Documentos de Académico
Documentos de Profesional
Documentos de Cultura
APPLICATION: ONSHORE
Date
Description
Author
Sponsor
6/02
General revision
MULI
MULI
8/05
General revision
XSON
MULI
11/09
MULI
MULI
November 2009
1 of 28
CIV-DU-5009-H
CONTENTS
1.0
Scope ..........................................................................................................................3
2.0
References ..................................................................................................................3
2.1 ......Purchaser Documents ......................................................................................3
2.2 ......Industry Codes and Standards .........................................................................3
2.3 ......Government Regulations ..................................................................................5
3.0
Definitions ...................................................................................................................6
4.0
5.0
6.0
7.0
November 2009
2 of 28
CIV-DU-5009-H
SCOPE
1. This specification defines minimum requirements for structural engineering and design of
process and manufacturing facilities at onshore U.S. and other sites.
2. Some content is reproduced and used under PIPs Membership Agreement.
3. More specific and comprehensive design requirements may need to be developed for specific
project needs.
4. Any exceptions to the requirement of this specification shall be submitted in writing for
resolution by the Purchaser.
2.0
REFERENCES
1. The documents listed in this section are referenced herein and are considered part of this
specification.
2. Use the edition of each referenced document in effect on the date of the publication of this
specification.
3. In the event of any inconsistency between the requirements stated in the various technical and
reference documents, the following order of precedence shall apply:
a. Local country statutes, regulations, and directives
b. Local country codes and standards
c. The project requisition
d. Data sheets
e. This specification
f.
Purchaser Documents
CIV-PU-4841
CIV-DS-5237
CIV-DS-5238
Standard Drawings
GD-Q68922
2.2
350/350R
3 of 28
CIV-DU-5009-H
NDS Supplement
Load and Resistance Factor Design (LRFD) Specification for Structural Steel Buildings
American Iron and Steel Institute (AISI)
SG 673, Part I
SG 673, Part II
SG 913, Part I
SG 913, Part II
SEI 37-02
A82/A82M
A185/A185M
A193/A193M
A307
Standard Specification for Carbon Steel Bolts and Studs, 60 000 PSI
Tensile Strength
November 2009
4 of 28
CIV-DU-5009-H
A325
Standard Specification for Structural Bolts, Steel, Heat Treated, 120/105 ksi
Minimum Tensile Strength
A354
A490
A615/A615M
A706/A706M
Standard Specification for Low-Alloy Steel Deformed and Plain Bars for
Concrete Reinforcement
A992/A992M
F1554
Standard Specification for Anchor Bolts, Steel, 36, 55, and 105 ksi
Yield Strength
Specifications for Top Running Bridge and Gantry Type Multiple Girder
Overhead Electric Traveling Cranes
No. 74
Specifications for Top Running and Under Running Single Girder Overhead
Electric Traveling Cranes Utilizing Under Running Trolley Hoist
PCEWE001
STE05121
STE03360
Government Regulations
Federal Standards and Instructions of the Occupational Safety and Health Administration (OSHA),
including any additional requirements by state or local agencies that have jurisdiction in the state
where the project is to be constructed, shall apply.
November 2009
5 of 28
CIV-DU-5009-H
DEFINITIONS
Blast loadsThe load on a structure caused by overpressure resulting from the ignition and
explosion of flammable material or by overpressure resulting from a vessel burst.
Bundle pull loads (Bp)The force required to pull the bundles out of the heat exchanger.
Dead loads (D)The actual weight of materials forming the building, structure, foundation, and
all permanently attached appurtenances. For this specification, dead loads are designated by the
following nomenclature:
Ds
Structure dead load is the weight of materials forming the structure (not the empty
weight of process equipment, vessels, tanks, piping, nor cable trays), foundation,
soil above the foundation resisting uplift, and all permanently attached
appurtenances (e.g., lighting, instrumentation, HVAC, sprinkler and deluge
systems, fireproofing, and insulation, etc.).
Df
Erection dead load is the fabricated weight of process equipment or vessels and is
generally taken from the certified equipment or vessel drawing.
De
Empty dead load is the empty weight of process equipment, vessels, tanks, piping,
and cable trays.
Do
Operating dead load is the empty weight of process equipment, vessels, tanks,
piping, and cable trays plus the maximum weight of contents (fluid load) during
normal operation.
Dt
Test dead load is the empty weight of process equipment, vessels, tanks, and/or
piping plus the weight of the test medium contained in the system.
