The Lighting Handbook

Seite 1

1st edition, July 2004

24.06.2004

10:21 Uhr

The Lighting Handbook

00_INHALTSVER_uk.qxd

Seite 2

00_INHALTSVER_uk.qxd

24.06.2004

10:21 Uhr

Chapter 1

Lighting fundamentals
Chapter 2

Recommended values for indoor and outdoor lighting


NEW: Based on the new European standards
Chapter 3

Luminaires
Chapter 4

Lamps and ballasts


Chapter 5

Lighting and room management,


Emergency lighting
Chapter 6

Quickplan Calculating luminaire quantities


Chapter 7

Lighting refurbishment
Chapter 8

Economic efficiency calculation


Chapter 9

The Lighting Handbook

Technical information
Chapter 10

Notes

Seite 1

00_INHALTSVER_uk.qxd

24.06.2004

10:21 Uhr

Seite 2

01_LICHTTECH_uk.qxd

24.06.2004

8:43 Uhr

Chapter 1

Lighting fundamentals
What is light? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Basic parameters used in lighting . . . . . . . . . . . . . . . .


Luminous flux . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Luminous intensity . . . . . . . . . . . . . . . . . . . . . . . . .
Illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Luminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General quality criteria for lighting . . . . . . . . . . . . . . . .
The right light traditional and new quality criteria . .
Illuminance definition of terminology . . . . . . . . . . .
Glare glare limitation . . . . . . . . . . . . . . . . . . . . . .
Lighting technology . . . . . . . . . . . . . . . . . . . . . . . . . .
Light colour . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Colour rendition . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

45
4
5
5
5
67
6
67
7
89
10
10

Seite 1

01_LICHTTECH_uk.qxd

24.06.2004

8:43 Uhr

Seite 2

01_LICHTTECH_uk.qxd

24.06.2004

8:43 Uhr

What is light?
Light is that part of the electromagnetic spectrum that is perceived
by our eyes.

What does the human eye see?

What is light?
Wavelength [m]
-10

10

Gamma rays
X-rays

1.0

Ultraviolet

0.8

Visible light
10-5

Microwaves
Television, VSW
Medium waves
105

Night

Day

0.6
0.4

Infrared

100

Relative spectral
brightness perception

0.2
350 450 550 650 750
Wavelength [nm]
Wavelength [m]

Radio waves

The Lighting Handbook

By day we see in colour, while at night we can only see in shades


of grey.

Chapter 1 / 3

Seite 3

01_LICHTTECH_uk.qxd

24.06.2004

8:43 Uhr

Basic parameters used in lighting


Luminous flux Luminous intensity Illuminance Luminance
Luminous flux

I=

E=

Lumen [lm]
Luminous intensity I

Illuminance E

Lux [lm/m2]=[lx]

Candela [lm/sr]=[cd]
Luminance L
L=

I
A

L=

[lm/(sr*m2 )]=[cd/m2 ]

Luminous flux

4 / Chapter 1

Abbreviation:
Unit:

lm

phi
lumen

The Lighting Handbook

The luminous flux describes


the quantity of light emitted
by a light source.
The luminous efficiency
is the ratio of the luminous
flux to the electrical power
consumed (lm/W).
It is a measure of a lamps
economic efficiency.

Seite 4

01_LICHTTECH_uk.qxd

24.06.2004

8:43 Uhr

Luminous intensity
The luminous intensity
describes the quantity of light
that is radiated in a particular
direction.
This is a useful measurement
for directive lighting elements
such as reflectors. It is represented by the luminous intensity distribution curve (LDC).

Abbreviation:
Unit:

cd

candela

Abbreviation:
Unit:

E
lx

lux

Abbreviation:
Unit:

L
cd/m2

Illuminance
Illuminance describes the
quantity of luminous flux falling
on a surface. It decreases by
the square of the distance
(inverse square law). Relevant
standards specify the required
illuminance (e.g. EN 12464
Lighting of indoor workplaces).
Illuminance:
(lm)
E(lx) = luminous flux
area (m2)

Luminance

The Lighting Handbook

The luminance is the only


basic lighting parameter that
is perceived by the eye.
It specifies the brightness of
a surface and is essentially
dependent on its reflectance
(finish and colour).

Chapter 1 / 5

Seite 5

01_LICHTTECH_uk.qxd

24.06.2004

8:43 Uhr

General quality criteria for lighting


The right light traditional and new
quality criteria
T
R
A
D
I
T
I
O
N
A
L

N
E
W

Harmonious
brightness distribution
Sufficient
illumination level

Glare
limitation
Avoidance
of reflections

Good modelling
Correct light colour
Appropriate
colour rendition

Quality criteria
Changing
lighting situations

Energy efficiency
Daylight integration

Personal
control

Light as an interior
design element

Illuminance definition of terminology


Each term corresponds to the new European standards
(see Chapter 2 / 2).
Illuminance maintenance value Em: Value that the illuminance
level must not fall below in the visual task area.
Visual task area: Illuminance levels are specified for specific
visual tasks and are designed for the area in which these may
take place. If the precise location is not known, then the whole
room or a specific working area is used to define it. The visual
task area may be a horizontal, vertical or inclined plane.

Maintenance factor: The initial value multiplied by the maintenance factor gives the illuminance maintenance value. The maintenance factor accounts for the reduction in luminous flux from
lamps, luminaires and room surfaces in the installation, and can
be determined on a case-by-case basis.
The maintenance schedule (the cleaning and maintenance
intervals for the lamps and installation) must be documented.
See also the chapter on Economic efficiency calculation.

6 / Chapter 1

The Lighting Handbook

Area immediately surrounding the visual task area: Here


the illuminance may be one level lower than in the visual task
area (e.g. 300 lx to 500 lx).

Seite 6

01_LICHTTECH_uk.qxd

24.06.2004

8:43 Uhr

relative illuminance (%)


initial
value

150
125
100

maintenance
value

75
50
25

operating time
Maintenance value = maintenance factor x initial value

Glare glare limitation

luminaires with limited


luminance levels
blinds

cause

The Lighting Handbook

loss of concentration
more frequent mistakes
fatigue

reflective surfaces
incorrect luminaire arrangement
incorrect workstation position

effect

luminaires without glare


control
very bright surfaces

Reflected glare

loss of concentration
more frequent mistakes
fatigue

remedy

Direct glare

matching luminaire to
workstation (layout)
indirect lighting
matt surfaces
Chapter 1 / 7

Seite 7

01_LICHTTECH_uk.qxd

24.06.2004

8:43 Uhr

Lighting technology
Under the new European standard for interior workplace lighting
EN 12464, (psychological) glare is assessed by the unified glare
rating method (UGR), which is based on a formula for glare.
It takes account of all the luminaires in a system contributing to
the sensation of glare. UGR tables derived from this formula are
provided by the manufacturers for glare rating.
The Quickplan tables in Chapter 6 and the lighting catalogues
contain reference values for specific room sizes.

UGR = 8 log 0,25


Lb
(1)

L2 
P2
(2)

The UGR method takes account of all the luminaires in the


system that contribute to the glare sensation (2) as well as the
brightness of walls and ceilings (1). It produces a UGR index.
The two methods the one set out in DIN 5035 and the one
defined in EN 12464 produce comparable results.

16
19
22
25
28

Technical drawing
Reading, writing, training, meetings,
computer-based work
Craft and light industries
Heavy industry
Railway platforms, foyers

8 / Chapter 1

The Lighting Handbook

UGR limits (UGRL), that must not be exceeded:

Seite 8

8:43 Uhr

The Lighting Handbook

1
45

55

65

 = 85

 = 45

75

8 103

3 4 5 6 8 104
2
Luminance L in cd/m2

3 4

8
6
4
3

a
hs

24.06.2004

85

Quality class
for nominal illuminance (lx)
A
1000 750 500
<300
1
2000 1500 1000 750 500 <300
2
2000 1000 500 <300
3
2000 1000 500 <300

UGRL

13

16

19

22

25

28

01_LICHTTECH_uk.qxd

The previously used luminance limiting curve method defined in


DIN 5035 assesses the mean luminance of the luminaires over
a beam angle of 45 to 85. The new European standard sets
UGR = 19 as the maximum permissible value for offices, which
is equivalent to the luminance limiting curve for 500 lx in Quality
class 1.
Chapter 1 / 9

Seite 9

01_LICHTTECH_uk.qxd

24.06.2004

8:43 Uhr

Light colour
The light colour describes the colour appearance of the light.
Colour temperature

Appearance

ww

up to 3,300 K

reddish

Association
warm

nw

3,300 K 5,300 K

white

intermediate

tw

above 5,300 K

blue-ish

cool

The light colour sets the underlying mood of the room!

Colour rendition
Colour rendition index Ra 90 8089 7079 6069 4059 2039
Daylight
Incandescent lamp
Compact fluorescent lamp
Fluorescent lamp
Mercury vapour highpressure lamp
Metal halide lamp
Sodium vapour highpressure lamp

Application examples:
Ra 90: colour inspection
Ra 8089: offices
Ra 7079: electronics industry

Ra 6069: assembly work


Ra 4059: fabrication shop
Ra 2039: warehouses

Display format on fluorescent lamps


Example 840: 8

40

Ra 80

10 / Chapter 1

The Lighting Handbook

Colour temperature 4,000 K (nw)

Seite 10

02_INNENRAUM_uk.qxd

24.06.2004

8:45 Uhr

Chapter 2

Standard values for indoor and outdoor lighting


Standard values for lighting of indoor and
outdoor workplaces and sports facility lighting . . . . . . .
Indoor workplaces
Traffic zones and general areas inside buildings . . . .
Industrial activities and crafts . . . . . . . . . . . . . . . . .
Offices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Retail premises . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Places of public assembly . . . . . . . . . . . . . . . . . . . .
Educational premises . . . . . . . . . . . . . . . . . . . . . . .
Health care premises . . . . . . . . . . . . . . . . . . . . . . .
Transportational areas . . . . . . . . . . . . . . . . . . . . . . .
Sports facilities . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Outdoor workplaces
General circulation areas . . . . . . . . . . . . . . . . . . . .
Airports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Building sites . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Canals, locks and harbours . . . . . . . . . . . . . . . . . . .
Farms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fuel filling service stations . . . . . . . . . . . . . . . . . . .
Industrial sites and storage areas . . . . . . . . . . . . . .
Off-shore gas and oil structures . . . . . . . . . . . . . . .
Parking lots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Petrochemical and other hazardous industries . . . . .
Power, electricity, gas and heat plants . . . . . . . . . . .
Railway areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Saw mills . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipyards and docks . . . . . . . . . . . . . . . . . . . . . . . .
Water and sewage plants . . . . . . . . . . . . . . . . . . . .

