E Ix 1st.LRFD
> 2 0,416
Lcol 1,7HC.LRFDLcol

Metode DKI:

PrC.ASD = 206,0 kN HC.ASD = 15,2 kN

1,6 Pr.ASD 2 E I x 1st.ASD


K x.ASD = 2 3,419
0,85 + 0,15RL.ASD PrC.ASD Lcol Ni.ASDLcol
2 E Ix 1st.ASD
> 0,415
L2col 1,7HC.ASDLcol

16 dari 282
Verifikasi kekuatan kolom menggunakan gaya-gaya dalam orde kedua, dengan panjang
efektif sebagai berikut (perhitungan tidak ditampilkan).

Kolom-kolom:

Metode DFBK: Kx.LRFD = 3,418 Lx = Lcol Kx.LRFD Lx = 20,509 m

Ky.LRFD = 1,0 Ly = Lcol Ky.LRFD Ly = 6 m

Metode DKI: Kx.ASD = 3,419 Lx = Lcol Kx.ASD Lx = 20,516 m

Ky.ASD = 1,0 Ly = Lcol Ky.ASD Ly = 6 m

17 dari 282
CONTOH C.1C DESAIN RANGKA PENAHAN MOMEN DENGAN METODE ORDE
PERTAMA

Ulangi Contoh C.1A menggunakan metode analisis orde pertama.

Tentukan kuat perlu dan faktor panjang efektif kolom-kolom pada rangka kaku seperti
gambar di bawah ini untuk kombinasi pembebanan gravitasi maksimum, menggunakan
DFBK. Gunakan metode analisis orde pertama. Seluruh komponen struktur terbuat dari baja
dengan Fy = 250 MPa.

Kolom-kolom tidak terbreis antara tumpuan dan atap pada sumbu x dan y serta diasumsikan
memiliki tumpuan sendi.

Solusi:

kN kN
wD = 4 wL = 12
m m

Lspan = 8 m Lcol = 6 m

Fy = 250 MPa E = 200 000 MPa

WF300x300x10x15 memiliki Ag = 119,8 cm2 Ix = 20 400 cm4

Balok-balok pada bentang A-B, C-D, dan D-E memiliki ujung sendi dan tidak berkontribusi
terhadap stabilitas lateral portal. Pengaruh P pada balok-balok tersebut tidak
diperhitungkan dan direncanakan memiliki K = 1,0.
Rangka penahan momen antara grid B dan C adalah komponen pendukung stabilitas lateral
sehingga harus direncanakan berdasarkan Lampiran 7 SNI 1729, Spesifikasi untuk
bangunan gedung baja struktural. Walaupun kolom-kolom pada grid A, D, dan E tidak
berkontribusi terhadap stabilitas lateral, gaya-gaya stabilitas kolom-kolom tersebut harus
diperhitungkan dalam analisis. Untuk analisis, seluruh rangka dapat dimodelkan seperti
gambar di bawah ini. Beban-beban stabilitas 'leaning column' digabung pada satu kolom.

Periksa batasan-batasan penggunaan metode panjang efektif berdasarkan Lampiran 7,


Pasal 7.3.1 SNI 1729, Spesifikasi untuk bangunan gedung baja struktural:

(1) Struktur menahan beban-beban gravitasi melalui kolom-kolom vertikal.

(2) Rasio simpangan maksimum orde kedua terhadap simpangan maksimum orde pertama
diasumsikan tidak lebih dari pada 1,5, dan perlu dilakukan verifikasi.

18 dari 282
(3) Kekuatan aksial perlu komponen-komponen rangka penahan momen diasumsikan tidak
melebihi 50% kekuatan leleh aksial, dan perlu dilakukan verifikasi.

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kombinasi pembebanan gravitasi maksimum:
kN
Metode DFBK: wu = 1,2wD + 1,6wL = 24
m

kN
Metode DKI: wa = wD + wL = 16
m

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Lampiran 7,
Pasal 7.3.2, kekuatan perlu ditentukan dari analisis struktur orde pertama dengan beban-
beban notional serta memperhitungkan faktor perbesaran B1 sebagaimana dijelaskan dalam
Lampiran 8.

Pembebanan Gravitasi untuk Analisis Struktur Rangka Penahan Momen.

Beban gravitasi seragam untuk analisis orde pertama pada balok B-C adalah:

kN
Metode DFBK: wu = 24
m

kN
Metode DKI: wa = 16
m

Beban-beban gravitasi terpusat untuk analisis orde kedua kolom di grid B dan C yang
diperoleh dari balok-balok di sebelahnya adalah:

Lspan
Metode DFBK: Pu = wu = 96 kN
2

Lspan
Metode DKI: Pa = wa = 64 kN
2

Pembebanan Notional untuk Analisis Struktur Rangka Penahan Momen.

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Lampiran 7
Pasal 7.3.2, ketidakvertikalan kolom harus diperhitungkan secara eksplisit pada pemodelan
atau dengan mengaplikasikan beban notional sesuai Pasal C2.2b.

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Persamaan A-7-
2, beban notional tersebut adalah:

Metode DFBK:

LRFD = 1,0
Pembebanan Notional untuk Analisis Struktur Rangka Penahan Momen
Yi.LRFD = 4Lspan wu = 768 kN

19 dari 282
= 0,0 mm (tidak ada simpangan akibat kombinasi beban gravitasi)

Lcol = 6 m

N i.LRFD = 0,021 LRFD Yi.LRFD = 0 kN > 0,0042Yi.LRFD = 3,226 kN
L
col

gunakan Ni.LRFD = 0,0042 Yi.LRFD = 3,226 kN

Ringkasan beban-beban untuk analisis Rangka Penahan Momen

Metode DKI:

ASD = 1,6
Yi.ASD = 4Lspan wa = 512 kN

= 0,0 mm (tidak ada simpangan akibat kombinasi beban gravitasi)

Lcol = 6 m


N i.ASD = 0,021 ASD Yi.ASD = 0 > 0,042Yi.ASD = 2,15 kN
Lcol

gunakan Ni.ASD = 0,0042 Yi.ASD = 2,15 kN

Ringkasan beban-beban untuk analisis Rangka Penahan Momen

Berdasarkan SNI 1729 Lampiran 7, Pasal 7.2.2, analisis dilakukan dengan kekakuan
nominal penuh (tidak direduksi).

Menggunakan program analisis struktur orde pertama, diperoleh hasil sebagai berikut:

Metode DFBK:

1st.LRFD = 4,71 mm
Metode DKI:

1st.ASD = 3,14 mm

Periksa asumsi rasio simpangan orde kedua terhadap simpangan orde pertama tidak
melebihi 1,5. Faktor B2 dapat digunakan sebagai kondisi batas. Hitung faktor B2 sesuai
Pasal 8.2.2 Lampiran 8 menggunakan hasil analisis orde pertama.

Metode DFBK:

Pmf.LRFD = Pleft.LRFD + Pright.LRFD = 384 kN

Pstory.LRFD = wu (4 Lspan) = 768 kN

20 dari 282
Pmf.LRFD
RM.LRFD =1- 0,15 = 0,925 (SNI 1729 Persamaan A-8-8)
P
story.LRFD

H.LRFD = 1st.LRFD = 4,71 mm

HLRFD = Ni.LRFD = 3,226 kN

L = Lcol = 6 m

H LRFD L
Pe.story.LRFD = RM.LRFD = 3800,866 kN (SNI 1729 Persamaan A-8-7)
H.LRFD
LRFD = 1

1
B 2.LRFD = =1,253 (SNI 1729 Persamaan A-8-6)
P
1- LRFD story.LRFD
Pe.story.LRFD

21 dari 282
Bab D Desain dari Komponen Struktur untuk Tarik

D1. PEMBATASAN KELANGSINGAN

Pasal D1 tidak menetapkan batas kelangsingan untuk komponen struktur tarik, tetapi
menyarankan pembatasan L/r untuk maksimum dari 300. Ini bukan suatu persyaratan
mutlak. Batang dan gantungan secara khusus dikecualikan dari rekomendasi ini.

D2. KEKUATAN TARIK

Kekuatan leleh tarik dan kekuatan runtuh tarik harus dipertimbangkan untuk desain dari
komponen struktur tarik. Hal ini tidak biasa untuk kekuatan runtuh tarik untuk menentukan
desain dari suatu komponen struktur tarik, terutama untuk komponen struktur kecil dengan
lubang-lubang atau profil berat dengan beberapa baris dari lubang.

D3. LUAS NETO EFEKTIF

Luas bruto, Ag, adalah luas penampang melintang komponen struktur.

Pada perhitungan luas neto, An, SNI 1729, Spesifikasi untuk bangunan gedung baja
struktural Pasal B4.3 mensyaratkan bahwa tambahan 1/16 in. akan ditambahkan pada
diameter lubang baut.

Perhitungan luas efektif untuk deretan lubang-lubang disajikan dalam Contoh D.9.

Kecuali semua elemen-elemen penampang melintang disambungkan, Ae = AnU, di mana U


adalah suatu faktor reduksi untuk menghitung shear lag.

Nilai-nilai yang sesuai U dapat diperoleh dari Tabel D3.1 SNI 1729 Spesifikasi untuk
bangunan gedung baja struktural.

D4. KOMPONEN STRUKTUR TERSUSUN

Pembatasan untuk sambungan-sambungan komponen struktur tersusun dibahas dalam


Pasal D4 SNI 1729 Spesifikasi untuk bangunan gedung baja struktural.

D5. KOMPONEN STRUKTUR TERSAMBUNG-SENDI

Contoh komponen struktur tersambung-sendi diberikan dalam Contoh D.7.

D6. EYEBAR

Contoh eyebar diberikan dalam Contoh D.8. Kekuatan eyebar memenuhi persyaratan
dimensional SNI 1729 Spesifikasi untuk bangunan gedung baja struktural Pasal D6 diatur
oleh leleh tarik dari body.

22 dari 282
CONTOH D.1 BATANG TARIK DENGAN PROFIL WF

Profil WF 200x100x5,5x8 digunakan untuk menahan gaya tarik sebesar 135 kN akibat
beban mati dan 400 kN akibat beban hidup. Panjang batang tarik 6,5 m. Periksa kekuatan
batang tarik tersebut berdasarkan DFBK, jika pada ujung batang terdapat sambungan baut
seperti tergambar.

Periksa apakah profil tersebut memenuhi persyaratan kelangsingan batang tarik. Kekuatan
sambungan dianggap tidak menentukan.

Solusi:

PD = 90 kN PL = 270 kN L = 6,5 m

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, gaya tarik desain minimum:

Metode DFBK: Pu = 1,2 PD + 1,6 PL = 540 kN

Metode DKI: Pu = PD + PL = 360 kN

Properti material baja:

Fy = 250 MPa Fu = 410 MPa

Besaran-besaran penampang WF 200x100x5,5x8:

Ag = 2716 mm2

bf = 100 mm

tf = 8 mm

d = 200 mm

ry = 22,2 mm

T 100x100x5,5x8 ybar = 28,3 mm

23 dari 282
Leleh Tarik

Pn.y = Ag Fy = 679 kN

Metode DFBK:

ty = 0,9 ty Pn.y = 611,1 kN > Pu = 540 kN

Pu
= 0,884
ty Pn.y

Metode DKI:

Pn.y
ty = 1,67 = 406,587 kN . > . Pa = 360 kN
ty

ty Pa
= 0,885
Pn.y

Putus Tarik

Hitung faktor shear lag, U, sebagai nilai terbesar berdasarkan SNI 1729, Spesifikasi untuk
bangunan gedung baja struktural Pasal D3, Tabel D3.1 kasus 2 dan kasus 7.

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D3, untuk
penampang terbuka, U tidak perlu lebih kecil daripada rasio luas utuh elemen-elemen
tersambung dengan luas utuh seluruh penampang.

2 bf tf
U1 = = 0,589
Ag

Kasus 2: Periksa sebagai sepasang profil T dengan:

xbar = ybar = 240 mm

xbar
U2 = 1 - = 0,882

Kasus 7:

2
bf = 100 mm < d = 133,333 mm
3
U3 = 0,85

Gunakan U = max(U1 , U2 , U3) = 0,882

Hitung An menggunakan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal
B4.3.

dh = 16 mm + 1,6 mm = 17,6 mm

24 dari 282
An = Ag 4 (dh + 1,6 mm) tf = 2101,6 mm2

Hitung Ae menggunakan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal
D3.

Ae = An U = 1853,786 mm2

Ae
= 0,683
Ag

Kekuatan putus tarik,

Pn.r = Fu Ae = 760,052 kN

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D2,
kekuatan putus tarik desain:

Metode DFBK:

tr = 0,75 tr Pn.r = 570,039 kN > Pu = 540 kN

Pu
= 0,947
tr Pn.r

Metode DKI:

Pn.r
tr = 2 = 380,026 kN > Pa = 360 kN
tr

tr Pa
= 0,947
Pn.r

Periksa syarat kelangsingan batang tarik

L
= 292,793 < 300 berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung
ry
baja struktural Pasal D1 (o.k.)

Kekuatan tarik profil tersebut ditentukan oleh kekuatan putus tarik di bagian sambungan.

Lihat BAB J untuk pemeriksaan kekuatan sambungan.

25 dari 282
CONTOH D.2 BATANG TARIK PROFIL SIKU

Profil siku 100x100x13 dengan material baja Fy = 250 MPa digunakan untuk menahan gaya
tarik sebesar 90 kN akibat beban mati dan 270 kN akibat beban hidup. Periksa kekuatan
batang tarik tersebut berdasarkan DFBK, jika pada ujung batang terdapat sambungan baut
berdiameter 20 mm seperti tergambar.

Hitung juga panjang profil maksimum agar memenuhi persyaratan kelangsingan batang
tarik. kekuatan sambungan dianggap tidak menentukan.

Solusi:

PD = 90 kN PL = 270 kN

Properti material baja:

Fy = 250 MPa Fu = 410 MPa

Properti penampang L100x100x13:

Ag = 2431 mm2 t = 13 mm

rz = 19,4 mm

ybar = 29,4 mm xbar = 29,4 mm

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan tarik perlu:

Metode DFBK: Pu = 1,2 PD + 1,6 PL = 540 kN

Metode DKI: Pa = PD + PL = 360 kN

Leleh Tarik

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D2,
kekuatan tarik leleh:

Pn.y = Ag Fy = 607,75 kN

Metode DFBK:

ty = 0,9 ty Pn.y = 546,975 kN > Pu = 540 kN

26 dari 282
Pu
= 0,987
ty Pn.y

Metode DKI:

Pn.y
ty = 1,67 = 363,922 kN > Pa = 360 kN
ty

ty Pa
= 0,989
Pn.y

Putus Tarik

Hitung U sebagai nilai terbesar berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural Pasal D3, Tabel D3.1 kasus 2 dan kasus 8.

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D3, untuk
penampang terbuka, U tidak perlu lebih kecil daripada rasio luas utuh elemen-elemen
tersambung dengan luas utuh seluruh penampang.

U1 = 0,500

Kasus 2:

xbar = 29,4 mm = 240 mm


xbar
U2 = 1 - = 0,877

Kasus 8, dengan 4 atau lebih alat penyambung per garis dalam arah pembebanan:

U3 = 0,800

Gunakan U = max(U1 , U2 , U3) = 0,877

Hitung An menggunakan SNI 1729, Spesifikasi untuk gedung baja struktural Pasal B4.3.

13
dh = mm
16

An = Ag (dh + 1,6 mm) t = 2399,638 mm2

Hitung Ae menggunakan SNI 1729, Spesifikasi untuk gedung baja struktural Pasal D3.

Ae = An U = 2105,682 mm2

Kekuatan putus tarik:

Pn.r = Fu Ae = 863,33 kN

27 dari 282
Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D2,
kekuatan putus tarik desain:

Metode DFBK:

tr = 0,75 tr Pn.r = 647,497 kN > Pu = 540 kN

Pu
= 0,834
tr Pn.r

Metode DKI:

Pn.r
tr = 2 = 431,665 kN > Pa = 360 kN
tr

tr Pa
= 0,834
Pn.r

Panjang batang maksimum, Lmax

Menggunakan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D1:

Lmax = 300 rz = 5820 mm

Catatan: Batas L/r merupakan rekomendasi, bukan persyaratan.

Lihat Bab J untuk pemeriksaan kekuatan sambungan.

28 dari 282
CONTOH D.3 BATANG TARIK PROFIL T

Profil T 200x100x8x12 dengan material baja Fy = 250 MPa digunakan untuk menahan gaya
tarik sebesar 180 kN akibat beban mati dan 540 kN akibat beban hidup. Panjang batang
tarik 9 m. Periksa kekuatan batang tarik tersebut berdasarkan DFBK, jika pada ujung batang
terdapat sambungan las sepanjang 300 mm seperti tergambar.

Periksa apakah profil tersebut memenuhi persyaratan kelangsingan batang tarik. Kekuatan
sambungan dianggap tidak menentukan.

Solusi:

PD = 110 kN PL = 330 kN L=6m

Properti material baja:

Fy = 250 MPa Fu = 410 MPa

Properti penampang T 200x100x8x12:

Ag = 3177 mm2

bf = 200 mm

tf = 12 mm

rx = 24,1 mm

ybar = 17,3 mm

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan tarik perlu:

Metode DFBK: Pu = 1,2 PD + 1,6 PL = 660 kN

Metode DKI: Pa = PD + PL = 440 kN

Leleh Tarik

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D2,
kekuatan leleh tarik:

Pn.y = Ag Fy = 794,25 kN

29 dari 282
Metode DFBK:

ty = 0,9 ty Pn.y = 714,825 kN > Pu = 660 kN

Pu
= 0,923
ty Pn.y

Metode DKI:

Pn.y
ty = 1,67 = 475,599 kN > Pa = 440 kN
ty

ty Pa
= 0,925
Pn.y

Putus Tarik

Hitung U sebagai nilai terbesar berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural Pasal D3, Tabel D3.1 kasus 2.

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D3, untuk
penampang terbuka, U tidak perlu lebih kecil daripada rasio luas utuh elemen-elemen
tersambung dengan luas utuh seluruh penampang.

bf tf
U1 = = 0,755
Ag

Kasus 2:

xbar = ybar = 300 mm

xbar
U2 = 1 - = 0,942

Gunakan U = max(U1 , U2) = 0,942

Hitung An menggunakan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal
B4.3.

An = Ag = 3177 mm2

Hitung Ae menggunakan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal
D3.

Ae = An U = 2993,793 mm2

Kekuatan putus tarik:

Pn.r = Fu Ae = 1227,455 kN

30 dari 282
Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D2,
kekuatan putus tarik desain:

Metode DFBK:

tr = 0,75 tr Pn.r = 920,591 kN > Pu = 660 kN

Pu
= 0,717
tr Pn.r

Metode DKI:

Pn.r
tr = 2 613,728 kN > Pa = 440 kN
tr

tr Pa
0,717
Pn.r

Pemeriksaan Batas Kelangsingan

L
= 248,963 < 300 berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung
rx
baja struktural Pasal D1 (o.k.)

Lihat BAB J untuk pemeriksaan kekuatan sambungan.

31 dari 282
CONTOH D.4 BATANG TARIK PROFIL TABUNG PERSEGI PANJANG

Profil tabung persegi panjang 180x100x10 dengan material baja Fy = 250 MPa digunakan
untuk menahan gaya tarik sebesar 150 kN akibat beban mati dan 450 kN akibat beban
hidup. Panjang batang tarik 7,5 m. Periksa kekuatan batang tarik tersebut berdasarkan
DFBK, jika pada ujung batang terdapat sambungan las sepanjang 300 mm pada pelat buhul
dengan tebal 10 mm.

Periksa apakah profil tersebut memenuhi persyaratan kelangsingan batang tarik. Kekuatan
sambungan dan pelat buhul dianggap tidak menentukan.

Solusi:

PD = 150 kN PL = 450 kN L = 7,5 m

Properti material baja:

Fy = 250 MPa Fu = 410 MPa

Properti penampang tabung persegi 150x100x10:

Ag = 4857mm2

B = 100 mm

H = 180 mm

t = 10 mm

rx = 38,9 mm

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan tarik perlu:

Metode DFBK: Pu = 1,2 PD + 1,6 PL = 900 kN

Metode DKI: Pa = PD + PL = 600 kN

32 dari 282
Leleh Tarik

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D2,
kekuatan leleh tarik:

Pn.y = Ag Fy = 1214,25 kN

Metode DFBK:

ty = 0,9 ty Pn.y = 1092,825 kN > Pu = 900 kN

Pu
= 0,824
ty Pn.y

Metode DKI:

Pn.y
ty = 1,67 727,096 kN > Pa = 600 kN
ty

ty Pa
0,825
Pn.y

Putus Tarik

Hitung U sebagai nilai terbesar berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural Pasal D3, Tabel D3.1 kasus 6.

B 2 + 2BH
xbar = = 41,071 mm
4 B + H

= 300 mm

xbar
U=1- = 0,863

Dengan adanya celah sebesar 1,6 mm antara profil tabung persegi dan pelat buhul:

tp = 10 mm

An = Ag 2 (tp + 1,6 mm)t = 4625 mm2

Hitung Ae menggunakan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal
D3.

Ae = An U = 3991,815 mm2

Kekuatan putus tarik:

Pn.r = Fu Ae = 1636,644 kN

33 dari 282
Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D2,
kekuatan putus tarik desain:

Metode DFBK:

tr = 0,75 tr Pn.r = 1227,483 kN > Pu = 900 kN

Pu
= 0,733
tr Pn.r

Metode DKI:

Pn.r
tr = 2 818,322 kN > Pa = 600 kN
tr
tr Pa
0,733
Pn.r

Kekuatan tarik profil tabung persegi ditentukan oleh kekuatan putus tarik.

Pemeriksaan Batas Kelangsingan

L
= 192,802 < 300 berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung
rx
baja struktural Pasal D1 (o.k.)

Lihat Bab J untuk pemeriksaan kekuatan sambungan.

34 dari 282
CONTOH D.5 BATANG TARIK PIPA

Profil pipa 150x12 dengan material baja Fy = 250 MPa digunakan untuk menahan gaya tarik
sebesar 160 kN akibat beban mati dan 480 kN akibat beban hidup. Panjang batang tarik 9
m. Periksa kekuatan batang tarik tersebut berdasarkan DFBK, jika pada ujung batang
terdapat sambungan las sepanjang 300 mm pada pelat buhul dengan tebal 12 mm.

Periksa apakah profil tersebut memenuhi persyaratan kelangsingan batang tarik. Kekuatan
sambungan dan pelat buhul dianggap tidak menentukan.

Solusi:

PD = 160 kN PL = 480 kN L=9m

Properti material baja:

Fy = 250 MPa Fu = 410 MPa

Properti penampang Pipa 150x12:

Ag = 5 202 mm2

D = 150 mm

t = 12 mm

r = 48,97 mm

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan tarik perlu:

Metode DFBK: Pu = 1,2 PD + 1,6 PL = 960 kN

Metode DKI: Pa = PD + PL = 640 kN

Leleh Tarik

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D2,
kekuatan leleh tarik:

Pn.y = Ag Fy = 1300,5 kN

35 dari 282
Metode DFBK:

ty = 0,9 ty Pn.y = 1170,45 kN > Pu = 960 kN

Pu
= 0,820
ty Pn.y

Metode DKI:

Pn.y
ty = 1,67 778,743 kN > Pa = 640 kN
ty

ty Pa
0,822
Pn.y

Putus Tarik

Periksa apakah asumsi Ae/Ag 0,75 terpenuhi.

Tentukan U berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
Tabel D3.1 Kasus 5.

D = 150 mm

= 300 mm

=2 > 1,3 oleh karena itu U = 1,00


D

Dengan adanya celah sebesar 1,6 mm antara profil pipa dan pelat buhul:

tp = 12 mm

An = Ag 2 (tp + 1,6 mm) t = 4875,6 mm2

Hitung Ae menggunakan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal
D3.

Ae = An U = 4875,6 mm2

Ae
0,937 (o.k., tetapi konservatif)
Ag

Kekuatan putus tarik adalah,

Pn.r = Fu Ae = 1998,996 kN

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D2,
kekuatan putus tarik desain:

36 dari 282
Metode DFBK:

tr = 0,75 tr Pn.r = 1499,247 kN > Pu = 960 kN

Pu
= 0,640
tr Pn.r

Metode DKI:

Pn.r
tr = 2 999,498 kN > Pa = 640 kN
tr

tr Pa
0,640
Pn.r

Kekuatan tarik profil pipa lingkaran ditentukan oleh kekuatan putus tarik.

Pemeriksaan Batas Kelangsingan

L
= 183,786 < 300 berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung
r
baja struktural Pasal D1 (o.k.)

Lihat Bab J untuk pemeriksaan kekuatan sambungan.

37 dari 282
CONTOH D.6 BATANG TARIK PROFIL SIKU GANDA

Profil siku ganda 2L100x100x13 (lebar pemisah 10 mm) dengan material baja Fy = 250 MPa
digunakan untuk menahan gaya tarik sebesar 180 kN akibat beban mati dan 540 kN akibat
beban hidup. Panjang batang tarik 7,5 m. Periksa kekuatan batang tarik tersebut
berdasarkan DFBK, jika pada ujung batang terdapat sambungan baut berdiameter 20 mm
seperti tergambar.

Hitung juga panjang profil maksimum agar memenuhi persyaratan kelangsingan batang
tarik. Kekuatan pelat buhul dan sambungan dianggap tidak menentukan.

Solusi:

PD = 180 kN PL = 540 kN L = 7,5 m

Properti material baja:

Fy = 250 MPa Fu = 410 MPa

Properti penampang L10010013:

Ag = 2 431 mm2

t = 13 mm

xbar = 29,4 mm

2L10010013 (s = 10 mm)

ry = 30,4 mm

rx = 46,2 mm

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan tarik perlu:

Metode DFBK: Pu = 1,2 PD + 1,6 PL = 1080 kN

Metode DKI: Pa = PD + PL = 720 kN

38 dari 282
Leleh Tarik

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D2,
kekuatan leleh tarik:

Pn.y = 2 Ag Fy = 1215,5 kN

Metode DFBK:

ty = 0,9 ty Pn.y = 1093,95 kN > Pu = 1080 kN

Pu
= 0,987
ty Pn.y

Metode DKI:

Pn.y
ty = 1,67 = 727,844 kN > Pa = 720 kN
ty

ty Pa
= 0,989
Pn.y

Putus Tarik

Hitung U sebagai nilai terbesar berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural Pasal D3, Tabel D3.1 kasus 2 dan kasus 8.

Berdasarkan SNI 1729, Spesifikasi untuk gedung baja struktural Pasal D3, untuk
penampang terbuka, U tidak perlu lebih kecil daripada rasio luas utuh elemen-elemen
tersambung dengan luas utuh seluruh penampang.

U1 = 0,500

Kasus 2:

xbar = 29,4 mm = 5 (70 mm) = 350 mm

xbar
U2 = 1 - = 0,916

Kasus 8, dengan 4 atau lebih alat penyambung per garis dalam arah pembebanan:

U3 = 0,800

Gunakan U = max(U1 , U2 , U3) = 0,916

Hitung An menggunakan SNI 1729, Spesifikasi untuk gedung baja struktural Pasal B4.3.

dh = 20 mm + 1,6 mm = 21,6 mm

An = 2 Ag 2 (dh + 1,6 mm) t = 4258,8 mm2

39 dari 282
Hitung Ae menggunakan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal
D3.

Ae = An U = 3 901,061 mm2

Kekuatan putus tarik adalah,

Pn.r = Fu Ae = 1599,435 kN

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D2,
kekuatan putus tarik desain:

Metode DFBK:

tr = 0,75 tr Pn.r = 1199,576 kN > Pu = 1080 kN

Pu
= 0,900
tr Pn.r

Metode DKI:

Pn.r
tr = 2 = 799,717 kN > Pa = 720 kN
tr

tr Pa
= 0,9
Pn.r

Pemeriksaan Batas Kelangsingan

L
= 162,338 < 300 berdasarkan SNI 1729, Pasal D1 (o.k.)
rx

Catatan: Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal
D4, jarak longitudinal antara alat penyambung pada batang dengan penampang tersusun
dipasang sedemikian sehingga rasio kelangsingan setiap komponen penyusunnya tidak
melebihi 300.

Lihat Bab J untuk pemeriksaan kekuatan sambungan.

40 dari 282
CONTOH D.7 BATANG TARIK TERHUBUNG-SENDI

Suatu batang tarik terhubung-sendi dengan material baja Fy = 250 MPa digunakan untuk
menahan gaya tarik sebesar 18 kN akibat beban mati dan 54 kN akibat beban hidup.
Diameter pin (sendi) 25 mm dengan diameter lubang lebih besar 1,6 mm. Asumsikan
kekuatan pin mencukupi. Periksa kekuatan tarik batang tersebut.

Solusi:

PD = 12 kN PL = 36 kN

Properti material baja:

Fy = 250 MPa Fu = 410 MPa

Dimensi-dimensi penampang:

w = 140 mm

t = 10 mm

d = 25 mm

a = 56,7 mm

c = 61,6 mm

dh = d + 1,6 mm = 26,6 mm

Periksa persyaratan dimensi berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural Pasal D5.2.

1. be = min(2 t + 16 mm, 61,6 mm) = 36 mm

2. a = 56,7 mm > 1,33 be = 47,88 mm o.k.

3. w = 140 mm > 3 be + d = 133 mm o.k.

41 dari 282
4. c = 61,6 mm > a = 56,7 mm o.k.

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan tarik perlu:

Metode DFBK: Pu = 1,2 PD + 1,6 PL = 72 kN

Metode DKI: Pa = PD + PL = 48 kN

Putus Tarik

Hitung kekuatan putus tarik pada penampang bersih efektif.

Pntr = Fu 2t be = 295,2 kN

Berdasarkan SNI 1729, Spesifikasi untuk gedung baja struktural Pasal D5.1, kekuatan putus
tarik desain:

Metode DFBK:

tr = 0,75 tr Pntr = 221,4 kN > Pu = 72 kN

Pu
= 0,325
tr Pntr

Metode DKI:

Pntr
tr = 2 = 147,6 kN > Pa = 48 kN
tr

trPa
= 0,325
Pntr

Putus Geser:

d 2
Asf = 2 t a + = 1384 mm
2

Pnsf = 0,6 Fu Asf = 340,464 kN

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D5.1,
kekuatan putus geser desain:

Metode DFBK:

sf = 0,75 sf Pnsf = 255,348 kN > Pu = 72 kN

Pu
= 0,282
sf Pnsf

42 dari 282
Metode DKI:

Pnsf
sf = 2 = 170,232 kN > Pa = 48 kN
sf

sf Pa
= 0,282
Pnsf

Kekuatan Tumpu

Apb = t d = 250 mm2

Rnpb = 1,8 Fy Apb = 112,5 kN

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal J7,
kekuatan tumpu desain:

Metode DFBK:

pb = 0,75 pb Rnpb = 84,375 kN > Pu = 72 kN

Pu
= 0,853
pb Rnpb

Metode DKI:

Rnpb
pb = 2 = 56,25 kN > Pa = 48 kN
pb

pbPa
= 0,853
Rnpb

Leleh Tarik

Ag = w t = 1,4 103 mm2

Pnty = Fy Ag = 350 kN

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D2,
kekuatan leleh tarik desain:

Metode DFBK:

t = 0,90 t Pnty = 315 kN > Pu = 72 kN

Pu
= 0,229
t Pnty

43 dari 282
Metode DKI:

Pnty
t = 1,67 = 209,581 kN > Pa = 48 kN
t

t Pa
= 0,229
Pnty

Kekuatan tarik ditentukan oleh kekuatan tumpu

Pn = min( tr Pntr , sf Pnsf , pb Rnpb , t Pnty) = 84,375 kN > Pu = 72 kN

Pu
= 0,853
Pn

Lihat Contoh J.6 untuk kekuatan pin pada pelat dengan lubang bor

44 dari 282
CONTOH D.8 BATANG TARIK EYEBAR

Sebuah eyebar dengan tebal 16 mm direncanakan menahan gaya tarik 120 kN akibat beban
mati dan 60 kN akibat beban hidup. Material eyebar adalah baja dengan Fy = 250 MPa.
Diameter pin 75 mm. Periksa kekuatan tarik batang tersebut.

b = 56 mm

dh = 75,781 mm

R = 200 mm

t = 16 mm

Solusi:

PD = 120 kN PL = 60 kN

Properti material baja:

Fy = 250 MPa Fu = 410 MPa

Besaran-besaran penampang:

w = 75 mm

b = 56 mm

t = 16 mm

dhead = 200 mm

d = 75 mm

dh = d + 0,781 mm = 75,781 mm

R = 200 mm

Periksa persyaratan dimensi berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural Pasal D6.1 and D6.2.

1. t = 16 mm > 13 mm

2. w = 75 mm < 8t = 128 mm o.k.

45 dari 282
7
3. d = 75 mm > w = 65,625 mm o.k.
8

4. dh = 75,781 mm d + 0,781 mm = 75,781 mm o.k.

5. R = 200 mm > dhead = 200 mm o.k.

2 3
6. w = 50 mm b = 56 mm w = 56,25 mm o.k
3 4
.
Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan tarik perlu:

Metode DFBK: Pu = 1,2 PD + 1,6 PL = 240 kN

Metode DKI: Pa = PD + PL = 180 kN

Leleh Tarik

Ag = w t = 1 200 mm2

Pnty = Fy Ag = 300 kN

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D2,
kekuatan leleh tarik desain:

Metode DFBK:

t = 0,90 t Pnty = 270 kN > Pu = 240 kN

Pu
0,889
ty Pnty

Metode DKI:

Pnty
ty = 1,67 = 179,641 kN < Pa = 180 kN
ty

ty Pa
1,002 (dapat dianggap sama dengan 1,0)
Pnty

Kekuatan tarik eyebar ditentukan oleh kekuatan leleh tarik.

Catatan: Persyaratan detailing eyebar perlu diperhatikan untuk menjamin kegagalan


ditentukan oleh kondisi leleh tarik. Alat penyambung pin juga perlu diperiksa terhadap
kondisi leleh geser, dan kondisi tumpu jika mutu material pin lebih rendah daripada material
eyebar.

Lihat Contoh J.6 untuk kekuatan pin pada pelat dengan lubang bor

46 dari 282
CONTOH D.9 PELAT DENGAN BAUT BERSELING

Hitunglah An dan Ae untuk pelat dengan lebar 360 mm dan tebal 12 mm yang mengalam
gaya tarik dengan lubang-lubang baut berseling di bawah ini.

Solusi:

Hitunglah diameter lubang baut berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural Pasal B4.3.

dbolt = 20 mm dh = dbolt + 1,6 mm = 21,6 mm

dnet = dh + 1,6 mm = 23,2 mm

Hitunglah lebar bersih untuk seluruh pola potongan melintang. Karena konfigurasi simetri,
beberapa pola memiliki lebar efektif yang identik dan tidak perlu dihitung.

b = 360 mm s = 65 mm g1 = 75 mm g2 = 100 mm tp = 12 mm

S2
w=b dnet + 4g berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja

struktural Pasal B4.3.

Pola A-B-E-F: w1 = b 2 dnet = 313,6 mm

S2
Pola A-B-C-D-E-F: w2 = b 4 dnet + 2 = 295,367 mm
4g1

S2
Pola A-B-C-D-G : w3 = b 3 dnet + = 304,483 mm
4 g1

S2 S2
Pola A-B-D-E-F : w4 = b 3 dnet + + = 310,519 mm
4g1 4 g1 + g 2

Sehingga, wmin = min(w1 , w2 , w3 , w4) = 295,367 mm

47 dari 282
An = wmin tp = 3544,4 mm2

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Tabel D3.1
kasus 1, karena beban tarik disalurkan pada seluruh elemen melalui baut,

U = 1,0

Ae = U An = 3544,4 mm2

48 dari 282
Bab E Desain Komponen Struktur untuk Tekan

Bab E ini meliputi desain komponen struktur tekan, yang paling umum di antaranya adalah
kolom.

profil kolom sayap lebar


PSB
siku ganda
siku tunggal

Dalam SNI 1729, Spesifikasi untuk bangunan gedung baja struktural, DKI dan DFBK akan
memberikan desain yang identik bila beban hidup adalah kira-kira tiga kali beban mati.

Desain profil tersusun dengan elemen langsing dapat menjadi tidak efisien, dianjurkan
menggunakan profil canai panas.

E1. KETENTUAN UMUM

Kekuatan tekan desain, c Pn , dan kekuatan tekan izin, Pn / c , ditentukan sebagai berikut:

Pn = kekuatan tekan nominal berdasarkan ragam tekuk yang menentukan

c = 0,90 (DFBK) c = 1,67 (DKI)

E2. PANJANG EFEKTIF

Dalam SNI 1729, Spesifikasi untuk bangunan gedung baja struktural tidak ada batasan pada
kelangsingan, KL/r. Dalam SNI 1729 direkomendasikan bahwa KL/r tidak melebihi 200,
sebagai batas praktis berdasarkan pertimbangan profesional dan ekonomis.

E3. TEKUK LENTUR KOMPONEN STRUKTUR TANPA ELEMEN PENAMPANG


LANGSING

Penampang nonlangsing, termasuk kolom profil I tersusun nonlangsing dan kolom PSB
nonlangsing, ditentukan oleh ketentuan-ketentuan ini. Kurva desain umum untuk tegangan
kritis versus KL/r ditunjukkan dalam Gambar E-1.

Tekuk
Tegangan kritis, MPa

inelastis E3-2

Tekuk elastis
E3-3

KL/r Transisi antara persamaan-persaman


(lokasi bervariasi oleh Fy)

Gambar E-1 Kurva kolom standar

49 dari 282
Notasi L yang digunakan dalam bab ini adalah panjang antara titik-titik yang terbreis
terhadap perpindahan lateral dan/atau perpindahan rotasi

E4. TEKUK TORSI DAN TEKUK TORSI LENTUR KOMPONEN STRUKTUR TANPA
ELEMEN LANGSING

Pasal ini adalah yang paling umum berlaku untuk siku ganda dan profil T, yang memiliki satu
sumbu simetri mengalami tekuk torsi dan tekuk torsi lentur.

E5. KOMPONEN STRUKTUR TEKAN SIKU TUNGGAL

Kekuatan komponen struktur tekan siku tunggal yang tersedia tidak diberikan dalam contoh
disini.

E6. KOMPONEN STRUKTUR TERSUSUN

Pasal ini menyarankan pemilihan komponen-komponen struktur tersusun tanpa elemen-


elemen langsing, sehingga membuat analisis relatif mudah.

E7. KOMPONEN STRUKTUR DENGAN ELEMEN LANGSING

Desain komponen struktur ini serupa dengan komponen-komponen struktur tanpa elemen-
elemen langsing kecuali bahwa formula dimodifikasi dengan suatu faktor reduksi untuk
elemen langsing, Q. Perhatikan kesamaan Persamaan E7-2 dengan Persamaan E3-2 SNI
1729, dan kesamaan Persamaan E7-3 Persamaan dengan Persamaan E3-3 SNI 1729.

Contoh-contoh desain telah dimasukkan dalam Bab E ini untuk komponen struktur profil I
tersusun dengan badan langsing dan sayap langsing. Contoh juga telah disertakan untuk
siku ganda, WT, dan profil PSB dengan elemen langsing.

50 dari 282
CONTOH E.1. PERHITUNGAN KUAT TEKAN PROFIL WF

Hitung kekuatan tekan yang tersedia dari suatu profil WF 350x175x7x11 dengan panjang tak
terbreis terhadap sumbu kuat 9 m dan panjang tak terbreis terhadap sumbu lemah dan
torsional sebesar 4,5 m. Fy = 250 MPa. E = 200 000 MPa. PD = 200 kN dan PL= 275 kN.

Data profil 350x175x7x11:

Ag = 6 314 mm2

rx = 147 mm

ry = 39,5 mm

E = 200 000 MPa

Fy = 250 MPa

Solusi:

Untuk kondisi pin-pin, K = 1,0 K Lx = 1,0 (9 m) = 9 m K Ly = 1,0 (4,5 m) = 4,5 m

Kontrol kelangsingan

KLx
= 61,224
rx

KLy
= 113,924 yang menentukan
ry

51 dari 282
Tegangan Kritis

Menghitung tegangan tekuk kritis elastik, Fe

2E
Fe = 2
= 152,089 MPa
KLy

ry

Menghitung tegangan tekuk lentur, Fcr

E KLy
4,71 = 133,219 karena = 113,924 < 133,219
Fy ry

Fy

maka Fcr = 0,658 0,658 Fe
Fy = 125,645 MPa

Kekuatan Tekan Nominal Pn = Fcr Ag = 793,322 kN

Dari SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal E1, Kekuatan
Tekan Yang Tersedia adalah :

DFBK

c = 0,9 c Pn = 713,99 kN Pu = 1,2 x 200 kN + 1,6 x 275 kN = 680 kN

Pu
= 0,9524
c Pn

DKI

Pn
c = 1,67 = 475,043 kN Pc = 200 kN + 275 kN = 475 kN
c

Pc
= 0,9999
Pn
c

52 dari 282
CONTOH E.2. KOLOM TERSUSUN DENGAN BADAN LANGSING

Verifikasi suatu kolom tersusun, dengan ukuran sayap PL1 25 mm x 200 mm dan ukuran
badan PL2 6 mm x 380 mm. Kontrol apakah kolom ini mampu menahan gaya tekan aksial
akibat beban mati PD = 500 kN dan akibat beban hidup PL= 600 kN.
Panjang kolom = 4,5 m dan kedua ujungnya berupa sendi terhadap kedua sumbu. Fy = 250
MPa. E = 200 000 MPa.

