Calculations

of
Induced Sheath Voltage
for
115 kV Feeder From GTS1 to EGAT
GULF - TASIT 1 Project

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

Power Cable Calculation

115 kV Power Cable

MVA kV kA

C K

CABLE TYPE:

115 kV CU/XLPE/CWS/PE cable, Single Core, copper conductor, wi th co pe r wi re shi el d,


1 x 800 mm2

CONNECTION:

Gulf-Tasit 1 Project to EGAT substation

INSTALLATION PLACE:

Rayong

METHOD OF INSTALLATION: Single core of triangle formation arrangement installed in HDD.

REFERENCES:
1.

ANSI/IEEE, 575-1988, IEEE Guide for Application of Sheath-Bonding Methods for Single-Conductor Cables and
the Calculation of Inducted Voltages and Current in Cable Sheaths

2. IEEE 80-2000: IEEE Guide for Safety in AC Substation Grounding


3. IEC 60502-1: Cables for rated voltages of 1 kV ((Um = 1,2 kV) and 3 kV (Um = 3,6 kV)

DATA:
a. System Data
U 115000

(phase to phase voltage, V)

f 50

(system frequency, Hz)

2 f

(angular frequency of system, Hz)

b. Cable Data

Prepared by : Raktham S.

See detaild technical data of power cable in ANNEX 1

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 2 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

np 2

(number of cable in parallel)

Acc 800

(cross-section of conductor, sq.mm)


3

dbcs

( 74.07 76.15) 10

(outer diameter below metalic copper screen, m)

dbcs 0.0751

2
3

dacs

( 77.17 79.25) 10

tcws dacs dbcs


dmm

(outer diameter above metalic copper screen, m)

dacs 0.0782

dbcs dacs

(thickness of copper screen wire, m)

tcws 0.0031

(mean diameter of metalic copper screen, m)

dmm 0.0767

c. Installation

Refer to Plan and Section Drawing in ANNEX 2

c.1 Underground Cable between SD-UG-2(1) to SD-UG-2(3)


SM1 12 70 106.25 59.7 168.72 119.75 20 12

SM1 568.42

m.

Select the single point bond at one end by sectionalizing the sheath at MHE3.
SM11 12 70 106.25 59.7

SM11 247.95

(cable length from SD-UG-2(1) to MHE3, m)

SM12 168.72 119.75 20 12

SM12 320.47

(cable length from MHE3 t0 SD-UG-2(3) , m)

SM 11

SM 12

A
B
C
Sheath
Voltage
Limiters

Sheath
Voltage
Limiters

Sheath
Voltage
Limiters

Sheath
Voltage
Limiters

A
B
C

SDUG2(1)

MHE3

SDUG2(3)

ParallelGroundContinuityConductor

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 3 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

c.2 Underground Cable between SD-UG-2(5) to SD-UG-2(7)


SM2 12 20 148.57 20 12

SM2 212.57

m.

Select the single point bond at one end (SD-UG-2(7))

SM 2

A
B
C
Sheath
Voltage
Limiters

A
B
C
Sheath
Voltage
Limiters

SDUG2(7)

SDUG2(5)
ParallelGroundContinuityConductor

c.3 Underground Cable between SD-UG-2(9) to EGAT


Select the cross-bond of three major sections:
sp11 12 20 138.5 189.7

sp11 360.2

(cable length from SD-UG-2(9) to MHE10, m)

sp12 195.3 85.15

sp12 280.45

(cable length from MHE10 to MHE12, m)

sp13 229.9 170.5

sp13 400.4

(cable length from MHE12 to MHE14, m)

sp21 143.99 46.68 166.93

sp21 357.6

(cable length from MHE14 to MHE17, m)

sp22 81.44 ( 140.4 158.8)

sp22 380.64

(cable length from MHE17 to MHE20, m)

sp23 156.9 182.33

sp23 339.23

(cable length from MHE20 to MHE22, m)

sp31 207.35

sp31 207.35

(cable length from MHE22 to MHE23, m)

sp32 206.2

sp32 206.2

(cable length from MHE23 to MHE24, m)

sp33 160.5 55.6 8 4

sp33 228.1

(cable length from MHE24 to EGAT, m)

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 4 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

Total cable length, m


SP sp11 sp12 sp13 sp21 sp22 sp23 sp31 sp32 sp33

SP 2760.17

The longest cable length of the minor section of cross-bonded system, m

spM max sp11 sp12 sp13 sp21 sp22 sp23 sp31 sp32 sp33

spM 400.4

The shortest cable length of the minor sectionof the cross-bonded system, m

spm min sp11 sp12 sp13 sp21 sp22 sp23 sp31 sp32 sp33

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

spm 206.2

page 5 of 31

Prepared by : Raktham S.