Earthquake loads (E)The effect of earthquake induced forces on the structure and/or
equipment as determined in accordance with the applicable design standard and code. For this
specification, earthquake loads are designated by the following nomenclature:
Eo
Earthquake load considering the unfactored operating dead load and the applicable
portion of the unfactored structure dead load
Ee
Earthquake load considering the unfactored empty dead load and the applicable
portion of the unfactored structure dead load
November 2009
6 of 28
CIV-DU-5009-H
Live loads (L)Loads produced by the use and occupancy of the building or structure. Live loads
include the weight of all movable loads, such as personnel, tools, miscellaneous equipment,
movable partitions, wheel loads, parts of dismantled equipment, stored material, etc.
Pressure loadsFor this specification, pressure loads for ground-supported tanks are designated
by the following:
Pi
Pe
External pressure
Pt
Snow loadsLoads on a building or structure as a result of the accumulation of snow on its roof
as defined by the applicable design standard.
Thermal loads (T)Loads or effects produced by thermal expansion and contraction of
equipment and piping. For this specification, thermal loads are designated by the following
nomenclature:
Tp
Af
Ff
Pipe rack friction forces caused by the sliding of pipes or friction forces caused by
the sliding of horizontal vessels or heat exchangers on their supports, in response
to thermal expansion
Traffic loadsDesign vehicle wheel loading as defined in the applicable standard for design of
highway bridges.
Wind loads (W) Loads on a building or structure caused by the wind pressure as defined in the
applicable design standard.
4.0
4.1
General
1. Design, construction, and general project requirements shall comply with the referenced
Purchaser and project specifications, codes, standards, and regulations applicable in the
country where the project is located.
2. New facilities, buildings, and other structures, including floor slabs and foundations, shall be
designed to resist the minimum loads defined in ASCE/SEI 7, local building codes, this
section and the loads defined in the project and plant site data sheets (CIV-DS-5237 and 5238).
3. In addition to the loads in this section, other loads shall be considered as appropriate. These
loads shall include, but are not limited to, snow, ice, rain, hydrostatic, dynamic, upset
conditions, earth pressure, vehicles, buoyancy, and erection.
4. Future loads shall be considered if specified by the Purchaser.
5. For existing facilities, actual loads may be used in lieu of the minimum specified loads.
November 2009
7 of 28
CIV-DU-5009-H
6. Eccentric loads (piping, platforms, etc.), particularly on horizontal and vertical vessels and
exchangers, shall be considered. For additional information regarding eccentric loads on
horizontal vessels and exchangers, see PIP STE03360.
7. The Purchaser shall be consulted to determine the classification of occupancy categories for
buildings and other structures for the purpose of applying wind, earthquake, snow, and ice load
provisions in accordance with Section 1.5 of ASCE/SEI 7.
Note
4.2
For process industry facilities, ASCE/SEI 7 Category III is the most likely
classification because of the presence of toxic or explosive substances. Category II
may be used if the Purchaser can demonstrate that release of the toxic or explosive
substances does not pose a threat to the public. See ASCE/SEI 7, Section 1.5.2 and
Table 1-1 for specific details. In some cases, it may be appropriate to select
Category IV.
4.2.2
November 2009
8 of 28
CIV-DU-5009-H
4.2.3
4.2.4
November 2009
9 of 28
CIV-DU-5009-H
b. The fluid load acts through the bottom of the tank and does not act vertically
through the wall of the tank. Therefore, the metal dead load and the fluid load
shall be used separately in design.
2. Empty dead load (De): The corroded metal weight (if a corrosion allowance is
specified) shall be considered as the empty dead load for checking uplift and
components controlled by minimum loading.
3. Test dead load (Dt)
a. Test dead load for a ground-supported storage tank is the same as the operating
load (Do), except that the fluid load shall be calculated based on the specific
gravity of the test medium used.
b. The test medium shall be as specified in the contract documents or as specified by
the Purchaser. Unless otherwise specified, a minimum specific gravity of 1.0 shall
be used for the test medium.
4.3
Concentrated**
2
75 psf
(3.6 kN/m2)
25 psf (1.2
kN/m2)
NA
This 250 psf (12.0 kN/m2) live load includes small equipment.
The loads provided in this table are to be used unless noted otherwise on the
Purchasers data sheet.