Solusi:

E
E = 200 000 MPa Fy = 250 MPa = 0,3 G=
2 1+

Properti geometri

Kolom tersusun:

d = 430 mm

bf = 200 mm tf = 25 mm

h = d - 2tf = 380 mm

tw = 6 mm

Properti penampang tersusun (dengan mengabaikan pengaruh las)

A = 2 bf t f h tw = 1,228 x 104 mm2

2t f bf3 h tw3 Iy
Iy = + = 3,334 x 107 mm4 ry = = 52,106 mm
12 12 A
2
1 3 1 d -t f
I x = 2 bf t f + tw h 2 bf t f
3
= 4,38 x 10 mm
8 4

12 12 2

53 dari 282
Tegangan Tekuk Lentur Elastik

Untuk kondisi pin-pin, K = 1,0 Karena panjang tak terbreis sama untuk kedua sumbu
lentur, maka sumbu y-y adalah sumbu yang
menentukan

Kontrol kelangsingan

KLy = 1,0 (4,5 m) = 4,5 m KLz = 1,0 (4,5 m) = 4,5 m

KLy
= 86,363
ry

Tegangan Kritis

Menghitung tegangan tekuk kritis elastik, Fe

2E
Fey 2
= 264,651 MPa
KLy

ry

Tegangan tekuk torsional kritis elastik

Catatan: Tekuk torsional umumnya tidak menentukan jika KLy > KLz. Meskipun demikian
disini dilakukan pengecekkan sebagai ilustrasi perhitungan.

h o = d - tf

I y h02
cw = 1,367 X 1012 mm6
4

J
b t 3

J

2 bf t f3 + h tw3
= 2,111 x 106 mm4
3 3

E C 1
Fet = w
+G J = 434,448 MPa > 264,651 MPa
K Lz I x + I y
2

Jadi yang menentukan adalah Fe = Fey

Kelangsingan

Cek kelangsingan sayap dengan menggunakan Tabel B4.1a SNI, kemudian menghitung Qs,
faktor reduksi elemen sayap tanpa pengaku dengan menggunakan Pasal E7.1 SNI 1729,
Spesifikasi untuk bangunan gedung baja struktural.

Hitung kc dengan menggunakan Tabel B4.1b catatan (a) di SNI 1729

54 dari 282
4
kc = 0,503 berada diantara 0,35 dan 0,76
h
tw

untuk sayap,

bf b
b t tf b =4
2 t

Hitung rasio kelangsingan batas untuk sayap, r , dari SNI 1729, Spesifikasi untuk
bangunan gedung baja struktural Tabel B4.1a kasus 2

kc E
r 0,64 = 12,834
Fy

r , maka sayap tidak langsing dan Qs = 1

Cek kelangsingan pada badan profil, kemudian hitung Qa, faktor reduksi elemen (badan)
yang diperkaku, menggunakan SNI 1729, Spesifikasi untuk bangunan gedung baja
struktural Pasal E7.2

h
= 63,333
tw

Hitung batas kelangsingan untuk badan sesuai SNI 1729 Tabel B4.1a kasus 5

E
r 1,49 = 42,144
Fy

Karena r , berarti bagian badan profil, langsing

Gunakan Persamaan E7-17, ambil f sebagai Fcr yang digitung berdasarkan Q = 1

Menghitung tegangan tekuk lentur, Fcr

E KLy
4,71 = 133,219 karena = 86,363 < 133,219
Fy ry

Fy

maka Fcr = 0,658 Fe F y = 168,356 MPa f = Fcr

55 dari 282

E 0,34 E
be = min h , 1,92 tw 1- = 323,589 mm
f h f
tw

A
Ae = be tw + 2 bf tf = 1,194 x 104 mm2 Qa = e = 0,972 Qs = 1
A
Q = Qs Qa = 0,972

Tegangan Tekuk Lentur

Menghitung tegangan tekuk lentur, Fcr

E KLy
4,71 = 135,094 karena = 86,363 < 133,219
Q Fy ry

Q Fy

Fcr = 0,658 Fe Fy = 170,201 MPa

Kekuatan Tekan Nominal Pn = Fcr A = 2,09 x 103 kN

Dari SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal E1, Kekuatan
Tekan Yang Tersedia adalah:

DFBK

c = 0,9 c Pn = 1,881 x 103 kN Pu = 1,2 x 500 kN + 1,6 x 600 kN = 1,56 x 103 kN

Pu
= 0,8293
c Pn

DKI

Pn
c = 1,67 = 1,252 x 103 kN Pc = 500 kN + 600 kN = 1,1 x 103 kN
c

c Pc
= 0,8789
Pn

56 dari 282
CONTOH E.3. KOLOM TERSUSUN DENGAN SAYAP LANGSING

Hitunglah suatu kolom tersusun, dengan ukuran sayap PL1 10 mm x 350 mm dan ukuran
badan PL2 6 mm x 180 mm. Kontrol apakah kolom ini mampu menahan gaya tekan aksial
akibat beban mati PD = 400 kN dan akibat beban hidup PL= 500 kN.

Panjang kolom = 4,5 m dan kedua ujungnya berupa sendi terhadap kedua sumbu. Fy = 250
MPa. E = 200 000 MPa.

Solusi:

E
E = 200 000 MPa Fy = 250 MPa = 0,3 G
2 1

Properti geometri

Kolom tersusun

d = 200 mm

bf = 350 mm tf = 10 mm

h = d - 2tf = 180 mm

tw = 6 mm

Properti Penampang tersusun (dengan mengabaikan pengaruh las)

A = 2 (bf tf ) + h tw = 8,08 x 103 mm2

2t f bf3 h tw3 Iy
Iy = + = 7,146 x 107 mm4 ry = = 94,044 mm
12 12 A
2
1 1 d -t f
I x = 2 bf t f3 + tw h 3 2 bf t f = 6,615 x 107 mm4
12 12 2

57 dari 282
Kelangsingan

Cek kelangsingan sayap dengan menggunakan Tabel B4.1a SNI 1729, kemudian hitung Qs,
faktor reduksi elemen sayap tanpa pengaku dengan menggunakan Pasal E7.1 SNI 1729,
Spesifikasi untuk bangunan gedung baja struktural.

Hitung kc dengan menggunakan Tabel B4.1b catatan (a) di SNI 1729.

4
kc = 0,73 berada diantara 0,35 dan 0,76
h
tw

untuk sayap,

bf b
b t = tf = 17,5
2 t

Hitung rasio kelangsingan batas untuk sayap, r , dari SNI 1729 Tabel B4.1a kasus 2

kc E
r 0,64 = 15,469
Fy

r , maka sayap tidak langsing dan Qs harus dihitung dan < 1,0

Hitung Qs berdasarkan SNI 1729 Pasal E7.1(b).

Tentukan persamaan yang sesuai untuk menghitung Qs, berdasarkan batas yang terdapat
dalam Persamaan E7-7 sampai E7-9

kc E
0,64 = 15,469
Fy

kc E
1,17 = 28,28
Fy

Karena 15,469 < 17,5 < 28.28, maka dipergunakan Persamaan E7-8 SNI 1729, Spesifikasi
untuk bangunan gedung baja struktural.

Fy
Qs =1,415 - 0,65 = 0,944 Persamaan E7-8
Ek c

Cek kelangsingan pada badan profil, kemudian hitung Qa, faktor reduksi elemen (badan)
yang diperkaku, menggunakan SNI 1729, Spesifikasi untuk bangunan gedung baja
struktural Pasal E7.2

h
= 30
tw

58 dari 282
Hitung batas kelangsingan untuk badan sesuai SNI 1729, Spesifikasi untuk bangunan
gedung baja struktural Tabel B4.1a kasus 5.

E
r =1,49 = 42,144
Fy

Karena r , berarti bagian badan profil, tidak langsing, Qa = 1

Q = Qs Qa = 0,944

Tegangan Tekuk Lentur Elastik

Untuk batang tekan dengan elemen penampang yang langsing, SNI 1729, Spesifikasi untuk
bangunan gedung baja struktural Pasal E7 berlaku. Kuat tekan nominal, Pn, harus dihitung
berdasarkan kondisi batas lentur, torsional dan tekuk torsional lentur. Tergantung
kelangsingan kolom, SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
Persamaan E7-2 atau E7-3 bisa digunakan. Fe digunakan di kedua persamaan dan dihitung
sebagai terkecil antara Persamaan E3-4 dan E4-4 SNI 1729, Spesifikasi untuk bangunan
gedung baja struktural.

Untuk kondisi pin-pin, K =1,0 Karena panjang tak terbreis sama untuk kedua sumbu
lentur, maka sumbu y-y adalah sumbu yang menentukan

Kontrol kelangsingan

KLy = 1,0 (4,5 m) = 4,5 m KLz = 1,0 (4,5 m) = 4,5 m

KLy
= 47,85
ry

Tegangan kritis elastik, Fey untuk tekuk lentur terhadap sumbu y

2E
Fey = 2
= 862,116 MPa Persamaan E3-4 SNI 1729, Spesifikasi untuk bangunan
KLy

ry
gedung baja struktural.

Tegangan kritis elastik, Fet, untuk Tekuk Torsional

h o = d tf

I y ho2
CW = = 6,449 x 1011 mm6
4

J =
bt 3

J=

2 bf t f3 + h tw3
= 2,463 x 105 mm4
3 3

59 dari 282
E C 1
Fet = w
+G J = 283,095 MPa Persamaan E4-4 SNI 1729, Spesifikasi
K Lz I x + I y
2

untuk bangunan gedung baja struktural.

Jadi yang menentukan adalah Fe = Fet

Tegangan Tekuk Lentur

Menghitung tegangan tekuk lentur, Fcr

E KLy
4,71 = 137,085 karena = 47,85 < 137,085
Q Fy ry

Q Fy

Fcr = 0,658 Fe Fy = 176,336 MPa

Kekuatan Tekan Nominal Pn = Fcr A = 1,425 x 103 kN

Dari SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal E1, Kekuatan
Tekan Yang Tersedia adalah:

DFBK

c = 0,9 c Pn = 1,282 x 103 kN Pu = 1,2 x 400 kN + 1,6 x 500 kN = 1,28 x 103 kN

Pu
= 0,9982
c Pn

DKI

Pn
c = 1,67 = 853,172 kN Pc = 400 kN + 500 kN = 900 kN
c

c Pc
= 1,0549
Pn

60 dari 282
CONTOH E.4. BATANG TEKAN SIKU GANDA DENGAN ELEMEN TIDAK LANGSING

Verifikasi kekuatan batang tekan dari profil tersusun siku ganda 2L100x100x10 (dengan
celah 10 mm). Kontrol apakah kolom ini mampu menahan gaya tekan aksial akibat beban
mati PD = 400 kN dan akibat beban hidup PL= 500 kN. Panjang kolom = 2,5 m dan kedua
ujungnya berupa sendi terhadap kedua sumbu lentur. Fy = 250 MPa. E = 200 000 MPa

Solusi:

E
E = 200 000 MPa = 0,3 G Fy = 250 MPa
2 1

Properti geometri

Profil tunggal

rz = 19,5 mm A1 = 1 900 000 mm2

b = 100 mm t = 10 mm Cy = 28,2 mm

Ix1 = 175000 cm4 = 1,75 x 109 mm4

Iy1 = Ix1 siku sama kaki

1 t
J = b - 2 t 3 = 6,333 x 104 mm4
3 2

Profil tersusun

celah dc = 10 mm xo = 0 mm yo = Cy 0,5 t

Ag = 2 A1 = 3,8 x 106 mm2

61 dari 282
Terhadap sumbu x

Ix
Ix = 2 Ix1 rx = = 30,349 mm KLx = 1,0 (2,5 m) = 2,5 m
Ag
KLx
= 82,375
rx

Terhadap sumbu y

Iy = 2 A1 (Cy + 0,5 dc)2 + 2 Iy1 = 7,689 x 109 mm4

Ix KLy
rx = = 44,981 mm KLy = 1,0 (2,5 m) = 2,5 m = 55,579
Ag ry

Ix + Iy
ro = x o2 + y o2 + = 59,013 mm
Ag

x o2 + y o2
H = 1- = 0,845
ro
2

Menurut Pasal E6.2 SNI 1729, Spesifikasi untuk bangunan gedung baja struktural, rasio
kelangsingan efektif dari komponen individu pembentuk penampang tersusun berdasarkan
jarak antara pelat penghubung, a, tidak boleh melampaui 3/4 kelangsingan maksimum profil
tersusun.

K Lx
max = K = 1,0
rx

3 max rz
maka a max = = 1,205 m
4 K

KLx
Jika jumlah medan yang digunakan n=3 maka a= = 0,833 m
n

Kontrol Kelangsingan

b
= = 10
t

Menghitung rasio kelangsingan batas, r , SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural Tabel B4.1a Kasus 3.

E
r = 0,45 = 12,728 karena lebih besar dari , jadi tidak ada elemen langsing untuk
Fy
batang tekan tanpa elemen langsing, SNI 1729, Spesifikasi untuk bangunan gedung baja
struktural Pasal E3 dan E4 bisa digunakan.

62 dari 282
Kekuatan tekan nominal, Pn, harus ditentukan berdasarkan kondisi batas tekuk lentur, tekuk
torsional dan tekuk torsional lentur.

Tekuk lentur terhadap sumbu x-x

2E
Fex = 2
= 290,894 MPa
KLx

rx

Menghitung tegangan tekuk lentur, Fcr

E KLx
4,71 = 133,219 karena = 82,375 < 133,219
Fy rx

Fy

Fcrx = 0,658 Fex
Fy = 174,47 MPa

Tekuk torsional dan Tekuk torsional-lentur

Untuk komponen siku ganda tidak langsing, SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural Persamaan E4-2 bisa digunakan.

Fcry diambil sebagai Fcr, untuk tekuk lentur terhadap sumbu y-y dari SNI 1729 untuk
Persamaan E3-2 dan E3-3 sesuai yang diperlukan.

Dengan menggunakan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal
E6, hitung kelangsingan modifikasi KL/ry untuk batang tersusun dengan alat penyambung
las atau baut pratarik. Anggap paling sedikit digunakan dua konektor.

a
= 42,735 > dari 40 untuk siku saling berpunggungan Ki = 0,5
rz

2
KL Ki a
2

maka m = y = 59,545 < 134


r
y rz

2 E
Fe = 2 = 556,725 MPa
m

Fy

Fcry = 0,658 Fe
Fy = 207,164 MPa

2G J
Fcrz = = 0,736 MPa angka dua karena ada dua siku
Ag ro2

63 dari 282

Fcry + Fcrz 4 Fcry Fcrz H = 0,736 MPa
Fcr = 1- 1- menentukan
2H Fcry + Fcrz
2

atau Fcr = min Fcr ,Fcrx

Kekuatan Tekan Nominal Pn = Fcr Ag = 2 796,263 kN

Dari SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal E1, Kekuatan
Tekan Yang Tersedia adalah:

DFBK

c = 0,9 c Pn = 2,517 x 103 kN Pu = 1,2 x 400 kN + 1,6 x 500 kN = 1,28 x 103 kN

Pu
= 0,5086
c Pn

DKI

Pn
c = 1,67 = 1,674 x 103 kN Pc = 400 kN + 500 kN = 900 kN
c

c Pc
= 0,5375
Pn

64 dari 282
CONTOH E.5. BATANG TEKAN SIKU GANDA DENGAN ELEMEN LANGSING

Verifikasi kekuatan batang tekan dari profil tersusun siku ganda 2L 75x100x7 (dengan celah
8 mm). Kontrol apakah kolom ini mampu menahan gaya tekan aksial akibat beban mati PD =
100 kN dan akibat beban hidup PL= 120 kN. Panjang kolom = 2,5 m dan kedua ujungnya
berupa sendi terhadap kedua sumbu lentur. Fy = 250 MPa. E = 200 000 MPa.

E
Solusi: E = 200 000 MPa = 0,3 G Fy = 250 MPa
2 1

Properti geometri

Profil tunggal

rz = 16 mm A1 = 11,9 cm2 = 1,19 x 103 mm2

b1 = 100 mm b2 = 75 mm t = 7 mm

Cy = 18,3 mm Cx = 30,6 mm

Ix1 = 118 cm4 = 1,18 x 106 mm4 Iy1 = 56,9 cm4 = 5,69 x 105 mm4

1 t t
J = b1 - + b2 - t 3 = 1,921 x 104 mm4
3 2 2

Profil tersusun

celah dc = 8 mm xo = 0 mm yo = Cx 0,5 t = 27,1 mm

Ag = 2 A1 = 2,38 x 103 mm2

65 dari 282
Terhadap sumbu x

Ix
Ix = 2 Ix1 rx = = 31,49 mm KLx = 1,0 (2,5 m) = 2,5 m
Ag

K Lx
= 79,391
rx
Terhadap sumbu y

I y = 2A1 c y +0,5d c + 2I y 1 = 2,322 x 106 mm4


2

Iy KLy
ry = = 31,232 mm KLy = 1,0 (2,5 m) = 2,5 m = 80,046
Ag ry

I +I x o2 + y o2
ro = x o + y o + x y = 51,975 mm
2 2
H =1- = 0,728
Ag ro
2

Menurut Pasal E6.2 SNI 1729, Spesifikasi untuk bangunan gedung baja struktural, rasio
kelangsingan efektif dari komponen individu pembentuk penampang tersusun berdasarkan
jarak antara pelat penghubung, a, tidak boleh melampaui 3/4 kelangsingan maksimum profil
tersusun.

KLx
max = K = 1,0
rx

3 max r z
maka a max = = 0,953 m
4 K

K Lx
Jika jumlah medan yang digunakan n=3 maka a= = 0,833 m
n

Kontrol Kelangsingan

b
b = max b1,b2 = = 14,286
t

Menghitung rasio kelangsingan batas, r , SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural Tabel B4.1a Kasus 3

E
r = 0,45 = 12,728 karena lebih kecil dari , elemen langsing
Fy

Untuk batang tekan siku ganda dengan elemen langsing, SNI 1729 Pasal E7 bisa
digunakan.

66 dari 282
Kekuatan tekan nominal, Pn, harus ditentukan berdasarkan kondisi batas tekuk lentur, tekuk
torsional dan tekuk torsional lentur. Fcr ditentukan dengan SNI 1729 Persamaan E7-2 atau
Persamaan E7-3.

Menghitung faktor reduksi kelangsingan, Qs, untuk siku individu dengan menggunakan SNI
1729, Persamaan E7-11 SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
Pasal E7.1c.

E
0,45 = 12,728
Fy

E
0,91 = 25,739
Fy

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Persamaan E7-
11:

b F
Qs =1,34 - 0,76 y
t E

Qs = 0,956 Qa = 1,0 Q = Qs Qa

SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Persamaan E7-2 dan E7-3
memerlukan perhitungan Fe, untuk komponen simetri tunggal bisa menggunakan
Persamaan E3-4 dan E4-5.

Tekuk lentur terhadap sumbu x-x

2E
Fex = 2
= 313,173 MPa
KLx

rx

Tekuk torsional dan Tekuk torsional-lentur

a
= 52,083 > dari 40 untuk siku saling berpunggungan Ki = 0,5
rz

2
KL Ki a
2

maka m = y = 84,176 < 134


r
y rz

2E
Fey = = 278,585 MPa
m2

2G J
Fez = = 459,616 MPa angka dua karena ada dua siku
Ag ro2

67 dari 282

F + Fez 4Fey Fez H = 222,114 MPa
Fe = ey 1- 1- menentukan
2H Fey + Fez
2

atau Fe = min Fe ,Fex Fe = 222,114 MPa

Gunakan batas menggunakan Fe untuk menentukan pemakaian Persamaan E7-2 atau E7-3

Q Fy
= 1,076 < 2,25 , maka digunakan Persamaan E7-2 SNI 1729, Spesifikasi
Fe
untuk bangunan gedung baja struktural

QFy

Fcr = Q 0,658 Fe
Fy Fcr = 152,349 MPa Persamaan E7-2

Kekuatan Tekan Nominal Pn = Fcr Ag = 362,591 kN

Dari SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal E1, Kekuatan
Tekan Yang Tersedia adalah:

DFBK

c = 0,9 c Pn = 326,332 kN Pu = 1,2 x 100 kN + 1,6 x 120 kN = 312 kN

Pu
= 0,9561
c Pn

DKI

Pn
c = 1,67 = 217,12 kN Pc = 100 kN + 120 kN = 220 kN
c

c Pc
= 1,0133
Pn

68 dari 282
CONTOH E.6. BATANG TEKAN PROFIL WT TANPA ELEMEN LANGSING

Hitung kekuatan batang tekan dari penampang profil WT 200x400x13x21, Kontrol apakah
kolom ini mampu menahan gaya tekan aksial akibat beban mati PD= 200 kN dan akibat
beban hidup PL= 220 kN. Panjang kolom = 6 m dan kedua ujungnya berupa sendi terhadap
kedua sumbu lentur. Fy = 250 MPa. E = 200 000 MPa.

KLx = 1,0 (6 m) = 6 m KLy = 1,0 (6 m) = 6 m

E
Solusi: E = 200 000 MPa = 0,3 G Fy = 250 MPa
2 1

Properti geometri Profil WT 200x400x13x21

Ag = 109,35 cm2 = 10 935 mm2

bf = 400 mm tf = 21 mm

d = 200 mm tw = 13 mm

Ix = 2470 cm4 = 2,47 x 107 mm4 rx = 47,5 mm

Iy = 11207 cm4 = 1,121 x 108 mm4 ry = 101,2 mm

y = 167,9 mm

Jadi koordinat pusat berat dari tepi atas sayap

C = d - y = 32,1 mm yo = C 0,5 tf = 21,6 mm xo = 0 m

69 dari 282
Besaran yang perlu dihitung

1 t
J = t f3bf + tw3 d - f = 1,374 x 106 mm4
3 2

1 bf3t f3 t f 3
3

Cw = + d - tw = 4,531 x 109 mm6


36 4 2

Ix + Iy
ro = x o2 + y o2 + 113,904 mm
Ag

x o2 + y o2
H =1- = 0,964
ro
2

Kontrol Kelangsingan badan profil

d
= = 15,385
tw

Hitung rasio kelangsingan batas untuk bagian badan profil, r , dari SNI 1729, Spesifikasi
untuk bangunan gedung baja struktural Tabel B4.1a Kasus 4:

E
r 0,75 = 21,213
Fy

karena r , badan profil tidak langsing

Kontrol kelangsingan sayap

bf
= = 9,524
2t f

Hitung rasio kelangsingan batas untuk bagian sayap profil, r , dari SNI 1729, Spesifikasi
untuk bangunan gedung baja struktural Tabel B4.1a Kasus 4.

E
r 0,56 = 15,839
Fy

karena r , sayap profil tidak langsing

Untuk batang tekan tanpa elemen langsing, SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural Pasal E3 dan E4 harus digunakan. Kekuatan tekan nominal, Pn harus
ditentukan berdasarkan kondisi batas lentur, tekuk torsional dan tekuk torsional-lentur.

70 dari 282
Tekuk lentur terhadap sumbu x-x

2E
Fex = 2
= 123,713 MPa 0,44 Fy = 110 MPa
KLx

rx

karena Fex > 0,44 Fy, maka

Fy

Fcrx = 0,658 Fex
Fy = 107,302 MPa

Tekuk Torsional-lentur dan Tekuk Torsional

Karena penampang WT200x400 tidak memiliki elemen langsing, SNI 1729, Spesifikasi
untuk bangunan gedung baja struktural Pasal E4 akan dipakai untuk tekuk torsional-lentur
dan tekuk torsional.

Fcr akan dihitung menggunakan SNI 1729, Spesifikasi untuk bangunan gedung baja
struktural Persamaan E4-2.

Menghitung Fcry

Fcry diambil sebagai Fcr dari SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
KL KLy
Pasal E3, dengan =
r ry

KLy
= 59,289
ry

2E
Fey = 2
= 561,55 MPa > 0,44 Fy = 110 MPa
KLy

ry

Fy

Fey
Fcr = 0,658 Fy = 207,498 MPa

Fcry = Fcr

GJ
Fcrz = = 744,755 MPa
Ag ro2

Fcry + Fcrz 4Fcry Fcrz H


Fcr = 1- 1- = 204,708 MPa tidak menentukan
2H Fcry + Fcrz

71 dari 282
atau Fcr = min Fcr ,Fcrx = 107,302 MPa
Kekuatan Tekan Nominal Pn = Fcr Ag = 1173,351 kN

DFBK

c = 0,9 c Pn = 1,056 x 103 kN Pu = 1,2 x 200 kN + 1,6 x 220 kN = 592 kN

Pu
= 0,5606
c Pn

DKI

Pn
c =1,67 = 702,605 kN Pc = 200 kN + 220 kN = 420 kN
c

c Pc
= 0,5978
Pn

72 dari 282
CONTOH E.7. BATANG TEKAN PROFIL WT DENGAN ELEMEN LANGSING

Hitung kekuatan batang tekan dari penampang WT 200x200x8x13. Kontrol apakah kolom ini
mampu menahan gaya tekan aksial akibat beban mati PD= 200 kN dan akibat beban hidup
PL= 220 kN. Panjang kolom = 6 m dan kedua ujungnya berupa sendi terhadap kedua sumbu
lentur. Fy = 250 MPa. E = 200 000 MPa.

KLx = 1,0 (6 m) = 6 m KLy = 1,0 (6 m) = 6 m

E
Solusi: E = 200 000 MPa = 0,3 G Fy = 250 MPa
2 1

Properti geometri Profil WT 200x200x8x13

Ag = 42,06 cm2 = 4206 mm2

bf = 200 mm tf = 13 mm

d = 200 mm tw = 8 mm

Ix = 1395 cm4 = 1,395 x 107 mm4 rx = 57,6 mm

Iy = 868 cm4 = 8,68 x 106 mm4 ry = 45,4 mm

y = 157,7 mm

Jadi koordinat pusat berat dari tepi atas sayap

C = d - y = 42,3 mm yo = C 0,5 tf = 35,8 mm xo = 0 m

Besaran yang perlu dihitung

1 t
J = t f3bf + tw3 d - f = 1,795 x 105 mm4
3 2

73 dari 282
1 bf3 t f3 tf 3
3

Cw = + d - tw = 2,251 x 108 mm6


36 4 2
I +I
ro = x o2 + y o2 + x y = 81,621 mm
Ag

x o2 + y o2
H =1- = 0,808
ro
2

Kontrol Kelangsingan badan profil

d
= = 25
tw

Hitung rasio kelangsingan batas untuk bagian badan profil, r , dari SNI 1729, Spesifikasi
untuk bangunan gedung baja struktural Tabel B4.1a:

Kasus 4

E
r 0,75 = 21,213
Fy

Karena r , badan profil langsing

Menentukan Qs

E
1,03 = 29,133
Fy

Berlaku Persamaan E7-14 SNI 1729, Spesifikasi untuk bangunan gedung baja struktural

1,22d Fy
Qs =1,908 - = 0,83
tw E

Q = Qs

Kontrol kelangsingan sayap

bf
= = 7,692
2t f

Hitung rasio kelangsingan batas untuk bagian sayap profil, r , dari SNI 1729, Spesifikasi
untuk bangunan gedung baja struktural Tabel B4.1a Kasus 4

E
r 0,56 = 15,839
Fy

74 dari 282
Karena r , sayap profil tidak langsing.
Karena Profil WT ini memiliki elemen langsing, Pasal E7 SNI 1729, Spesifikasi untuk
bangunan gedung baja struktural harus digunakan.

Kekuatan tekan nominal, Pn harus ditentukan berdasarkan kondisi batas lentur, tekuk
torsional dan tekuk torsional-lentur.

TeganganTekuk lentur elastik kritis terhadap sumbu x-x

2E
Fex = 2
= 181,917 MPa
KLx

rx

Tegangan Tekuk Torsional-lentur dan Tekuk Torsional elastik kritis

KLy
= 132,159
ry

2E
Fey = 2
= 113,016 MPa
KLy

ry

GJ
Fez = = 492,744 MPa
Ag ro 2


Fey + Fez 4Fey Fez H = 107,273 MPa
Fey = 1- 1- menentukan
2H Fey + Fez
2

atau Fe = min Fex ,Fey = 107,273 MPa

Q Fy
= 1,934 < 2,25
Fe

Tegangan Kritis

Q Fy

Fcr = Q 0,658 Fe Fy = 92,337MPa Persamaan E7-2 SNI 1729, Spesifikasi untuk


bangunan gedung baja struktural

Kekuatan Tekan Nominal Pn = Fcr Ag = 388,368 kN

75 dari 282
DFBK

c = 0,9 c Pn = 349,532 kN Pu = 1,2 x 100 kN + 1,6 x 120 kN = 312 kN

Pu
= 0,8926
c Pn

DKI

Pn
c =1,67 = 232,556 kN Pc = 100 kN + 120 kN = 220 kN
c

c Pc
= 0,946
Pn

76 dari 282
CONTOH E.8. PERHITUNGAN KUAT TEKAN PROFIL PSB

Hitung kekuatan tekan yang tersedia dari suatu profil PSB 200x200x10 dengan panjang 6 m,
yang menahan gaya tekan akibat beban mati PD = 300 KN dan PL = 475 kN. Ujung bawah
dalam keadaan terjepit sedang ujung atas pin/sendi. Fy = 250 MPa. E = 200 000 MPa.

Data profil PSB 200x200x10 E = 200 000 MPa Fy = 250 MPa

Ag = 7 600 mm2 b = 200 mm t = 10 mm rx = 77,7 mm ry = rx

Solusi:

Berdasarkan AISC Specification Commentary Table C-A-7.1, untuk kondisi jepit-sendi, K =


0,8

KLx = 0,8 (6 m) = 4,8 m KLy = KLx = 4,8 m

Catatan: Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal
B4.1b, jika jari jari sudut tidak diketahui, maka b dan h harus diambil dimensi terluar
penampang minus tiga kali tebal dinding profil. Ini merupakan asumsi yang konservatif.

Hitung b/t dari dinding yang paling langsing

h b - 3t
= 17
t t

Hitung rasio kelangsingan batas, r , dari SNI 1729 Tabel B4. 1a Kasus 6

E
r 1,4 = 39,598
Fy

r ; penampang tidak memiliki elemen yang langsing

77 dari 282
Tegangan Kritis

Menghitung tegangan tekuk kritis elastik, Fe

2E
Fe 2
= 517,237 MPa
K Ly

ry

Menghitung tegangan tekuk lentur, Fcr

E KLy
4,71 = 133,219 karena = 61,776 < 133,219
Fy ry

Fy

maka Fcr = 0,658 Fe
F y = 204,212 MPa

Kekuatan Tekan Nominal Pn = Fcr Ag = 1,552 x 103 kN

Dari SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal E1, Kekuatan
Tekan Yang Tersedia adalah:

DFBK

c = 0,9 c Pn = 1,397 x 103 kN Pu = 1,2 x 300 kN + 1,6 x 475 kN = 1120 kN

Pu
= 0,8018
c Pn

DKI

Pn
c = 1,67 = 929,349 kN Pc = 300 kN + 475 kN = 775 kN
c

c Pc
= 0,8339
Pn

78 dari 282
CONTOH E.9. PERHITUNGAN KUAT TEKAN PROFIL PSB DENGAN ELEMEN
LANGSING

Hitung kekuatan tekan yang tersedia dari suatu profil PSB 260x260x6.3 dengan panjang 6
m, yang menahan gaya tekan akibat beban mati PD= 300 KN dan PL= 475 kN. Ujung bawah
dalam keadaan terjepit sedang ujung atas pin/sendi. Fy = 250 MPa. E = 200 000 MPa.

Data profil PSB 260x260x6.3 E = 200 000 MPa Fy = 250 MPa

Ag = 7256 mm2 H = 400 mm B = 200 mm t = 6,3 mm

rx = 145,3 mm ry = 85,3 mm

Solusi:

Berdasarkan AISC Specification Commentary Table C-A-7.1, untuk kondisi jepit-sendi, K =


0,8

KLx = 0,8 (6 m) = 4,8 m KLy = KLx = 4,8 m

Catatan: Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal
B4.1b, jika jari jari sudut tidak diketahui, maka b dan h harus diambil dimensi terluar
penampang minus tiga kali tebal dinding profil. Ini merupakan asumsi yang konservatif.

Hitung b/t dari dinding yang paling langsing

H - 3t B - 3t
1 = 60,492 2 = 28,746
t t
Hitung rasio kelangsingan batas, r , dari SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural Tabel B4. 1a Kasus 6

E
r 1,4 = 39,598
Fy

79 dari 282
1 r ; penampang memiliki elemen yang langsing

SNI 1729 Pasal E7 digunakan untuk PSB dengan elemen langsing. Kekuatan tekan
nominal, Pn, dihitung berdasarkan kondisi batas tekuk lentur. Tekuk torsional tidak
berpengaruh untuk PSB kecuali panjang tak terbreis torsional jauh melampaui panjang tak
terbreis lentur yang menentukan.

Luas efektif, Ae

Qa = Ae/Ag SNI 1729 Persamaan E7-16

dengan Ae = jumlah luas efektif dari penampang yang dihitung berdasarkan lebar efektif
yang tereduksi, be

Untuk sayap elemen langsing dari penampang pesegi dan pesegi panjang dengan tebal
merata,


E 0,38 E
be =1,92t 1- < b SNI 1729 Persamaan E7-18
f b f

t

dengan f = Pn/Ae, tetapi bisa diambil konservatif sebagai Fy sesuai catatan untuk pemakai
dalam SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal E7.2


E 0,38 E
be =1,92t 1- be = 281,339 mm
Fy H - 3t F y

t

Panjang yang tidak efektif : (H - 3 t) - be = 99,761 mm

Ae = Ag 2 [(H - 3 t) be] t = 5,999 x 103 mm2

Untuk penampang yang hanya memiliki elemen langsing yang diperkaku,

Q = Qa (Qs = 1).

Ae
Q= = 0,827 SNI 1729 Persamaan E7-16
Ag

Tegangan Kritis

Menghitung tegangan tekuk kritis elastik, Fe

2E
Fe 2
= 623,369 MPa
K Ly

ry

80 dari 282
Menghitung tegangan tekuk lentur, Fcr

E K Ly
4,71 = 146,513 karena = 56,272 < 146,513
Q Fy ry

Q Fy

maka Fcr = Q 0,658 Fe Fy = 179,908 MPa

Kekuatan Tekan Nominal Pn = Fcr Ag = 1305,4142 kN

Dari SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal E1, Kekuatan
Tekan Yang Tersedia:

DFBK

c = 0,9 c Pn = 1,175 x 103 kN Pu = 1,2 x 300 kN + 1,6 x 475 kN = 1120 kN

Pu
= 0,9533
c Pn

DKI

Pn
c = 1,67 = 781,685 kN Pc = 300 kN + 475 kN = 775 kN
c

c Pc
= 0,9914
Pn

81 dari 282
CONTOH E.10. PERHITUNGAN KUAT TEKAN PROFIL PIPA

Hitung kekuatan tekan yang tersedia dari suatu profil PIPA ASTM A53 Grade B produksi PT
Gunung Garuda D 10" dengan panjang tak terbreis terhadap sumbu kuat x-x = 6 m dan
panjang tak terbreis terhadap sumbu lemah y-y = 3 m. Kedua ujung kolom adalah sendi. Fy
= 241,317 MPa (= 35 ksi ), Fu = 413,685 MPa (= 60 ksi). E = 200 000 MPa. PD = 200 kN dan
PL= 275 kN.

Data profil Pipa:

E = 200 000 MPa Fy = 35 000 psi = 241,317 MPa

Pipa D10": Dout = 267,4 mm t = 9,3 mm D = Dout

Ag = 7 540,8591 mm2 r = 91,3113 mm

Solusi:

Untuk kondisi pin-pin, K = 1,0 KLx = 1,0 (6 m) = 6 m KLy = 1,0 (3,0 m) = 3 m

Kontrol kelangsingan elemen

D
= 28,753
t

Rasio batas lebar ke tebal

E
r 0,11 = 91,167 dari SNI 1729 Tabel B4. 1a kasus 9
Fy

1 r ; jadi elemen pipa tidak langsing

82 dari 282
Kontrol kelangsingan

K Lx K Ly
= 65,709 menentukan = 32,855
r r
Tegangan Kritis

Menghitung tegangan tekuk kritis elastik, Fe

2E
Fe 2 = 457,1685 MPa
KLx

r

Menghitung tegangan tekuk lentur, Fcr

E K Lx
4,71 = 135,595 karena = 65,709 < 133,219
Fy r

Fy

maka Fcr = 0,658 Fe F y = 193,481 MPa

Kekuatan Tekan Nominal Pn = Fcr Ag = 1 459,0103 kN

Dari SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal E1, Kekuatan
Tekan Yang Tersedia adalah:

DFBK

c = 0,9 c Pn = 1 313,1092 kN Pu = 1,2 x 200 kN + 1,6 x 275 kN = 680 kN

Pu
= 0,5179
c Pn

DKI

Pn
c = 1,67 = 873,6588 kN Pc = 200 kN + 275 kN = 475 kN
c

c Pc
= 0,5437
Pn

83 dari 282
CONTOH E.11. KOLOM I TERSUSUN DENGAN UKURAN SAYAP BERBEDA

Hitunglah kekuatan tekan suatu kolom tersusun, dengan ukuran sayap luar PL 20 mm x 125
mm, sayap dalam PL 20 mm x 200 mm dan ukuran badan PL 10 mm x 280 mm. Kontrol
apakah kolom ini mampu menahan gaya tekan aksial akibat beban mati PD = 400 kN dan
akibat beban hidup PL = 500 kN. Panjang kolom = 4,0 m dan kedua ujungnya berupa sendi
terhadap kedua sumbu lentur. Fy = 250 MPa. E = 200 000 MPa.

E
Solusi: E = 200 000 MPa Fy = 250 MPa = 0,3 G
2 1

Properti geometri

Kolom tersusun

h = 280 mm tw = 10 mm

bf1 = 200 mm tf1 = 20 mm Af1 = bf1 tf1 = 4 x 103 mm2

bf2 = 125 mm tf2 = 20 mm Af2 = bf2 tf2 = 2,5 x 103 mm2

d = h + tf1 + tf2 = 320 mm Aw = h tw = 2,8 x 103 mm2

Properti Penampang tersusun (dengan mengabaikan pengaruh las)

Ag = Af1 + Af2 + h tw = 9 300 mm2

Lokasi pusat berat penampang dari sisi bawah sayap luar (bawah)

h
Af 1 d - 0,5t f 1 + Af 2 0,5t f 2 + Aw + t f 2
2 = 184,194 mm
y=
Ag

1 1 1
I xo = bf 1t f31 + bf 2t f32 + tw h 3
12 12 12

84 dari 282
2 2
tf 1 tf 2 h
2

I x = I xo + Af 1 d - y - + Af 2 y - + Aw + t f 2 - y = 1,593 x 108 mm
4

2 2 2

Ix
rx = = 130,885 mm
Ag

1 1 1 Iy
Iy = t f 1 bf31 + t f 2 bf32 + h tw3 = 1,661 x 107 mm4 ry = = 42,264 mm
12 12 12 Ag

Kelangsingan

Cek kelangsingan sayap luar (bawah)

Hitung kc dengan menggunakan Tabel B4.1b catatan (a)

4
kc = = 0,756 berada diantara 0,35 dan 0,76
h
tw

untuk sayap luar,

bf 2 b
b= t = tf2 = = 3,125
2 t

Hitung rasio kelangsingan batas untuk sayap, r , dari SNI 1729, Spesifikasi untuk
bangunan gedung baja struktural Tabel B4.1a kasus 2

kc E
r 0,64 = 15,739
Fy

r , maka sayap luar tidak langsing

Cek kelangsingan sayap dalam (atas)

bf 1 b
b= t = tf1 = =5
2 t

r , maka sayap dalam tidak langsing

Cek kelangsingan pada badan profil, kemudian hitung Qa, faktor reduksi elemen (badan)
yang diperkaku, menggunakan SNI 1729 Pasal E7.2.

h
= = 28
tw

85 dari 282
Hitung batas kelangsingan untuk badan sesuai SNI 1729, Spesifikasi untuk bangunan
gedung baja struktural Tabel B4.1a kasus 5

E
r 1,49 = 42,144
Fy

Karena r , berarti bagian badan profil, tidak langsing,

Tegangan Tekuk Lentur Elastik terhadap sumbu x-x

Untuk kondisi pin-pin, K = 1,0

KLx = 1,0 (4 m) = 4 m rx = 130,885 mm

K Lx
= 30,561
rx

2E
Fex 2
= 2 113,4279 MPa
KLx

rx

Tegangan Tekuk Elastik Kritis Torsional-Lentur

Menghitung konstanta torsional, J

1 1 1
J = bf 1t f31 + bf 2t f32 + h tw3
3 3 3

J = 9,6 x 105 mm4

Jarak antara pusat sayap

tf 1 tf 2
ho = d - - = 300 mm
2 2

Konstanta pilin

Tebal semua sayap sama tf = tf1

t f ho2 bf31 bf32


Cw = = 2,355 x 1011 mm
6

12 bf31 + bf32

Akibat simetri, pusat berat dan pusat geser terletak pada sumbu y. Oleh karena itu xo = 0.
Jarak dari pusat sayap bawah ke pusat geser adalah:

bf31
e = ho 3
= 241,13 mm
bf 1 + bf 2
3

86 dari 282
Jadi pusat geser diukur dari sisi bawah sayap bawah

tf
e+ = 251,13 mm
2

t
y o = e + f y = 66,937 mm xo = 0 mm
2

Ix + Iy
ro = x o2 + y o2 + = 152,963 mm SNI 1729 Persamaan E4-11
Ag

x o2 + y o2
H =1- = 0,809 SNI 1729 Persamaan E4-10
ro 2

KLy = 1,0 (4,0 m) = 4 m KLz = 1,0 (4,0 m) = 4 m

KLy
= 94,644
ry

Tegangan kritis elastik, Fey. untuk tekuk lentur terhadap sumbu y

2E
Fey 2
= 220,366 MPa Persamaan E3-4
KLy

ry

EC 1
Fez w
+GJ = 381,868 MPa Persamaan E4-9
KLz Ag ro
2 2


Fey + Fez 4Fey Fez = 272,561 MPa
Fe 1- 1- Persamaan E4-5
2H Fey + Fez
2

Jadi yang menentukan adalah

Fe = min Fex ,Fe = 272,561 MPa

Tegangan Tekuk Lentur

Menghitung tegangan tekuk lentur, Fcr

Fy
= 0,917 < 2,25
Fe

87 dari 282
Fy

Fcr = 0,658
Fe
Fy = 170,299 MPa


Kekuatan Tekan Nominal Pn = Fcr Ag = 1583,7798 kN

Dari SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal E1, Kekuatan
Tekan Yang Tersedia:

DFBK

c = 0,9 c Pn = 1,425 x 103 kN Pu = 1,2 x 400 kN + 1,6 x 500 kN = 1280 kN

Pu
= 0,898
c Pn

DKI

Pn
c = 1,67 = 948,371 kN Pc = 400 kN + 500 kN = 900 kN
c

c Pc
= 0,949
Pn

88 dari 282
Bab F Desain Komponen-komponen struktur untuk lentur

PENDAHULUAN

Bab F SNI 1729, Spesifikasi untuk bangunan gedung baja struktural berisi ketentuan untuk
menghitung kekuatan lentur komponen-komponen struktur yang memikul lentur sederhana
di sekitar sumbu utama. Termasuk ketentuan spesifik untuk komponen struktur profil I,
Kanal, PSB, T, siku ganda, siku tunggal, batang tulangan persegi dan bundar serta
penampang tidak simetris. Juga termasuk penampang dengan memproporsikan persyaratan
untuk balok dan gelagar.