SDUG2(9)

Sheath
Voltage
Limiters

Sheath
Voltage
Limiters

Minor Section
sp11

MHE10

Sheath
Voltage
Limiters

Sheath
Voltage
Limiters

Minor Section
sp12

1st Major Section

MHE12

Minor Section
sp13

MHE14

Sheath
Voltage
Limiters

Sheath
Voltage
Limiters

Minor Section
sp21

MHE17

Sheath
Voltage
Limiters

Sheath
Voltage
Limiters

Minor Section
sp22

2nd Major Section

MHE20

Minor Section
sp23

MHE22

Sheath
Voltage
Limiters

Sheath
Voltage
Limiters

Minor Section
sp31

MHE23

Sheath
Voltage
Limiters

Sheath
Voltage
Limiters

Minor Section
sp32

3rd Major Section

MHE24

Minor Section
sp33

EGAT

Gult-Tasit 1 Project
Power Cable Calculations
Sheath Induced Voltage

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 6 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

c.4 Horizontal drilling duct-HDD Configuration and Cable Arrangment

c.5 Parallel Ground Continuity Conductor - PGCC


PGCC is installed for reducing a sheath overvoltage occurred at single point bonded section through providing
a return path of fault current.
As per IEEE 80-2000, equation (40), on page 43, the require ground conductor size is calculated as follows from the
following equation

A I
c f

TCAP ln K0 Tm
t K T
c r r 0 a
1

where
Ief

Ac
Tm
Ta
r
r
K0
tc

is the rms current in kA

Ief 40kA

is the conductor cross section in sq.mm

CV copper conductor

is the maximum allowable temperature in C

Tm 250 C

is the maximum ambient temperature in C

Ta 40 C

is the thermal coefficient of resistivity at reference


temperature (Tr) , from IEEE 80-2000 Table 1 in 1/C

r 0.00393

is the resistivity of the earthing conductor at reference


temperature (Tr) , from IEEE 80-2000 Table 1 in .cm

r 1.72 10

1/a0 or (1/a r ) - Tr , from IEEE 80-2000 Table 1 in C

K0 234.5C

is the duration of fault current considering the last line of


protection system for the high fault current i.e. operating time of
Zone 2 of distance protection from EGAT Substation, in s

1
C

cm

tc 0.35s

( TCAP) is the thermal capacity per unit volume from


IEEE 80-2000 Table 1 in J/(cm3.C)

TCAP 3.42

Therefore, the minimum size of PGCC is

Ac 139.574 mm2

J
cm

The 150 sq.mm. CV copper conductor is selected.


The insulated cable is selected to prevent the corrosion.

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 7 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

Calculation for the PGCC resistance:


2

0.0179

mm

copper cable resistivity at 20 C,

RPGCC_20

150mm
RPGCC_20 0.1193

PGCC cable resistance at 20 C

km

250 234.5
RPGCC_250 RPGCC_20

20 234.5
RPGCC_250 0.2272

PGCC cable resistance at 250 C

km

Assign
Rg

RPGCC_250
1000

(the resistance of ground conductor, ohm/m)

Rg 0.2272 10

(the geometric mean radius of ground conductor, mm)

rg 10.95

km
rg 0.75 14.6

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 8 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

CALCULATIONS:
For double circuit system (refer to Clause D.2.4 of IEEE 575-2014), the conductor current are;
Ia

assigned to cable 1a

Ib 1 i 0
Ic

assigned to cable 1b
3

assigned to cable 1c

For distance between cable, the numbering is assigned to the phase conductor as follows:

