Documentos de Académico
Documentos de Profesional
Documentos de Cultura
ZTE CORPORATION
No. 55, Hi-tech Road South, ShenZhen, P.R.China
Postcode: 518057
Tel: +86-755-26771900
Fax: +86-755-26770801
URL: http://ensupport.zte.com.cn
E-mail: support@zte.com.cn
LEGAL INFORMATION
Copyright 2013 ZTE CORPORATION.
The contents of this document are protected by copyright laws and international treaties. Any reproduction or
distribution of this document or any portion of this document, in any form by any means, without the prior written
consent of ZTE CORPORATION is prohibited.
Revision History
Revision No.
Revision Date
Revision Reason
R1.2
20131015
R1.1
20130730
R1.0
20130416
First edition
SJ-20121213161403-006|20131015 (R1.2)
Contents
About This Manual ......................................................................................... I
Chapter 1 Installation Preparations .......................................................... 1-1
1.1 Technical Documents Preparation ....................................................................... 1-1
1.2 Tools Preparation ............................................................................................... 1-2
1.3 Equipment Assemblies ....................................................................................... 1-4
1.4 Installation Environment Requirements ................................................................ 1-4
II
SJ-20121213161403-006|20131015 (R1.2)
Figures............................................................................................................. I
III
SJ-20121213161403-006|20131015 (R1.2)
Tables .............................................................................................................V
Glossary .......................................................................................................VII
IV
SJ-20121213161403-006|20131015 (R1.2)
Intended Audience
l
l
Installation engineers
Maintenance engineers
Summary
Inspection
Chapter 3, Cabinet Installation
Power-Off
Feeder System
installation.
Installation
Appendix A, Cables
I
SJ-20121213161403-006|20131015 (R1.2)
II
SJ-20121213161403-006|20131015 (R1.2)
Chapter 1
Installation Preparations
Table of Contents
Technical Documents Preparation ..............................................................................1-1
Tools Preparation .......................................................................................................1-2
Equipment Assemblies ...............................................................................................1-4
Installation Environment Requirements ......................................................................1-4
Product manuals
1-1
SJ-20121213161403-006|20131015 (R1.2)
Note:
Technical documents required for the equipment installation include but are not limited to
those given in this section. Installation personnel should prepare the documents according
to actual requirement.
Tool
Long tape measure
Ruler (1 m)
Marking tools
Marking pen
Marking pin
Hydraulic pressure percussion drill
Concrete drilling tools
Fastening tools
Socket wrench M6 ~ M19
Ring wrench M6 ~ M19
Industrial horizontal ruler
Tape
Measurement tools
Ruler
Angle square
1-2
SJ-20121213161403-006|20131015 (R1.2)
Category
Tool
Brush
Nipper
Paper knife
Bellows
Electric iron
Auxiliary tools
Tin wire
Ladder
Forklift
Iron hammer
Plumb
Power connector board (with 2-phase and 3-phase sockets)
Sharp nose pliers
Diagonal pliers
Pliers
Hand-held electric drill
Locksmith tools
Hand file
Handsaw
Crowbar
Rubber hammer
Torque wrench (45 Nm)
Multimeter
Common instruments
500 V megohmmeter (used to measure insulation resistance)
Coaxial trunk self-loop cable
Coaxial cable installation tool
Grounding resistance tester
Antistatic wrist strap
Clamping pincers
Special-purpose tools
Cable winding gun
Wire stripper
Crimper
Washer
Marking template
1-3
SJ-20121213161403-006|20131015 (R1.2)
l
l
Grounding cable
Power cable
Clock cable
Service cable
PD485 cable
Caution!
To facilitate heat dissipation, if the cabinets are arranged in rows, the adjacent rows
should face contrary directions, that is, back-to-back or face-to-face.
1-4
SJ-20121213161403-006|20131015 (R1.2)
Note:
The maximum power consumptions at full configuration are as follows:
1-5
SJ-20121213161403-006|20131015 (R1.2)
Grounding facilities
The grounding facilities have been installed and passed the test.
External interfaces
The devices to be externally connected, such as transmission devices, ODF, or DDF
are installed completely. The interfaces to be used for the installation are reserved.
1-6
SJ-20121213161403-006|20131015 (R1.2)
Chapter 2
Determine the participants from both parties, and both the users representatives and
the vendors representatives must be present during Unpacking & acceptance.
Determine where and how to keep the goods after the inspection.
Prepare proper tools like iron hammer, paper cutter, crowbar, and others.
Caution!
Do not remove the plastic bag until pulling out the cabinet. Hold the solid base of the
cabinet. Do not apply forces on non-rigid areas, which include cable support and fixing
beam, to avoid damaging the equipment.
End of Steps
2-1
SJ-20121213161403-006|20131015 (R1.2)
Example
For unpacking the cabinet, refer to Figure 2-1.
Figure 2-1 Unpacking Wooden Case
1. Cushion 1
2. Upper Cover
3. Cushion 2
4. Main Frame
5. Cabinet
6. Side Cover
Caution!
When taking the board out, do not remove the antistatic protection bag.
End of Steps
Goods Inspection
It contains cabinet inspection and board inspection.
Cabinet inspection may check the following items:
l
l
l
l
l
l
After unpacking, make sure the boards are not scratched or damaged, no components
or devices on the boards are damaged or missing, and the board numbers and version
numbers match the packing list.
The vendor should take the major responsibility for checking electrically sensitive
equipment and devices. The inspected goods should be placed by types.
Goods Handover
After goods inspection completes, both parties should sign Unpacking and Inspecting
Report. The equipment is handed over to the user. Each party should hold one copy of
Unpacking and Inspecting Report. Within 7 days, the project supervisor should feed back
Inspection Conclusion in Unpacking and Inspecting Report to ZTE for archiving.
2-3
SJ-20121213161403-006|20131015 (R1.2)
Caution!
Inspect the goods according to Unpacking and Inspecting Report and the label attached
on the exterior of the packing case. If there are shortages, wrong deliveries, and damaged
packing materials, report them in time.
2-4
SJ-20121213161403-006|20131015 (R1.2)
Chapter 3
Cabinet Installation
Table of Contents
Overview ....................................................................................................................3-1
Cabinet Installation.....................................................................................................3-1
Cabinet Layout Requirements ....................................................................................3-2
Cabinet Components..................................................................................................3-3
Cabinet Installation Modes .........................................................................................3-6
Perform Insulation Test.............................................................................................3-20
Connecting Adjacent Cabinets .................................................................................3-20
Cabinet Accessory Installation..................................................................................3-21
3.1 Overview
This section describes the ZXUR 9000 UMTS cabinet installation procedure, including
two installation modes, that is, cabinet installation on cement floor and adjustable base
installation.
3-1
SJ-20121213161403-006|20131015 (R1.2)
The cabinet layout should facilitate hardware installation, daily maintenance, and
future capacity expansion.
The bearing capacity of the floor is within the secure range, and the load is distributed
evenly.
The cabinet layout must be designed and confirmed together by technical personnel
of the equipment supplier and the installation personnel. The installation position
and direction of the cabinet should comply with the requirement in the engineering
design drawing. The main walkway between rows of cabinets must be straight, with
an tolerance not over 5 mm.
Usually, cabinets are arranged in the equipment room in the form of rows. For
information details of distance between cabinets and distance between cabinet
3-2
SJ-20121213161403-006|20131015 (R1.2)
Model A
160 mm ~ 240 mm
Model B
240 mm ~ 390 mm
Model C
390 mm ~ 690 mm
Figure 3-3, Figure 3-4, and Figure 3-5 show the appearance of each base model. Two
bases are used in fixing the cabinet.
3-3
SJ-20121213161403-006|20131015 (R1.2)
3-4
SJ-20121213161403-006|20131015 (R1.2)
2. Big washer
3. Movable bracket
3-5
SJ-20121213161403-006|20131015 (R1.2)
8. Adjusting washer (1 mm or
2 mm)
3-6
SJ-20121213161403-006|20131015 (R1.2)
Caution!
The applicable height range refers to the height L between the cabinet bottom and the
ground after the cabinet is installed.
Use the adjustable base and expansion bolts to fix the cabinet on the ground. Adjust the
height of the adjustable base, and make the cabinet bottom align with the antistatic floor,
as shown in Figure 3-8.
Figure 3-8 Adjustable Base Installation (Front View)
1. Cabinet
2. Antistatic floor
3. Adjustable base
4. Groundsill
Steps
1. Loosen the height-locking screws of the adjustable base. Adjust the movable bracket
along the direction of arrows shown in Figure 3-9 up and down according to the height
of the antistatic floor.
3-8
SJ-20121213161403-006|20131015 (R1.2)
1. Movable bracket
2. Fixed bracket
2. Use the height-locking bolt (provided with the adjustable base) to connect the movable
bracket and the fixed bracket. Use the torque wrench to fasten the height-locking bolt
to 75 Nm. To ensure a reliable connection between the movable bracket and the fixed
bracket, fasten bolts at sides first, then fasten bolts at the front.
Note:
Use three height-locking bolts at each connection point of the movable bracket and
the fixed bracket.
End of Steps
3-9
SJ-20121213161403-006|20131015 (R1.2)
Steps
1. If the ground of the equipment room has not been measured, use a horizontal ruler to
measure the equipment room to ensure that the cabinet will not slant after installation.
2. According to the installation drilling template, decide the positions of expansion bolt
holes, which are marked with 1, as shown in Figure 3-10.
Figure 3-10 Installing Drilling Template
Caution!
The structure diagram of adjustable base and the installation drilling template
indicate that there are three holes at the adjustable base bottom for fixing-screw
installation. However, only the two side holes are used in practical installation of
the ZXUR 9000 UMTS cabinet.
When determining the installation position, avoid conflict between the positions of
installing the base and the frame of antistatic floor, and try to keep the integrity
of the floor's framework. If the position conflict is inevitable, the floor's framework
involved must be removed during the installation.
End of Steps
l
l
l
l
Steps
1. Drill holes on the ground. Hold the drill stock of a percussion drill (or an electric
hammer) firmly with both hands, and press it downwards vertically. Drill four holes
of 15.5, with a depth of 110 mm.
Note:
If the ground surface is too smooth to position the drill bit, drill a concave hole at the
hole position first to help positioning.
3-11
SJ-20121213161403-006|20131015 (R1.2)
Steps
1. Adjust the height of the adjustable base, and place it at the corresponding position
according to the expansion bolt positions.
2. Place the flat washer, spring washer, and insulating washer on the expansion bolt. Fix
the base to the ground with nuts, and the fastening torque should reach 75 Nm. Figure
3-12 shows the base fixed to the ground.
Figure 3-12 Connecting Base and Ground
1. Spring washer
2. Flat washer
3. Insulating gasket
4. Sleeve
5. Hexagon head bolt
M1290
6. Adjusting washer
3. Measure the level of the adjustable base with a gradienter. The level tolerance of a
single base should be not more than 1 mm. The tolerance of level difference between
two adjacent bases should be not more than 1 mm. If the base is not level, put the
adjusting washer between the base and the ground to make the base level, as shown
Figure 3-12.
3-12
SJ-20121213161403-006|20131015 (R1.2)
Caution!
In connecting the cabinet and the base, it is required that the contact resistance
between them must be very small. Therefore, the lacquer between the surface of the
base and the cabinet must be cleaned.
End of Steps
Steps
1. Place the cabinet on the adjustable base manually or with the hoisting equipment.
Make sure that the four sides (front, rear, left, and right) of the cabinet parallel to the
walls of the equipment room.
2. Fix the cabinet with the flat washer, spring washer, and bolts, and the fastening torque
should reach 75 Nm, as shown in Figure 3-13.
