RELAY SETTING CALCULATIONS FOR RELAY

(MICOM P343)

TG52780
REV00

HYDERABAD

PROJECT: 67.5 MW STG for RINL VSP


Generator&SystemData:
1.0 Ratedactiveoutput
2.0 RatedApparentoutput
3.0 RatedVoltage

4.0 Alloweddeviaiononthevoltage(+/)
5.0 RatedCurrent

67.5 MW
84.375 MVA
11 KV
5%
4429 A

6.0 Ratedpowerfactor

0.8

7.0 RatedFrequency

50 Hz

8.0 DAxisSynchronousReactance(Xd)

2.159 P.U

9.0 DAxistransientReactance(Xd)

0.2262 P.U

10 DAxissubtransientReactance(Xd)

0.1509 P.U

11 CTprimarycurrent
CT primary current
12 CTsecondarycurrent

5000 A
1A

13 CTratio

5000

14 PTprimaryvoltage(11000/3)

6351 V

15 PTsecondaryvoltage(110/3)

63.5 V

16 PTratio

100

17 ContinuousNeg.Seq.Capability(Percentageofratedcurent)

10 %

2
18 Thermalcapability(I2 t)

20 Sec

19 Transformerimpedance

12.5 %

20 FaultCurrent

31.5 KA

21 TransformerSecondaryVoltage

34.5 KV

22

HVCTratio

20 TransformerMVA

ELECTRICALMACHINESENGINEERING
Prepared
Checked
Approved
SUNITA
SUNITA
SKPANDEY

1750
90 MVA

Date:13.11.10
Rev00

HYDERABAD

RELAY SETTING CALCULATIONS FOR RELAY


(MICOM
P343))
(
PROJECT: 67.5 MW STG for RINL VSP

ListofProtections(PartofMICOMP343)
1

DifferentialProtection(87G)

StatorEarthfaultprotection(95%)(64G1)

StatorEarthfaultprotection(100%)(64G2)

Poleslippingprotection(78G)

DeadMachineProtection(50G)

LowforwardpowerProtection(37G)

LossofExcitationwithU/Vprotection(40G)

LossofExcitationwithoutU/Vprotection(27/40G)

GeneratorOvercurrentprotection(51.1G)

10

U d f
Underfrequencyprotection(Stagel)(81.1G)
t ti (St
l) (81 1G)

11

Underfrequencyprotection(Stage2)(81.2G)

12

Overfrequencyprotection(Stagel)(81.3G)

13

Overfrequencyprotection(Stage2)(81.4G)

14

GeneratorNegativeSequenceProtection(Stage1)(46G1)

15

GeneratorNegativeSequenceProtection(Stage2)(46G2)

16

Gen.OvervoltageProtection(stagel)(59.1G)

17

Gen.OvervoltageProtection(stage2)(59.2G)

18

UndervoltageProtection(27G)

19

ReversepowerProtection(32G)

20

BackupImpedanceprotection(21G)

21

Voltage Restrained over current protection(51 2G)


VoltageRestrainedovercurrentprotection(51.2G)

22

LocalBreakerBackupProtection(50LBB)

ListofProtections(PartofMICOMP633)
23

Generatortransformeroveralldifferentialprotection(87OA)

ListofProtections(PartofMICOMP632)
24

Generatortransformerdifferentailprotection(87GT)

25

RestrictedE/Fprotection(64RT)

26

StandbyE/Fprotection(64ST)

27

Overfluxingrelayoperated(99GT)

PartofMicomP141
28

df/dtprotection(81R)

PartofMX3IGP2A
29

RotorFirstEarthFaultprotection(Stagel)(64F1)

30

RotorFirstEarthFaultprotection(Stage2)(64F2)

TG52780
REV00

HYDERABAD

RELAY SETTING CALCULATIONS FOR RELAY (MICOM P343)


PROJECT:67.5MW STG FOR RINL VSP

TG52780
REV00

1.0 Over voltage protection: Stage -I ( 59.1)


This protection is provided to change regulation of AVR from auto to Manual in case Auto
channel of AVR fails.
Type of relay

: Part of MICOM P343

Rated voltage of generator

11 KV

The percentage of higher voltage than rated cont.voltage for I Stage


of over voltage protection for changeover from auto to manual
Hence, setting shall be (110 + x) % of rated Voltage
PT Secondary rated voltage for setting
Time delay recommended =

5%
115 %
126.5 V
0.5 Sec

Action : Alarm and change regulation from Auto to Manual..