S12 0.16

S18

S23

S19 2 0.16

2 0.16

10 0.16

S13 0.16

S17 3 0.16

S14 3 0.16

S27

S25 0.16

S28 3 0.16

S36 3 0.16

S29

S15 2 0.16

S39 0.16

S35

5 0.16

S78 0.16

S16

10 0.16

S79 0.16

S37 2 0.16

S89

10 0.16

5 0.16

S1_11

13 0.16

S2_11

10 0.16

S1_12

13 0.16

S1_10 3
S38

2 0.16

5 0.16

S3_11 2
S3_12

2 0.16

10 0.16

2 0.16

The impedance are


7

Xaa 2 10

Xab 2 10

Xac 2 10

Xbb 2 10

Xbc 2 10

Xcc 2 10

dmm S14

ln

S12 S15

ln

S13 S16

ln

1
1

ln S S ln S S

12 18
12 1_11
1
ln 1 ln

S S
S S

13 19
13 1_12

dmm S25

ln

S23 S35

ln

dmm S36

Prepared by : Raktham S.

2
2

ln d S ln d S

mm 28
mm 2_11

1
ln 1 ln

S S
S S

23 38
23 3_11

ln

2
2

ln d S ln d S

mm 17
mm 1_10

2
2

ln d S ln d S

mm 39
mm 3_12

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 9 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

The open-circuit voltage on shields/sheaths to neutral are, (V/m) :


Ea0 Ia i Xaa Ib iXab Ic i Xac

Ea0 0.0002

[IEEE 575-2014, Eq. D14, page 41]

Eb0 Ia i Xab Ib iXbb Ic i Xbc

Eb0 0.0003

[IEEE 575-2014, Eq. D15, page 41]

Ec0 Ia i Xac Ib iXbc Ic i Xcc

Ec0 0.0003

[IEEE 575-2014, Eq. D16, page 41]

1 In case of normal operation


The current flow in the power cable based on 90 MW for one cable is;
3

Ifl

90 10
0.85

Ifl 265.7878

3 115 np

load current, in A

The three-sheath voltage gradients for a group of cables in HDD carrying balanced three-phase conductor currents are
given by:
(sheath voltage on Phase A cable, V/m)
Ea Ifl Ea0

Ea 0.063

(sheath voltage on Phase B cable , V/m)


Eb Ifl Eb0

Eb 0.0913

(sheath voltage on Phase C cable, V/m)


Ec Ifl Ec0

Prepared by : Raktham S.

Ec 0.0913

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 10 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

1. Underground Cable between SD-UG-2(1) to SD-UG-2(3)


Tthe metallic screen of power cables are bonded single point bond at one end by sectionalizing the sheath at MHE3.
The voltage gradient induced in a cable sheath during the current flow through the conductor are:
20.18

247.95

Sheath Voltage (V)

17.3
14.41
11.53
Ea. ( n)
8.65
5.77
2.88
0
0

94.67

189.33

284

378.67

473.33

568

473.33

568

473.33

568

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-A cable


29.25

247.95

Sheath Voltage (V)

25.07
20.89
16.72
Eb. ( n)
12.54
8.36
4.18
0
0

94.67

189.33

284

378.67

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-B cable

29.25

247.95

Sheath Voltage (V)

25.07
20.89
16.72
Ec.( n)
12.54
8.36
4.18
0
0

94.67

189.33

284

378.67

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-C cable

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 11 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

2. Underground Cable between SD-UG-2(5) to SD-UG-2(7)


Tthe metallic screen of power cables are bonded at single one end. The voltage gradient induced in a cable sheath
during the current flow through the conductor are:
13.39

Sheath Voltage (V)

11.48
9.56
7.65
Ea. ( n)
5.74
3.83
1.91
0
0

35.33

70.67

106

141.33

176.67

212

176.67

212

176.67

212

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-A cable

19.41

Sheath Voltage (V)

16.63
13.86
11.09
Eb. ( n)
8.32
5.54
2.77
0
0

35.33

70.67

106

141.33

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-B cable


19.41

Sheath Voltage (V)

16.63
13.86
11.09
Ec.( n)
8.32
5.54
2.77
0
0

35.33

70.67

106

141.33

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-C cable

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 12 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

3. Underground Cable between SD-UG-2(9) to EGAT


Tthe metallic screen of power cables are cross-bonded. The voltage gradient induced in a cable sheath during the
current flow through the conductor are:
distance to the end of the 1st major section

sp11 sp12 sp13 1041.05

distance to the end of the 2 nd major section sp sp sp sp sp sp 2118.52


11
12
13
21
22
23

distance to the end of the 3 rd major section

Prepared by : Raktham S.

