6ACPSB-P-HP Series
COOLING CAPACITY-
30 TO 1468 MBH
AIR-COOLED PACKAGE UNITS
GENERAL DESCRIPTION
The 6ACPSB-P-HP series with new features is suitable for hotel, office, hospital, school, factory and
supermarket applications. The low noise and compact series are completely leak tested, evacuated,
dehydrated and charged with refrigerant prior to shipment.
Scroll Compressor(s)
Reliability
No contact scroll design that minimizes friction, increases
volumetric efficiency and reduces vibration, thus longer service life.
Suction gas cooled motor.
Multiple Compressor
(250P and above)
By cycling off compressor operation to match building load, no energy is being wasted when room
load requires lesser cooling capacity.
No total shut down when servicing or repairing a faulty compressor.
Safety Control
High-low pressure cutout to protect compressor from high discharge pressure and system leakage.
Suction accumulator to prevent liquid flood back to the compressor during heating cycle.
-2-
AIR-COOLED PACKAGE UNITS
Casing
Constructed from heavy gauge galvanized steel.
Panels are painted with epoxy powder paint for excellent finish, weatherability and corrosion
resistance.
Evaporator section is insulated with 1 x 1 1/2 lb per.cu.ft of linacoustic fibreglass.
Filters
1 thick with side loading for model 30P to 145P.
2 thick with side loading for model 160P to
570P.
2 thick with front loading for model 640P and
above.
-3-
SYSTEM COOLING CAPACITY
-4-
SYSTEM COOLING CAPACITY
NOTES : 1.) RATINGS ARE GROSS CAPACITIES - FOR NET CAPACITIES , DEDUCT EVAPORATOR BLOWER MOTOR HEAT.
2.) AT 80 F ( 26.6C ) AIR ON EVAPORATOR.
3.) COMPRESSOR KW INPUT.
-5-
SYSTEM COOLING CAPACITY
NOTES : 1.) RATINGS ARE GROSS CAPACITIES - FOR NET CAPACITIES, DEDUCT EVAPORATOR BLOWER MOTOR HEAT.
2.) AT 80 F ( 26.6C ) AIR ON EVAPORATOR.
3.) COMPRESSOR KW INPUT
-6-
SYSTEM COOLING CAPACITY
NOTES : 1.) RATINGS ARE GROSS CAPACITIES - FOR NET CAPACITIES , DEDUCT EVAPORATOR BLOWER MOTOR HEAT.
2.) AT 80 F ( 26.6C ) AIR ON EVAPORATOR.
3.) COMPRESSOR KW INPUT.
-7-
SYSTEM HEATING CAPACITY
-8-
SYSTEM HEATING CAPACITY
-9-
SYSTEM HEATING CAPACITY
- 10 -
SYSTEM HEATING CAPACITY
- 11 -
BLOWER PERFORMANCE
Available External Static Pressure - IWG - For Accessories And Duct System Static Resistance
(Allowance Made For Wet Coil And Filters)
- 12 -
BLOWER PERFORMANCE
CFM FAN
RPM
SP BHP SP BHP SP BHP SP BHP SP BHP MODEL
6ACPSB 510P-HP