Figure 3-13 Fixing Cabinet and Adjustable Base
3-13
SJ-20121213161403-006|20131015 (R1.2)
3. Perform the insulation test. For operations details, refer to Performing Insulation Test
in this chapter.
4. To install multiple cabinets, after the cabinets in one row are positioned, adjust and fix
the outmost cabinet in the row first. Then, take this cabinet as the reference, adjust
other cabinets one by one, connect adjacent two cabinets, and fix the cabinets. Repeat
the above operations to install the subsequent rows of cabinets.
5. Clean the ground.
End of Steps
Result
Figure 3-14 shows a single cabinet installed on the adjustable base.
Note:
To clarity the position relationship among the cabinet, adjustable base, and ground, the
antistatic floor is omitted in the figure.
3-14
SJ-20121213161403-006|20131015 (R1.2)
Flow
Figure 3-15 shows the installation flow.
3-15
SJ-20121213161403-006|20131015 (R1.2)
Steps
1. If the ground of the equipment room has not been measured, use a horizontal ruler to
measure the equipment room to ensure that the cabinet will not slant after installation.
2. According to the installation drilling template, decide the positions of expansion bolt
holes, which are marked with 2, as shown in Figure 3-16.
3-16
SJ-20121213161403-006|20131015 (R1.2)
End of Steps
Steps
1. Use the horizontal ruler to measure the level of the cement floor.
If the cement floor is not level, put the adjusting washer between the cabinet and the
floor to make the cabinet level.
3-17
SJ-20121213161403-006|20131015 (R1.2)
2. Place the cabinet on the positions of expansion bolts manually or with the hoisting
equipment. Make sure that the four sides (front, rear, left, and right) of the cabinet
parallel to the walls of the equipment room.
3. Fix the cabinet with the flat washer, spring washer, and bolts, and the fastening torque
should reach 75 Nm, as shown in Figure 3-17.
Figure 3-17 Cabinet Installation on Cement Floor
Result
Figure 3-18 shows a fixed single cabinet.
3-18
SJ-20121213161403-006|20131015 (R1.2)
3-19
SJ-20121213161403-006|20131015 (R1.2)
Context
To avoid static electricity generated between cabinet bottom and ground, use the
multimeter to check whether the circuit at the cabinet bottom is disconnected.
Steps
1. Set the multimeter to the resistor gear.
2. Use the multimeter's two measure probes to contact the metal part of cabinet bottom
and the expansion bolt to measure the resistance.
3. Perform relevant operations according to the test result.
Test Result
Operation
nected
If the circuit is con-
The cabinet bottom is not insulated from the ground. Check whether the
nected
End of Steps
Context
l
l
In connecting adjacent cabinets, only the two cabinet doors at the two sides of the
same row should be installed, and other side doors need not be installed.
Upon delivery, each cabinet contains two connecting plates for combining cabinets
and eight cross recess head screws (M412) on the cabinet top.
3-20
SJ-20121213161403-006|20131015 (R1.2)
Steps
1. Disassemble the four cross recess head screws that are used to fix the connecting
plate for combining cabinets. Put the screws away lest they might fall into the cabinet
or the gap between cabinets.
2. Move the connecting plate for combining cabinets to the position between two adjacent
cabinets. Make the two screw holes align with the screw holes on the cabinet top, and
make the other two screw holes align with the connection holes on the top of the other
cabinet.
3. Use four cross recess head screws to fix the connecting plate for combining cabinets
between two adjacent cabinets. Fasten screws to make the two cabinet cling together.
The fastening torque should reach 1.5 ~ 1.8 Nm.
4. Repeat step 1 ~ 3 for the other connecting plate for combining cabinets. Figure 3-19
shows the connected two adjacent cabinets.
Figure 3-19 Connecting Adjacent Cabinets
End of Steps
The installation positions of shelves are decided according to the engineering design.
The following tools are required: flathead screwdriver and cross screwdriver.
Prepare a pencil.
3-21
SJ-20121213161403-006|20131015 (R1.2)
Context
l
The guide rails are used to support the subrack. The floating nuts are used to fix the
subrack. Before installing the service subrack, power distribution subrack, ventilation
subrack, and enclosing-wind subrack, the guide rails and floating nuts must be
installed.
The guide rails and floating nuts have been installed upon delivery of the cabinet. Only
in case of special requirement can maintenance personnel install the guide rails and
floating nuts according to the operation steps described in this topic.
Steps
1. Install the guide rails (in pairs).
a. Find the installation position of the subrack on the post according to the
engineering design, and mark the position at corresponding holes on the angle
rail.
b. Use the tapping screws to fix the guide rail at the holes marked on the angle rail,
as shown in Figure 3-20.
Figure 3-20 Installing Guide Rail
1. Angle rail
2. Guide rail
3. Tapping screw
a. Check both ends of the guide rail to see whether it is horizontal and whether the
pairs of guide rails are horizontal.
2. Install the floating nuts.
a. Use pencil to mark at the shelf-fixing hole on the front of the angle rail above the
guide rail.
b. Use the installation spring plate to fix the floating nut at the marked position, as
shown in Figure 3-21.
3-22
SJ-20121213161403-006|20131015 (R1.2)
1. Floating nut
2. Angle rail
3. Installation spring
plate
c. Check whether the floating nut position is correct and whether it is fastened.
End of Steps
Result
Figure 3-22 and Figure 3-23 show the installed floating nut.
Figure 3-22 Installed Floating Nut (Side View)
3-23
SJ-20121213161403-006|20131015 (R1.2)
The installation positions of shelves are decided according to the engineering design.
The following tools are required: flathead screwdriver and cross screwdriver.
The left and the right guide rails of the shelf have been installed on the front and the
rear posts of the cabinet.
Caution!
The shelf must be empty (dummy panel can be contained) during the shelf installation;
otherwise, the shelf and the boards might be damaged due to an unstable center of gravity.
Context
The shelves have been installed upon delivery of the cabinet. Only in case of special
requirement can maintenance personnel install the shelves according to the operation
steps described in this topic.
Steps
1. Hold the bottom and two flanges of the shelf, and slowly move it to the cabinet front.
Make sure that the shelf and the cabinet have the same orientation.
3-24
SJ-20121213161403-006|20131015 (R1.2)
Caution!
When taking the shelf, do not put hands through parts like the fan subrack's handle,
the power module's handle, or cable trough.
2. Put the shelf on the left and the right guide rails, and push the shelf into the cabinet
along the rail until the two flanges of the shelf touch the posts of the cabinet.
3. Insert the screw into the floating nut from the hole for installing the flange. Fasten each
screw and fix the shelf, as shown in Figure 3-24. Here, the M6 screw is used, and the
fastening torque should reach 3.2 ~ 3.7 Nm.
Figure 3-24 Installing Shelf
End of Steps
3-25
SJ-20121213161403-006|20131015 (R1.2)
Follow-Up Action
Check the shelf installation:
l
l
l
Push the shelf to see whether it is loosened. Make sure that the shelf is fixed tightly
in the cabinet.
Check whether the shelf is installed horizontally. Make sure that the shelf is not slanting.
Make sure that the left and the right guide rails are not distorted, and make sure that
they can bear the weight of the shelf.
The fan subrack has been installed upon delivery of the cabinet. If the fan does not
work normally, user should replace it with a normal one.
The fan subrack gets power supply from the power interface on the backplane of ETCA
service subrack. It does not have the power cable, and is hot-pluggable.
The number of fans differs in the front fan subrack and the rear fan subrack of the
ETCA service subrack. However, the methods of replacing them are the same.
Steps
1. Pull out the fan subrack: Press the two red buttons on the panel of the fan subrack,
and pull out the fan subrack from the fan slot of the ETCA service surack, as shown
in Figure 3-25.
3-26
SJ-20121213161403-006|20131015 (R1.2)
2. Install the fan subrack: Push the fan subrack into the fan slot of the ETCA service
subrack until hearing a click, which indicates that it is firmly installed, as shown in
Figure 3-26.
Note:
During the installation, you need not press the two red buttons, just push the fan
subrack.
3-27
SJ-20121213161403-006|20131015 (R1.2)
l
l
Caution!
To guarantee the ventilation and heat dissipation of the whole system, the
maintenance time for each fan subrack should be within 25 minutes.
Before pushing the fan subrack into the fan slot, make sure that the cables inside
the fan module are not higher than the fan's upper surface, which helps avoid
cable damage.
End of Steps
Follow-Up Action
Use either of the following methods to observe the fan's working status:
l Put a small strip of paper above the fan subrack to test whether the fan ventilates
normally.
l If the RUN indicator flashes every second and the ALM indicator is OFF, the fan works
normally.
3-28
SJ-20121213161403-006|20131015 (R1.2)
Context
There are two power-box slots at the back of each ETCA service subrack for installing the
power box, providing the -48 V DC power supply for the ETCA subrack.
Steps
1. Hold the handle of the power box, and insert the power box into the power-box slot at
the back of the ETCA service subrack until the power box panel aligns with the shelf
panel.
Now, the power box and the power interface at the shelf's backplane are connected
completely.
2. Fasten screws on the power box with the cross screwdriver, as shown in Figure 3-27.
Figure 3-27 Installing Power Box
1. Handle 1
2. Handle 2
3. Screw
End of Steps
3-29
SJ-20121213161403-006|20131015 (R1.2)
Follow-Up Action
Repeat the above operations to install the other power box for the same ETCA service
subrack.
Context
There are two ECDM slots at the back of each ETCA service subrack for installing the
ECDM module. The ECDM module is used for managing the information of slots inside
the shelf.
Steps
1. Hold the handle of the ECDM module, and insert the ECDM module into the ECDM
slot until the ECDM panel aligns with the shelf panel. Now, the ECDM module and the
ECDM interface at the ETCA backplane are connected completely.
2. Fasten screws on the ECDM module with the cross screwdriver, as shown in Figure
3-28.
Figure 3-28 Installing ECDM Module
1. Screw
2. Handle
End of Steps
3-30
SJ-20121213161403-006|20131015 (R1.2)
Context
The power distribution subrack is also called Power Distribution Unit (PDU). The power
distribution subrack has been installed upon delivery of the cabinet. Only in case of special
requirement can maintenance personnel install the power distribution subrack according
to the operation steps described in this topic.
Steps
1. Hold the bottom and two flanges of the power distribution subrack, and slowly move
it to the cabinet front. Make sure that the power distribution subrack and the cabinet
have the same orientation.
2. Put the power distribution subrack on the left and the right guide rails, and push the
power distribution subrack into the cabinet along the rail until the two flanges of it touch
the posts of the cabinet.
3. Insert the screw into the floating nut from the hole for installing the flange. Fasten each
screw and fix the power distribution subrack, as shown in Figure 3-29. Here, the M6
screw is used, and the fastening torque should reach 3.2 ~ 3.7 Nm.
Figure 3-29 Installing Power Distribution Subrack
End of Steps
3-31
SJ-20121213161403-006|20131015 (R1.2)
Context
The ventilation subrack is used to change the ventilation pipe from vertical to front-back
directional.
Steps
1. Hold the bottom and two flanges of the ventilation subrack, and slowly move it to the
cabinet front. Make sure that the ventilation subrack and the cabinet have the same
orientation.
2. Put the ventilation subrack on the left and the right guide rails, and push the ventilation
subrack into the cabinet along the rail until the two flanges of it touch the posts of the
cabinet.
3. Insert the screw into the floating nut from the hole for installing the flange. Fasten each
screw and fix the ventilation subrack, as shown in Figure 3-30. Here, the M6 screw is
used, and the fastening torque should reach 3.2 ~ 3.7 Nm.
