(MICOM P343)
TG52780
REV00
HYDERABAD
4.0 Alloweddeviaiononthevoltage(+/)
5.0 RatedCurrent
67.5 MW
84.375 MVA
11 KV
5%
4429 A
6.0 Ratedpowerfactor
0.8
7.0 RatedFrequency
50 Hz
8.0 DAxisSynchronousReactance(Xd)
2.159 P.U
9.0 DAxistransientReactance(Xd)
0.2262 P.U
10 DAxissubtransientReactance(Xd)
0.1509 P.U
11 CTprimarycurrent
CT primary current
12 CTsecondarycurrent
5000 A
1A
13 CTratio
5000
14 PTprimaryvoltage(11000/3)
6351 V
15 PTsecondaryvoltage(110/3)
63.5 V
16 PTratio
100
17 ContinuousNeg.Seq.Capability(Percentageofratedcurent)
10 %
2
18 Thermalcapability(I2 t)
20 Sec
19 Transformerimpedance
12.5 %
20 FaultCurrent
31.5 KA
21 TransformerSecondaryVoltage
34.5 KV
22
HVCTratio
20 TransformerMVA
ELECTRICALMACHINESENGINEERING
Prepared
Checked
Approved
SUNITA
SUNITA
SKPANDEY
1750
90 MVA
Date:13.11.10
Rev00
HYDERABAD
ListofProtections(PartofMICOMP343)
1
DifferentialProtection(87G)
StatorEarthfaultprotection(95%)(64G1)
StatorEarthfaultprotection(100%)(64G2)
Poleslippingprotection(78G)
DeadMachineProtection(50G)
LowforwardpowerProtection(37G)
LossofExcitationwithU/Vprotection(40G)
LossofExcitationwithoutU/Vprotection(27/40G)
GeneratorOvercurrentprotection(51.1G)
10
U d f
Underfrequencyprotection(Stagel)(81.1G)
t ti (St
l) (81 1G)
11
Underfrequencyprotection(Stage2)(81.2G)
12
Overfrequencyprotection(Stagel)(81.3G)
13
Overfrequencyprotection(Stage2)(81.4G)
14
GeneratorNegativeSequenceProtection(Stage1)(46G1)
15
GeneratorNegativeSequenceProtection(Stage2)(46G2)
16
Gen.OvervoltageProtection(stagel)(59.1G)
17
Gen.OvervoltageProtection(stage2)(59.2G)
18
UndervoltageProtection(27G)
19
ReversepowerProtection(32G)
20
BackupImpedanceprotection(21G)
21
22
LocalBreakerBackupProtection(50LBB)
ListofProtections(PartofMICOMP633)
23
Generatortransformeroveralldifferentialprotection(87OA)
ListofProtections(PartofMICOMP632)
24
Generatortransformerdifferentailprotection(87GT)
25
RestrictedE/Fprotection(64RT)
26
StandbyE/Fprotection(64ST)
27
Overfluxingrelayoperated(99GT)
PartofMicomP141
28
df/dtprotection(81R)
PartofMX3IGP2A
29
RotorFirstEarthFaultprotection(Stagel)(64F1)
30
RotorFirstEarthFaultprotection(Stage2)(64F2)
TG52780
REV00
HYDERABAD
TG52780
REV00
11 KV
5%
115 %
126.5 V
0.5 Sec
125 %
PT Secondary voltage =
110 V
This time delay shall not be too long to avoid strain on the machine
Recommended time delay =
Relay setting =
2 sec
137.5 V
-56.25 W
-0.28 W
-0.3 W
Setting recommended
-0.3 W
1 sec
56.25 W
0.28 W
0.3 W
Setting recommended
0.3 W
1.5 sec
G:\RELAY_SETTING\PROJECTS_09&10\RINLVSPREV00.xls
HYDERABAD
TG52780
REV00
11 KV
5%
5%
90 %
99 V
3 Sec
48.5 Hz
2 Sec
Action : Alarm
Stage -2: Freqency setting :
Time delay :
47 5 Hz
47.5
1.5 Sec
51 Hz
1 Sec
51.5 Hz
1.5 Sec
0.8857 Amps
0.0886 p.u
0.0886 p.u
20 sec
Time Delay
20 sec
Stage-2 : Trip
Trip threshold setting I2>> (little higher than alarm threshold)
G:\RELAY_SETTING\PROJECTS_09&10\RINLVSPREV00.xls
0.09
HYDERABAD
TG52780
REV00
15.69 sec
Hence setting K
15.69 sec
500 Sec
3 Sec
0.05 In
1.2 In
0%
Bias Slope K2
10 %
Time Delay :
0.1 Sec
:(Typical)
:
7V
1 Sec
Note: - The voltage relay may have to be co-ordinated with system relaying for system ground
faults. System phase to ground faults will be induced zero sequence voltages at the generator
due to capacitive coupling between the windings of the Unit Transformer. This induced voltage
will appear on the secondary of the grounding distribution transformer and may cause
operation of Zero Sequence voltage relay. Time delay shall be coordinated with 33KV
system.Voltage across secondary winding shall be measured and setting shall be done 1 V
higher than measured value.
64G2
Third harmonics U/V threshold setting ( VN3H < ) must be set below the 3 rd hormonics
voltage present during normal operation and Third harmonics O/V threshold setting ( VN3H >
) must be set above the 3rd harmonics voltage present during normal operation
Third Harmonic U/V ( VN3H < ) =
0.5 V
Time Delay
1 Sec
1V
Time Delay
1 Sec
These settings are typical. Voltage shall be measured during normal operation.
