SCOPE OF WORK 11.

11. THE CONTRACTOR SHALL AT ALL TIMES PROTECT THE BUILDING EXTERIOR AND INTERIOR FINISHES AGAINST 2. CONTRACTOR SHALL INSTALL SHORING WHERE REQUIRED PRIOR TO REMOVING CONCRETE. REFER TO NOTE 13 OF
DAMAGE RESULTING FROM THE WORK PERFORMED. CONTRACTOR SHALL INSTALL AND MAINTAIN TEMPORARY THE GENERAL NOTES ON THIS SHEET.
1. INSTALL FIBER-REINFORCED POLYMER (FRP) REPAIRS ON CONCRETE JOISTS AND GIRDERS AS INDICATED ON THE PROTECTION AS REQUIRED TO PROTECT BUILDING ELEMENTS AND FINISHES FROM WATER INFILTRATION OR OTHER
REPAIR PLANS AND SCHEDULES. (SEE SHEETS SR2.0 AND SR3.0) ELEMENTS DURING THE COURSE OF THE WORK. ANY DAMAGE CAUSED TO THE EXISTING BUILDING ELEMENTS 3. ALL UNSOUND CONCRETE SHALL BE REMOVED TO SOUND CONCRETE, EXTENDING A MINIMUM OF 3/4 IN. BEYOND
SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE REPAIRED TO THE SATISFACTION OF THE EXPOSED REINFORCEMENT.
2. PERFORM EPOXY INJECTION OF CRACKED CONCRETE MEMBERS AS REQUIRED AT FRP REPAIR LOCATIONS. REFER OWNER AT THE CONTRACTOR'S EXPENSE.
TO FRP NOTES ON THIS SHEET FOR REQUIREMENTS. FOR THE BASE SCOPE OF WORK, ASSUME 900 LINEAR FEET OF 4. EXPOSED REINFORCING SHALL BE THOROUGHLY CLEANED BY ABRASIVE BLASTING TO REMOVE ALL RUST AND
INJECTION WILL BE REQUIRED ON THE CONCRETE JOISTS AND GIRDERS AT THE FRP REPAIR LOCATIONS. 12. FIBER-REINFORCED POLYMER (FRP) REPAIRS SHALL BE PERFORMED BY THE CONTRACTOR IN ACCORDANCE WITH UNSOUND CONCRETE.
IN ADDITION, PERFORM ADDITIONAL EPOXY INJECTION AT OTHER LOCATIONS INDICATED ON SHEETS SR2.0 AND SR3.0 OF ACI 440.2R-08 GUIDE FOR THE DESIGN AND CONSTRUCTION OF EXTERNALLY BONDED FRP SYSTEMS FOR
PLANS. IN ADDITION TO AREAS NOTED ON PLANS OR REQUIRED AT FRP LOCATIONS, CONTRACTOR SHALL ALSO PERFORM STRENGTHENING CONCRETE STRUCTURES. 5. ARCHITECT/ENGINEER SHALL BE ALLOWED A MINIMUM OF 24 HOURS FOR THE INSPECTION OF PROPERLY PREPARED
AN ADDITIONAL 300 LINEAR FEET OF EPOXY INJECTION AT LOCATIONS AWAY FROM FRP REPAIRS TO BE SELECTED BY THE CONCRETE SURFACES AND REINFORCEMENT BEFORE BEGINNING THE CONCRETE PLACEMENT.
ENGINEER DURING THE COURSE OF CONSTRUCTION. 13. CONTRACTOR SHALL INSTALL TEMPORARY SHORING AND BRACING WHERE REQUIRED AT ALL CONCRETE REPAIR
LOCATIONS, INCLUDING JOISTS, COLUMNS AND GIRDER REPAIR LOCATIONS. THE CONTRACTOR SHALL PROVIDE 6. INSTALL NEW SUPPLEMENTAL STEEL DOWELS OR BARS AT THE DIRECTION OF THE ENGINEER AT THE CONCRETE
3. PERFORM CONCRETE REPAIRS TO EXISTING CONCRETE JOISTS, COLUMNS, GIRDERS, AND SLABS AT LOCATIONS SHORING, BRACING, AND SUPPORT AS REQUIRED TO MAINTAIN THE STRUCTURAL INTEGRITY OF THE NEW OR REPAIR LOCATIONS.
NOTED ON SHEET SR2.0. CONTRACTOR TO PROVIDE SHORING AND BRACING AS REQUIRED AT ALL REPAIR EXISTING CONSTRUCTION DURING THE WORK. CONSTRUCTION DEBRIS SHALL BE REMOVED IN A MANNER THAT
LOCATIONS. REFER TO NOTE 13 OF THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL SHORING AVOIDS OVERLOADING ADJACENT STRUCTURAL MEMBERS. SHORING SHALL BE INSTALLED PRIOR TO REMOVING 7. CONCRETE SHALL BE PLACED AND CURED IN ACCORDANCE WITH SPECIFICATION SECTIONS 03 30 01 - CAST IN PLACE
REQUIREMENTS AND INFORMATION. CONCRETE AT ALL REPAIR LOCATIONS WHERE SHORING IS REQUIRED. ASSUME SHORING WILL NEED TO EXTEND CONCRETE AND 03 95 00 - CONCRETE REPAIR. SHOTCRETE SHALL BE PLACED AND CURED IN ACCORDANCE WITH
DOWN TO GRADE, WITH SHORING ON THE 2ND FLOOR, 1ST FLOOR, AND BASEMENT LEVEL. CONTRACTOR SHALL SECTION 03 37 13 - SHOTCRETE. RECAST CONCRETE REPAIR AREAS TO MATCH EXISTING GIRDER AND
CHICAGO
4. PERFORM CONCRETE REPAIRS AS REQUIRED AT FRP REPAIR LOCATIONS, REFER TO FRP NOTES ON SHEET SR1.0
FOR REQUIREMENTS. NOTE THAT THE REPAIR LOCATIONS ARE TO BE IDENTIFIED BY CONTRACTOR AND ENGINEER
SUBMIT PROPOSED SHORING TO ENGINEER FOR REVIEW PRIOR TO INSTALLING SHORING. SHORING SUBMITTAL
SHALL INCLUDE DRAWINGS AND CALCULATIONS STAMPED BY AN ILLINOIS LICENSED STRUCTURAL ENGINEER.
8.
JOIST SECTION INCLUDING TAPERED AREAS (HORIZONTAL AND VERTICAL) ON JOISTS, AND BUMP-OUTS ON GIRDERS.