2.0 Over voltage Protection : Stage II ( 59 .2)
This protection is provided to protect generator against over voltages
Type of relay : Part of MICOM P343
This protection shall be chosen at 10 % higher than stage -I
Over voltage setting =

125 %

PT Secondary voltage =

110 V

This time delay shall not be too long to avoid strain on the machine
Recommended time delay =
Relay setting =

2 sec
137.5 V

Action : To trip 86C1 & 86C2


3.0 Reverse power protection ( 32R)
This protection is provided to protect generator against motoring
Type of relay : Part of MICOM P343
Rated power in terms of signals to the relay ={(KV/Root3)/PT ratio }*{ Rated Current/CT Ratio}

-56.25 W

Relay shall be able to sense 0.5% of rated power.


Relay Setting

-0.28 W

Min. setting available

-0.3 W

Setting recommended

-0.3 W

Time delay recommended

1 sec

Delayed drop off: 0 sec, Compensating angle: 0 Deg.


Action : To trip 86C1 & 86C2
4.0 Low Forward power protection ( 32F)
This protection is provided to protect generator against motoring
Type of relay : Part of MICOM P343
Rated power in terms of signals to the relay =KV/Root3 * Rated Current/CT Ratio

56.25 W

Relay shall be able to sense 0.5% of rated power.


Relay Setting

0.28 W

Min. setting available

0.3 W

Setting recommended

0.3 W

Time delay recommended

1.5 sec

Delayed drop off: 0 sec, Compensating angle: 0 Deg.


Action : To trip 86A1 & 86A2

G:\RELAY_SETTING\PROJECTS_09&10\RINLVSPREV00.xls

RELAY SETTING CALCULATIONS FOR RELAY (MICOM P343)


PROJECT:67.5MW STG FOR RINL VSP

HYDERABAD

TG52780
REV00

5.0 Under voltage relay : ( 27G)


This protection is provided to protect the generator against operation at
very low voltage.
Type of relay : Part of MICOM P343
Rated voltage of generator =
Allowed voltage dip on the rated voltage of generator
Under voltage setting recommended lower than minimum operating voltage

11 KV
5%
5%

Percentage setting recommended :

90 %

Voltage setting recommended : (line to line)

99 V

Time delay recommended

3 Sec

Action : To trip 86C1 & 86C2


6.0 Under frequency protection : ( 81.1 & 81.2 )
This protection is provided to protect the generator against operation at low frequencies .
Type of relay : Part of MICOM P343
Alarm settings are to be made at 0.5 Hz intervals to alert the operator for corrective
action and load management. Hence, following settings are recommended.
Stage -1: Freqency setting :
Time delay

48.5 Hz
2 Sec

Action : Alarm
Stage -2: Freqency setting :
Time delay :

47 5 Hz
47.5
1.5 Sec

Action : To trip 86B1 & 86B2


7.0 OVER FREQUENCY PROTECTION ( 81.3G & 81.4G)
This protects the machine against over speeding.
Type of relay : MICOM P343
Stage I : for Alarm.
Frequency Setting :
Time delay

51 Hz
1 Sec

Stage II : for trip.


Frequency Setting :
Time delay

51.5 Hz
1.5 Sec

Action : To trip 86B1 & 86 B2


8.0 Negative Sequence Current Protection: (46 G1 & 46G2)
This protection is provided to protect the generator against unbalanced loads and
as a backup for uncleared unsymmetrical faults.
Type of relay : Part of MICOM P343 relay
Stage-1 : Alarm
Rated current of generator/CT primary current

0.8857 Amps

I2s capability of generator = 10 % of rated current


Alarm threshold ( I2>)

0.0886 p.u

Recommended alarm threshold

0.0886 p.u

Recommended time setting for alarm

20 sec

Time Delay

20 sec

Stage-2 : Trip
Trip threshold setting I2>> (little higher than alarm threshold)

G:\RELAY_SETTING\PROJECTS_09&10\RINLVSPREV00.xls

0.09

RELAY SETTING CALCULATIONS FOR RELAY (MICOM P343)


PROJECT:67.5MW STG FOR RINL VSP

HYDERABAD

TG52780
REV00

Thermal capability constant (heating) K

15.69 sec

Hence setting K

15.69 sec

Thermal capacity constant (Cooling) : Kreset = Same as K


Maximum operating time

500 Sec

Minimum operating time

3 Sec

Action : To trip 86B1 & 86B2


9 Generator Differential Protection : ( 87 G)
This protection is provided to protect the generator against phase
to phase faults in generator.
Type of relay : Part of relay MICOM P343
The basic differential current setting defines the pickup setting of
differential protection for internal faults. The lowest possible value should
be chosen to enable it to detect the worst case faults.
Hence , Recommended Pick Up IS1:
Threshold for increase bias IS2
Bias Slope K1