Figure 3-30 Installing Ventilation Subrack
End of Steps
3-32
SJ-20121213161403-006|20131015 (R1.2)
The installation position of wind trap subrack is decided according to the engineering
design.
The following tools are required: flathead screwdriver and cross screwdriver.
The left and the right guide rails of the wind trap subrack have been installed on the
front and the rear posts of the cabinet.
Context
The wind trap subrack is used to trap the wind from around.
Steps
1. Hold the two flanges of the wind trap subrack, and slowly move it to the cabinet front.
Make sure that the wind trap subrack and the cabinet have the same orientation.
2. Put the wind trap subrack on the left and the right guide rails, and push the wind trap
subrack into the cabinet along the rail until the two flanges of it touch the posts of the
cabinet.
3. Insert the screw into the floating nut from the hole for installing the flange. Fasten each
screw and fix the wind trap subrack, as shown in Figure 3-31. Here, the M6 screw is
used, and the fastening torque should reach 3.2 ~ 3.7 Nm.
Figure 3-31 Installing Wind Trap Subrack
End of Steps
3-33
SJ-20121213161403-006|20131015 (R1.2)
Context
The ventilation panel is used for ventilation and cabinet decoration.
Steps
1. Install the ventilation panel at blank area between subracks, and fix it with screws, as
shown in Figure 3-32.
Figure 3-32 Installing Ventilation Panel
End of Steps
Context
The cabling rack and cable drum inside cabinet perform the following functions:
l To prevent cables from damage and make cable layout tidily, the cables are bound in
the cabling rack inside the cabinet.
l Redundant fibers should be wound in the cable drum below the cabling rack inside
the cabinet.
3-34
SJ-20121213161403-006|20131015 (R1.2)
The cabling rack inside the cabinet consists of the following two parts:
l Horizontal passage
l Vertical passage
Note:
The cabling rack and cable drum have been installed upon delivery of the cabinet. Only
in case of special requirement can maintenance personnel install them according to the
operation steps described in this topic.
Steps
1. Install the horizontal passage. Ensure that it is parallel or perpendicular to the rack
row.
a. Install the cable drum below the horizontal passage, as shown in Figure 3-33.
Here, the M3 screw is used, and the fastening torque should reach 0.6 ~ 0.8 Nm.
Figure 3-33 Installing Cable Drum
3-35
SJ-20121213161403-006|20131015 (R1.2)
1. Position for
installing the
service subrack
2. L-shaped
component
3. Ventilation
subrack (or wind
trap subrack)
1. Position for
installing the
service subrack
2. L-shaped
component
3. Ventilation
subrack (or wind
trap subrack)
a. Fix the horizontal passage with the cable drum on the L-shaped component, as
shown in Figure 3-36. Here, the M5 screw is used, and the fastening torque should
reach 3.2 ~ 3.7 Nm.
3-36
SJ-20121213161403-006|20131015 (R1.2)
Figure 3-37 shows the installed horizontal passage and cable drum.
Figure 3-37 Installed Horizontal Passage and Cable Drum
2. Install the vertical passage. Make sure that the vertical passage is perpendicular to
the ground.
End of Steps
Result
The cabling rack should meet the following requirements:
l
l
l
l
3-37
SJ-20121213161403-006|20131015 (R1.2)
Steps
1. Align the hinge hole at the bottom of the door with the lower hinge of the door to install
the lower part of the door.
2. Pull down the door's pin to align it with the upper hinge hole of the door, as shown in
Figure 3-38.
Figure 3-38 Installing Cabinet Front/Rear Door (1)
1. Pin
2. Hinge
3-38
SJ-20121213161403-006|20131015 (R1.2)
3. Release the door's pin to install the upper part of the door, as shown in Figure 3-39.
Figure 3-39 Installing Cabinet Front/Rear Door (2)
End of Steps
Result
Move the door to make sure that the door can be opened or closed smoothly.
3-39
SJ-20121213161403-006|20131015 (R1.2)
Follow-Up Action
Use cross recess head screws M816 to connect the lower part of the door and the
grounding cable (yellow/green) between cabinets.
Context
To keep the cabinet safe and clean, install the side door at both sides of a cabinet or a row
of cabinets.
Steps
1. Take out the side doors from the packing box. Handle with care to avoid any damage
to door surface.
2. Put the side door close to the cabinet, and adjust the side door position to align the
connection holes of the side door and the cabinet.
3. From the cabinet outside, connect the cabinet and the side door through M512
screws, and the fastening torque should reach 3.2 ~ 3.7 Nm, as shown in Figure 3-40.
3-40
SJ-20121213161403-006|20131015 (R1.2)
End of Steps
3-41
SJ-20121213161403-006|20131015 (R1.2)
Description
The cabinet row number indicates the cabinet number in the same equipment room.
Usually, the label is pasted on the top right corner of the cabinet's front door.
Figure 3-41 shows the positions where labels are pasted.
Figure 3-41 Label Positions
1. Cabinet top
3. Product nameplate
3-42
SJ-20121213161403-006|20131015 (R1.2)
Chapter 4
Cable Installation
Table of Contents
Cable Types and Installation Modes ...........................................................................4-1
Cable Layout Requirements .....................................................................................4-30
Caution!
Pay attention to the following things before installation:
l
l
l
l
The installation of system power cable and grounding cable complies with the principle
of from small to large, from device to system, and from device to power supply.
Never connect or disconnect any hot power cables. Do turn off the power supply
before installing or removing a power cable.
Make sure that lightning protection measures in installation environment check are
ready.
Make sure that the grounding resistance in installation environment check is qualified
and less than 1 ohm.
Required Tools
l
l
l
l
l
Straight screwdriver
Cross screwdriver
Socket wrench
Diagonal pliers
Cable tie
Related Information
DC PDU provides -48 V power for ZXUR 9000 UMTS cabinet. Two -48 V power
branches, after led out by ZXUR 9000 UMTS DC PDU, connect the input terminal of
power distribution subrack via cabinet-top. DC PDU does not belong to the ZXUR 9000
UMTS device components.
4-1
SJ-20121213161403-006|20131015 (R1.2)
The following contents introduce the two power cable categories in the respects of
specifications, structure, installation location, cabling direction and cabling diagram.
Type
ble Se-
Color
End A
End B
quence
PWR-20952002
ETCA
-48 V cable
PWR-91237-
-48VRTN
102
cable
PWR-20952002
-48 V cable
PWR-91237-
-48VRTN
102
cable
PWR-20952002
-48 V cable
PWR-91237-
-48VRTN
102
cable
PWR-20952002
-48 V cable
Blue
subrack
ing post A
nal B1
ETCA
2
Black
Blue
Black
Blue
Black
Blue
subrack
binding post A
terminal B1
ETCA
subrack
binding post B
nal B2
ETCA
subrack
binding post B
terminal B2
ETCA
subrack
binding post A
nal A1
ETCA
subrack
binding post A
terminal A1
ETCA
subrack
binding post B
nal A2
4-2
SJ-20121213161403-006|20131015 (R1.2)
CaCable ID
Type
ble Se-
Color
End A
End B
quence
PWR-91237-
-48VRTN
102
cable
ETCA
8
Black
subrack
binding post B
terminal A2
Figure 4-1 shows the structure of the exterior power cables. H-PWR-006 and H-PWR-007
cables have different colors, but the same structure.
Figure 4-1 Structure of an Exterior Power Cable
3. Non-flammable
heat-shrinkage tube
Figure 4-2 shows the cabling diagram (taking upward cabling mode as an example) of the
exterior power cables.
Figure 4-2 Cabling Diagram of Interior Power Cables
4-3
SJ-20121213161403-006|20131015 (R1.2)
Type
Color
No.
End A
PDU subrack
PWR-20908003
-48 V cable
Blue
INPUT (A) 48
V
connection
terminal 1
End B
-48 V connection terminal of
DC PDU
PDU subrack
PWR-20908-
004
ble
Black
INPUT (A) 48
V RTN con-
minal of DC
nection termi-
PDU
nal 1
PWR-20908-
-48 V cable
Blue
003
PWR-20908-
-48VRTN
004
cable
Black
PDU subrack
-48 V
INPUT (A) 48
connection
V connection
terminal of DC
terminal 2
PDU
PDU subrack
-48 V RTN
INPUT (A)
terminal of DC
48 V RTN
PDU
connection
terminal 2
PWR-20908-
-48 V cable
Blue
003
PWR-20908-
-48 VRTN
004
cable
Black
PDU subrack
-48 V
INPUT 48
connection
V connection
terminal of DC
terminal 1
PDU
PDU subrack
-48 V RTN
INPUT 48
terminal of DC
V RTN
PDU
connection
terminal 3
PWR-20908-
-48 V cable
Blue
003
PWR-20908-
-48 VRTN
004
cable
Black
PDU subrack
-48 V
INPUT (A) 48
connection
V connection
terminal of DC
terminal 1
PDU
PDU subrack
-48 V RTN
INPUT (B)
terminal of DC
48 V RTN
PDU
connection
terminal 1
4-4
SJ-20121213161403-006|20131015 (R1.2)
Cable ID
PWR-20908-
Type
-48 V cable
Color
Blue
No.
9
003
PWR-20908-
-48 VRTN
004
cable
Black
10
End A
End B
PDU subrack
-48 V
INPUT (B) 48
connection
V connection
terminal of DC
terminal 2
PDU
PDU subrack
-48 V RTN
INPUT (B)
terminal of DC
48 V RTN
PDU
connection
terminal 2
PWR-20908-
-48 V cable
Blue
11
003
PWR-20908-
-48 VRTN
004
cable
Black
12
PDU subrack
-48 V
INPUT (B) 48
connection
V connection
terminal of DC
terminal 3
PDU
PDU subrack
-48 V RTN
INPUT (B)
terminal of DC
48 V RTN
PDU
connection
terminal 3
Caution!
Pay attention to the following things before installation:
l
l
l
l
The joint grounding mode is adopted. For information about joint grounding mode,
read the section Environmental Requirements > Grounding Requirements of the
Equipment Room > Three Types of Grounding System and Joint Grounding.
Ground cables must be laid separately. Be sure not to form a closed circuit via the
building concrete bar or via the rack.
Ground cables in the equipment room should be installed in a radiating or flat manner.
Ensure that the grounding resistance as stated in Installation Environment Check
is less than 1 . Grounding resistance measurements should be accurate. If the
grounding resistance fails to meet the requirement, it should affect the normal
operation of the system.
4-5
SJ-20121213161403-006|20131015 (R1.2)
Required Tools
l
l
l
l
l
Straight screwdriver
Cross screwdriver
Socket wrench
Diagonal pliers
Cable tie
Related information
DC PDU
-48 V power for cabinet is provided by DC PDU. Two -48 V power branches, after led out
by DC PUD, connect the input terminal of power distribution subrack via cabinet-top. DC
PDU does not belong to ZXUR 9000 UMTS components.
The following contents introduce the four grounding cable categories in the respects of
specifications, structure, installation location, cabling direction and cabling diagram.
H-PE-010
Type
PE protection
ground cable
Color
Yellow green
End A
End B
ing post
Installation location and cabling direction of the service subrack grounding cables
l The cables are installed at the back of the cabinet.
l The cabling applies the left routing.
l End A of the H-PE-010 grounding cable connects with the grounding terminal of the
service subrack. End B connects with the closest cabinet grounding terminal.
4-6
SJ-20121213161403-006|20131015 (R1.2)
Figure 4-4 shows the cabling diagram of the service subrack grounding cables.
Figure 4-4 Cabling Diagram of the Service Sub-rack Grounding Cables
1. Grounding cable
H-PE-007
Type
Color
End A
PE protection
Yellow
ground cable
green
End B
Grounding
inside
the
terminal
cabinet
Figure 4-5 shows the structure of a power distribution subrack grounding cable.