THE CONCRETE REPAIR AREAS WILL BE MEASURED AND QUANTIFIED PER SQ. FT. OR PER LINEAR FT. FOR THE
PUBLIC
SCHOOLS
CPS
BY SOUNDING DURING THE REPAIR PROCESS AS NOTED IN NOTE 6 OF THE FRP NOTES. FOR THE BASE SCOPE OF
WORK, ASSUME THAT A TOTAL OF 200 SQ. FT OF PARTIAL DEPTH REPAIRS WILL BE REQUIRED ON THE VERTICAL OR FRP REPAIR NOTES VARIOUS REPAIR TYPES AS INDICATED ON THE DRAWINGS. AREAS WILL BE ROUNDED UP TO THE NEAREST 1/2 SQ.
UNDERSIDE SURFACES OF THE CONCRETE JOISTS AND GIRDERS AT THE FRP REPAIR LOCATIONS. PROVIDE FT.
SHORING AS REQUIRED AT ALL REPAIR LOCATIONS. 1. THE CONTRACTOR SHALL INSTALL THE FRP SYSTEM IN ACCORDANCE WITH ACI 440.2R-08 GUIDE FOR THE DESIGN
AND CONSTRUCTION OF EXTERNALLY BONDED FRP SYSTEMS FOR STRENGTHENING CONCRETE STRUCTURES, THE
5. IN ADDITION TO THE ASSUMED 200 SQ.FT. OF CONCRETE REPAIRS AT FRP REPAIR LOCATIONS, CONTRACTOR SHALL MANUFACTURER'S REQUIREMENTS AND INSTRUCTIONS, AND SPECIFICATION SECTION 03 72 50 - EXTERNALLY BEARING PADS
ALSO PERFORM THE FOLLOWING CONCRETE REPAIRS, AND PROVIDE SHORING AS REQUIRED, AT LOCATIONS TO BE BONDED FRP REINFORCEMENT .
SELECTED BY THE ENGINEER DURING THE COURSE OF CONSTRUCTION: 1. BEARING PADS AT CONCRETE SHEAR COLLARS SHALL BE MASTICORD TYPE AS MANUFACTURED BY JVI, OR
2. SUBMIT DESIGN CALCULATIONS PREPARED BY AN ENGINEER EXPERIENCED IN THE DESIGN OF FRP COMPOSITE APPROVED EQUAL. BEARING PAD THICKNESS SHALL BE 1/2 IN.
A. 150 SQ. FT OF CONCRETE REPAIR ON UNDERSIDE OR VERTICAL SURFACE OF JOISTS AND BEAMS. STRENGTHENING SYSTEMS ON BEHALF OF THE CONTRACTOR TO DETERMINE THE LAYOUT OF THE FRP MATERIALS
TO BE INSTALLED. SUBMITTED CALCULATIONS SHALL BE STAMPED BY A STRUCTURAL ENGINEER LICENSED IN THE 2. INSTRUCT MANUFACTURER TO REMOVE WAX COATING OF MASTICORD PAD PRIOR TO DELIVERING. MASTICORD
B. 150 SQ. FT OF FULL DEPTH CONCRETE REPAIR ON JOIST SLAB SURFACES BETWEEN CONCRETE JOISTS STEMS. STATE OF ILLINOIS. DESIGN CALCULATIONS SHALL CONFORM TO REQUIREMENTS SET FORTH IN ACI 440.2R-08 GUIDE CANNOT BE INSTALLED WITH WAX COATING.
FOR THE DESIGN AND CONSTRUCTION OF EXTERNALLY BONDED FRP SYSTEMS FOR STRENGTHENING CONCRETE
6. INSTALL NEW CONCRETE SHEAR COLLARS AT LOCATIONS INDICATED ON PLANS. STRUCTURES, AND BE BASED ON THE DESIGN MODULUS AND AREA OF THE COMPOSITE TO BE INSTALLED. THE 3. ADHERE BEARING PAD TO CONCRETE SURFACES WITH JVI TWO-PART EPOXY, OR APPROVED EQUAL
COMPOSITE SYSTEM SHALL BE DESIGNED TO ACHIEVE THE STRUCTURAL PERFORMANCE SHOWN ON THE
7. REMOVE AND DISPOSE OF THE EXISTING STEEL GRID SYSTEM SUPPORTING THE ROOF SLAB, INCLUDING ALL STEEL DRAWINGS. a. SURFACE PREPARATION