sp11 sp12 sp13 sp21 sp22 sp23 sp31 sp32 sp33 2760.17

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 13 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

26.07

1041.05

2118.52

Sheath Voltage (V)

22.34
18.62
14.9
Ea. ( n)
11.17
7.45
3.72
0
0

460

920

1380

1840

2300

2760

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-A cable


38.5

1041.05

2118.52

Sheath Voltage (V)

32.09
25.67
Eb( n) 19.25
12.83
6.42
0
0

230

460

690

920

1150

1380

1610

1840

2070

2300

2530

2760

2300

2530

2760

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-B cable


36.47

1041.05

2118.52

Sheath Voltage (V)

30.39
24.31
Ec( n) 18.23
12.16
6.08
0
0

230

460

690

920

1150

1380

1610

1840

2070

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-C cable


For all cases, the maximum sheath voltage induced during normal operation is 38.5 V which is less than the
specified value i.e. 66 V of PEA design criteria.

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 14 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

2 In case of maximum permissible current


The current flow in the power cable based on the calculated maximum permissible current of one cable;
Refer to the calculation report for permissible current carrying capacity of cable.
the calculated maximum permissible current, in A
Ifl 421
Maximum power of one cable circuit is, in MVA
np

Ifl

3 115 167.7145

1000

The three-sheath voltage gradients for a group of cables in HDD carrying balanced three-phase conductor currents are
given by:
(sheath voltage on Phase A cable, V/m)
Ea Ifl Ea0

Ea 0.0998

(sheath voltage on Phase B cable , V/m)


Eb Ifl Eb0

Eb 0.1446

(sheath voltage on Phase C cable, V/m)


Ec Ifl Ec0

Prepared by : Raktham S.

Ec 0.1446

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 15 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

1. Underground Cable between SD-UG-2(1) to SD-UG-2(3)


31.97

247.95

Sheath Voltage (V)

27.4
22.83
18.27
Ea. ( n)
13.7
9.13
4.57
0
0

94.67

189.33

284

378.67

473.33

568

473.33

568

473.33

568

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-A cable


46.33

247.95

Sheath Voltage (V)

39.71
33.1
26.48
Eb. ( n)
19.86
13.24
6.62
0
0

94.67

189.33

284

378.67

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-B cable

46.33

247.95

Sheath Voltage (V)

39.71
33.1
26.48
Ec.( n)
19.86
13.24
6.62
0
0

94.67

189.33

284

378.67

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-C cable

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 16 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

2. Underground Cable between SD-UG-2(5) to SD-UG-2(7)


21.21

Sheath Voltage (V)

18.18
15.15
12.12
Ea. ( n)
9.09
6.06
3.03
0
0

35.33

70.67

106

141.33

176.67

212

176.67

212

176.67

212

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-A cable

30.74

Sheath Voltage (V)

26.35
21.96
17.56
Eb. ( n)
13.17
8.78
4.39
0
0

35.33

70.67

106

141.33

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-B cable

30.74

Sheath Voltage (V)

26.35
21.96
17.56
Ec.( n)
13.17
8.78
4.39
0
0

35.33

70.67

106

141.33

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-C cable

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 17 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

3. Underground Cable between SD-UG-2(9) to EGAT


41.29

1041.05

2118.52

Sheath Voltage (V)

35.39
29.49
23.59
Ea. ( n)
17.7
11.8
5.9
0
0

460

920

1380

1840

2300

2760

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-A cable

60.99

1041.05

2118.52

Sheath Voltage (V)

50.82
40.66
Eb( n) 30.49
20.33
10.16
0
0

230

460

690

920

1150

1380

1610

1840

2070

2300

2530

2760

2300

2530

2760

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-B cable

57.77

1041.05

2118.52

Sheath Voltage (V)

48.14
38.51
Ec( n) 28.88
19.26
9.63
0
0

230

460

690

920

1150

1380

1610

1840

2070

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-C cable


For all cases, the maximum sheath voltage induced during maximum permissible current carrying capacity of
cable is 60.99 V which is less than the specified value i.e. 66 V of PEA design criteria.

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 18 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

3 In case of MAX. 3-PHASE-FAULT CURRENT


I3sc

40 10

designed maximum 3-ph fault current flow through one cable, in A

np

(sheath voltage on Phase A cable, V/m)


Ea I3sc Ea0

Ea 4.7392

(sheath voltage on Phase B cable , V/m)


Eb I3sc Eb0

Eb 6.8694

(sheath voltage on Phase C cable, V/m)


Ec I3sc Ec0

Prepared by : Raktham S.