Tabel-tabel properti penampang untuk profil I, kanal dan PSB memberikan informasi yang
dapat digunakan untuk mempermudah identifikasi penampang elemen nonkompak dan
langsing. Informasi DFBK dan DKI disajikan berurutan.

Sebagian besar formula dari bab ini diilustrasikan dengan contoh-contoh berikut. Teknik-
teknik desain dan pemilihan diilustrasikan dalam contoh-contoh untuk DFBK dan DKI akan
menghasilkan rasio desain yang hampir sama.

F1. KETENTUAN UMUM

Pemilihan dan evaluasi semua komponen struktur yang berdasarkan pada persyaratan
defleksi dan kekuatan, ditentukan sebagai kekuatan lentur desain, bMn , atau kekuatan
lentur izin, Mn / b ,

dengan

Mn = kekuatan lentur nominal terendah berdasarkan kondisi batas leleh, tekuk torsi lateral,
dan tekuk lokal, di mana berlaku

b = 0,90 (DFBK) b = 1,67 (DKI)

Pendekatan desain diikuti dalam semua contoh.

Istilah Lb yang digunakan dalam bab ini untuk menggambarkan panjang antara titik-titik yang
terbreis mencegah perpindahan lateral dari sayap yang mengalami tekan atau untuk
mencegah puntir penampang. Persyaratan untuk sistem breising dan kekuatan serta
kekakuan yang diperlukan pada titik-titik terbreis diberikan dalam Lampiran 6 SNI 1729,
Spesifikasi untuk gedung baja struktural.

Penggunaan Cb diilustrasikan dalam beberapa contoh berikut.

F2. KOMPONEN STRUKTUR KOMPAK SIMETRIS GANDA PROFIL I DAN KANAL


MELENTUR DI SUMBU MAJOR

SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal F2 berlaku untuk desain
balok kompak dan kanal. Sebagaimana ditunjukkan dalam Catatan dalam Pasal F2 SNI
1729, sebagian besar balok profil I gilas dan kanal termasuk dalam kategori ini. Kurva yang
disajikan sebagai garis solid pada Gambar F-1 adalah hubungan umum kekuatan lentur
nominal, Mn, sebagai fungsi dari panjang tidak terbreis, Lb. Segmen horizontal dari kurva di
ujung kiri, antara Lb = 0 ft (m) dan Lp, adalah rentang di mana kekuatan dibatasi oleh leleh

89 dari 282
lentur. Di wilayah ini, kekuatan nominal diambil sebagai kekuatan momen plastik penuh
penampang yang diberikan oleh Persamaan F2-1 SNI 1729. Dalam rentang kurva di ujung
kanan, mulai pada Lr, kekuatan dibatasi oleh tekuk elastis. Kekuatan di daerah ini diberikan
oleh Persamaan F2-3 SNI 1729. Antara daerah ini, di dalam daerah linier dari kurva antara
Mn = Mp pada Lp di sebelah kiri, dan Mn = 0,7My = 0,7FySx pada Lr di sebelah kanan,
kekuatan dibatasi oleh tekuk inelastis. Kekuatan di daerah ini diberikan dalam Persamaan
F2-2 SNI 1729, Spesifikasi untuk bangunan gedung baja struktural.

Kurva diplot sebagai garis solid tebal merupakan kasus di mana Cb = 1,0, sedangkan garis
putus-putus yang tebal merupakan kasus di mana Cb melebihi 1,0. Kekuatan nominal
dihitung dalam Persamaan F2-2 dan F2-3 SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural berbanding lurus terhadap Cb, tetapi dibatasi oleh Mp seperti yang ditunjukkan
pada gambar ini
Persamaan F2-1
Persamaan F2-2
Mp

0,7Fy Sx Persamaan F2-3

Mn Mn dengan Cb = 1,0

Mn dengan Cb = 1,0

Lp Lr

Lb

Gambar F-1 Kekuatan balok versus panjang tidak terbreis

Mn = Mp = Fy Zx (SNI 1729 Persamaan F2-1)

L - L
Mn = Cb M p M p 0,7Fy Sx b p M p (SNI 1729 Persamaan F2-1)
L - L
r p

Mn = FcrSx Mp (SNI 1729 Persamaan F2-3)

dengan

2
C 2E J c Lb
Fcr = b 1+10,078
Lb Sx ho rts

rts

Ketentuan pasal ini diillustrasikan dalam Contoh F.1 (balok profil I) dan Contoh F.2 (kanal).

Ketentuan desain plastis diberikan dalam Lampiran 1 SNI 1729, Spesifikasi untuk bangunan
gedung baja struktural. Lpd, panjang tidak terbreis maksimum untuk segmen komponen
struktur prismatis mengandung sendi plastis yang kurang dari Lp.

90 dari 282
F3. KOMPONEN STRUKTUR PROFIL I SIMETRIS GANDA DENGAN BADAN KOMPAK
DAN NONKOMPAK ATAU SAYAP LANGSING MELENGKUNG DI SUMBU MAJOR

Kekuatan profil yang dirancang sesuai dengan pasal ini dibatasi oleh tekuk lokal sayap
tertekan. Hanya beberapa profil sayap lebar standar yang memiliki sayap nonkompak.

Kurva kekuatan untuk keadaan batas tekuk lokal sayap, ditunjukkan dalam Gambar F-2,
menyerupai kurva tekuk lateral-torsional. Parameter sumbu horizontal adalah =bf/2tf.
Bagian datar dari kurva di sebelah kiri pf adalah kekuatan leleh plastis, Mp. Bagian
melengkung di sebelah kanan rf adalah kekuatan yang dibatasi oleh tekuk sayap elastis.
Transisi linear antara dua daerah ini adalah kekuatan yang dibatasi oleh tekuk sayap
inelastis.

Persamaan F2-1
Persamaan F3-1
Mp

0,7Fy Sx Persamaan F3-2


Mn

pf rf
bf
2t f

Gambar F-2 Kekuatan tekuk lokal sayap

Tidak ada komponen struktur profil I standar dengan sayap langsing. Ketentuan sayap
nonkompak pasal ini diilustrasikan dalam Contoh F.3.

F4. KOMPONEN STRUKTUR PROFIL I LAIN DENGAN BADAN KOMPAK ATAU


NONKOMPAK MELENTUR DI SUMBU MAJOR

Pasal F4 SNI 1729, Spesifikasi untuk bangunan gedung baja struktural berlaku untuk
komponen struktur profil I simetris ganda dengan badan nonkompak dan komponen struktur
profil I simetris tunggal (dengan sayap yang berbeda) dengan badan kompak atau
nonkompak.

F5. KOMPONEN STRUKTUR PROFIL I SIMETRIS GANDA DAN SIMETRIS TUNGGAL


DENGAN BADAN LANGSING MELENTUR DI SUMBU MAJOR

Pasal ini berlaku untuk komponen struktur profil I dengan badan langsing, sebelumnya
ditetapkan sebagai "balok induk pelat".

F6. KOMPONEN STRUKTUR PROFIL I DAN KANAL MELENTUR DI SUMBU MINOR

Komponen struktur profil I dan C melentur di sumbu minor tidak mengalami tekuk torsi
lateral. Profil gilas atau tersusun dengan sayap nonkompak atau langsing, sebagaimana
ditentukan oleh Tabel B4.1a dan B4.1b SNI 1729, Spesifikasi untuk bangunan gedung baja
struktural harus diperiksa untuk kekuatan berdasarkan kondisi batas tekuk lokal sayap
menggunakan Persamaan F6-2 atau F6-3 yang sesuai.

91 dari 282
Pada umumnya profil I dan Kanal memiliki sayap kompak, sehingga dapat mengembangkan
momen plastis penuh, Mp, terhadap sumbu minor. Ketentuan-ketentuan pasal ini
diilustrasikan dalam Contoh F.5.

F7. KOMPONEN STRUKTUR PSB PERSEGI DAN PERSEGI PANJANG SERTA


KOMPONEN STRUKTUR BERBENTUK BOKS

PSB persegi dan persegi panjang hanya perlu diperiksa untuk kondisi batas leleh dan tekuk
lokal. Meskipun tekuk torsi lateral secara teoritis dapat terjadi pada PSB persegi panjang
yang melentur terhadap sumbu kuat dalam jangka waktu lama, secara praktis defleksi akan
menentukan desain.

Pemilihan PSB persegi atau persegi panjang dengan sayap kompak digambarkan dalam
Contoh F.6. Ketentuan untuk PSB persegi atau persegi panjang dengan sayap nonkompak
diilustrasikan dalam Contoh F.7. Ketentuan untuk PSB dengan sayap langsing diilustrasikan
dalam Contoh F.8.

F8. PSB BUNDAR

Definisi PSB meliputi produk tabung dan pipa. Kondisi batas tekuk torsi lateral tidak berlaku,
tetapi PSB bundar mengalami reduksi kekuatan akibat tekuk lokal. Desain pipa diilustrasikan
dalam Contoh F.9.

F9. PROFIL T DAN SIKU GANDA YANG DIBEBANI DALAM BIDANG SIMETRI

SNI 1729, Spesifikasi untuk bangunan gedung baja struktural menyediakan pemeriksaan
tekuk lokal sayap, yang hanya berlaku bila sayap mengalami tekan akibat lentur. Kondisi
batas ini jarang terjadi. Pemeriksaan tekuk lokal badan telah ditambahkan dalam SNI 1729.
Perhatian harus diberikan pada kondisi ujung profil T untuk mencegah momen ujung terjepit
tak terduga yang menginduksi tekan pada badan kecuali kondisi batas ini telah diperiksa.
Desain profil T yang mengalami lentur digambarkan dalam Contoh F.10.

F10. SIKU TUNGGAL

SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal F10 memperkenankan
desain lentur siku tunggal dengan menggunakan sumbu utama atau sumbu geometris
(sumbu x-x dan sumbu y-y). Dalam merancang siku tunggal tanpa breising menerus dengan
menggunakan ketentuan desain sumbu geometris, My harus dikalikan dengan 0,80 pada
saat menggunakan Persamaan F10-1, F10-2 dan F10-3. Desain siku tunggal yang
mengalami lentur digambarkan dalam Contoh F.11.

F11. BATANG TULANGAN PERSEGI PANJANG DAN BUNDAR

Keadaan batas tekuk lokal tidak berlaku untuk setiap batang tulangan. Kecuali jika batang
tulangan persegi panjang melentur terhadap sumbu kuat, persegi pejal, batang tulangan
persegi panjang dan bundar tidak mengalami tekuk torsi lateral dan ditentukan oleh kondisi
batas leleh saja. Batang tulangan persegi panjang yang melentur terhadap sumbu kuat
mengalami tekuk torsi lateral dan diperiksa untuk kondisi batas ini sesuai dengan
Persamaan F11-2 dan F11-3.

Ketentuan-ketentuan ini dapat digunakan untuk memeriksa pelat dan badan profil T pada
sambungan. Contoh desain batang tulangan persegi panjang yang mengalami lentur
digambarkan dalam Contoh F.12. Contoh desain batang tulangan bundar yang mengalami
lentur digambarkan dalam Contoh F.13.

92 dari 282
F12. PROFIL-PROFIL TIDAK SIMETRIS

Karena banyaknya jenis profil tidak simetris, ketentuan tekuk torsi lateral dan tekuk lokal
tidak tersedia secara spesifik pada pasal SNI 1729, Spesifikasi untuk bangunan gedung baja
struktural. Contoh umum disediakan, tetapi kajian literatur dan pertimbangan teknis yang
sesuai diperlukan untuk penerapan pasal ini.

F13. PROPORSI BALOK DAN GELAGAR

Pasal F13 SNI 1729, Spesifikasi untuk bangunan gedung baja struktural meliputi
pemeriksaan kondisi batas untuk keruntuhan tarik akibat lubang-lubang pada sayap balok
yang mengalami tarik, batas proporsi untuk komponen struktur profil I, persyaratan detail
untuk pelat penutup dan persyaratan sambungan untuk balok tersusun yang tersambung
bersebelahan. Juga termasuk persyaratan panjang tidak terbreis untuk balok yang
dirancang menggunakan ketentuan redistribusi momen Pasal B3.7 SNI 1729, Spesifikasi
untuk bangunan gedung baja struktural.

93 dari 282
94 dari 282
95 dari 282
Catatan: Lp dan Lr nilainya tergantung Fy

96 dari 282
CONTOH F.1-1 PERENCANAAN KOMPONEN STRUKTUR LENTUR PROFIL WF
TERHADAP SUMBU KUAT (TERSOKONG PENUH DALAM ARAH LATERAL)

Rencanakan profil WF yang digunakan sebagai balok tertumpu sederhana dengan panjang
12 m. Material baja Fy = 250 MPa. Batasan lendutan akibat beban hidup sebesar L/360.
Beban nominal balok adalah beban mati terbagi rata sebesar 1 kN/m dan beban hidup
terbagi rata sebesar 3 kN/m. Balok diasumsikan tersokong penuh dalam arah lateral.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

kN kN
Beban terbagi rata: wD = 1 wL= 3
m m

Panjang bentang: L = 12 m

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

kN 1
Metode DFBK: wu = 1,2 wD + 1,6 wL = 6 Mu = wu L2 = 108 kN m
m 8

kN 1
Metode DKI: wa = wD + wL = 4 Ma = wa L2 = 72 kN m
m 8

Momen inersia penampang minimum berdasarkan batasan lendutan akibat beban hidup
L/360

L
max = = 33,333 mm
360
4
5 WL .L
I x_reqd = = 1,215 108 mm4
384 E. max

Gunakan profil WF 400x200x8x13: (Gunakan Tabel Profil WF)

Ix = 1,356 108 mm4 > I x_reqd = 1,215 108 mm4

97 dari 282
Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal F2, profil
tersebut termasuk penampang kompak. Karena balok tersokong penuh arah lateral dan
penampang kompak, kekuatan lentur ditentukan oleh kondisi batas leleh.

Zx = 8,679 105 mm3

Mpx = Zx Fy = 216,975 kN m

Metode DFBK:

b = 0,9 b Mpx = 195,278 kN m > Mu = 108 kN m (o.k.)

Mu
0,553
b M px

Metode DKI:

M px
b = 1,67 129,925 kN m > Ma = 72 kN m (o.k.)
b

b M a
0,554
M px

98 dari 282
CONTOH F.1-2 PERENCANAAN KOMPONEN STRUKTUR LENTUR PROFIL WF
TERHADAP SUMBU KUAT (TERSOKONG LATERAL DI TITIK SEPERTIGA BENTANG)

Periksa kekuatan profil WF 400x200x8x13 yang digunakan sebagai balok tertumpu


sederhana dengan panjang 12 m. Material baja Fy = 250 MPa. Beban nominal balok adalah
beban mati terbagi rata sebesar 1 kN/m dan beban hidup terbagi rata sebesar 3 kN/m. Balok
tersokong lateral di titik-titik ujung dan sepertiga bentang.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

kN kN
Beban terbagi rata: wD = 1 wL = 3
m m

Panjang bentang: L = 12 m

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

kN 1
Metode DFBK: wu = 1,2 wD + 1,6 wL = 6 Mu = wu L2 = 108 kN m
m 8

kN 1
Metode DKI: wa = wD + wL = 4 Ma = wa L2 = 72 kN m
m 8

Panjang tak tersokong untuk semua segmen sama, yaitu:

L
Lb = =4m
3

Besaran penampang profil WF 400x200x8x13: (Lihat Tabel Profil WF)

d = 400 mm bf = 200 mm tw = 8 mm tf = 13 mm

Ix = 1,356 108 mm4 Sx = 7,748 105 mm3 Zx = 8,679 105 mm3

Kekuatan lentur nominal, Mn

99 dari 282
Menghitung Cb.

Untuk perhitungan tekuk torsi lateral, faktor modifikasi momen tak seragam dapat dihitung
berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Persamaan F1-1.
Karena distribusi beban hidup dan beban mati sama, nilai Cb akan sama baik untuk metode
DFBK maupun metode DKI.

Pada segmen tengah:

Lb
x = Lb + =5m Mu.A = Mu (x) = 105 kN m Ma.A = Ma (x) = 70 kN m
4

Lb
x = Lb + =6m Mu.B = Mu (x) = 108 kN m Ma.B = Ma (x) = 72 kN m
2

3Lb
x = Lb + =7m Mu.C = Mu (x) = 105 kN m Ma.C = Ma (x) = 70 kN m
4

Mu.max = Mu (6m) = 108 kN m

12,5Mu.max
Cb.mid = 1,014
2,5Mu.max + 3Mu.A + 4Mu.B + 3Mu.C

Lp = 1,966 m Lr = 5,787m

atau dengan rumus:

E
Lp 1,76ry
Fy

0,7 Fy
2 2
E Jc Jc
Lr 1,9rts 6,76
0,7Fy S x h0 S x h0 E

dengan

I y cw
rts2 dan c =1
Sx

Untuk balok dengan penampang kompak dan panjang bentang tak tertumpu lateral, Lp < Lb
Lr, kekuatan lentur nominal ditentukan oleh nilai terkecil kondisi batas leleh lentur atau tekuk
torsi lateral inelastis.

Mpx = Zx Fy = 216,975 kN m

L -L
M n.mid c b.mid Mpx M px - 0,7Fy S x b p = 175,999 kN m
L -L
r p

100 dari 282


Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal F1,
kekuatan lentur desain:

Metode DFBK:

Mu.mid Mu 6m = 108 kN m

b = 0,9 b Mn.mid = 158,399 kN m > Mu.mid = 108 kN m

M u.mid
0,682
b M n.mid

Metode DKI

M a.mid M a 6m = 72 kN m

M n.mid
b = 1,67 105,388 kN m > Ma.mid = 72 kN m
b

b M a.mid
0,683
M n.mid

Pada segmen ujung:

Lb
x= =1m Mu.A = Mu (x) = 33 kN m Ma.A = Ma (x) = 22 kN m
4

Lb
x= =2m Mu.B = Mu (x) = 60 kN m Ma.B = Ma (x) = 40 kN m
2

3Lb
x= =3m Mu.C = Mu (x) = 81 kN m Ma.C = Ma (x) = 54 kN m
4

Mu.max = Mu (4m) = 96 kN m

12,5 Mu.max
Cb.end = = 1,46
2,5 Mu.max + 3 Mu.A + 4 Mu.B + 3 Mu.C

L -L
M n.end c b.end M px M px - 0,7Fy S x b p = 253,507 kN m
L -L
r p

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal F1,
kekuatan lentur desain:

101 dari 282


Metode DFBK:

Mu.end = Mu (4m) = 96 kN m

b = 0,9 b Mn.end = 228,156 kN m > Mu.end = 96 kN m

M u.end
0,421
b M n.end

Metode DKI:

Ma.end = Ma (4m) = 64 kN m

M n.end
b = 1,67 151,8 kN m > Ma.end = 64 kN m
b

b M a.end
0,422
M n.end

102 dari 282


CONTOH F.1-3 PERENCANAAN KOMPONEN STRUKTUR LENTUR PROFIL WF
TERHADAP SUMBU KUAT (TERSOKONG DI TITIK SETENGAH BENTANG)

Periksa kekuatan profil WF 350 x 175 x 7 x 11 yang digunakan sebagai balok tertumpu
sederhana dengan panjang 12 m. Material baja Fy = 250 MPa. Beban nominal balok adalah
beban mati terbagi rata sebesar 1 kN/m dan beban hidup terbagi rata sebesar 3 kN/m. Balok
tersokong arah lateral di titik-titik ujung dan setengah bentang.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

kN kN
Beban terbagi rata: wD = 1 wL= 3
m m

Panjang bentang: L = 12 m

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

kN 1
Metode DFBK: wu = 1,2 wD + 1,6 wL = 6 Mu = wu L2 = 108 kN m
m 8

kN 1
Metode DKI: wa = wD + wL = 4 Ma = wa L2 = 72 kN m
m 8

Panjang tak tersokong:

L
Lb = =6m
2

Besaran penampang profil WF 350 x 175 x 7 x 11: (Lihat Tabel Profil WF)

d = 350 mm bf = 175 mm tw = 7 mm tf = 11 mm

Ix = 1,356 108 mm4

Sx = 7,748 105 mm3

Zx = 8,679 105 mm3

103 dari 282


Kekuatan lentur nominal, Mn

Menghitung Cb.

Untuk perhitungan tekuk torsi lateral, faktor modifikasi momen tak seragam dapat dihitung
berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Persamaan F1-1.

Pada segmen ujung:

Lb
x= = 1,5 m Mu.A = Mu (x) = 47,25 kN m Ma.A = Ma (x) = 31,5 kN m
4

Lb
x= =3m Mu.B = Mu (x) = 81 kN m Ma.B = Ma (x) = 54 kN m
2

3 Lb
x= = 4,5 m Mu.C = Mu (x) = 101,25 kN m Ma.C = Ma (x) = 67,5 kN m
4

Mu.max = Mu (6m) = 108 kN m

12,5Mu.max
Cb = = 1,299
2,5Mu.max + 3Mu.A + 4Mu.B + 3Mu.C

Berdasarkan Tabel Profil WF:

Lp = 1,966 m Lr = 5,787 m

Untuk balok dengan penampang kompak dan panjang bentang tak tertumpu lateral, Lb > Lr,
kekuatan lentur nominal ditentukan oleh nilai terkecil kondisi batas leleh lentur atau tekuk
torsi lateral elastis.

Berdasarkan Tabel Profil WF:

h0 = d tf = 339 mm

J = 1,94 105 mm4

rts = 46,408 mm

c = 1,0 (untuk profil WF simetris ganda)

2
cb 2E Jc Lb
Fcr = 2
1+ 0,0078 = 160,578 MPa
Lb Sx h0 rts

rts

Mpx = Zx Fy = 216,975 kN m

Mn = Fcr Sx = 124,416 kN m < Mpx = 216,975 kN m

104 dari 282


Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal F1,
kekuatan lentur desain:

Metode DFBK:

Mu = Mu (6m) = 108 kN m

b = 0,9 b Mn = 111,974 kN m > Mu = 108 kN m

Mu
0,965 < 1,00 (o.k.)
b M n

Metode DKI:

Ma = Ma (6m) = 72 kN m

Mn
b = 1,67 74,501 > Ma = 72 kN m
b

b M a
0,966 < 1,00 (o.k.)
Mn

105 dari 282


CONTOH F.2-1 BALOK KANAL PENAMPANG KOMPAK TERSOKONG PENUH DALAM
ARAH LATERAL

Tentukan profil kanal yang digunakan sebagai balok tepi atap yang tertumpu sederhana
sepanjang 7,5 m. Lendutan akibat beban hidup dibatasi L/360. Material baja Fy = 250 MPa.

Beban nominal balok adalah beban mati terbagi rata sebesar 3,2 kN/m dan beban hidup
terbagi rata sebesar 10 kN/m. Balok diasumsikan tersokong penuh dalam arah lateral.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

kN kN
Beban terbagi rata: wD = 3,2 wL = 10
m m

Panjang bentang: L = 7,5 m

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

kN 1
Metode DFBK: wu = 1,2 wD + 1,6 wL = 19,84 Mu = wu L2 = 139,5 kN m
m 8

kN 1
Metode DKI: wa = wD + wL = 13,2 Ma = wa L2 = 92,813 kN m
m 8

Seluruh profil kanal material baja Fy = 250 MPa termasuk penampang kompak. Karena
penampang kompak dan balok tersokong penuh, kondisi batas leleh menentukan, sehingga
Mn = Mp.

Dicoba profil C 380 x 100 x 10,5 x 16

106 dari 282


Besaran penampang profil C 380 x 100 x 10,5 x 16: (pengaruh kelengkungan antara sayap
dan badan diabaikan)

d = 380 mm bf = 100 mm t = 10,5 mm tf = 16 mm

1 d - tf 1
2

d - 2t f
3
I x 2 bf tf 3 bf t f tw 1,429 108 mm4
12 2 12

Zx = bf tf (d tf ) + 1/4 tw (d 2tf )2 = 9,003 105 mm3

Kekuatan lentur nominal, Mn

Mp = Fy Zx = 225,075 kN m

Mn = Mp = 225,075 kN m

Kekuatan lentur desain:

Metode DFBK:

b = 0,9 b Mn = 202,567 kN m > Mu = 139,5 kN m (o.k.)

Lendutan akibat beban hidup:

L
Batasan lendutan maksimum: limit = = 20,833 mm
360

Lendutan maksimum di tengah bentang:

5 w L L4
max = = 14,411 mm < limit = 20,833 mm (o.k.)
384 E I x

107 dari 282


CONTOH F.2-2 BALOK KANAL PENAMPANG KOMPAK TERSOKONG DALAM ARAH
LATERAL DI SETIAP SEPERLIMA BENTANG

Periksa kekuatan profil kanal yang digunakan dalam Contoh F.2-1. Balok diasumsikan
tersokong dalam arah lateral di setiap seperlima bentang.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

Besaran penampang profil C380x100x10.5x16:(pengaruh kelengkungan antara sayap dan


badan diabaikan)

d = 380 mm bf = 100 mm tw = 10,5 mm tf = 16 mm

1 d - tf 1
2

d - 2t f
3
I x 2 bf tf bf t f
3
tw 1,429 x 108 mm4
12 2 12

2I x
Sx 7,523 x 105 mm3
d

Zx = bf tf (d tf ) + 1/4 tw (d 2tf )2 = 9,003 105 mm3

Dari Contoh F.2-1:

Metode DFBK: Momen terfaktor maksimum Mu = 139,5 kN m

Metode DKI: Momen kerja maksimum Ma = 92,813 kN m

Kekuatan lentur nominal, Mn

Seluruh profil kanal dari material Fy = 250 MPa termasuk penampang kompak. Pada
segmen tengah, yaitu lokasi momen maksimum, bidang momen mendekati distribusi
seragam.

Cb = 1,00

108 dari 282


Berdasarkan Tabel Profil Kanal untuk Balok:

Lp = 1487,1 m Lr = 5322,8 m

atau dengan rumus:

E
Lp = 1,76 ry
Fy

0,7Fy
2 2
E Jc Jc
L r 1,9rts 6,76
0,7Fy Sx ho Sx ho E

dengan

I y cw h0 Iy
rts2 dan c
Sx 2 cw
L
Panjang bentang tak tersokong arah lateral: Lb = = 1,5 m
5
Untuk profil kanal kompak dengan Lp < Lb < Lr, kekuatan lentur ditentukan oleh nilai terkecil
antara kondisi batas leleh atau tekuk torsi lateral inelastis.

Mp = Fy Zx = 225,075 kN m

L -L
Mn = min cb M p M p 0,7Fy Sx b p ,M p 225,075 kN m
L -L
r p

Kekuatan lentur desain:

Metode DFBK:

b = 0,9 b Mn = 202,567 kN m > Mu = 139,5 kN m (o.k.)

Mu
0,689
b M n

Metode DKI:

Mn
b = 1,67 = 134,775 kN m > Ma = 92,813 kN m (o.k.)
b

b M a
0,689
Mn

109 dari 282


Lendutan maksimum di tengah bentang:

5 w L L4
max = 14,411 < limit = 20,833 mm (o.k.)
384 E I x

110 dari 282


CONTOH F.2-2 BALOK KANAL PENAMPANG KOMPAK TERSOKONG DALAM ARAH
LATERAL DI SETIAP SEPERLIMA BENTANG

Periksa kekuatan profil kanal yang digunakan dalam Contoh F.2-1. Balok diasumsikan
tersokong dalam arah lateral di setiap seperlima bentang.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

Besaran penampang profil C380x100x10.5x16:(pengaruh kelengkungan antara sayap dan


badan diabaikan)

d = 380 mm bf = 100 mm tw = 10,5 mm tf = 16 mm

1 d - tf 1
2

d - 2t f
3
I x 2 bf tf bf t f
3
tw 1,429 108 mm4
12 2 12

2I x
Sx 7,523 x 105 mm3
d

1
Zx = bf tf (d tf ) + tw (d 2tf )2 = 9,003 105 mm3
4

Dari Contoh F.2-1:

Metode DFBK: Mu = 139,5 kN m

Metode DKI: Ma = 92,813 kN m

Kekuatan lentur nominal, Mn

Seluruh profil kanal dari material baja Fy = 250 MPa termasuk penampang kompak. Pada
segmen tengah, yaitu lokasi momen maksimum, bidang momen mendekati distribusi
seragam.

Cb = 1,00

111 dari 282


Berdasarkan Tabel Profil Kanal untuk Balok:

Lp = 1487,1 m Lr = 5322,8 m

atau dengan rumus:

E
Lp 1,76ry
Fy

0,7Fy
2 2
E Jc Jc
L r 1,9rts 6,76
0,7Fy Sx ho Sx ho E

dengan

I y cw h0 Iy
rts2 dan c
Sx 2 cw

L
Panjang bentang tak tersokong arah lateral: Lb = = 15 m
5

Untuk profil kanal kompak dengan Lp < Lb < Lr, kuat lentur ditentukan oleh nilai terkecil
antara kondisi batas leleh atau tekuk torsi lateral inelastis.

Mp = Fy Zx = 225,075 kN m

L -L
Mn = min cb M p M p 0,7Fy Sx b p ,M p 225,075 kN m
L -L
r p

Kekuatan lentur desain:

Metode DFBK:

b = 0,9 b Mn = 202,567 kN m > Mu = 139,5 kN m (o.k.)

Mu
0,689
b M n

Metode DKI:

Mn
b = 1,67 134,775 kN m > Ma = 92,813 kN m (o.k.)
b

bM a
0,689
Mn

112 dari 282


CONTOH F.3 BALOK WF DENGAN SAYAP NON-KOMPAK YANG MENGALAMI
LENTUR TERHADAP SUMBU KUAT

Tentukan profil WF untuk digunakan sebagai balok tertumpu sederhana sepanjang 12 m.


Material baja Fy = 250 MPa. Beban nominal balok adalah beban mati terbagi rata sebesar
0,75 kN/m dan sepasang beban hidup terpusat masing-masing sebesar 80 kN.

Balok diasumsikan tersokong penuh dalam arah lateral.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

kN
Beban terbagi rata: wD = 0,75 PL = 80 kN
m

Panjang bentang: L = 12 m

Berdasarkan Pasal 2 SNI 1729, Spesifikasi untuk bangunan gedung baja struktural,
kekuatan lentur desain minimum:

kN
Metode DFBK: wu = 1,2 wD = 0,9 Pu = 1,6 PL = 128 kN
m

1 L
Mu = wu L2 + Pu = 528,2 kN m
8 3

kN
Metode DKI: wa = wD = 0,75 Pa = PL = 80 kN
m

1 L
Ma = wa L2 + Pa = 333,5 kN m
8 3

Di coba profil WF dengan besaran 394 x 398 x 11 x 18:

d = 394 mm bf = 398 mm tw = 11 mm tf = 18 mm

Sx = 2,85 106 mm3 Zx = 3,12 106 mm3

113 dari 282


bf
f = = 11,056
2tf

Batasan kelangsingan penampang sayap berdasarkan SNI 1729, Spesifikasi untuk


bangunan gedung baja struktural Tabel B4.1b (Kasus 10):

E
pf = 0,38 = 10,748
Fy

E
rf = 1,0 = 28,284
Fy

Karena pf < f < rf sayap dikategorikan sebagai penampang nonkompak

Kekuatan lentur nominal, Mn

Karena balok tersokong penuh arah lateral sehingga tekuk torsi lateral tidak menentukan,
kekuatan lentur ditentukan oleh kondisi Tekuk Lokal Sayap Tertekan. (SNI 1729, Spesifikasi
untuk bangunan gedung baja struktural Pasal F3.2)

Mpx = Fy Zx = 780 kN m

-
Mn = M px M px 0,7Fy Sx f pf = 775,068 kN m
-
rf pf

Metode DFBK:

b = 0,9 b Mn = 697,561 kN m > Mu = 528,2 kN m (o.k.)

Mu
0,757
b M n

Metode DKI:

Mn
b = 1,67 464,112 kN m > Ma = 333,5 kN m (o.k.)
b

bM a
0,719
Mn

114 dari 282


CONTOH F.4 PERANCANGAN BALOK PROFIL WF BERDASARKAN MOMEN INERSIA
TERHADAP SUMBU KUAT

Rencanakan profil WF yang digunakan sebagai balok tertumpu sederhana dengan panjang
9 m. Material baja Fy = 250 MPa. Batasan lendutan akibat beban hidup sebesar 25 mm.
Beban nominal balok adalah beban mati terbagi rata sebesar 10 kN/m dan beban hidup
terbagi rata sebesar 20 kN/m. Balok diasumsikan tersokong penuh dalam arah lateral.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

kN kN
Beban terbagi rata: wD = 10 wL = 20
m m

Panjang bentang: L=9m

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

kN 1
Metode DFBK: wu = 1,2 wD + 1,6 wL = 44 Mu = wu L2 = 445,5 kN m
m 8

kN 1
Metode DKI: wa = wD + wL = 30 Ma = wa L2 = 303,75 kN m
m 8

Momen inersia penampang minimum berdasarkan batasan lendutan max = 25 mm

5 w LL4
I x_reqd = = 3,417 108 mm4
384 E max

Gunakan profil WF 500 x 200 x 10 x 16: (Lihat Tabel Profil WF)

Ix = 4,785 108 mm4 > I x_reqd = 3,417 108 mm4

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal F2, profil
tersebut termasuk penampang kompak. Karena balok tersokong penuh arah lateral dan
penampang kompak, kekuatan lentur ditentukan oleh kondisi batas leleh.

Zx = 2,175 106 mm3

115 dari 282


Mpx = Zx Fy = 543,75 kN m

Mn = Mpx = 543,75 kN m

Kekuatan lentur desain:

Metode DFBK:

b = 0,9 b Mn = 489,375 kN m > Mu = 445,5 kN m (o.k.)

Mu
0,91
b M n

Metode DKI:

Mn
b = 1,67 325,599 kN m > Ma = 303,75 kN m (o.k.)
b

bM a
0,933
Mn

116 dari 282


CONTOH F.5 BALOK PROFIL WF YANG MENGALAMI LENTUR TERHADAP SUMBU
LEMAH

Rencanakan profil WF yang digunakan sebagai balok tertumpu sederhana yang dibebani
terhadap sumbu lemah dengan panjang 4 m. Material baja Fy = 250 MPa.

Batasan lendutan akibat beban hidup sebesar L/240. Beban nominal balok adalah beban
mati terbagi rata sebesar 5 kN/m dan beban hidup terbagi rata sebesar 15 kN/m. Balok
diasumsikan tersokong dalam arah lateral di kedua ujung.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

kN kN
Beban terbagi rata: wD = 5 wL = 15
m m

Panjang bentang: L=4m

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

kN 1
Metode DFBK: wu = 1,2 wD + 1,6 wL = 30 Mu = wu L2 = 60 kN m
m 8

kN 1
Metode DKI: wa = wD + wL = 20 Ma = wa L2 = 40 kN m
m 8

Momen inersia penampang minimum berdasarkan batasan lendutan L/240

L
max = = 16,667 mm
240

5 w LL4
I y_reqd = = 1,5 107 mm4
384 E max

Gunakan profil WF 400 x 200 x 8 x 13: (Lihat Tabel Profil WF)

Iy = 1,737 107 mm4 > I y_reqd = 1,5 107 mm4

117 dari 282


Sy = 1,737 105 mm3

Zy = 2,676 105 mm3

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal F2, profil
tersebut termasuk penampang kompak. Karena balok mangalami lentur terhadap sumbu
lemah dan penampang kompak, kekuatan lentur ditentukan oleh kondisi batas leleh.

Mpy = Zy Fy = 66,9 kN m 1,6 Sy Fy = 69,48 kN m

Mn = min(Mpy , 1.6 Sy Fy) = 66,9 kN m

Kekuatan lentur desain:

Metode DFBK:

b = 0,9 b Mn = 60,21 kN m > Mu = 60 kN m (o.k.)

Mu
0,997
b M n

Metode DKI:

Mn
b = 1,67 40,06 kN m > Ma = 40 kN m (o.k.)
b

bM a
0,999
Mn

118 dari 282


CONTOH F.6 BALOK PSB DENGAN SAYAP KOMPAK

Tentukan profil PSB untuk digunakan sebagai balok dengan panjang bentang 4,8 m yang
menahan beban mati terbagi rata sebesar 4 kN/m dan beban hidup terbagi rata sebesar 12
kN/m. Lendutan akibat beban hidup dibatasi L/240. Material baja dengan Fy = 250 MPa.
Balok diasumsikan tersokong penuh dalam arah lateral.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

kN kN
Beban terbagi rata: wD = 4 wL = 12
m m

Panjang bentang: L = 4,8 m

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur rencana minimum:

kN 1
Metode DFBK: wu = 1,2 wD + 1,6 wL = 24 Mu = wu L2 = 69,12 kN m
m 8

kN 1
Metode DKI: wa = wD + wL = 16 Ma = wa L2 = 46,08 kN m
m 8

Penentuan momen inersia minimum yang diperlukan:

L
Batasan lendutan maksimum akibat beban hidup: limit = = 20 mm
240

Momen inersia profil minimum yang diperlukan:

5 w L L4
Ix.req = = 2,074 107 mm4
384 E limit

Pemilihan profil balok

Pilih profil PSB dengan Ix > Ix.req

119 dari 282


Berdasarkan tabel profil: PSB 180x180x8

H = 180 mm B = 180 mm t = 8 mm

Ix = 2,72 107 mm4 > Ix.req = 2,074 107 mm4 (o.k.)

Pemeriksaan kekompakan penampang:

B E
= 22,5 < p = 1,12 = 31,678 (penampang kompak)
t Fy

Kekuatan lentur ditentukan oleh kondisi batas leleh:

Zx = 3,553 105 mm3 (dari Tabel Profil PSB)

Mp = Zx Fy = 88,825 kN m

Mn = Mp = 88,825 kN m

Kekuatan lentur desain:

Metode DFBK:

b = 0,9 b Mn = 79,942 kN m > Mu = 69,12 kN m (o.k.)