WJE
BEAMS, CHANNELS, AND ACCESSORIES ABOVE THE ROOF SLAB AND IN THE ATTIC SPACE BETWEEN THE SECOND i. CLEAN BONDING SURFACE TO REMOVE ANY DUST, DIRT, GREASE, OILS, OR WAXES. ENGINEERS
FLOOR CEILING AND THE ROOF SLAB. COORDINATE REMOVAL OF EXISTING STEEL FRAMING WITH INSTALLATION OF 3. CARBON FIBER-REINFORCED POLYMER (CFRP) SYSTEM SHALL HAVE A MINIMUM ELASTIC MODULUS OF 8900 KSI AND ii. DRY SURFACES PRIOR TO APPLICATION OF EPOXY. ARCHITECTS
FRP REINFORCEMENT AND OTHER REPAIRS. SUBMIT PROPOSED SEQUENCE OF WORK TO ENGINEER FOR REVIEW A LAYER THICKNESS OF 0.04 IN. THE CFRP SYSTEM SHALL BE USED FOR ALL FLEXURAL AND SHEAR REPAIRS. MATERIALS SCIENTISTS
AND APPROVAL PRIOR TO REMOVING EXISTING STEEL FRAMING. b. GENERAL BINDING PROCEDURE
4. THE FRP SYSTEM SHALL BE DESIGNED FOR A MAXIMUM ULTIMATE STRAIN OF 0.002 FOR SHEAR AND 0.006 FOR i. MIX EPOXY 1:1 RATIO BY WEIGHT Wiss, Janney, Elstner Associates, Inc.
330 Pfingsten Road
8. REPAIR CONCRETE ROOF DECK AT ROD PENETRATIONS AFTER REMOVAL OF STEEL BEAMS AND HANGER RODS. FLEXURE. ii. TROWEL EPOXY TO ONE SURFACE AND PLACE BEARING PAD ON EPOXY. Northbrook, Illinois 60062
iii. USE CLAMPS TO APPLY PRESSURE TO THE BEARING PAD AND AID IN THE CURING PROCESS. 847.272.7400 tel | 847.291.4813 fax
www.wje.com
9. INSTALL NEW STEEL PLATE FLEXURAL REINFORCEMENT ON THE TOP SIDE OF THE ROOF STRUCTURE AT THE 5. MATERIAL WITNESS PANELS OF EACH COMPOSITE TYPE SHALL BE MANUFACTURED ON SITE TO BE TESTED BY AN iv. ALLOW 24 HOURS FOR INITIAL SET OF EPOXY, AND 7 DAYS FOR FULL CURE.
LOCATIONS IDENTIFIED ON SHEETS SR2.0 AND SR3.0. INDEPENDENT LAB IN ACCORDANCE WITH ASTM D3039 AND SPECIFICATION SECTION 03 72 50 - EXTERNALLY BONDED
FRP REINFORCEMENT TO VERIFY THE PROPERTIES USED FOR DESIGN. STRUCTURAL STEEL NOTES