Ec 6.8694

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 19 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

1. Underground Cable between SD-UG-2(1) to SD-UG-2(3)


1518.53

247.95

Sheath Voltage (V)

1301.6
1084.66
867.73
Ea. ( n)
650.8
433.87
216.93
0
0

94.67

189.33

284

378.67

473.33

568

473.33

568

473.33

568

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-A cable

2201.1

247.95

Sheath Voltage (V)

1886.66
1572.22
1257.77
Eb. ( n)
943.33
628.89
314.44
0
0

94.67

189.33

284

378.67

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-B cable

2201.1

247.95

Sheath Voltage (V)

1886.66
1572.22
1257.77
Ec.( n)
943.33
628.89
314.44
0
0

94.67

189.33

284

378.67

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-C cable

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 20 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

2. Underground Cable between SD-UG-2(5) to SD-UG-2(7)


1007.41

Sheath Voltage (V)

863.49
719.58
575.66
Ea. ( n)
431.75
287.83
143.92
0
0

35.33

70.67

106

141.33

176.67

212

176.67

212

176.67

212

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-A cable


1460.24

Sheath Voltage (V)

1251.63
1043.03
834.42
Eb. ( n)
625.82
417.21
208.61
0
0

35.33

70.67

106

141.33

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-B cable

1460.24

Sheath Voltage (V)

1251.63
1043.03
834.42
Ec.( n)
625.82
417.21
208.61
0
0

35.33

70.67

106

141.33

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-C cable

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 21 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

3. Underground Cable between SD-UG-2(9) to EGAT


1961.54

1041.05

2118.52

Sheath Voltage (V)

1681.32
1401.1
1120.88
Ea. ( n)
840.66
560.44
280.22
0
0

460

920

1380

1840

2300

2760

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-A cable


2897.38

1041.05

2118.52

Sheath Voltage (V)

2414.48
1931.59
Eb( n) 1448.69
965.79
482.9
0
0

230

460

690

920

1150

1380

1610

1840

2070

2300

2530

2760

2300

2530

2760

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-B cable

2744.27

1041.05

2118.52

Sheath Voltage (V)

2286.89
1829.51
Ec( n) 1372.13
914.76
457.38
0
0

230

460

690

920

1150

1380

1610

1840

2070

x( n)
Cable Length (m)

The sheath voltage gradient in Phase-C cable


For all cases, the maximum sheath voltage induced during 3-phase short circuit current flow through cable is
2897.4 V

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 22 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

3 In case of MAX. SINGLE LINE-TO-GROUND FAULT CURRENT


3

Ief

40 10

designed maximum single line to ground fault current, in A

np

1. Underground Cable between SD-UG-2(1) to SD-UG-2(3)


Since the cables are bonded at mid span (one end ).
The PGCC is installed in vancant conduit of HDD paralleling to the phase conductors as depicted below

Geometric Mean Spacing between cable to PGCC


s1g

2 0.16

(distance from center of phase-A cable (1) to PGCC cable, mm)

s2g 0.16

(distance from center of phase-B cable (2) to PGCC cable, mm)

s3g 0.16

(distance from center of phase-C cable (3) to PGCC cable, mm)

s7g

(distance from center of phase-A cable (7) to PGCC cable, mm)

5 0.16

s8g 2 0.16

(distance from center of phase-B cable (8) to PGCC cable, mm)

s9g

(distance from center of phase-C cable (9) to PGCC cable, mm)

2 0.16

For the phase conductor (3-Phase group 1-2-3)


When Phase A - to -ground fault
(sheath voltage on Phase A cable when Phase-A to ground fault, V/m)
Ea Ief

2 s 2
s1g s7g
1g

Rg i 2 10
ln

d r ln S r

mm g
17 g

[IEEE 575-2014, Eq. E.5, page 40]

Ea

9.103

(sheath voltage on Phase B cable when Phase-A to ground fault , V/m)

ln

Eb Ief Rg i 2 10

s 1g s2g

s s
ln 1g 8g
S12 rg
S18 rg

[IEEE 575-2014, Eq. E.6, page 40]