3. Uniform and concentrated live loads listed in Table 3 shall not be applied simultaneously.
4. According to ASCE/SEI 7, concentrated loads equal to or greater than 1,000 lb (4.5 kN) may
be assumed to be uniformly distributed over an area of 2.5 ft (750 mm) by 2.5 ft (750 mm) and
shall be located to produce the maximum load effects in the structural members.
5. Stair treads shall be designed according to OSHA regulations or building code as applicable.
6. Live load reductions shall be in accordance with ASCE/SEI 7.
7. For manufacturing floor areas not used for storage, the live load reduction specified by
ASCE/SEI 7 for lower live loads may be used.
November 2009
10 of 28
CIV-DU-5009-H
8. The loadings on handrails and guardrails for process equipment structures shall be in
accordance with OSHA 1910.
9. The loadings on handrails and guardrails for buildings and structures under the jurisdiction of
a building code shall be in accordance with the building code.
4.4
4.5
The earthquake loads in ASCE/SEI 7 are limit state earthquake loads, and this should
be taken into account if using allowable stress design methods or applying load
factors from other codes. Earthquake loads for API Standard 650 storage tanks are
allowable stress design loads.
2. Site specific design parameters shall conform to the Plant Site data sheet, CIV-DS-5238.
3. Guidelines for Seismic Evaluation and Design of Petrochemical Facilities may also be used as
a general reference for earthquake design.
November 2009
11 of 28
CIV-DU-5009-H
4. Earthquake loading shall be determined using ASCE/SEI 7, Chapter 15, if ASCE/SEI 7 is used
for the earthquake design of nonbuilding structures as defined in ASCE/SEI 7, Section 15.1.1
and Tables 15.4-1 and 15.4-2.
Note
Nonbuilding structures include but are not limited to elevated tanks or vessels, stacks,
pipe racks, and cooling towers.
5. The importance factor I for nonbuilding structures shall be determined from ASCE/SEI 7,
Section 15.4.1.1.
Note
4.6
Impact Loads
1. Impact loads shall be in accordance with ASCE/SEI 7.
2. Impact loads for davits shall be the same as those for monorail cranes (powered).
3. Lifting lugs or pad eyes and internal members (included both end connections) framing into
the joint where the lifting lug or pad eye is located shall be designed for 100% impact.
4. All other structural members transmitting lifting forces shall be designed for 15% impact.
5. Allowable stresses shall not be increased when combining impact with dead load.
4.7
Thermal Loads
1. All support structures and elements thereof shall be designed to accommodate the loads or
effects produced by thermal expansion and contraction of equipment and piping.
2. Thermal loads shall be included with operating loads in the appropriate load combinations.
Thermal load shall have the same load factor as dead load.
3. Thermal loads and displacements shall be calculated on the basis of the difference between
ambient or equipment design temperature and installed temperature. To account for the
significant increase in temperatures of steel exposed to sunlight, 35F (20C) shall be added to
the maximum ambient temperature.
4. Friction loads caused by thermal expansion shall be determined using the appropriate static
coefficient of friction. Coefficients of friction shall be in accordance with Table 4.
Table 4:
Coefficients of Friction
0.3
0.4
Steel to Concrete
0.6
5. Friction loads shall be considered temporary and shall not be combined with wind or
earthquake loads. However, anchor and guide loads (excluding their friction component) shall
be combined with wind or earthquake loads.
November 2009
12 of 28
CIV-DU-5009-H
6. For pipe racks supporting multiple pipes, use the following guidelines:
a. 10% of the total estimated operating weight (i.e., 4 psf or 0.19 kPa) shall be used as an
estimated horizontal friction load applied only to local supporting beams.
b. For pipes larger than 12-inches nominal diameter, the actual friction load shall be used.
For the remainder area not occupied by the larger pipes, 10% of the estimated operating
weight (i.e., 4 psf or 0.19 kPa) shall be used.
c. When there will be three or fewer pipes (i.e., no future pipe addition), 30% of the total of
the actual operating weight of the pipes shall be used.
d. An estimated friction load equal to 5% of the total piping weight shall be accumulated and
carried into pipe rack struts, columns, braced anchor frames, and foundations.
Note
Under normal loading conditions with multiple pipes, torsional effects on the local
beam need not be considered because the pipes supported by the beam limit the
rotation of the beam to the extent that the torsional stresses are minimal. Under
certain circumstances, engineering judgement shall be applied to determine whether
a higher friction load and/or torsional effects should be used.
7. Pipe anchor and guide loads shall have the same load factor as dead loads.
8. Internal pressure and surge shall be considered for pipe anchor and guide loads.
9. Beams, struts, columns, braced anchor frames, and foundations shall be designed to resist
actual pipe anchor and guide loads.