GENERAL NOTES 6. CONCRETE SURFACES TO RECEIVE FRP SHALL BE SOUNDED BY THE CONTRACTOR. ANY UNSOUND CONCRETE 1. ALL STRUCTURAL STEEL MATERIAL, FABRICATION, AND ERECTION SHALL COMPLY WITH REQUIREMENTS OF THE
SHALL BE REMOVED AND REPAIRED IN ACCORDANCE WITH SPECIFICATION SECTION 03 95 00 - CONCRETE REPAIR. AISC "MANUAL OF STEEL CONSTRUCTION","SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS", "CODE OF
1. ALL WORK SHALL BE IN ACCORDANCE WITH THE CITY OF CHICAGO BUILDING CODE, 2015 EDITION. STANDARD PRACTICE", AND SECTION 05 12 00 - STRUCTURAL STEEL OF THE PROJECT SPECIFICATION.
7. BEFORE INSTALLING FRP, ALL CRACKS IN THE REPAIR AREA GREATER THAN 0.010 INCH SHALL BE EPOXY INJECTED
2. DESIGN LOADS: IN ACCORDANCE WITH THE SPECIFICATION SECTION 03 64 23 - EPOXY INJECTION. 2. SHOP DRAWINGS SHALL BE SUBMITTED BY THE CONTRACTOR FOR THE ENGINEER'S REVIEW BEFORE COMMENCING
WITH FABRICATION.
ROOF SNOW LOAD 25 PSF, PLUS DRIFTING 8. WHERE FIBERS WILL BE WRAPPED AROUND THE CORNERS OF RECTANGULAR CROSS SECTIONS, THE CORNERS
ROOF SUPERIMPOSED DEAD LOAD 25 PSF SHOULD BE ROUNDED TO PROVIDE A MINIMUM RADIUS OF 3/4 IN. 3. STRUCTURAL STEEL SHALL BE AS INDICATED BELOW UNLESS NOTED OTHERWISE.

FLOOR LIVE LOADS 9. UNEVEN CONCRETE SURFACES SHALL BE GROUND OR FILLED WITH APPROVED FILLER MATERIALS IN ACCORDANCE STRUCTURAL STEEL ASTM SPECIFICATION NO. DATE DESCRIPTION
CLASSROOMS 40 PSF WITH FRP MANUFACTURER'S REQUIREMENTS AND SPECIFICATION SECTION 03 72 50 - EXTERNALLY BONDED FRP PLATES (roof level joist reinforcement) A572, GRADE 50
CORRIDORS, 2ND FLOOR 80 PSF REINFORCEMENT . PLATES (other locations) A36
1ST FLOOR 100 PSF ANGLES A36
GYMNASIUM 100 PSF 10. PREPARE SUBSTRATE CONCRETE SURFACES TO RECEIVE FRP BY ABRASIVE BLASTING OR OTHER EQUIVALENT
AUDITORIUM (NO FIXED SEATS) 100 PSF MECHANICAL MEANS TO REMOVE ALL LAITANCE, GREASE, CURING COMPOUNDS, WAXES, AND OTHER BOND 4. STEEL PLATES SHALL BE HOT-DIPPED GALVANIZED AT ALL LOCATIONS. CONTRACTOR SHALL TOUCH UP
INHIBITING MATERIALS. THE SURFACE OF THE CONCRETE SHALL BE PROFILED USING ABRASIVE BLASTING AND/OR GALVANIZING FOLLOWING INSTALLATION WITH COLD APPLIED GALVANIZING COMPOUND.
FLOOR SUPERIMPOSED DEAD LOADS DISC GRINDING TO A MINIMUM CONCRETE SURFACE PROFILE DESIGNATION OF CSP-3 AS DEFINED BY ICRI
SECOND FLOOR 25 PSF GUIDELINE #03732. 5. ALL WELDING ELECTRODE SHALL BE E7018. WELD PROCESS SHALL BE SHIELDED METAL ARE WELDING. ALL
FIRST FLOOR (EXCEPT AUDITORIUM) 10 PSF WELDING SHALL BE PERFORMED BY A CERTIFIED WELDER IN ACCORDANCE WITH AWS D1.1 SPECIFICATIONS.
PARTITION WALLS 930 PLF 11. SPLICES IN THE FRP MATERIAL SHALL BE AVOIDED, UNLESS APPROVED BY THE ENGINEER.
CONCRETE ANCHORS AND DOWELS
3. CONTRACTOR SHALL NOT USE THE EXISTING PLASTER CEILING AS A STAGING AREA FOR THE WORK OR FOR 12. WHERE SPLICES ARE APPROVED BY THE ENGINEER, MINIMUM LAP LENGTH IN THE STRONG FIBER DIRECTION OF
STORAGE OF MATERIALS. THE FRP MATERIAL SHALL BE 12 IN. 1. ANCHORS SHALL BE AS NOTED ON DRAWINGS. COMPATIBLE NUTS AND WASHERS SHALL BE ALSO BE USED. RHS
As indicated
4. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS, AND EXISTING CONDITIONS IN THE FIELD. DO NOT 13. THE MANUFACTURER'S TECHNICAL REPRESENTATIVE SHALL BE PRESENT TO INSPECT THE SURFACE PREPARATION 2. EPOXY USED TO SET DOWELED-IN REINFORCING STEEL BARS SHALL BE HILTI HIT-RE 500 OR HIT-HY 200 EPOXY 2014.6445
SCALE DRAWINGS. DIMENSIONS SHOWN ON THE DRAWINGS ARE PROVIDED FOR INFORMATION ONLY. THE WORK BEFORE THE FRP IS APPLIED AND TO OBSERVE THE INITIAL FRP INSTALLATION IN ITS ENTIRETY. ADHESIVE AS NOTED ON THE DRAWINGS. MINIMUM EMBEDMENT DEPTH AS SHOWN ON DRAWINGS. FOLLOW
CONTRACTOR SHALL REPORT ANY INCONSISTENCIES OR VARIANCES TO THE ENGINEER/ARCHITECT BEFORE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
PROCEEDING WITH THE WORK. 14. CURE FRP RESINS IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND SPECIFICATION SECTION
03 72 50 - EXTERNALLY BONDED FRP REINFORCEMENT . 3. POST INSTALLED ANCHORS MUST BE INSTALLED USING THE SPACING AND EDGE DISTANCES GIVEN ON THE PLANS
5. THE CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, LICENSES AND GOVERNMENT FEES AS REQUIRED. OR DETAILS. IF FIELD CONDITIONS DICTATE THAT THE ANCHORS SPACING OR EDGE DISTANCES BE MODIFIED, THE
permission from Wiss, Janney, Elstner Associates, Inc. (WJE). WJE disclaims any responsibility for its unauthorized use.

