CIRCUIT DRAWN WITH POWER SUPPLY OFF FOR TYPICAL REMOTE CONTROL
M 2
2 DETAILS, SEE DOCUMENT
3
3 V
4
1
3
PHASE
RWS100
SUPPLY
U
3 1 TRANSFORMER TAPPING OPTIONS
6

5 Tap Nominal 50/60Hz


U V W E
TYPE 1
FS1
W 220/230
X 380/400
C1 C2 Y 400,415/420
U W X Y Z
Z 440/460
FUSE FS1=250mA ANTI-SURGE
SK2
0VAC 1 TYPE 2
TRANSISTOR SWITCHING FOR W 346/380
PS1
24VDC CONTACTORS (IQ10-35) 120VAC 4
X 480/500
RELAYS ONLY FITTED WHEN
0VDC Y 240/240
120VAC CONTACTOR IS FITTED 3 4
24VDC
FOR IQ40,70,90,91 & 95 24VDC 6 Z 550/575
_ 5 NOMINAL SUPPLY

+
(OUTPUT) FUSE FS1=250mA ANTI-SURGE
SK14 TYPE 3
0VDC 1 X 660/660-690
24VDC 2 Y 690/-
SK13 FUSE FS1=150mA ANTI-SURGE

26 WAY
REFER TO SHEET 2 FOR NOTES
& OPTION PCB'S IF FITTED

SK3 SK13 SK14


6 1 42
MONITOR RELAY
5 3 43
TORQUE 4 2 44
3
2
SK7
SENSOR 1 1 6
SK8 MAKE AT FULLY SHUT S1 8 7
POSITION 10 WAY 2 8
SENSOR MAKE AT FULLY OPEN S2 7 9
SK9 BREAK AT FULLY SHUT
3 10
BATTERY - 4
S3 6 11
4 12
+
1 BREAK AT FULLY OPEN S4 5 13
FS2 (IF FITTED) 100mA SK4
CLOSE 9 33
STOP/ MAINTAIN 10 34
50% SK6 OPEN 8 35
COMMON -VE 1 36
18 WAY
REMOTE
ESD 12 25
CLOSED
STOP

OPEN LOCAL
OPEN INTERLOCK 13 37
CLOSE INTERLOCK 14 38
COMMON -VE 5 31
SK1 SK2
SLOT A SLOT B

Iss Date Chkd Revision Details IQ BASIC DIAGRAM


5 090113 PMJ Re-track of the 24V DC pin www. .com
of SK14 to behind the diode.
6 060614 PMJ 400v added to type 1 ROTORK CONTROLS LTD ROTORK CONTROLS INC Drawn by: PMJ Circuit Diagram Number Issue Sheet
BATH, BA1 3JQ ROCHESTER Date : 160512 No
tapping Y. Note added to
sheet 2 note 1. ENGLAND NY 14624, USA
Base WD: 100B0000
Job No : - -
100B0000 6
1
of 2
Tel:01225-733200 Tel:585-247-2304 MI No : - - B1 C1 B2 C2
IQ3
CIRCUIT DRAWN WITH POWER SUPPLY OFF

NO
OPTIONS
FITTED

NOTES
1.FUSES:
-PS1 is a self-resetting fuse. 3.INDICATION:
-Refer to publication PUB002-039 for approved fuses FS1 and FS2. -For typical position, status and alarm indication see PUB002-041.
-Actuator rated voltage specified on nameplate. Voltage tolerance +/-10%, -S contacts are user configurable and are shown in their default
applies for rated torque performance; duty cycle is not gauaranteed. setting.
2.REMOTE CONTROL: -Refer to PUB002-040 for functions and configuration instructions.
-For typical remote control circuits refer to: -Monitor Relay indicates actuator availability for remote control (shown
-RWS indicated or PUB002-041. unavailable). It can be configured to exclude local/remote selection.
-For DC and AC control, connect ve/0V to terminal 36. -Refer to PUB002-040 for monitored functions and configuration
-(For negative switch / positive common, refer to RWS indicated). instructions.
-Control signal threshold voltages: -Voltage applied to indication contacts must not exceed 150Vac
-DC: on 16Vdc / off 8Vdc, max 60Vdc. -Individual Switch current must not exceed 3.5A inductive, 5A resistive
-AC: on 60Vac / off 40Vac, max 120Vac. and no more than 8A in total for all 4 contacts.
-Control signal duration to be 300ms minimum. 4.BATTERY:
-Maximum current drawn from remote control signals is: -Battery maintains local and remote S contact indication only.
-8mA at 24Vdc or 12mA at 120Vac. -Refer to installation manual for approved replacement battery types.
-Supply provided on terminals 4 & 5:
-Intended for remote control. Issue Sheet
-Max external load 5W at 24Vdc / 5VA at 120Vac Circuit Diagram Number
No
100B0000 6 2
See Sheet 1 for all Revision details/information of 2
IQ3