Figure 4-5 Structure of a Power Distribution Subrack Grounding Cable
Installation location and cabling direction of the power distribution subrack grounding
cables
l The cables are installed at the back of the cabinet.
l The cabling applies the right routing.
l End A of the H-PE-007 grounding cable connects with the grounding terminal of the
power distribution subrack. End B connects with the grounding terminal at the cabinet
top.
Figure 4-6 shows the cabling diagram of the power distribution subrack grounding cables.
4-7
SJ-20121213161403-006|20131015 (R1.2)
Figure 4-6 Cabling Diagram of the Power Distribution Sub-rack Grounding Cables
1. Grounding cable
Type
Color
End A
Grounding ter-
H-PE-010
PE
protection
ground cable
Yellow green
minal
inside
the cabinet at
End B
Grounding terminal
the
inside
cabinet
at lower part
bottom
Installation location and cabling direction of the cabinet door grounding cables
l The installation locations are at the bottom of the front/rear cabinet door.
l The cabling applies the right routing.
l End A of a cabinet door grounding cable connects with the grounding terminal of
the cabinet bottom. End B connects with the grounding terminal of the cabinet door
bottom.
Figure 4-8 shows the cabling diagram of the cabinet door grounding cables.
4-8
SJ-20121213161403-006|20131015 (R1.2)
1. Grounding cable
Model
PE protec-
PE-20970-006
tion ground
cable
Color
End A
End B
PE copper busbar of DC
green
PDU
Installation location and cabling direction of the cabinet door grounding cables
l The cables are installed at the back of the cabinet.
l There are two cabling methods: top routing and bottom routing.
Top routing
End A of a 35YGP/2 grounding cable connects with the grounding nut at the top
of the outer cabinet, and then extend to the cabling rack. End B connects with
the PE copper bar on the DC Power Cabinet.
Bottom routing
End A of a 35YGP/2 grounding cable connects with the grounding nut at the
bottom of the inner cabinet. The cable goes out of the cabinet bottom to the
anti-static floor. End B connects with the PE copper bar on the DC Power Cabinet.
4-9
SJ-20121213161403-006|20131015 (R1.2)
Figure 4-10 shows the cabling diagram of the exterior grounding cables (take top routing
as an example).
Figure 4-10 Cabling Diagram of the Exterior Grounding Cables
1. Grounding cable
4-10
SJ-20121213161403-006|20131015 (R1.2)
Caution!
Before installing clock cables, first ensure that the networking solution is determined and
appropriate clock transmission mode is selected.
Required Tools
l
l
Diagonal pliers
Cable tie
Note:
Whether the reference clock source of the system is from upper level office or BITS
is determined by the actual networking situation at site. The two modes can be used
independently or cooperatively.
The following contents introduce the three clock cable categories in the respects of
specifications, structure, installation location, cabling direction and cabling diagram.
SE1
Type
End A
Clock reference
cable
End B
The line reference clock cable is an E1 cable in appearance, as shown in Figure 4-11.
Figure 4-11 Structure of the Line Reference Clock Cable
1. Heat-shrinkable tube
Figure 4-12 shows the routing diagram of line reference clock cable. The figure uses active
and standby EGPB boards for example.
4-12
SJ-20121213161403-006|20131015 (R1.2)
Type
End A
End B
Clock reference
cable
DDF
The BITS reference clock cable is an E1 line in appearance, as shown in Figure 4-11.
Figure 4-13 Structure of the BITS Reference Clock Cable
1. Heat-shrinkable tube
SJ-20121213161403-006|20131015 (R1.2)
There are two cabling methods: top routing and bottom routing.
Top routing
Lay all clock cables on the cabling rack vertically from the cabinet top.
Bottom routing
All the clock cables go through the left and right cable troughs and out of the
cabinet bottom to the anti-static floor.
For one SE1 clock cable, connect end A to the REF1 or REF2" reference clock input
port on active EGFS board of master shelf, and connect end B to DDF, which is then
connected to BITS system clock output port. For the other SE1 cable, connect the
two ends to the clock ports of the standby board.
Note:
Based on the networking at site, determine whether to connect end B to REF1 or
REF2.
Figure 4-14 shows the cabling diagram of the BITS reference clock cables (take top routing
for example).
Figure 4-14 Cabling Diagrams of the BITS Reference Clock Cables
Type
End A
Side B1
CLK1, CLK2,
or CLK3 port
DS-G0505-001
Clock cable
on
EGFS
PTP1 or PTP2
port on slave
shelf of active
EGFS board
Side B2
PTP1
or
PTP2 port on
standby EGFS
board of slave
shelf
The inter-shelf clock cable is split into two at one end, as shown in Figure 4-15.
Figure 4-15 Structure of the Inter-Shelf Clock Cable
3. Labels
Figure 4-16 shows the cabling diagram of the inter-shelf clock cables.
4-15
SJ-20121213161403-006|20131015 (R1.2)
4-16
SJ-20121213161403-006|20131015 (R1.2)
Caution!
Before installing service cables, first ensure that the networking solution is determined and
appropriated data transmission mode is selected.
Required Tools
l
l
Diagonal pliers
Cable tie
The following contents introduce the five service cable categories in the respects of
specifications, structure, installation location, cabling direction and cabling diagram.
Direction A
Direction B
Function
Master
shelf
EGFS
board
port
RX1TX1
and
RX2TX2
port
port
The media plane interconnection fiber is a single-mode fiber in appearance. Ends A and
B are LC/PC plug.
Installation location and cabling direction of media plane interconnection fiber
l
l
SJ-20121213161403-006|20131015 (R1.2)
1. For the first fiber, connect end A to RX1TX1 interfaces on active media plane
switching board EGFS of master shelf, and connect end B to RX1TX1 interface
on active EGFS of slave shelf 1.
2. For the second fiber, connect end A to the RX2TX2 interfaces on active EGFS
of master shelf, and connect end B to RX1TX1 interface on active EGFS of
slave shelf 2.
3. Use the same method to connect the third and fourth fibers.
Figure 4-17 describes the cabling diagram of the media-plane interconnection fibers.
4-18
SJ-20121213161403-006|20131015 (R1.2)
4-19
SJ-20121213161403-006|20131015 (R1.2)
network
Direction A
Direction B
Function
data
ETH1 ~ ETH4
interfaces
on
EGBS of master
shelf
The control plane interconnection Ethernet cables use super category-5 shielded network
cable. Ends A and B are RJ45 connectors.
The installation location and routing direction for control plane interconnection network
cables are as follows:
l
l
Figure 4-18 describes the cabling diagram of the control plane interconnection Ethernet
cables.
4-20
SJ-20121213161403-006|20131015 (R1.2)
Figure 4-18 Cabling Diagram of the Control Plane Interconnection Ethernet Cables
4-21
SJ-20121213161403-006|20131015 (R1.2)
Interface Fibers
Table 4-12 describes the specifications of interface fibers.
Table 4-12 Specifications of Interface Fibers
Type
Direction A
Direction B
Function
TX1RX1~TX4RX4
Single mode fiber
Iu-CS/PS interface:
inter-
face of EGPB-
connects CN
Optical switch
/ESDTI/ESDTA
Node B
board
Note:
In actual situation, whether to use the interface board EGPB/ESDTI/ESDTA must be
determined according to the networking plan at site. The cabling diagram uses ESDTI
as an example.
4-22
SJ-20121213161403-006|20131015 (R1.2)
network
Direction A
Direction B
Function
Iu-CS/PS interface:
connects CN
External switch
board
Node B
The interface network cables use super category-5 shielded network cable. End A is RJ45
connector.
Installation location and cabling direction of the interface network cables
l
l
4-23
SJ-20121213161403-006|20131015 (R1.2)
4-24
SJ-20121213161403-006|20131015 (R1.2)
E1-G0505-003
T1-G0505-001
Type
75 ohms E1 cable
Direction A
"E1/T1 18", "E1/T1
916",
1724",
cable
2532" of EDTA or
or "E1/T1
Function
Iu-CS/PS interface:
"E1/T1
120 ohms E1
100 T1 cable
Direction B
DDF
connects CN
Iub interface:
connects Node B
EDTI
Figure 4-21, Figure 4-22, and Figure 4-23 show the appearances of interface E1/T1 cables.
Figure 4-21 Outline Structure of 75 E1 Cable
3. Label
3. Label
4-25
SJ-20121213161403-006|20131015 (R1.2)
3. Label
4-26
SJ-20121213161403-006|20131015 (R1.2)
Diagonal pliers
Cable tie
The following contents introduce the three cable categories in the respects of
specifications, structure, installation location, cabling direction and cabling diagram.
network
Direction A
Master
shelf
EGBS
board
ETH-MP1 port or
Direction B
Function
External switch
ETH-MP2 port
Appearance of OMC network cable: Ends A and B are 8P8C straight cable crimping
shielded connectors, as shown in Figure 4-25.
Figure 4-25 Structure of an OMC Cable
PD485 Cable
Table 4-16 describes the specifications of the PD485 cable.
Table 4-16 Specifications of PD485 Cable
Cable ID
Type
Direction
Direction of
Direction of
End B1
End B2
Function
It
RS485
DS-G0505002
enables
the
communication
RS485
(IN) inter-
RS485
monitoring
face
on master shelf
on master shelf
cable
PDU sub-
EGBS board
EGBS board
on
rack
interface
RS485
interface
between
tion
opera-
and
tenance
mainboard
Appearance of PD485 cable: Ends A and B are 8P8C straight cable crimping shielded
connectors, as shown in Figure 4-27.
4-28
SJ-20121213161403-006|20131015 (R1.2)
When laying 10-core or 12-core cables, bind them into a bundle with ties or wax string.
When fixing the cables to the cable trough, the distance between cable ties cannot
exceed 1 m. The cable between ties cannot be fully extended.
The cables connected to the farther wiring terminals should be laid at the outside and
the cables connected to the nearer wiring terminals should be laid at the inside. f the
equipment room applies top routing, first lay the very bottom of the cables. If the room
applies bottom routing, the sequence should be from top to bottom.
Cables may be distributed in an overlapped mode, but the overlap height should not be
too great, so as to ensure the normal circulation of the cold air and the heat dissipation
of the cabinet.
The laying positions should be arranged considering the largest cable configuration
at the cable troughs and at the cabinet outlet. The cable routing should provide
convenience for maintenance and future expansion.
The reserved cables in the back of DDF, ODF boards should be uniformly arranged
with a proper length to allow the boards for free flipping.
After binding, trim the remaining parts of the cable straps from the root. Dont leave
sharp cuts, as shown in Figure 4-30. In the figure, the tick mark indicates correct
binding and the cross mark indicates wrong binding.
4-31
SJ-20121213161403-006|20131015 (R1.2)
In a finished cable bundle, the space between two cable ties should be 3 to 4 times
the cable bundle diameter, as shown in Figure 4-31.
Figure 4-31 Cable Ties of a Cable Bundle
At the turn of a cable bundle, bind the cable ties at positions shown in Figure 4-32 to
avoid breaking the cable cores at the turn because of big stress. In the figure, the tick
mark indicates correct bundling and the cross mark indicates wrong bundling.
Figure 4-32 Cable Ties of A Cable Bundle at Turning
l
l
Do not mix black cables with white cables. The black cables are for outdoor installation
and the white cables are for indoor installation.
The cables into cabinets should be tired at every wiring rack vertical to the backplane.
Note:
The internal cables have been installed before delivery. Therefore, this part of contents
can be used as reference for equipment check and maintenance.
4-32
SJ-20121213161403-006|20131015 (R1.2)
4-33
SJ-20121213161403-006|20131015 (R1.2)
Warning!