Mu
= 0,865
b M n

Metode DKI:

Mn
b = 1,67 = 53,189 kN m > Ma = 46,08 kN m (o.k.)
b
bM a
= 0,866
Mn

120 dari 282


CONTOH F.7 BALOK PSB DENGAN SAYAP NONKOMPAK

Tentukan profil PSB untuk digunakan sebagai balok dengan panjang bentang 7,5 m yang
menahan beban mati terbagi rata sebesar 2 kN/m dan beban hidup terbagi rata sebesar 6
kN/m. Lendutan akibat beban hidup dibatasi L/240. Material baja dengan Fy = 250 MPa.
Balok diasumsikan tersokong dalam arah lateral hanya di kedua ujung. Profil yang dipilih
dalam contoh ini adalah profil nonkompak sebagai ilustrasi penerapan Pasal F7.2 dan Pasal
F7.3.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

kN kN
Beban terbagi rata: wD = 2 wL = 6
m m

Panjang bentang: L = 7,5 m

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

kN 1
Metode DFBK: wu = 1,2 wD + 1,6 wL = 12 Mu = wu L2 = 84,375 kN m
m 8
kN 1
Metode DKI: wa = wD + wL= 8 Ma = wa L2 = 56,25 kN m
m 8

Penentuan momen inersia minimum yang diperlukan:

L
Batasan lendutan maksimum akibat beban hidup: limit = = 31,25 mm
240

Momen inersia profil minimum yang diperlukan:

5 w L L4
Ix.req = = 3,955 107 mm4
384 E limit

121 dari 282


Pemilihan profil balok

Pilih profil PSB dengan Ix > Ix.req

Berdasarkan tabel profil: PSB 220x220x6.3

H = 220 mm B = 220 mm t = 6,3 mm

Ix = 4,102 107 mm4 > Ix.req = 3,955 107 mm4 (o.k.)

Sx = 3,729 105 mm3 Zx = 4,317 105 mm3

Pemeriksaan kelangsingan sayap:

B E
= 34,921 > p= 1,12 = 31,678
t Fy
E
< r = 1,4 = 39,598 (sayap nonkompak)
Fy

Pemeriksaan kekompakan badan:

H E
= 34,921 < p = 2,42 = 68,448 (badan kompak)
t Fy

Kondisi batas leleh:

Zx = 4,317 105 mm3 (dari Tabel Profil PSB)

Mp = Zx Fy = 107,925 kN m

Mn1 = Mp = 107,925 kN m

Karena sayap nonkompak, gunakan Persamaan F7-2

B Fy
M n 2 M p - M p - Fy S x 3,57 4,0 101,933 kN m
t E

Kekuatan lentur desain:

Kekuatan lentur nominal diambil dari nilai terkecil untuk kedua kondisi batas di atas:

Mn = min(Mn1, Mn2) = 101,933 kN m

Metode DFBK:

b = 0,9 b Mn = 91,74 kN m > Mu = 84,375 kN m (o.k.)

Mu
0,920
b M n

122 dari 282


Metode DKI:

Mn
b = 1,67 = 61,038 kN m > Ma = 56,25 kN m (o.k.)
b

bM a
0,922
Mn

123 dari 282


CONTOH F.8 BALOK PSB DENGAN SAYAP LANGSING

Periksa kekuatan lentur balok profil PSB 250x250x6.3 untuk digunakan sebagai balok
dengan panjang bentang 6,5 m yang menahan beban mati terbagi rata sebesar 2 kN/m dan
beban hidup terbagi rata sebesar 6 kN/m. Material baja dengan Fy = 250 MPa.

Balok diasumsikan tersokong penuh dalam arah lateral.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

kN kN
Beban terbagi rata: wD = 2 wL= 6
m m

Panjang bentang: L = 6,5 m

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

kN 1
Metode DFBK: wu = 1,2 wD + 1,6 wL = 12 Mu = wu L2 = 63,375 kN m
m 8

kN 1
Metode DKI: wa = wD + wL = 8 Ma = wa L2 = 42,25 kN m
m 8

Berdasarkan tabel profil: PSB 250x250x6.3

H = 250 mm B = 250 mm t = 6,3 mm

Ix = 4,102 107 mm4 Sx = 3,729 105 mm3 Zx = 4,317 105 mm3

Pemeriksaan kelangsingan sayap:

B E
= 39,683 > r = 1,4 = 39,598 (sayap langsing)
t Fy

Pemeriksaan kekompakan badan:

124 dari 282


H E
= 39,683 > p= 2,42 = 68,448 (badan kompak)
t Fy

Kekuatan lentur nominal

Untuk profil PSB dengan sayap langsing dan badan kompak, gunakan Pasal F7.2(c):

Mn = Fy Se

Dengan Se adalah modulus penampang efektif dengan lebar sayap tertekan efektif, be:


E 0,38 E
be = 1,92 t 1 = 249,462 mm < B = 250 mm
Fy B Fy
t

Lebar sayap tertekan yang tidak efektif:

bineff = B be = 0,538 mm

Momen inersia efektif dihitung dengan memperhitungkan lebar sayap tertekan efektif dan
memperhatikan pergeseran garis netral. Cara alternatif yang lebih mudah dan konservatif
adalah dengan memperhitungkan pengurangan lebar sayap secara simetris untuk sayap
atas dan sayap bawah.

1 H t
2

I x.eff = I x 2 bineff t 3 bineff t 40,919 mm2


12 2 2

Modulus penampang efektif:

I x.eff
Sx.eff = = 3,274 105 mm3
H

2

Kekuatan lentur desain:

Mn = Fy Sx.eff = 81,838 kN m

Metode DFBK:

b = 0,9 b Mn = 73,655 kN m > Mu = 63,375 kN m (o.k.)

Mu
= 0,860
b M n

125 dari 282


Metode DKI:

Mn
b = 1,67 = 49,005 kN m > Ma = 42,25 kN m (o.k.)
b

bM a
= 0,862
Mn

126 dari 282


CONTOH F.9 BALOK PROFIL PIPA LINGKARAN

Periksa kekuatan lentur balok profil Pipa 220x12 untuk digunakan sebagai balok dengan
panjang bentang 5 m yang menahan beban mati terbagi rata sebesar 6 kN/m dan beban
hidup terbagi rata sebesar 18 kN/m. Material baja dengan Fy = 250 MPa.

Balok diasumsikan tersokong dalam arah lateral hanya di kedua ujung.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

kN kN
Beban terbagi rata: wD = 6 wL = 18
m m

Panjang bentang: L=5m

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kuat lentur desain minimum:

kN 1
Metode DFBK: wu = 1,2 wD + 1,6 wL = 36 Mu = wu L2 = 112,5 kN m
m 8

kN 1
Metode DKI: wa = wD + wL = 24 Ma = wa L2 = 75 kN m
m 8

Berdasarkan tabel profil: Pipa 220x12

D = 220 mm t = 12 mm

1 3
D D 2t = 5,197 105 mm3
3
Zx =
6

Pemeriksaan kelangsingan penampang:

D E
= 18,333 < p = 0,07 = 56 (penampang kompak)
t Fy

127 dari 282


D E
= 18,333 < 0,45 = 360 (Pasal F8 dapat digunakan)
t Fy

Kekuatan lentur nominal berdasarkan leleh lentur

Mn = Fy Zx = 129,936 kN m

Kekuatan lentur desain:

Metode DFBK:

b = 0,9 b Mn = 116,942 kN m > Mu = 112,5 kN m (o.k.)

Mu
= 0,962
b M n
Metode DKI:

Mn
b = 1, 67 = 77,806 kN m > Ma = 75 kN m (o.k.)
b
bM a
= 0,964
Mn

128 dari 282


CONTOH F.10 BALOK PROFIL T

Tentukan profil T untuk digunakan sebagai balok dengan panjang bentang 2,4 m yang
menahan beban mati terbagi rata sebesar 2 kN/m dan beban hidup terbagi rata sebesar 6
kN/m. Material baja dengan Fy = 250 MPa. Balok diasumsikan tersokong penuh dalam arah
lateral.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

kN kN
Beban terbagi rata: wD = 2 wL = 6
m m

Panjang bentang: L = 2,4 m

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

kN 1
Metode DFBK: wu = 1,2 wD + 1,6 wL = 12 Mu = wu L2 = 8,64 kN m
m 8

kN 1
Metode DKI: wa = wD + wL = 8 Ma = wa L2 = 5,76 kN m
m 8

Dicoba profil: T 220x12

d = 125 mm bf = 125 mm tw = 6 mm tf = 9 mm

Besaran lain:

tw d - t f bf tf
yp = = 7,284 mm < tf = 9 mm (PNA di sayap)
2bf

tf yp d - yp
z x = bf - tw t f y p y ptw d - y p tw = 4,471 104 mm3
2
2 2

A = (bf tw) tf + d tw = 1,821 103 mm2

129 dari 282


tf d
bf - tw tf d tw
y=
2 2 = 28,388 mm
A
2
1 t 1 d
Ix bf - tw tf3 bf - tw t f y - f + d 3tw + dtw - y = 2,468 106 mm4
12 2 12 2

Ix
Sx = 2,554 104 mm3
d - y
Ix
Sx = 8,693 104 mm3
y

Leleh Lentur

Mp = Fy Zx = 11,178 kN m

My = Fy Sx = 6,386 kN m 1,6 My = 10,217 kN m

Karena stem tertarik, maka: Mp = min(Mp , 1.6 My) = 10,217 kN m

Tekuk Torsi Lateral (SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal
F9.2)

Karena balok tersokong secara penuh, tekuk torsi lateral tidak perlu diperiksa.

Tekuk Lokal Sayap (SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal
F9.3)

Pemeriksaan batas rasio kelangsingan berdasarkan Tabel B4.1b Kasus 10.

bf E
= 6,944 < pf = 0,38 = 10,748 (sayap kompak)
2t f Fy

Kekuatan lentur nominal berdasarkan leleh lentur

Mn = Mp = 10,217 kN m

Kekuatan lentur desain:

Metode DFBK:

b = 0,9 b Mn = 9,195 kN m > Mu = 8,64 kN m (o.k.)

Mu
= 0,940
b M n

130 dari 282


Metode DKI:

Mn
b = 1,67 = 6,118 kN m > Ma = 5,76 kN m (o.k.)
b

bM a
= 0,942
Mn

131 dari 282


CONTOH F.11A BALOK PROFIL SIKU TUNGGAL

Tentukan profil siku tunggal untuk digunakan sebagai balok dengan panjang bentang 1,8 m
yang menahan beban mati terbagi rata sebesar 0,8 kN/m dan beban hidup terbagi rata
sebesar 2,4 kN/m. Kaki vertikal dipasang di bagian atas sehingga ujung kaki mengalami
tekan. Tidak ada beban dalam arah horizontal. Material baja dengan Fy = 250 MPa. Balok
diasumsikan tersokong dalam arah lateral di kedua ujung.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

kN kN
Beban terbagi rata: wD = 0,8 wL = 2,4
m m

Panjang bentang: L = 1,8 m

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

kN 1
Metode DFBK: wu = 1,2 wD + 1,6 wL = 4,8 Mu = wu L2 = 1,944 kN m
m 8

kN 1
Metode DKI: wa = wD + wL = 3,2 Ma = wa L2 = 1,296 kN m
m 8

Dicoba profil: L 100x100x7

b = 100 mm t = 7 mm

A = b t + (b t) t = 1,351 103 mm2

t b
b - t t bt
cx = 2 2 = 27,593 mm
A

132 dari 282


2 2
1 3 b 1 t
Ix b t + b t c x b - t t 3 b - t t c x = 1,315 106 mm4
12 2 12 2
Ix
Sx = 1,817 104 mm3
b - c x
Leleh Lentur

Berdasarkan Pasal F10.1, kekuatan lentur nominal berdasarkan kondisi leleh lentur:

Mn1 = 1,5 (Fy Sx) = 6,812 kN m

Tekuk torsi lateral

Berdasarkan Pasal F10.2, untuk profil siku tunggal yang melentur terhadap sumbu
geometris dan tidak tersokong dalam arah lateral, My diambil sebesar 0,80 momen leleh
menggunakan modulus penampang geometris

My = 0,8 Fy Sx = 3,633 kN m

Untuk momen lentur terhadap salah satu sumbu geometris siku tunggal sama kaki tanpa
gaya tekan, tanpa sokongan torsi lateral, dan gaya tekan maksimum pada ujung kaki,
gunakan persamaan 10-6a.

Cb = 1,14 (untuk balok dengan beban terbagi rata dan sokongan lateral di kedua ujung)

Lb = L = 1,8 m

0,66 E b 4 t cb Lb t
2

Me 1+ 0,78 b2 1 = 16,129 kN m > My = 3,633 kN m
L2b

sehingga SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Persamaan F10-3
dapat digunakan

My
M n 2 min 1,92 -1,17 My , My = 3,633 kN m
Me

Tekuk lokal kaki

Pasal 10.3 digunakan untuk kondisi ujung kaki mengalami tekan

Pemeriksaan kelangsingan kaki.

b E
= = 14,286 < p = 0,54 = 15,274
t Fy

kaki kompak, tidak terjadi tekuk lokal kaki

Kekuatan lentur nominal berdasarkan nilai terkecil kondisi leleh lentur dan tekuk torsi

133 dari 282


lateral:

Mn = min(Mn1, Mn2) = 3,633 kN m

Kekuatan lentur desain:

Metode DFBK:

b = 0,9 b Mn = 3,27 kN m > Mu = 1,944 kN m (o.k.)

Mu
= 0,595
b Mn

Metode DKI:

Mn
b = 1,67 = 2,176 kN m > Ma = 1,296 kN m (o.k.)
b

bM a
= 0,596
Mn

134 dari 282


CONTOH F.11B BALOK PROFIL SIKU TUNGGAL

Tentukan profil siku tunggal untuk digunakan sebagai balok dengan panjang bentang 1,8 m
yang menahan beban mati terbagi rata sebesar 0,8 kN/m dan beban hidup terbagi rata
sebesar 2,4 kN/m. Kaki vertikal dipasang di bagian atas sehingga ujung kaki mengalami
tekan. Tidak ada beban dalam arah horizontal. Material baja dengan Fy = 250 MPa. Balok
diasumsikan tersokong dalam arah lateral di kedua ujung dan di titik
tengah bentang.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

kN kN
Beban terbagi rata: wD = 0,8 wL = 2,4
m m

Panjang bentang: L = 1,8 m

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

kN 1
Metode DFBK: wu = 1,2 wD + 1,6 wL = 4,8 Mu = wu L2 = 1,944 kN m
m 8

kN 1
Metode DKI: wa = wD + wL = 3,2 Ma = wa L2 = 1,296 kN m
m 8

Dicoba profil: L 100x100x7

b = 100 mm t = 7 mm

A = b t + (b t) t = 1,351 103 mm2

t b
b - t t bt
cx 2 2 = 27,593 mm
A

135 dari 282


2 2
1 3 b 1 t
Ix b t + b t c x b - t t 3 b - t t c x = 1,315 106 mm4
12 2 12 2

Ix
Sx = 1,817 104 mm3
b - c x
Leleh Lentur

Berdasarkan Pasal F10.1, kekuatan lentur nominal berdasarkan kondisi leleh lentur:

Mn1 = 1,5 (Fy Sx) = 6,812 kN m

Tekuk torsi lateral

Berdasarkan Pasal F10.2(b)(iii)(b), untuk profil siku tunggal yang tersokong dalam arah
lateral di titik momen maksimum, My diambil sebesar momen leleh menggunakan modulus
penampang geometris.

My = Fy Sx = 4,541 kN m

Untuk momen lentur terhadap salah satu sumbu geometris siku tunggal sama kaki tanpa
gaya tekan, tanpa sokongan torsi lateral, dan gaya tekan maksimum pada ujung kaki,
gunakan persamaan 10-6a.

Cb = 1,30 (untuk balok dengan beban terbagi rata dan sokongan lateral di kedua ujung
dan titik tengah bentang)

Lb = L = 1,8 m

0,66 E b 4 t cb Lb t

2

M e 1,25 1+ 0,78 b2 1 = 22,991 kN m > My = 4,541 kN m


L2b

sehingga SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Persamaan F10-3
dapat digunakan

My
M n 2 min 1,92 -1,17 My , My = 4,541 kN m
Me

Tekuk lokal kaki

Pasal 10.3 digunakan untuk kondisi ujung kaki mengalami tekan

Pemeriksaan kelangsingan kaki.

b E
= = 14,286 < p = 0,54 = 15,274
t Fy

kaki kompak, tidak terjadi tekuk lokal kaki

136 dari 282


Kekuatan lentur nominal berdasarkan nilai terkecil kondisi leleh lentur dan tekuk torsi lateral:
Mn = min(Mn1, Mn2) = 4,541 kN m

Kekuatan lentur desain:

Metode DFBK:

b = 0,9 b Mn = 4,087 kN m > Mu = 1,944 kN m (o.k.)

Mu
= 0,476
b Mn

Metode DKI:

Mn
b = 1,67 = 2,719 kN m > Ma = 1,296 kN m (o.k)
b

bM a
= 0,477
Mn

137 dari 282


CONTOH F.11C BALOK PROFIL SIKU TUNGGAL

Tentukan profil siku tunggal untuk digunakan sebagai balok dengan panjang bentang 1,8 m
yang menahan beban vertikal berupa beban mati terbagi rata sebesar 0,8 kN/m dan beban
hidup terbagi rata sebesar 2,4 kN/m. Beban horizontal adalah beban angin terbagi rata
sebesar 1,8 kN/m. Material baja dengan Fy = 250 MPa. Balok diasumsikan tersokong dalam
arah lateral di kedua ujung. Gunakan kombinasi 4 untuk DFBK dan kombinasi 6a untuk DKI.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

kN kN kN
Beban terbagi rata: wD = 0,8 wL = 2,4 wW = 1,8
m m m

Panjang bentang: L = 1,8 m Lb = L = 1,8 m


Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

kN 1
Metode DFBK: wux = 1,2 wD + wL = 3,36 Mux = wux L2 = 1,361 kN m
m 8
kN 1
wuy = 1,0 wW = 1,8 Muy = wuy L2 = 0,729 kN m
m 8

kN 1
Metode DKI: wax = wD + 0,75 wL = 2,6 Max = wax L2 = 1,053 kN m
m 8

kN 1
way = 0,75 wW = 1,35 May = way L2 = 0,547 kN m
m 8

Dicoba profil: L 100x100x7

b = 100 mm t = 7 mm A = b t + (b t) t = 1,351103 mm2

Besaran-besaran penampang terhadap sumbu geometris:

138 dari 282


t b
b - t t bt
cx 2 2 = 27,593 mm
A
2 2
1 3 b 1 t
Ix b t + b t c x b - t t 3 b - t t c x = 1,315 106 mm4
12 2 12 2

Ix
Sx = 1,817 104 mm3
b - c x
cy = cx = 27,593 mm Iy = Ix = 1,315106 mm4 Sy = Sx = 1,817104 mm3

t b t b-t
Ixy = b t c x - c y - + b - t t c x - c y - t + 5
= 7,842 10 mm
4

2 2 2 2

Besaran-besaran penampang terhadap sumbu utama:

= 45o
zc = b cos( ) = 70,711 mm

wB = cx sec( ) = 39,023 mm

wC = b sin( ) wB = 31,688 mm

2
Ix + Iy I - I
Iz - x y + I xy2 = 5,311 105 mm4
2 2

2
Ix + Iy I - I
Iw - x y + I xy2 = 2,1 x 106 mm4
2 2

Iz
SzB = 1,361 104 mm3
wB

Iz
SzC = 1,676 104 mm3
wC

Iw
SwC = 2,969 104 mm3
zc

139 dari 282


Penyesuaian tanda momen:

Metode DFBK: Mux = Mux = 1,361 kN m

Muy = Muy = 0,729 kN m

Metode DKI: Max = Max = 1,053 kN m

May = May = 0,547 kN m

Momen terhadap sumbu utama:

Metode DFBK: Muw = Mux cos() + Muy sin() = 0,447 kN m

Muz = Mux sin() + Muy cos() = 1,478 kN m

Metode DKI: Maw = Max cos() + May sin() = 0,358 kN m

Maz = Max sin() + May cos() = 1,131 kN m


Kekuatan lentur nominal terhadap sumbu Z

Karena Muz dan Maz positif, ujung kaki mengalami tekan

Leleh Lentur

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal F10.1,
kekuatan lentur nominal berdasarkan kondisi leleh lentur:

Mnz = 1,5 (Fy SzB) = 5,104 kN m

Tekuk torsi lateral

Berdasarkan Pasal F10, kondisi batas tekuk torsi lateral tidak terjadi pada saat jika momen
terhadap sumbu minor.

140 dari 282


Tekuk lokal kaki

Pasal 10.3 digunakan untuk kondisi ujung kaki mengalami tekan

Pemeriksaan kelangsingan kaki.

b E
= 14,286 < p 0,54 = 15,274
t Fy

kaki kompak, tidak terjadi tekuk lokal kaki

Kekuatan lentur nominal berdasarkan kondisi leleh lentur:

Mnz = 5,104 kN m

Kekuatan lentur desain:

Metode DFBK:

b = 0,9 b Mnz = 4,593 kN m > Muz = 1,478 kN m (o.k.)

Metode DKI:

M nz
b = 1,67 = 3,056 kN m > Maz = 1,131 kN m (o.k.)
b
Kekuatan lentur nominal terhadap sumbu W

Leleh Lentur

Mnw1 = 1,5 (Fy SwC) = 11,135 kN m

Tekuk torsi lateral

Menghitung Me

Untuk lentur terhadap sumbu kuat profil siku sama kaki yang tidak tersokong secara lateral
dalam arah menerus, gunakan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
Persamaan F10-4.

Cb = 1,14

0,46 E b 2 t 2 c b
Me = = 28,551 kN m > My = Fy SwC = 7,423 kN m
Lb

sehingga SNI 1729 Persamaan F10-3 dapat digunakan

My
M nw 2 = min 1,92 -1,17 M y ,M y = 7,423 kN m
Me

Tekuk lokal kaki

141 dari 282


Karena kaki kompak, tidak terjadi tekuk lokal kaki

Kekuatan lentur nominal berdasarkan nilai terkecil antara kondisi leleh lentur dan tekuk torsi
lateral:

Mnw = min(Mnw1 , Mnw2) = 7,423 kN m

Kekuatan lentur desain:

Metode DFBK:

b = 0,9 b Mnw = 6,681 kN m

Metode DKI:

M nw
b = 1,67 = 4,445 kN m
b

Resultan momen memiliki komponen terhadap setiap sumbu utama, sehingga rasio
tegangan harus diperiksa sesuai Pasal H2.

f ra f rbw f rbz
+ + 1,0
Fca Fcbw Fcbz

Catatan:
Agar perhitungan lebih mudah, persamaan interaksi dapat digunakan dalam bentuk momen daripada
tegangan. Tanda positif dan negatif momen agar diperhatikan pada saat memeriksa kondisi di titik-
titik kontrol.

di titik B

Mw tidak menghasilkan tegangan di titik B, sedangkan Mz menghasilkan tegangan tarik di


titik B.
Muz
Metode DFBK: 0- = 0,322 < 1,0
bM nz
b Maz
Metode DKI: 0- = 0,37 < 1,0
M nz

di titik C

Mw menghasilkan tegangan tarik di titik C, sedangkan Mz menghasilkan tegangan tekan di


titik C.

Muw Muz
Metode DFBK: - = 0,255 < 1,0
bMnw bM nz

b Maw b Maz
Metode DKI: - = 0,29 < 1,0
Mnw M nz

142 dari 282


di titik A

Mw dan Mz menghasilkan tegangan tekan di titik A.

Muw Muz
Metode DFBK: = 0,389 < 1,0
bMnw bM nz

b Maw b Maz
Metode DKI: = 0,451 < 1,0
Mnw M nz

Karena seluruh interaksi tegangan bernilai < 1.0, profil tersebut kuat memikul beban desain.
Walaupun pemeriksaan telah dilakukan di ketiga titik, titik A merupakan titik kontrol karena
pada titik tersebut kedua momen menghasilkan tegangan tekan.

143 dari 282


CONTOH F.12 BATANG TULANGAN PERSEGI PANJANG

Tentukan batang tulangan persegi panjang untuk digunakan sebagai balok dengan panjang
bentang 3,6 m yang menahan beban mati terbagi rata sebesar 6 kN/m dan beban hidup
terbagi rata sebesar 18 kN/m. Material baja dengan Fy = 250 MPa. Balok tersokong penuh
dalam arah lateral di kedua ujung dan titik tengah bentang. Secara konservatif, gunakan Cb
= 1,0.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

kN kN
Beban terbagi rata: wD = 6 wL = 18
m m

Panjang bentang: L = 3,6 m

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

kN 1
Metode DFBK: wu = 1,2 wD + 1,6 wL = 36 Mu = wu L2 = 58,32 kN m
m 8

kN 1
Metode DKI: wa = wD + wL = 24 Ma = wa L2 = 38,88 kN m
m 8

Coba batang tulangan persegi 120 mm x 80 mm.

d = 120 mm b = 80 mm

bd 2
Sx = 1,92 105 mm3
6
bd 2
Zx = 2,88 105 mm3
4

Kekuatan lentur nominal

Leleh lentur:

Periksa batasan sesuai Pasal F11.1

144 dari 282


L
Lb = 1,8 m
2

L bd 0,08E
= 33,75 < = 64
b2 Fy

sehingga kondisi batas leleh menentukan dan tekuk torsi lateral tidak terjadi

Mp = Fy Zx = 72 kN m

My = Fy Sx = 48 kN m

Mn = min(Mp , 1.6 My) = 72 kN m

Kekuatan lentur desain:

Metode DFBK:

b = 0,9 b Mn = 64,8 kN m > Mu = 58,32 kN m (o.k.)

Mu
= 0,9 < 1,00 (o.k.)
b Mn

Metode DKI:

Mn
b = 1,67 = 43,114 kN m > Ma = 38,88 kN m (o.k)
b

bM a
= 0,902 < 1,00 (o.k.)
Mn

145 dari 282


CONTOH F.13 BATANG TULANGAN BUNDAR

Tentukan batang tulangan bundar untuk digunakan sebagai balok dengan panjang bentang
0,8 m yang menahan beban mati terpusat sebesar 0,5 kN dan beban hidup terpusat sebesar
1,25 kN/m. Material baja dengan Fy = 250 MPa. Berat sendiri balok dapat diabaikan. Balok
tersokong penuh dalam arah lateral hanya di kedua ujung.

Secara konservatif, gunakan Cb = 1,0.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

Beban terbagi rata: PD = 0,4 kN PL = 1,2 kN

Panjang bentang: L = 0,8 m

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

1
Metode DFBK: Pu = 1,2 PD + 1,6 PL = 2,4 kN Mu= Pu L = 0,48 kN m
4

1
Metode DKI: Pa = PD + PL = 1,6 kN Ma= Pa L = 0,32 kN m
4

Coba batang tulangan bundar berdiameter 25 mm

d = 25 mm

d 3
Sx = = 1,534 103 mm3
32

d3
Zx = = 2,604 103 mm3
6

146 dari 282


Kekuatan lentur nominal

Leleh lentur:

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal F11.1,
kekuatan lentur nominal ditentukan oleh kondisi leleh lentur

Mp = Fy Zx = 0,651 kN m

My = Fy Sx = 0,383 kN m

Mn = min(Mp , 1.6 My) = 0,614 kN m

Kekuatan lentur desain:

Metode DFBK:

b = 0,9 b Mn = 0,552 kN m > Mu = 0,48 kN m (o.k.)

Mu
0,869
bMn

Metode DKI:

Mn
b = 1,67 = 0,367 kN m > Ma = 0,32 kN m (o.k.)
b

bM a
= 0,871
Mn

147 dari 282


Bab G Desain Komponen Struktur untuk Geser

PENDAHULUAN

Bab G SNI 1729, Spesifikasi untuk bangunan gedung baja struktural meliputi badan
komponen struktur simetris tunggal atau ganda memikul geser pada pelat badan, siku
tunggal, penampang PSB, dan geser dalam arah sumbu lemah profil simetris tunggal atau
ganda.

Sebagian besar persamaan dalam Bab G ini diilustrasikan dengan contoh.

DFBK dan DKI akan menghasilkan desain yang sama untuk kasus di mana efek beban
hidup kira-kira tiga kali efek beban mati.

G1. KETENTUAN UMUM

Kekuatan geser desain, v Vn, dan kekuatan geser ijin, Vn / v , ditentukan sebagai berikut:

Vn = kekuatan geser nominal berdasarkan leleh geser atau tekuk geser

Vn = 0,6 Fy AwCv (SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
Persamaan G2-1)

v = 0,90 (DFBK) v = 1,67 (DKI)

Pengecualian:

Untuk profil I canai panas dengan h/tw 2,24 E / Fy dapat digunakan

v = 1,00 (DFBK) v = 1,50 (DKI)

SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G2 tidak menggunakan
aksi medan tarik. SNI 1729 Pasal G3 secara khusus membahas penggunaan aksi medan
tarik.

G2. KOMPONEN STRUKTUR DENGAN BADAN TIDAK DIPERKAKU ATAU BADAN


DIPERKAKU

Sebagaimana ditunjukkan dalam Catatan SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural pasal G2 ini, hampir semua profil I tidak mengalami tekuk geser dan juga
memenuhi syarat untuk faktor keamanan dan ketahanan yang lebih besar, v = 1,00
(DFBK) dan v = 1,50 (DKI)

Perhitungan desain kekuatan geser Profil I disajikan dalam Contoh G.1. Desain kekuatan
geser kanal disajikan dalam Contoh G.2.

G3. AKSI MEDAN TARIK

Sebuah gelagar tersusun dengan badan tipis dan pengaku transversal disajikan dalam
Contoh G.8.

148 dari 282


G4. SIKU TUNGGAL

Contoh desain kekuatan geser siku tunggal diilustrasikan dalam Contoh G.3.

G5. PSB PERSEGI PANJANG DAN KOMPONEN STRUKTUR BERBENTUK BOKS

Ketinggian geser, h, diambil sebagai jarak bersih antara sayap dikurangi radius sudut dalam
pada setiap sisi. Jika jari-jari kelengkungan tidak diketahui, h harus diambil sebagai dimensi
luar dalam arah geser dikurangi 3 kali ketebalan. Desain kekuatan geser PSB persegi
disajikan dalam Contoh G.4.

G6. PSB BUNDAR

Desain kekuatan geser PSB bundar disajikan dalam Contoh G.5.

G7. GESER SUMBU LEMAH PADA PROFIL SIMETRIS GANDA DAN TUNGGAL

Desain kekuatan geser sumbu lemah, lihat Contoh G.6 dan Contoh G.7.

G8. BALOK DAN GELAGAR DENGAN BUKAAN BADAN

Untuk balok dan gelagar dengan contoh bukaan badan, lihat AISC Design Guide 2, Steel
and Composite Beams with Web Openings (Darwin, 1990).

149 dari 282


CONTOH G.1 BALOK PROFIL WF YANG MENGALAMI GESER TERHADAP SUMBU
KUAT

Periksa kekuatan geser balok profil WF 400x200x8x13 yang menahan gaya geser sebesar
120 kN akibat beban mati dan 180 kN akibat beban hidup.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

Gaya geser: VD = 120 kN VL = 180 kN

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan geser desain minimum:

Metode DFBK: Vu = 1,2 VD + 1,6 VL = 432 kN

Metode DKI: Va = VD + VL = 300 kN

Data profil WF 400x200x8x13: (Gunakan Tabel Profil I)

d = 400 mm bf = 200 mm tw = 8 mm tf = 13 mm r = 16 mm

h = d 2 (tf + r) = 342 mm

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G2.1(a),
koefisien geser badan:

h E
= 42,75 < 2,24 = 63,357
tw Fy

sehingga Cv = 1,0

Menghitung Aw

Aw = d tw = 3,2 103 mm2

Menghitung Vn

Vn = 0,6 Fy Aw Cv = 480 kN

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural G2.1(a),
kekuatan geser desain:

Metode DFBK:

v = 1,00 Vn = v Vn = 480 kN > Vu = 432 kN (o.k.)

Vu
= 0,9
V n

150 dari 282


Metode DKI:

Vn
v = 1,50 = 320 kN > Va = 300 kN (o.k.)
v
Va
= 0,938
Vn

v

151 dari 282


CONTOH G.2 BALOK PROFIL KANAL YANG MENGALAMI GESER TERHADAP SUMBU
KUAT

Periksa kekuatan geser balok profil C 380x100x10.5x16 yang menahan gaya geser sebesar
80kN akibat beban mati dan 220 kN akibat beban hidup. Material baja Fy = 250 MPa.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

Gaya geser: VD = 80 kN VL = 220 kN

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan geser desain minimum:

Metode DFBK: Vu = 1,2 VD + 1,6 VL = 448 kN

Metode DKI: Va = VD + VL = 300 kN

Data profil C 380x100x10,5x16: (Gunakan Tabel Profil Kanal)

d = 380 mm bf = 100 mm tw = 10,5 mm tf = 16 mm

h = d 2 tf = 348 mm

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G2.1(b),
koefisien tekuk geser pelat badan:

h
= 33,143 < 260
tw

sehingga kv = 5

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural G2.1(b),
koefisien geser badan:

h kv E
= 33,143 < 1,10 = 69,57
tw Fy

sehingga Cv = 1,0

Menghitung Aw

Aw = d tw = 3,99 103 mm2

Menghitung Vn

Vn = 0,6 Fy Aw Cv = 598,5 kN

152 dari 282


Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G2.1(a),
kekuatan geser desain dengan faktor v = 1,00 (DFBK) dan v = 1,50 (DKI) tidak berlaku
untuk profil kanal:

Metode DFBK:

v = 0,90 Vn = v Vn = 538,65 kN > Vu = 448 kN (o.k.)

Vu
= 0,832
V n

Metode DKI:

Vn
v = 1,67 = 358,383 kN > Va = 300 kN (o.k.)
v

Va
= 0,837
Vn

v

153 dari 282


CONTOH G.3 BALOK PROFIL SIKU YANG MENGALAMI GESER

Periksa kekuatan geser balok profil L120x120x8 yang menahan gaya geser sebesar 15 kN
akibat beban mati dan 50 kN akibat beban hidup. Material baja Fy = 250 MPa.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

Gaya geser: VD = 15 kN VL = 50 kN

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan geser desain minimum:

Metode DFBK: Vu = 1,2 VD + 1,6 VL = 98 kN

Metode DKI: Va = VD + VL = 65 kN

Data profil L120x120x8: (Gunakan Tabel Profil Siku)

b = 120 mm t = 8 mm

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G2.4,
koefisien tekuk geser pelat badan: kv = 1,2

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G2.1(b),
koefisien geser badan:

b kv E
= 15 < 1,10 = 34,082
t Fy

sehingga Cv = 1,0

Menghitung Aw

Aw = b t = 960 mm2

Menghitung Vn

Vn = 0,6 Fy Aw Cv = 144 kN

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G2.1,
kekuatan geser desain:

Metode DFBK:

v = 0,90 Vn = v Vn = 129,6 kN > Vu = 98 kN (o.k.)


Vu
= 0,756
V n

154 dari 282


Metode DKI:

Vn
v = 1,67 = 86,228 kN > Va = 65 kN (o.k.)
v

Va
= 0,754
Vn

v

155 dari 282


CONTOH G.4 BALOK PROFIL PSB PERSEGI PANJANG YANG MENGALAMI GESER

Periksa kekuatan geser balok profil PSB persegi panjang 180x100x8 yang menahan gaya
geser sebesar 50 kN akibat beban mati dan 150 kN akibat beban hidup. Material baja Fy =
250 MPa. Orientasi profil balok agar gaya geser sejajar sisi yang lebih panjang.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

Gaya geser: VD = 50 kN VL = 150 kN

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan geser desain minimum:

Metode DFBK: Vu = 1,2 VD + 1,6 VL = 300 kN

Metode DKI: Va = VD + VL = 200 kN

Data profil PSB 180x100x8: (Gunakan Tabel Profil PSB)

H = 180 mm B = 100 mm tw = 8 mm

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G5,
koefisien tekuk geser pelat badan: kv = 5

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G5, jika
radius tidak diketahui, h diambil sebesar tinggi total profil dikurangi tiga kali tebal profil.

h = H 3 tw = 156 mm

Berdasarkan SNI 1729 Pasal G2.1(b), koefisien geser badan:

h kv E
= 19,5 < 1,10 = 69,57
tw Fy

sehingga Cv = 1,0

Menghitung Aw

Aw = 2 h tw = 2496 mm2

Menghitung Vn

Vn = 0,6 Fy Aw Cv = 374,4 kN

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G2.1,
kekuatan geser desain:

156 dari 282


Metode DFBK:

v = 0,90 Vn = v Vn = 336,96 kN > Vu = 300 kN (o.k.)

Vu
= 0,89
V n

Metode DKI:

Vn
v = 1,67 = 224,192 kN > Va = 200 kN (o.k.)
v

Va
= 0,892
Vn

v

157 dari 282


CONTOH G.5 BALOK PROFIL PIPA YANG MENGALAMI GESER

Periksa kekuatan geser balok profil pipa dengan diameter luar 355,6 mm. Panjang balok
tersebut 10 meter dan direncanakan menahan gaya geser sebesar 130 kN akibat beban
mati dan 400 kN akibat beban hidup. Material baja Fy = 250 MPa.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

Gaya geser: VD = 120 kN VL = 250 kN

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan geser desain minimum:

Metode DFBK: Vu = 1,2 VD + 1,6 VL = 544 kN

Metode DKI: Va = VD + VL = 370 kN

Data profil pipa:

D = 355,6 mm t = 8 mm

Setengah panjang bentang: Lv = 5 m

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G6, Fcr
adalah nilai terbesar dari Fcr1 dan Fcr2 di bawah ini:

1,60E
Fcr1 = 5
= 743,543 MPa
Lv D 4

Dt

0,78E
Fcr2 = 3
= 526,401 MPa
D 2

t

Fcr = max(Fcr1 , Fcr2) = 743,543 MPa

dan dibatasi 0,6 Fy = 150 MPa (menentukan)

sehingga Fcr = 0,6 Fy = 150 MPa

Menghitung Ag

2
D - D - 2t = 8736,141 mm2
2
Ag =
4

158 dari 282


Menghitung Vn berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
Pasal G6

Fcr Ag
Vn = = 655,211 kN
2

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G2.1,
kekuatan geser desain:

Metode DFBK:

v = 0,90 Vn = v Vn = 589,69 kN > Vu = 544 kN (o.k.)

Vu
= 0,923
V n

Metode DKI:

Vn
v = 1,67 = 392,342 kN > Va = 370 kN (o.k.)
v

Va
= 0,943
Vn

v

159 dari 282


CONTOH G.6 BALOK PROFIL SIMETRI GANDA YANG MENGALAMI GESER
TERHADAP SUMBU LEMAH

Periksa kekuatan geser balok profil WF 400x200x8x13 yang menahan gaya geser sebesar
80kN akibat beban mati dan 240 kN akibat beban hidup. Material baja Fy = 250 MPa.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

Gaya geser: VD = 80 kN VL = 240 kN

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan geser desain minimum:

Metode DFBK: Vu = 1,2 VD + 1,6 VL = 480 kN

Metode DKI: Va = VD + VL = 320 kN

Data profil WF 400x200x8x13: (Gunakan Tabel Profil WF)

d = 400 mm bf = 200 mm tw = 8 mm tf = 13 mm r = 16 mm

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G7, untuk
geser terhadap sumbu lemah, gunakan Persamaan G2-1 dan ketentuan di SNI 1729 Pasal
G2.1(b) dengan Aw = bf tf untuk masing-masing sayap.

Koefisien tekuk geser: kv = 1,2

bf
Lebar tiap sisi sayap: b= = 100 mm
2

b kv E
= 7,692 < 1,10 = 34,082
tf Fy

sehingga Cv = 1,0

Menghitung Aw

Aw = 2 bf tf = 5 200 mm2

Menghitung Vn

Vn = 0,6 Fy Aw Cv = 780 kN

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G2.1,
kekuatan geser desain:

Metode DFBK:

v = 0,90 Vn = v Vn = 702 kN > Vu = 480 kN (o.k.)

160 dari 282


Vu
= 0,684
V n

Metode DKI:
Vn
v = 1,67 = 467,066 kN > Va = 320 kN (o.k.)
v

Va
= 0,685
Vn

v

161 dari 282


G7. GESER SUMBU LEMAH PADA PROFIL SIMETRIS GANDA DAN TUNGGAL

Desain kekuatan geser sumbu lemah, lihat Contoh G.6 dan Contoh G.7.

CONTOH G.7 BALOK PROFIL SIMETRI TUNGGAL YANG MENGALAMI GESER


TERHADAP SUMBU LEMAH

Periksa kekuatan geser balok profil C380x100x10.5x16 yang menahan gaya geser sebesar
60kN akibat beban mati dan 180 kN akibat beban hidup. Material baja Fy = 250 MPa.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

Gaya geser: VD = 60 kN VL = 180 kN

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan geser desain minimum:

Metode DFBK: Vu = 1,2 VD + 1,6 VL = 360 kN

Metode ASD: Va = VD + VL = 240 kN

Data profil C380x100x10.5x16: (Gunakan Tabel Profil Kanal)

d = 380 mm bf = 100 mm tw = 10,5 mm tf = 16 mm

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G7, untuk
geser terhadap sumbu lemah, gunakan SNI 1729 Persamaan G2-1 dan ketentuan SNI 1729
Pasal G2.1(b) dengan Aw = bf tf untuk masing-masing sayap.

Koefisien tekuk geser: kv = 1,2

bf kv E
= 6,25 < 1,10 = 34,082
tf Fy

sehingga Cv = 1,0

Menghitung Aw

Aw = 2 bf tf = 3 200 mm2

Menghitung Vn

Vn = 0,6 Fy Aw Cv = 480 kN

162 dari 282


Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G2.1,
kekuatan geser desain:

Metode DFBK:

v = 0,90 Vn = v Vn = 432 kN > Vu = 360 kN (o.k.)