THE CONTRACTOR SHALL COMPLY WITH CODES, ORDINANCES, RULES, REGULATIONS, ORDERS AND OTHER LEGAL 15. APPLY A CLASS 1(A) SMOKE AND FLAME SPREAD COATING TO ALL FRP REPAIRS, USING TYFO RR COATING OR AN CONTRACTOR SHALL SUBMIT A FIELD SKETCH TO THE STRUCTURAL ENGINEER FOR REVIEW PRIOR TO MAKING ANY
Copyright 2015. All rights reserved. No part of this document may be reproduced in any form or by any means without

REQUIREMENTS OF PUBLIC AUTHORITY, WHICH BEAR ON THE PERFORMANCE OF THE WORK. APPROVED EQUAL, IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. MODIFICATIONS.

6. THE EXISTING BUILDING WILL REMAIN IN OPERATION FOR THE DURATION OF THE PROJECT. THE CONTRACTOR EPOXY INJECTION NOTES
SHALL PROVIDE ALL TEMPORARY CONTROLS AS NECESSARY TO ALLOW FOR THE BUILDING OPERATIONS.
1. REFER TO SCOPE OF WORK NOTE 2 FOR DESCRIPTION OF INJECTION SCOPE.
7. CONTRACTOR SHALL PROVIDE AND MAINTAIN REQUIRED DUST BARRIERS, BARRICADES, PROTECTION AND
WARNING LIGHTS IN GOOD WORKING CONDITION UNTIL COMPLETION OF THE WORK REQUIRING SUCH PROTECTION 2. REFERENCE SPECIFICATION SECTION 03 64 23 - EPOXY INJECTION FOR REPAIR MATERIALS AND PROCEDURES.
AND THEN REMOVE THE SAME. ALL SIGNS, BARRIERS AND BARRICADES SHALL COMPLY WITH FEDERAL, STATE AND
LOCAL LAWS AND REGULATIONS.
SHEAR COLLAR NOTES
8. THE CONTRACTOR SHALL MAINTAIN PREMISES FREE FROM ACCUMULATIONS OF WASTE MATERIAL AND RUBBISH.
PRECAUTIONS SHOULD BE TAKEN TO MINIMIZE DUST FROM ENTERING THE BUILDING ALL DUST AND DEBRIS 1. NEW SHEAR COLLAR WORK SHALL BE PERFORMED IN ACCORDANCE WITH SPECIFICATION SECTIONS 03 20 00 AND 03
CREATED BY THE WORK WITHIN THE BUILDING SHALL BE REMOVED AND THE WORK AREAS CLEANED, INCLUDING 30 01.
THE FINISHED AND UNFINISHED ATTIC AND BASEMENT AREAS.
2. HANGER RODS SUPPORTING CONCRETE GIRDER SHOULD BE TENSIONED TO ENSURE EXISTING SHORING IS TIGHT
9. CONTRACTOR SHALL REMOVE AND REPLACE PORTIONS OF EXISTING SUSPENDED CEILING, PLASTER CEILING, AND TO UNDERSIDE OF GIRDER AND DEAD LOAD IS TRANSFERRED TO STEEL BEAM ABOVE ROOF.
EXISTING PARTITION WALLS AS NECESSARY TO ACCESS REPAIR LOCATIONS AND INSTALL SHORING. AFTER