Don't directly look at fiber section or optical interface on installation and maintenance.
Serious eye injury may occur if laser bundle accesses into your eyeball.
Cabling racks are required for cabling outdoor cables. All the cables should be bound
with the cabling racks securely.
When the power cables and signal cables are routed parallel, they must not be bound
together. Enough space is necessary.
Water-proof and anti-sunburn measures are required.
The cable through-holes should be sealed.
4-34
SJ-20121213161403-006|20131015 (R1.2)
Chapter 5
Installation Check
Table of Contents
Installation Check Flow...............................................................................................5-1
Installation Check Contents and Standards ................................................................5-1
5-1
SJ-20121213161403-006|20131015 (R1.2)
Check Rack
Check Shelf
Check Board
Check Cable
5-2
SJ-20121213161403-006|20131015 (R1.2)
Chapter 6
The power switch for the ZXUR 9000 UMTS power distribution subrack is turned off
on the DC PDU.
All power supplies of the power distribution subrack are switched off.
Context
This procedure is applicable for initial power-on.
Steps
1. Unplug all boards out of their slots.
Tip:
For the information about how to unplug boards, refer to section 5.2.2 Unplugging
Board.
2. Use a multimeter to measure and verify that the power output from the DC PDU to
ZXUR 9000 UMTS power distribution subrack is within the range -57 V DC to -40 V.
3. On the DC PDU, turn on the power switch for the power distribution subrack . Use a
multimeter to measure and verify that power input at the power distribution subrack is
within the range -57 V DC to -40 V DC.
4. Turn on the PWR air switch on the power distribution subrack. Ensure that the PWR
IN indicator is lit.
5. Insert the EGBS board into slots 19 and 20 of the primary service subrack.
6-1
SJ-20121213161403-006|20131015 (R1.2)
6. On the power distribution subrack, turn on the two air switches for the primary service
subrack. Observer the LED indicators on the EGBS board. Ensure that the ECMM is
in normal status, specifically:
l Active board
The CCM ACT indicator is ON in green.
l
Standby board
The CMM ACT indicator is OFF; the CMM H/S indicator is OFF; the CMM HOST
indicator flashes at 1 Hz in green.
7. Verify that the two front fan units and one rear fan unit of the primary service subrack
operate properly. Normally, the RUN indicator flashes at 1 Hz in green, and the H/S
and ALM indicators are OFF. If any exception is found, immediately shut off the power
supply, remove the faults, and then repeat the power-on steps.
Note:
If the EGBS board is not inserted or the ECMM module is in abnormal status, the fan
will operate at full speed after operating at a low speed for two minutes, causing a
large noise.
ii.
Choose precise ventilation to increase the cooling air volume for the area.
iii. Ensure that the ventilation route is not obstructed by cable, cabling tray, or other
articles.
End of Steps
6-2
SJ-20121213161403-006|20131015 (R1.2)
Warning!
The system stops working and terminate all the business providing after power-off. Do
operate with care.
Steps
1. Turn off the -48 V power switch corresponding to the service subrack on the panel of
the power distribution subrack.
2. Turn off the -48 V power supply output to the cabinet on the DC power distribution
cabinet.
End of Steps
6-3
SJ-20121213161403-006|20131015 (R1.2)
6-4
SJ-20121213161403-006|20131015 (R1.2)
Chapter 7
Board Installation
Table of Contents
Preparations for Board Installation..............................................................................7-1
Board Installation Methods .........................................................................................7-2
7-1
SJ-20121213161403-006|20131015 (R1.2)
l
l
7.
8.
9.
10.
11.
12.
13.
14.
Note:
The lower part of the shelf front and the shelf rear each has a ESD interface, which
functions as the grounding jack of the antistatic wrist strip.
If the cabinet is not connected to the protective ground, connect the binding post
PGND at cabinet top to the indoor grounding busbar.
Make sure that the power supply switch of all equipments are turned off.
Pull out all external cables (including the power cable).
Make sure that all shelves are clean.
Make sure that the pins at backplane are not bent, short, or broken. If the pins are
backplane are bent, replace them immediately. In case of emergency, use the sharp
nose plier to rectify the bent pin to be straight. If the pins at backplane are short or
broken, replace the backplane.
Check the jacks on the backplane and boards to see whether they are distorted. If a
jack is slightly distorted, use the sharp nose plier to rectify it to the normal shape. If a
jack is greatly distorted, replace the backplane or board.
Check components on the board to make sure that they are welded appropriately.
Check the front panels of boards, make sure that all indicators are firm, buttons and
switches are reliable and flexible, and interfaces are firm and reliable.
Prepare a flathead screwdriver or cross screwdriver with a diameter of 6 mm (#2) to
fasten the captive screws on the board extractor.
Note:
If the type of screwdriver is not clear, it is recommended to try the screwdrivers from
large-diameter to small-diameter until the most appropriate type is found.
7-2
SJ-20121213161403-006|20131015 (R1.2)
Steps
1. Take out the board from the antistatic packing box according to the ESD protection
regulations.
l
l
Note:
When taking a board, hold the board's panel, do not touch the board's components
and Printed Circuit Board (PCB).
Avoid any contact between the board and the clothes. The antistatic wrist strap
can only prevent damages caused by the static electricity on human body. To
avoid damage by the static electricity on the clothes, wear the antistatic clothes.
2. Hold the board's panel with the left hand and hold the board's spanner with the right
hand. Move the sliding block on the spanner in the direction of the arrow, and turn the
spanner outwards to open the spanner completely, as shown in Figure 7-2.
Figure 7-2 Opening Spanner
1. Panel
2. Sliding block
3. Spanner
4. Captive screw
3. Push the board smoothly into the shelf along the slot's guide rail, until the board panel's
positioning pin contacts the positioning hole in the shelf, as shown in Figure 7-3.
7-3
SJ-20121213161403-006|20131015 (R1.2)
4. Push the board panel until it clings the shelf's panel. Press down the upper spanner
and the lower spanner of the board towards the panel to make the board be inserted
into the shelf completely, as shown in Figure 7-4.
Figure 7-4 Plugging Board
7-4
SJ-20121213161403-006|20131015 (R1.2)
5. Make sure that the spanners buckle on the shelf. Use the screwdriver to clockwise
fasten captive screws on the panel to fix the board. The positions of captive screws
are shown in the figure above.
Note:
During the board installation, if the board cannot be pushed into the shelf with the
board's spanner, pull out the board and check the following items:
l Make sure that the position the board is installed is consistent with the required
position.
l Make sure that the board does not deviate from the guide rail.
l Make sure that the pins of connectors at backplane are not bent or damaged.
Result
l
l
Figure 7-5 illustrates the front board and the rear board being inserted into the shelf.
Figure 7-5 Front Board and Rear Board Plugged in Shelf
7-5
SJ-20121213161403-006|20131015 (R1.2)
Steps
1. Use flathead screwdriver or cross screwdriver to loosen the captive screws on the
upper/lower board extractor.
2. Move the sliding block on the upper/lower spanner in the direction of the arrow, and
turn the two spanners outwards to pull out the board, as shown in Figure 7-6 and
Figure 7-7.
Figure 7-6 Moving Sliding Block
7-6
SJ-20121213161403-006|20131015 (R1.2)
Caution!
i.
ii.
End of Steps
7-7
SJ-20121213161403-006|20131015 (R1.2)
7-8
SJ-20121213161403-006|20131015 (R1.2)
Chapter 8
8-1
SJ-20121213161403-006|20131015 (R1.2)
Name
Quantity
050531800083
Anti-interference, enhanced
052523000013
044070200031
splitter
052621000396
056469000266
056469000248
cable
042010500029
male adapter
056471200154
056471200157
056471200159
mm 6.5 mm)
056472000030
056472000031
056472000046
1. Use the 042010500024 Type-N male connector for the 1/2 feeder cable. Use the
042010500001 Type-N male connector for the 1/4 feeder cable.
2. The feeder cable grounding clip is optional. Use it when necessary.
3. It is recommended to use the 1/2 feeder cable combination: Type-N male connector
(code: 042010500024) + 1/2 cable, + 1/2" feeder cable grounding clip.
050531800083LJ
8-2
SJ-20121213161403-006|20131015 (R1.2)
Model
MBGPS-38-001
Work frequency
Gain
38 dBi 2 dBi
2.5
Polarization direction
110 10
Axial ratio
5 dB
Front-to-back ratio
10 dB
0 dBm
12 dB
MHz)
Out-of-band attenuation (f0 = 1575.42 MHz 50
35 dB
MHz)
Out-of-band attenuation (f0 = 1575.42 MHz 100
70 dB
MHz)
Strengthened signal congestion
Output impedance
50
4 V 5.5 V
45 mA
Noise coefficient
2.7 dB
3:1
8-3
SJ-20121213161403-006|20131015 (R1.2)
N male connector
Material code
042010500024ZY
Model
53S114-C03N1//N-JA(1/2)RC//NM-1/2"L
Impedance
50
1.1
Insertion loss
0.2
Material code
052523000018TY
Model
HCAAY-50-12//HCAATY-5012//RF1/2"-50//RF5012(1/2")
Impedance
50
4.8 mm
internal conductor
Maximum outer diameter of the
16.4 mm
sheath
Attenuation
Other materials
1.2
056469000248
056469000241
The attenuation of the 1/2 feeder cable in the GPS frequency band is estimated as 10 dB per 100 meters.
Material code
042010500001ZY
Model
N-JA(1/4)//NM-1/4L
Impedance
50
Rated voltage
1,000 V
Frequency range
0 3 GHz
Withstanding voltage
1,500 V
1.30 3 GHz
(VSWR)
N male connector b)
Material code
042010500082ZY
Model
NMW-14"L//N-JWA(1/4)-RC
Impedance
50
1.2
Insertion loss
0.2
8-4
SJ-20121213161403-006|20131015 (R1.2)
Material code
052523000013TY
Model
HCAAY-50-6(1/4")//RFF
1/4"-50//LDF1-50//RF5014(1/4")
2.6 mm
internal conductor
Nominal outer diameter of the
6 mm
insulating layer
Impedance
50
Attenuation
Other requirements
600 m/reel
The attenuation of the 1/4 feeder cable in the GPS frequency band is estimated as 20 dB per 100 meters.
044070200031ZY
Model
CSP-III-006
Frequency band
Interface type
Impedance
50
50 W
1.2
Insertion loss
4.0
10 kA
052621000396ZY
Model
RF-06221-018
SMA-JW
Cable type
SM86
SMA-JW
Length
1.95 m
SJ-20121213161403-006|20131015 (R1.2)
l
l
l
l
Ensure that no obstacles exist above the 15-degree elevation angle (horizon plane at
the top of the antenna).
The GPS antenna is in the frequency band of 1575.42 5 MHz.
Ensure that no high-power microwave transmitter with the same frequency band exist
in the surroundings of the GPS antenna.
Avoid direct high-power radiation of other frequency bands.
If the GPS cable length is less than 70 m, select 1/4 or 1/2 feeder cables and the
corresponding connectors.
If the GPS cable length is between 70 m and 140 m, select 1/2 feeder cables and the
corresponding connectors.
When installing the feeder cables, ensure that the minimum bending radius of the feeder
cables meets the following requirements:
l
Single bend: 40 mm
Single bend: 80 mm
The GPS feeder cable should be connected to outdoor grounding bar using a grounding
clip at a point within 1 meter in front of the feeder window.
Note:
The shield corrugated copper tube on the feeder cable is thin, so avoid trampling on the
feeder cable.