Vu
= 0,833
V n

Metode DKI:

Vn
v = 1,67 = 287,425 kN > Va = 240 kN (o.k.)
v

Va
= 0,835
Vn

v

163 dari 282


CONTOH G.8 BALOK PROFIL TERSUSUN DENGAN PENGAKU TRANSVERSAL

Balok profil I tersusun dari material baja Fy = 250 MPa dengan panjang bentang 15 meter
dibebani secara terdistribusi sebesar 12 kN/m (beban mati) dan 36 kN/m (beban hidup).
Tinggi penampang balok 900 mm dengan lebar sayap 300 mm. Tebal badan 8 mm dan
tebal sayap 36 mm. Periksa apakah balok tersebut cukup kuat terhadap gaya geser di ujung
balok, dengan dan tanpa aksi medan tarik. Gunakan pengaku transversal jika diperlukan.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

Data profil tersusun:

d = 900 mm bft = 300 mm bfc = 300 mm tw = 8 mm tf = 36 mm

h = d 2 tf = 828 mm

kN kN
Beban terbagi rata: wD = 12 wL = 36
m m

Panjang bentang: L = 16 m

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

Metode DFBK: Vu =
1,2w D +1,6w L L = 576 kN
2
Metode DKI: Va =
w D +w L L = 384 kN
2

Pemeriksaan kebutuhan pengaku:

Aw = d tw = 7 200 mm2

164 dari 282


h
= 103,5 < 260 sehingga kv = 5 untuk badan tanpa pengaku transversal
tw
kv E
> 1,37 = 86,646
Fy

sehingga Cv dihitung berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja
struktural Persamaan G2-5:

1,51k v E
Cv = 2
= 0,564
h
Fy
tw

menghitung Vn

Vn = 0,6 Fy Aw Cv = 608,948 kN

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G2.1,
kekuatan geser desain:

Metode DFBK:

v = 0,90 Vn = v Vn = 548,053 kN < Vu = 576 kN

Vu
= 1,051
V n
(perlu pengaku transversal)

Metode DKI:

Vn
v = 1,67 = 364,639 kN < Va = 384 kN
v
Va
= 1,053
Vn

v
(perlu pengaku transversal)

Gunakan pengaku transversal pada setiap jarak: a = 1,6 m

Batasan penggunaan aksi medan tarik

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G3.1, aksi
medan tarik tidak boleh diperhitungkan jika terdapat minimal salah satu kondisi di bawah ini:

(a) panel ujung pada elemen dengan pengaku transversal

(b) elemen dengan a/h lebih besar dari 3,0 atau [260/(h/tw)]2

(c) 2Aw/(Afc + Aft) > 2,5

165 dari 282


(d) h/bfc atau h/bft > 6,0

Syarat (b):
2


a 260 = 6,311
= 1,932 <
h h

tw

Syarat (c):

Afc = bfc tf = 10 800 mm2 Aft = bft tf = 10 800 mm2

2A w
= 0,667 < 2,5
A fc + A ft

Syarat (d):

h h
= 2,76 < 6,0 = 2,76 < 6,0
b fc b ft

Persyaratan (b), (c) dan (d) terpenuhi, aksi medan tarik dapat diperhitungkan kecuali untuk
panel ujung.

Kekuatan geser panel ujung

Tentukan kv berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
Pasal G2.1(b) dan periksa batasan a/h

a
= 1,932 < 3,0
h
2


260
< = 6,311
h

tw
sehingga

5
kv = 5 + = 6,339
a
2

Aksi medan tarik tidak boleh diperhitungkan pada panel ujung karena

h kv E
= 103,5 > 1,37 = 97,561
tw Fy

166 dari 282


1,51 k v E
Cv = 2
= 0,715
h
Fy
tw

Vn = 0,6 Fy Aw Cv = 772,028 kN

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G2.1,
kekuatan geser desain:

Metode DFBK:

v = 0,90 Vn = v Vn = 694,825 kN > Vu = 576 kN (o.k.)

Vu
= 0,829 < 1,00 (o.k.)
V n

Metode DKI:

Vn
v = 1,67 = 462,292 kN > Va = 384 kN (o.k.)
v

Va
= 0,831 < 1,00 (o.k.)
Vn

v

Kekuatan geser panel kedua

Kekuatan geser perlu pada panel kedua:

Metode DFBK: Vu =
1,2w D +1,6w L L (1,2 wD + 1,6 wL) a = 460,8 kN
2

Metode DKI: Va =
w D +w L L (wD + wL) a = 307,2 kN
2

Tentukan kv berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
a
Pasal G2.1(b) dan periksa batasan
h

167 dari 282


a
= 1,932 < 3,0
h
2


260
< = 6,311
h

tw

sehingga

5
kv = 5 + = 6,339
a
2

Aksi medan tarik tidak boleh diperhitungkan pada panel ujung

h kv E
karena = 103,5 > 1,37 = 97,561
tw Fy

1,51k v E
Cv = 2
= 0,715
h
Fy
tw

Periksa batasan tambahan dari SNI 1729, Spesifikasi untuk bangunan gedung baja
struktural Pasal G3.1 untuk aksi medan tarik

2A w
= 0,667 2,5
A fc + A ft

h h
= 2,76 6,0 = 2,76 6,0
b ft b fc

Panel tersebut bukan panel ujung dan semua kondisi memenuhi syarat untuk perhitungan
aksi medan tarik.

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G3.2

kv E
1,10 = 78,334
Fy

h
karena = 103,5 > 76 gunakan persamaan G3-2
tw

168 dari 282




1 Cv
Vn = 0,6 Fy Aw Cv = 895,111 kN
2
a
1,15 1-
h

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal G2.1,
kekuatan geser desain:

Metode DFBK:

v = 0,90 Vn = v Vn = 805,6 kN < Vu = 460,8 kN

Vu
= 0,572
V n

Metode DKI:

Vn
v = 1,67 = 535,994 kN < Va = 307,2 kN
v

Va
= 0,573
Vn

v

169 dari 282


Bab H Desain Komponen Struktur untuk Kombinasi Gaya-gaya dan Torsi

Untuk semua persamaan interaksi dalam SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural Bab H, gaya dan momen yang diperlukan harus mencakup efek orde kedua,
seperti yang disyaratkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Bab
C. Pengguna DKI, SNI 1729, Spesifikasi untuk bangunan gedung baja struktural 1989
terbiasa menggunakan persamaan interaksi yang mencakup amplifikasi orde kedua parsial.
Efek orde kedua yang sekarang dihitung dalam analisis dan tidak termasuk dalam
persamaan interaksi.

170 dari 282


CONTOH H.1

Periksa kekuatan suatu balok-kolom profil WF 350x175x7x11 yang menerima beban aksial
tarik PD = 30 kN dan PL = 40 kN. Panjang tak terbreis adalah 9 m dan kedua ujung adalah
sendi, dengan sambungan tanpa lubang. Batang ini juga memiliki momen akibat beban
terdistribusi merata.

MxD = 34 kN m PD = 30 kN PL = 40 kN

MxL = 20 kN m Lb = 6 m

MyD = 5 kN m

MyL = 8 kN m

Pasal 2 kekuatan perlu dari SNI 1727, Beban minimum untuk perancangan bangunan
gedung dan struktur lain sebagai berikut:

DFBK DKI

Pu = 1,2 PD + 1,6 PL = 100 kN Pa = PD + PL = 70 kN

Mux = 1,2 MxD + 1,6 MxL = 72,8 kN m Max = MxD + MxL = 54 kN m

Muy = 1,2 MyD + 1,6 MyL = 18,8 kN m May = MyD + MyL = 13 kN m

Data penampang WF 350 x 175 x 7 x 11

E
E = 200 000 MPa G= = 7,692 x 104 MPa Fy = 250 MPa
2,6

Ix = 1,36 x 108 mm4 Iy = 9,84 x 106 mm4 Ag = 6,314 x 103 mm2

d = 350 mm tw = 7 mm bf = 175 mm tf = 11 mm r = 14 mm

Besaran penampang yang perlu dihitung: ho = d - tf = 339 mm

I y ho2
CW = = 2,827 x 1011 mm6 h = d - 2 tf - 2 r = 300 mm
4

Ix Iy
Sx = = 7,771 x 105 mm3 Sy = = 1,125 x 105 mm3
0,5 d 0,5 bf
1
Z x = bf t f d - t f + tw d - 2t f
2
= 8,408 x 105 mm3
4

2 1
Z y = t f bf2 + d - 2t f tw2 = 1,725 x 105 mm3
4 4

2bf t f3 + d - t f tw3
J= = 1,94 x 105 mm4
3

171 dari 282


Ix Iy
rx = = 146,763 mm ry = = 39,477 mm
Ag Ag

I y CW E
rts = Lp =1,76r y = 1,965 m
Sx Fy

0,78 Fy S x ho
2
E J
Lr =1,95 rts 1+ 1+ 6,76 = 5,999 m
0,7 Fy S x ho E J

Solusi:

Kekuatan Tarik Nominal

Dari SNI 1729 Pasal D2(a), kekuatan tarik nominal akibat kelelehan tarik pada penampang
bruto adalah:

Pn = Fy Ag = 1,578 x 103 kN SNI 1729 Persamaan D2-1

Catat bahwa untuk batang dengan lubang, kuat rupture dari batang juga harus dihitung
dengan menggunakan SNI 1729 Persamaan D2-2

Kekuatan Lentur Nominal untuk lentur terhadap sumbu X-X

Kelelehan

Mpx = Fy Zx = 210,212 kN m

Mnx1 = Mpx SNI 1729 Persamaan F2-1

Tekuk Torsional-Lateral

Dari SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal F2.2, kuat lentur
nominal akibat tekuk torsional-lentur dihitung sebagai berikut:

Karena Lp < Lb < Lr , maka berlaku SNI 1729 Persamaan F2-2

Cb = 1,14 untuk pembebanan merata, tanpa mempertimbangkan efek dari gaya


tarik.

Walaupun demikian, menurut SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
Pasal H1.2, Cb bisa diperbesar karena kolom mengalami gaya tarik

2EI y Pu
Pey = 2 = 539,538 kN DFBK = 1,0 1+ = 1,089
Lb Pey

Pa
DKI = 1,6 1+ = 1,099
Pey

172 dari 282


Pu
Cb = Cb 1+ = 1,298
Pey

Lb - Lp
M nx 2 = Cb M px - M px - 0,7Fy S x = 176,516 kN m Persamaan F2-2
L -L
r p

Jadi M nx = min M nx 1,M nx 2 = 176,516 kN m

Tekuk Lokal

Sayap

bf b E
b= t = tf = 7,955 p = 0,38 = 10,748
2 t Fy

Jadi sayap kompak

Badan

h E
= 42,857 p = 3,76 = 106,349
tw Fy

Jadi badan juga kompak

Berarti tekuk lokal tidak menjadi masalah di profil ini

Kekuatan lentur nominal terhadap sumbu y-y

Karena sayap kompak, maka kondisi batas kelelehan yang menentukan

M ny = min Fy Z y ,1.6Fy S y = 43,114 kN m SNI 1729 Persamaan F6-1

Kekuatan yang tersedia:

Dari SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal D2 dan F1:

DFBK

b = 0,9 t = 0,9

Pc = t Pn M cx = b M nx M cy = b M ny

Pu
= 0,07 < dari 0,2, maka digunakan SNI 1729 Persamaan H1-1b
Pc

173 dari 282


Pu M ux M uy
rasio = + = 0,978 < 1 (memenuhi)
2Pc M cx M cy

DKI

t = 1,67 b = 1,67

Pn M nx M ny
Pc M cx M cy
t b b

Pa
= 0,074 < 0,2, harus menggunaan SNI 1729 Persamaan H1-1b
Pc

Pa M ax M ay
rasio = + = 1,051 > 1 (tidak memenuhi)
2Pc M cx M cy

174 dari 282


CONTOH H.2.

Periksa kekuatan suatu balok-kolom profil WF 350x175x7x11 yang menerima beban aksial
PD = 23 kN dan PL= 70 kN. Panjang tak terbreis adalah 4 m dan kedua ujung adalah sendi.
Batang ini juga memiliki momen akibat beban terdistribusi merata, belum memperhitungkan
efek P-:

MxD = 10 kN m MxL = 7,5 kN m Lb = 4 m Lx = 4 m Ly = Lx

MyD = 7,5 kN m MyL = 8 kN m Lz = Lb

Sistim balok-kolom ini tidak bisa bergoyang

Data penampang WF 350 x 175 x 7 x 11

E
E = 200 000 MPa G= = 7,692 x 104 MPa Fy = 250 MPa
2,6

Ix = 1,36 x 108 mm4 Iy = 9,84 x 106 mm4 Ag = 6,314 x 103 mm2

d = 350 mm tw = 7 mm bf = 175 mm tf = 11 mm r = 14 mm

Besaran penampang yang perlu dihitung: ho = d - tf = 339 mm

I y ho2
CW = = 2,827 x 1011 mm6 h = d - 2 tf - 2 r = 300 mm
4

Ix
Sx = = 7,771 x 105 mm3
0,5d

Iy
Sy = = 1,125 x 105 mm3
0,5bf

1
Z x = bf t f d - t f + tw d - 2t f
2
= 8,408 x 105 mm3
4

2 1
Z y = t f bf2 + d - 2t f tw2 = 1,725 x 105 mm3
4 4

2bf t f3 + d - t f tw3
J= = 1,94 x 105 mm4
3

Ix Iy
rx = = 146,763 mm ry = = 39,477 mm
Ag Ag

I y CW E
rts = Lp =1,76r y = 1,965 m
Sx Fy

175 dari 282


0,78 Fy S x ho
2
E J
Lr =1,95 rts 1+ 1+ 6,76 = 5,999 m
0,7 Fy S x ho E J

Momen plastis

Mpx = Zx Fy Mpx = 210,212 kN m

Mpy = Zy Fy Mpy = 43,114 kN m

Solusi:

PD = 23 kN PL = 70 kN Pr = 1,2 PD + 1,6 PL = 139,6 kN

Kekuatan lentur perlu ( termasuk amplifikasi orde kedua)

Gunakan metode pendekatan prosedur analisis orde kedua dari SNI 1729 Apendik 8.
Karena batang tidak bergoyang, amplifikasi yang diperlukan hanya P-

Cm = 1 K1 = 1,0

Amplifikasi lentur terhadap sumbu x-x

2EI x
Pe 1x = = 16778,3275 kN = 1,0 karena DFBK
K 1Lx
2


C
B1x = max m
,1.0 = 1,008
1- Pr
P
e 1x

Momen orde kedua

M rx = B1x 1,2M xD +1,6M xL = 24,201 kN m

Amplifikasi lentur terhadap sumbu y-y

2EI y
Pe 1y = = 1213,9613 kN = 1,0 karena DFBK
K L
2
1 y



Cm
B1y = max ,1.0 = 1,13
1- Pr
P
e 1y

176 dari 282


Momen orde kedua

M ry = B1y 1,2M xD +1,6M xL = 27,119 kN m

Kekuatan Lentur nominal terhadap sumbu x-x

Kelelehan

Mnx1 = Mpx = 210,212 kN m Persamaan F2-1 SNI 1729, Spesifikasi untuk bangunan
gedung baja struktural

Tekuk Torsional-Lateral

Karena Lp < Lb < Lr , maka berlaku SNI 1729, Spesifikasi untuk bangunan gedung baja
struktural Persamaan F2-2

Cb = 1,14 pembebanan merata

Lb - Lp
M nx 2 = Cb M px - M px - 0,7Fy S x = 196,966 kN m Persamaan F2-2 SNI
L -L
r p
1729, Spesifikasi untuk bangunan gedung baja struktural

Jadi M nx = min M nx 1,M nx 2 = 196,966 kN m

Tekuk Lokal

Sayap

bf b E
b= t = tf = 7,955 p = 0,38 = 10,748
2 t Fy

jadi sayap kompak

badan

h E
= 42,857 p = 3,76 = 106,349
tw Fy

Jadi badan juga kompak

Berarti tekuk lokal tidak menjadi masalah di profil ini

Kekuatan lentur nominal terhadap sumbu y-y

Karena sayap kompak, maka kondisi batas kelelehan yang menentukan

M ny = min Fy Z y ,1.6Fy S y = 43,114 kN m

177 dari 282


Kekuatan Tekan Nominal

Tegangan tekuk lentur

Tekuk lokal

Sayap

b E
= 7,955 r = 0,56 = 15,839 Qs = 1,0
t Fy

Badan

h E
= 42,857 r =1,49 = 42,144
tw Fy

Perlu menghitung Qa

K 1 Ly K 1 Lx
= 101,325 = 27,255
ry rx

2E
Fe = 2
= 192,265 MPa
K 1Ly

ry

Anggap

iterasi ke-1

Qa = 1 Q1 = Qs Qa 0,44 Q1 Fy = 110 MPa < Fe

Q1 Fy

f = 0,658 Fe F y Q1 = 145,071 MPa



E 0,34 E
be = min h, 1,92 tw 1- = 268,165 mm
Fy h f

tw

Ae = Ag (h - be) tw = 6,091 x 103 mm2

Ae
Qa 1 = = 0,965
Ag

178 dari 282


iterasi ke-2

Q2 = Qs Qa1 = 0,965 0,44 Q2 Fy = 106,118 MPa < Fe

Q2 Fy

f = 0,658 Fe Fy Q 2 = 142,665 MPa




E 0,34 E = 267,225 mm
be = min h, 1,92 tw 1-
Fy h f

tw

Ae = Ag (h be) tw = 6,085 x 103 mm2

Ae
Qa 2 = = 0,964
Ag

iterasi ke-3

Q3 = Qs Qa2 = 0,964 0,44 Q3 Fy = 106,003 MPa < Fe

Q3 F y

f = 0,658 Fe F y Q3 = 142,592 MPa



E 0,34 E
be = min h, 1,92 tw 1- = 267,196 mm
Fy h f

tw

Ae = Ag (h be) tw = 6,084 x 103 mm2

Ae
Qa 3 = = 0,964 sudah konvergen
Ag

Jadi Q = Qs Qa3 = 0,964

Q Fy

Fcr 1 = 0,658 Fe Fy Q = 142,59 MPa


Tegangan Tekuk Torsi

2 E Cw 1
Fe 2 = +G J
k Lz
2
I x +I y

179 dari 282


Q Fy

Fcr 2 = 0,658 Fe 2 Fy Q = 179,316 MPa

Fcr = min(Fcr1,Fcr2) = 142,59 MPa

c = 0,9 Pn = Fcr Ag = 900,311 kN

Kontrol dengan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Persamaan
H1-1a dan H1-1b: b = 0,9

DFBK

Kapasitas

Pc = c Pn Mcx = b Mnx Mcy = b Mny

Pr
= 0,172 < dari 0,2, maka digunakan SNI 1729 Persamaan H1-1b
Pc

Pr M rx M ry
rasio = + + = 0,922
2Pc M cx M cy

DKI

Pr = PD + PL = 93 kN c = 1,5 b = 1,67

Max = MxD + MxL = 17,5 kN m

May = MyD + MyL = 15,5 kN m

= 1,6


C
Cm
B1x = max m
,1.0 = 1,009 B1y = min ,1.0 = 1
1- Pr 1- Pr
P P
e 1x e 1y

Momen orde kedua

Mrx = B1x Max = 17,657 kN m Mry = B1y May = 15,5 kN m

Kapasitas

Pn M nx M ny
Pc = M cx = M cy =
c b b

180 dari 282


Pr
= 0,155 < 0,2, harus menggunaan SNI 1729 Persamaan H1-1b
Pc

Pr M rx M ry
rasio = + + = 0,828
2Pc M cx M cy

CONTOH H.3 a. KEKUATAN TORSIONAL PENAMPANG PSB

Hitunglah kekuatan torsional yang tersedia dari penampang PSB 200 x 200 x 12

Solusi

E = 200 000 MPa Fy = 250 MPa Fu = 410 MPa

h = 200 mm b = 200 mm t = 12 mm

C = 2 (b - t) (h - t) t 4,5 (4 - ) t3 = 8,416 x 105 mm3


Menghitung Tegangan Kritis, Fcr

h E
= 16,667 < 2,45 = 69,296
t Fy

maka digunakan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Persamaan
H3-3

Fcr = 0,6Fy = 150 MPa SNI 1729 Persamaan H3-3

Kekuatan Torsional Nominal

Tn = Fcr C = 126,237 kN m SNI 1729 Persamaan H3-1

Dari SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal H3.1, kekuatan
torsional yang tersedia:

DFBK DKI

t = 0,9 t = 1,67
Tn
t Tn = 113,613 kN m = 75,591 kN m
t

Catatan:
Untuk memperoleh petunjuk lebih lengkap tentang desain terhadap torsi, lihat AISC Design Guide 9,
Torsional Analysis of Structural Steel Members (Seaburg and Carter, 1997)

181 dari 282


CONTOH H.3 b. KEKUATAN TORSIONAL PENAMPANG PIPA

Hitunglah kekuatan torsional yang tersedia dari penampang PIPA D10 ASTM A500 Grade B
dengan panjang 6 m

Solusi

E = 200 000 MPa Fy = 290 MPa Fu = 400 MPa

D = 267,4 mm t = 9,3 mm L=6m

D - t t
2

C= = 9,731 x 105 mm3


2

Menghitung Tegangan Kritis, Fcr

Maka digunakan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Persamaan
H3-2a dan H3-2b

diambil terbesar antara

0,6E
Fcr = 3
= 778,33 MPa
D 2

t
dan
1,23E
Fcr = 5
= 779,996 MPa
L D 4

Dt

Tetapi tidak boleh lebih besar dari

Fcr = 0,6 Fy = 174 MPa

Kekuatan Torsional Nominal

Tn = Fcr C = 169,328 kN m SNI 1729 Persamaan H3-1

Dari SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal H3.1, kekuatan
torsional yang tersedia adalah

DFBK DKI

t = 0,9 t = 1,67

Tn
t Tn = 152,395 kN m = 101,394 kN m
t

Catatan :
Untuk memperoleh petunjuk lebih lengkap tentang desain terhadap torsi, lihat AISC Design Guide 9,
Torsional Analysis of Structural Steel Members (Seaburg and Carter, 1997)

182 dari 282


CONTOH H.3 c. KOMBINASI KEKUATAN LENTUR DAN TORSIONAL PENAMPANG
PSB

Periksa kekuatan penampang PSB ASTM A500 Grade B yang dibebani seperti tergambar.
Balok diatas dua tumpuan sederhana dan kedua ujungnya bersifat jepit terhadap torsi.
Lentur terhadap sumbu kuatnya.

kN kN
WD = 40 WL = 50 kerja kedua beban ofset 150 mm terhadap sumbu balok
m m

L = 2,5 m e = 250 mm eksentrisitas beban terhadap sumbu memanjang balok

Solusi

E = 200 000 MPa Fy = 290 MPa Fu = 400 MPa

PSB 250x250x9

h = 250 mm b = 250 mm t = 9 mm Zx = 7,845 x 105 mm3

DFBK DKI

wu = 1,2 x wD + 1,6 x wL wa = wD + wL

kN kN
wu = 128 wa = 90
m m

Menghitung gaya geser maksimum di tumpuan

wu L wa L
Vr = Vra =
2 2

Vr = 160 kN Vra = 112,5 kN

Menghitung torsi maksimum di tumpuan

wu L e wa L e
Tr = Tra =
2 2

Tr = 40 kN m Tra = 28,125 kN m

183 dari 282


Kekuatan geser yang tersedia

Menghitung kekuatan geser yang tersedia berdasarkan SNI 1729, Spesifikasi untuk
bangunan gedung baja struktural Pasal G5

h = h - 3 t = 223 mm

Aw = 2 h t = 4,014 x 103 mm2

kv = 5

Koefisien geser badan profil dihitung dari SNI 1729 Pasal G2.1(b)

h kv E
= 24,778 < 1,18 = 69,292 maka Cv = 1 (Persamaan G2-3 SNI 1729)
t Fy

Kekuatan geser nominal SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal
G2.1:

Vn = 0,6 Fy Aw Cv = 698,436 kN (Persamaan G2-1 SNI 1729)

Dari SNI 1729 Pasal G1, kekuatan geser yang tersedia adalah

DFBK DKI

v = 0,9 t = 1,67

Vn
Vc = v Vn = 628,592 kN Vca = = 418,225 kN
v

Kekuatan Lentur yang tersedia

Kekuatan lentur yang tersedia dihitung dari SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural Pasal F7 untuk PSB.

Untuk kondisi batas dari lentur leleh, kuat lentur nominal:

Mn = Fy Zx = 227,505 kN m

Hitung apakah kondisi batas tekuk lokal sayap terjadi,

b
f = 27,778
t

Hitung batas kelangsingan kompak sayap dari SNI 1729 Tabel B4.1b Kasus 17

E
p =1,12 = 29,413
Fy

f p ; sayap kompak dan tekuk lokal sayap tidak terjadi

184 dari 282


Hitung apakah tekuk lokal badan terjadi
h
w = 24,778
t

Hitung batas kelangsingan kompak badan dari SNI 1729, Spesifikasi untuk bangunan
gedung baja struktural Tabel B4.1b Kasus 19

E
p = 2,42 = 63,552
Fy

w p ; badan kompak dan tekuk lokal badan tidak terjadi

Karena itu, Mn , ditentukan oleh kondisi batas kelelehan lentur

Mn = 227,505 kN m

Dari SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal F1, Kekuatan
Lentur yang tersedia

DFBK DKI

b = 0,9 b = 1,67

Mn
M c = b M n M ca =
b

Mc = 204,755 kN m Mca = 136,231 kN m

Kekuatan Torsi yang tersedia

C = 2 (b - t) (h - t) t 4,5 (4 - ) t3 = 9,255 x 105 mm3


Menghitung Tegangan Kritis, Fcr

h E
= 24,778 < 2,45 = 64,34
t Fy

maka digunakan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Persamaan
H3-3

Fcr = 0,6 Fy = 174 MPa SNI 1729 Persamaan H3-3

Kekuatan Torsional Nominal adalah

Tn = Fcr C = 161,04 kN m SNI 1729 Persamaan H3-1

185 dari 282


Dari SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal H3.1, kekuatan
torsional yang tersedia:
DFBK DKI

T = 0,9 T = 1,67
Tn
Tc = TTn Tca =
T
Tc = 144,936 kN m Tca = 96,431 kN m

Dengan menggunakan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal
H3.2, Kontrol Kekuatan kombinasi pada beberapa lokasi dimana Tu > 0,2 Tc

Kontrol di tumpuan, lokasi geser dan torsi maksimum

DFBK

Tr
= 0,276 > 0,2 di tumpuan Mr = 0 kN m
Tc

Oleh karena itu, gunakan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
Persamaan H3-6

2 2
P M V T V T
rasio = r + r + r + r rasio = (0 + 0) + r + r = 0,281 < 1,0
Pc Mc Vc Tc Vc Tc

DKI

Tra
= 0,292 > 0,2 di tumpuan Mr = 0 kN m
Tca

Oleh karena itu, gunakan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
Persamaan H3-6

2
P M V T
rasio = ra + ra + ra + ra
Pca Mca Vca Tca
2
V T
rasio = (0 + 0) + ra + ra = 0,314 < 1,0
Vca Tca

Kontrol di lokasi dimana Tr = 0,2 Tc. Ini adalah lokasi dengan momen lentur terbesar yang
harus dipertimbangkan dalam masalah interaksi.

Hitung gaya geser dan momen pada lokasi ini, x

DFBK

Tr - 0,2Tc
x= = 0,344 m
wu e

186 dari 282


Tr = 0,2 Tc
Vr = Vr x wu = 115,949 kN

-Wu x 2
Mr = +Vr x = 32,324 kN m
2
2
M V T
rasio = 0 + r + r + r = 0,306 < 1,0 (o.k.)
Mc Vc Tc

DKI

Tra - 0,2Tca
x= = 0,393 m
wa e

Tra = 0,2 Tca

Vra = Vra x wa = 77,145 kN

-Wa x 2
M ra = +Vra x = 23,361 kN m
2
2
M V T
rasio = 0 + ra + ra + ra = 0,319 < 1,0 (o.k.)
Mca Vca Tca

Catatan:
Di lokasi lain di balok, dimana Tr < Tc, juga harus di cek untuk menentukan apakah kekuatan tanpa
torsi lebih menentukan dibandingkan dengan interaksi puntir.

187 dari 282


Bab I Desain Komponen Struktur Komposit

I1. KETENTUAN UMUM

Desain, pendetailan, dan properti material yang terkait dengan beton dan tulangan baja
bagian-bagian dari komponen struktur komposit diatur oleh ACI 318 seperti dimodifikasi
dengan ketentuan khusus komposit oleh SNI 1729, Spesifikasi untuk bangunan gedung baja
struktural.

Kekuatan yang tersedia dari penampang komposit dapat dihitung dengan salah satu dari
dua metode; metode distribusi tegangan plastis, atau metode regangan-kompatibilitas.

Penampang komposit terisi beton diklasifikasikan untuk tekuk lokal yang sesuai dengan
kelangsingan elemen baja yang mengalami tekan seperti digambarkan dalam Tabel I1.1 SNI
1729, Spesifikasi untuk bangunan gedung baja struktural dan Contoh I.2, I.4 dan I.5. Efek
tekuk lokal tidak perlu dipertimbangkan untuk komponen struktur komposit terbungkus
beton.

Terminologi yang digunakan dalam Contoh-contoh untuk geometri penampang komposit


terisi beton diilustrasikan dalam Gambar I-2.

I2. GAYA AKSIAL

Kekuatan tekan yang tersedia dari komponen struktur komposit didasarkan pada
penjumlahan kekuatan-kekuatan dari semua komponen kolom dengan reduksi yang
diterapkan untuk kelangsingan komponen struktur dan efek tekuk lokal di mana berlaku.

Untuk komponen struktur yang mengalami tarik, kekuatan tarik beton diabaikan dan hanya
kekuatan komponen struktur baja dan tulangan yang tersambung dengan benar yang
diperbolehkan untuk digunakan dalam perhitungan kekuatan tarik yang tersedia.

Desain dari komponen struktur tekan komposit terisi beton dan komponen struktur tarik
disajikan dalam Contoh I.2 dan I.3.

Desain dari komponen struktur tekan komposit terbungkus beton dan komponen struktur
tarik disajikan dalam Contoh I.6 dan I.7.

Perhatikan bahwa SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
menyatakan bahwa kekuatan tekan yang tersedia tidak perlu kurang dari yang ditetapkan
untuk komponen struktur baja tanpa beton.

I3. LENTUR

Desain balok komposit tipikal dengan angkur baja digambarkan dalam Contoh I.1. Tabel 3-
20 menyediakan momen inersia batas terendah (lower-bound) untuk penampang komposit
plastis, dan Tabel 3-21 memberikan kekuatan geser angkur stud baja yang digunakan untuk
aksi komposit pada balok komposit.

Desain komponen struktur komposit terisi beton untuk lentur digambarkan dalam Contoh I.9
dan I.5, dan desain komponen struktur komposit terbungkus beton untuk lentur digambarkan
dalam Contoh I.8.

188 dari 282


I4. GESER

Untuk balok komposit dengan dek baja terbentuk, kekuatan geser yang tersedia didasarkan
pada properti penampang baja saja sesuai dengan Bab G SNI 1729, Spesifikasi untuk
bangunan gedung baja struktural seperti yang digambarkan dalam Contoh I.1.

Untuk komponen struktur komposit terisi beton dan terbungkus beton, baik kekuatan geser
dari penampang baja saja, penampang baja ditambah baja tulangan, atau beton bertulang
saja diizinkan untuk digunakan dalam perhitungan kekuatan geser yang tersedia.
Perhitungan kekuatan geser untuk komponen struktur komposit terisi beton digambarkan
dalam Contoh I.4 dan I.5 dan untuk komponen struktur komposit terbungkus beton dalam
Contoh I.8.

I5. KOMBINASI LENTUR DAN GAYA AKSIAL

Desain untuk kombinasi gaya aksial dan lentur dapat dicapai dengan menggunakan metode
kompatibilitas regangan atau metode distribusi plastis. Prosedur yang berbeda untuk
menggunakan metode distribusi plastis diuraikan dalam Penjelasan, dan masing-masing
prosedur ditunjukkan untuk komponen struktur terisi beton dalam Contoh I.2 dan untuk
komponen struktur terbungkus beton dalam Contoh I.8. Perhitungan interaksi untuk
komponen struktur terisi beton non-kompak dan langsing diilustrasikan dalam Contoh I.5.

Untuk membantu dalam mengembangkan kurva interaksi yang diilustrasikan dalam contoh
desain, rangkaian persamaan-persamaan disediakan dalam Gambar I-1. Persamaan-
persamaan ini mendefinisikan poin-poin terpilih pada kurva interaksi, tanpa
mempertimbangkan efek-efek kelangsingan. Gambar I-1a sampai I-1d menjelaskan kasus-
kasus tertentu, dan penerapan persamaan-persaman untuk penampang yang berbeda
harus dipertimbangkan dengan hati-hati. Sebagai sebuah contoh, persamaan-persamaan
dalam Gambar I-1a yang sesuai untuk kasus batang tulangan sisi yang terletak di tengah,
tetapi tidak untuk lokasi batang tulangan sisi lainnya. Sebaliknya, persamaan yang sesuai
untuk jumlah tulangan sembarang di lokasi batang tulangan ekstrim. Pada Gambar I-1b,
persamaan hanya cocok untuk kasus 4 batang tulangan di sudut-sudut penampang yang
terbungkus beton.

Bila kasus-kasus desain menyimpang dari yang disajikan persamaan interaksi yang tepat
dapat diturunkan dari prinsip-prinsip pertama. Ketika kasus desain menyimpang dari yang
disajikan persamaan interaksi yang tepat dapat diturunkan dari prinsip-prinsip pertama.
Ketika kasus desain menyimpang dari yang disajikan persamaan interaksi yang tepat dapat
diturunkan dari prinsip-prinsip pertama. Ketika kasus desain menyimpang dari yang disajikan
persamaan interaksi yang tepat dapat diturunkan dari prinsip-prinsip pertama. Ketika kasus
desain menyimpang dari yang disajikan persamaan interaksi yang tepat dapat diturunkan
dari prinsip-prinsip pertama.

I6. TRANSFER BEBAN

Spesifikasi untuk bangunan gedung baja struktural menyediakan beberapa persyaratan


untuk memastikan bahwa bagian-bagian beton dan baja dari penampang bekerja bersama-
sama. Persyaratan ini membahas alokasi gaya - berapa banyak beban yang diterapkan
yang ditahan oleh baja versus beton bertulang, dan mekanisme transfer gaya - bagaimana
gaya ditransfer antara dua material.

189 dari 282


I7. DIAFRAGMA KOMPOSIT DAN BALOK KOLEKTOR

Penjelasan ini memberikan panduan tentang metodologi desain untuk kedua diafragma
komposit dan balok kolektor komposit.

I8. ANGKUR BAJA

Pasal I8 SNI 1729, Spesifikasi untuk bangunan gedung baja struktural membahas kekuatan
angkur baja pada balok komposit dan pada komponen komposit. Contoh I.1
menggambarkan desain balok komposit dengan angkur stud berkepala baja.

Penerapan angkur baja dalam ketentuan komponen komposit memiliki batasan yang ketat
seperti yang dirangkum dalam Catatan diberikan pada awal Pasal I8.3 SNI 1729, Spesifikasi
untuk bangunan gedung baja struktural. Ketentuan ini tidak berlaku untuk desain balok
komposit tipikal, juga tidak berlaku untuk konstruksi hibrida di mana baja dan beton tidak
menahan beban bersama-sama melalui aksi komposit seperti di pelat yang tertanam.
Penerapan ketentuan-ketentuan ini untuk angkur terisolasi dalam suatu sistem komposit
yang berlaku yang digambarkan dalam Contoh I.9.

190 dari 282


KAPASITAS PLASTIS UNTUK PERSEGI
PANJANG, PROFIL W TERBUNGKUS
BETON MELENTUR DI SUMBU X-X

Penampang Distribusi Titik Definisi Persamaan


tegangan
PA = As Fy + Asr Fyr +0,85f c' Ac
MA = 0
A As = luas profil baja
Asr = luas seluruh batang tulangan menerus
Ac = h1h2 As- Asr

C
PC = 0,85f c' Ac
M C = MB
0,85f c' Ac
PD =
2
Zc
M D = Z s Fy + Z r Fyr +
2
0,85f
c
'

Zs = modulus penampang plastis sumbu x penuh dari profil baja


D Asrs = luas batang tulangan menerus pada centerline
h2
Z r = Asr - Asrs -c
2
h1h22
ZC = - Zs - Zr
4
PB = 0
1
M B = M D - Z sn Fy -
2

Z cn 0,85f c'
Z cn = h1hn2 - Z sn
d
Untuk hn di bawah sayap hn - tf
2
0,85f c Ac + Asrs - 2Fyr Asrs
'
hn
2 0,85f c' h1 - tw + 2Fy tw
Z cn = tw hn2
d d
Untuk hn di sayap - t f < hn
B 2 2
0,85f c Ac + As - dbf + Asrs - 2F y As dbf - 2F yr Asrs
'
hn =
2 0,85f c' h1 - bf + 2Fy bf
d d
Z sn = z s - bf - hn + hn
2 2
d
Untuk hn di bawah sayap hn >
2
0,85f c Ac + As + Asrs - 2F y As - 2F yr Asrs
'
hn =
2 0,85f c' h1
Zsn = Zsr = modulus penampang plastis sumbu x penuh dari
profil baja

191 dari 282


KAPASITAS PLASTIS UNTUK
PERSEGI PANJANG, PROFIL W TERBUNGKUS
BETON MELENTUR
DI SUMBU y-y
Penampang Distribusi Titik Definisi Persamaan
Tegangan
PA = As Fy + Asr Fyr +0,85f c' Ac
MA = 0
A As = luas profil baja
Asr = luas batang tulangan menerus
Ac = h1h2 As- Asr
h1 A
PE = As Fy + 0,85f c' Ac - h2 - bf + sr
2 2
M E = M D - Z sE Fy - 1/ 2 Z cE 0,85f c
'

E
ZsE = Zsy = modulus penampang plastis sumbu y penuh dari
profil baja
h1bf2
Z cE = - Z sE
4
C
PC = 0,85f c' Ac
MC = MB
0,85f c' Ac
PD =
2
Zc
M D = Z s Fy + Z r Fsy +
2
0,85f c
'

D Zs = modulus penampang plastis sumbu y full dari profil baja


h
Z r = Asr 2 - c
2
hh 2
ZC = 1 2 - Z s - Z r
4
PB = 0
1
M B = M D - Z sn Fy -
2

Z cn 0,85f c'
Z cn = h1hn2 - Z sn
tw b
Untuk hn di bawah sayap < hn f
2 2
0,85f c Ac + As - 2t f bf - 2F y As - 2t f bf
'

hn
2 4t f Fy + h1 - 2t f 0,85f
c
'
B
b b
Z sn = z s - 2t f f + hn f - hn
2 2
b
Untuk hn di bawah sayap hn > f
2
0,85f c Ac + As - 2Fy As
'
hn =
2 0,85f c' h1
Zsn = Zsy = modulus penampang plastis sumbu y full dari profil
baja

192 dari 282


KAPASITAS PLASTIS UNTUK
KOMPOSIT, PSB TERISI BETON
MELENTUR DI SUMBU X-X

Penampang Distribusi Titik Definisi Persamaan


Tegangan

PA = Fy As +0,85 f c' Ac
MA = 0
As = luas profil baja
A Ac bi hi - 0,85 ri 2
bi B - 2 t
hi H - 2 t
ri t
PE =1/ 2 0,85 f c' Ac +0,85 f c' bi hE + 4 Fy t hE
M E = M D - Fy Z sE -1/ 2 0,85f c' Z cE
Z cE bi hE2
E
Z sE 2 t hE2
h H
hE n +
2 4
hn = lihat titik B
PC = 0,85 f c' Ac
MC = M D
0,85f c' Ac
PD =
2
M D = Fy Z s +1/ 2 0,85f c' Z c
D Z s = modulus penampang plastis sumbu x penuh dari
PSB
bi hi2
Zc = - 0,192 ri 3
4
PB = 0
1
M B = M D - Fy Z sn
2

0,85 f c' Z cn
B Z sn = 2 t h22
Z cn = bi hn2
0,85 f c' Ac h
hn = i
2 0,85 f c bi + 4 t Fy 2
'

193 dari 282


KAPASITAS PLASTIS UNTUK KOMPOSIT,
PSB BUNDAR TERISI MELENTUR DI
SEMBARANG SUMBU

Penampang Distribusi Titik Definisi Persamaan


Tegangan
PA = As Fy + 0,95f c' Ac
MA = 0
A
As dt - t 2
Ac h 2 / 4
PE = PA 1/ 4 Fy d - h 2 2
+1/ 2 0,95f h
c
' 2
2 - sin 2
M E = Fy Z sE +1/ 2 0,95f c Z cE '

h
3

Z cE sin3 2
6 2
E
Z sE
d 3
-h
3
sin 3 2

6 2
hE hn / 2 + h / 4
2h
2 2 arcsin E
h
C PC = 0,95f c Ac
'

MC = MD
0,95f c' Ac
PD =
2
D M D = Fy Z s +1/ 2 0,95f c' Z c
Zs = Modulus penampang plastis dari profil baja d 3 / 6- Z c
Zc = h 3 / 6
PB = 0

M B = Fy Z sB 1/ 2 Z cn 0,95f c' Z cB


Z sB d 3 - h 3 / 6 sin / 2

Z cB h sin / 2 / 6
3 3

0,0260K c + 2K s
2
0,0260K c - 2K s + 0,857K c K s
rad
B 0,0848K c 0,0848K c

K c = f c' h 2
d -t
K s = Fy t (diasumsikan dinding PSB tipis)
2
h - h
hn = sin
2 2 2

194 dari 282


Gambar Terminologi yang digunakan untuk komponen struktur terisi beton

t = 0,93 tnom , in.