Voltage setting may be adopted accordingly.
Action : To trip 86A1 & 86A2
11 Rotor earth fault relay (64R)
Type of relay :
MX3IGP2A
G:\RELAY_SETTING\PROJECTS_09&10\RINLVSPREV00.xls
HYDERABAD
Stage I Setting:
Time Delay
TG52780
REV00
4 Kohms
10 Sec
Action: Alarm
Stage II Setting
200 ohms
Time Delay
10 Sec
1.43 Ohms
71.704 Ohms
16.22 Ohms
8.11
8 Ohms
8 Ohms
154.81 Ohms
154.81
154.81
2 sec
2 sec
Settings:Xa
8 Ohms
Xd = Xb
155 Ohms
1 sec
2 sec
8 Ohms
77 Ohms
2 sec
2 sec
0.22 A
200 msec
Action : To open 33KV bus coupler breaker & trip any other feeders which feeds to 33KV bus
15 OVER CURRENT PROTECTION(51.1G)
This protection is used to protect the Generator against over currents.
Type of Relay : Part of MICOM P343
Current setting
Time setting
0.930 A
:
G:\RELAY_SETTING\PROJECTS_09&10\RINLVSPREV00.xls
10 Sec
HYDERABAD
TG52780
REV00
Action : Alarm
16 Pole slipping protection (78G)
Type of Relay :Part of MICOM P343
D-Axis transient Reactance ( Xd )
0.2262 p.u
Base Power
84.375 MVA
Base voltage
11.000 KV
Base Impedance
Transformer Reactance (XT)
System Impedance
System Impedance (11KV Side)
X1 = System Impedance * Base Impedance
ZA = (Xt +X1)
ZB = 2x Xd'
1.434
0.125
0.632
0.064
0.092
0.217
0.4524
Ohms
Ohms
Ohms
Ohms
Ohms
Ohms
Ohms
31.5 KA
0.161 Ohms
Lens angle
Blinder Angle
120 Deg
75 Deg
T1 & T2 are set to 15ms and system impedance angle is set to 80 deg
Action : To trip 86A1 & 86A2
17 Phase Impedance Protection (21G)
Type of Relay :Part of MICOM P343
Generator full load current
4429 Amps
0.97 Amps
112.90 Ohms
79.03 Ohms
79 Ohms
79 Ohms
Time delay
Action : To trip 86C2
3 sec
0.89 In
0.3
0.4
G:\RELAY_SETTING\PROJECTS_09&10\RINLVSPREV00.xls
HYDERABAD
TG52780
REV00
0.2 Iref
10 Iref
0.2
1.5
1506.18
1750
317
0.181
2642
8.33
0.309
110 V
50 Hz
2.46 V/Hz
2.46
1 Sec
2.53 V/Hz
1 Sec
G:\RELAY_SETTING\PROJECTS_09&10\RINLVSPREV00.xls
0.8857
1.063
1.06 A
30 V
77 V
Instantenous
0.5 sec
90 MVA
HYDERABAD
HV Side Voltage
TG52780
REV00
34.5 KV
LV SideVoltage
HV CT ratio
LV CT Ratio
% Impedance
Tap +10% at the rate of
11 KV
1750
5000
12.5 %
Available
1,506.18 Amps
0.86 Amps
1.16
4429 Amps
0.89
1.13
31.05 KV
1674 Amps
0.956
1.11
0.11
1.06
0.411
Differential current at worst tap condition not be more than 90% of operating current for better
stability
Differential current at worst tap
Operating current at worst tap
This is less than 30% od operating current
Hence Bias setting of m1
m2
At +10% Tap condition current in HV Bias circuit
Rated voltage at +10% tap
Full Load primary current (MVA/(1.732 * KV)
Equivalent current in CT secondary
With the ratio correction the current at the relay Bias terminal
Hence Differential current
Bias current (I1 + I2)/2
Operating current of relay will be (Is + (Bias setting *Bias Current)
0.11
0.411
20%
80%
37.95
1369
0.782
0.909
0.091
0.955
0.391
Differential current at worst tap condition should not be more than 90% of operating current for
better stability
Differential current at worst tap
Operating current at worst tap
This is less than 25% of operating current
Hence Bias setting of m1
m2
Action: To trip 86A1
24 Overall differential protection (87OA)
Type of Relay : Part of MICOM P633
Power
HV Side Voltage
LV SideVoltage
G:\RELAY_SETTING\PROJECTS_09&10\RINLVSPREV00.xls
0.091
0.391
20%
80%
90 MVA
34.5 KV
11 KV
HYDERABAD
TG52780
REV00
HV CT ratio
LV CT Ratio
% Impedance
Tap +10% at the rate of
1750
5000
12.5 %
Available
1,506.18 Amps
0.86 Amps
1.16
4429 Amps
0.89
1.13
4429 Amps
0.89
1.13
31.05 KV
1674 Amps
0.956
1.11
0.11
1 06
1.06
0.411
0.11
0.411
20%
80%
37.95
1369
0.782
0.909
0.091
0.955
0.391
Differential current at worst tap condition should not be more than 90% of operating current for
better stability
Differential current at worst tap
Operating current at worst tap
This is less than 25% of operating current
Hence Bias setting of m1
m2
Action: To trip 86A1
25 df/dt protection
Part of Micom P141
Thesesettings are required to be coordinated with upstream breaker by customer and hence,
settings for df/dt protection are not provided in this document.
G:\RELAY_SETTING\PROJECTS_09&10\RINLVSPREV00.xls
0.091
0.391
20%
80%