3
37
7
7
8
89
9 10
10 11
11 12
13
13
13
13
13
13
14
14
14
14 15
15
15
15
16
16

Seite 1

02_INNENRAUM_uk.qxd

24.06.2004

8:45 Uhr

Standard values for lighting of indoor and


outdoor workplaces and sports facility lighting
Em gives the illuminance maintenance values specified in the
European standards which partially or completely replace
national standards (e.g. DIN 5035, Austrian standard O 1040,
Swiss lighting standard SLG 8912, DIN 67526).
Lighting of indoor workplaces, EN 12464-1 (April 2003)
Lighting of outdoorwork places, pr EN 12464-2
Sports facility lighting, EN 12193 (September 1999)
(see also Definition of terminology, Chapter 1 / 6)
Illuminance levels must not fall below the Em maintenance
values in the visual task area. If the precise location is not
known, the limit should be applied to the whole room or a
specific working area.
Example for an
office task
area:

task
height = 0.75 m

use

area

r flo

or-a

rea

1.00 m
The maintenance factors
can be determined on a case-by-case
basis from the manufacturers data (see also Chapter 8).

The maintenance factors and schedules for Zumtobel Staff


luminaires are given in the Quickplan tables (Chapter 6).
Where no individual maintenance data is available, the following
values are recommended as reference maintenance factors for
modern technology and three-yearly maintenance: 0.67 in a
clean atmosphere, and 0.50 in very dirty environments.

UGRL is the upper limit for direct glare. The UGR value calculated
in the design process must lie below this (the Quickplan tables
give the UGR figure for the luminaire used in a medium-size
reference room).
Ra is the lower limit for the colour rendition index. The Ra of the
selected lamp must be equal to or greater than this value.

The Lighting Handbook

EN 12464 specifies that the lighting designer must document


the maintenance factor and maintenance schedule.

Seite 2

02_INNENRAUM_uk.qxd

24.06.2004

Type of interior,
task or activity

Em

8:45 Uhr

UGRL

Ra

Traffic zones and general areas inside buildings


Traffic zones
Circulation areas and corridors
Stairs, escalators, travolators
Loading ramps/bays
Rest, sanitation and first aid rooms
Canteens, pantries
Rest rooms
Rooms for physical exercise
Cloakrooms, washrooms, bathrooms, toilets
Sick bay
Rooms for medical attention
Control rooms
Plant rooms, switch gear rooms
Telex, post room, switchboard
Store rooms, cold stores
Store and stockrooms
Dispatch packing handling areas
Storage rack areas
Gangways: unmanned
Gangways: manned
Control stations

100
150
150

28
25
25

40
40
40

200
100
300
200
500
500

22
22
22
25
19
16

80
80
80
80
80
90

200
500

25
19

60
80

100
300

25
25

60
60

20
150
150

22
22

40
60
60

200
50
200
200

25

25
25

80
40
80
80

300
500

22
22

80
80

50

28

20

200
300
300

28
25
25

40
80
80

50
300

28
25

20
80

300

25

80

750

19

80

The Lighting Handbook

Industrial activities and crafts


Agriculture
Loading and operating of goods, handling
equipment and machinery
Buildings for livestock
Sick animal pens; calving stalls
Feed preparation; dairy; utensil washing
Bakeries
Preparation and baking
Finishing, glazing, decorating
Cement, cement goods, concrete, bricks
Drying
Preparation of materials; work on kilns
and mixers
General machine work
Rough forms
Ceramics, tiles, glass, glassware
Drying
Preparation, general machine work
Enamelling, rolling, pressing, shaping
simple parts, glazing, glass blowing
Grinding, engraving, glass polishing,
shaping precision parts, manufacture
of glass instruments

Chapter 2 / 3

Seite 3

24.06.2004

Type of interior,
task or activity
Grinding of optical glass, crystal, hand
grinding and engraving
Precision work e.g. decorative grinding,
hand painting
Manufacture of synthetic precious stones
Chemical, plastics and rubber industry
Remote-operated processing installations
Processing installations with limited manual
intervention
Constantly manned work places in processing
installations
Precision measuring rooms, laboratories
Pharmaceutical production
Tyre production
Colour inspection
Cutting, finishing, inspection
Electrical industry
Cable and wire manufacture
Winding:
large coils
medium-sized coils
small coils
Coil impregnating
Galvanising
Assembly work:
rough e.g. large transformers
medium e.g. switchboards
fine e.g. telephones
precision e.g. measuring equipment
Electronic workshops, testing, adjusting
Food stuffs and luxury food industry
Work places and zones in
breweries, malting floor
for washing, barrel filling, cleaning, sieving,
peeling
cooking in preserve and chocolate factories
work places and zones in sugar factories
for drying and fermenting raw tobacco,
fermentation cellar
Sorting and washing of products, milling,
mixing, packing
Work places and critical zones in slaughter
houses, butchers, dairies mills, on filtering
floor in sugar refineries
Cutting and sorting of fruit and vegetables
Manufacture of delicatessen foods, kitchen
work, manufacture of cigars and cigarettes
Inspection of glasses and bottles, product
control, trimming, sorting, decoration

4 / Chapter 2

8:45 Uhr

Em

UGRL

Ra

750

16

80

1000
1500

16
16

90
90

50

20

150

28

40

300
500
500
500
1000
750

25
19
22
22
16
19

80
80
80
80
90
80

300

25

80

300
500
750
300
300

25
22
19
25
25

80
80
80
80
80

300
500
750
1000
1500

25
22
19
16
16

80
80
80
80
80

200

25

80

300

25

80

500
300

25
25

80
80

500

22

80

500

22

80

The Lighting Handbook

02_INNENRAUM_uk.qxd

Seite 4

02_INNENRAUM_uk.qxd

24.06.2004

The Lighting Handbook

Type of interior,
task or activity
Laboratories
Colour inspection
Foundries and metal casting
Man-size underfloor tunnels, cellars, etc.
Platforms
Sand preparation
Dressing room
Work places at cupola and mixer
Casting bay
Shake out areas
Machine moulding
Hand and core moulding
Die casting
Model building
Hairdressers
Hairdressing
Jewellery manufacturing
Working with precious stones
Manufacture of jewellery
Watch making (manual)
Watch making (automatic)
Laundries and dry cleaning
Goods in, marking and sorting
Washing and dry cleaning
Ironing, pressing
Inspection and repairs
Leather and leather goods
Work on vats, barrels, pits
Fleshing, skiving, rubbing, tumbling of skins
Saddlery work, shoe manufacture: stitching,
sewing, polishing, shaping, cutting, punching
Sorting
Leather dyeing (machine)
Quality control
Colour inspection
Shoe making
Glove making
Metal working and processing
Open die forging
Drop forging
Welding
Rough and average machining:
tolerances 0.1 mm
Precision machining; grinding:
tolerances < 0.1 mm
Scribing; inspection
Wire and pipe drawing shops; cold forming
Plate machining: thickness 5 mm

8:45 Uhr

UGRL

Ra

500
1000

19
16

80
90

50
100
200
200
200
200
200
200
300
300
500

25
25
25
25
25
25
25
25
25
22

20
40
80
80
80
80
80
80
80
80
80

500

19

90

1500
1000
1500
500

16
16
16
19

90
90
80
80

300
300
300
750

25
25
25
19

80
80
80
80

200
300

25
25

40
80

500
500
500
1000
1000
500
500

22
22
22
19
16
22
22

80
90
80
80
90
80
80

200
300
300

25
25
25

60
60
60

300

22

60

500
750
300
200

19
19
25
25

60
60
60
60

Em

Chapter 2 / 5

Seite 5

24.06.2004

Type of interior,
task or activity
Sheet metalwork: thickness < 5 mm
Tool making; cutting equipment manufacture
Assembly:
rough
medium
fine
precision
Galvanising
Surface preparation and painting
Tool, template and jig making, precision
mechanics, micromechanics
Paper and paper goods
Edge runners, pulp mills
Paper manufacture and processing, paper and
corrugating machines, cardboard manufacture
Standard bookbinding work, e.g. folding, sorting,
gluing, cutting, embossing, sewing
Power stations
Fuel supply plant
Boiler house
Machine halls
Side rooms, e.g. pump rooms, condenser
rooms etc.; switchboards (inside buildings)
Control rooms
Outdoor switch gear
Printers
Cutting, gilding, embossing, block engraving,
work on stones and platens, printing machines,
matrix making
Paper sorting and hand printing
Type setting, retouching, lithography
Colour inspection in multicoloured printing
Steel and copper engraving
Rolling mills, iron and steel works
Production plants without manual operation
Production plants with occasional manual
operation
Production plants with continuous manual
operation
Slab Store
Furnaces
Mill train; coiler; shear line
Control platforms; control panels
Test, measurement and inspection
Underfloor man-sized tunnels; belt sections;
cellars etc.
Textile manufacture and processing
Work places and zones in baths, bale opening

6 / Chapter 2

8:45 Uhr

Em

UGRL

Ra

300
750

22
19

60
60

200
300
500
750
300
750

25
25
22
19
25
25

80
80
80
80
80
80

1000

19

80

200

25

80

300

25

80

500

22

80

50
100
200

28
25

20
40
80

200
500
20

25
16

60
80
20

500
500
1000
1500
2000

19
19
19
16
16

80
80
80
90
80

50

20

150

28

40

200
50
200
300
300
500

25

25
25
22
22

80
20
20
40
80
80

50

20

200

25

60

The Lighting Handbook

02_INNENRAUM_uk.qxd

Seite 6

02_INNENRAUM_uk.qxd

24.06.2004

Type of interior,
task or activity

8:45 Uhr

UGRL

Ra

22
22
22
22
22
22
28
25
19
16
19
22

80
80
80
80
90
80
60
80
80
90
90
80

22
22
19
19
19

80
80
90
80
80

28
28
25
25
22

40
40
60
80
80

19
22
22
19

80
90
90
90

300
500
750
500
500
300
200

19
19
16
19
19
22
25

80
80
80
80
80
80
80

300
500
500

22
19
19

80
80
80

Em

Carding, washing, ironing, devilling machine work,


drawing, combing, sizing, card cutting,
pre-spinning, jute and hemp spinning
300
Spinning, plying, reeling, winding
500
Warping, weaving, braiding, knitting
500
Sewing, fine knitting, taking up stitches
750
Manual design, drawing patterns
750
Finishing, dyeing
500
Drying room
100
Automatic fabric printing
500
Burling, picking, trimming
1000
Colour inspection; fabric control
1000
Invisible mending
1500
Hat manufacturing
500
Vehicle construction
Body work and assembly
500
Painting, spraying chamber, polishing chamber 750
Painting: touch-up, inspection
1000
Upholstery manufacture (manned)
1000
Final inspection
1000
Wood working and processing
Automatic processing e.g. drying,
plywood manufacturing
50
Steam pits
150
Saw frame
300
Work at joiners bench, gluing, assembly
300
Polishing, painting, fancy joinery
750
Work on wood working machines e.g. turning,
fluting, dressing, rebating, grooving, cutting,
sawing, sinking
500
Selection of veneer woods
750
Marquetry, inlay work
750
Quality control, inspection
1000

