Está en la página 1de 1

MC INTERLOCKED ARMORED

3 Conductors
EPR
AIA/PVC
UL MC/MV-105
5kV 133%
8kV 100%
PRODUCT CONSTRUCTION
Conductor: 4 AWG through 1000 kcmil bare copper compact, Class B strand.
Extruded Strand Shield (ESS): Thermoset semi-conducting stress-control layer over conductor.
Insulation: Ethylene Propylene Rubber (EPR) insulation, colored to contrast with black conducting layers.
Extruded Insulation Shield (EIS): Thermoset semi-conducting polymeric layer, free stripping from insulation.
Shield: 5 mil annealed copper tape with a minimum 25% overlap.
Ground: Annealed bare copper Class B stranding per ASTM B8.
Armor: Aluminum Interlocked Armor (AIA)
Jacket: Flame-retardant moisture- and sunlight-resistant Polyvinyl Chloride (PVC), yellow.

APPLICATIONS
For use in wet or dry locations, indoors or outdoors, in exposed or concealed work. May be used in cable trays or on approved support
in protected areas. Permitted for use in Class I; Class II, Division 2; and Class III, Divisions 1 and 2 hazardous locations per the NEC.
Ideal for use in commercial, industrial and utility applications where space is limited and reliability, maximum performance, ease of
installation and fire resistance are important.

FEATURES
Rated at 105C wet or dry. Excellent heat and moisture resistance. Outstanding corona resistance. Flexible for easy handling. High
dielectric strength. Low moisture absorption. Electrically stable under stress. Low dielectric loss. Chemical- and radiation-resistant.
Excellent crush resistance. Cost-effective alternative to installations in conduit. Meets cold bend test at -25C.

COMPLIANCES
Industry: UL 1072. ICEA S-93-639/NEMA WC74. AEIC CS8. UL Type MV-105. UL Type MC.
Flame Test: IEEE 383 (70,000 BTU/hr). UL 1581 (70,000 BTU/hr). IEEE 1202 (70,000 BTU/hr) CSA FT4. ICEA T-29-520 (210,000 BTU/hr).
ICEA T-30-520 (210,000 BTU/hr).
Other: EPA 40 CFR, Part 261, for leachable lead content per TCLP. OSHA acceptable.

Copper Phase Conductors


Nom. Nom. Weight
Size Diam. Diam. Copper (lbs./1000 ft.)
(AWG No. Insul. Over PVC Jkt. Over Grounding Ampacity* Ampacity**
USAWC or of Thick. Armor Thick. PVC Jkt. Conductor Alum. Steel
Part # kcmil) Strands (Mils) (Inches) (Mils) (Inches) (AWG) Armor Armor Copper
5000 VOLTS 133% INSULATION LEVEL or 8000 VOLTS 100% INSULATION LEVEL
USA4-035KVESAIA 4 7 115 1.44 50 1.54 6 1360 1745 619 100 115
USA2-035KVESAIA 2 7 115 1.57 60 1.70 6 1775 2160 864 135 154
USA1-035KVESAIA 1 19 115 1.65 60 1.78 4 2055 2475 1074 155 180
USA1/0-035KVESAIA 1/0 19 115 1.78 60 1.91 4 2335 2745 1298 185 205
USA2/0-035KVESAIA 2/0 19 115 1.88 60 2.01 4 2705 3130 1566 210 240
USA3/0-035KVESAIA 3/0 19 115 1.99 60 2.12 3 2920 3375 1918 245 280
USA4/0-035KVESAIA 4/0 19 115 2.11 60 2.24 3 3730 4290 2360 285 320
USA250-035KVESAIA 250 37 115 2.23 60 2.36 3 4200 4770 2735 315 355
USA350-035KVESAIA 350 37 115 2.46 75 2.62 2 5590 6220 3736 390 440
USA500-035KVESAIA 500 37 115 2.77 75 2.93 1 7490 8210 5222 475 545
USA750-035KVESAIA 750 61 115 3.18 85 3.37 1/0 10385 11195 7684 585 685
USA1000-035KVESAIA 1000 61 115 3.50 85 3.69 1/0 13345 14150 10057 660 790

*AMPACITY for cables installed in uncovered cable tray without maintained spacing: 105C conductor temperature, 40C ambient.
**AMPACITY for cables installed in uncovered cable tray with maintained spacing of one cable diameter: 105C conductor temperature, 40C ambient.
For other installation conditions refer to the NEC.

También podría gustarte