0.05 In
1.2 In
0%

Bias Slope K2

10 %

Time Delay :

0.1 Sec

Action : To trip 86A1 & 86A2


10 Stator E/F relay ( 0 to 95 % ) (64G1) :
This protection is provided to protect the generator against earth faults
in generator & 11 KV system.
Type of relay : Part of MICOM P343 relay
PickUp
Time Delay

:(Typical)
:

7V
1 Sec

Note: - The voltage relay may have to be co-ordinated with system relaying for system ground
faults. System phase to ground faults will be induced zero sequence voltages at the generator
due to capacitive coupling between the windings of the Unit Transformer. This induced voltage
will appear on the secondary of the grounding distribution transformer and may cause
operation of Zero Sequence voltage relay. Time delay shall be coordinated with 33KV
system.Voltage across secondary winding shall be measured and setting shall be done 1 V
higher than measured value.
64G2
Third harmonics U/V threshold setting ( VN3H < ) must be set below the 3 rd hormonics
voltage present during normal operation and Third harmonics O/V threshold setting ( VN3H >
) must be set above the 3rd harmonics voltage present during normal operation
Third Harmonic U/V ( VN3H < ) =

0.5 V

Time Delay

1 Sec

Third Harmonic O/V ( VN3H > ) (Typical)

1V

Time Delay

1 Sec

These settings are typical. Voltage shall be measured during normal operation.
Voltage setting may be adopted accordingly.
Action : To trip 86A1 & 86A2
11 Rotor earth fault relay (64R)
Type of relay :

MX3IGP2A

G:\RELAY_SETTING\PROJECTS_09&10\RINLVSPREV00.xls

RELAY SETTING CALCULATIONS FOR RELAY (MICOM P343)


PROJECT:67.5MW STG FOR RINL VSP

HYDERABAD

Stage I Setting:
Time Delay

TG52780
REV00
4 Kohms

10 Sec

Action: Alarm
Stage II Setting

200 ohms

Time Delay

10 Sec

Action : To trip 86A1 & 86A2


12 Protection Against Loss of Excitation (40 G)
This protection is provided to prevent generator running as asynchronous generator.
Type of Relay : Part of MICOM P343.
Gen.Impedance: Zbase.pri =((KV)/MVA)
Gen.Impedance refered to secondary : Zbase.sec = (Zbase.pri)x(CTR/PTR)
Actual D axis reactance = Xd' p.u x Zbase.sec
Mho Offset Xa =Xd'/2

1.43 Ohms
71.704 Ohms
16.22 Ohms
8.11

Nearest setting available above the required value


Hence setting Xa

8 Ohms
8 Ohms

Gen. Syn. Reactance in Sec. Ohms = Xd p.u x Zbase.sec


Mho diameter = Xd

154.81 Ohms
154.81

Recommended Setting for Xd

154.81

Delayed pickup time

2 sec

Delayed drop off time .

2 sec

Settings:Xa

8 Ohms

Xd = Xb

155 Ohms

Delayed pick-up time

1 sec

Delayed Drop off time

2 sec

Action : To trip 86A1 & 86A2


13 Protection Against Loss of Excitation With Under Voltage (27/40 G)
Type of Relay : Part of MICOM P343.
Xa
Xd = Xb

8 Ohms
77 Ohms

Delayed pick-up time

2 sec

Delayed Drop off time

2 sec

Action : To trip 86B1 & 86B2


14 Gen. Breaker failure Protection (50 LBB)
Type of Relay :Part of MICOM P343
Setting :
Phase current setting
Time Delay

0.22 A
200 msec

Action : To open 33KV bus coupler breaker & trip any other feeders which feeds to 33KV bus
15 OVER CURRENT PROTECTION(51.1G)
This protection is used to protect the Generator against over currents.
Type of Relay : Part of MICOM P343
Current setting
Time setting

0.930 A
:

G:\RELAY_SETTING\PROJECTS_09&10\RINLVSPREV00.xls

10 Sec

RELAY SETTING CALCULATIONS FOR RELAY (MICOM P343)


PROJECT:67.5MW STG FOR RINL VSP

HYDERABAD

TG52780
REV00

Action : Alarm
16 Pole slipping protection (78G)
Type of Relay :Part of MICOM P343
D-Axis transient Reactance ( Xd )