12400 13200 14000 14800 15600
600 0.31 5.45 0.14 6.03 - - - - - -
500x500
700 0.95 6.84 0.82 7.53 0.67 8.24 0.49 8.99 0.28 9.76 (mm)
800 1.60 8.43 1.50 9.21 1.39 10.03 1.25 10.91 1.08 11.81
900 2.29 10.29 2.22 11.18 2.13 12.08 2.02 13.06 1.89 14.09
6ACPSB 570P-HP
12000 13000 14000 15000 16000
600 0.38 5.18 0.18 5.89 - - - - - -
500x500
700 1.00 6.52 0.84 7.34 0.65 8.22 0.43 9.18 0.19 10.21
(mm)
800 1.64 8.07 1.51 8.99 1.37 10.01 1.19 11.11 0.99 12.29
850 1.97 8.94 1.87 9.95 1.75 11.03 1.59 12.20 1.40 13.42
6ACPSB 640P-HP
14000 15000 16000 17000 18000
600 0.87 6.81 0.75 7.49 0.60 8.21 0.45 9.027 0.26 9.87
560x560
650 1.20 7.72 1.11 8.51 0.98 9.30 0.83 10.14 0.66 11.06
(mm)
700 1.54 8.78 1.47 9.61 1.36 10.47 1.24 11.41 1.07 12.34
750 1.89 9.90 1.84 10.81 1.74 11.71 1.65 12.76 1.51 13.80
6ACPSB 700P-HP
15200 16200 17200 18200 19200
650 0.98 8.68 0.84 9.49 0.68 10.35 0.49 11.257 0.29 12.21
560x560
700 1.34 9.75 1.22 10.66 1.08 11.59 0.91 12.58 0.74 13.65
(mm)
750 1.71 10.98 1.61 11.94 1.49 12.95 1.33 13.98 1.18 15.14
800 2.09 12.29 2.01 13.33 1.91 14.42 1.78 15.56 1.62 16.70
6ACPSB 760P-HP
16000 17000 18000 19000 20000
650 0.91 9.33 0.75 10.17 0.58 11.085 0.39 12.052 0.15 13.00
560x560
700 1.29 10.50 1.15 11.41 0.98 12.34 0.82 13.42 0.61 14.49
(mm)
750 1.67 11.74 1.56 12.76 1.42 13.80 1.26 14.89 1.08 16.09
800 2.05 13.05 1.97 14.20 1.85 15.32 1.70 16.46 1.53 17.70
6ACPSB 800P-HP
16600 18100 19600 21100 22600
600 1.57 10.05 1.52 11.28 1.45 12.60 1.35 14.00 1.22 15.51
630x630
650 1.94 11.56 1.90 12.87 1.85 14.32 1.78 15.88 1.67 17.51
(mm)
700 2.32 13.19 2.30 14.64 2.26 16.23 2.21 17.91 2.12 19.62
750 2.72 14.98 2.73 16.61 2.69 18.22 2.66 20.06 2.60 22.00
6ACPSB 890P-HP
19000 20500 22000 23500 25000
600 1.41 12.02 1.31 13.38 1.18 14.58 1.03 16.41 0.85 18.09
630x630
650 1.81 13.72 1.75 15.29 1.64 16.87 1.51 18.54 1.34 20.29
(mm)
700 2.23 15.61 2.17 17.21 2.09 18.98 1.99 20.82 1.84 22.69
750 2.66 17.63 2.60 19.29 2.53 21.15 2.47 23.22 2.36 25.33
6ACPSB 960P-HP
20000 21500 23000 24500 26000
600 1.38 12.96 1.26 14.36 1.12 15.89 0.94 17.50 0.74 19.21
630x630
650 1.79 14.72 1.70 16.29 1.60 18.02 1.44 19.74 1.27 21.60
(mm)
700 2.22 16.68 2.16 18.43 2.05 20.14 1.93 22.08 1.79 24.11
750 2.65 18.74 2.61 20.63 2.54 22.59 2.43 24.61 2.31 26.77
6ACPSB 1020P-HP
22800 24300 25800 27300 28800
550 1.56 14.55 1.49 15.84 1.40 17.24 1.29 18.63 1.16 20.13
710x710