Offices

The Lighting Handbook

Offices
Filing, copying, etc.
Writing, typing, reading, data processing
Technical drawing
CAD work stations
Conference and meeting rooms
Reception desk
Archives

Retail premises
Retail premises
Sales area
Till area
Wrapper table

Chapter 2 / 7

Seite 7

02_INNENRAUM_uk.qxd

24.06.2004

Type of interior,
task or activity

8:45 Uhr

Em

UGRL

Ra

100
200
200
300

22
25
22
22

80
80
80
80

300
500

200
300
500
100

22
22

22
22
19
25

80
80
80
80
80
80
80

300

22

80

300

22

80

200
500
500

19
19
19

80
80
80

300
75
75
75
300

25
25
25

19

20
20
20
20
80

300
300
300

19
19
19

80
80
80

Places of public assembly


General areas
Entrance halls
Cloakrooms
Lounges
Ticket offices
Restaurants and hotels
Reception/cashier desk, porters desk
Kitchen
Restaurant, dining room, function room
Self-service restaurant
Buffet
Conference rooms
Corridors
Theatres, concert halls, cinemas
Practice rooms, dressing rooms
Trade fairs, exhibition halls
General lighting
Museums
Exhibits, insensitive to light
Light sensitive exhibits
Libraries
Bookshelves
Reading area
Counters
Public car parks (indoor)
In/out ramps (during the day)
In/out ramps (at night)
Traffic lanes
Parking areas
Ticket office
Nursery school, play school
Play room
Nursery
Handicraft room
Educational buildings
Classrooms, tutorial rooms
Classroom for evening classes and adults
education
Lecture hall
Black board
Demonstration table
Art rooms
Art rooms in art schools
Technical drawing rooms

8 / Chapter 2

300

19

80

500
500
500
500
500
750
750

19
19
19
19
19
19
16

80
80
80
80
80
90
80

The Lighting Handbook

Educational premises

Seite 8

02_INNENRAUM_uk.qxd

24.06.2004

Type of interior,
task or activity
Practical rooms and laboratories
Handicraft rooms
Teaching workshop
Music practice rooms
Computer practice rooms (menu driven)
Language laboratory
Preparation rooms and workshops
Entrance halls
Circulation areas, corridors
Stairs
Student common rooms and assembly halls
Teachers rooms
Library: bookshelves
Library: reading areas
Stock rooms for teaching materials
Sports halls, gymnasiums, swimming pools
(general use)
School canteens
Kitchen

8:45 Uhr

Em

UGRL

Ra

500
500
500
300
300
300
500
200
100
150
200
300
200
500
100

19
19
19
19
19
19
22
22
25
25
22
19
19
19
25

80
80
80
80
80
80
80
80
80
80
80
80
80
80
80

300
200
500

22
22
22

80
80
80

200
200
50
200

22
22
22
22

80
80
80
80

500
300

19
19

80
80

100
300
300
1000
5
200

19
19
19
19

22

80
80
80
90
80
80

500
1000

19
19

90
90

300
1000

19

80
90

500

16

90

300
1000

19

80
90

The Lighting Handbook

Health care premises


Rooms for general use
Waiting rooms
Corridors: during the day
Corridors: during the night
Day rooms
Staff rooms
Staff office
Staff rooms
Wards, maternity wards
General lighting
Reading lighting
Simple examinations
Examination and treatment
Night lighting, observation lighting
Bathrooms and toilets for patients
Examination rooms (general)
General lighting
Examination and treatment
Eye examination rooms
General lighting
Examination of the outer eye
Reading and colour vision tests with vision
charts
Ear examination rooms
General lighting
Ear examination

Chapter 2 / 9

Seite 9

02_INNENRAUM_uk.qxd

24.06.2004

Type of interior,
task or activity
Scanner rooms
General lighting
Scanners with image enhancers and television
systems
Delivery rooms
General lighting
Examination and treatment
Treatment rooms (general)
Dialysis
Dermatology
Endoscopy rooms
Plaster rooms
Medical baths
Massage and radiotherapy
Operating areas
Pre-op and recovery rooms
Operating theatre
Operating cavity
Intensive care unit
General lighting
Simple examinations
Examination and treatment
Night watch
Dentists
General lighting
At the patient
Operating cavity
White teeth matching
Laboratories and pharmacies
General lighting
Colour inspection
Decontamination rooms
Sterilisation rooms
Disinfection rooms
Autopsy rooms and mortuaries
General lighting
Autopsy table and dissecting table

8:45 Uhr

Em

UGRL

Ra

300

19

80

50

19

80

300
1000

19
19

80
80

500
500
300
500
300
300

19
19
19
19
19
19

80
90
80
80
80
80

500
1000

19
19

90
90

100
300
1000
20

19
19
19
19

90
90
90
90

500
1000
5000
5000

19

90
90
90
90

500
1000

19
19

80
90

300
300

22
22

80
80

500
5000

19

90
90

200
150
500
500
200
200
300

22
22
19
19
22
25
19

80
80
80
80
80
80
80

Airports
Arrival and departure halls, baggage claim
areas
Connecting areas, escalators, travolators
Information desks, check-in desks
Customs and passport control desks
Waiting areas
Luggage store rooms
Security check areas

10 / Chapter 2

The Lighting Handbook

Transportational areas

Seite 10

02_INNENRAUM_uk.qxd

24.06.2004

Type of interior,
task or activity
Air traffic control tower
Testing and repair hangars
Engine test areas
Measuring areas in hangars
Railway installations
Covered platforms and passenger subways
(underpasses)
Ticket hall and concourse
Ticket and luggage offices and counters
Waiting rooms

8:45 Uhr

Em

UGRL

Ra

500
500
500
500

16
22
22
22

80
80
80
80

50
200
300
200

28
28
19
22

40
40
80
80

The Lighting Handbook

Sport facilities
The following values are based on top level competition and
correspond to EN 12193 and EN 12464
Ra value of 80 is preferable
For training purposes, a UGRL rating of 19 should bei adhered to
Aerobics
500
Archery
200
Athletics (all disciplines)
500
Badminton
750
Basketball
750
Billards
750
Boccia
300
Boules
300
Bowling
200
Bowls
500
Boxing (competition/training)
2000/300
Climbing
500
Cricket
750
Cricket nets
1500
Curling (target/playing area)
300/200
Cycling
750
Dancing (fitness)
500
Darts
200
Fencing
750
Football (indoor)
750
Gymnastics
500
Handball
750
Hockey
750
Ice hockey
750
Ice skating
750
Judo
750
Kendo/Karate
750
Netball
750
Petanque
300
Racketball
750
Riding
500
Roller skating
500
School sports
750

60
60
60
60
60
80
60
60
60
60
80
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60

Chapter 2 / 11

Seite 11

24.06.2004

8:45 Uhr

Type of interior,
task or activity

Em

Ra

Shooting
Snooker
Speed skating
Squash
Swimming
Swimmung (school level)
Table tennis
Tennis
Volleyball
Weight lifting
Wrestling

200
750
500
750
300
500
750
750
750
750
750

60
80
60
60
80
60
60
60
60
60
60

12 / Chapter 2

The Lighting Handbook

02_INNENRAUM_uk.qxd

Seite 12

02_INNENRAUM_uk.qxd

24.06.2004

Type of area,
task or activity

8:45 Uhr

Ra

Em

General circulation areas


Walkways exclusively for pedestrians
Traffic areas for slowly moving vehicles max. (10 km/h),
e.g. bicycles, trucks and excavators
Regular vehicle traffic (max. 40 km/h)
Pedestrian passages, vehicle turning,
loading and unloading points

20

10
20

20
20

50

20

20
30
50
50

20
40
40
40

50
20

20
20

50

20

100

40

200

40

10

20

10
20
20
50
50
50

20
20
20
20
20
20

50

20

20
50
50

20
20
20

5
20
50

20
20
20

150
150

20
20

Airports
Hangar apron
Terminal apron
Loading areas
Fuel depot

Building sites
General lighting at building sites
Clearance, excavation and loading
Drain pipes mounting, transport, auxiliary and
storage tasks
Framework element mounting, light reinforcement
work, wooden mould and framework mounting,
electric piping and cabling
Element jointing, demanding electrical,
machine and pipe mountings

Canals, locks and harbours


Waiting quays at canals and locks
Gangways and passages exclusively for pedestrians,
waiting areas
Outport embankment ballasting at canals and locks
Lock control area
Cargo handling, loading and unloading
Passenger areas in passenger harbours
Coupling of hoses, pipes and ropes
Dangerous part of walkways and driveways.
(See also parking areas)

Farms
Farm yard
Equipment shed (open)
Animals sorting pen

The Lighting Handbook

Fuel filling service stations


Vehicle parking and storage areas
Entry and exit driveways: dark environment
Entry and exit driveways: light environment (i.e. cities)
Air pressure and water checking points and
other service areas
Meter reading area

Chapter 2 / 13

Seite 13

02_INNENRAUM_uk.qxd

24.06.2004

Type of area,
task or activity

8:45 Uhr

Ra

Em

Industrial sites and storage areas


Short term handling of large units and raw materials,
loading and unloading of solid bulk goods
Continuous handling of large units and raw materials,
loading and unloading of freight, lifting and descending
location for cranes, open loading platforms
Reading of addresses, covered loading platforms,
use of tools, ordinary reinforcement and casting
tasks in concrete plants
Demanding electrical, machine and piping
installations, inspection

20

20

50

20

100

20

200

20

300
500
150
100
300
200

40
40
40
40
40
40

200
300
100
100
300
100
200
30
100

20
40
40
20
40
20
20
20
20

20

10

20

20

20

20

20

50

20

100

40

Off-shore gas and oil structures


Drill floor and monkey board
Rotary table
Pipe rack area/deck
Derrick
Mud room, sampling
Test station, shale shaker, wellhead
Process areas:
Pumping areas
Crude oil pumps
Treatment areas
Ladders, stairs, walkways
Plant areas
Boat landing areas/transport areas
Life boat areas
Sea surface below the rig
Helideck

Parking lots
Light traffic, e.g. parking lots of shops, schools,
churches, terraced and apartment houses
Medium traffic, e.g. parking lots of department stores,
office buildings, plants, sports and multipurpose
building complexes
Heavy traffic, e.g. parking lots of major shopping centres,
major sports and multipurpose building complexes
Handling of servicing tools, utilisation of manually regulated
valves, starting and stopping motors, lighting of burners
Filling and emptying of container trucks and wagons
with risk free substances, inspection of leakage,
piping and packing
Filling and emptying of container trucks and wagons
with dangerous substances, replacements of pump
packing, general service work, reading of instruments