COMPLETION OF THE REPAIR WORK IN EACH AREA, CONTRACTOR SHALL REPLACE ALL REMOVED PORTIONS OF THE 3. ROUGHEN ALL SURFACES OF CONCRETE COLUMN AT LOCATION OF NEW SHEAR COLLAR TO A FULL AMPLITUDE OF
CEILING AND PARTITION WALLS TO MATCH THE ORIGINAL. REFER TO ARCHITECTURAL DRAWINGS. 1/4 IN.
GENERAL
10. CONTRACTOR SHALL DETERMINE THE NEED FOR, AND PERFORM, ALL DISCONNECTION AND/OR TEMPORARY OR
PERMANENT REROUTING OF EXISTING UTILITIES, INCLUDING ELECTRICAL, HVAC, AND PLUMBING, IN CONSULTATION
4. CONSTRUCT NEW CONCRETE SHEAR COLLAR AS SPECIFIED. CLEAN ROUGHENED CONCRETE SURFACES OF DUST
AND LAITANCE IMMEDIATELY PRIOR TO CONCRETE PLACEMENT.
NOTES
WITH THE OWNER, SCHOOL, AND CONSTRUCTION MANAGER, TO FACILITATE THE REPAIR INSTALLATION. THE
ARCHITECTURAL DRAWINGS INDICATE WHERE SOME OF KNOWN INTERFERENCES EXIST. HOWEVER, IT IS THE 5. ALLOW ALL CONCRETE TO CURE 28 DAYS OR UNTIL CONCRETE CYLINDER TESTS VERIFY THE CONCRETE HAS
CONTRACTOR'S RESPONSIBILITY TO VERIFY THE EXISTING UTILITIES AND RELATED INTERFERENCES AT ALL REPAIR ACHIEVED ITS DESIGN STRENGTH BEFORE REMOVING STEEL SHORING.
LOCATIONS. AT THE COMPLETION OF THE REPAIR WORK AT EACH AREA, CONTRACTOR SHALL REINSTALL ALL
UTILITIES TO MATCH EXISTING. REFER TO ARCHITECTURAL AND MECHANICAL DRAWINGS. CONCRETE REPAIR NOTES

1. THE CONCRETE REPAIRS SHALL BE PERFORMED IN ACCORDANCE WITH SPECIFICATION SECTIONS 03 20 00


CONCRETE REINFORCEMENT, 03 30 01 - CAST IN PLACE CONCRETE, 03 95 00 - CONCRETE REPAIR, AND 03 37 13
SHOTCRETE.
SR1.0
CHICAGO
PUBLIC
SCHOOLS
CPS

WJE
ENGINEERS
ARCHITECTS
MATERIALS SCIENTISTS
ROOF LEVEL REINFORCEMENT PLAN
1 NOT TO SCALE Wiss, Janney, Elstner Associates, Inc.
330 Pfingsten Road
N Northbrook, Illinois 60062
847.272.7400 tel | 847.291.4813 fax
www.wje.com

NO. DATE DESCRIPTION

RHS
As indicated

SECOND FLOOR REINFORCEMENT PLAN 2014.6445


2 NOT TO SCALE

N
permission from Wiss, Janney, Elstner Associates, Inc. (WJE). WJE disclaims any responsibility for its unauthorized use.
Copyright 2015. All rights reserved. No part of this document may be reproduced in any form or by any means without

REPAIR
LOCATIONS

FIRST FLOOR REINFORCEMENT PLAN


3
N
NOT TO SCALE

SR2.0
CHICAGO
PUBLIC
SCHOOLS
CPS

WJE
ENGINEERS
ARCHITECTS
MATERIALS SCIENTISTS

Wiss, Janney, Elstner Associates, Inc.