8-6
SJ-20121213161403-006|20131015 (R1.2)
1. Type-N connector
2. Lightning arrester
8-7
SJ-20121213161403-006|20131015 (R1.2)
l
l
6. 1/2 RF cable
Note:
The length of a thin cable is limited by its large power loss, so the thin cable is used
only inside the rack for connecting the clock board. Use the 1/2 low-loss cable for
other places in the equipment room.
The 1:8 splitter can be used for 8 ZXUR 9000 UMTS. The 1:4 splitter can be used for
4 ZXUR 9000 UMTS.
On the power splitter, the first output is DC-coupled with the input. The first output
provides power supply for the GPS antenna, while the second output provides standby
power supply for the GPS antenna.
When the first output cannot provide power supply, the diode of the second output
is turned on to provide power supply to the GPS antenna. When the power splitter
is used for output, either OUT1 or OUT2 should be used. If the output port is not
connected to the cable, a 50 ohm matched load must be connected.
Name
Description
Quantity
042010500024
1/2" N connector
12
044070200008
Loss 10 dB/100 m
Determined by project
lightning arrester
056803000010
056803000011
052523000018
1/2" Foamed
polyethylene dielectric,
survey
corrugated copper-tube
outer conductor, 50
ohm radio frequency
coaxial cable
044070200043
N(K)->SMA(K) adapter
8-8
SJ-20121213161403-006|20131015 (R1.2)
Material code
Name
Description
Quantity
052621000396
Semi-flexible coaxial
Ultra-wideband
attenuation,
dB
cable, SMA-JW//RG405//SMA-JW
050531800083
anti-interference,
enhanced lightning
protection GPS
antenna
056469000230
Determined by project
survey
per meter
056469000248
Determined by project
survey
per 15 meters
056472000031
Electrical insulating
tape (black)
075251000002
Electrical insulating
tape (black)
075251000003
Waterproof insulating
Cable tie
(2004.5//2004.5)
056471200159
Black ultraviolet-proof
tie (2506.5
(H)//2506.5 (H))
042010500024
Model
53S1C7-C03N1//N-JA(1/2)-1//NM-1/2L
Rated voltage
1,000 V
Grounding resistance
1 M
Insulation resistance
5000 M
Impedance
50
8-9
SJ-20121213161403-006|20131015 (R1.2)
Withstanding voltage
1,500 V
Insertion loss
0.2 dB
044070200008
Model
CSPW-L-N-F(F)
Frequency range
10 kA
Interface
N-F(F)
Impedance
50
1.2
Insertion loss
0.2 dB
Residual voltage
20 V
Waterproof level
IP65
Insertion loss
Isolation level
25 dB
1.5
Inband smoothness
0.4 dB
Amplitude balance
0.5 dB
Output impedance
50
Interfaces
052523000018
Model
HCAAY-50-12//HCAAY-50-12(1/2")//HPL
50-1/2F//RF1/2"-50//RF5012(1/2")
4.8 mm
diameter
Foamed polyethylene insulation, nominal outer
12 mm
diameter
8-10
SJ-20121213161403-006|20131015 (R1.2)
13.9 mm
Impedance
50
Attenuation
1.2
044070200043
Model
107-0802RM-A//LA-FT2500 Z5N2-SA
Frequency range
20 kA
Interface
N-SMA
Impedance
50
1.2
Insertion loss
0.4 dB
Residual voltage
7.2 V
Waterproof level
IP67
050531800083
Model
MBGPS-38-001//TG-15AE-38-02//TSA1575AT4C&Q01-S5-02
Frequency
Gain
38 2 dBi
2.5
Polarization direction
110 10
Axial ratio
5 dB
Front-to-back ratio
10 dB
0 dBm
12 dB
MHz)
8-11
SJ-20121213161403-006|20131015 (R1.2)
35 dB
MHz)
Out-of-band attenuation (f0 = 1575.42 MHz 100
70 dB
MHz)
Strengthened signal congestion
Output impedance
50
4 5.5 V
45 mA
Noise coefficient
2.7 dB
3:1
If the GPS cable length is less than 40 m, select 1/4 or 1/2 feeder cables and the
corresponding connectors.
If the GPS cable length is between 40 m and 90 m, select 1/2 feeder cables and the
corresponding connectors.
During the installation process, ensure that the minimum bending radius of the feeder cable
meets the following requirements:
l
SJ-20121213161403-006|20131015 (R1.2)
Single bend: 40 mm
Single bend: 80 mm
The GPS feeder is grounded at a point: Use a grounding clip to connect the GPS feeder
cable to the outdoor grounding bar at a point within 1 meter in front of the feeder window.
Bend the feeder cable in the U shape at the place it enters the room to prevent water
ingress.
Note:
The shield corrugated copper tube on the feeder cable is thin, so avoid trampling on the
feeder cable.
Through-wall installation
Lug installation
l
l
Note:
Select an installation method in accordance with the on-site conditions.
The grounding area must be greater than 6 mm2 for either installation method.
Through-wall installation
Figure 8-3 shows the through-wall installation. The wall thickness should be less than
the connectors length. In most cases, the wall is replaced by a steel plate, which
must be grounded and fixed on the cabling rack or any fixed position.
The installation procedure: Drill a proper hole on the steel plate, put the connector
through the hole, and fasten the screw.
8-13
SJ-20121213161403-006|20131015 (R1.2)
Lug installation
Figure 8-4 shows the lug installation. The lightning protector is fixed on the cabling
rack or any fixed position. The copper lug of the outgoing cable is connected to the
grounding bar in the equipment room.
8-14
SJ-20121213161403-006|20131015 (R1.2)
8-15
SJ-20121213161403-006|20131015 (R1.2)
8.3 Precautions
8.3.1 Signal Reception Environment
The larger sky to which the GPS antenna is exposed, the more satellites signals are
available to the receiver, and the more accurate the time can be provided by the GPS
antenna.
The GPS signal has the following characteristics:
l
l
l
All metal entities can entirely cover the GPS signal. The car films containing metal
coating can also shield some GPS signals.
After passing through liquid entities thicker than 1 cm, the GPS signal attenuates to
being unavailable.
Glass and plastics only weakens the GPS signal slightly, but thick nonmetallic objects
can entirely cover the signal, such as a chunk of wood and a thick book of several
centimeters.
1475.42 MHz microwave signals has a wavelength of 19 cm, and can pass through
metal nets with hole diameters greater than 19 cm or metal truss structures such as
power transmission tower.
Therefore, the antenna must be installed in high places with few obstacles, such as the
roof. Following are some issues related to installing the GPS antenna.
l
l
l
l
l
Ensure that no obstacles exist above the 30-degree elevation angle, so that the GPS
antenna can receive signals from the most possible satellites.
Avoid installing the GPS antenna inside a building, because the indoor GPS signals
are too weak.
For tower-mounted installation, the antenna pole should have a horizontal distance of
30 cm off the tower to prevent signals from being shielded by the tower.
Trees or plastic awnings above the antenna normally has little influence on signal
reception.
Ensure that no vines grow up intertwined on the antenna.
8.3.2 Interference
To avoid co-frequency blocking on the receiver caused by electromagnetic interference,
the following issues should be considered:
l
l
l
l
Ensure that no high-power microwave transmitter with the same frequency band exist
in the surroundings of the GPS antenna.
Avoid direct high-power radiation of other frequency bands.
Avoid installing the GPS antenna under microwave transmission antennas,
high-voltage cables, and TV transmission towers.
Ensure that the GPS antenna is not radiated by the main lobe of a mobile antenna.
8-16
SJ-20121213161403-006|20131015 (R1.2)
The feeder cable on the tower is not grounded directly, but connected to the grounding
bar. On the prerequisite that the 30-degree elevation and the theft-proof height is
guaranteed, the antenna should be installed as low as possible to reduce lightning
induction. The GPS antenna feeder needs DC power supply, so the lightning
discharging of the tower increases the ground level of the GPS antenna, and the
grounding status of the tower cannot be guaranteed.
The feeder cable should be grounded at the following places:
l The place where the tower touches the ground.
l A place near the feeder window.
l Every point at a 20-meter interval between the above two grounding points.
2. Roof Installation: Figure 8-6 shows the roof installation.
8-17
SJ-20121213161403-006|20131015 (R1.2)
l
l
l
l
The GPS antenna and feeder cables should be installed within the 45-degree
cone protected by lightning receptors. If the GPS antenna is out of the protection
area, a special lightning rod should be installed on the antenna.
The GPS pole or feeder cable should be at least 0.5 meter off the lightning rod
pole horizontally.
The outdoor feeder cables should be as short as possible (no greater than 20
meters) to reduce changes of lightning induction. If the cable is longer than 20
meters, route the cable through the steel tube and ground both ends of the tube.
GPS feeder cable should be routed from the low-voltage well in the middle of the
building to the outside. Avoid routing the GPS feeder cable along the outer wall.
The GPS feeder cable must be routed under the lightning receptor, with a distance
of at least 0.2 meter.
8-18
SJ-20121213161403-006|20131015 (R1.2)
Chapter 9
Attached Equipment
Installation
Table of Contents
Alarm System.............................................................................................................9-1
Environment Monitoring System .................................................................................9-9
Composition
The alarm system consists of alarm server (usually the OMC server) and alarm box, as
shown in Figure 9-1.
Figure 9-1 Alarm System
The alarm server allows the administrators to set such parameters as the levels of
alarms to be sent to the alarm box, the mobile phone numbers to send alarm SMS
messages.
The alarm server sends alarm messages to alarm box through TCP/IP protocol, and
the mobile phone module in the alarm box delivers the alarm SMS messages to the
mobile phone number as specified.
9-1
SJ-20121213161403-006|20131015 (R1.2)
The alarm box displays the alarm messages on the LCD screen with the alarm
indicator and the alarm sound.
Functions
The alarm box provides the following functions:
l
l
l
l
l
l
SMS sending: Through proper settings on the alarm server, the built-in mobile phone
module in the alarm box sends current alarms to the mobile phones of the specified
staff. Alarms can be set according to preset severity levels. Alarm box supports CDMA
or GSM system, but not both.
Audio alarm: The built-in speaker of the alarm box reports alarms with beeps and the
current alarm severity with real voices.
Alarm Indicator: Alarms of different severity levels are indicated by LEDs of different
colors (yellow, orange, blue and red in the ascending order of alarm severity).
Alarm server indicator: The alarm box panel has 10 LED indicators that are connected
to 10 groups of alarm servers (usually 10 servers). The indicators report the status of
each group of alarm servers, such as link status, and alarm status.
LCD display of alarm information: The alarms from alarm server are displayed on the
LCD screen of the alarm box. Users may press the alarm menu and panel buttons to
set the alarm box parameters, such as the IP address, the UDP port number, button
sound switch control, and back-light control.
Remote function: The alarm box can connect to a server in the same network
segment, or a remote server in a different network segment. In the latter case, you
need to add a route on the alarm box. Therefore, the alarm box need not be placed
in the computer room. It can be placed in the office or the meeting room, which
increases its flexibility.
Multiple office integration: The alarm box supports up to 128 alarm servers, which
can be classified into 10 groups. Usually, these servers are not in the same network
segment, so this function needs support from the remote connection function.
Supports cross-VLAN alarm servers: The alarm box may be connected to the alarm
servers in different VLANs through the layer-2 switch. This cross-VLAN connectivity
eliminates the need for a high-cost layer-3 switch, while ensuring the separation of
alarm servers from each other.
Network storm detection and alarm: Proper setting of the network storm threshold on
the alarm box helps you to avoid network congestion caused by data broadcast.
Alarm group confirmation: The alarm box confirms alarms on the per-group basis.
9-2
SJ-20121213161403-006|20131015 (R1.2)
l
l
l
Alarm statistics information query: The statistic data of various alarms connected with
alarm servers can be queried through LCD.