600 2.02 16.95 1.97 18.39 1.88 19.82 1.80 21.42 1.68 23.01
(mm)
650 2.50 19.61 2.46 21.16 2.39 22.75 2.32 24.44 2.23 26.25
700 3.00 22.53 2.96 24.14 2.91 25.90 2.87 27.83 2.79 29.74
6ACPSB 1140P-HP
23200 24800 26400 28000 29600
500 1.18 12.72 1.08 13.97 0.96 15.29 0.84 16.77 0.69 18.28
710x710
550 1.63 14.92 1.54 16.26 1.44 17.71 1.34 19.35 1.21 21.01
(mm)
600 2.08 17.28 2.02 18.81 1.94 20.42 1.86 2.21 1.74 23.97
650 2.58 20.06 2.52 21.65 2.46 23.41 2.38 25.25 2.29 27.23
6ACPSB 1340P-HP
28000 30000 32000 34000 36000
450 1.30 15.75 1.23 17.42 1.14 19.15 1.02 20.96 0.89 22.90
800x800
500 1.82 18.86 1.75 20.62 1.67 22.52 1.58 24.61 1.47 26.78
(mm)
550 2.35 22.23 2.31 24.28 2.24 26.34 2.16 28.61 2.06 30.95
600 2.91 25.98 2.87 28.14 2.83 30.51 2.78 33.11 2.69 35.64
6ACPSB 1520P-HP
33000 34500 36000 37500 39000
450 0.96 20.07 0.87 21.56 0.77 23.03 0.66 24.56 0.54 26.20
800x800
500 1.50 23.55 1.42 25.18 1.33 26.79 1.24 28.53 1.12 30.25
(mm)
550 2.07 27.43 3.00 29.21 1.93 31.04 1.85 32.93 1.75 34.87
600 2.67 31.73 2.62 33.74 2.56 35.73 2.49 37.78 2.40 39.89
- 13 -
DIMENSIONAL DATA
6ACPSB 50P-HP
6ACPSB 68P-HP
- 14 -
DIMENSIONAL DATA
6ACPSB 145P-HP
- 15 -
DIMENSIONAL DATA
- 16 -
DIMENSIONAL DATA
- 17 -
DIMENSIONAL DATA
- 18 -
PHYSICAL DATA
Compressor Condenser Condenser Fan Evaporator Blower Evaporator Coil Air Filter R-22
Approx.
Coil Charge
Operating
Weight
Model Qty Power MRA LRA NRA Face Rows/ Qty Blade Mtr. Mtr Blower Mtr Fan Face Row/ Qty Size Qty. X
Supply Area Dia. Hp FLA Cfm Area Lbs
Each Each Each Sq. Ft FPI Each Each Qty Size MAX Min-Max Sq.Ft FPI (Inch) Per (Lbs)
(Inch) HP Cfm Comp.
6ACPRB 1 230-1- - 1x62 1x12.5 4.6 3/12 1 18 1/5 1.3 1 9x7 0.6 650 2.1 3/12 1 16x25x1 1x3.5 550
30P-HP 60Hz 1280
6ACPRB 1 230-1- - 1x45 1x16.4 7.2 3/12 1 18 1/5 1.3 1 9x7 0.6 920 3.1 3/12 1 20x25x1 1x3.7 600
40P-HP 60Hz 1800
6ACPSB 1 460-3- - 1x56 1x8.2 8.3 3/12 1 20 1/5 1.3 1 9x9 0.6 1100 3.7 3/12 1 20x25x1 1x4.8 650
50P-HP 60Hz 2200
6ACPSB 1 460-3- - 1x45 1x9.3 8.3 2/12 1 26 1/3 or 1.8-3.4 1 9x9 1.0 1400 4.7 3/12 2 16x25x1 1x5.9 1100
68P-HP 60Hz 1/2 2800
6ACPSB 1 460-3- 1x15.0 1x101 1x10.5 9.4 3/12 1 26 1/3 or 1.8-3.4 1 10x10 1.0 1550 5.2 3/12 1 16x25x1 1x8.3 1200
81P-HP 60Hz 1/2 3100 1 20x25x1
6ACPSB 1 460-3- 1x15.6 1x95 1x12.5 10.9 3/12 1 26 1/3 or 1.8-3.4 1 10x10 1.0 1550 5.2 4/12 1 16x25x1 1x9.9 1300
95P-HP 60Hz 1/2 3100 1 20x25x1