0.2262 p.u

Base Power

84.375 MVA

Base voltage

11.000 KV

Base Impedance
Transformer Reactance (XT)
System Impedance
System Impedance (11KV Side)
X1 = System Impedance * Base Impedance
ZA = (Xt +X1)
ZB = 2x Xd'

1.434
0.125
0.632
0.064
0.092
0.217
0.4524

Zc is set to 90% of transformer reactance


Zc

Ohms
Ohms
Ohms
Ohms
Ohms
Ohms
Ohms

31.5 KA
0.161 Ohms

Lens angle
Blinder Angle

120 Deg
75 Deg

T1 & T2 are set to 15ms and system impedance angle is set to 80 deg
Action : To trip 86A1 & 86A2
17 Phase Impedance Protection (21G)
Type of Relay :Part of MICOM P343
Generator full load current

4429 Amps

Allowing for a 10% overload current on the generator


CT secondary current
Generator full load impedance

0.97 Amps
112.90 Ohms

The relay is to be set to operate at 70% of rated load impedance


Zs

79.03 Ohms

Nearest setting available

79 Ohms

Hence setting for Zs

79 Ohms

Time delay
Action : To trip 86C2

3 sec

18 Voltage Restrained Overcurrent Protection


Type of Relay : MICOM P343
The current setting is chosen such that neither false tripping nor false signals can occur
during normal operation and yet minimum fault current is detected
Function recommended: Voltage Restrained
Settings: Vs1 = 80V, Vs2 = 35V
Characteristic recommended: Standard inverse.
t = [ (0.14)/ { I/Is) ^ 0.02 1 ) }) * TMS
where I = measured current , Is = Current threshold setting , TMS = Time multiplier setting
If the relay has to operate in 3 Sec when fault current is 2 times rated current,
Gen. rated current in CT sec.

0.89 In

The settings recommended are


I>= 0.8 In ( Where In = 1 A )
Time multiplier (TMS) = 0.3

0.3

0.4

G:\RELAY_SETTING\PROJECTS_09&10\RINLVSPREV00.xls

HYDERABAD

RELAY SETTING CALCULATIONS FOR RELAY (MICOM P343)


PROJECT:67.5MW STG FOR RINL VSP

TG52780
REV00

These setting are required to be coordinated with upstream breaker by customer.


Action : To trip 86C1
19 GT Restriced Earth Fault Protection (64GT)
Type of Relay : Micom P632
Idiff>
Idiff>>>
m1
m2
Action : To trip 86A1

0.2 Iref
10 Iref
0.2
1.5

20 Standby Earth fault protection (64ST)


Type of Relay : Micom P632
Threshold can be more sensistive to take care of faults near to star point. Normal recommended
value is 10% of the rated full load current

HV side rated current


CT ratio
Pick up setting (Full load current *0.2)/(Pickup to drop off ratio)
Pickup setting in Secondary
Fault current in HV
Opearting time at TMS '1'
PSM
TMS
Action : To trip 86A1
21 Overfluxing Protection (99G1 & 99G2)
Type of Relay : MICOM P632
PT secondary voltage: 110
Rated Frequency
V/F
5 % tolerance in voltage at rated frequency is allowed.
Stage-1-Alarm
Relay Setting Recommended
Relay Setting
Time Delay
Stage-2-Trip
Trip setting
Time Delay
Action: To trip 86A1

1506.18
1750
317
0.181
2642
8.33
0.309

110 V
50 Hz

2.46 V/Hz
2.46
1 Sec
2.53 V/Hz
1 Sec

22 Dead Machine Protection (50G)


This protects the machine against inadvartent closing of the Gen.CB.
Type of Relay :Part of MICOM P343
Rated current of Gen. /CT Primary current
Setting chosen = 1.2 In
Min setting available
Min. Voltage setting available
Setting chosen
Pick Up Delay Time (tpu)
Drop-Off Time Delay (tdo)
Action: To trip 86A1 & 86A2
23 Generator Transformer differential protection (87GT)
Type of Relay : Part of MICOM P632
Power

G:\RELAY_SETTING\PROJECTS_09&10\RINLVSPREV00.xls

0.8857
1.063
1.06 A
30 V
77 V
Instantenous
0.5 sec

90 MVA

HYDERABAD

RELAY SETTING CALCULATIONS FOR RELAY (MICOM P343)


PROJECT:67.5MW STG FOR RINL VSP

HV Side Voltage

TG52780
REV00
34.5 KV

LV SideVoltage
HV CT ratio
LV CT Ratio
% Impedance
Tap +10% at the rate of

11 KV
1750
5000
12.5 %
Available

At normal condition current in HV Bias current (Winding A)


