CAPACITOR SIZING CALCULATION

Inputs Voltages 11000.000 KV 10%


Frequency 50.000 Hz
Motor Power 900.000 KW
PF1 Motor Power Factor 0.900
PF2 Target Power Factor 0.982
Series Reactor 0.002 0.2% of Xc
Vn (with COV) 6986143.187 V

Formulas 1. KVAr Required= MotorkW (tan 1tan 2)


Where 1= COS INVERSE (PF1)
2= COS INVERSE (PF2)
2. Xc = Xeq / (1% of reactor)
3. Vc = Vn (With COV) + VI
Where Vc = Voltage across Capacitor
Vn = Nominal Voltage
Vl = Voltage drop across Capacitor
4. Vl = 3 * If * XL
5.If = Vph with COV / Xeq
6. Compensation Required Qc = Vc^2/Xc
7. Inrush Current Is= 2 Vph / (Xc* *Xl)
Where Xc * = 3Vph ^2 {1/Q1 + 1/Q2 } * 106
8. Capacitor rated current ln = KVAR / 3 * V
As per IEC 608711 the inrush current for a capacitor bank is to be limited to 100 times
of its rated current.

Calculation COS INVERSE (PF1) = 0.451 rad


COS INVERSE (PF2) = 0.190 rad
tan1 = 0.484 rad
tan2 = 0.192 rad
KVAr 262.781 KVAr
Xeq = (KV)^2/MVAr 460459272.206 Ohm/phase
Xc = 461382036.278 Ohm/phase
Xl 922764.073 Ohm/phase
If 0.015 A
Vl 24248.497 V
Vc 7274.549 Kv
Qc 114.697 KVAr
Series Reactor 0.229 KVAr
ln = 0.000 A
ln * 100 = 0.002 A
Xc* = Ohm/phase
Xl* = Ohm/phase
ls = A
C Farad
L Henry
Resonance Freq = Hz

Conclusion 1. Calculated rating of Capacitor Bank at Vc = KVAr


2. Selected rating of Capacitor Bank at Vc = KVAr
3. The inrush current is well within the limits
TRUE
specified by IEC 608711