B = lebar keseluruhan sisi terpendek, in.
D = radius sisi terluar dari PSB bundar, in.
H = Lebar keseluruhan dari sisi terpanjang, in.
bi = Lebar sisi dalam dari sisi terpendek, in. = B - 2t
di = radius dalam dari PSB bundar, in.
hi = lebar sisi dalam dari sisi terpanjang, in. = H 2t
b = Lebar elemen yang mengalami tekan diperkaku pada sisi terpendek, in. = B 3t per
SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal B4.1b(d)
h = Lebar elemen yang mengalami tekan diperkaku pada sisi terpanjang, in. = H 3t per
SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal B4.1b(d)
r = 1,5t untuk b/t dan h/t, in.
r = 2,0t untuk seluruh perhitungan luas, modulus, dan momen inersia, in.

195 dari 282


CONTOH I.1 DESAIN BALOK INDUK KOMPOSIT

Diketahui:

Dua bentang tipikal dari suatu sistim lantai komposit diperlihatkan dalam gambar di bawah
ini. Tentukan profil WF dan hitung jumlah angkur stud baja yang diperlukan.

Balok induk tidak ditopang selama pekerjaan konstruksi.

wr

Potongan A-A

Agar mampu menahan kebakaran selama dua jam tanpa perlu penyemprotan bahan anti
kebakaran, dipasang pelat beton normal di atas dek baja BONDEK II. Mutu beton f c' = 30
MPa.

Pembebanan sebagai berikut:

Beban mati:

kN
c = 25 hr = 54 mm hc = 100 mm wr = 32 mm
m3
kN
Sr = 200 mm berat deck: wd = 0,136 tebal 1 mm
m2

Pra-komposit:

Pelat
w r hr kN
w s = c + hc +w d ws = 2,852
Sr m2

196 dari 282


Berat sendiri profil

kN
wp1 = 0,213 WF200.100.5.5.8
m
kN
wp2 = 0,496 WF350.175.7.11
m

Setelah komposit

kN
Beban mati tambahan wSDL = 1,5
m2

Beban hidup:

Pra-komposit:

kN
Konstruksi wconstr = 1,25 beban sementara selama
m2
pengecoran beton
Setelah komposit

kN
wLL = 5 tidak boleh direduksi
m2

Catatan beban yang digunakan:

Menurut AISC Design Guide 3, untuk pelat yang dipasang di elevasi tetap,
direkomendasikan penambahan beban 10% dari berat sendiri pelat untuk memperhitungkan
ponding akibat lendutan dari berat beton basah selama pengecoran.

Walaupun demikian, dalam desain ini karena pelat dipasang dengan tebal yang tetap jadi
tidak diperlukan penambahan berat tersebut.

Menurut ASCE/SEI 37-02 Design Loads on Structure During Construction (ASCE,2002)


untuk pelaksanaan konstruksi klas ringan, pada saat pra-komposit diberikan beban hidup
sebesar 1,25 kN/m2 untuk memperhitungkan transportasi beton dan penempatan peralatan.

Solusi:

Persyaratan Dek Komposit dan Angkur

Menurut SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal I1.3, I3.2c dan
I8

20 MPa < f c < 69 MPa


'
(1) Kekuatan Beton:

f c' = 30 MPa o.k.

(2) Tinggi rib/rusuk hr < 75 mm

hr = 54 mm tinggi pelat beton hc = 100 mm

197 dari 282


(3) Lebar rusuk/rib rata-rata: wr > 50 mm

wr = 32 mm lihat gambar, tidak memenuhi syarat

(4) Gunakan angkur stud baja diameter 19 mm atau lebih kecil

Pilih angkur dengan diameter 19 mm dsa = 19 mm

(5) Diameter angkur stud: dsa < 1,5 (tf)

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal I8.1,
batas ini hanya bisa diterapkan jika angkur tidak di las langsung di atas badan profil.
Angkur D19 akan ditempelkan in suatu pola bergiliran, maka batas ini harus dipenuhi.
Pilih balok induk dengan tebal sayap minimum 7,6 mm.

19 mm
tf > dsa/25 tf = = 7,6 mm
2,5

(6) Angkur stud, setelah diinstal, haraus diperpanjang tidak kurang 37.5 mm di atas sisi
atas deck baja

Panjang angkur 75 mm plus 37,5 mm diperlukan untuk memenuhi tinggi deck 75 mm.
Berdasarkan data dari pabrik, panjang stok standar yang dipilih adalah 125 mm.
Dengan menggunakan reduksi 5 mm untuk memperhitungkan pembakaran selama
instalasi angkur secara langsung ke sayap balok menghasilkan panjang final angkur
menjadi 120 mm.

120 mm > hc = 100 mm o.k.

(7) Panjang minimum angkur = 4 dsa

120 mm > 4.(19 mm) =76 mm o.k.

(8) Paling sedikit ada selimut beton setebal 13 mm dari bagian atas dari angkur stud

hr + hc = 154 mm > 120 mm

(9) Tebal pelat diatas deck harus > 50 mm

hc = 100 mm > 50 mm

Desain pada saat kondisi Pra-Komposit

Pembebanan Konstruksi (Pra-Komposit)

Balok induk akan dibebani di tiap 1/3 bentang. Menghitung Beban Terpusat berdasarkan
luas tributary

L1 = 6 m L2 = 6 m

L
PD = L2 1 w s + L2w p 1 PD = 35,502 kN
3

198 dari 282


L1
PL = L2 w constr PL = 15 kN
3

Kekuatan Lentur kondisi Pra-Komposit

DFBK

Pu = 1,2 PD + 1,6 PL = 66,602 kN

kN
wu = 1,2 wp2 = 0,595
m

L1 w u L12
M u = Pu + = 135,883 kN m
3 8

Cek Kekuatan Lentur WF 350.175.7.11 Fy = 250 MPa E = 200 000 MPa

L1
Lp = 1 965,7 mm Lr = 5 786,9 mm Lb = = 2 x 103 mm
3

Zx = 867 900 mm3 Zy = 173 600 mm3 Cb = 1 b = 0,9

Karena penampang kompak menurut Tabel Profil Sx = 774 800 mm3

Mpx = Zx Fy = 216,975 kN m

Lb - Lp
M nx = Cb M px - M px - 0,7Fy S x = 216,244 kN m
L -L
r p

M nx = min M px ,M nx M nx = b M nx = 194,62 kN m

Mu
rasio = = 0,698 o.k.
M nx

Lendutan Pra-Komposit

AISC Design Guide-3 merekomendasikan lendutan akibat beton dan berat sendiri tidak
melampaui L/360

Ix = 1,356 108 mm4

PD L13 5w p 2 L14 L
nc = + = 10,407 mm < 1 = 16,667 mm OK
28 E I x 384 E I x 360

Catatan
Bisa juga dilakukan lawan lendut (camber) waktu pelaksanaan untuk mereduksi lendutan.

199 dari 282


Lawan lendut (camber) = 0,8 nc = 8,326 mm

Desain untuk Kekuatan Lentur Komposit

Kekuatan Lentur Perlu

Dengan menggunakan perhitungan luas tributary, beban total terpusat dihitung sebagai
berikut

L
PD = L2 1 w s + w SDL + L2w p 1 PD = 53,502 kN
3

L1
PL = L2 w LL PL = 60 kN
3

L1
Pr = 1,2 PD + 1,6 PL = 160,202 kN a= =2m
3

kN
wu = 1,2 wp2 = 0,595
m

wua
M r 1 = Pr a + L1 - a = 322,786 kN m Mr3 = Mr1
2
w L2
M r 2 = Pr a + u 1 = 323,083 kN m
8

Menghitung b

Lebar efektif pelat beton adalah jumlah lebar efektif tiap sisi dari sumbu balok yang dihitung
berdasarkan nilai minimum dari 3 kondisi SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural Pasal I3.1a

(1) Seperdelapan bentang balok induk

200 dari 282


L1
(2) = 1,5 m dua sisi
8

(2) Setengah jarak antara sumbu balok induk yang bersebelahan

L2
(2) = 6 m dua sisi
2

(3) Jarak ke tepi pelat

tidak berlaku untuk balok induk interior

berarti beff = 1,5 m

Kekuatan Lentur yang tersedia

Menurut SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal I3. 2a,
kekuatan lentur nominal harus dihitung berdasarkan distribusi tegangan plastis penampang
komposit jika h/tw < 3,76.(E/Fy)0,5

WF 350.175.7.11

d = 350 mm bf = 175 mm tf = 11 mm tw = 7 mm

r = 14 mm h = d - 2 tf - 2 r = 300 mm As = 6314,2 mm2

h E
= 42,857 < 3,76 = 106,349 Ixs = 1,356 108 mm4
tw Fy

Jadi harus digunakan distribusi tegangan plastis untuk menghitung kekuatan lentur nominal.

Metode Perhitungan langsung

(1) Beton pecah

Ac = luas pelat beton selebar lebar efektif. Anggap profil deck 50% kosong dan 50%
terisi beton

beff
Ac = beff hc + hr Ac = 1,905 x 105 mm2
2

Cc = 0,85 f c' Ac = 4,858 x 103 kN

(2) Baja leleh

Cs = As Fy = 1,579 x 103 kN

(3) Transfer Geser

70% digunakan sebagai persentasi percobaan penampang komposit sebagai berikut

C = 0,7 min(Cc,Cs) = 1104,985 kN untuk mencapai 70% aksi komposit

201 dari 282


Menentukan lokasi Sumbu Netral Plastis (SNP)

Sumbu Netral Plastis dicari dengan menyamakan gaya yang bekerja di atas dan di bawah
sumbu netral. Konsep ini diperlihatkan pada gambar di bawah, dengan menganggap lokasi
SNP terletak di sayap balok baja

n
Fdiatas SNP = Fdibawah SNP
n

C + x bf Fy = (As - bf x) Fy

maka x diperoleh:

As Fy - C
x= = 5,4121714 mm < tf = 11 mm SNP di sayap profil sesuai asumsi
2 bf F y

Menghitung Kekuatan Momen Nominal dari penampang komposit mengikuti prosedur


penjelasan Pasal I3. 2a

C
a= = 28,888 mm < hc = 100 mm di atas bagian atas deck
0,85 f c' beff

a
d 1 = hc - = 85,556 mm
2

x
d2 = = 2,706 mm
2

d
d3 = = 175 mm
2

Py = As Fy = 1,579 x 103 kN

Mn = C (d1 + d2) + Py (d3 - d2) = 369,503 kN m

b M n = 332,552 kN m > Mr2 = 323,083 kN m

202 dari 282


Mr 2
rasio = = 0,972
b M n

Kekuatan Angkur Baja

Kekuatan Angkur Stud Headead baja bisa dihitung sesuai SNI 1729, Spesifikasi untuk
gedung baja struktural Pasal I8.2a sebagai berikut:

Qn = 0,5 Asa f c' E c


0,5
Rg R p Asa Fu

1 f c'
Asa = d sa2 = 283,529 mm2 E c = 4 700 MPa = 25 742,9602 MPa
4 MPa

Rg = 1 angkur stud dilas langsung ke profil baja diantara kemiringan pelat

Rp = 0,75 angkur stud dilas langsung ke profil baja

Fu = 450 MPa untuk angkur baja ASTM A108


Qn = min 0,5 Asa f c' E c , Rg R p Asa Fu Qn = 95,691 kN

Jumlah dan jarak angkur

Menurut SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal I8.2c, jumlah
angkur yang diperlukan antara setiap beban terpusat dan titik terdekat dengan lokasi
momen nol harus cukup untuk mengembangkan momen maksimum yang diperlukan di titik
beban terpusat.

Dari gambar di atas, momen di lokasi beban terpusat, Mr1 dan Mr3, hampir sama besar
dengan momen balok maksimum, Mr2. Jumlah angkur antara ujung balok dan beban titik
harus sedemikian rupa mengembangkan gaya tekan perlu sehubungan momen maksimum,
C, yang sebelumnya sudah dihitung.

i Qn C
Nangkur = Nangkur = = 11,547
Qn Qn

Nangkur = 12 dari ujung balok ke titik beban terpusat

Sesuai SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal I8.2d, angkur
antara beban terpusat harus ditempatkan untuk jarak maksimum:

smax = min(1 500 mm, 900 mm) smax = 900 mm

Untuk balok dengan rusuk dek yang sejajar balok, jarak angur tidak tergantung dari jarak
galur/alur dari deck. Angkur tunggal bisa dipasang sebagaimana diperlukan sepanjang balok
dengan jarak minimum 6dds sesuai SNI 1729, Spesifikasi untuk bangunan gedung baja
struktural Pasal I8.2d. Angkur juga bisa ditempatkan sebagai pasangan sebaris atau
berselang seling dengan jarak minimum antara 4 diameter stud = 75 mm. Untuk desain ini,
dipilih menggunakan pasangan angkur sampai dengan ujung balok sesuai persyaratan

203 dari 282


kekuatan dan angkur tunggal sepanjang sumbu penampang yang memenuhi persyaratan
jarak maksimum seperti diperlihatkan dalam gambar di bawah ini.

Kolom Balok Balok Kolom

mininum 3
Balok induk

Dek tidak
diperlihat-
kan

WF WF

SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal I8.2d mensyaratkan
bahwa jarak dari pusat suatu angkur ke tepi bebas dalam arah gaya geser adalah minimum
180 mm untuk pelat beton normal. Untuk balok komposit dengan tumpuan sederhana,
persyaratan ini bisa diterapkan ke jarak antara tepi pelat dan angkur pertama disetiap ujung
balok. Dengan menganggap tepi pelat sepusat dengan sumbu dari tumpuan, pada gambar
jarak ini adalah 180 mm, dalam kasus ini sayap kolom akan mencegah perlunya kontrol ini.
Tepi pelat sering ditumpu secara merata oleh sayap kolom atau penghentian pengecoran
dalam konstruksi komposit, yang akan mencegah terjadinya kegagalan beton yang jebol dan
menghapus persyaratan jarak tepi.

Pada contoh ini, jumlah minimum angkur diperlukan untuk memenuhi batas jarak maksimum
yang telah dihitung digunakan di tengah pertigaan dari bentang balok. Harap dicatat juga
bahwa SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal I3.2c(1)(4)
mensyaratkan deck baja yang diangkur ke semua elemen penumpu berjarak maksimum 450
mm. Tambahan, ANSI/SDI C1.0-2006, Standard for Composite Steel Floor Deck (SDI,2006),
meminta deck untuk dipasang pada rata-rata sejarak 300 mm tapi tidak lebih dari 450 mm.

Kriteria Lendutan Beban Hidup

Lendutan akibat beban hidup diterapkan setelah aksi komposit terjadi akan dibatasi ke L/360
dengan besar beban hidup sesuai SNI 1727, Beban minimum untuk perancangan bangunan
gedung dan struktur lain, atau 25 mm dengan menggunakan reduksi 50% dalam beban
hidup desain sebagaimana direkomendasikan oleh AISC Design Guide 3.

Lendutan untuk komponen komposit bisa dihitung dengan menggunakan momen inersia
batas bawah dalam Penjelasan AISC Persamaan C-I3-1 dan ditabulasi dalam AISC Manual
Tabel 3-20. Penjelasan AISC juga memberikan metode alternatif untuk menghitung lendutan
melalui perhitungan momen inersia efektif. Kedua metode bisa diterima dan akan
diilustrasikan dalam contoh berikut untuk maksud perbandingan.

Metode 1: Menghitung momen inersia batas bawah, ILB

Qn
I LB = I xs + As YENA - d 3 + i 2 d + d -Y

2 2
3 1 ENA
Fy

204 dari 282


Variabel d1, d2 dan d3 dihitung dengan prosedur yang telah dilakukan di atas waktu
menghitung kapasitas momen nominal. Walaupun demikian, untuk perhitungan ILB, kuat
nominal angkur baja dihitung diantara titik lokasi momen maksiumum positif dan titil lokasi
momen nol, bukan antara beban terpusat dan lokasi momen nol seperti yang telah
digunakan di atas. Momen maksimum terletak di tengah bentang .

jumlah total angkur: 12 + 1 = 13 Qn = 1 243,982 kN C = 1 104,985 kN

max C , 13 Qn
a= = 32,522 mm
0,85 f c' beff

a
d 1 = hc - = 83,739 mm
2

As Fy -13 Qn
x= = 3,824 mm < tf = 11 mm SNP di sayap profil
2 bf Fy

x
d2 = = 1,912 mm
2

d
d3 = = 175 mm
2

Jarak dari sisi atas profil baja ke sumbu netral elastik, YENA, untuk digunakan dalam
Persamaan C-I3-1 dihitung dengan prosedur yang diberikan dalam AISC Specification
Commentary Section I3.2 sebagai berikut

13 Qn
As d 3 + 2 d 3 + d 1
YENA = Fy = 289,035 mm
13 Qn
As +
Fy

Dengan mensubstitusikan nilai nilai ini kedalam AISC Specification Commentary Section
Equation C-I3-1, diperoleh inersia batas bawah:

13 Qn
I LB = I xs + As YENA d 3 + 2 d 3 + d 1 -YENA
2 2
F
y

ILB = 3,219 x 108 mm4

Metode 2: Perhitungan Momen Inersia Efektif, Ieff

Prosedur alternatif untuk menghitung momen inersia dalam perhitungan lendutan


penampang komposit dijelaskan dalam AISC Specification Commentary Section I3.2
sebagai berikut:

Momen Inersia transformasi, Itr

205 dari 282


Lebar efektif dari beton di bawah sisi atas deck bisa didekati dengan profil deck yang
memiliki 50% lebar efektif.

Lebar pelat pengganti dihitung sebagai berikut:

E beff
n= = 7,769 btr 1 = = 193,072 mm
Ec n

0,5beff
btr 2 = = 96.536 mm
n
beff

0,5 beff

Gambar Lebar beton efektif

Hitung sumbu netral elastik dari penampang yang telah ditransform dengan menganggap
aksi komposit penuh dan hitung momen inersia transform.

Untuk soal ini, lokasi sumbu elastik (ENA) coba-coba dianggap terletak di deck komposit.

Dilakukan di mathcad:

given x = 0,1 mm

hc x d
btr 1 hc
+ x + btr 2 x + As x - hr + 2 = 0
2 2

x = find(x) = 18,138 mm < hr = 54 mm sumbu netral elastik ada dalam dek komposit

Dengan menggunakan teorema sumbu sejajar dan mensubstitusikan nilai x, hasilnya:

2
1 1 hc
2
x
2
d
I tr = I xs + btr 1hc + btr 2 x + btr 1hc + x + btr 2 x + As
3 3
x - hr + 2
12 12 2 2

Itr = 5,223 x 108 mm4

206 dari 282


Menghitung momen inersia equivalen, Iequiv

Cf = min(Cc, Cs) = 1578,55 kN

13Qn
I equiv = I xs + I tr - I xs = 4,789 x 10 mm
8 4

Cf

Berdasarkan AISC Specification Commentary Section I3.2:

Ieff = 0,75 Iequiv = 3,591 x 108 mm4

Perbandingan hasil kedua metode dan Perhitungan Lendutan Final

ILB = 3,219 x 108 mm4 Ieff = 3,591 x 108 mm4

Akan digunakan ILB

PLL13
LL = = 7,189 mm < 25 mm, o.k. menurut batas AISC Design Guide 3
28EI LB

(reduksi 50% dalam beban hidup desain menurut AISC Design Guide 3 tidak perlu dilakukan
dalam batas ini)

= L1 /834,608 < L1 / 360, o.k. berdasarkan batas SNI pembebanan

Kekuatan Geser yang tersedia

Menurut SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal I4.1, balok
induk harus dianggap sebagai balok baja saja pada waktu menahan gaya geser.

w u L1
Vu = Pr + = 161,988 kN v = 1,0 Vn = 0,6 Fy d tw 1
2

v Vn = 367,5 kN kuat terhadap geser

Kinerja

Tergantung maksud penggunaan dari bentang ini, vibrasi mungkin perlu dipertimbangkan.
Lihat AISC Design Guide 11 untuk informasi tambahan.

Perlu diperhatikan terjadinya retak pada pelat di garis sejajar balok induk, jadi perlu
dipasang tulangan yang melintang dibagian atas pelat beton.

207 dari 282


CONTOH I.2 BATANG TEKAN TERISI BETON KOMPOSIT

Kontrol apakah batang tekan komposit dengan panjang 4 m seperti yang diperlihatkan pada
gambar mampu menahan gaya tekan akibat beban mati dan beban hidup.

Mutu beton f c' = 25 MPa sedang Profil PSB Fy = 250 MPa

f c' = 25 MPa Fy = 250 MPa E = 200 000 MPa

f c'
E c = 4 700 MPa = 23 500 MPa L=4m
MPa

Data Profil

As = 7 527 mm2

H = 250 mm

B = 150 mm

t = 10 mm

h
h = H - 2 t = 230 mm = 23
t

b
b = B - 2 t = 130 mm = 13
t

Isx = 5 825,01 cm4 = 5,825 x 107 mm4

Isy = 2 634,2 cm4 = 2,634 x 107 mm4

Data beton

Ac = b h - t2 (4 - ) = 2,981 x 104 mm2 Asr = 0 mm2

208 dari 282


Isr = 0 mm4

Kekuatan penampang komposit untuk Alokasi Gaya

Untuk menghitung kekuatan penampang komposit, batang harus diklasifikasi terlebih dahulu
sebagi kompak, nonkompak atau langsing sesuai SNI 1729, Spesifikasi untuk bangunan
gedung baja struktural Tabel I1.1a. Walaupun demikian, hasil dari kontrol ini tidak
mempengaruhi perhitungan alokasi gaya karena SNI 1729 Pasal I6.2 meminta penggunaan
Persamaan I2-9a dengan mengabaikan klasifikasi tekuk lokal, maka perhitungan ini
diabaikan pada contoh ini. Kekuatan Tekan Aksial Nominal dihitung tanpa memperhitungkan
efek panjang, Pno, digunakan untuk perhitungan alokasi gaya yang dihitung sebagai berikut:

C2 = 0,85 untuk penampang pesegi

E
Pno = Fy As + C 2 f c' Ac + Asr 3
= 2,515 x 10 kN
Ec

Ag = As + Ac = 3,734 x 104 mm2

Menghitung momen inersia beton dengan menggunakan geometri yang kompatibel dengan
yang digunakan dalam perhitungan luas baja, yang memperhitungkan tebal dinding dan
radius sudut dari 2 kali tebal dinding. Persamaan berikut bisa digunakan:

Untuk lentur terhadap sumbu x-x

I cx =
B - 4 t h 3 + t H - 4 t
3

+
9 2
- 64 t 4 2 H - 4t 4t
+ t +
2


12 6 36 2 3

Icx = 1,307 x 108 mm4

Untuk lentur terhadap sumbu y-y

I cy =
H - 4 t h 3 t B - 4 t
+
3

+
9 2
- 64 t 4 B - 4t 4t
+ t
2
+
2


12 6 36 2 3

Icy = 2,162 x 108 mm4

Pembatasan menurut SNI 1729 Pasal I1.3 dan I2.2a

Kekuatan Beton: 20 MPa < f c < 68,95 MPa


'
(1)

f c' = 25 MPa o.k.

(2) Tegangan Leleh minim dari baja struktur: Fy < 517 MPa

Fy = 250 MPa o.k.

(3) Luas penampang baja: As > 0,01 Ag

209 dari 282


As = 7527mm2 > 0,01 Ag = 373,412 mm2

Tidak ada persyaratan tulangan minimum dalam kasus ini; jadi luas tulangan , Asr, adalah
nol untuk contoh ini.

Klasifikasi penampang untuk tekuk lokal

Untuk menghitung kekuatan penampang komposit terhadap gaya aksial, batang harus
diklasifikasi apakah kompak, nonkompak atau langsing sesuai SNI 1729 Tabel I1. 1A.

E
p = 2,26 = 63,922
Fy

h b
controlling = max , = 23 < p penampang kompak
t t

Kekuatan Tekan yang tersedia

Kekuatan tekan nominal untuk penampang kompak, dihitung dengan SNI 1729, Spesifikasi
untuk bangunan gedung baja struktural Pasal I2.2b:

Pno = 2 515,3009 kN

Karena panjang takterbreis sama untuk kedua sumbu x-x dan y-y, kolom akan tertekuk
terhadap sumbu y-y ( sumbu dengan momen inersia lebih rendah).

Icy dan Isy akan digunakan untuk memperhitungkan efek kelangsingan sesuai dengan SNI
1729 Pasal I2.2b dan I2.1b sebagai berikut:

As
C 3 = 0,6 + 2 = 1,003 harus 0,9 C3 = 0,9
A
c + As

E Ieff = E Isy + E Isr + C3 Ec Icy = 9,842 x 103 kN m2

KL = 1,0 (4 m) = 4 m

2 E I eff = 6,071 x 103 kN


Pe =
K L
2

Pno
= 0,414 > 2,25
Pe

Pn = 0,877 Pe = 5,324 x 103 kN SNI 1729 Persamaan I2-3

Bila PD = 800 kN PL = 1200 kN

Pr = 1,2 PD + 1,6 PL = 2880 kN

Pa = PD + PL = 2000 kN

210 dari 282


DFBK

c = 0,75 c Pn = 3 993,225 kN

Pr
rasio = = 0,721
c Pn

DKI

Pn
c = 2 = 2662,15 kN
c

Pa
rasio = = 0,751
Pn
c

Kekuatan Tekan dari Penampang Baja Nonkomposit

Karena perbedaan dalam kapasitas dan faktor keamanan antara kolom komposit dan kolom
nonkomposit, adalah mungkin untuk menghitung kuat tekan yang tersedia yang terendah
untuk suatu kolom komposit dari pada menghitung penampang baja.

Walaupun demikian, sesuai SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
Pasal I2.1b, kekuatan tekan yang tersedia tidak boleh kurang daripada kekuatan baja sesuai
Bab E.

211 dari 282


CONTOH I.3 BATANG KOMPOSIT TERISI YANG MENAHAN GAYA TARIK

Kontrol apakah batang komposit dengan panjang 4 m seperti yang diperlihatkan pada
gambar mampu menahan gaya tekan akibat beban mati dan gaya tarik akibat angin.

Mutu beton f c' = 25 MPa sedang Profil PSB Fy= 250 MPa

f c' = 25 MPa Fy = 250 MPa E = 200 000 MPa fy = 400 MPa

f c'
E c = 4 700 MPa = 23 500 MPa L=4m
MPa

Penampang Tampak samping

PD = 500 kN PW = 1300 kN (tarik)

Data Profil
As = 7 527 mm2

H = 250 mm

B = 150 mm

t = 10 mm
h
h = H - 2 t = 230 mm = 23
t

b
b = B - 2 t = 130 mm = 13
t
Isx = 5825,01 cm4 = 5,825 x 107 mm4

Isy = 2634,2 cm4 = 2,634 x 107 mm4

212 dari 282


Data beton

Ac = b h - t2 (4 - ) = 2,981 x 104 mm2


Tidak ada persyaratan minimum untuk tulangan memanjang dalam SNI 1729, Spesifikasi
untuk bangunan gedung baja struktural , oleh karena itu adalah umum dalam praktek pada
batang komposit ini tidak dipasang tulangan.

Asr = 0 mm2

DFBK DKI

Pr = - 0,9 (PD) + 1,0(PW) = 850 kN Pa = - 0,6 PD + 0,6 PW = 480 kN

Catatan : positif berarti tarik

Kekuatan Tarik yang tersedia

Dihitung sesuai SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal I2.2c

Pn = As Fy + Asr fy = 1881,75 kN t = 0,9 t = 1,67

DFBK DKI

Pr Pa
rasio = = 0,502 rasio = = 0,426
t Pn Pn
t

Alokasi Gaya dan Transfer Beban

Perhitungan transfer beban tidak disyaratkan untuk batang tarik yang terisi beton yang tidak
berisi tulangan memanjang, seperti contoh ini, hanya penampang baja yang menahan tarik.

213 dari 282


CONTOH I.4 BATANG KOMPOSIT TERISI YANG MENAHAN GAYA TEKAN, MOMEN
LENTUR DAN GESER

Kontrol apakah batang komposit dengan panjang 4 m seperti yang diperlihatkan pada
gambar mampu menahan gaya tekan, geser dan momen hasil Analisis Langsung dari SNI
1729 Pasal C untuk kombinasi pembebanan yang kritis sesuai SNI 1727 Pembebanan.

Mutu beton f c' = 25 MPa sedang Profil PSB Fy = 250 MPa

f c' = 25 MPa Fy = 250 MPa E = 200 000 MPa fy = 400 MPa

f c'
E c = 4 700 MPa = 23 500 MPa L=4m
MPa

Pr

Mr

Vr

MMr r

Vr

Mr

Pr
Penampang Tampak samping

Pr = 450 kN Pa = 275 kN

Mr = 135,9 kN m Ma = 75 kN m

Vr = 80 kN Va = 46 kN

Data Profil

As = 7 527 mm2

H = 250 mm

B = 150 mm tg = 10 mm

t = 0,93 tg
h
h = H - 2 t = 231,4 mm = 24,882
t
b
b = B - 2 t = 131,4 mm = 14,129
t
Isx = 5825,01 cm4 = 5,825 x 107 mm4

214 dari 282


Isy = 2634,2 cm4 = 2,634 x 107 mm4

H h
Z sx = B - 2 t t H - t + 2 t = 5,631 x 10 mm
5 3

2 t

Data beton

Ac = b h - t2 (4 - ) = 3,033 x 104 mm2


Penampang Komposit

Tidak ada persyaratan minimum untuk tulangan memanjang dalam SNI 1729, oleh karena
itu adalah umum dalam praktek pada batang komposit ini tidak dipasang tulangan.

Asr = 0 mm2 Ag = As + Ac = 3,786 x 104 mm2 Isr = 0 mm4

Untuk lentur terhadap sumbu x-x

I cx =
B - 4 t h 3 t H - 4 t
+
3

+
9 2
- 64 t 4 H - 4t 4t
+ t
2
+
2


12 6 36 2 3

Icx = 1,347 x 108 mm4

Untuk lentur terhadap sumbu y-y

I cy =
H - 4 t h 3 t B - 4 t
+
3

+
9 2
- 64 t 4 B - 4t 4t
+ t
2
+
2


12 6 36 2 3

Icy = 2,229 x 108 mm4

Batasan SNI 1729 Pasal I1.3 dan I2.2a

(1) Mutu beton: 20 MPa < f c' < 68,95 MPa

f c' = 25 MPa o.k.

(2) Tegangan leleh baja struktur: Fy < 517 MPa

Fy = 250 MPa

(3) Luas penampang profil: As > 0,01 Ag

As = 7527 mm2 > 0,01 Ag = 378,587 mm2

Klasifikasi penampang untuk tekuk lokal

Batang komposit ini telah dibuktikan kompak pada contoh I.4 berdasarkan SNI 1729 Tabel
I1.1a. Penampang harus dikontrol terhadap persyaratan tekuk lokal untuk lentur sesuai SNI
1729 Tabel I1. 1b; tapi karena batas untuk lentur sama atau kurang ketat dibandingkan
batang yang mengalami tekan, maka batang juga kompak untuk aksi lentur.

215 dari 282


Interaksi gaya aksial dan lentur

Interaksi antara gaya aksial dan lentur pada batang komposit diatur oleh SNI 1729 Pasal I5,
yang untuk batang kompak, mengijinkan digunakannya metode kompatibilitas regangan
atau metode distribusi tegangan plastis, dengan opsi menggunakan persamaan Pasal H1. 1.

Metode kompatibilitas regangan adalah pendekatan yang umum yang memperbolehkan


pembentukan diagram interaksi berdasarkan konsep yang sama seperti pada desain beton
bertulang. Penerapan metode kompatibilitas regangan diperlukan untuk penampang tidak
teratur atau nonsimetris, dan aplikasi umumnya bisa dilihat dalam buku teks beton bertulang
dan tidak akan didiskusikan lagi disini.

Metode distribusi tegangan plastis didiskusikan dalam AISC Specification Commentary


Section I5 yang memberikan 3 prosedur yang bisa diterima untuk batang komposit yang
terisi beton. Prosedur pertama, Metode 1, memerlukan persamaan interaksi dari Pasal H1.
Ini adalah satu satunya metode yang bisa diterima untuk penampang nonkompak dan
langsing. Metode 2, melibatkan pembentukan kurva interaksi sebagian linier dengan
menggunakan persamaan kekuatan plastis yang tersedia di Gambar I. 1c yang ditempatkan
dibagian depan Bab I Contoh Desain. Prosedur ketiga, Metode 2-Sederhana, adalah reduksi
dari kurva interaksi sebagian linier yang memperbolehkan penggunaan persamaan interaksi
yang kurang konservatif dari pada yang tersedia dalam Bab H.

Untuk contoh desain, masing-masing penerapan prosedur distribusi plastis akan ditinjau dan
dibandingkan

Metode 1: Persamaan Interaksi Pasal H1

Metode paling langsung dan konservatif dari menaksir efek interaksi melalui penggunaan
persamaan interaksi dari SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
Pasal H1. Sesuai dengan penggunaan Metode Analisis Langsung, Faktor K = 1 digunakan.
Karena panjang tak terbreis sama untuk kedua sumbu lentur x-x dan y-y, dan Ix lebih besar
dari Iy, tekuk disumbu y-y akan menentukan kekuatan tekan. Kekuatan lentur dihitung
terhadap sumbu x-x untuk menahan momen lentur yang terjadi di sumbu ini.

c = 0,75 Pn = 4,437 x 103 kN

c Pn = 3 327,75 kN

Menghitung M n

b = 131,4 mm h = 231,4 mm b = 0,9

Zsx = 5,631 x 105 mm3

b h2
Zc = - 0,192 t 3 = 1,759 x 106 mm3
4
1
M D = Fy Z sx +
2

0,85 f c' Z c = 159,473 kN m

0,85 f c' Ac h
hn = min , = 53,303 mm
0,85 f c b + 4 t Fy 2
'

216 dari 282


Z sn = 2 t hn2 = 5,285 x 104 mm3

Z cn = b hn2 = 3,733 x 105 mm3

0,85 f c' Z cn
M n = M D - Fy Z sn - = 142,295 kN m
2

b M n = 128,066 kN m

DFBK

Pc = c Pn = 3,328 x 103 kN Mc = b M n = 128,066 kN m

Pr
= 0,135 < 0,2
Pc

Pr M
rasioLRFD = + r = 1,129
2 Pc M c

DKI

Pn
c = 1,67 Pa = 445,4 kN Pc = = 2,657 x 103 kN
c

Mn
b = 1,67 Ma = 75 kN m Mc = = 85,207 kN m
b

Pa
= 0,168 < 0,2
Pc

Pa M
rasioASD = + a = 0,964
P
2 n Mc
c

Dengan menggunakan DFBK, Metode 1 menunjukan bahwa penampang tidak kuat


terhadap beban terfaktor. Perencana bisa memilih penampang baru yang memenuhi kontrol
interaksi atau melakukan analisis ulang dengan menggunakan metode desain kurang
konservatif seperti Metode 2. Metode ini akan dijelaskan sebagai berikut:

Metode 2: Kurva Interaksi dari Model Distribusi Platis

Prosedur untuk membuat kurva interaksi dengan menggunakan model distribusi tegangan
plastis diperlihatkan dalam gambar di bawah ini.
Kekuatan material
(persamaan kekuatan)

217 dari 282


Kekuatan material
(persamaan kekuatan)
Kelangsingan
(kurva kolom)

Desain ,
= Reduksi kelangsingan
Kekuatan tekan

= A/A

Kekuatan Lentur

Gambar Metode 2 Diagram interaksi untuk balok-kolom komposit

Berdasarkan gambar di atas, permukaan interaksi kekuatan nominal A,B,C,D,E mula mula
dihitung dengan menggunakan persamaan dari Gambar I-1c yang tercantum dalam
introduksi Bab I Contoh Desain. Kurva ini mewakili kekuatan batang kolom pendek tanpa
memperhitungkan efek panjang batang. Suatu faktor reduksi kelangsingan, , dihitung dan
dipasang kesetiap titik untuk membuat permukaan A', B', C', D', E'. Kemudian ketahanan
yang sesuai atau faktor keamanan diterapkan untuk membuat permukaan desain A'', B'', C'',
D'', E''. Akhirnya, gaya dan momen terfaktor hasil kombinasi pembebanan di plot dalam
permukaan desain, dan batang bisa diterima jika semua hasil plot terletak didalam kurva
desain. Langkah perhitungan akan dijelaskan detail dengan perhitungan sebagai berikut:

Langkah 1: Buat permukaan interaksi kuat nominal A, B, C, D, E tanpa memperhitungkan


efek kelangsingan.

Dengan menggunakan persamaan persamaan yang tersedia dalam Gambar I-1c untuk
lentur terhadap sumbu x-x :

Titik A (gaya tekan murni)

P1 = Fy As + 0,85 f c Ac = 2 526,299 kN
'

M1 = 0 kN m

Titik D (kuat momen nominal maksimum)

0,85 f c' Ac
P4 = 322,274 kN
2

Zsx = 5,631 x 105 mm3

Zc = 1,759 x 106 mm3

0,85 f c' Z c
M 4 Fy Zsx = 159,473 kN m
2

218 dari 282


Titik B (lentur murni)

P5 = 0 kN

0,85 f c' Ac h
hn = min , = 53,303 mm
0,85 f c b + 4 t Fy 2
'

Z sn = 2 t hn2 = 5,285 x 104 mm3

Z cn = b hn2 = 3,733 x 105 mm3

0,85 f c' Z cn
M 5 MD - Fy Zsn = 142,295 kN m
2

Titik C ( titik antara)

P3 = 0,85 f c' Ac = 644,549 kN

M3 = M4 = 159,473 kN m

Titik E (tambahan)

Titik E adalah titik tambahan untuk membantu membuat kurva interaksi menjadi lebih baik.

hn H
hE = + = 89,151 mm
2 4

0,85 f c' Ac
P2 0,85 f c' b hE + 4 Fy t hE = 1,4 x 103 kN
2

Z cE = b hE2 = 1,044 x 106 mm3

Z sE = 2 t hE2 = 1,478 x 105 mm3

0,85 f c' Z cE
M 2 M 4 - Fy Z sE = 111,419 kN m
2

Titik yang dihitung di plot untuk membentuk permukaan interaksi kekuatan nominal kolom
pendek.

219 dari 282


Langkah 2: Buat permukaan kuat nominal A', B', C', D' ,E' memperhitungkan efek
kelangsingan

Faktor reduksi kelangsingan, , dihitung untuk titik A dengan menggunakan SNI 1729 Pasal
I2.2 sesuai dengan AISC Specification Commentary Section I5

Pno = P1 = 2,526 x 103 kN

As
C 3 = min 0.9,0.6 + 2 = 0,9
Ac + As

EIeff = E Isy + E Isr + C3 Ec Icy = 9,984 x 103 kN m2

2 E I eff
Pe = = 6,158 x 103 kN
1.L
2

Pno
= 0,41 < 2,25
Pe
Pno

Pn = Pno 0,658 Pe = 2127,73367 kN SNI 1729 Persamaan I2-2

Pn
= 0,842
Pno

220 dari 282


Berdasarkan AISC Specification Commentary Section I5, reduksi kelangsingan yang sama
diterapkan untuk titik-titik yang lain pada permukaan interaksi

PR1 = P1

PR2 = P2

PR3 = P3

PR4 = P4

PR5 = P5

Langkah 3 Buat permukaan interaksi desain dan cek kekuatan batang komposit

Langkah terakhir dalam Prosedur Metode 2 adalah mereduksi semua titik dengan faktor
reduksi kapasitas atau faktor keamanan yang sesuai.

DFBK

Kekuatan Tekan Desain

c = 0,75

P1 = c PR1 P2 = c PR2 P3 = c PR3 P4 = c PR4 P5 = c PR5

Kuat Lentur Desain

b = 0,9

M1 = b M1 M2 = b M2 M3 = b M3 M4 = b M4 M5 = b M5

221 dari 282


Dengan mengeplot besar Pr dan Mr ke dalam kurva interaksi desain yang diperoleh dari
kombinasi pembebanan yang kristis, bisa dilihat bahwa (Mr,Pr) ada di dalam kurva, berarti
batang komposit mampu menahan pembebanan yang ada Metode 2 yang disederhanakan
Versi sederhana dari Metode 2 adalah dengan menghapus titik D dan E dari permukaan
interaksi, sehingga tinggal titik A", B",dan C''.

Jadi

P 1 = P1 P2 = P3 P3 = P5 M1 = M1 M2 = M3 M3 = M5

Dengan mereduksi jumlah titik interaksi, harus dilakukan kontrol interaksi bilinier yang
didefinisikan AISC Specification Commentary Equations C-I5-1a dan C-I5-1b.