14 / Chapter 2

The Lighting Handbook

Petrochemical and other hazardous industries

Seite 14

02_INNENRAUM_uk.qxd

24.06.2004

8:45 Uhr

Type of area,
task or activity

Em

Ra

Repair of machines and electric devices


Fuel loading and unloading sites

200
100

60
20

5
20
50
100
100
200

20
20
20
40
40
60

15

40

20
50

40
40

50
100
50
100
20
50

40
40
40
40
40
40

10
20
20
50
100
30

20
20
40
40
40
20

10
10
100
50
10
20
20

20
20
40
20
20
40
20

20

20

50
100
200
300

20
40
40
40

Power, electricity, gas and heat plants


Pedestrian movements within electrically safe areas
Handling of servicing tools, coal
Overall inspection
General servicing work and reading of instruments
Wind tunnels: servicing and maintenance
Repair of electric devices

Railway areas
Passenger areas:
Open platforms, small stations, rural and local trains
Open platforms, medium-size stations, suburban and
regional trains
Open platforms, large stations, inter-city services
Covered platforms, medium-size stations, suburban
and regional trains
Covered platforms, large stations, inter-city services
Stairs, small and medium-size stations
Stairs, large stations
Walkways, small and medium-size stations
Walkways, big stations
Freight areas:
Freight track, short duration operations
Freight track, continuous operation
Open platforms
Covered platform, short duration operations
Covered platform, continuous operation
Railway yards handling areas
Railway yards: flat marshalling, retarder and
classification yards
Hump areas
Wagon inspection pit
Coupling area
Tracks in passenger station areas, including stabling
Servicing trains and locomotives
Level crossings

The Lighting Handbook

Saw mills
Timber handling on land and in water, sawdust and
chip conveyors
Sorting of timber on land or in water, timber unloading
points and sawn timber loading points, mechanical
lifting to timber conveyor
Reading of addresses and markings of sawn timber
Grading and packaging
Feeding into stripping and chopping machines

Chapter 2 / 15

Seite 15

02_INNENRAUM_uk.qxd

24.06.2004

Type of area,
task or activity

8:45 Uhr

Em

Ra

20
50
100
200

20
20
60
60

20

40

50

20

100
200

40
60

Shipyards and docks


Short term handling of large units
Cleaning of ship hull
Painting and welding of ship hull
Mounting of electrical and mechanical components
General lighting of shipyard area, storage areas
for prefabricated goods

Water and sewage plants


Handling of service tools, utilisation of manually
operated valves, starting and stopping of motors,
piping packing and raking plants
Handling of chemicals, inspection of leakage,
changing of pumps, general servicing work,
reading of instruments
Repair of motors and electric devices

EN 12464-1
EN 12464-2 (draft)
EN 12193
by kind permission of the Austrian Norm Institute,
A-1020 Vienna
http://www.on-norm.at

16 / Chapter 2

The Lighting Handbook

Extracts from

Seite 16

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Chapter 3

Luminaires
Zumtobel Staff applications . . . . . . . . . . . . . . . . . . . .
Types of lighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3
45

X as in XENO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
x-tra strong lighting accents
STARFLEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modular fibre-optic system
PANOS L and H . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Multitalented downlights
PANOS S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
More degrees of vertical freedom
PANOS M/MWW . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Impressive and powerful
LIGHT FIELDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modular micro-pyramidal lighting system
MELLOW LIGHT IV . . . . . . . . . . . . . . . . . . . . . . . . . . .
A piece of sky
MIRAL T16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Surface-mounted louvre luminaire
MIREL T16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Recessed louvre luminaire
MIRAL/MIREL T16 BWS . . . . . . . . . . . . . . . . . . . . . . .
Louvre luminaire for sports halls
AERO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
High-tech light with waveguide
OREA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Double array (waveguide luminaire)
RTX II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Design-oriented continuous-row lighting system
LED luminaires . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
From semiconductor to lighting innovation
FREE-STANDING UPLIGHTS . . . . . . . . . . . . . . . . . . . .
LIGHT FIELDS-S, KAREA, LANOS, FLEXOS
TECTON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Continuous-row lighting system

67
8 11
12 13
14
15
16 17
18 19
20 21
22 23
23
24 26
27
28 29
30 31
32 33
34 35

Seite 1

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Seite 2

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Office and Education


Intensifies sense of well-being
Improves human factors
Increases motivation
Creates sense of identity
Industry and Engineering
Provides time reference
Prevents accidents
Reduces stress
Boosts productivity
Health & Care
Encourages relaxation
Facilitates convalescence
Encourages rehabilitation
Creates feel-good atmosphere
Art and Culture
Conveys information
Sets the stage for art
Structures content
Adapts concepts
Presentation and Retail
Makes objects look attractive
Creates branded landscapes
Gets message across
Shopping becomes an
experience
Hotels and Restaurants
Creates an unmistakeable look
Paints a backdrop for events
Stimulates sense of well-being
Stimulates communication

The Lighting Handbook

Sport and Leisure


Facilitates identification
Encourages self discovery
Celebrates surfaces
Stimulates performance

Chapter 3 / 3

Seite 3

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Seite 4

Types of lighting

Direct lighting:
highly directional
strong glare reduction at certain angles
dark ceiling (cave effect)
limited choice of workstation layout
energy-efficient

diffuse lighting conditions


room gains in height
glare-free
workstations can be positioned anywhere
low energy efficiency

4 / Chapter 3

The Lighting Handbook

Indirect lighting:

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Indirect/direct lighting:
pleasant room impression
high user acceptance
good contrast ratios
flexible workstation layout
(indirect component > 60 %)

The Lighting Handbook

Mellow Light:
indirect/direct solution for low ceiling heights
workstations can be positioned anywhere
glare-free
reduced luminance levels at all viewing angles
gives impression of daylight in room

Chapter 3 / 5

Seite 5

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Seite 6

X as in XENO x-tra strong lighting accents

XENO QR-CBC covers a huge


spectrum of applications thanks
to its use of low-voltage halogen
cool-beam reflector lamps with
beam angles from superspot to
flood.

6 / Chapter 3

Basically, all spotlights have


the following features: they
rotate through 365, the X-joint
pivots through 90. Low-voltage
models are dimmable via rotary
potentiometer on the spotlight.

XENO QT 12, fitted with the


QT 12100 W low-voltage
halogen lamp, as superspot 8,
spot 15 and flood 40.
With choice of additional optical
systems.

The Lighting Handbook

XENO is a spotlight generation


for professionally setting the
lighting stage, providing ideal
light for display, accentuation
and presentation whether in
shops and malls, exhibitions
and trade fairs, or galleries
and museums. The new
spotlight-system range,
with models ranging from
LV halogen lamps to projection spotlights, is complemented by a huge choice of
accessories such as filters,
glass covers, lenses, honeycomb louvres or anti-glare
blades.

The Lighting Handbook

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

XENO QR 111 is particularly


suitable for impressive accent
lighting. Can be used with
QR 111 LV halogen lamps in
50 W, 75 W or 100 W versions.

XENO HST: By using high-pressure sodium vapour lamps, the


spotlight (spot 10/flood 40)
provides good colour rendition,
particularly for warmer colour
tones.

XENO HIT-CRI has been


optimised for HIT-CRI metal
halide lamps with single-ended
base (70 W to 150 W).
PulseControl starters monitor
lamp parameters and guarantee
optimum performance.
XENO HIT-CRI is available
as superspot 10, spot 15,
flood 35 and superflood 50.

PROJECTOR: The XENO projection spotlight is a highperformance compact spotlight


system for accentuation or
sharply outlined projection of
logos, gobos or slides. Separate
motor control of slide and
colour magazine allows the use
of various patterns and colour
filters.

Chapter 3 / 7

Seite 7

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Seite 8

STARFLEX Modular fibre optic system


System components

Light engine

Accessories

QR-CBC 50 W/100 W

Colour-wheel module

HIT 35 W/70 W

Sparkle-effect wheel module


HIT 150 W/250 W
HIT 150 W/250 W controllable

IP 54 150 W/250 W
IP 54 150 W/250 W controllable

8 / Chapter 3

Colour temperature correction


filters

The Lighting Handbook

Static colour
filters

03_LEUCHTEN_uk.qxd

24.06.2004

Optical fibres

8:46 Uhr

Light outlets (selection)

Adjustable light outlet


Terminal light emitting glass fibres

Crystal light outlet

Terminal light emitting PMMA fibres


Light outlet for
stairway/path lighting

Side-radiating PMMA fibres

The Lighting Handbook

Curved tube light outlet

Projection attachment
Chapter 3 / 9

Seite 9

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Seite 10

Properties and applications of optical fibres


Fibre
Properties
material
Glass
can withstand relatively high
temperatures (up to 110 C)
extremely long service life
(in excess of 20 years)
relatively tight bending radius
projects preferring
relatively warm light colour
PMMA
cheaper than glass
life time in excess of
20 years
projects involving relatively
cool light colour
choice of side-radiating or
terminal light emitting fibres
side-radiating and terminal
light-emitting fibres can be
combined in a single fibre
bundle
fibre bundle can optionally
be assembled on site

Applications
glass display cases in
museums
saunas and steam baths
hotel and restaurant
lighting

applications requiring
high levels of
illumination
retail shop windows,
display shelving and
show cases
starry skies in hotels
and wellness areas
outdoor lighting or in
areas with high air
humidity

Assembly of glass fibre bundles

1.0 mm
1.5 mm
2.0 mm
3.0 mm
4.5 mm
6.0 mm

Outer diameter Maximum number


of sheathing
of individual fibres
per common end
spigot
2.2 mm
615
2.7 mm
307
3.9 mm
176
4.9 mm
79
6.4 mm
36
8.7 mm
20

Minimum
bending
radius
7 mm
11 mm
14 mm
21 mm
32 mm
42 mm

Length-dependent correction factors (attenuation) for glass


fibre cables
1m 2m 3m 4m

5m

6m

7m

8 m 9 m 10 m

0.93 0.87 0.81 0.76 0.71 0.66 0.62 0.57 0.54 0.50

10 / Chapter 3

The Lighting Handbook

Active
diameter of
fibre cable

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Assembly of PMMA fibre bundles


(terminal light emission, factory-assembled)
Active
diameter of
fibre cable

1.0 mm
1.5 mm
2.0 mm
3.0 mm
4.5 mm
6.0 mm
8.0 mm
10.0 mm

Outer diameter Maximum number


of sheathing
of individual fibres
per common end
spigot
crimped/spliced
2.2 mm
575/300
2.7 mm
342/165
4.0 mm
143/70
5.0 mm
72/35
6.5 mm
37/18
8.5 mm
20/10
10.5 mm
13/6
12.0 mm
8/4

Minimum
bending
radius

8 mm
12 mm
16 mm
24 mm
36 mm
48 mm
60 mm
75 mm

Length-dependent correction factors (attenuation) for PMMA cables


1m 2m 3m 4m

5m

6m

7m

8 m 9 m 10 m

0.95 0.91 0.87 0.83 0.79 0.75 0.72 0.69 0.65 0.62

Assembly of PMMA fibre bundles


(side radiation, factory-assembled)

The Lighting Handbook

Outer diameter Maximum number of


of sheathing
individual fibres per
common end spigot
(crimped)
4.5 mm
80
8.0 mm
19
11.0 mm
11
14.0 mm
6

Maximum number of
individual fibres per
common end spigot
(spliced)
40
10
5
3

Chapter 3 / 11

Seite 11

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Seite 12

PANOS L and H Multi-talented downlights


PANOS L
Recessed depth of just 100 mm.
Also suitable for use with VDT
workstations thanks to radial
louvre.
PANOS H
Satisfies the most stringent glare
limitation requirements without
the need for accessories.

