5) Rated frequency:
Standard frequencies are 50 Hz and 60 Hz
The manufacturer assumes suitability of the
MCC within +/- 2 % of the rated frequency
required.
Table 1 : End user specifications Rated diversity factor (Part 0 clause 13.4)
Ambient air temperature (Part 0 clause 8.7) Rated diversity factor defines the maximum allowable
loading of the system. In the case of no specific
Ambient air temperature requirements depend most agreement between manufacturer and user reference is
often on geographical positions. In areas (e.g. Middle made to table 101 of IEC 61439-2.
East) MCCs are put into air-conditioned substations but Table 101 of IEC 61439-2 edition 1 suggests assumed
when the aircon fails the MCC needs to continue to do its loading factors depending of the number of main circuits
job (for at least a number of hours to allow for aircon per panel only. E.g. when more than 10 motor starters are
repair). installed into one panel it suggests an assumed loading
factor of 0.6.
The impact on MCC design for higher ambient However IEC 61439-2 edition 2 suggests assumed
temperatures is such that the MCC will become larger in loading factors also depending on the type of load. E.g.
dimensions and more expensive. Either conservative for motors smaller than 100 kW the assumed loading
derating calculations will be used or the vendor will use a factor is 0,8.
verified by testing design at the requested ambient
temperature.
In many circumstances it is preferred that arc prevention [1] IEC 61439 Low-voltage switchgear and controlgear
measures (E.g. such as insulated main busbars) are the assemblies
solution to protect the assembly. [2] PCIC 2012, PR-22; A View on Internal Arc Testing
of Low Voltage Switchgear.
Bas Bouman, Eric Alferink, Marco Lusing, Jan
Verstraten