222 dari 282


DFBK

Pr = 450 kN > P2 = 407,146 kN

Gunakan persamaan C-I5-1b

Pr - P2 M r
rasio = + = 1,256 rasioLRFD = 1,129
P1 - P2 M 2

Perbandingan antara Metode

Menurut Metode 1 yang menggunakan persamaan interaksi Bab H SNI 1729, batang
komposit tidak kuat, tetapi kuat menurut Metode 2 dan Metode 2 penyederhanaan.
Perbandingan antara metode dengan mudah dilihat jika kurva desain masing masing
metode diperlihatkan dalam satu grafik seperti gambar di bawah ini.

Metode 2
Kekuatan Tekan (MPa)

Metode 2 - Disederhanakan

Metode 1 Interaksi Bab H

Kekuatan Lentur (kN m)

Dari gambar bisa dilihat, kondisi konservatif dari penggunaan Bab H SNI 1729, Spesifikasi
untuk bangunan gedung baja struktural. Metode 2 memberikan nilai kekuatan yang tertinggi,
walaupun demikian, Metode 2-yang disederhanakan representasi yang baik dari kurva
desain lengkap.

Kekuatan Geser yang tersedia

SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal I4.1 memberikan 3
metode untuk menghitung kuat geser tersedia dari batang komposit ini: kuat geser yang
tersedia dari penampang baja sendiri sesuai Pasal G SNI 1729, kekuatan geser tersedia
dari beton bertulang sendiri sesuai SNI 2847 atau kuat geser tersedia dari penampang baja
plus tulangan dengan mengabaikan kontribusi dari beton.

Kekuatan Geser Penampang baja yang tersedia

Dari SNI 1729 Pasal G5, kekuatan geser nominal Vn, dari batang PSB komposit, dihitung
dengan menggunakan Pasal G2.1(b) dengan kv = 5.

223 dari 282


h
h = H - 3 t = 222,1 mm = 23,882 kv = 5
t

Aw = 2 h t = 4,131 x 103 mm2

Koefisien badan, Cv berdasarkan kelangsingan, h/tw

h E
= 23,882 < 1,1 kv = 69,57
t F
y

Gunakan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Persamaan G2-3

Cv = 1 Persamaan G2-3

Kekuatan Geser nominal dihitung sebagai:

Vn = 0,6 Fy Aw Cv = 619,659 kN Persamaan G2-1 SNI 1729

DFBK

Vr
v = 0,9 rasio = = 0,143 o.k.
vV n
DKI

Va
v = 1,67 rasio = = 0,124 o.k.
Vn
v

Kekuatan Geser beton bertulang yang tersedia

Batang komposit tidak memiliki tulangan, oleh karena itu perhitungan geser untuk beton
bertulang tidak tepat untuk kasus ini, kekuatan geser desain untuk beton tanpa tulangan
dengan menggunakan Pasal 22 SNI 2847 dihitung sebagai berikut

= 0,6 untuk beton tanpa tulangan dari SNI 2847 Pasal 9.3.5

=1 untuk beton normal dari SNI 2847 Pasal 8.6.1

bw = b

4 fc '
Vn = bw h MPa SNI 2847 Persamaan 22-9
3 MPa

Vn = 116,736 kN

Vr
rasio = = 0,685 o.k.
V n

224 dari 282


Bisa dilihat dari perhitungan ini, ketahanan terhadap geser dari beton tanpa tulangan itu
kecil dan kuat geser dari baja sendirian saja mampu menahan gaya geser.

Alokasi gaya dan Transfer Beban

Perhitungan transfer beban akibat gaya aksial harus dilakukan sesuai SNI 1729 Pasal I6.
Aplikasi spesifik dari provisi transfer beban tergantung konfigurasi dan detailing dari elemen
yang bersambungan.

225 dari 282


CONTOH I.5 KOLOM BOKS KOMPOSIT TERISI BETON DENGAN ELEMEN LANGSING

Kontrol apakah batang komposit dengan panjang 4 m seperti yang diperlihatkan pada
gambar mampu menahan gaya tekan, geser dan momen hasil Analisis Langsung dari SNI
1729 Pasal C untuk kombinasi pembebanan yang kritis sesuai SNI 1727, Beban minimum
untuk perancangan bangunan gedung dan struktur lain.

Mutu beton f c' = 35 MPa sedang Profil PSB Fy = 250 MPa

f c' = 35 MPa Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

f c'
E c = 4 700 MPa = 27 805,575 MPa L=6m
MPa

Pr = 6 000 kN Pa = 4 500 kN

Mr = 760 kN m Ma = 500 kN m

Vr = 167 kN Va = 96 kN

Dicoba data profil

Untuk mempermudah perhitungan, kontribusi dari pelat yang menonjol kekuatan batang
diabaikan, sebagaimana diperlihatkan pada penampang analitis.

Tebal pelat percobaan t = 10 mm

Harap dicatat, reduksi tebal dinding desain SNI 1729 Pasal B4.2 berlaku hanya untuk PSB
yang dilas listrik dan tidak berlaku untuk penampang tersusun seperti dalam kasus ini.

226 dari 282


H = 750 mm hi = H - 2 t = 730 mm

B = 750 mm bi = B - 2 t = 730 mm

As = 2 H t + 2 bi t = 2,96 x 104 mm2 Ac = hi bi = 5,329 x 105 mm2

Ag = As + Ac = 5,625 x 105 mm2

B H3 bi hi3
I gx = = 2,637 x 1010 mm4 I cx = = 2,367 x 1010 mm4
12 12

Isx = Igx - Icx = 2,702 x 109 mm4

Batasan SNI 1729 Pasal I1.3 dan I2.2a

(1) Mutu beton: 20 MPa < f c' < 68.95 MPa

f c' = 35 MPa o.k.

(2) Tegangan leleh baja struktur: Fy < 517 MPa

Fy = 250 MPa

(3) Luas penampang profil: As > 0,01 Ag

As = 2,96 x 104 mm2 > 0,01 Ag = 5,625 x 103 mm2

Klasifikasi penampang untuk tekuk lokal

Klasifikasi penampang terhadap persyaratan tekuk lokal dilakukan sesuai SNI 1729 Tabel
I1.1A untuk tekan dan Tabel I1.1B untuk lentur. Sebagaimana dicatat dalam SNI 1729 Pasal
I1.4, definisi lebar, tinggi dan tebal yang digunakan dalam evaluasi kelangsingan tercantum
dalam Tabel B4.1a dan B4.1b.

Untuk kolom bentuk boks, lebar dari elemen tekan yang diperkaku yang digunakan untuk
kontrol kelangsingan, b dan h adalah sama dengan jarak bersih antara dinding kolom, bi, hi.
rasio kelangsingan dihitung sebagai berikut

b h
max i , i = 73
t t

Klasifikasi penampang untuk tekuk lokal di elemen baja yang mengalami gaya aksial tekan
dari SNI 1729 Tabel I1.1A:

E E E
p = 2,26 = 63,922 r = 3 = 84,853 max = 5 = 141,421
Fy Fy Fy

Karena p < < r , penampang nonkompak

227 dari 282


Kekuatan Tekan yang tersedia

Kekuatan tekan untuk batang komposit terisi beton nonkompak dihitung sesuai SNI 1729,
Spesifikasi untuk bangunan gedung baja struktural Pasal I2.2b(b).

C2 = 0,85 untuk penampang pesegi

Asr = 0 mm2 Isr = 0 mm2

E
Pp = Fy As +C 2 f c' Ac + Asr 4
= 2,325 x 10 kN (SNI 1729 Persamaan I2-9b)
Ec
E
Py = Fy As + 0,7 f c' Ac + Asr 4
= 2,046 x 10 kN (SNI 1729 Persamaan I2-9d)
E c

P -P
Pno = Pp - p y 2 - p = 2,273 x 104 kN
2
(SNI Persamaan I2-9c)
r - p
Pno = 22727,52924 kN

As
C3 = min 0,6 + 2 ,0.9 = 0,705
Ac + As

EIeff = E Isx + E Isr + C3 Ec Icx = 1,004 x 106 kN m2

2 EI eff
Pe = = 2,754 x 105 kN (SNI 1729 Peramaans I2- 5)
1,0 L
2

Pno
= 0,083 < 2,25
Pe

Oleh karena itu, menurut SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
Persamaan I2-2

Pno

Pn = Pno 0,658 Pe = 21 955,84355 kN (SNI 1729 Persamaan I2-2)

Menurut SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal I2.2b, kekuatan
tekan tidak lebih kecil dari pada kekuatan tekan untuk penampang baja saja sebagaimana
ditentukan di SNI 1729 Pasal E, di kasus ini kekuatan tekan baja lebih kecil.

c = 0,75 c Pn = 1,647 x 104 kN

Pn
c = 2 = 1,098 x 104 kN
c

228 dari 282


Kekuatan Lentur yang tersedia

Kekuatan lentur dari batang komposit terisi beton nonkompak ditentukan sesuai SNI 1729,
Spesifikasi untuk bangunan gedung baja struktural Pasal I3.4b(b):

M n = M p - M p - M y
-
p

-
(SNI 1729 Persamaan I3-3b)
r p

Untuk menggunakan Persamaan tersebut di atas, Momen plastis dan momen leleh
penampang harus dihitung terlebih dahulu.

Momen Plastis

Langkah pertama untuk menghitung kekuatan lentur tersedia dari suatu penampang
nonkompak adalah dengan menghitung momen terhadap distribusi tegangan plastis yang
bekerja di penampang komposit. Konsep ini diperlihatkan secara grafis pada gambar di
bawah ini sesuai AISC Specification Commentary Figure C-I3.7(a) dan mengikuiti distribusi
gaya pada gambar di bawah ini.
Tegangan Tegangan Resultante
baja beton gaya

Sumbu netral plastis

Blok tegangan momen plastis dan distribusi gaya

Komponen Gaya Lengan Momen

tf
Gaya tekan pada sayap baja C1 = bi t f Fy y c1 = ap -
2
a p tf
Gaya tekan pada beton C2 = 0,85 f c' a p - t f bi yc2 =
2
ap
Gaya tekan pada badan baja C 3 = a p 2 tw Fy yc3 =
2
H - ap
Gaya tarik pada badan baja T1 = H - a p 2 tw Fy yr1 =
2
tf
Gaya tarik pada sayap baja T2 = bi t f Fy y r 2 = H - ap
2
dengan:
2 Fy H tw + 0,85 f c' bi t f
ap =
4 tw Fy + 0,85 f c' bi
Mp = gaya lengan momen

229 dari 282


tw = t tf = t

2Fy H tw + 0,85 f c' t f bi


ap = = 125,078 mm
4 tw Fy + 0,85 f c' bi

tf
C1 = bi tf Fy = 1,825 x 103 kN y c1 = ap - = 120,078 mm
2

a p - tf
C2 = 0,85 f c' a p - t f bi = 2,499 x 103 kN yc2 = = 57,539 mm
2

ap
C3 = ap 2 tw Fy = 625,392 kN yc3 = = 62,539 mm
2

H - ap
T1 = (H ap) 2 tw Fy = 3,125 x 103 kN yt1 = = 312,461 mm
2

tf
T2 = bi tf Fy = 1,825 x 103 kN y t 2 = H - ap - = 619,922 mm
2
3 2
M p = Ci y ci + Ti y ti = 2509,73187 kN m
i =1 i =1

Kekuatan Momen Leleh

Langkah berikutnya dalam menentukan kekuatan lentur tersedia dari batang komposit terisi
beton nonkompak adalah menghitung kekuatan momen leleh. Momen leleh sebagaimana
didefinisikan dalam SNI 1729 Pasal I3.4b(b) adalah momen dengan kelelehan pertama
terjadi pada sayap tekan dihitung dengan menggunakan distribusi tegangan elastik linier
dengan tegangan tekan beton maksimum adalah 0,7 f c' . Konsep ini diperlihatkan secara
diagram dalam AISC Specification Commentary Figure C-I3.7(b) dan diperlihatkan pada
gambar di bawah ini.
Tegangan Tegangan Resultante
Baja Beton Gaya

Sumbu netral inelastis

Blok tegangan momen leleh dan distribusi gaya

230 dari 282


Komponen Gaya Lengan Momen
tf
Gaya tekan pada sayap baja C1 = bi t f Fy y c1 = ay -
2
2 a y t f
Gaya tekan pada beton C2 = 0,35 f c' a y - t f bi yc2 =
3
ay
Gaya tekan pada badan baja C3 = a y 2 tw 0,5 Fy yc3 =
3
2a y
T1 = a y 2 tw 0,5 Fy yr1 =
3
T2 = H - a y 2 t w F y
Gaya tarik pada badan baja
H
yr 2 =
2
tf
Gaya tarik pada sayap baja T3 = bi t f Fy y r 3 = H - ay
2
dengan:
2 Fy H tw + 0,35 f c' bi t f
ay =
4 tw Fy + 0,35 f c' bi
Mp = gaya lengan momen
2 Fy H tw + 0,35 f c' bi t f
ay = = 202,688 mm
4 tw Fy + 0,35 f c' bi

tf
C1 = bi tf Fy = 1,825 x 103 kN y c1 = ay - = 197,688 mm
2
2 a y - t f = 128,459 mm
C2 = 0,35 f c' (ay - tf) bi = 1,723 x 103 kN yc2 =
3
2 ay
C3 = ay 2 tw 0,5 Fy = 506,721 kN yc3 = = 135,126 mm
3
2 ay
T1 = ay 2 tw 0,5 Fy = 506,721 kN yt1 = = 135,126 mm
3
H
T2 = (H - 2 ay) 2 tw Fy = 1,723 x 103 kN yt 2 = = 0,375 m
2
tf
T3 = bi tf Fy = 1,825 x 103 kN yt 3 = H - ay - = 542,312 mm
2
3 3
M y = Ci y ci + Ti y ti = 2393,1666 kN m
i =1 i =1

Sekarang Mp dan My telah dihitung, Persamaan I3-3b bisa digunakan bersama-sama


dengan kelangsingan lentur yang telah dihitung sebelumnya untuk menghitung kekuatan
lentur penampang komposit sebagai berikut:

M n = M p - M p - M y
-
p

-
= 2459,17724 kN m (SNI 1729 Persamaan I3-3b)
r p

231 dari 282


b = 0,9 Mn = b Mn = 2213,25951 kN m

Mn
b = 1,67 = 1472,56122 kN m
b

Interaksi Lentur dan Tekan

DFBK

Pr = 6000 kN

Mr = 760 kN m

Pc = c Pn = 1,647 x 104 kN

Mc = Mn = 2,213 x 103 kN m

Pr
= 0,364 > 0,2
Pc

Pr 8 M r
rasioLRFD = = 0,67
Pc 9 M c

DKI

Pa = 4500 kN

Ma = 500 kN m

Pn
Pc = = 1,098 x 104 kN
c

Mn
Mc = = 1,473 x 103 kN m
b

Pa
= 0,41 > 0,2
Pc

Pa 8 M a
rasioASD = = 0,712
Pc 9 M c

Catatan:

Kuat Lentur untuk batang komposit terisi beton dengan penampang yang langsing harus
dihitung sesuai SNI 1729 Pasal I3.4b(c). Kekuatan lentur nominal ditentukan sebagai
momen leleh pertama, Mcr, yaitu momen dengan tegangan sayap tekan Fcr menggunakan
distribusi tegangan elastik linier yang memiliki tegangan tekan maksimum beton 0,7 f c .
'

232 dari 282


Konsep ini diperlihatkan secara diagram dalam AISC Specification Figure C-I3.7(c) dengan
distribusi seperti pada gambar di bawah:
Tegangan Tegangan Resultante
baja beton gaya

'
0,70 fc

Sumbu netral
elastis

Blok tegangan momen leleh pertama dan distribusi gaya

Tabel Persamaan Momen Plastis


Komponen Gaya Lengan Momen
tf
Tekan pada sayap baja C1 = bi t f Fy y c1 = ap -
2
a p - tf
Tekan pada beton C2 = 0,85f c' a p - t f bi yc2 =
2
ap
Tekan pada badan baja C3 = a p 2tw Fy yc3 =
2
H - ap
Tarik pada badan baja T1 = H - a p 2 tw Fy yT 1 =
2
tf
Tarik pada sayap baja T2 = bi t f Fy yT 2 = H - a p -
2
dengan:
2 Fy H tw + 0,35 f c' bi t f
ay =
4 tw Fy + 0,35 f c' bi
Mp = gaya lengan momen
Dengan M n = 0,9 M cr

233 dari 282


CONTOH I.6 KOLOM TEKAN KOMPOSIT TERISI BETON DAN PROFIL WF

Kontrol apakah batang komposit dengan panjang 4 m seperti yang diperlihatkan pada
gambar mampu menahan gaya tekan PD dan PL dari kombinasi pembebanan yang kritis
sesuai SNI 1727, Beban minimum untuk perancangan bangunan gedung dan struktur lain.

Mutu beton f c' = 35 MPa sedang Profil WF Fy = 250 MPa

Fy = 250 MPa Fu = 410 MPa fy = 400 MPa E = 200 000 MPa

f c'
f c' = 35 MPa E c = 4 700 MPa = 27 805,575 MPa L=6m
MPa

DATA PENAMPANG BETON

h1 = 600 mm h2 = 600 mm diameter tulangan db = 25 mm

selimut beton cover = 40 mm diameter sengkang dbs = 10 mm

1
Asri = d b2 = 490,874 mm2 Asr = 8 Asri = 3 926,9908 mm2
4
h1 h23
5
Ag = h1 h2 = 3,6 x 10 mm 2
Ig = = 1,08 x 1010 mm4
12

DATA PENAMPANG WF 350X175x7x11

d = 350 mm bf = 175 mm tw = 7 mm tf = 11 mm h = 300 mm

As = 6314,2 mm2 Isy = 9,845 x 106 mm4 Zsx = 8,679 x 105 mm3 J = 1,94 x 105 mm4

Ac = Ag - As - Asr = 3,498 x 105 mm2 Cw = 2,829 x 1011 mm6

DATA TULANGAN

db h
cs = cover + dbs + = 62,5 mm e= - c s = 87,5 mm
2 2

234 dari 282


d b4
I sri = = 1,917 x 104 mm4
64

I sr = 8 I sri +6Asri e 2 + 2 Asri 0 mm = 2,27 x 107 mm4

Momen inersia beton untuk setiap sumbu dihitung sebagai berikut:

Icy = Ig - Isy - Isr = 1,077 x 1010 mm4 Icx = Icy

Klasifikasi penampang terhadap tekuk lokal

Menurut SNI 1729 Pasal I1.2, efek tekuk lokal tidak perlu dipertimbangkan pada kasus
batang komposit tipe ini, jadi diperlakukan sebagai penampang kompak.

Pembatasan bahan dan pendetailan

Berdasarkan Catatan Pengguna pada akhir SNI 1729 Pasal I1.1, maksud dari spesifikasi
adalah untuk mengimplementasi persyaratan pendetailan nonkomposit dari SNI 2847
sehubungan dengan persyaratan spesifik komposit dari SNI 1729 Pasal I. Persyaratan
pendetailan bisa di grupkan ke batas bahan yang sesuai, tulangan transversal, tulangan
memanjang dan persyaratan tulangan baja struktur seperti digambarkan melalui diskusi
berikut.

Batasan bahan yang tersedia dalam SNI 1729 Pasal I1.1(2) dan I1.3 sebagai berikut:

(1) Mutu beton: 20 MPa < f c' < 68,95 MPa


f c' = 35 MPa o.k.

(2) Tegangan leleh baja struktur: Fy < 517 MPa

Fy = 250 MPa o.k.

(3) Tegangan leleh tulangan fy < 517 MPa

fy = 400 MPa o.k.

Batasan tulangan transversal yang tercantum dalam SNI 1729 Pasal I1.1(3), I2.1a(2) dan
SNI 2847 sebagai berikut:

(1) Ukuran dan jarak dari tulangan pengikat:

SNI meminta baik tulangan ikat atau spiral yang digunakan sebagai tulangan
tranversal. Ketika digunakan sengkang ikat lateral, diameter minimum adalah 10 mm
yang berjarak maksimum 300 mm pusat ke pusat atau diameter 13 mm dengan
berjarak maksimum 400 mm.

digunakan dbs = 10 mm dengan s = 300 mm o.k.

Harap dicatat bahwa SNI 1729 Pasal I1.1(1) secara spesifik mengabaikan persyaratan
kolom komposit dari SNI 2847 Pasal 10.13, maka tidak perlu memenuhi persyaratan
SNI 2847 Pasal 10.13.8 ketika mendesain kolom komposit dengan menggunakan SNI
1729 Pasal I.

235 dari 282


Jika digunakan spiral, persyaratan SNI 2847 Pasal 7.10 dan 10.9.3 harus dipenuhi
sesuai dengan Catatan Pengguna pada akhir SNI Pasal I2.1a.

(2) Pembatasan tambahan untuk ukuran sengkang ikat

Sengkang ikat dengan diameter 13 mm atau lebih besar diperlukan bila digunakan
tulangan memanjang diameter 29 mm atau lebih besar sesuai SNI 2847 Pasal 10.5.1

Digunakan sengkang ikat dbs = 10mm dengan tulangan memanjang db = 25 mm

(3) Jarak antara sengkang ikat seharusnya tidak melampaui 0,5 kali ukuran penampang
kolom terkecil

smaks = 0,5 min(h1,h2) = 300 mm < smaks, o.k.

(4) Selimut beton:

SNI 2847 Pasal 7.7 berisi persyaratan selimut beton. Untuk beton yang tidak
berhubungan langsung dengan cuaca atau dengan tanah, selimut beton untuk
sengkang ikat adalah 40 mm.

cover = 40 mm o.k.

(5) Pasang sengkang ikat sebagai tumpuan lateral tulangan memanjang AISC
Specification Commentary Section I2.1a merujuk Pasal 7 SNI 2847 untuk persyaratan
sengkang ikat tranversal. Berdasarkan SNI 2847 Pasal 7.10.5.3 dan gambar R7.10.5,
sengkang ikat diperlukan untuk menumpu tulangan memanjang yang ditempatkan
lebih dari 150 mm jarak bersih pada masing masing sisi dari tulangan yang ditumpu
lateral.Untuk tulangan sudut, tumpuan secara tipikal diberikan oleh sengkang ikat
keliling yang utama. Untuk tulangan di tengah, bisa digunakan sengkang ikat bentuk
miring.

Batas Tulangan memanjang dan baja struktural tercantum di SNI 1729 Pasal I1.1(4), I2.1
dan SNI 2847 sebagai berikut:

(1) Rasio minimum luas baja struktural: As / Ag > 0,01

As
= 0,018 o.k.
Ag

Rasio maksimum secara eksplisit untuk profil baja komposit tidak tersedia di SNI;
walaupun demikian, telah dicatat di literatur sekirat 8 % - 12% agar diperoleh batang
komposit yang ekonomis terhadap beban gravitasi (Leon and Hajjar, 2008).

(2) Rasio tulangan memanjang minimum: Asr / Ag > 0,004

Asr
= 0,0109 o.k.
Ag

(3) Rasio tulangan memanjang maksimum: Asr / Ag < 0,08

236 dari 282


Asr
= 0,0109 o.k.
Ag

Batas tulangan memanjang ini tercantum dalam SNI 2847 Pasal 10.9.1.
Direkomendasikan bahwa semua tulangan memanjang, termasuk tulangan tidak
menerus tidak digunakan dalam perhitungan kekuatan, jika rasio ini dimasukan karena
rasio tersebut dipertimbangkan sebagai suatu batas praktis untuk mengurangi kongesti
tulangan. Jika digunakan panjang lewatan, batas ini tereduksi menjadi 4% di luar
daerah lokasi pemutusan tulangan.

(4) Jumlah minimum tulangan memanjang:

SNI 2847 Pasal 1.9.2 mensyaratkan jumlah minimum 4 tulangan untuk komponen
pesegi atau bundar dengan sengkang ikat dan 6 tulangan untuk kolom berspiral.
Tujuan untuk penampang pesegi untuk memberikan minimum satu tulangan di tiap
sudut, maka untuk geometris tidak teratur dengan banyak sudut perlu tulangan
memanjang tambahan.

Dipasang 8 tulangan, o.k.

(5) Jarak bersih antara tulangan memanjang:

SNI 2847 Pasal 7.6.3 mensyaratkan jarak bersih antara tulangan adalah 1,5 db atau
37,5 mm

db
dc = cover + dbs + = 62,5 mm
2

h1 - d c
hs = = 268,75 mm
2

smin = max(1.5 db ,37.5 mm) = 37,5 mm

s = hs - db = 243,75 mm > smin = 37,5 mm

(6) Jarak bersih antara tulangan memanjang dan inti baja:

smin = max(1.5 db,37.5 mm) = 37,5 mm

Tulangan terdekat dengan profil baja adalah tulangan tengah dengan masing masing
sayap.

h2 d d b
s= - - - 62,5 mm = 50 mm > smin = 37,5 mm, o.k.
2 2 2

(7) Selimut beton untuk tulangan memanjang

SNI 2847 Pasal 7.7 memberikan persyaratan selimut beton minimum untuk tulangan.
Persyaratan selimut beton untuk sengkang ikat kolom dan tulangan utama adalah
sama, dan selimut sengkang ikat yang telah dihitung sebelum ini bisa diterima, maka
selimut beton untuk tulangan memanjang pun bisa diterima.

237 dari 282


Gaya Tekan yang bekerja

PD = 1 000 kN PL = 3 000 kN

Pr = 1,2 PD + 1,6 PL = 6 000 kN Pa = PD + PL = 4 000 kN

Kekuatan Tekan yang tersedia

Kekuatan Tekan Aksial Nominal tanpa mempertimbangkan efek kelangsingan, Pno dihitung
dari SNI 1729 Pasal I2.1b:

Pno = Fy As + fy Asr + 0,85 f c' Ac = 13 554,6709 kN

Karena panjang tak terbreis terhadap sumbu x-x dan y-y adalah sama, kolom akan tertekuk
terhadap sumbu yang memiliki kekakuan komposit terkecil, EIeff. Telah tercatat bahwa nilai
momen inersia yang dihitung sebelumnya untuk beton dan tulangan adalah sama untuk
kedua sumbu lentur, kolom akan tertekuk terhadap sumbu lemah dari profil baja. Icy, Isy dan
Isry akan digunakan untuk perhitungan efek kelangsingan menurut SNI 1729 Pasal I2.1b
sebagai berikut:

As
C1 = min 0,1+ 2 ,0.3 = 0,135
Ac + As

EIeff = E Isy + 0,5 E Isr + C1 Ec Icy = 4,48 x 104 kN m2

2E I eff
Pe = = 1,228 x 104 kN
1,0 L
2

Pno
= 1,104 < 2,25
Pe

Oleh karena itu, menurut SNI 1729 Persamaan I2-2

Pno

Pn = Pno 0,658 Pe = 8,54 x 103 kN (SNI 1729 Persamaan I2- 2)

DFBK DKI

Pn
c = 0,75 c Pn = 6,405 x 103 kN c = 2 = 4,27 x 103 kN
c

Pr Pa
rasioLRFD = = 0,937 rasioASD = = 0,937
c Pn Pn
c

238 dari 282


Perjanjian dalam pendetailan tipikal

Perencana dianjurkan untuk membaca AISC Design Guide 6 (Griffis, 1992) untuk diskusi
tambahan dan detail tipikal dari kolom komposit jenis ini yang secara eksplisit tidak
dijelaskan di contoh ini.

239 dari 282


CONTOH I.7 KOLOM KOMPOSIT TERISI BETON DAN PROFIL WF MENAHAN TARIK

Kontrol apakah batang komposit dengan panjang 4 m seperti yang diperlihatkan pada
gambar mampu menahan gaya tarik akibat PD dan PW dari kombinasi pembebanan yang
kritis sesuai SNI Pembebanan.

Mutu beton f c' = 35 MPa sedang Profil WF Fy = 250 MPa

Fy = 250 MPa Fu = 410 MPa fy = 400 MPa E = 200 000 MPa

f c'
f c' = 35 MPa E c = 4 700 MPa = 27 805,575 MPa
MPa

DATA PENAMPANG BETON

h1 = 600 mm h2 = 600 mm diameter tulangan db = 25 mm

selimut beton cover = 40 mm diameter sengkang dbs = 10 mm

1
Asri = d b2 = 490,874 mm2 Asr = 8 Asri = 3 926,9908 mm2
4

h1 h23
Ag = h1 h2 = 3,6 x 105 mm2 Ig = = 1,08 x 1010 mm4
12

DATA PENAMPANG WF 350X175x7x11

d = 350 mm bf = 175 mm tw = 7 mm tf = 11 mm h = 300 mm

As = 6314,2 mm2 Isy = 9,845 x 106 mm4 Zsx = 8,679 x 105 mm3 J = 1,94 x 105 mm4

Ac = Ag - As - Asr = 3,498 x 105 mm2 Cw = 2,829 x 1011 mm6

240 dari 282


DATA TULANGAN

db h
cs = cover + dbs + = 62,5 mm e= - c s = 87,5 mm
2 2
d b4
I sri = = 1,917 x 104 mm4
64

Isr = 8 (Isri) + 6 Asri e2 + 2 (Asri) (0 mm) = 2,27 x 107 mm4

Momen inersia beton untuk setiap sumbu dihitung sebagai berikut:

Icy = Ig - Isy - Isr = 1,077 x 1010 mm4 Icx = Icy

Pembatasan Pendetailan dan Bahan

Untuk pembatasan ini, bisa lihat pada Contoh I.9 untuk kasus batang komposit yang sama.
Gaya Tekan yang bekerja

PD = - 1 000 kN (tekan) PW = 3 000 kN (tarik)

Pr = 0,9 PD + 1,0 PW = 2 100 kN Pa = 0,6 (PD + PW) = 1 200 kN

Kekuatan Tarik yang tersedia

Kekuatan Tarik dihitung sesuai SNI 1729 Pasal I2.1c.

Pn = Fy As + fy Asr = 3,149 x 103 kN (SNI 1729 Persamaan I2 - 8)

DFBK DKI

Pn
t = 0,90 t Pn = 2834,4117 kN t = 1,67 = 1885,8361 kN
t

Pr Pa
rasioLRFD = = 0,741 rasioASD= = 0,636
t Pn Pn
t

241 dari 282


CONTOH I.8 BATANG KOMPOSIT WF TERBUNGKUS BETON YANG MENAHAN GAYA
TEKAN, MOMEN LENTUR DAN GESER

Kontrol apakah batang komposit dengan panjang 6 m seperti yang diperlihatkan pada
gambar mampu menahan gaya tekan, geser dan momen dari hasil Analisis Langsung
meurut SNI 1729 Pasal C untuk kombinasi pembebanan yang kritis sesuai SNI 1727
Pembebanan.

Mutu beton f c' = 35 MPa sedang Profil PSB Fy = 250 MPa

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa fy = 400 MPa

f c'
f c' = 35 MPa E c = 4700 MPa = 27 805,575 MPa L=6m
MPa

Pr = 5 507 kN Pa = 4 387 kN

Mr = 135,9 kN m Ma = 103 kN m

Vr = 326 kN Va = 250 kN

DATA PENAMPANG BETON

h1 = 600 mm h2 = 600 mm diameter tulangan db = 25 mm

selimut beton cover = 40 mm diameter sengkang dbs = 10 mm

1
Asri = d b2 = 490,874 mm2 Asr = 8 Asri = 3 926,9908 mm2
4

h1 h23
Ag = h1 h2 = 3,6 x 105 mm2 Ig = = 1,08 x 1010 mm4
12

242 dari 282


DATA PENAMPANG WF 350X175x7x11

d = 350 mm bf = 175 mm tw = 7 mm tf = 11 mm h = 300 mm

As = 6 314,2 mm2 Isy = 9,845 x 106 mm4 Zsx = 8,679 x 105 mm3

Ssx = 7,748 x 105 mm3 Ssy = 1,125 x 105 mm3 J = 1,94 x 105 mm4

Ac = Ag - As - Asr = 3,498 x 105 mm2 Cw = 2,829 x 1011 mm6

DATA TULANGAN

db h
cs = cover + dbs + = 62,5 mm e= - c s = 87,5 mm
2 2

d b4
Isri = = 1,917 x 104 mm4
64

Isr = 8 (Isri) + 6 Asri e2 + 2 (Asri) (0 mm) = 2,27 x 107 mm4

Luas dari tulangan yang terletak di garis sumbu penampang komposit, Asrs, dihitung sebagai
berikut:

Asrs = 2(Asri) = 981,748 mm2

Untuk penampang ini, Asrs adalah sama terhadap sumbu x-x atau y-y.

Momen inersia beton untuk setiap sumbu dihitung sebagai berikut:

Icy = Ig - Isy - Isr = 1,077 x 1010 mm4 Icx = Icy

Klasifikasi Penampang terhadap tekuk lokal

Sesuai dengan SNI 1729 Pasal I1.2, efek tekuk lokal tidak perlu dipertimbangkan untuk
batang komposit terbungkus beton, maka semua penampang komposit yang terbungkus
beton diperlakukan sebagai penampang kompak untuk perhitungan kekuatan.

Batasan Bahan dan Pendetailan

Bisa dilihat pada Contoh I.9 tentang kontrol pembatasan pendetailan dan bahan.

Interaksi gaya aksial dan lentur

Interaksi antara gaya aksial dan lentur pada batang komposit diatur oleh SNI 1729 Pasal I5,
yang untuk batang kompak, mengijinkan digunakannya metode kompatibilitas regangan
atau metode distribusi tegangan plastis.

Metode kompatibilitas regangan adalah pendekatan yang umum yang memperbolehkan


pembentukan diagram interaksi berdasarkan konsep yang sama seperti pada desain beton
bertulang. Penerapan metode kompatibilitas regangan diperlukan untuk penampang tidak
teratur atau nonsimetris, dan aplikasi umumnya bisa dilihat dalam buku teks beton bertulang
dan tidak akan didiskusikan lagi disini.

243 dari 282


Metode distribusi tegangan plastis didiskusikan dalam AISC Specification Commentary
Section I5 yang memberikan 4 prosedur. Prosedur pertama, Metode 1, memerlukan
persamaan interaksi dari Pasal H1. Metode 2, melibatkan pembentukan kurva interaksi
sebagian linier dengan menggunakan persamaan kekuatan plastis yang tersedia di Gambar
I-1 yang ditempatkan dibagian depan Bab I Contoh Desain. Prosedur ketiga, Metode 2-
Sederhana, adalah reduksi dari kurva interaksi sebagian linier yang memperbolehkan
penggunaan persamaan interaksi yang kurang konservatif dari pada yang tersedia dalam
bab H. Prosedur ke empat dan Final, Metode 3, menggunakan AISC Design Guide 6 (Griffis,
1992).

Untuk contoh desain, masing-masing penerapan prosedur distribusi plastis akan ditinjau dan
dibandingkan. Metode 3 tidak diperlihatkan karena tidak bisa diterapkan terhadap
penampang yang sedang dipertimbangkan karena luas profil baja relatif lebih kecil dari pada
batas minimum 4% luas kotor penampang komposit yang tersedia dalam SNI lama yang
berdasarkan Design Guide 6.

Metode 1: Persamaan Interaksi Pasal H1

Metode paling langsung dan konservatif dari menaksir efek interaksi melalui penggunaan
persamaan interaksi dari SNI 1729 Pasal H1. Perhitungan dilakukan secara eksplisit sesuai
SNI 1729 Pasal I.

Kekuatan Tekan yang tersedia

Kekuatan Tekan Aksial Nominal tanpa mempertimbangkan efek kelangsingan, Pno dihitung
dari SNI 1729 Pasal I2.1b:

Pno = Fy As + fy Asr + 0,85 f c' Ac = 13 554,6709 kN

Karena panjang tak terbreis terhadap sumbu x-x dan y-y adalah sama, kolom akan tertekuk
terhadap sumbu yang memiliki kekakuan komposit terkecil, EIeff. Telah tercatat bahwa nilai
momen inersia yang dihitung sebelumnya untuk beton dan tulangan adalah sama untuk
kedua sumbu lentur, kolom akan tertekuk terhadap sumbu lemah dari profil baja. Icy, Isy dan
Isry akan digunakan untuk perhitungan efek kelangsingan menurut SNI 1729 Pasal I2.1b
sebagai berikut:

As
C1 = min 0,1+ 2 ,0.3 = 0,135
Ac + As

EIeff = E Isy + 0,5 E Isr + C1 Ec Icy = 4,48 x 104 kN m2

2E I eff
Pe = = 1,228 x 104 kN
1,0 L
2

Pno
= 1,104 < 2,25
Pe

244 dari 282


Oleh karena itu, menurut SNI 1729 Persamaan I2-2

Pno

Pn = Pno 0,658 Pe = 8,54 x 103 kN (SNI 1729 Persamaan I2- 2)

Menghitung Mn

Momen yang berkerja ditahan oleh kuat lentur dari penampang komposit terhadap sumbu
kuat (x-x). Kekuatan penampang lentur murni dihitung menggunakan persamaan dari
Gambar I-1a yang dibagian depan Pasal Contoh Desain untuk titik B. Harap dicatat bahwa
perhitungan kuat lentur pada titik B memerlukan terlebih dahulu perhitungan kuat lentur
pada titik D sebagai berikut:

h2
Z r = Asr - Asrs - c s = 6,995 x 105 mm3
2

h1 h22
Zc = - Zsx - Zr = 5,243 x 107 mm3
4

Zc
MD = Zsx Fy + Zr fy + 0,85 f c' = 1,277 x 103 kN m
2

Asumsi hn di daerah sayap (d/2 - tf < hn < d/2)

0,85 f c' Ac + As - d bf + Asrs - 2 F y As - d bf - 2 f y Asrs


hn = = 177,159 mm
2 0,85 f c' h1 - bf + 2 Fy bf
Cek asumsi:

d
hn = 177,159 mm > = 175 mm
2

maka :

0,85 f c' Ac + As + Asrs - 2 Fy As - 2 f y Asrs


hn = = 187,112 mm
2 x 0,85 f c' h1

Zsn = Zsx = 8,679 x 105 mm3

Zcn = h1 hn - Zsn = 2,014 x 107 mm3


2

0,85 f c' Z cn
M n = M D - Fy Z sn - = 760,172 kN m
2

DFBK

c = 0,75 b = 0,9

245 dari 282


Pc = c Pn = 6,405 x 103 kN Mc = b Mn = 684,155 kN m

Pr
= 0,86 > 0,2
Pc

Pr 8 M r
rasioLRFD = = 1,036
Pc 9 M c

DKI

Pn
c = 1,67 Pa = 4,387 x 103 kN Pc = = 5,114 x 103 kN
c

Mn
b =1,67 Ma = 103 kN m Mc = = 455,193 kN m
b
Pa
= 0,858 > 0,2
Pc

Pa 8 M a
rasioASD = + = 1,059
Pn 9 M c
c

Dengan menggunakan DFBK, Metode 1 menunjukan bahwa penampang tidak kuat


terhadap beban terfaktor. Perencana bisa memilih penampang baru yang memenuhi kontrol
interaksi atau melakukan analisis ulang dengan menggunakan metode desain kurang
konservatif seperti Metode 2. Metode ini akan dijelaskan sebagai berikut.

Metode 2: Kurva Interaksi dari Model Distribusi Platis

Prosedur untuk membuat kurva interaksi dengan menggunakan model distribusi tegangan
plastis diperlihatkan dalam gambar di bawah ini (AISC Specification Commentary C-I5.2).
Kekuatan material
(persamaan kekuatan)
Kelangsingan
(kurva kolom)

Desain , - Metode 2

= Reduksi kelangsingan
= A/A

Gambar C-15.2 Diagram interaksi untuk balok-kolom komposit Metode 2

246 dari 282


Berdasarkan Gambar C.I5.2, permukaan interaksi kekuatan nominal A,B,C,D,E mula mula
dihitung dengan menggunakan persamaan dari gambar I-1a yang tercantum dalam
introduksi Bab I Contoh Desain. Kurva ini mewakili kekuatan batang kolom pendek tanpa
memperhitungkan efek panjang batang. Suatu faktor reduksi kelangsingan, , dihitung dan
dipasang kesetiap titik untuk membuat permukaan A', B', C', D', E'. Kemudian ketahanan
yang sesuai atau faktor keamanan diterapkan untuk membuat permukaan desain A'', B'', C'',
D'', E''. Akhirnya, gaya dan momen terfaktor hasil kombinasi pembebanan di plot dalam
permukaan desain, dan batang bisa diterima jika semua hasil plot terletak didalam kurva
desain. Langkah perhitungan akan dijelaskan detail dengan perhitungan sebagai berikut.

Langkah 1: Buat permukaan interaksi kekuatan nominal A, B, C, D, E tanpa


memperhitungkan efek kelangsingan.

Dengan menggunakan persamaan persamaan yang tersedia dalam Gambar I-1a untuk
lentur terhadap sumbu x-x :

Titik A (gaya tekan murni)

P1 = Fy As + 0,85 f c' Ac = 11 983,875 kN

M1 = 0 kN m

Titik D (kekuatan momen nominal maksimum)

0,85 f c' Ac
P3 = = 5 202,662 kN
2

Zsx = 8,679 x 105 mm3

Zc = 5,243 x 107 mm3

Zc
M3 = Zsx Fy + Zr fy + 0,85 f c' = 1 276,708 kN m
2

Titik B (lentur murni)

P4 = 0 kN

0,85 f c' Z cn
M4 = MD - Fy Zsn - = 760,172 kN m
2

Titik C ( titik antara)

P2 = 0,85 f c Ac = 1,041 x 104 kN


'

M2 = M4 = 760,172 kN m

Titik yang dihitung di plot untuk membentuk permukaan interaksi kuat nominal kolom
pendek.