HF/LF
The precision-shaped facets
provide brilliant effects, reduced
luminance levels and optimum
efficiency.

HG/LG
Highly specular darklight reflector
optic for glare-free working at
the highest level.

HM/LM
Good looks are guaranteed by
this matt reflector optic with
reduced dust sensitivity.

HL/LL
The white reflector optic is a
perfect match for the decorative
accessories.

HWW
The special ribbed structure of
the reflector produces asymmetrical light distribution, ideal for
highlighting vertical surfaces.

12 / Chapter 3

The Lighting Handbook

Reflectors and their applications

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Attachments for interior design (selection)

IP 54 kit, clear glass

Akamar

IP 54 kit, opal glass

Adhara

IP 54 kit, structured glass

Alhena

PANOS L and H with compact fluorescent lamps (TC)


PANOS L

PANOS H

Diameter
175 mm
200 mm
250 mm
175 mm
200 mm
250 mm

Wattage
1326 W
1826 W
2657 W
1326 W
1842 W
2657 W

Mounting depth
100 mm
100 mm
100 mm
120 mm
150 mm
190 mm

Installation instructions

The Lighting Handbook

No-tool installation
The mounting ring made of diecast aluminium is fitted without
tools using spring clips.

Combined reflector/flange unit


The reflector/flange unit is installed by means of a twist and
lock mechanism without any
tools. The ballast box has a rapid
locking device and forms a preassembled luminaire unit with
the reflector.

Chapter 3 / 13

Seite 13

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Seite 14

PANOS S
More degrees of
vertical freedom
The innovative tilting principle
allows 45 pivoting into the
ceiling and up to 60 pivoting
out of the ceiling, with horizontal
rotation through 360.
A convenient grip clip makes
positioning easy.
rotates through 360

When pivoted at 60, it can illuminate the wall from the ceiling
down, or light the top surface of
a shelf. A choice of flood or spot
reflectors are available.
With completely independent
adjustment of lighting head and
housing possible, PANOS S
works like a spotlight with antiglare blades to prevent seeing
directly into the lamp.

Diameter
100 mm
150 mm
200 mm

14 / Chapter 3

Lamps
QT-LP 12
QR-CBC 51
QT-LP 12
HIT
QT-LP 12
QR 111
HIT
HST

Wattage
75 W
50 W
100 W
2070 W
100 W
100 W
70150 W
100 W

Mounting depth
125 mm
125 mm
145 mm
145 mm
230 mm
230 mm
230/240 mm
230 mm

The Lighting Handbook

Pivoting into the ceiling at 45


enables asymmetrical light
distribution for an unobtrusive
and calm ceiling effect.

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

PANOS M/MWW
Impressive and powerful
PANOS M
Metal reflector for high thermal
stability. Die-cast aluminium
mounting rings and cooling
attachment. Ideal for lamps
with high heat output.

PANOS MTE
Dust and dirt stand no chance
on the Teflon-coated surface.
The high-tech Teflon material
also results in efficiencies up to
10 % higher than conventional
surface finishes.

The Lighting Handbook

PANOS MWW
The sophisticated wallwasher
with asymmetrical light distribution looks just like its rotationally
symmetrical counterparts when
installed in the ceiling, ensuring
a consistent interior design.

Wide range of lamps


PANOS M and MWW can
accommodate a huge range of
lamps. For the lighting designer,
this means complete freedom
when professionally setting the
lighting stage.
Chapter 3 / 15

Seite 15

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Seite 16

LIGHT FIELDS Modular micro-pyramidal


lighting system

Design by Sottsass Associati


Pure innovation for the office

Micro-pyramidal optic

base
micro-pyramidal layer
for directing the light
diffuser layer

16 / Chapter 3

The Lighting Handbook

Even in surface-mounted and recessed luminaires, the sandwich


construction of the micro-pyramidal
optic ensures both glare control
in conformity with standards and
reduced luminance for direct illumination ideal for office lighting
according to standard EN 12464.

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Available as recessed/surface-mounted/pendant/
free-standing or cluster luminaires, they are ideal for
the more stylish office, with EN 12464 compliance
over a range of ceiling heights and floor areas.

M 625

M 600

Recessed
1198 x 298
2/28 W T16
1498 x 298
2/35 W T16
598 x 598
4/14 W T16
1248 x 310
2/28 W T16
1548 x 310
2/35 W T16
623 x 623
4/14 W T16

Surfacemounted
1248 x 310
2/28 W T16
1548 x 310
2/35 W T16
623 x 623
4/14 W T16

The Lighting Handbook

LIGHT FIELDS model


Recessed
L-FIELDS E 4 x 4/14 W T16
L-FIELDS E 4 x 2/28 W T16
L-FIELDS E 4 x 2/28 W T16
L-FIELDS E 6 x 4/14 W T16
Surface-mounted
L-FIELDS A 4 x 4/14 W T16
L-FIELDS A 4 x 2/28 W T16
L-FIELDS A 3 x 2/35 W T16
L-FIELDS A 4 x 2/28 W T16
L-FIELDS A 6 x 4/14 W T16

ID pendant
1248 x 310
2/54 W T16
1548 x 310
2/49 W T16
623 x 623
4/24 W T16

Free-standing
luminaire
3/55 W TCL
3/80 W TCL

1-person
office

2-person
office

3-person
office

Chapter 3 / 17

Seite 17

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Seite 18

MELLOW LIGHT IV A piece of sky

T16 lamp
Colour filter (optional)
Light scattering (diffuse
reflection from surface)

Light scattering
(diffuse reflection from surface)
Reflector
Enclosed lighting chamber
Light scattering
(opal translucent material)
Colour filter (optional)
T16 lamp
Optic (louvre or diffuser)

18 / Chapter 3

The Lighting Handbook

Reflector
Enclosed lighting
chamber
Light scattering
(opal translucent
material)
Optic (louvre or
diffuser)

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Diffuser optic
Optic can be fitted without
tools
Optic has fly-proof seal
Diffuser optic with slotted
sheet steel for all-round
glare control
Suitable for glare control on
upright and steeply inclined
displays
Mounting kit required for
concealed ceiling systems
and sawn cut-outs
Dimmable DALI luminaires
contain a DALI-controllable
electronic ballast and are
suitable for all DALI and
Luxmate Professional
applications.

MELLOW LIGHT IV recessed


luminaire with slotted sheet
steel diffuser optic
Recessed sheet steel housing
with die-cast structure
Lighting chamber made of
high purity PMMA diffuserpearl material
Lighting chamber can be backlit in colour using colour filters

76

T16

MELLOW LIGHT IV
dimensions

105,6
LxB

42

81

TC-L

The Lighting Handbook

Module 600

Module 625

Cat. no.
L
W
H
Cat. no.
L
W
H
24 W T16
623
623 81
24 W T16
598
598 81
28 W T16 1248 310 76
28 W T16 1198 298 76
35 W T16 1548 310 76
35 W T16 1498 298 76
49 W T16 1548 310 76
49 W T16 1498 298 76
54 W T16 1248 310 76
54 W T16 1198 298 76
55 W TC-L 623
623 81
55 W TC-L 598
598 81
Calculating the size of the sawn cut-out in the ceiling:
length/width of ceiling cut-out = length/width of luminaire 16 mm

Chapter 3 / 19

Seite 19

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Seite 20

MIRAL T16 Surface-mounted louvre luminaire


Complete louvre luminaire range:
surface-mounted luminaire
indirect/direct pendant luminaire
wallwasher
Application: offices, schools, shops
Benefits: BIVERGENZ plus lighting technology
quick installation thanks to
mounting bracket
pre-fitted lamp
protective film
Fold up

Light source included


MIRAL T16 is pre-fitted with
an LF840 lamp (LF830 available
on request). This keeps the
installation effort to a minimum,
saving the time, resources and
energy that would otherwise be
spent on lamp procurement,
transport and temporary storage.
Packaging
The mounting brackets are
located ready for use outside
the box so there is no need to
open it. Advantage: the luminaire
remains protected in its packaging during pre-installation.
The installation instructions and
drilling template are printed on
the outside of the box.

20 / Chapter 3

Snap in

Electrical connection
Quick installation is also
guaranteed thanks to the exactly
centered 5-pole plug-in terminal
(CE-compliant) easily accessible
from outside the luminaire.
Thus the connecting cable can
be fitted conveniently and in
minimum time without needing
to open the luminaire housing.
Protective film
A special self-adhesive protective film made of recyclable
material offers optimum protection against louvre soiling.
MIRAL T16 can therefore be
fully installed whilst building
work is still in progress, and
even used to light the construction site. Once the building is
finished, simply pull away the
film which leaves no residue.

The Lighting Handbook

Lay in

03_LEUCHTEN_uk.qxd

Traditional
installation

24.06.2004

8:46 Uhr

MIRAL T16
installation

The Lighting Handbook

Traditional installation for the electrician


meant four trips up and down the
ladder, two operations with the
electric screwdriver.
MIRAL T16 installation for the electrician means getting the same result in
half the time!

Chapter 3 / 21

Seite 21

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Seite 22

MIREL T16 Recessed louvre luminaire


Complete louvre luminaire
range:
narrow recessed luminaire
recessed luminaire module
wallwasher
Application: offices
Benefits: BIVERGENZ plus lighting
technology
ergonomic installation
pre-fitted lamp
Balanced Colour

BIVERGENZ plus
The secret of success of Zumtobel Staffs louvre luminaire is:
ONE (BIVERGENZ technology) plus ONE (UniQue blade) = FOUR (benefits)

The patented BIVERGENZ


technology, based on 25 years
of experience, has two new
features developed specifically
with the new European standard
EN 12464 in mind: a higherreflection coating in the latest
materials, and the innovative
freeform surface technology of
the UniQue blade.

Divergence

Convergence

This provides FOUR benefits:


Optimum uniformity thanks to practically ideal batwing
distribution of direct light

Standard narrow-width louvre for fitting one or two lamps


Maximum efficiency thanks to louvre material increasing
reflection

22 / Chapter 3

The Lighting Handbook

Gentle all-round glare control in conformity with the new


EN 12464 standard

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Solutions
MIREL T16 in continuous-row
lighting system
Straightforward installation of
a continuous row system with
clean, visually unbroken lines
in the narrow louvre design.
Emergency lighting
components
Power failure? No problem
thanks to optional emergency
lighting components!
Electrical connection
Optionally available with Euro,
T12 or Wieland connectors,
built-in or with cable.
Integrated light source
Option of complete luminaire
with pre-fitted lamp for straightforward, fast installation: unpack

the luminaire, fit, remove protective film, and its done!