Permanent muting: User may mute the alarms according to their severity levels on
the alarm box.
Remote operation: Users may log in to the alarm box with Telnet, and complete alarm
server configuration, router configuration, VLAN configuration, SMS parameter configuration and time parameter configuration with MML commands.
Technical Parameters
l
l
l
l
l
Context
The alarm box is installed in the control room or office to provide the maintenance
personnel with alarm information of different levels. The alarm box should be installed
in a conspicuous place, so that the on-duty personnel can see the alarm indicators and
here the alarm sound. It is mounted on the wall about 1.5 m above the floor to facilitate
operations on it.
Steps
1. Use the mounting panel to mark the positions of the installation holes, or draw the lines
according to the dimension provided in Figure 9-2. The alarm box bottom is around
1,500 mm above the ground. The lines should be parallel to the ground or the wall.
9-3
SJ-20121213161403-006|20131015 (R1.2)
1. 8 hole
2. Plastic expansion pipe
3. Mounting panel
4. M5 wooden sunk
screw
9-4
SJ-20121213161403-006|20131015 (R1.2)
1. Hanging hole
6. Lock the alarm box so that it cannot be taken off from the mounting panel.
End of Steps
SJ-20121213161403-006|20131015 (R1.2)
Context
If the equipment room has DC power, use the 3-meter long DC power cable attached in the
package, or make the power cable as needed. The specifications of a self-made power
cable cannot be lower-leveled than the attached cables, as shown in Table 9-1.
Table 9-1 Specifications of Power Cable
Specification
Standard sectional
area
External diameter
Insulation layer
thickness
Insulation outer
diameter
The maximum DC
resistance in 20
Parameter Value
1 mm2
Specification
Jacket thickness
External diameter of
1.3 mm
tube (mm)
0.65 mm
Rated voltage
Highest working
2.6 mm
temperature
20 /km
N/A
Parameter Value
0.87 mm
6.94 mm
300 V/500 V
70
N/A
The power cables and the network cables should have jackets before being fixed to the
wall. The cable layout should be good-looking. The cable should bend smoothly at the
bending position, and the tail should not be pulled tight to avoid damage of the cable.
Steps
1. Connect one end of the straight-through network cable (RJ-45 plug) into the port of
the alarm box, and connect the other end to port on the hub or the layer 2 switch in
the LAN.
2. Connect the DC power cable to the power port on the lower right part of the alarm
box. Connect the first power cable (usually black) to the -48 V RTN port, and connect
the other power cable (usually blue) to the -48 V port. Fasten the built-in screw of the
cable port. Each port that connects with a cable must be consistent with the other part
of the cable.
3. Install a PVC cable trough on the wall based on the cabling scheme and position of
the alarm box.
l If the cables go to the same destination (such as in a cabinet) at the other end,
install the PVC cable chute along the wall to the cable ladder, and then run the
cables from the cable ladder into the cabinet (cabling in cable racks); or, install
the PVC cable chute along the wall to the floor, and then run the cables through
the cable chute under the raised floor into the cabinet (cabling under the raised
floor, in which case the cable chute is optional).
l If the cables go to different destinations at the other end, separate them at an
appropriate location, put them respectively into narrower cable chutes, and run
9-6
SJ-20121213161403-006|20131015 (R1.2)
them to their respective destinations in the cable chutes along the wall or under
the raised floor.
4. Put the power cables and the network cables into the wider cable trough, and then
cover the trough.
End of Steps
Context
A power adapter is needed under the AC power supply. Make sure that there is a AC
power socket near the alarm box. The power adapter delivered with the equipment has
a two-meter-long DC power cable and a 2-meter-long AC power cable. When installing
the alarm box, take into consideration the placement of power adapter and the length of
power cable.
The power cables and the network cables should have jackets before being fixed to the
wall. The cable layout should be good-looking. The cable should bend smoothly at the
bending position, and the tail should not be pulled tight to avoid damage of the cable.
Steps
1. Connect one end of the straight-through network cable (RJ-45 plug) into the port of
the alarm box, and connect the other end to port on the hub or the layer 2 switch in
the LAN.
2. Connect the three-electrode plug to the AD power socket and connect the other end
to the power adapter. Make sure that the power supply at the socket is switched off.
The power adapter and power cables are shown in Figure 9-5 and Figure 9-6.
Figure 9-5 Power Adapter From Top View (Left) and Side View (Right)
9-7
SJ-20121213161403-006|20131015 (R1.2)
Note:
The actual power cable plug might be different with that shown in the figure because of
various standards in different countries. Based on actual situation, select power cable
or use connector board for adapting upon delivery.
3. Connect the power cable at DC side of the adapter to the power terminal at the right
lower part of the alarm box. Connect the power cable with GND label to the -48 V RTN
port, and connect the other cable to the -48 V port. Fasten the built-in screw of the
cable port.
4. Install a PVC cable trough on the wall based on the cabling scheme and position of
the alarm box.
l If the cables go to the same destination (such as in a cabinet) at the other end,
install the PVC cable chute along the wall to the cable ladder, and then run the
cables from the cable ladder into the cabinet (cabling in cable racks); or, install
the PVC cable chute along the wall to the floor, and then run the cables through
the cable chute under the raised floor into the cabinet (cabling under the raised
floor, in which case the cable chute is optional).
l If the cables go to different destinations at the other end, separate them at an
appropriate location, put them respectively into narrower cable chutes, and run
them to their respective destinations in the cable chutes along the wall or under
the raised floor.
5. Put the power cables and the network cables into the wider cable trough, and then
cover the trough.
Note:
If the power adapter is not easy to hide, find an appropriate position to place it.
End of Steps
9-8
SJ-20121213161403-006|20131015 (R1.2)
Principles
PDU performs alarm signal processing. The alarm indicator on the power distribution
subrack panel indicates alarm if the following problems occur: The -48 V power supply
has problems such as over-voltage, under-voltage, or power-down; The fan becomes
abnormal; Smoke signal, intrusion signal, or signal of temperature/humidity exceeding limit
is detected. At the same time, the signal is reported to EGBS (rear board of UMP) or server
through RS485 interface.
Cable Structure
For monitoring signal cable H-MON-025, the end of power subrack connects DB15
interface. There are four DB9 interfaces at the sensor end, which is used to connect
different sensors. Figure 9-7 shows the structure of H-MON-025 cable.
Figure 9-7 H-MON-025 Cable
Table 9-2 describes the relation between cable ports and sensors.
9-9
SJ-20121213161403-006|20131015 (R1.2)
Sensor
B1
Infrared Sensor
B2
Temperature/humidity sensor
B3
Fog sensor
B4
Reserved
Installation Instructions
The end A connects with the DB15 interface at "SENSOR" label on the back of the power
distribution sub-rack. The end B leads out cables from the cabinet top, and cables are
bound and fixed. If there is no configuration of sensor cable, the plastic protection sleeve
for the plugs on end B must not be lost.
9-10
SJ-20121213161403-006|20131015 (R1.2)
The smog sensor is mounted on the ceiling, right over the top of the cabinet.
Steps
1. Drill two holes (diameter 6 mm) on wall surface (the depth should be consistent with
the length of the plastic expansion tube, advisably not less than 30 mm), which are 97
mm away from each other and of the same height from the ground.
2. Insert plastic expansion tube into these two holes, and hammer them fully into the
holes with proper force.
3. Detach the base of fog sensor, thread two nutted M4 screws into preset holes of the
base, and rotate the screws into the plastic expansion tube on the wall.
4. Connect the DB9 male plug on the smog sensor to the end B3 on PDU external
monitoring cable H-MON-025 or the end B4 on H-MON-009.
End of Steps
9-11
SJ-20121213161403-006|20131015 (R1.2)
Steps
1. Drill two holes (diameter 6 mm) on wall surface (the depth should be consistent with
the length of the plastic expansion tube, advisably not less than 30 mm), which are 60
mm away from each other and of the same height from the ground.
2. Insert plastic expansion tube into these two holes, and hammer them fully into the
holes with proper force.
3. Force wooden screws M4 into the expansion tube but not to the end. The screw cap
should be kept 10 mm away from the wall surface.
4. Connect the DB9 male plug at end A of the temperature/humidity sensor to the end
B3 on PDU external monitoring cable H-MON-009 or the end B2 on H-MON-025. DB9
female plug on end B connects to the sensor. The appearance of a sensor cable is
shown in Figure 9-10.
9-12
SJ-20121213161403-006|20131015 (R1.2)
5. Align the two installation holes on the back of the temperature & humidity sensor with
the two screw cap, and insert the screws. Pull the temperature & humidity sensor
downward slightly to check if it has been engaged with the screws properly.
End of Steps
Note:
The infrared sensor mentioned below is just one of the multiple types available. The actual
structure of the infrared sensor on the site may be different, and you should follow the
instruction manual of device to install it.
9-13
SJ-20121213161403-006|20131015 (R1.2)
1. Cable outlet
2. Preset hole
3. Preset hole
4. Cable outlet
Steps
1. Drill two holes (diameter 6 mm) on wall surface (the depth should be consistent with
the length of the plastic expansion tube, advisably not less than 30 mm), which are
81.7 mm away from each other and of the same height from the ground.
2. Insert plastic expansion tube into these two holes, and hammer them fully into the
holes with proper force.
3. Detach the base of infrared sensor, thread nutted M4 screws into preset holes of the
base, and rotate the screws into the plastic expansion tube on the wall.
4. Engage the infrared sensor with the base. One end of the sensor is DB9 male plug, as
shown in Figure 9-13. D89 make plug connects to the end B2 of external monitoring
cable H-MON-009 on PDU or the end B1 of H-MON-025.
Note:
The infrared sensor has been cabled before delivery.
9-14
SJ-20121213161403-006|20131015 (R1.2)
End of Steps
Context
Figure 9-14 shows the structure of door access sensor cable in equipment room.
Figure 9-14 Structure of a Door Control Sensor Cable
The end A is connected to the "DOOR" mark at the back of the power distribution subrack.
The end B is connected to the sensor. Table 9-3 describes the function of the end B.
9-15
SJ-20121213161403-006|20131015 (R1.2)
Functions
B1
B2
B3
B4
B5
B6
Index
Distance
16 mm ~ 45 mm
Working current
Working voltage
100V DC
Lifecycle
Impedance
0.3
Withstanding voltage
250 DCV
Steps
1. Install a PVC cable trough on the wall based on the cabling scheme and position of
the alarm box.
2. Along the wall, lay the cable to the upward cabling tray or the downward cabling tray
under the anti-static floor. Lead the cable to PDU external monitoring cable on the top
of the cabinet through the cabling tray.