330 Pfingsten Road
Northbrook, Illinois 60062
847.272.7400 tel | 847.291.4813 fax
www.wje.com

NO. DATE DESCRIPTION

RHS
As indicated
1
2014.6445

4 2
permission from Wiss, Janney, Elstner Associates, Inc. (WJE). WJE disclaims any responsibility for its unauthorized use.
Copyright 2015. All rights reserved. No part of this document may be reproduced in any form or by any means without

NOTES: SHEAR COLLAR GIRDER LOCATIONS


1 NOT TO SCALE
1. MINIMUM SHEAR REINFORCEMENT PROVIDED PER ACI 11.4.6
2. EXISTING CONCRETE COMPRESSIVE STRENGTH = 3,250 PSI.
3. EXISTING REINFORCING STEEL YIELD STRENGTH ASSUMED TO BE 50 KSI BASED ON TENSILE
TESTING OF REINFORCING STEEL REMOVED FROM THE BUILDING AND NOTES ON THE
ORIGINAL DESIGN DRAWINGS.
4. FLEXURAL AND SHEAR CAPACITIES PROVIDED ARE PER ACI 318-14 CHAPTERS 10 AND 11, AND
INCLUDE APPLICABLE RESISTANCE, OR PHI, FACTORS FOR CONVENTIONAL REINFORCED SCHEDULES
CONCRETE ELEMENTS.
5. FLEXURAL AND SHEAR DEMANDS PROVIDED ARE FOR FACTORED LOAD CONDITIONS, USING
DEAD AND LIVE LOAD FACTORS OF 1.2 AND 1.6, RESPECTIVELY.
6. UNLESS NOTED OTHERWISE IN REPAIR SCHEDULES, CARBON FIBER-REINFORCED
POLYMER (CFRP) SYSTEM SHALL BE USED FOR ALL REPAIRS.
7. THE "ESTIMATED NO. OF LAYERS" IS FOR BIDDING PURPOSES ONLY. CONTRACTOR SHALL
SUBMIT CALCULATIONS SEALED BY A LICENSED STRUCTURAL ENGINEER IN ACCORDANCE
WITH SPECIFICATION SECTION 03 72 50 - EXTERNALLY BONDED FRP REINFORCEMENT -
LAMINATES.
SR3.0
CHICAGO
PUBLIC
SCHOOLS
CPS

FLEXURAL REINFORCEMENT -- GIRDER SHEAR REINFORCEMENT --

WJE
ENGINEERS
FIRST AND SECOND FLOORS FLEXURAL REINFORCEMENT -- ROOF LEVEL FIRST AND SECOND FLOORS GIRDER SHEAR REINFORCEMENT -- ROOF LEVEL
1 NOT TO SCALE
2 NOT TO SCALE
3 NOT TO SCALE
4 NOT TO SCALE
ARCHITECTS
MATERIALS SCIENTISTS

Wiss, Janney, Elstner Associates, Inc.


330 Pfingsten Road
Northbrook, Illinois 60062
847.272.7400 tel | 847.291.4813 fax
www.wje.com

1 12" CLEAR COVER TO HOOP


STEEL, AT CORNERS, TYP.
(12) No. 3 (6) No. 5 BAR
STIRRUPS CIRCULAR TIES

ROUGHEN SURFACES
7 OF EXISTING COLUMN
3 TO A FULL AMPLITUDE NO. DATE DESCRIPTION
SR4.0 4" CLEAR TO
STIRRUPS AT OF 1/4" (TYP.)
EXISTING GIRDER TO BE SUPPORTED CORNERS, TYP.
EXISTING BY SHEAR COLLAR
COLUMN TO
REMAIN NEW BEARING PAD SIZED TO PROVIDE

4" TYP.
3/4" CLR. FULL CONTACT AREA BETWEEN
SHEAR COLLAR AND GIRDER.
PROVIDE STUB-COLUMNS AS SHOWN WHERE
REQUIRED TO MAKE UP HEIGHT DIFFERENCE TO 1 1/2" CLR.
(6) No.5 1 1/2" CLR. UNDERSIDE OF EACH GIRDER TO BE (TYP.)
CIRCULAR TIES
(TYP.) SUPPORTED, WITH 2 HOOKED NO. 4 BARS WITH
EVENLY SPACED
18 IN. VERTICAL LEGS.