Air extraction openings
Through special openings in the
standard luminaire housing,
used air from the room flows
directly into the ventilated ceiling.
Extensive measurement data is
available to assist accurate
air-handling calculations.
Lighting control system
Requirements for lighting
intensity and lighting scene vary:
optional LUXMATE lighting
control components can be used
for easy control of MIREL T16
luminaires and dynamic light
changes.

The Lighting Handbook

MIRAL/MIREL T16 BWS


Louvre luminaire for sports halls

Louvre luminaire range:


Surface-mounted luminaire
BWS T16
Recessed luminaire BWS T16
Trunking installation
accessories

Benefits:
High luminous efficiency thanks
to T16 lamp
Narrow housing thanks to
2-in-1 lamp capability (two
lamps in one louvre panel)
Good price/performance ratio

Application: sports halls


Chapter 3 / 23

Seite 23

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Seite 24

AERO High-tech light with waveguide


Principle of operation

Directional light emission in batwing distribution

Light distribution
Operating efficiency
= 70 % (2/54W)
I : D = 75 % : 25 %

560 cd/m2 at 60
Reduced
luminance levels

24 / Chapter 3

3800 cd/m2 at 30

The Lighting Handbook

2900 cd/m2 at 0

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

AERO waveguide luminaire


Models and designs

Geometric

2 x 54 W T516 mm

Softline

2 x 28 W T516 mm

Softline
semi-transparent

The Lighting Handbook

Features and typical applications


Features

Effect

Application

Reduced
luminance levels

No direct or
reflected glare

Offices with modern


office equipment
(standard screens,
flat-panel displays,
VDTs)

Lamps cannot be
seen from any angle

Restricted brightness

Flat-panel displays, e.g.


in doctors surgeries

Indirect/direct
ratio 75:25

Ceiling pleasantly
illuminated, good
modelling, good
contrast rendition

Ceiling heights of
2.50 m or more,
flexible workstation
layout

Light directed using


microprismatic
arrays

Louvre-like
directional
light distribution,
easy to clean

Rooms with longer


maintenance
intervals

Chapter 3 / 25

Seite 25

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

Seite 26

AERO with SLC technology

Principle of operation (SLC lateral light coupler)


See OREA luminaire

26 / Chapter 3

The Lighting Handbook

See OREA luminaire for description of lighting technology

03_LEUCHTEN_uk.qxd

24.06.2004

8:46 Uhr

OREA Double array (waveguide luminaire)


OGZ-ID 2/54

Principle of operation (SLC lateral light coupler)

The Lighting Handbook

directional direct-light
component with reduced
luminance of to
L 2,500 cd/m2 at 65
for standard situations
luminaires can be arranged
freely in the room, including
directly above workstations
(except where flat-panel
displays are used)

direct component approximately 5 % higher than


AERO

Chapter 3 / 27

Seite 27

03_LEUCHTEN_uk.qxd

24.06.2004

8:47 Uhr

Seite 28

RTX II
Design-oriented continuous row lighting system

Design by Charles Keller


Avant-garde in terms of both
material and shape
Application: offices and schools

Individual luminaires and


continuous row systems:
Pure aluminium
Matt bivergent or darklight
reflector optic
Wallwasher for illuminating
blackboards
Decorative optics

Typical applications
RTX II-C
1/35W 1/49W 1/54W 1/80W 2/28W 2/35W 2/49W 2/54W

Day school
Technical college/
evening school
Office
Office with DSE
Open-plan office
Technical drawing

RTX II-D
Day school
Technical college/
evening school
Office
Office with DSE
Open-plan office
Technical drawing

28 / Chapter 3

The Lighting Handbook

1/35W 1/49W 1/54W 1/80W 2/28W 2/35W 2/49W 2/54W

03_LEUCHTEN_uk.qxd

24.06.2004

8:47 Uhr

RTX II Wallwasher
RTX II 1 x 49 W
RTX II 1 x 54 W
RTX II 1 x 80 W
RTX
RTX
RTX
RTX

II
II
II
II

2 x 28 W
2 x 35 W
2 x 49 W
2 x 54 W

300 Lux

0.20

(Day school)

0.40 0.60 0.80 1.00 1.20 1.40


blackboard
luminaire distance [m]

optimum
range
possible
range
possible range under
certain conditions*

* Use strongly depends on architectural parameters and


luminaire arrangement.

RTX II 1 x 80 W
RTX II 2 x 49 W
RTX II 2 x 54 W

500 Lux
(Evening school
and technical
colleges)

0.20

0.40 0.60 0.80 1.00 1.20 1.40


blackboard
luminaire distance [m]

optimum
range
possible
range

The Lighting Handbook

possible range under


certain conditions*

* Use strongly depends on architectural parameters and


luminaire arrangement.

Chapter 3 / 29

Seite 29

03_LEUCHTEN_uk.qxd

24.06.2004

8:47 Uhr

Seite 30

LED luminaires From semiconductor


to lighting innovation
Static and dynamic light
Overview of LED luminaires
static

dynamic

LEDOS RG

LEDOS RGB

LEDOS M
PHAOS LED lighting tile

PHAOS Lighting tube


LEDOS B

KAVA LED

PHAOS Spotlight PHAOS Line

long service life = low maintenance costs


low power consumption = minimum operating costs
vibration and impact-proof
compact size
high colour stability
efficient control thanks to simple control system
low heat generation
30 / Chapter 3

The Lighting Handbook

Benefits of LED technology

Diameter of
circular
luminaires
Dimensions of
square
luminaires
IP
Voltage

Name
Colours

85 x 85
100 x 100
120 x 120
54/67
24 V
230 V

80 x 80
80 x 115
20/54
24 V
230 V

100 x 100

KAVA LED
Blue
Yellow
Green
Red
White
120

67
24 V

120 x 120

120

LEDOS RG
Alternately
red/green

dynamic

67
230 V

120 x 120

LEDOS RGB
Full
spectrum

20
24 V

228 x 228

PHAOS
Lighting tile
Full
spectrum

20
24 V

310
900

PHAOS
Lighting tube
Full
spectrum

67
230 V

310 x 100
900 x 100

PHAOS
Line*
Full
spectrum

8:47 Uhr

Chapter 3 / 31

* only available as analog version

20
230 V

PHAOS
Spotlight
Full
spectrum

24.06.2004

67/68
24 V

LEDOS B
Blue
Yellow
Green
Red
White
85/100/120

LEDOS M
Blue
Yellow
Green
Red
White
65

static

Technical data (selection)

The Lighting Handbook

03_LEUCHTEN_uk.qxd
Seite 31

03_LEUCHTEN_uk.qxd

24.06.2004

8:47 Uhr

Seite 32

FREE-STANDING UPLIGHTS
LIGHT FIELDS-S, KAREA, LANOS, FLEXOS

enable personal adjustment


and control to suit viewing conditions and the visual task in hand;

can be adjusted easily and


economically to evolving office
situations;

allow individual illumination


of the workstation;

use sensors to provide


optimum user convenience and
large potential energy savings.

can be placed in the


optimum position, making the
whole office space useable;

LIGHT FIELDS-S

KAREA

Free-standing uplight with


indirect/direct light distribution
3/55 W or 3/80 W TC-L
Direct light component with
micro-pyramidal optic (MPO)
with defined glare-free light
emission L < 1000 cd/m2 at
60/65
Luminaire head and stand
made of anodised aluminium
SensControl LCD with built-in
display for intuitive operation

Free-standing luminaire with


indirect/direct light distribution
4/55 W TC-L
Extremely flat angular
luminaire head
Direct light component with
perforated metal optic
Angular aluminium stand
Optionally available with
SensControl lighting
management system
SensControl LCD with built-in
display for intuitive operation
Colour: titanium

32 / Chapter 3

The Lighting Handbook

Free-standing uplights

03_LEUCHTEN_uk.qxd

24.06.2004

LANOS

FLEXOS

Free-standing luminaire with


indirect/direct light distribution
4/55 W TC-L
Luminaire head with lateral
perforated metal refractors
Stand made of aluminium
extrusion
Two-step switching
(50/100 %)
Optionally available with
SensControl lighting
management system
SensControl LCD with built-in
display for intuitive operation
Colour: titanium

Free-standing luminaire with


indirect/direct light distribution, with 1 to 4 heads
Direct light component with
louvre optic or perforated
metal optic
2/55 W TC-L per head
Optimum two-point adjustment of each luminaire head
in relation to workstation
Optionally available with
SensControl lighting
management system
Single- and twin-head version
dimmable via touch switch
Colour: titanium

SensControl LCD

The Lighting Handbook

8:47 Uhr

SensControl LCD is the highly


convenient SensControl lighting
management system for LIGHT
FIELDS-S, LANOS, FLEXOS and
KAREA uplights.
The main feature is a small
LCD display which provides
details of the various operating
states and settings.

Straightforward menu-driven
software allows near-intuitive
control of the luminaire and easy
programming of individual
functions.
Besides individual adjustment of
the daylight sensor and presence
detector, SensControl LCD also
makes it possible to call up preset profiles, program switch-on
times or select the menu language
desired at the press of a button.
This innovative electronic system
combines intelligent technology
with optimum operating
convenience.

Chapter 3 / 33

Seite 33

03_LEUCHTEN_uk.qxd

24.06.2004

8:47 Uhr

Seite 34

TECTON
continuous-row lighting system
TECTON Compact

TECTON Retail

34 / Chapter 3

The Lighting Handbook

TECTON-I Industry

03_LEUCHTEN_uk.qxd

24.06.2004

8:47 Uhr

TECTON provides flexibility


Layout changes occur at ever shorter intervals in retail,
business and industry, demanding maximum flexibility from any
continuous-row lighting system. TECTON allows the luminaire
modules to be placed anywhere on the trunking. Technical
alterations to the lighting can also be made on site, with 11-pole
wiring allowing any modifications in terms of brightness control
or emergency lighting supply in conformity with relevant
standards.
TECTON saves on installation costs
The easier, the better. The specially designed power conductor
integrated in the trunking revolutionises installation, making
TECTON both versatile and easy to handle. Not only does this
save time, but lower qualified and hence cheaper staff can do
the work. All components can be combined logically and simply
in the modular system, reducing TECTON installation costs by
up to 60 percent through time savings, depending on the
continuous row configuration chosen.

TECTON provides safety


TECTON provides safety in several ways:
At the design stage, by the integration of mains lighting,
emergency lighting and control;

The Lighting Handbook

By the clear separation of emergency and escape-sign


luminaires in two emergency-lighting circuits;
By the ONLITE emergency luminaire range that can be fully
customized to the TECTON system for safety and reliability of
the lighting solution in conformity with relevant standards.