3. After the cabling, cover PVC cabling trough.
End of Steps
9-16
SJ-20121213161403-006|20131015 (R1.2)
Appendix A
Cables
Table of Contents
Internal Cables ....................................................................................................... A-1
External Cables ...................................................................................................... A-3
Meaning
PWR-20952-002
-48 V cable
Direction A
Direction B
box
(PDU)
Meaning
PWR-91237-102
Direction A
Direction B
box
(PDU)
A-1
SJ-20121213161403-006|20131015 (R1.2)
Type
Direction A
PE protection ground
cable
Service subrack
Direction B
PE binding post inside
the cabinet
Type
Direction A
Direction B
PE protection ground
Grounding point at
cable
point
Type
Direction A
Direction B
PE protection ground
PDU grounding
cable
terminal
Direction A
Direction B
Function
Media Plane
Subordinate shelf
Transmission media
Interconnection Fiber
board
EGFS board
plane data
Appendix A Cables
Direction A
Direction B
Function
Super category 5
Subordinate shelf
board
EGBS board
data
Name
Direction A
Direction B
SE1
board
board
Name
Direction A
Direction B
DS-G0505003
Clock Cable
Subordinate shelf
board
EGFS board
DS-G0505-002
Name
RS485 monitoring
Direction A
PDU subrack
cable
Direction of End
Direction of End
B1
B2
Master shelf
Master shelf
EGBS board
EGBS board
SJ-20121213161403-006|20131015 (R1.2)
l
l
l
l
l
l
l
l
Type
Direction A
PWR-20908-003
-48 V cable
Direction B
Customer -48 V RTN
(OUT)
Type
Direction A
PWR-20908-004
Direction B
Customer -48 VRTN
(OUT)
PE-20970-006
Type
Direction A
PE protection ground
cable
Protective ground
terminal at top of
exterior cabinet
Direction B
PE copper busbar of
DC PDU
A-4
SJ-20121213161403-006|20131015 (R1.2)
Appendix A Cables
Name
Direction A
Direction B
SE1
DDF
board
Direction A
Direction B
Function
Interface Fiber
Optical switch
Iu-CS/PS: connects CN
EGPB
BTS
ESDT1
Four pairs of TX-RX on
ESDTA
Direction A
Direction B
Function
Super category 5
ETH1~4 of EGPB
External switch
Iu-CS/PS interface:
connects CN
Iub interface: connects
BTS
A-5
SJ-20121213161403-006|20131015 (R1.2)
Type
Direction A
Direction B
Function
E1G0505001
75 E1 cable
E1/T1 interface of
DDF
Iu-CS/PS
E1G0505003
120 E1 cable
T1G0505001
100 T1 cable
E1G0505008
75 E1 cable
E1G0505010
120 E1 cable
T1G0505003
100 T1 cable
EDTI
interface:
connects CN
Iub interface:
E1/T1 interface of
connects BTS
EDTA
End A (DB44)
Signal
38
RX1
23
RX1+
37
RX2
22
RX2+
36
RX3
21
RX3+
35
RX4
20
RX4+
34
RX5
19
RX5+
33
RX6
18
RX6+
32
RX7
17
RX7+
31
RX8
16
RX8+
End A (DB44)
Signal
15
TX1
30
TX1+
14
TX2
29
TX2+
A-6
SJ-20121213161403-006|20131015 (R1.2)
Appendix A Cables
Cable 1
End A (DB44)
Signal
13
TX3
28
TX3+
12
TX4
27
TX4+
11
TX5
26
TX5+
10
TX6
25
TX6+
TX7
24
TX7+
TX8
TX8+
End A (DB44)
Signal
Blue (red1)
38
RX1
Blue (black1)
23
RX1+
Pink (Red1)
37
RX2
Pink (Black1)
22
RX2+
Green (red1)
36
RX3
Green (black1)
21
RX3+
Yellow red 1
35
RX4
Yellow black 1
20
RX4+
Gray (red1)
34
RX5
Gray (black1)
19
Blue (red2)
33
RX6
Blue (black2)
18
RX6+
Pink (Red2)
32
RX7
Pink (Black2)
17
RX7+
Green (red2)
31
RX8
RX5+
A-7
SJ-20121213161403-006|20131015 (R1.2)
Cable 1
End A (DB44)
Signal
Green (black2)
16
RX8+
Cable 2
End A (DB44)
Signal
Yellow red 2
15
TX1
Yellow black 2
30
TX1+
Gray (red2)
14
TX2
Gray (black2)
29
Blue (red3)
13
TX3
Blue (black3)
28
TX3+
Pink (Red3)
12
TX4
Pink (Black3)
27
TX4+
Green (red3)
11
TX5
Green (black3)
26
TX5+
Yellow red 3
10
TX6
Yellow black 3
25
TX6+
Gray (red3)
TX7
Gray (black3)
24
Blue (red4)
TX8
Blue (black4)
TX8+
TX2+
TX7+
End A (DB44)
Signal
White
38
RX1
Blue
23
RX1+
White
37
RX2
Orange
22
RX2+
White
36
RX3
Green
21
RX3+
White
35
RX4
Brown
20
RX4+
White
34
RX5
A-8
SJ-20121213161403-006|20131015 (R1.2)
Appendix A Cables
Cable 1
End A (DB44)
Signal
Grey
19
RX5+
Red
33
RX6
Blue
18
RX6+
Red
32
RX7
Orange
17
RX7+
Red
31
RX8
Green
16
RX8+
Cable 1
End A (DB44)
Signal
Red
15
TX1
Brown
30
TX1+
Red
14
TX2
Grey
29
TX2+
Black
13
TX3
Blue
28
TX3+
Black
12
TX4
Orange
27
TX4+
Black
11
TX5
Green
26
TX5+
Black
10
TX6
Brown
25
TX6+
Black
TX7
Grey
24
TX7+
Yellow
TX8
Blue
TX8+
Direction A
Direction B
Super category 5
External switch
board
Remarks
Connects OMC NMS
client
A-9
SJ-20121213161403-006|20131015 (R1.2)
Direction A
Direction B
Remarks
H-MON-024
socket DOOR
status
sensors
Direction A
Direction B
Remarks
H-MON-025
Dual path
B1: infrared
Monitors the
PDU-environment
B2" temperature/hu-
environment
monitoring DB15
midity
socket
B3: smog
(SENSOR)
B4: reserved
Direction A
Direction B
Remarks
H-M0N-012
H-MON-025: B1
Infrared microwave
Infrared monitoring
sensor
Direction A
Direction B
Remarks
H-M0N-013
H-MON-025: B3
Fog sensor
A-10
SJ-20121213161403-006|20131015 (R1.2)
Appendix A Cables
Direction A
Direction B
Remarks
H-MON-014
H-MON-025: B2
Temperature/Humidity
Sensor
A-11
SJ-20121213161403-006|20131015 (R1.2)
A-12
SJ-20121213161403-006|20131015 (R1.2)
Figures
Figure 1-1 Equipment Room Layout.......................................................................... 1-5
Figure 2-1 Unpacking Wooden Case ........................................................................ 2-2
Figure 3-1 Cabinet Installation Flow .......................................................................... 3-2
Figure 3-2 Adjusting Washer..................................................................................... 3-3
Figure 3-3 Type-A Adjustable Base........................................................................... 3-4
Figure 3-4 Type-B Adjustable Base........................................................................... 3-4
Figure 3-5 Type-C Adjustable Base........................................................................... 3-5
Figure 3-6 Adjustable Base Structure........................................................................ 3-5
Figure 3-7 Adjustable Base Installation Flow............................................................. 3-7
Figure 3-8 Adjustable Base Installation (Front View) ................................................. 3-8
Figure 3-9 Adjustable Base's Height Illustration ........................................................ 3-9
Figure 3-10 Installing Drilling Template ................................................................... 3-10
Figure 3-11 Installing Expansion Bolts .................................................................... 3-11
Figure 3-12 Connecting Base and Ground .............................................................. 3-12
Figure 3-13 Fixing Cabinet and Adjustable Base..................................................... 3-13
Figure 3-14 Cabinet and Adjustable Base Being Fixed............................................ 3-15
Figure 3-15 Flow of Installing Cabinet on Cement Floor .......................................... 3-16
Figure 3-16 Installing Drilling Template ................................................................... 3-17
Figure 3-17 Cabinet Installation on Cement Floor ................................................... 3-18
Figure 3-18 Single Cabinet Installed on Cement Floor ............................................ 3-19
Figure 3-19 Connecting Adjacent Cabinets ............................................................. 3-21
Figure 3-20 Installing Guide Rail ............................................................................. 3-22
Figure 3-21 Installing Floating Nuts ........................................................................ 3-23
Figure 3-22 Installed Floating Nut (Side View) ........................................................ 3-23
Figure 3-23 Installed Floating Nut (Front View) ....................................................... 3-24
Figure 3-24 Installing Shelf ..................................................................................... 3-25
Figure 3-25 Unplugging Fan Subrack...................................................................... 3-27
Figure 3-26 Installing Fan Subrack ......................................................................... 3-28
Figure 3-27 Installing Power Box ............................................................................ 3-29
Figure 3-28 Installing ECDM Module....................................................................... 3-30
Figure 3-29 Installing Power Distribution Subrack ................................................... 3-31
Figure 3-30 Installing Ventilation Subrack ............................................................... 3-32
I
SJ-20121213161403-006|20131015 (R1.2)
Figures
III
SJ-20121213161403-006|20131015 (R1.2)
IV
SJ-20121213161403-006|20131015 (R1.2)
Tables
Table 1-1 Installation Tools........................................................................................ 1-2
Table 3-1 Applicable Height Ranges of Adjustable Bases ......................................... 3-3
Table 4-1 Specifications of Interior Power Cables ..................................................... 4-2
Table 4-2 Specifications of exterior Power Cables..................................................... 4-4
Table 4-3 Specification of the Service Sub-rack Grounding Cables ........................... 4-6
Table 4-4 Specifications of the Power Distribution Subrack Grounding Cables ........... 4-7
Table 4-5 Specifications of Cabinet Door Grounding Cables ..................................... 4-8
Table 4-6 Specifications of Exterior Grounding Cables .............................................. 4-9
Table 4-7 Specifications of the Line Reference Clock Cable.................................... 4-12
Table 4-8 Specifications of the BITS Reference Clock Cable................................... 4-13
Table 4-9 Specifications of the Inter-Shelf Clock Cable ........................................... 4-15
Table 4-10 Specifications of Media Plane Interconnection Fibers ............................ 4-17
Table 4-11 Specifications of Control Plane Interconnection Ethernet Cables ........... 4-20
Table 4-12 Specifications of Interface Fibers ........................................................... 4-22
Table 4-13 Specifications of Interface Network Cables ............................................ 4-23
Table 4-14 Specifications of Interface E1/T1 Cables ............................................... 4-25
Table 4-15 Specifications of OMC Network Cables ................................................. 4-27
Table 4-16 Specifications of PD485 Cable .............................................................. 4-28
Table 5-1 Installation Check Contents and Standards ............................................... 5-2
Table 8-1 Installation Materials.................................................................................. 8-2
Table 8-2 Power Splitter Solution Materials ............................................................... 8-8
Table 9-1 Specifications of Power Cable ................................................................... 9-6
Table 9-2 Relation of Ports and Sensors for Cable H-MON-025 .............................. 9-10
Table 9-3 Functions of End B for Door Access Sensor Cable .................................. 9-16
Table 9-4 Technical indices of door access sensor .................................................. 9-16
Table A-1 Connection of Interior -48 V Power Cable .................................................A-1
Table A-2 Connection of Interior -48 V RTN Power Cable .........................................A-1
Table A-3 Connection of Grounding Cable for Service Subrack.................................A-2
Table A-4 Connection of Cabinet Door Grounding Cable...........................................A-2
Table A-5 Connection of Grounding Cable for PDU...................................................A-2
Table A-6 Connections of Media Plane Interconnection Fiber....................................A-2
Table A-7 Connections of Control Plane Interconnection Cable.................................A-3
V
SJ-20121213161403-006|20131015 (R1.2)
VI
SJ-20121213161403-006|20131015 (R1.2)
Glossary
DDF
- Digital Distribution Frame
ECDM
- ETCA Chassis Data Module
ESD
- Electrostatic Discharge
ETCA
- Enhanced ATCA
ODF
- Optical Distribution Frame
OMC
- Operation & Maintenance Center
PE
- Protective Earth
PVC
- Polyvinyl Chloride
PWR
- Power
RTN
- Return
TCP
- Transmission Control Protocol
UDP
- User Datagram Protocol
VLAN
- Virtual Local Area Network
VII
SJ-20121213161403-006|20131015 (R1.2)