EJERCICIO

DETERMINE LA CARGA FACTORIZADA DE DISEO DE UNA COLUMNA DE PB PARA UNA


EDIFICACIN TIPO APORTICADA UBICADA EN ZONA SSMICA Y CUYO USO ASIGNADA
ES PARA VIVIENDAS. LAS CARGAS DE SERVICIO QUE ACTAN SON LAS SIGUIENTES:
CP: 44
CV:24
W:18
CVT: 0

Sx:36
Sy: 20
Sh:12

= 0.25
o = 2.5
COMBINACIONES DE ACCIONES (SIN SISMO)
I) 1.40CP = 1,40*44tn = 61.6tn
II) 1.2 CP + 1.6 CV + 0.5 Cvt 1.20*44 tn+1.60*24tn+0.5*0= 91.2tn
III) 1.2 CP + 1.6 CVt + 0.5 CV 1.20*44tn+1.60*0+0.5*24tn = 64.8 tn
1.2 CP + 1.6 CVt + 0.8 W 1.20*44tn+1.60*0+0.8*18tn = 67.2 tn
IV) 1.2 CP + 1.3 W + 0.5 CV + 0.5 CVt 1.20 * 44tn +1.30*18tn+05*24+0.5*0 = 88.2 tn
V) 0.9 CP + 1.3 W 0.9 * 44tn + 1.3*18tn = 63 tn
0.9 CP - 1.3 W 0.9 * 44tn - 1.3*18tn = 16.2 tn
ACCIONES SSMICAS: EFECTOS ORTOGONALES
VI) 1.2 CP + CV +/- S 1.20*44tn + 0.25*24 +36 = 94.8 tn
1.20*44tn + 0.25*24 +20 = 78.8 tn
1.20*44tn + 0.25*24 -36 = 22.8 tn
1.20*44tn + 0.25*24 -20 =38.8 tn
VII) 0.9 CP +/- S 0.90*44tn + 36 = 75.6 tn
0.90*44tn + 20 = 59.6 tn
0.90*44tn - 36 = 3.6 tn
0.90*44tn - 20 = 19.6 tn
Todos los valores con Viento o con Sismo son positivos (compresin en columnas) o sea que
no hay problemas de traccin ni de volcamiento en la estructura.
REQUISITOS ADICIONALES
IX) 1.2 CP + CV +/- o SH

1.20*44 + o.25*24+ 2.5*12 = 88.8 tn


1.20*44 + o.25*24 - 2.5*12 = 28.8 tn

X) 0.9 CP +/- o SH 0.90*44+2.5*12 = 69.6 tn


0.90*44+2.5*12 = 9.6 tn
LA CARGA FACTORIZADA QUE CONTROLA EL DISEO ES DE 91.2 TN TON.