Chapter 3 / 35

Seite 35

00_INHALTSVER_uk.qxd

24.06.2004

10:21 Uhr

Seite 2

04_LAMPEN_uk.qxd

24.06.2004

8:49 Uhr

Seite 1

Chapter 4

Lamps and ballasts


Lamp selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lamp characteristics . . . . . . . . . . . . . . . . . . . . . . . . .
The main lamp types . . . . . . . . . . . . . . . . . . . . . . . . .
Application notes, T16 fluorescent lamps . . . . . . . . . .
A comparison of fluorescent lamps T16/T26 . . . . . .
Application notes, compact fluorescent lamps . . . . . . .
Application notes, metal halide lamps . . . . . . . . . . . . .
Characteristics of metal halide lamps 250 + 400 W . .
Lamp names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comparison of lamp names . . . . . . . . . . . . . . . . . . . .
Characteristic values of the major lamps . . . . . . . . . . .
Energy efficiency of luminaires . . . . . . . . . . . . . . . . . .
Properties of dimmable electronic ballasts . . . . . . . . .
Power consumption, energy savings, required power . .

2
3
48
9 10
11
12 13
14
15 16
17
17
18 22
23
24
25

04_LAMPEN_uk.qxd

24.06.2004

8:49 Uhr

Seite 2

Choosing the right lamp


An important first decision
Choosing the right lamp depends on what is required of the
lighting (see Chapter 5 / 2).
For instance, incandescent lamps are still the most popular
lighting option used in domestic areas to help create that cosy
atmosphere. Even though the lamps may generate little light, the
poor efficiency is acceptable because they are comparatively
cheap to buy and are normally on for short periods.
In other situations, users happily tolerate the higher purchase
price of discharge lamps because their high luminous efficiency
and long lifetime make them economic.
Thus it is part of the expertise of the lighting designer to find
the most suitable lamp for a lighting task.
Lamp characteristics can essentially be specified by the
following key terms:

Lamp
power

Warm-up
time

Service
life

Light
colour

Colour
rendition

Dimming
capability

Burning
position

Lamp
characteristics

Re-start
time

The Lighting Handbook

Luminous
flux/
efficiency

04_LAMPEN_uk.qxd

24.06.2004

8:49 Uhr

Seite 3

The Lighting Handbook

Lamp characteristics
1. Power The electrical power consumption of the lamp as
opposed to the power consumption of a system comprising
lamp and ballast.
2. Luminous flux/luminous efficiency The luminous flux
specifies the total amount of light generated by a lamp. The
rated luminous flux is measured at a standardised measurement
temperature of 25 C in units of lumen [lm]. The ratio of luminous flux to electrical power consumption gives the luminous
efficiency [lm/W]. The system luminous efficiency also includes
the power consumption of the ballast.
3. Service life The average service life is normally specified,
being the time by which statistically half the lamps are still
working (mortality). The drop in luminous flux also needs to be
taken into account.
4. Light colour The light colour describes the colour impression
made by a white light source as relatively warm (ww = warm) or
relatively cool (nw = intermediate, tw = cool). It is affected by
the red and blue colour components in the spectrum.
5. Colour rendition The spectral components of the light determine how well various object colours can be reproduced. The
higher the colour rendition index (Ra or CRI), or the lower the
colour rendition group number, the better the colour rendition in
comparison with the optimum reference light.
6. Warm-up time Discharge lamps in particular need between
30 seconds and several minutes to warm up and output the full
luminous flux.
7. Re-start High-pressure discharge lamps need to cool down
for several minutes before they can be started again.
8. Dimming capability Besides incandescent and halogen
incandescent lamps, nowadays all fluorescent and compact
fluorescent lamps can also be dimmed over almost any range.
Metal halide lamps, however, are still not approved by the manufacturers for dimming, because this may have uncontrollable
effects on light quality and lamp service life. The power of highpressure sodium- and mercury-vapour lamps can be varied, but
only in discrete levels.
9. Burning position Manufacturers specify the permitted
burning positions for their lamps. For some metal halide lamps,
only certain burning positions are allowed so as to avoid unstable operating states. Compact fluorescent lamps may usually
be used in any burning position, although important properties
such as the luminous flux vs. temperature curve may vary with
position.
Chapter 4 / 3

04_LAMPEN_uk.qxd

24.06.2004

8:49 Uhr

Seite 4

Halogen

lamps

The main lamp types

Halogen lamps
For mains and low-voltage Brilliant light
Excellent colour rendition
operation
Applications: retail
Longer service life and
and domestic areas,
higher luminous efficiency
restaurants and
than incandescent lamps
catering
Easy to dim

4 / Chapter 4

The Lighting Handbook

How they work Current flows through a filament and


heats it up, just as in incandescent lamps. These lamps
therefore generate a relatively large amount of heat. The
halogen cycle increases the efficiency and extends the
service life compared with traditional incandescent lamps.
Low-voltage types are very small and are ideal for precise
direction of light, but do require a transformer.

Fluorescent

lamps

04_LAMPEN_uk.qxd

24.06.2004

Fluorescent lamps
High to very high luminous efficiency (in
particular T16 HE)
Good to excellent
colour rendition

8:49 Uhr

Seite 5

Long service life


Extensive range of types
Dimmable

The Lighting Handbook

Compact

fluorescent

lamps

How they work An alternating electric field generates


invisible UV radiation between the two electrodes in the
discharge tube. This radiation is converted into high-quality
visible light in the fluorescent material. The lamps need a
starting aid and a current limiting device, usually combined
in an electronic ballast. The luminous flux is highly dependent on the ambient temperature.

Compact fluorescent
lamps
Compact designs
High luminous efficiency
Excellent colour rendition
Extensive range of types

Dimmable
Applications: commercial and high-profile
interiors, restaurants
and catering

How they work These lamps are compact versions of the


linear or circular fluorescent lamps, and operate in a very
similar way. The luminous flux depends on the burning
position and temperature.

Chapter 4 / 5

Metal halide lamps

04_LAMPEN_uk.qxd

24.06.2004

8:49 Uhr

Seite 6

Metal halide lamps


High luminous efficiency Cannot be dimmed
Good to excellent colour Applications: industrial
rendition
bays, spotlighting,
High colour stability for cer- floodlighting, retail
amic discharge-tube lamps areas

6 / Chapter 4

The Lighting Handbook

How they work In metal halide lamps, a highly compact


electric arc is produced in a discharge tube. The composition of the materials in the tube determines the light
quality. A starter is needed to switch on the lamp, and the
current must be limited by a ballast. Practical electronic
ballasts are also available for low-power lamps.
The use of ceramic discharge tubes further improves the
lamp properties.

04_LAMPEN_uk.qxd

24.06.2004

8:49 Uhr

Seite 7

Sodium

vapour

lamps

Colour-improved
(Philips SDW):
Excellent colour rendition
Warm light
Long service life
Application: retail
areas

Sodium vapour lamps


High luminous efficiency and
long service life
Satisfactory to poor colour
rendition

Can be dimmed in
discrete steps
Applications: industrial bays, street
lighting

The Lighting Handbook

Mercury vapour lamps

How they work The discharge in the linearly extended


ceramic discharge tube is defined by sodium, so the light
is yellowish and only suitable for special applications. The
colour-improved SDW lamp by Philips is a popular choice
for lighting retail areas. A starter is usually needed to
switch on the lamp, and the current must be limited by
a ballast.
Mercury vapour lamps
No starter, just ballast
required
Satisfactory to poor
colour rendition
Can be dimmed in
discrete steps
Applications: industrial bays, street
lighting
How they work The high-pressure mercury vapour lamp
is actually the forerunner to the modern metal halide lamp,
although it provides a far poorer light quality. The lamps
can be started at mains voltage, and so only need a
ballast for current limiting.

Chapter 4 / 7

Induction

lamps

04_LAMPEN_uk.qxd

24.06.2004

QL
55 W, 85 W and 165 W
Rotationally symmetrical light
distribution
Applications: areas where
it is difficult to replace

8:49 Uhr

Seite 8

lamps; commercial
and industrial
interiors, retail,
indoor and outdoor
public areas

8 / Chapter 4

The Lighting Handbook

How they work A high-frequency electromagnetic field is


coupled into the glass bulb via an antenna protruding into
the bulb. This produces UV radiation which is then converted into visible light by fluorescent material, just as
in fluorescent lamps. The amalgam technology used in
these lamps makes their luminous flux only very slightly
temperature-dependent. The lamps can only be operated
with special electronic ballasts. Systems have a very long
service life because the only parts subject to wear are in
these ballasts. As yet there are no dimmable electronic
ballasts available.

04_LAMPEN_uk.qxd

24.06.2004

8:49 Uhr

Seite 9

Application notes
T16 fluorescent lamps
T16 lamps differ from T26 versions in several characteristics
that the user should be particularly aware of.
1. Luminous flux temperature curve
As for all fluorescent lamps, the lamps luminous flux is
temperature-dependent. The maximum value is obtained at an
optimum ambient temperature, with losses increasing at higher
and lower temperatures. The T16 basically follows the same
curve as the T26, but the maximum occurs not at an ambient
temperature of 20 to 25 C but at about 35 C. The reason for
this is that the cool spot of the T16 lamp does not lie in the
centre of the lamp but typically at one end of the tube near the
lamp end.
The rated luminous flux is generally specified for an ambient
temperature of 25 C. For the T16, the maximum value therefore lies above this rated value. Thus luminaire efficiencies may
have levels greater than 1.
%
100
80
T26 58 W
60

T16

40
T26 36 W

20

-20

20

40

60

80 C

The Lighting Handbook

Ambient temperature

Chapter 4 / 9

04_LAMPEN_uk.qxd

24.06.2004

8:49 Uhr

Seite 10

2. Lamp orientation
Owing to the two electrodes (tube ends) not being identical in
design, it matters how one or more lamps are fitted in the
luminaires. In general, lamp ends should always have the same
orientation i.e. in multi-lamp luminaires they should lie next to
each other, and where lamps are positioned vertically, they
should preferably also be at the bottom. For cool environments
it may be practical to choose a different orientation.
single-lamp

multi-lamp

normal
ambient
temperature

cool
ambient
temperature

3. Ageing/burning in

10 / Chapter 4

The Lighting Handbook

Brand new lamps stabilise during the ageing phase. This is the
period immediately after the lamps are switched on for the first
time, when the initially encapsulated mercury is vaporised and
evenly distributed in the lamp. To ensure perfect operation, one
should allow a period of 2 to 4 days of operation without
dimming or switching, particularly in dimming installations.
Unstabilised lamps may differ in brightness and light colour,
even exhibiting flickering at low dimming levels. One should
also wait for proper ageing before assessing the illuminance
level and the light quality. This ageing has no effect on the
lamp service life.