Eb

11.281

(sheath voltage on Phase C cable when Phase-A to ground fault , V/m)

Ec Ief Rg i 2 10

ln

s 1g s3g

s s
ln 1g 9g
S13 rg
S19 rg

[IEEE 575-2014, Eq. E.7, page 40]

Ec

11.1528

The maximum induced sheath voltage is occurred at the un-bonded end of Phase B cable (i.e. Eb) =
Eb SM12 3615.234

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 23 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

When Phase B - to -ground fault


(sheath voltage on Phase A cable when Phase-B to ground fault , V/m)

ln

Ea Ief Rg i 2 10

s 1g s2g

s s
ln 2g 7g
S12 rg
S27 rg

Ea 11.5519

(sheath voltage on Phase B cable when Phase-B to ground fault, V/m)


Eb Ief

2 s 2
s2g s8g
2g

Rg i 2 10
ln
ln

d r
S28 rg

mm g

Eb 10.3818

(sheath voltage on Phase C cable when Phase-B to ground fault , V/m)

ln

Ec Ief Rg i 2 10

s 2g s3g

s s
ln 2g 9g
S23 rg
S29 rg

Ec

12.488

The maximum induced sheath voltage is occurred at the un-bonded end of Phase C cable (i.e. Ec) =
Ec SM12 4002.0365

When Phase C - to -ground fault


(sheath voltage on Phase A cable when Phase-C to ground fault , V/m)

ln

Ea Ief Rg i 2 10

s 1g s3g

s s
ln 1g 9g
S13 rg
S19 rg

Ea 11.1528

(sheath voltage on Phase B cable when Phase-C to ground fault , V/m)

ln

Eb Ief Rg i 2 10

s 3g s2g

s s
ln 3g 8g
S23 rg
S28 rg

Eb

12.4264

(sheath voltage on Phase C cable when Phase-C to ground fault, V/m)


Ec Ief

2 s 2
s3g s9g
3g

7
Rg i 2 10 ln
ln

d r
S39 rg

mm g

Ec 9.541

The maximum induced sheath voltage is occurred at the un-bonded end of Phase C cable (i.e. Ec) =
Eb SM12 3982.2829

For the phase conductor (3-Phase group 7-8-9)


When Phase A - to -ground fault
(sheath voltage on Phase A cable when Phase-A to ground fault, V/m)
Ea Ief

2 s 2
s1g s7g
7g

Rg i 2 10
ln
ln

d r
S17 rg

mm g

Ea

8.1256

Eb

10.2376

(sheath voltage on Phase B cable when Phase-A to ground fault , V/m)

Eb Ief Rg i 2 10

Prepared by : Raktham S.

ln

s 7g s2g

s s
ln 7g 8g
S27 rg
S78 rg

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 24 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

(sheath voltage on Phase C cable when Phase-A to ground fault , V/m)

ln

Ec Ief Rg i 2 10

s 7g s3g

s s
ln 7g 9g
S37 rg
S79 rg

Ec

10.1122

The maximum induced sheath voltage is occurred at the un-bonded end of Phase B cable (i.e. Eb) =

Eb

SM12 3280.8513

When Phase B - to -ground fault


(sheath voltage on Phase A cable when Phase-B to ground fault , V/m)

ln

Ea Ief Rg i 2 10

s 1g s8g

s s
ln 7g 8g
S18 rg
S78 rg

Ea

9.9738

Eb

8.8483

Ec

10.8838

(sheath voltage on Phase B cable when Phase-B to ground fault, V/m)


Eb Ief

2 s 2
s2g s8g
8g

Rg i 2 10
ln

d r ln S r

mm g
28 g

(sheath voltage on Phase C cable when Phase-B to ground fault , V/m)

ln

Ec Ief Rg i 2 10

s 8g s3g

s s
ln 8g 9g
S38 rg
S89 rg

The maximum induced sheath voltage is occurred at the un-bonded end of Phase C cable (i.e. Ec) =

Ec

SM12 3487.9377

When Phase C - to -ground fault


(sheath voltage on Phase A cable when Phase-C to ground fault , V/m)

ln

Ea Ief Rg i 2 10

s 9g s1g

s s
ln 9g 7g
S19 rg
S79 rg

Ea

10.2376

Eb

11.281

(sheath voltage on Phase B cable when Phase-C to ground fault , V/m)