10. For local beam design, only the top flange shall be considered effective for horizontal bending
unless the pipe anchor engages both flanges of the beam.
4.8
If it can be assured that the bundles will be removed strictly by the use of a bundle
extractor attached directly to the exchanger (such that the bundle pull force is not
transferred to the structure or foundation), the structure or foundation need not be
designed for the bundle pull force. Such assurance would typically require the
addition of a sign posted on the exchanger to indicate bundle removal by an extractor
only.
3. The portion of the bundle pull load at the sliding end support shall equal the friction force or
half the total bundle pull load, whichever is less. The remainder of the bundle pull load shall
be resisted at the anchor end support.
4.9
Traffic Loads
1. Buildings, trenches, and underground installations accessible to truck loading shall be
designed to withstand HS2O load as defined by AASHTO HB-17.
2. Maintenance or construction crane loads shall also be considered where applicable.
3. Truck or crane loads shall have the same load factor as live load.
November 2009
13 of 28
CIV-DU-5009-H
Blast Load
1. Control houses or other buildings housing personnel and control equipment near processing
plants may need to be designed for blast resistance.
2. Blast load shall be computed and applied in accordance with the Project data sheet,
CIV-DS-5237, and the Design of Blast Resistant Buildings in Petrochemical Facilities.
4.11
4.12
Occasional Loads
1. Occasional loads from sources such as system upset, equipment start up, regeneration, water
hammer etc. shall be considered and treated as live loads (L).
2. Occasional loads need not be combined with seismic or wind loads.
5.0
LOAD COMBINATIONS
5.1
General
1. Buildings, structures, equipment, vessels, tanks, and foundations shall be designed in
accordance with the following:
a. Appropriate load combinations from ASCE/SEI 7 except as otherwise specified in this
specification
b. Local building codes
c. Any other applicable design codes and standards
d. Any other probable and realistic combination of loads
2. The non-comprehensive list of typical load combinations for specific type of structure
provided in Sections 5.2.2 through 5.2.6 in both allowable stress design (ASD) and strength
design format shall be considered and used as applicable.
3. Engineering judgment shall be used in establishing all appropriate load combinations.
4. Unless otherwise permitted by the applicable design standard of the material or component,
the use of a one-third stress increase for load combinations (including wind or earthquake
loads) shall not be allowed.
5. The load combinations provided are appropriate for use with the strength design provisions of
either AISC LRFD (third edition or later) or ACI 318 (2002 edition or later).
Note
November 2009
The dead load factor used for the earthquake uplift ASD load combinations is
generally taken as 0.9. This factor is greater than the 0.6 dead load factor used in the
ASD load combinations of ASCE/SEI 7, Chapter 2, because the dead loads of
nonbuilding structures are known to a higher degree of accuracy than are the
corresponding dead loads of buildings. A dead load factor of 0.9 instead of 1.0 is
used to account for the effect of vertical seismic forces. The use of this reduction is
necessary because foundations sized using ASD loads, except for foundations for
ground-supported storage tanks, are generally not required to consider the effect of
14 of 28
CIV-DU-5009-H
vertical seismic uplift forces if a dead load factor of 0.6 is used. A dead load factor of
1.0 is used for the wind uplift ASD load combinations because of the higher accuracy
of dead loads of nonbuilding structures
5.2
5.2.2
Vertical Vessels
Load combinations for vertical vessels are shown in Tables 5 and 6. Refer to Section 3.0
for definitions of Load abbreviations.
Table 5:
Load
Comb.
No.
Load
Combination
Allowable
Stress
Multiplier
Description
D s + Do + L
1.00
Ds + D o +
(W or 0.7 Eoa)
1.00
Ds + De + W
1.00
4a
1.00
4b
1.00
D s + Df + W p
1.00
D s + Dt + W p
1.20
Notes:
a) For skirt-supported vertical vessels and skirt-supported elevated tanks classified as
Occupancy Category IV in accordance with ASCE/SEI 7, Section 1.5 and Table 1-1,
the critical earthquake provisions and implied load combination of ASCE/SEI 7,
Section 15.7.10.5, shall be followed.
b) Erection weight + partial wind is required only if the erection weight of the vessel is
significantly less than the empty weight of the vessel.
c) Thrust forces caused by thermal expansion of piping shall be included in the
calculations for operating load combinations, if deemed advisable. The pipe stress
engineer shall be consulted for any thermal loads that are to be considered.