(12) No.3 2'-6" MIN. LAP. STAGGER


STIRRUPS NEW SHEAR COLLAR. PROVIDE STUB-COLUMNS LOCATION OF LAP SPLICES, TYP. RHS
AS SHOWN TO MAKE UP HEIGHT DIFFERENCE
ROUGHEN SURFACES As indicated
TO UNDERSIDE OF EACH GIRDER TO BE
OF EXISTING COLUMN
SUPPORTED.
JOIST SHEAR REINFORCEMENT TO A FULL AMPLITUDE 2014.6445
5 NOT TO SCALE OF 1/4" AND REMOVE LOOSE
SHEAR COLLAR DETAIL PLAN - TOP OF SHEAR COLLAR
CONCRETE, TYP.
6 NOT TO SCALE
7 NOT TO SCALE
permission from Wiss, Janney, Elstner Associates, Inc. (WJE). WJE disclaims any responsibility for its unauthorized use.
Copyright 2015. All rights reserved. No part of this document may be reproduced in any form or by any means without

REPAIR
DETAILS

PROTECTION FOR FRP INSTALLED ON ROOFTOP


8 NOT TO SCALE

SR4.0
2 1/2"- 3"

TYPICAL
UNDERSIDE SPALL

CHICAGO
PUBLIC
SCHOOLS
CPS
EXISTING CONDITION REPAIRED CONDITION

ROOF DECK REPAIR AT HANGER-ROD PENETRATIONS JOIST FLEXURAL REINFORCEMENT


1 NOT TO SCALE
2 NOT TO SCALE

2" 2"
8'-6" 13'-8" 4'-0"

1/2"
4 1/2"

2"
2" TYP.

WJE
ENGINEERS
ARCHITECTS
1'-8" MATERIALS SCIENTISTS

8"
Wiss, Janney, Elstner Associates, Inc.

2"
330 Pfingsten Road
Northbrook, Illinois 60062
8" TYP.

4"
847.272.7400 tel | 847.291.4813 fax

6"
www.wje.com

VARIES
4 1/2"

7"
2 1/4" 2 1/4"

7 3/4"

JF1 ANCHORAGE AT EXHAUST FAN JF1 TERMINATION PLATE


4 SCALE: 1 1/2" = 1'-0"
5 SCALE: 1 1/2"" = 1'-0"
NO. DATE DESCRIPTION
JOIST FLEXURAL REINFORCEMENT - PLAN VIEW
3 NOT TO SCALE

12"

12" 4" AVG.


DEPTH

RHS
As indicated
2014.6445
9"
permission from Wiss, Janney, Elstner Associates, Inc. (WJE). WJE disclaims any responsibility for its unauthorized use.
Copyright 2015. All rights reserved. No part of this document may be reproduced in any form or by any means without

REPAIR
DETAILS

TOP OF SPANDREL BEAM CONCRETE REPAIR VERTICAL FACE CONCRETE REPAIR ON SPANDREL BEAM
6 SCALE: 1 1/2" = 1'-0"
7 SCALE: 1 1/2" = 1'-0"

SR5.0
3/4" CLR.

6 IN. AVG.
DEPTH

3/4" CLR.

5 IN. AVG.
DEPTH
CHICAGO
PUBLIC
SCHOOLS
CPS

GIRDER CONCRETE REPAIR


2 NOT TO SCALE
JOIST CONCRETE REPAIR - BOTTOM OF STEM
1 NOT TO SCALE

5&6
SR6.0

WJE
T
ENGINEERS
T ARCHITECTS
MATERIALS SCIENTISTS

Wiss, Janney, Elstner Associates, Inc.


330 Pfingsten Road
Northbrook, Illinois 60062
847.272.7400 tel | 847.291.4813 fax
www.wje.com

JOIST SLAB CONCRETE REPAIR - FULL DEPTH


3 NOT TO SCALE

JOIST CONCRETE REPAIR - FULL DEPTH


4 NOT TO SCALE
NO. DATE DESCRIPTION

2-1/2" COVER

a TYP. T 2-1/2" COVER

b TYP. D T
a TYP.

c TYP. D b TYP.

1" COVER c TYP.


RHS

1" COVER As indicated


2014.6445
permission from Wiss, Janney, Elstner Associates, Inc. (WJE). WJE disclaims any responsibility for its unauthorized use.

PARTIAL LENGTH JOIST CONCRETE REPAIR


Copyright 2015. All rights reserved. No part of this document may be reproduced in any form or by any means without

5 NOT TO SCALE
3"

FULL LENGTH JOIST CONCRETE REPAIR


6 NOT TO SCALE

REPAIR
DETAILS
TYPICAL JOIST DIMENSIONS
8 NOT TO SCALE

SUPPLEMENTAL EPOXY DOWEL SHEAR REINFORCEMENT


7 NOT TO SCALE

SR6.0