Provisions
Type of rising main system shall be provided appropriate to the building as
follow:
FSS
No:
6.2
Notes
Type
3.0
All parts of any floor not more than 28m above the ground level is
within 38m from a landing valve, the distance to be measured along a
route suitable for hose lines, including any distance up or down a
stairway.
One rising main is provided for one or a series of floors higher than
28m above ground, with each rising main serving not more than 930m2
of any floor and subject to all parts of the floor to be within 38m from a
landing valve.
Number
Location
5.0
Size
100mm where the rising main does not exceed 45m in habitable height
and only one landing
1 of 6
Location of
Breeching inlet
Provisions
same riser stack.
Prepared by:
6.2
Notes
b. As close as possible to the rising main they serve with any connecting
pipe between thee inlet and the vertical run of the rising main kept to a
minimum and given a fall towards the drain valve. The total pressure
loss of the dry rising main shall not exceed 6bars based on the design
water flow rate. This is correspond with the maximum habitable height
of 60m.
6.0
FSS
No:
Date:
2 of 6
18 February 2008
3 of 6
10m
28m
Annex A
28m
28m
23m
4 of 6
<28m
5 of 6
10m
6 of 6