November 2009
15 of 28
CIV-DU-5009-H
Load
Comb.
No.
Load Combination
Description
Operating Weightc
5a
5b
Test Weight
Notes
a) For skirt-supported vertical vessels and skirt-supported elevated tanks classified as
Occupancy Category IV in accordance with ASCE/SEI 7, Section 1.5 and Table 1-1,
the critical earthquake provisions and implied load combination of ASCE/SEI 7,
Section 15.7.10.5, shall be followed.
b) Erection weight + partial wind is required only if the erection weight of the vessel is
significantly less than the empty weight of the vessel.
c) Thrust forces caused by thermal expansion of piping shall be included in the
calculations for operating load combinations, if deemed advisable. The pipe stress
engineer shall be consulted for any thermal loads that are to be considered. The
same load factor as used for dead load shall be used.
5.2.3
November 2009
Allowable
Stress
Multiplier
Description
Ds + Do +
(T or Ff)b
1.00
Operating Weight +
Thermal Expansion or Friction Force
Ds + Do + L +
(T or Ff)b
1.00
Ds + Do +
(W or 0.7 Eo)
1.00
D s + De + W
1.00
16 of 28
CIV-DU-5009-H
Load
Comb.
No.
Load
Combination
Allowable
Stress
Multiplier
Description
5a
1.00
5b
1.00
D s + D f + Wp
1.00
D s + D t + Wp
1.20
Ds + Ded + Bp
1.00
Notes:
a. Wind and earthquake forces shall be applied in both transverse and longitudinal
directions, but shall not necessarily be applied simultaneously.
b. The design thermal force for horizontal vessels and heat exchangers shall be the
lesser of T or Ff.
c. Erection weight + partial wind is required only if the erection weight of the vessel or
exchanger is significantly less than the empty weight of the vessel or exchanger.
d. Heat exchanger empty dead load will be reduced during bundle pull because of the
removal of the exchanger head.
e. Sustained thermal loads not relieved by sliding caused by vessel or exchanger
expansion shall be considered in operating load combinations with wind or
earthquake.
f. Thrust forces caused by thermal expansion of piping shall be included in the
calculations for operating load combinations if deemed advisable. The pipe stress
engineer shall be consulted for any thermal loads that are to be considered.
Table 8:
November 2009
Load
Comb.
No.
Load Combination
Description
Operating Weight +
Thermal Expansion or Friction Force
Operating Weight +
Wind or Earthquakea
5a
5b
17 of 28
CIV-DU-5009-H
Load
Comb.
No.
Load Combination
Description
Test Weight
(For Horizontal Vessels Only)
10
Notes:
a. Wind and earthquake forces shall be applied in both transverse and longitudinal
directions, but shall not necessarily be applied simultaneously.
b. The design thermal force for horizontal vessels and heat exchangers shall be the
lesser of T or Ff.
c. Erection weight + partial wind is required only if the erection weight of the vessel or
exchanger is significantly less than the empty weight of the vessel or exchanger.
d. Heat exchanger empty dead load will be reduced during bundle pull because of the
removal of the exchanger head.
e. Sustained thermal loads not relieved by sliding from vessel or exchanger expansion
shall be considered in operating load combinations with wind or earthquake.
f. Thrust forces caused by thermal expansion of piping shall be included in the
calculations for operating load combinations, if deemed advisable. The pipe stress
engineer shall be consulted for any thermal loads that are to be considered. The
same load factor as used for dead load shall be used.
5.2.4
Load
Comb.
No.
Load Combination
Allowable
Stress
Multiplier
D s + Do + F f + T + A f
1.00
Ds + D o + A f +
(W or 0.7 Eo)
1.00
D s + D ec + W
1.00
4a
1.00
November 2009
Description
18 of 28
CIV-DU-5009-H
Load
Comb.
No.
Load Combination
Allowable
Stress
Multiplier
Description
4b
1.00
D s + Dt + W p
1.20
Notes:
a. Considerations of wind forces are normally not necessary in the longitudinal
direction because friction and anchor loads will normally govern.
b. Earthquake forces shall be applied in both transverse and longitudinal directions, but
shall not necessarily be applied simultaneously.
c. 0.6Do may be used as a close approximation of the empty pipe condition De.
d. Test weight + partial wind normally is required only for local member design because
test is not typically performed on all pipes simultaneously.
e. Pipe-stress engineer shall be consulted for the nature of the anchor loads (static or
dynamic) that are to be considered in structural analysis of pipe racks and bridges.