6ACPSB 1 460-3- 1x16.8 1x111 1x13.7 14.2 3/12 1 26 1/3 or 1.8-3.4 2 10x10 0.75 1850 6.1 4/12 2 20x25x1 1x12.3 1500
108P-HP 60Hz 1/2 3600
6ACPSB 1 460-3- 1x19.6 1x118 1x15.8 16.3 3/12 1 26 1/3 or 1.8-3.4 2 10x10 0.75 2000 6.6 4/12 2 20x25x1 1x13.2 1600
125P-HP 60Hz 1/2 3900
6ACPSB 1 460-3- 1x22.3 1x118 1x17.6 19.2 3/12 1 26 1/3 or 1.8-3.4 2 10x10 1.0 2600 8.5 4/12 2 20x25x1 1x17.6 1750
145P-HP 60Hz 1/2 5100
6ACPSB 1 460-3- 1x25.6 1x167 1x19.1 19.5 3/12 2 26 5/8 1.9 1 15x15 5.5 3500 11.7 3/12 2 20x20x2 1x16.0 2100
160P-HP 60Hz 7000 2 20x25x2
6ACPSB 1 460-3- 1x30.0 1x198 1x23.7 19.5 3/12 2 26 5/8 1.9 1 15x15 5.5 3500 11.7 4/12 2 20x20x2 1x23.8 2300
190P-HP 60Hz 7000 2 25x20x2
6ACPSB 1 460-3- 2x16.8 2x111 2x13.7 19.5 4/12 2 26 5/8 1.9 1 15x15 5.5 3700 12.3 4/12 2 20x20x2 1x25.3 2600
220P-HP 60Hz 7300 2 25x20x2
6ACPSB 2 460-3- 2x19.6 2x118 2x15.8 27.4 4/12 2 26 5/8 1.9 1 18x13 7.5 4400 14.6 4/12 4 25x25x2 2x13.2 2800
250P-HP 60Hz 8700
6ACPSB 2 460-3- 2x22.3 2x118 2x17.6 27.4 5/12 2 26 5/8 1.9 1 18x13 7.5 5000 16.7 4/12 4 25x25x2 2x17.6 3000
290P-HP 60Hz 10000
6ACPSB 2 460-3- 2x25.6 2x167 2x19.1 37.5 4/12 3 26 5/8 1.9 1 18x18 10.0 5850 19.4 4/12 2 16x25x2 2x16.0 4000
320P-HP 60Hz 11600 4 20x25x2
6ACPS B 2 460-3- 2x30.0 2x198 2x23.7 37.5 5/12 3 26 5/8 1.9 1 18x18 10.0 6700 22.4 4/12 3 16x20x2 2x23.8 4400
380P-HP 60Hz 13400 6 20x20x2
6ACPSB 2 460-3- 3x22.3 3x118 3x17.6 40.0 5/12 3 26 5/8 1.9 1 450x450 20.0 7000 23.3 4/12 3 16x20x2 2x25.3 4700
435P-HP 60Hz 14000 6 20x20x2
6ACPSB 3 460-3- 3x25.6 3x167 3x19.1 48.3 4/12 4 26 5/8 1.9 1 500x500 20.0 8900 29.9 3/12 2 20x20x2 3x16.0 5500
480P-HP 60Hz 17900 5 20x25x2
2 25x25x2
6ACPSB 3 460-3- 2x25.6 2x167 2x19.1 48.3 4/12 4 26 5/8 1.9 1 500x500 20.0 8900 29.9 3/12 2 20x20x2 3x23.8 5700
510P-HP 60Hz 1x30.0 1x198 1x23.7 17900 5 20x25x2
2 25x25x2
6ACPSB 3 460-3- 3x30.0 3x198 3x23.7 48.3 5/12 4 26 5/8 1.9 1 500x500 20.0 8900 29.9 4/12 2 20x20x2 2x23.8 5950
570P-HP 60Hz 17900 5 20x25x2 1x25.3
2 25x25x2
6ACPSB 3 460-3- 4x25.6 4x167 4x19.1 65.3 3/12 4 31.5 1 1/2 3.2 1 560x560 30.0 10000 33.4 4/12 4 20x20x2 3x25.3 6500
640P-HP 60Hz 20000 8 20x25x2
6ACPSB 4 460-3- 2x25.6 2x167 2x19.1 65.3 4/12 4 31.5 1 1/2 3.2 1 560x560 30.0 10000 33.4 4/12 4 20x20x2 4x23.8 6650
700P-HP 60Hz 2x30.0 2x198 2x23.7 20000 8 20x25x2
6ACPSB 4 460-3- 4x30.0 4x198 4x23.7 65.3 4/12 4 31.5 1 1/2 3.2 1 560x560 30.0 10400 34.7 4/12 4 20x20x2 2x23.8 6750
760P-HP 60Hz 20800 8 20x25x2 2x25.3