Full Load primary current (MVA/(1.732 * KV)
Equivalent current in CT secondary
Required ratio compensation

1,506.18 Amps
0.86 Amps
1.16

At normal condition current in LV Bias current (Winding B)


Full Load primary current (MVA/(1.732 * KV)
Equivalent current in CT secondary
Required ratio compensation

4429 Amps
0.89
1.13

At -10% Tap condition current in HV Bias circuit


Rated voltage at -10% tap
Full Load primary current (MVA/(1.732 * KV)
Equivalent current in CT secondary
With the ratio correction the current at the relay Bias terminal
Hence Differential current
Bias current (I1 + I2)/2
Operating current of relay will be (Is + (Bias setting *Bias Current)

31.05 KV
1674 Amps
0.956
1.11
0.11
1.06
0.411

Differential current at worst tap condition not be more than 90% of operating current for better
stability
Differential current at worst tap
Operating current at worst tap
This is less than 30% od operating current
Hence Bias setting of m1
m2
At +10% Tap condition current in HV Bias circuit
Rated voltage at +10% tap
Full Load primary current (MVA/(1.732 * KV)
Equivalent current in CT secondary
With the ratio correction the current at the relay Bias terminal
Hence Differential current
Bias current (I1 + I2)/2
Operating current of relay will be (Is + (Bias setting *Bias Current)

0.11
0.411

20%
80%

37.95
1369
0.782
0.909
0.091
0.955
0.391

Differential current at worst tap condition should not be more than 90% of operating current for
better stability
Differential current at worst tap
Operating current at worst tap
This is less than 25% of operating current
Hence Bias setting of m1
m2
Action: To trip 86A1
24 Overall differential protection (87OA)
Type of Relay : Part of MICOM P633
Power
HV Side Voltage
LV SideVoltage

G:\RELAY_SETTING\PROJECTS_09&10\RINLVSPREV00.xls

0.091
0.391

20%
80%

90 MVA
34.5 KV
11 KV

HYDERABAD

RELAY SETTING CALCULATIONS FOR RELAY (MICOM P343)


PROJECT:67.5MW STG FOR RINL VSP

TG52780
REV00

HV CT ratio
LV CT Ratio
% Impedance
Tap +10% at the rate of

1750
5000
12.5 %
Available

At normal condition current in HV Bias current (Winding A)


Full Load primary current (MVA/(1.732 * KV)
Equivalent current in CT secondary
Required ratio compensation

1,506.18 Amps
0.86 Amps
1.16

At normal condition current in LV Bias current (Winding B)


Full Load primary current (MVA/(1.732 * KV)
Equivalent current in CT secondary
Required ratio compensation

4429 Amps
0.89
1.13

At normal condition current in LV Bias current (Winding C)


Full Load primary current (MVA/(1.732 * KV)
Equivalent current in CT secondary
Required ratio compensation

4429 Amps
0.89
1.13

At -10% Tap condition current in HV Bias circuit


Rated voltage at -10% tap
Full Load primary current (MVA/(1.732 * KV)
Equivalent current in CT secondary
With the ratio correction the current at the relay Bias terminal
Hence Differential current
rrent (I1 + I2)/2
Bias c
current
Operating current of relay will be (Is + (Bias setting *Bias Current)
Diffential current at worst tap condition not be more than 90% of operating current for better stab

31.05 KV
1674 Amps
0.956
1.11
0.11
1 06
1.06
0.411

Differential current at worst tap


Operating current at worst tap

0.11
0.411

This is less than 30% od operating current


Hence Bias setting of m1
m2
At +10% Tap condition current in HV Bias circuit
Rated voltage at +10% tap
Full Load primary current (MVA/(1.732 * KV)
Equivalent current in CT secondary
With the ratio correction the current at the relay Bias terminal
Hence Differential current
Bias current (I1 + I2)/2
Operating current of relay will be (Is + (Bias setting *Bias Current)

20%
80%

37.95
1369
0.782
0.909
0.091
0.955
0.391

Differential current at worst tap condition should not be more than 90% of operating current for
better stability
Differential current at worst tap
Operating current at worst tap
This is less than 25% of operating current
Hence Bias setting of m1
m2
Action: To trip 86A1
25 df/dt protection
Part of Micom P141
Thesesettings are required to be coordinated with upstream breaker by customer and hence,
settings for df/dt protection are not provided in this document.

G:\RELAY_SETTING\PROJECTS_09&10\RINLVSPREV00.xls