Table 10:
Load
Comb.
No.
Load Combination
Description
4a
4b
Test Weight
Notes:
a. Considerations of wind forces are normally not necessary in the longitudinal
direction because friction and anchor loads will normally govern.
b. Earthquake forces shall be applied in both transverse and longitudinal directions, but
shall not necessarily be applied simultaneously.
c. 0.6Do may be used as a close approximation of the empty pipe condition De.
d. Test weight + partial wind normally is required only for local member design because
test is not typically performed on all pipes simultaneously.
e Pipe-stress engineer shall be consulted for the nature of the anchor loads (static or
dynamic) that are to be considered in structural analysis of pipe racks and bridges.
November 2009
19 of 28
CIV-DU-5009-H
Load
Comb.
No.
Load Combination
Description
Ds + Do + Pi
Operating Weight +
Internal Pressurea
Ds + Dt + P t
Test Weight +
Test Pressure
Ds + Do + (L or S) + 0.4 Peb
Ds + Do + 0.1 S + Eoc
Notes:
a. For internal pressures sufficient to lift the tank shell according to the rules of API
Standard 650, tank, anchor bolts, and foundation shall be designed to the additional
requirements of API Standard 650, Appendix F.7.
b. If the ratio of operating pressure to design pressure exceeds 0.4, the Purchaser shall
consider specifying a higher factor on design pressure in load combinations 3, 4, 5,
and 7 of Table 9.
c. Earthquake loads for API Standard 650 tanks taken from ASCE/SEI 7 bridging
equations or from API Standard 650 already include the 0.7 ASD seismic load factor.
5.2.6
November 2009
20 of 28
CIV-DU-5009-H
Test Combinations
1. Engineering judgment shall be used in establishing the appropriate application of test load
combinations to adequately address actual test conditions in accordance with project and code
requirements while avoiding overly conservative design.
2. Consideration shall be given to the sequence and combination of testing for various
equipment, vessels, tanks, and/or piping systems supported on common structures, pipe racks,
or foundations.
3. Full wind and earthquake loads are typically not combined with test loads unless an unusually
long test duration is planned (i.e., if a significant probability exists that the partial wind
velocity will be exceeded or an earthquake event may occur).
4. Additional loading shall be included with test if specified in the contract documents.
5. For allowable stress design, a 20% allowable stress increase shall be permitted for any test
load combination.
6. For ultimate strength/limit states design, no load factor reduction shall be permitted for any
test load combination.
6.0
STRUCTURAL DESIGN
6.1
Steel
1. Steel design shall be in accordance with AISC/ANSI 360-05 specification.
2. For cold-formed shapes, design shall be in accordance with AISI/SG-673 or AISI/SG-913
specifications.
3. Steel joists shall be designed in accordance with SJI standards.
Note
Supplement number 1 to the AISC ASD specification deleted the one-third stress
increase for use with load combinations including wind or earthquake loads. Because
of the deletion of the one-third stress increase, designs made to the AISC LRFD
specifications should be considered for economy.
4. Steel design, including steel joists and metal decking, shall be in accordance with OSHA 29
CFR 1926, Subpart R, to provide structural stability during erection and to protect employees
from the hazards associated with steel erection activities.
5. Common requirements that affect steel design areas are as follow (not an all inclusive list):
a. All column base plates shall be designed with a minimum of four anchor bolts. Posts
(which weigh less than 300 lb [136 kg]) are distinguished from columns and are excluded
from the four-anchor bolt requirement.
b. Columns, column base plates, and their foundations shall be designed to resist a minimum
eccentric gravity load of 300 lb (136 kg) located 18 inches (450 mm) from the extreme
outer face of the column in each direction at the top of the column shaft. Column splices
shall be designed to meet the same load-resisting characteristics as those of the columns.
c. Double connections through column webs or at beams that frame over the tops of columns
shall be designed so that at least one installed bolt remains in place to support the first
beam while the second beam is being erected. The fabricator may also supply a seat or
equivalent device with a means of positive attachment to support the first beam while the
second beam is being erected.
November 2009
21 of 28
CIV-DU-5009-H
d. Perimeter columns shall extend 48 inches (1,200 mm) above the finished floor (unless
constructability does not allow) to allow the installation of perimeter safety cables.
Provision shall be made for the attachment of safety cables.
e. Structural members of framed metal deck openings shall be turned down to allow
continuous decking, except where not allowed by design constraints or constructability.