6ACPSB 4 460-3- 5x25.6 5x167 5x19.1 94.0 4/12 4 31.5 1 1/2 3.2 1 630x630 40.0 13500 45.1 4/12 4 20x20x2 4x25.3 7000
800P-HP 60Hz 27000 9 20x25x2
2 25x25x2
6ACPSB 5 460-3- 2x25.6 2x167 2x19.13x2 94.0 5/12 4 31.5 1 1/2 3.2 1 630x630 40.0 14000 46.9 4/12 4 20x20x2 5x23.8 7100
890P-HP 60Hz 3x30.0 3x198 3.7 28000 9 20x25x2
2 25x25x2
6ACPSB 6 460-3- 6x25.6 6x167 6x19.1 94.0 5/12 4 31.5 1 1/2 3.2 1 630x630 40.0 14500 48.6 4/12 4 20x20x2 6x16.0 7250
960P-HP 60Hz 29000 9 20x25x2
2 25x25x2
6ACPSB 6 460-3- 4x25.6 4x167 4x19.1 123.0 4/12 6 31.5 1 1/2 3.2 1 710x710 40.0 16600 55.6 4/12 12 20x20x2 4x16.0 8350
1020P-HP 60Hz 2x30.0 2x198 2x23.7 33300 8 20x25x2 2x23.8
6ACPSB 6 460-3- 6x30.0 6x198 6x23.7 123.0 5/12 6 31.5 1 1/2 3.2 1 710x710 40.0 19000 63.9 4/12 20 20x25x2 4x23.8 9400
1140P-HP 60Hz 38300 2x25.3
6ACPSB 6 460-3- 6x25.6 6x167 6x19.1 129.0 5/12 6 31.5 1 1/2 3.2 1 800x800 50.0 21600 72.2 4/12 8 20x20x2 6x25.3 10400
1340P-HP 60Hz 2x30.0 2x198 2x23.7 43300 16 20x25x2
6ACPSB 8 460-3- 8x30.0 8x198 8x23.7 129.0 5/12 6 31.5 1 1/2 3.2 1 800x800 50.0 21600 72.2 5/12 8 20x20x2 6x23.8 11000
1520P-HP 60Hz 43300 16 20x25x2 2x25.3
Notes: 1.) Condenser fan motors voltage is 220/240-1-60Hz for 4.) LRA- Locked Rotor Amp.
model 30 to 50. 5.) NRA- Nominal Running Amp.
2.) Blower motor for model 30 to 145 is 220/240-1-60Hz and 6.) MRA- Maximum Running Amp.
direct drive. 7.) FLA- Full Load Amp.
3.) Minimum-maximum voltage is 432V to 488V. 8.) 6ACPRB 30P and 6ACPRB 40P are rotary compressors.
- 19 -
NOMENCLATURE
6 AC P S B 435 P - HP Q P
6- 60 Hz Blank - R22
Blank - 50Hz P - R407C
Packaged
Heat Pump
S- Scroll Compressor
R- Rotary Compressor Propeller Fan
OPERATING LIMITS
COOLING (AIR TEMPERATURE F) HEATING (AIR TEMPERATURE F)
DB WB DB WB
CORRECTION FACTORS
To correct for variation in air To correct for altitude, use To correct sensible capacity
flow, use this multiplier. this multiplier. for varying dry bulb.
AIR FLOW TOTAL SENSIBLE ALTITUDE ABOVE COOLING CAPACITY DRY WET BULB
VARIATION CAPACITY CAPACITY SEA LEVEL - FT BULB 57 62 67 72
0.8 0.960 0.900 0 1.00
75 0.84 0.81 0.78 0.74
2000 0.98
0.9 0.980 0.950 80 1.00 1.00 1.00 1.00
3000 0.97
85 1.16 1.18 1.21 1.26
1.0 1.000 1.000 4000 0.96
5000 0.95 Note: If The Capacity After Multiplying The
1.1 1.015 1.045
6000 0.93 Sensible With The Correction Factor
1.2 1.025 1.090 7000 0.92 Exceeds The Total Capacity, Then The
Sensible Must Be Equal To The Total.
04-07