Eb Ief Rg i 2 10

s s
ln 9g 8g
S29 rg
S89 rg

ln

s 9g s2g

(sheath voltage on Phase C cable when Phase-C to ground fault, V/m)


Ec Ief

2 s 2
s3g s9g
9g

Rg i 2 10
ln

d r ln S r

mm g
39 g

Ec 8.7849

The maximum induced sheath voltage is occurred at the un-bonded end of Phase C cable (i.e. Ec) =

Eb

SM12 3615.234

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 25 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

2. Underground Cable between SD-UG-2(5) to SD-UG-2(7)


The cables are bonded at one end.
The PGCC is installed in vancant conduit of HDD paralleling to the phase conductors as depicted below

Since the cable length of this section


m

SM2 212.57

is signeficantly shorter than

SM2

<

SM12 320.47

the cable length of item 1 above

SM12

Therefore, the calculated induced sheath voltage of this cable section is lower.
No calculation is done for this cable section.

3. Underground Cable between SD-UG-2(9) to EGAT


As the single major section of cross-bonding cable having the sheath earthed at both ends, the returning current
circulates in the path formed by the three sheaths and the ground and divides equally between three sheath circuits
Considering the longest minor section, the voltage between sheaths at cross-bonding points can be calculated as
follows;
For the phase conductor (3-Phase group 1-2-3)
For Phase A-Ground Fault
(sheath voltage between Phase A and Phase B at the cross bonding point, when fault in phase A cable, V/m

Vab Ief i 2 10

ln

2 S12
dmm

S
ln 27

S17

[IEEE 575-2014, Eq. E.18, page 49]

Vab

1.8619

(sheath voltage between Phase B and Phase C at the cross bonding point, when fault in phase A cable, V/m)
[IEEE 575-2014, Eq. E.19, page 49]

( Vbc 0)

Vbc

(sheath voltage between Phase C and Phase A at the cross bonding point, when fault in phase A cable, V/m),
[IEEE 575-2014, Eq. E.20, page 49]

( Vca Vab)

Vca

1.8619

So, the sheath voltage between Phase A and Phase B at the cross bonding point, when fault in phase A cable

Vab_max Vab sp M

Vab_max

745.4888

For Phase B-Ground Fault


(sheath voltage between Phase B and Phase C at the cross bonding point, when fault in phase B cable, V/m

Vbc Ief i 2 10

Prepared by : Raktham S.

ln

2 S23
dmm

S
ln 38

S28

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

Vbc 1.8619

page 26 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

(sheath voltage between Phase C and Phase A at the cross bonding point, when fault in phase B cable, V/m)
Vca 0

Vca 0

(sheath voltage between Phase C and Phase B at the cross bonding point, when fault in phase B cable, V/m),
Vcb Vbc

Vcb 1.8619

So, the sheath voltage between Phase A and Phase B at the cross bonding point, when fault in phase A cable
Vbc_max Vbc sp M

Vbc_max 745.4888

For Phase C-Ground Fault


(sheath voltage between Phase C and Phase A at the cross bonding point, when fault in phase C cable, V/m

Vca Ief i 2 10

ln

2 S13
dmm

S
ln 19

S39

Vca 2.6667

(sheath voltage between Phase A and Phase B at the cross bonding point, when fault in phase c cable, V/m)
Vab 0

Vab 0

(sheath voltage between Phase B and Phase C at the cross bonding point, when fault in phase C cable, V/m),
Vcb Vbc

Vbc 1.8619

So, the sheath voltage between Phase A and Phase B at the cross bonding point, when fault in phase A cable
Vca_max Vca sp M

Vca_max 1067.7445

Therefore, the maximum induced voltage due to earth fault is;


Vpp_max max( Vab_max Vbc_max Vca_max )

Vpp_max 1067.7445

The calculated max. induced voltage is a voltage across two phase metallic sheath. Each one is connected to ground
via Sheath Voltage Limiter (SVL). So, the maximum induced voltage to ground is:
Vef

Vpp_max

Vef 533.8723

For the phase conductor (3-Phase group 7-8-9)


For Phase A-Ground Fault
(sheath voltage between Phase A and Phase B at the cross bonding point, when fault in phase A cable, V/m

Vab Ief i 2 10

ln

2 S78
dmm

S
ln 18

S17

Vab

1.8619

(sheath voltage between Phase B and Phase C at the cross bonding point, when fault in phase A cable, V/m)

( Vbc 0)

Vbc

(sheath voltage between Phase C and Phase A at the cross bonding point, when fault in phase A cable, V/m),

( Vca Vab)

Vca

1.8619

So, the sheath voltage between Phase A and Phase B at the cross bonding point, when fault in phase A cable
Vab_max Vab sp M

Prepared by : Raktham S.