The openings in the metal deck shall not be cut until the hole is needed.
f.
Shear stud connectors that will project vertically from or horizontally across the top flange
of the member shall not be attached to the top flanges of beams, joists, or beam
attachments until after the metal decking or other walking/working surface has been
installed.
6. All welded structural connections shall use weld filler material conforming to AWS D1.1/
D1.1M, Section 3.3 (including Table 3.1), and have an electrode strength of 58 ksi (400 MPa)
minimum yield strength and 70 ksi (480 MPa) tensile strength, unless otherwise required.
7. Structural steel wide-flange shapes, including WT shapes, shall be in accordance with
ASTM A992/A992M, unless otherwise specified.
8. All other structural shapes, plates, and bars shall be in accordance with ASTM A36/A36M,
unless otherwise specified.
9. Preference in design shall be given to shop-welded, field-bolted connections.
10. Compression flanges of floor beams, not supporting equipment, may be considered braced by
decking (concrete or floor plate) if positively connected thereto.
11. Grating shall not be considered as lateral bracing for support beams.
12. Except as specified in Section 6.1, item 13 or if slip-critical connections are required by
the RSCS Specification for Structural Joints Using ASTM A325 or A490 Bolts, all bolts 3/4
inches (19 mm) and larger (except anchor bolts) shall be type-N (bearing-type with threads
included in the shear plane) high-strength ASTM A325 bolts.
13. Bolt size shall be as follows:
a. Structural members: 3/4 inch (19 mm) minimum
b. Railings, ladders, purlins, and girts: 5/8 inch, (16 mm) ASTM A307
14. Minimum thickness of bracing gusset plates shall be 3/8 inch (10 mm).
6.2
Concrete
1. Concrete design shall be in accordance with ACI 318/318R.
2. Concrete design for liquid-containing structures shall also be designed in accordance with
ACI 350/350R.
3. Unless otherwise specified, all reinforcing steel shall be in accordance with ASTM A615/
A615M Grade 60 deformed.
4. ASTM A615/A615M Grade 60 plain wire conforming to ASTM A82/A82M may be used for
spiral reinforcement.
5. Welded wire fabric shall conform to ASTM A185/A185M.
November 2009
22 of 28
CIV-DU-5009-H
Masonry
Masonry design shall be in accordance with ACI 530/ASCE 5/TMS 402.
6.4
Elevator Supports
Elevator support design shall be in accordance with ASME A17.1.
6.5
Crane Supports
1. Vertical deflection of support runway girders shall not exceed the limits given in Table 12,
below, if loaded with the maximum wheel load(s), without impact (where L = the span length).
Table 12:
L/600
L/800
L/1000
L/450
Monorails
L/450
2. Vertical deflection of jib crane support beams shall not exceed L/225 (where L = the maximum
distance from the support column to load location along the length of the jib beam) if loaded
with the maximum lifted plus hoist load(s), without impact.
3. Lateral deflection of support runway girders for cranes with lateral moving trolleys shall not
exceed L/400 (where L = the span length) if loaded with a total crane lateral force not less than
20% of the sum of the weights of the lifted load (without impact) and the crane trolley. The
lateral force shall be distributed to each runway girder with consideration for the lateral
stiffness of the runway girders and the structure supporting the runway girders.
4. Crane stops shall be designed in accordance with the crane manufacturers requirements or, if
not specified, for the following load:
F = W V2/(2gTn)
where:
F
50% of bridge weight + 90% of trolley weight, excluding the lifted load, kips (kN)
November 2009
23 of 28
6.6
CIV-DU-5009-H
Length of travel (ft) of spring or plunger required to stop crane, from crane
manufacturer, typically 0.15 ft (0.05 m)
Bumper efficiency factor (0.5 for helical springs. Consult crane manufacturer for
hydraulic plunger.)
For...
Pipe racks
Occupied buildings
3. Pipe racks and structure supporting process equipment that are subjected to vibration shall be
evaluated by means of detail dynamic analysis to show the following:
a. The pipe, equipment, and supporting structure are not vibrating at their resonance
frequency, and
b. The pipe deflection due to the vibration is within the acceptable limit as set by the
responsible piping engineer.
6.7
Foundations
1. Foundation design shall be based on the results of a geotechnical engineering investigation.
2. The minimum overturning stability ratio and the minimum factor of safety against sliding
for wind, earthquake and other service loads shall be as shown in Table 14.