247 dari 282


Langkah 2: Buat permukaan kuat nominal A', B', C', D' ,E' yang memperhitungkan efek
kelangsingan.

Faktor reduksi kelangsingan, , dihitung untuk titik A dengan menggunakan SNI 1729
Pasal I2.1 sesuai dengan AISC Specification Commentary Section I5

Pno = P1 = 1,198 x 104 kN

As
C1 = min 0.3, 0.1+ 2 = 0,135
Ac + As

EIeff = E Isy + E Isr + C1 Ec Icy = 4,707 x 104 kN m2

2E I eff
Pe = = 1,29 x 104 kN
1,0 L
2

Pno
= 0,929 < 2,25
Pe

Pno

Pn = Pno 0,658 Pe = 8 124,22385 kN SNI 1729 Persamaan I2-2


P
n = 0,678
Pno

248 dari 282


Berdasarkan AISC Specification Commentary Section I5, reduksi kelangsingan yang sama
diterapkan untuk titik-titik yang lain pada permukaan interaksi.

PR1 = P1 MR1 = M1

PR2 = P2 MR2 = M2

PR3 = P3 MR3 = M3

PR4 = P4 MR4 = M4

Nilai kekuatan aksial yang telah dimodifikasi, diplot dengan kekuatan lentur yang telah
dihitung sebelumnya untuk membentuk permukaan interaksi nominal yang menperhitungkan
efek kelangsingan.

Pertimbangan efek kelangsingan menghasilkan suatu reduksi dari kurva kekuatan nominal.
Pergerakan vertikal ini membentuk suatu zona tidak aman, dimana kurva kapasitas lentur
kuat nominal dengan efek kelangsingan melampaui kapasitas penampang. Aplikasi
ketahanan atau faktor keamanan mereduksi zona tidak aman ini sebagaimana dijelaskan di
step berikutnya. walaupun demikian, perencana harus menyadari kemungkinan terjadinya
ketidak amanan dalam desain dengan beban yang mendekati kapasitas lentur dari
penampang. Alternatif lain, gunakan Metode 2 yang disederhanakan, yang mengeleminasi
kemungkinan ini bersama sama.

Langkah 3: Buat permukaan interaksi desain dan check kekuatan batang komposit Langkah
terakhir dalam Prosedur Metode 2 adalah mereduksi semua titik dengan faktor reduksi
kapasitas atau faktor keamanan yang sesuai.

DFBK

Kekuatan Tekan Desain

c = 0,75

Pu1 = c PR1 Pu2 = c PR2 Pu3 = c PR3 Pu4 = c PR4

249 dari 282


Kekuatan Lentur Desain

b = 0,9

Mu1 = b M1 Mu2 = b M2 Mu3 = b M3 Mu4 = b M4

Dengan mengeplot besar Pr dan Mr ke dalam kurva interaksi desain yang diperoleh dari
kombinasi pembebanan yang kristis, bisa dilihat bahwa (Mr , Pr ) ada di dalam kurva, berarti
batang komposit mampu menahan pembebanan yang ada.

Metode 2 yang disederhanakan

Versi sederhana dari Metode 2 adalah dengan menghapus titik D dari permukaan interaksi,
sehingga tinggal titik A", B",dan C''

Jadi

Pu1 = Pu1 Mu1 = Mu1 Titik A

Pu2 = Pu2 Mu2 = Mu2 Titik C

Pu3 = Pu4 Mu3 = Mu4 Titik B

Pr = 5507 kN Mr = 135,9 kN m

Dengan mereduksi jumlah titik interaksi, harus dilakukan kontrol interaksi bilinier yang
didefinisikan AISC Specification Commentary Equations C-I5-1a dan C-I5-1b.

DFBK

Pr = 5 507 kN > Pu2 = 5 290,559 kN

Gunakan persamaan C-I5-1b

250 dari 282


Pr - Pu 2 M
rasioLRFD = + r = 0,468 rasioLRFD = 0,468
Pu 1 - Pu 2 Mu 2

Jadi batang kuat terhadap beban yang bekerja

Perbandingan antara Metode

Dari gambar di atas, terlihat konservatif bila persamaan interaksi Bab H, batang komposit
tidak kuat, Metode 2 memberikan kekuatan yang tertinggi; walaupun demikian, Metode 2
penyederhanaan juga menghasilkan penampilan kurva desain yang baik. Perbandingan
antara metode dengan mudah dilihat jika kurva desain masing masing metode diperlihatkan
dalam satu grafik seperti gambar di bawah ini.
Kekuatan Tekan (MPa)

M u , Pu

Metode 2-Disederhanakan

Metode 1 Interaksi Bab H

Kekuatan Lentur (kN m)

Gambar I.11-6 Perbandingan dari metode interaksi (DFBK)

Dari gambar bisa dilihat, kondisi konservatif dari penggunaan Bab H SNI 1729. Metode 2
memberikan nilai kekuatan yang tertinggi, walaupun demikian, Metode 2-yang
disederhanakan representasi yang baik dari kurva desain lengkap.

Kuat Geser yang tersedia

SNI 1729 Pasal I4.1 memberikan 3 metode untuk menghitung kekuatan geser tersedia dari
batang komposit ini: kekuatan geser yang tersedia dari penampang baja sendiri sesuai
Pasal G SNI 1729, kekuatan geser yang tersedia dari beton bertulang sendiri sesuai SNI
2847 atau kekuatan geser yang tersedia dari penampang baja plus tulangan dengan
mengabaikan kontribusi dari beton.

Opsi 1 - Kekuatan Geser Penampang baja yang tersedia

Profil ini memenuhi kriteria SNI 1729 Pasal G2.1(a) sesuai dengan Catatan Pengguna pada
akhir pasal. Sebagaimana diperlihatkan dalam Contoh I.9, digunakan sengkang ikat D10-
300 untuk memenuhi persyaratan pendetailan dari SNI 1729. Kekuatan geser nominal Vn,
dari batang komposit, dihitung sebagai berikut:

251 dari 282


Gunakan SNI persamaan G2-3 SNI 1729, Spesifikasi untuk bangunan gedung baja
struktural.

Cv = 1 Persamaan G2-3

Aw = d tw = 2,45 x 103 mm2

Kekuatan Geser nominal dihitung sebagai:

Vn_steel = 0,6 Fy Aw Cv = 367,5 kN Persamaan G2-1 SNI 1729

DFBK

Vr
v = 1,0 rasio = = 0,887 o.k.
vVn_steel

DKI

Va
v = 1,5 rasio = = 1,02 o.k.
V n_steel
v

Opsi 2 - Kekuatan Geser beton bertulang yang tersedia

Batang komposit tidak memiliki tulangan, oleh karena itu perhitungan geser untuk beton
bertulang tidak tepat untuk kasus ini, kuat geser desain untuk beton tanpa tulangan dengan
menggunakan Pasal 22 SNI 2847 dihitung sebagai berikut:

v = 0,75 untuk beton tanpa tulangan dari SNI 2847 Pasal 9.3.5

= 1 untuk beton normal dari SNI 2847 Pasal 8.6.1


bw = h1 d = h2 - cs = 537,5 mm

1 f c'
Vc = bw d MPa = 317,989 kN SNI 2847 Persamaan 22-9
6 MPa

v Vc = 238,492 kN Vr = 326 kN

DFBK

Vr - v Vc
Av = = 0,543 mm
v f y d

0,35 MPa b f c' bw


Avs_min = max w
, 0.062 MPa = 0,55 mm
fy MPa fy

Av = max Avs_min ,Av = 0,55 mm

252 dari 282


1
digunakan 2@D10 Avs = 2 d bs2 = 157,08 mm2
4

Avs d
s = min , = 268,75 mm digunakan 2@D10-250
Av 2

DKI
Vc
Va -
Va = 250 kN v = 2 Av = v = 0,847 mm
fyd

v

Av = max Avs_min ,Av = 0,847 mm

1
digunakan 2@D10 Avs = 2 d bs2 = 157,08 mm2
4

Avs d
s = min , = 185,55 mm digunakan 2@D10-180
Av 2

Batas Tullangan Geser Maksimum

Avs f y d
Vs = = 182,011 kN
s
1 f c'
Vs_max = MPa bw d = 635,979 kN > Vs
3 MPa

Jadi jarak antara sengkang memenuhi syarat

Opsi 3 - Menghitung Kekuatan Geser yang tersedia dari profil baja dan tulangan

Prosedur ketiga mengkombinasikan kuat geser dari tulangan dan profil baja dengan
mengabaikan kontribusi beton. SNI 1729 Pasal I4.1(c) memberikan suatu kombinasi
ketahanan dan faktor keamanan untuk prosedur ini. Harap dicatat bahwa kombinasi tahanan
dan faktor keamanan lebih diutamakan dibandingkan faktor faktor dalam Pasal G SNI 1729
yang digunakan untuk penampang baja yang dibungkus beton saja dalam opsi 1. Jumlah
tulangan trasversal yang diperlukan untuk ketahanan geser dihitung sebagai berikut:

Persyaratan untuk Ketahanan Geser

Kekuatan geser nominal dari penampang baja telah dihitung:

Vn_steel = 367,5 kN

253 dari 282


Persyaratan sengkang pengikat untuk ketahanan geser dihitung sesuai SNI 2847 Pasal 11
dan SNI 1729 Pasal I4.1(c), sebagai berikut:

DFBK

Vr = 326 kN

Vr - v Vn_steel
Av = = 0,312 mm
v f y d

0,35 MPa b f c' bw


Avs_min = max w
, 0.062 MPa = 0,55 mm
fy MPa fy

Av = max Avs_min ,Av = 0,55 mm

1
digunakan 2@D10 Avs = 2 d bs2 = 157,08 mm2
4

Avs d
s = min , = 268,75 mm digunakan 2@D10-250
Av 2

DKI
V
Va - n_steel
Va = 250 kN v = 2 Av = v = 0,616 mm
fy d

v

Av = max Avs_min ,Av = 0,616 mm

1
digunakan 2@D10 Avs = 2 d bs2 = 157,08 mm2
4

Avs d
s = min , = 254,884 mm digunakan 2@D10-250
Av 2

Ringkasan dan Perbandingan dari Perhitungan Kekuatan Geser

Penggunaan penampang baja saja adalah merupakan cara yang sangat berguna untuk
menghitung kekuatan geser yang tersedia dan memperbolehkan penggunaan jarak
sengkang ikat yang mungkin lebih besar dari pada tahanan geser dari SNI 2847. Ketika
kekuatan penampang baja saja tidak kuat, Opsi 3 umumnya menghasilkan reduksi
persyaratan tulangan geser dibandingkan Opsi 2.

254 dari 282


CONTOH I 9 ANGKUR BAJA DI KOMPONEN KOMPOSIT

Diketahui angkur kepala paku baja Tipe B yng menahan gaya akibat beban mati dan beban
hidup seperti diperlihatkan pada gambar di bawah. Angkur merupakan bagian dari suatu
sistim komposit yang di desain dengan mengunakan angkur baja dalam komponen komposit
sesuai SNI 1729 Pasal I8.3.

Angkur kepala paku baja dibungkus dengan beton bertulang normal dengan f c' = 30 MPa
Sesuai AWS D1.1, Angkur kepala paku baja harus dibuat dari bahan yang memenuhi
persyaratan ASTM A108, tegangan tarik minimum Fu = 450 MPa.

Angkur ditempatkan jauh dari tepi sehingga pecahnya beton akibat geser bukan merupakan
kondisi batas, dan angkur terdekat berjarak 600 mm. Beton dianggap tidak retak.

f c'
f c' = 30 MPa E c = 4 700 MPa = 2,574 x 104 MPa
MPa

Fu = 450 MPa db = 19 mm

PD = 10 kN PL = 24 kN

VD = 7 kN VL = 18 kN

Solusi:

SNI 1729 Pasal I8.3 memberikan rasio panjang minimum terhadap diameter untuk angkur
yang mengalami geser, tarik, dan interaksi geser dan tarik untuk beton normal dan beton
ringan. Rasio ini di ringkas di Catatan Pengguna pada Pasal I8.3. Untuk beton normal:

h
8 h = 8 db = 152 mm
db

Panjang ini diukur dari dasar angkur kepala paku baja sampai dengan bagian atas kepala
setelah pemasangan. Berdasarkan data dari pabrik, panjang standar adalah

3
hs = 6 in.+ in. = 157,162 mm untuk mengantisipasi hilangnya sebagian dari
16
panjang akibat terbakar waktu dipasang

255 dari 282


Kekuatan Tarik dan Kekuatan Geser yang terjadi

DFBK DKI

Quv = 1,2 VD + 1,6 VL = 37,2 kN Qav = VD + VL = 25 kN

Qut = 1,2 PD + 1,2 PL = 40,8 kN Qat = PD + PL = 34 kN

Kekuatan Geser yang tersedia:

Sesuai dengan soal diatas bahwa tidak ada beton yang pecah, karena itu digunakan SNI
1729 persamaan I8-3:

1
Asa = d b2 = 283,529 mm2 v = 0,65
4

Qnv = Fu Asa = 127,588 kN (SNI persamaan I8-3)

Q nv
v Qnv = 82,932 kN v = 2,31 = 55,233 kN
v

Kekuatan Tarik yang tersedia

Kekuatan Tarik Nominal dari angkur kepala paku dihitung dengan menggunakan SNI 1729
Persamaan I8-4 dengan pembatasan jarak dan tepi dalam SNI 1729 Pasal I8.3b dipenuhi
sebagai berikut:

(1) Jarak minimum dari pusat angkur ke tepi bebas:

1,5 h = 228 mm karena tidak ada tepi bebas, ketentuan ini tidak dipakai

(2) Jarak minimum antara pusat angkur yang bersebelahan:

3 h = 456 mm < 600 mm, o.k.

Persaman I8-4 digunakan sebagai berikut:

Qnt = Fu Asa = 127,588 kN

DFBK DKI

t = 0,75 t = 2

Q nt
t Qnt = 95,691 kN = 63,794 kN
t

256 dari 282


Interaksi dari Geser dan Tarik

Batas pendetailan pada jarak tepi dan jarak antara angkur dalam SNI 1729 Pasal I8.3c
untuk interaksi tarik dan geser adalah sama seperti pembahasan sebelumnya yang
dijelaskan terpisah untuk masing masing geser atau tarik sendiri.

Kontrol

DFBK

5 5
Q 3 Quv 3
rasioLRFD = ut + = 0,504
t Qnt v Qnv

DKI

5 5
3 3
Q Q
rasioASD = at + av = 0,617
Qnt Qnv

t v

Jadi angkur kepala paku baja D19 kuat menerima gaya yang terjadi

Batas Penerapan

Aplikasi angkur baja dalam komponen komposit memiliki batasan yang ketat sebagaimana
tertulis pada Catatan Pengguna pada awal SNI 1729 Pasal I8.3.

Persyaratan-persyaratan ini tidak berlaku untuk desain balok komposit tipikal juga tidak
berlaku untuk konstruksi hibrid dimana baja dan beton tidak menahan beban bersama-sama
seperti pada pelat yang terbenam. Contoh ini dimaksudkan hanya untuk sekedar ilustrasi
perhitungan sehubungan dengan suatu angkur terisolasi dengan bagian dari sistim komposit
yang sesuai.

257 dari 282


Bab J Desain Sambungan

Bab J SNI 1729, Spesifikasi untuk bangunan gedung baja struktural membahas desain dan
review sambungan. Fokus utama bab ini adalah desain sambungan dilas dan berbaut.
Persyaratan desain untuk pengisi, splices, dasar kolom, gaya terpusat, batang angkur dan
bagian-bagian berulir lainnya juga dibahas. Persyaratan khusus untuk sambungan yang
memikul fatik tidak tercakup dalam bab ini.

258 dari 282


CONTOH J.1 LAS SUDUT YANG MENGALAMI GESER LONGITUDINAL

Sebuah pelat dengan lebar 400 mm dan tebal 6 mm disambung ke pelat dengan tebal 10
mm menggunakan las sudut. Material baja Fy = 250 MPa. Elektroda las E70xx.

Periksa kekuatan sambungan tersebut

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

Ukuran pelat: Bp = 400 mm tp = 6 mm

Elektroda las: FEXX = 482 MPa

Gaya tarik nominal: PD = 120 kN PL = 360 kN

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kuat lentur rencana minimum:

Metode DFBK: Pu = 1,2 PD + 1,6 PL = 720 kN

Metode DKI: Pa = PD + PL = 480 kN

Ukuran las maksimum dan minimum

Karena tebal pelat yang overlap adalah 6 mm, maka ukuran las maksimum yang dapat
digunakan tanpa ketentuan khusus dalam Pasal J2.2b, adalah 4 mm yang dapat dipasang
dalam posisi horizontal.

Berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Tabel J2.4,
ukuran minimum las sudut berdasarkan ketebalan pelat 6 mm adalah 3 mm.

Panjang las yang dibutuhkan

Kekuatan las nominal per mm panjang ditentukan dari Pasal J2.4(a) adalah:

259 dari 282


Gunakan ukuran las: w = 4 mm

Fnw = 0,6 FEXX = 289,2 MPa

w kN
Rn = Fnw = 0,818 mm
2

Metode DFBK:

Pu
= 0,75 Lreq = = 1173,621 mm atau diambil sebesar 600 mm per sisi
R n

Metode DKI:

Pa
= 2,00 Lreq = = 1173,621 mm atau diambil sebesar 600 mm per sisi
Rn

Gunakan Lw = 600 mm

Berdasarkan Pasal J2.2b, untuk las sudut yang hanya dipasang dalam arah longitudinal
pada pelat yang mengalami tarik, panjang masing-masing las sudut tidak boleh lebih kecil
daripada jarak tegak lurus antara kedua sisi las tersebut.

Lw = 600 mm > Bp = 400 mm (o.k.)

Berdasarkan Pasal J2.2b, periksa rasio panjang terhadap ukuran las, karena merupakan las
sudut yang dibebani bagian ujungnya.

Lw
= 150 > 100
w

Sehingga Persamaan J2-1 harus diaplikasikan, dan panjang las meningkat, karena nilai
akan mereduksi kekuatan yang tersedia.

Coba panjang las, Lw = 700 mm


Lw
= 175 > 100
w

untuk rasio ini:

Lw
1,2 - 0,002 = 0,85 < 1,0
w

Pemeriksaan ulang kekuatan las yang direduksi:

Rnw = Rn 2 Lw = 973,398 kN

260 dari 282


Metode DFBK:

= 0,75 Rnw = 730,048 kN > Pu = 720 kN

Pu
= 0,986 < 1,00 (o.k.)
Rnw

Metode DKI:

Rnw
= 2,00 = 486,699 kN > Pa = 480 kN

Pa
= 0,986 < 1,00 (o.k.)
Rnw

261 dari 282


CONTOH J.2 LAS SUDUT YANG DIBEBANI DALAM ARAH MIRING

Desain sambungan las sudut pada sisi pelat buhul dengan tebal 20 mm yang menahan gaya
200 kN akibat beban mati dan 600 kN akibat beban hidup yang berarah 60 o terhadap sumbu
las. Asumsikan tebal dan panjang balok dan pelat buhul mencukupi.

Elektroda las E70xx.

Solusi:

Tebal pelat buhul: tp = 20 mm

Elektroda las: FEXX = 482 MPa

Gaya tarik nominal: PD = 200 kN PL = 600 kN

Arah gaya: = 60o


Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

Metode DFBK: Pu = 1,2 PD + 1,6 PL = 1200 kN

Metode DKI: Pa = PD + PL = 800 kN

Asumsikan las sudut dengan ukuran 8 mm dipasang di kedua sisi pelat.

Berdasarkan SNI 1729, Spesifikasi untuk gedung baja struktural Tabel J2.4, ukuran
minimum las sudut berdasarkan ketebalan pelat 20 mm adalah 8 mm.

Gunakan ukuran las: w = 8 mm

Kekuatan geser las sudut per mm panjang

w
Awe = = 5,657 mm
2
= 0,60FEXX 1+0,5sin = 405,737 MPa
1,5
Fnw

kN
Rn = Fnw Awe = 2,295
mm

262 dari 282


Panjang las yang dibutuhkan

Metode DFBK:

Pu
= 0,75 Lreq = = 697,108 mm atau diambil sebesar 350 mm per sisi
R n

Metode DKI:

Pa
= 2,00 Lreq = = 697,108 mm atau diambil sebesar 350 mm per sisi
Rn

263 dari 282


CONTOH J.3 KOMBINASI TARIK DAN GESER PADA SAMBUNGAN TIPE TUMPU

Baut A325-N berdiameter 20 mm menahan gaya tarik sebesar 14 kN akibat beban mati dan
42 kN akibat beban hidup, serta gaya geser sebesar 6 kN akibat beban mati dan 18 kN
akibat beban hidup. Periksa kekuatan baut terhadap kombinasi tegangan-tegangan yang
terjadi berdasarkan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
Persamaan J3-3a dan J3-3b.

Solusi:

Gaya tarik nominal: TD = 14 kN TL = 42 kN

Gaya geser nominal: VD = 6 kN VL = 18 kN

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

Metode DFBK: Tu = 1,2 TD + 1,6 TL = 84 kN

Vu = 1,2 VD + 1,6 VL = 36 kN

Metode DKI: Ta = TD + TL = 56 kN

Va = VD + VL = 24 kN

Kekuatan tarik baut

Baut yang mengalami kombinasi tarik dan geser, kekuatan tarik baut ditentukan
berdasarkan kondisi batas tarik dan geser, berdasarkan SNI 1729, Spesifikasi untuk gedung
baja struktural J3.7 sebagai berikut.

Berdasarkan Tabel J3.2,

Fnt = 620 MPa Fnv = 372 MPa

Diameter baut nominal: db = 20 mm


Luas penampang baut nominal: Ab = d b2 = 314,159 mm2
4
Tegangan geser yang tersedia ditentukan sebagai berikut dan harus sama atau lebih besar
daripada tegangan geser perlu.

Metode DFBK:

Vu
= 0,75 Fnv = 279 MPa > frv.LRFD = = 114,592 MPa
Ab

Metode DKI:

Fnv Va
= 2,00 = 186 MPa > frv.ASD = = 76,394 MPa
Ab

264 dari 282


Kekuatan tarik baut yang mengalami kombinasi tarik dan geser sebagai berikut:

Metode DFBK

Fnt
Fnt.LRFD
'
= 1,3Fnt - f = 551,352 MPa < Fnt = 620 MPa
Fnv rv.LRFD

Rn.LRFD = F'nt.LRFD Ab = 173,212 kN

Untuk kombinasi tarik dan geser,

= 0,75 dari SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal
J3.7

Kekuatan tarik desain:

Rn.LRFD = 129,909 kN > Tu = 84 kN

Tu
= 0,647
Rn.LRFD

Metode DKI

Fnt
Fnt.ASD
'
=1,3Fnt - f rv.ASD = 551,352 MPa < Fnt = 620 MPa
Fnv

Rn.ASD = F'nt.ASD Ab = 173,212 kN

Untuk kombinasi tarik dan geser,

= 2,00 dari SNI 1729, Spesifikasi untuk gedung baja struktural Pasal J3.7

Kekuatan tarik desain:

Rn.ASD
= 86,606 kN > Ta = 56 kN

Ta
= 0,647 < 1,00 (o.k.)
Rn.ASD

265 dari 282


CONTOH J.4A SAMBUNGAN SLIP-KRITIS DENGAN LUBANG SLOT PENDEK

Tentukan jumlah baut ASTM A325 berdiamater 20 mm dengan permukaan Kelas A yang
dibutuhkan untuk memikul beban-beban seperti gambar di bawah. Pelat penyambung
memiliki lubang slot pendek melintang arah beban dan tidak ada pengisi. Tentukan jumlah
baut berdasarkan ketahanan slip saja.

Solusi:

Gaya tarik nominal: TD = 90 kN TL = 270 kN

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

Metode DFBK: Tu = 1,2 TD + 1,6 TL = 540 kN

Metode DKI: Ta = TD + TL = 360 kN

Berdasarkan SNI 1729 J3.8(a), ketahanan slip yang tersedia berdasarkan kondisi batas slip
untuk lubang standar dan slot pendek yang tegak lurus arah beban, sebagai berikut:

Metode DFBK: = 1,00 Metode DKI: = 1,5

= 0,30 untuk permukaan Kelas A

Dn = 1,13

hf = 1,0 terdapat tidak lebih dari satu pengisi

Tb = 142 kN berdasarkan Tabel J3.1

ns = 2 jumlah bidang geser

Rn = Dn hf Tb ns = 96,276 kN

266 dari 282


Jumlah baut yang dibutuhkan:

Tu
Metode DFBK: nb = = 5,609 gunakan 6 baut
R n

T a
Metode ASD: nb = = 5,609 gunakan 6 baut
Rn

Catatan:
Dalam perencanaan sambungan, kondisi batas geser baut, tumpu baut, leleh tarik, putus tarik, dan
geser blok harus diperhitungkan

CONTOH J.4B SAMBUNGAN SLIP-KRITIS DENGAN LUBANG SLOT PANJANG

Ulangi perhitungan Contoh J.4A tetapi pelat penyambung memiliki lubang slot panjang
searah beban.

Baut Db = 20 mm

Solusi:

Gaya tarik nominal: TD = 85 kN TL = 255 kN

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

Metode DFBK: Tu = 1,2 TD + 1,6 TL = 510 kN

Metode DKI: Ta = TD + TL = 340 kN

Berdasarkan SNI 1729 J3.8(c), ketahanan slip yang tersedia berdasarkan kondisi batas slip
untuk lubang slot panjang, sebagai berikut:

Metode DFBK: = 0,70 Metode DKI: = 2,14

= 0,30 untuk permukaan Kelas A

267 dari 282


Dn = 1,13

hf = 1,0 terdapat tidak lebih dari satu pengisi

Tb = 142 kN berdasarkan Tabel J3.1 SNI 1729, Spesifikasi untuk gedung baja struktural

ns = 2 jumlah bidang geser

Rn = Du hf Tb ns = 96,276 kN

dengan:

Rn = kekuatan nominal dari mekanisme transfer yang berlaku, kN

= koefisien selip rata-rata untuk permukaan kelas A atau B, yang sesuai, atau seperti
ditetapkan oleh pengujian

Du = pada sambungan selip-kritis, pengali yang mencerminkan rasio baut pratarik rata-rata
yang terpasang terhadap baut pratarik minimum yang disyaratkan

hf = faktor untuk pengisi

Tb = gaya tarik minimum sarana penyambung yang diberikan Tabel J3.1, kips, atau J3.1M,
kN

Jumlah baut yang dibutuhkan:

Metode DFBK:

Tu
nb = = 7,568 gunakan 8 baut
R n

Metode DKI:

T a
nb = = 7,557 gunakan 8 baut
Rn

Catatan:
Dalam perencanaan sambungan, kondisi batas geser baut, tumpu baut, leleh tarik, putus
tarik, dan geser blok harus diperhitungkan

268 dari 282


CONTOH J.5 KOMBINASI TARIK DAN GESER PADA SAMBUNGAN SLIP-KRITIS

Kelompok baut pada gambar di bawah ini memikul gaya tarik dan geser. Gunakan baut
ASTM A325 berdiameter 20 mm dengan permukaan Kelas A dan lubang standar. Pada
contoh ini baut hanya didesain terhadap ketahanan slip dan diasumsikan kekuatan balok
dan pelat mencukupi. Periksa apakah baut-baut tersebut cukup kuat.

Baut Db = 20 mm

Solusi:

Gaya tarik nominal: PD = 60 kN PL = 180 kN

3
Arah beban: a tan
4

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

Metode DFBK: Pu = 1,2 PD + 1,6 PL = 360 kN

Tu = Pu sin( ) = 216 kN

Vu = Pu cos( ) = 288 kN

Metode DKI: Pa = PD + PL = 240 kN

Ta = Pa sin( ) = 144 kN

Va = Pa cos() = 192 kN

Berdasarkan SNI 1729 J3.8(c), ketahanan slip yang tersedia berdasarkan kondisi batas slip
untuk lubang slot panjang, sebagai berikut:

Db = 20 mm

= 0,30 untuk permukaan Kelas A

269 dari 282


Dn = 1,13

nb = 8 jumlah baut yang memikul beban

hf = 1,0 terdapat tidak lebih dari satu pengisi

Tb = 142 kN berdasarkan Tabel J3.1


ns = 1 jumlah bidang geser

Kekuatan tarik baut berdasarkan Pasal J3.6

Berdasarkan Tabel J3.2, kekuatan tarik nominal, Fnt = 620 MPa


Ab = Db2 = 314,159 mm2
4

Kekuatan tarik nominal:

Rnt = Fnt Ab = 194,779 kN

dengan:

Fnt = tegangan tarik nominal

Ab = luas tubuh baut tak-berulir nominal atau bagian berulir, mm2 (in.2)

Kekuatan tarik desain satu baut

Metode DFBK:

Tu
t = 0,75 t Rnt = 146,084 kN > = 27 kN
nb

Tu
= 0,185 < 1,00
n b t Rnt

Metode DKI:

R nt Ta
t = 2,00 = 97,389 kN > = 18 kN
t nb

Ta t
= 0,185 < 1,00
n b Rnt

Ketahanan slip satu baut berdasarkan Persamaan J3-4 dan Pasal J3.8

Rn = Du hf Tb ns = 48,138 kN

dengan:

= koefisien slip rata-rata

270 dari 282


Du = 1,13; suatu pengali yang mencerminkan rasio dari rata-rata pratarik baut terpasang
terhadap pratarik baut minimum yang disyaratkan

hf = faktor untuk pengisi

Tb = gaya tarik minimum sarana penyambung (Tabel J3.1M, kN atau Tabel J3.1, kips)
ns = jumlah bidang slip yang diperlukan untuk mengizinkan sambungan tersebut dengan
slip

Metode DFBK:

s = 1,00

Tu
k sc =1- = 0,832 (Persamaan J3-5a, SNI 1729, Spesifikasi untuk
DuTb nb
bangunan gedung baja struktural)

dengan:

Tu = gaya tarik yang diperlukan menggunakan kombinasi beban DFBK, kN

nb = jumlah baut yang menahan gaya tarik yang diterapkan

s Rn ksc nb = 320,304 kN > Vu = 288 kN

Vu
= 0,899 < 1,00
sRn k sc nb

Metode DKI:

s = 1,50

1,5Ta
k sc =1- = 0,832 (Persamaan J3-5b, SNI 1729, Spesifikasi untuk bangunan
DuTb nb
gedung baja struktural)

dengan:

Ta = gaya tarik yang diperlukan menggunakan kombinasi beban DKI, kN

nb = jumlah baut yang menahan gaya tarik yang diterapkan

Rn k sc n b
= 213,536 kN > Va = 192 kN
s

sVa
= 0,899 < 1,00
Rn k sc n b

271 dari 282


CONTOH J.6 KEKUATAN TUMPU PADA LUBANG DIBOR

Sebuah pin berdiameter 24 mm dipasang pada pelat dengan tebal 36 mm. Mutu baja pelat
dengan Fy = 250 MPa. Tentukan kekuatan tumpu sambungan tersebut dengan
mengasumsikan pin lebih kuat dari pada pelat.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

Tebal pelat: tp = 36 mm

Diameter pin: d = 24 mm

Kekuatan tumpu ditentukan dari Pasal J7, SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural sebagai berikut:

Luas proyeksi bidang tumpu:

Apb = d tp = 864 mm2

Kekuatan tumpu nominal: (Persamaan J7-1 SNI 1729, Spesifikasi untuk bangunan gedung
baja struktural)

Rn = 1,8 Fy Apb = 388,8 kN

dengan:

Apb = luas penumpu terproyeksi, mm2 (in.2)

Fy = tegangan leleh minimum yang disyaratkan, MPa (ksi)

Kekuatan tumpu desain:

Metode DFBK:

= 0,75 Rn = 291,6 kN

Metode DKI:

Rn
= 2,00 = 194,4 kN

272 dari 282


CONTOH J.7 KEKUATAN TUMPU PELAT DASAR KOLOM PADA BETON

Sebuah kolom WF 300x300x10x15 menumpu pada pedestal beton berukuran 600 mm x 600
mm dengan f c' = 27,5 MPa. Desain pelat dasar dengan mutu Fy = 50 MPa untuk memikul
beban aksial tekan, PD = 500 kN dan PL = 1500 kN.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

Dimensi kolom: d = 300 mm bf = 300 mm tw = 10 mm tf = 15 mm

Mutu beton: f c' = 27,5 MPa

Dimensi pedestal: Bped = 600 mm

Gaya aksial tekan: PD = 500 kN PL = 1 500 kN

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan geser desain minimum:

Metode DFBK: Pu = 1,2 PD + 1,6 PL = 3 000 kN

Metode DKI: Pa = PD + PL = 2 000 kN

Desain dimensi pelat dasar berdasarkan Pasal J8 SNI 1729, Spesifikasi untuk bangunan
gedung baja struktural mengasumsikan seluruh bagian menumpu pada beton.

Pu
Metode DFBK: c = 0,65 A1.req = = 197 449,609 mm2
c 0,85f c'

273 dari 282


c Pa
Metode DKI: c = 2,31 A1.req = = 197 647,059 mm2
0,85f c'

Gunakan dimensi pelat dasar: B = 500 mm N = 500 mm

Periksa dimensi pelat dasar terhadap dimensi kolom dan ruang untuk angkur:

d + 2 (75 mm) = 450 mm < N = 500 mm

bf + 2 (75 mm) = 450 mm < B = 500 mm

Luas pelat dasar:

A1 = N B = 250 000 mm2

Kekuatan tumpu beton

Gunakan Persamaan J8-2 SNI 1729, Spesifikasi untuk bangunan gedung baja struktural
karena pelat dasar menutupi kurang dari luas tumpuan beton.

Karena pedestal berbentuk pesedi dan posisi pelat dasar konsentris, pedestal memiliki luas
yang sama secara geometris

A2 = A2 = B ped = 360 000 mm2


2

Kekuatan tumpu:

A2
Pp = min 0,85 f c' A 1 ,1.7 f c A 1 = 7 012,5 kN
'

A1

dengan

A1 = Luas dari tumpuan baja konsentris pada suatu penumpu beton, mm2 (in.2)

A2 = Luas maksimum dari bagian permukaan yang menumpu secara geometris serupa
dengan dan konsentris dengan luas yang dibebani, mm2 (in.2)

f c' = kekuatan tekan beton yang disyaratkan, MPa (ksi)

274 dari 282


Metode DFBK:

c = 0,65 c Pp = 4558,125 kN > Pu = 3000 kN

Pu
= 0,658
c Pp

Metode DKI:

Pp
c = 2,31 = 3035,714 kN > Pa = 2000 kN
c

c Pa
= 0,659
Pp

A2
Karena = 1,44 < 4,0 batas atas Persamaan J8-2 tidak menentukan
A1

A2
= 1,2 mendekati 1,0, hasil perhitungan Persamaan J8-2 mendekati hasil
A1
Persamaan J8-1

Tebal pelat dasar yang dibutuhkan:

N - 0,95 d
m = 107,5 mm
2

B - 0,8 bf
n = 130 mm
2

d bf
n' = 75 mm
4

Metode DFBK:

4d b P
X f
u = 0,658
d + bf c Pp
2

2 X
= 1,024 > 1,0 Gunakan = 1,0
1+ 1- X

. n' = 75 mm

= max(m, n , n') = 130 mm

275 dari 282


Pu
f pu = = 12 MPa
BN

2 f pu
t min = = 42,458 mm
0,9 F y

Metode DKI:

4d b P
X = f
c a = 0,659
d + bf Pp
2

2 X
= 1,025 > 1,0 Gunakan = 1,0
1+ 1- X

n' = 75 mm

= max(m, n , n') = 130 mm

Pa
f pa = = 8 MPa
BN

3,33 f pa
t min = = 42,437 mm
Fy

Gunakan tebal pelat dasar 45 mm.

276 dari 282


Bab K Desain Sambungan Komponen Struktur PSB dan Boks

Perhitungan untuk gaya transversal dan longitudinal diterapkan untuk PSB diilustrasikan
dalam Contoh K.1 dan K.2.

277 dari 282


CONTOH K.1 PELAT TRANSVERSAL YANG DIBEBANI TEGAK LURUS PSB PERSEGI

Periksa kekuatan lokal kolom PSB persegi yang dibebani dalam arah tegak lurus melalui
pelat dengan lebar 140 mm dan tebal 12 mm. Kolom menggunakan profil PSB 200x200x12
mengalami gaya tekan nominal PD.kolom = 240 kN dan PL.kolom = 720 kN.

Kekuatan lentur profil PSB tidak perlu ditinjau. Material baja dengan Fy = 250 MPa.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

Data profil PSB:

H = 200 mm B = 200 mm t = 12 mm

Data Pelat:

Bp = 140 mm tp = 12 mm

Beban transversal: PD = 35 kN PL = 105 kN

Beban aksial tekan: PDkolom = 240 kN PLkolom = 720 kN

Batasan penggunaan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal
K1.3

SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Tabel K1.2A memberikan
batasan untuk penggunaan sambungan pelat-PSB persegi.

Kelangsingan dinding profil PSB:

B
= 16,667 < 35 (o.k.)
t

278 dari 282


Rasio lebar:

Bp
0,25 < = 0,7 < 1,0 (o.k.)
B
Kekuatan material:

Fy = 250 MPa < 360 MPa (o.k.)

Daktilitas:

Fy
= 0,61 < 0,8 (o.k.)
Fu

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

Gaya transversal dari pelat:

Metode DFBK: Pu = 1,2 PD + 1,6 PL = 210 kN

Metode DKI: Pa = PD + PL = 140 kN

Gaya aksial kolom:

Metode DFBK: Pu.kolom = 1,2 PD.kolom + 1,6 PL.kolom = 1 440 kN

Metode DKI: Pa.kolom = PD.kolom + PL.kolom = 960 kN

Kekuatan leleh lokal yang dimiliki pelat berdasarkan Tabel K1.2

10
Rn = Fy t B p = 252 kN < Fy tp Bp = 420 kN (o.k.)
B

t

Metode DFBK:

= 0,95 Rn = 239,4 kN > Pu = 210 kN (o.k.)

Pu
= 0,877 < 1,00 (o.k.)
R n
Metode DKI:

Rn
= 1,58 = 159,494 kN > Pa = 140 kN (o.k.)

Pa
= 0,878 < 1,00 (o.k.)
Rn

279 dari 282


Kelelehan geser (pons) PSB

Kondisi ini tidak perlu diperiksa jika Bp > B -2t atau Bp < 0,85B.

B 2 t = 176 mm > 0,85B = 170 mm

sehingga kondisi ini tidak menentukan

Kondisi batas lain

Kondisi batas lain yang dijelaskan dalam Tabel K1.2 diperhitungkan hanya jika = 1,0.

Karena B/Bp < 1,0, kondisi batas tersebut tidak perlu diperhitungkan.

280 dari 282


CONTOH K.2 PELAT LONGITUDINAL YANG DIBEBANI TEGAK LURUS PSB BUNDAR

Periksa kekuatan lokal kolom PSB bundar yang dibebani dalam arah tegak lurus melalui
pelat dengan ukuran 100 mm x 100 mm dan tebal 20 mm. Kolom menggunakan profil PSB
Bundar 150x10. Kekuatan lentur profil PSB tidak perlu ditinjau. Material baja dengan Fy =
250 MPa.

Solusi:

Properti material baja:

Fy = 250 MPa Fu = 410 MPa E = 200 000 MPa

Data profil PSB Bundar:

D = 150 mm t = 10 mm

Data Pelat:

Bp = 100 mm tp = 20 mm

Beban transversal: PD = 18 kN PL = 54 kN

Batasan penggunaan SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Pasal
K1.2

SNI 1729, Spesifikasi untuk bangunan gedung baja struktural Tabel K1.1A memberikan
batasan untuk penggunaan sambungan pelat-PSB bundar.

Kelangsingan dinding profil PSB:

D
= 15 < 50 (o.k.)
t

Kekuatan material:

Fy = 250 MPa < 360 MPa (o.k.)

281 dari 282


Daktilitas:

Fy
= 0,61 < 0,8 (o.k.)
Fy

Berdasarkan Pasal 2 SNI 1727, Beban minimum untuk perancangan bangunan gedung dan
struktur lain, kekuatan lentur desain minimum:

Gaya transversal dari pelat:

Metode DFBK: Pu = 1,2 PD + 1,6 PL = 108 kN

Metode DKI: Pa = PD + PL = 72 kN

Kondisi batas plastifikasi PSB

Kondisi batas plastifikasi PSB ditentukan berdasarkan Tabel K1.1.

Panjang sambungan pelat: b = 100 mm


Berdasarkan Tabel K1.1, untuk permukaan PSB yang mengalami tarik: Qf = 1,0

b
Rn = 5,5Fy t 2 1+ 0,25 Q = 160,417 kN
D f

Metode DFBK:

= 0,95 Rn = 152,396 kN > Pu = 108 kN (o.k.)

Pu
= 0,709 < 1,00 (o.k.)
R n

Metode DKI:

Rn
= 1,58 = 101,53 kN > Pa = 72 kN (o.k.)

Pa
= 0,709 < 1,00 (o.k.)
Rn

282 dari 282