Vab_max

745.4888

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 27 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

For Phase B-Ground Fault


(sheath voltage between Phase B and Phase C at the cross bonding point, when fault in phase B cable, V/m

Vbc Ief i 2 10

ln

2 S89
dmm

S
ln 29

S28

Vbc 1.8619

(sheath voltage between Phase C and Phase A at the cross bonding point, when fault in phase B cable, V/m)
Vca 0

Vca 0

(sheath voltage between Phase C and Phase B at the cross bonding point, when fault in phase B cable, V/m),
Vcb Vbc

Vcb 1.8619

So, the sheath voltage between Phase A and Phase B at the cross bonding point, when fault in phase A cable
Vbc_max Vbc sp M

Vbc_max 745.4888

For Phase C-Ground Fault


(sheath voltage between Phase C and Phase A at the cross bonding point, when fault in phase C cable, V/m

Vca Ief i 2 10

ln

2 S79
dmm

S
ln 37

S39

Vca 2.6667

(sheath voltage between Phase A and Phase B at the cross bonding point, when fault in phase c cable, V/m)
Vab 0

Vab 0

(sheath voltage between Phase B and Phase C at the cross bonding point, when fault in phase C cable, V/m),
Vcb Vbc

Vbc 1.8619

So, the sheath voltage between Phase A and Phase B at the cross bonding point, when fault in phase A cable
Vca_max Vca sp M

Vca_max 1067.7445

Therefore, the maximum induced voltage due to earth fault is;


Vpp_max max( Vab_max Vbc_max Vca_max )

Vpp_max 1067.7445

The calculated max. induced voltage is a voltage across two phase metallic sheath. Each one is connected to ground
via Sheath Voltage Limiter (SVL). So, the maximum induced voltage to ground is:
Vef

Vpp_max
2

Vef 533.8723

For all cases, the maximum sheath voltage induced during single to ground fault current flow through cable is
4002 V

4. Insulation of Cable Outer Sheath (Jacket)


The maximum sheath voltage induced during three phase short circuit current is 4,002 V. In order to
determined the insulation level of outer sheath of cable, IEC std 60502-1 could be used. The power frequency
withstand voltage of a 2.8 mm PVC sheath thickness for 3.6 kV cable, 800 sq.mm. is 6.5 kV (refer to pages 27 &
49 respectively) The insulation level of PE is superier to PVC.
So the insulation level of the 3.5 mm thickness of PE outer sheath for 115 kV power cable is higher than
3.5mm

6.5kV 8.125 kV

The outer sheath of cable can withstand the maximum induced sheath voltage.

2.8mm

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 28 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

5. Selection of Sheath Voltage Limiter


The induced volatge in cable sheaths at the cross-bonding points is high during fault external to the cable circuit.
The Sheath Voltage Limiter (SVL) shall be installed to connected between the cable sheath and the earth with
separated limiter as per diagram in FIGURE 1.
The basic design criterion for selection of cable sheath voltage limiter in case using of non-linear resistance surge
arrester, is to keep sheath overvoltage as low as practical.
However, the maximum continuous operating voltage (MCOV) of surge arrester shall be high enough to withstand the
50 Hz overvoltages resulting from system faults external to cable circuit [IEEE 575-2014].
The maximum sheath voltage induced from the maximum allowable 3-phase fault current external to the cable circuit is
4002. The IEEE Std C62.22- 1991 recommendation is a minimum margin of protection greater than or equal to 20%.
So, the MCOV of the surge arrester shall be not less than = 4002 1.2 4802.4 Select the surge arrester is
Ur = 6 kV, 10 kA
MCOV = 5.1 kV

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 29 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

ANNEX 1

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 30 of 31

Gult-Tasit 1 Project

Power Cable Calculations


Sheath Induced Voltage

ANNEX 2

Prepared by : Raktham S.

Date :10-Jul-16
File: Gult-TS1-GTS1 - Sheath Voltage

page 31 of 31