3. For earthquake loads calculated by the Equivalent Lateral Force Procedure in ASCE/
SEI 7, additional stability checks shall be performed in accordance with ASCE/SEI 7,
Section 12.8.5, Overturning.
November 2009
24 of 28
CIV-DU-5009-H
Loading Condition
Overturning
Sliding
Normal Operating
2.0
2.0
1.5
1.5
Wind
1.5
1.5a
Seismic
1.0
1.0
Notes:
a. The minimum overturning stability ratio and factor of safety against sliding shall
be 1.0 if the dead load factor of 0.6 in accordance with ASCE/SEI 7, Chapter 2
is used in the load combination involving wind. This requirement is consistent
with ASCE/SEI 7 provisions, in which the factor of safety is built into the 0.6
dead load factor in the load combinations.
4. For foundations designed using seismic load combinations from Tables 5, 7, and 9 of this
specification, the reduction in overturning effects at the soil-foundation interface permitted in
ASCE/SEI 7, Section 12.13.4, shall not be used.
5. The minimum factor of safety against buoyancy shall be 1.2 if using actual unfactored service
loads.
6. Long-term and differential settlement shall be considered if designing foundations supporting
interconnected, settlement-sensitive equipment or piping systems.
7. Unless otherwise specified, maximum absolute (long term) total and differential settlement for
shallow foundations shall be 1 inch and 1/2 inch, respectively, for structural, equipment, or
piping systems that are sensitive to settlement.
8. Because OSHA requires shoring or the equivalent for excavations 5 ft (1,525 mm) deep or
greater and because it is costly to shore excavations, minimizing the depth of spread footings
shall be considered in the design.
9. Unless otherwise specified, the top of grout (bottom of base plate) of pedestals and ringwalls
shall be 1 ft (300 mm) above the high point of finished grade.
10. Except for foundations supporting ground-supported storage tanks, uplift load combinations
containing earthquake loads do not need to include the vertical components of the seismic load
effect, E, if used to size foundations.
11. Foundations for ground-supported storage tanks that have sufficient internal pressure to lift the
shell shall be designed for the requirements of API Standard 650, Appendix F.7.5.
12. For high temperature equipment supported by concrete foundations, the foundations/structures
shall be isolated from hot equipment with spacers, lugs, rings, such that temperature of
concrete does not exceed 400F (240C).
a. Alternatively, heat resistant concrete may be used.
b. When heat resistant concrete is used, it shall have compressive strength equal to that of
structural concrete it protects.
November 2009
25 of 28
CIV-DU-5009-H
6.9
Anchor Bolts
1. Anchor bolts shall be headed type or threaded rods with compatible nuts using ASTM A36/
A36M, A307, F1554 Grade 36, F1554 Grade 55, F1554 Grade 105, A193/A193M Grade B7,
A354 Grade BC, or A354 Grade BD material.
2. All ASTM A36/A36M, A307, and F1554 Grade 36 anchor bolts shall be hot dip galvanized.
3. Standard cast-in-place anchor bolt shall be in accordance with Purchaser standard drawing
No. GD-Q68922, unless otherwise specified in the contract document.
4. When the minimum anchor bolt spacing and edge distance requirements specified in the
Standard Drawing No. GD-Q68922 cannot be met, special reinforcing bar to transfer tensile
and shear forces shall be required to achieve ductile design. Design of the special
reinforcement for anchors shall be in accordance with Guidelines for Wind Loads and Anchor
Bolt Design for Petrochemical Facilities and PIP STE05121
6.10
Wood
Wood design shall be in accordance with the ANSI/AF&PA NDS-2005 (National Design
Specification for Wood Construction) and the NDS Supplement (Design Values for Wood
Construction).
November 2009
26 of 28
CIV-DU-5009-H
November 2009
27 of 28
CIV-DU-5009-H
6.13
7.0
EXISTING STRUCTURES
If the Purchaser and the engineer of record agree that the integrity of the existing structure is 100%
of the original capacity based on the design code in effect at the time of original design, structural
designs shall be performed in accordance with the following:
1. If additions or alterations to an existing structure do not increase the force in any structural
element or connection by more than 5%, no further analysis is required.
2. If the increased forces on the element or connection are greater than 5%, the element or
connection shall be analyzed to show that it is in compliance with the applicable design code
for new construction.
3. The strength of any structural element or connection shall not be decreased to less than that
required by the applicable design code or standard for new construction for the structure in
question.
November 2009
28 of 28