04_LAMPEN_uk.qxd

24.06.2004

8:49 Uhr

Seite 11

A comparison of fluorescent lamps T16/T26


Advantages of T16 fluorescent lamps

Reduction in the lamp diameter by about 40 %


Higher optical efficiencies possible
Improved luminous efficiency
Improved luminaire efficiencies from the shift in the
luminous-flux peak
Standardised luminance levels for all lamp lengths for
high-efficiency lamps
Larger range of types makes it easier to meet lighting
requirements more closely
Summary type comparison (selection):
Length
549 mm
849 mm
1149 mm
1449 mm

T16
Power Rated luminous flux (25)
14 W 1200 lm
24 W 1750 lm
21 W 1900 lm
39 W 3100 lm
28 W 2600 lm
54 W 4450 lm
35 W 3300 lm
49 W 4300 lm
80 W 6150 lm

T26
Power Rated luminous flux (25)
590 mm 18 W 1350 lm
Length

895 mm 30 W 2350 lm
1200 mm 36 W 3350 lm
1500 mm 58 W 5200 lm

Example of interior lighting using T16 and T26

The Lighting Handbook

Room dimensions: length = 8 m, width = 6 m, height = 3 m


Reflection factors: ceiling = 70 %, walls = 50 %, floor = 20 %
Required maintenance value of illuminance: 500 lx
Option 1: SPHEROS ind/direct luminaire, matt louvre, 2/36 W electr. ballast
Option 2: SPHEROS ind/direct luminaire, matt louvre, 2/28 W electr. ballast
Option 1
2/36 W
Number of luminaires
8
Max. lamp luminous efficiency
93 lm/W
Power consumption per m2 per 100 lx 2.2 W/m2/100 lx
Luminaire efficiency
85 %
Utilization factor
66 %
Energy saving

Option 2
2/28 W
8
104 lm/W
2.0 W/m2/100 lx
91 %
73 %
10 %
Chapter 4 / 11

04_LAMPEN_uk.qxd

24.06.2004

8:49 Uhr

Seite 12

Application notes
Compact fluorescent lamps
1. Amalgam lamps
The strong temperature dependence of the luminous flux of
traditional fluorescent and compact fluorescent lamps can be
compensated by adding amalgam (mercury compound).
This helps to somewhat check the steep drop-off at higher or
lower temperatures, so that at least 90 % of the maximum
luminous flux is achieved over a wide temperature range of
about +5 to +70 C. Above and below this range, however, the
light level still falls off sharply. The tables provide an overview
of those major
without amalgam TC-T, TC-TE
manufacturers
13 W 18 W 26 W 32 W 42 W lamps in the TC-T
design (three-fold
Osram 2-pin
DULUX T
X
X
X
double tube) that
Osram 4-pin
have added
X
X
X
X
X
DULUX T/E
amalgam.
GE 2-pin
BIAX T
Sylvania 2-pin
Lynx CF-T

with amalgam TC-TI, TC-TELI, TC-QELI


13 W 18 W 26 W 32 W 42 W 57 W 60 W 70 W 85 W 120 W

12 / Chapter 4

X
X

The Lighting Handbook

Osram
2-pin
DULUX T IN
Osram
4-pin
DULUX T/E IN
Philips
2-pin
PL-T 2p
Philips
4-pin
PL-T 4p
GE
4-pin
BIAX T/E
BIAX Q/E
Sylvania
4-pin
Lynx CF-TE

04_LAMPEN_uk.qxd

24.06.2004

8:49 Uhr

Seite 13

2. Lamp orientation

The Lighting Handbook

The luminous flux from compact fluorescent lamps is highly


dependent on the burning position. The light output ratio can
therefore be maximized by inserting the lamps correctly.
Standard types have a cool spot in the exposed lamp bend, so
that self-heating and convection may lead to a temperature rise
here. In amalgam lamps, the cool spot lies in the lamp base.
In compact luminaires with horizontal lamp arrangement
(e.g. downlights), it is therefore recommended to fit the lamps
with electrodes uppermost wherever possible. Since the lamp
end does not allow consistent identification of the electrode
position, that lamp side on which adjacent tubes are not
connected should be placed uppermost these are the two
tube ends containing the internal electrodes. The exception to
this is the PHILIPS PL-T, in which the electrodes are arranged
diagonally. Either possible orientation of these lamps is equivalent.

Chapter 4 / 13

04_LAMPEN_uk.qxd

24.06.2004

8:49 Uhr

Seite 14

Application notes
Metal halide lamps
1. Ballasts
The manufacturers of metal halide lamps use a range of operating principles, resulting in different electrical operating values.
Some lamps are therefore approved for operation both with
ballasts for metal halide lamps (e.g. COPA I 1/400 HIE) and with
ballasts for high-pressure sodium vapour lamps (e.g. COPA I
1/400 HSE). The higher operating current then leads to higher
luminous flux levels for the same lamps together with a slightly
altered light quality. In both cases suitable starters are required.
2. Glass covers
In general, metal halide lamps require a glass cover to protect
people and property in the event of the lamp exploding.
It is the manufacturers responsibility to decide whether to
permit individual lamp types to be used in uncovered luminaires.
Suitable safety devices are installed in the lamps for this
purpose (e.g. integral safety tube, outer protective coating).
The detailed information from the manufacturer must be
observed without fail.
3. Service life characteristics

14 / Chapter 4

The Lighting Handbook

The average lamp service life (lamp survival factor) and the reduction in luminous flux (lamp luminous flux maintenance factor)
can vary markedly in some of the different lamp types. They also
depend on the switching frequency and the position of use.
Once again the detailed data from the manufacturer must be
taken into account. The maintenance factor tables in Chapter 8
contain some typical values.

Ellipsoid
E40
any
yes

Tube
E40
any
no

Ellipsoid
E40
vertical 15
no

25,500 lm
3,800 K
69

20,000 lm
5,300 K
90

25,500 lm
3,800 K
69

19,000 lm
4,300 K
69

20,000 h

Ellipsoid
E40
vertical 15
yes

HPI-PLUS
250 W BU-P

23,000 lm
4,000 K
65

19,000 lm
4,500 K
65

20,000 h

Tube
E40
horizontal 20
no

HPI-T PLUS
250 W

24.06.2004
8:49 Uhr

All data subject to change. For reliable information and data on other lamp types, please refer to the manufacturers data.

19,000 lm
4,300 K
69

not permitted

12,000 h
12,000 h
12,000 h
20,000 h
See maintenance factors in Chapter 8 Calculation of economic efficiency

Ellipsoid
E40
any
no

PHILIPS
HPI-PLUS
250 W-BU

HQI-T
250 W/D

HQI-E
250 W/D

HQI-E/P
250 W/D

OSRAM

Operation with metal-halide lamp ballast (HI)


Luminous flux
not permitted
not permitted
Colour temperature
Colour rendition index Ra
Operation with high-pressure sodium-vapour lamp ballast (HS)
Luminous flux
19,000 lm
17,000 lm
Colour temperature
5,200 K
6,000 K
Colour rendition index Ra
90
90

Design
Base
Burning position
Approved for operation in
uncovered luminaires
Average service life
Reduction in luminous flux

The Lighting Handbook

04_LAMPEN_uk.qxd
Seite 15

Characteristics of metal halide lamps 250 W

Chapter 4 / 15

PHILIPS

no

no

Tube
E40
horizontal
45
no
20,000 h

Ellipsoid
E40
horizontal
20
no
20,000 h

Tube
E40
horizontal
20
no

8:49 Uhr

All data subject to change. For reliable information and data on other lamp types, please refer to the manufacturers data.

Operation with high-pressure sodium-vapour lamp ballast (HS)


Luminous flux
30,000 lm 27,000 lm 43,000 lm 45,000 lm 32,000 lm 42,000 lm 42,500 lm 42,500 lm 35,000 lm 38,000 lm
Colour temperature
5,900 K 4,500 K 4,000 K 4,000 K 5,200 K 3,700 K 3,800 K 3,800 K 3,800 K 4,000 K
Colour rendition index Ra
90
90
70
70
90
65
69
69
69
65

Operation with metal-halide lamp ballast (HI)


Luminous flux
26,000 lm 23,000 lm 34,000 lm 36,000 lm 25,000 lm 34,000 lm 35,000 lm 35,000 lm 30,000 lm 35,000 lm
Colour temperature
5,800 K 5,000 K 3,600 K 3,600 K 6,100 K 3,800 K 4,300 K 4,300 K 4,700 K 4,300 K
Colour rendition index Ra
90
90
65
65
90
65
69
69
69
65

no

Tube
E40
any

20,000 h

yes

Ellipsoid
E40
any

12,000 h 12,000 h 12,000 h 12,000 h 12,000 h 12,000 h 20,000 h


See maintenance factors in Chapter 8 Calculation of economic efficiency

no

Approved for operation in


uncovered luminaires
Average service life
Reduction in luminous flux

Ellipsoid
E40
any

Ellipsoid
E40
vertical
15
yes

Ellipsoid
E40
any

Ellipsoid
E40
vertical
15
no

Ellipsoid
E40
any

24.06.2004

The Lighting Handbook

16 / Chapter 4

Design
Base
Burning position

HQI-E
HQI-E/P HQI-E
HQI-E
HQI-BT HQI-T
HPI-PLUS HPI-PLUS HPI PLUS HPI-T PLUS
400 W/D 400 W/D 400 W/N 400 W/N 400 W/D 400 W/N 400 W- 400 W
400 W
400 W
clear
BU
BU-P

OSRAM

04_LAMPEN_uk.qxd
Seite 16

Characteristics of metal halide lamps 400 W

04_LAMPEN_uk.qxd

24.06.2004

8:49 Uhr

Seite 17

Lamp names as given by the LIS (ZVEI) a selection


Abbreviation Description
A
R
QT 18
QT 32
QT-DE
Q PAR
QT9
QT12
QR
QR-CB
QR-CBC
T16
T26
TC-S/SEL
TC-D/DEL
TC-T/TEL
TC-L
TC-TELI/
QELI
HI
HM
HS
LS

General-purpose incandescent lamps


Reflector lamps
Halogen incandescent lamps for mains voltage 18 mm
Halogen incandescent lamps for mains voltage 32 mm
Halogen incandescent lamps for mains voltage, linear doubleended
Halogen incandescent lamps for mains voltage with reflector
Low-voltage halogen incandescent lamps 9 mm
Low-voltage halogen incandescent lamps 12 mm
Low-voltage halogen incandescent lamps with reflector
Low-voltage halogen incandescent lamps with cool-light
specular reflector
Low-voltage halogen incandescent lamps with cool-light
specular reflector and glass cover
Fluorescent lamps 16 mm
Fluorescent lamps 26 mm
Compact fluorescent lamps (1 tube) up to 11 W/for electr. ballast
Compact fluorescent lamps (2 tubes) up to 26 W/for electr. ballast
Compact fluorescent lamps (3 tubes) up to 42 W/for electr. ballast
Compact fluorescent lamps (1 tube) up to 80 W
Compact fluorescent lamps (34 tubes) amalgam technology
up to 120 W/only for electronic ballast
Metal halide lamps: various designs
High-pressure mercury vapour lamps: ellipsoid
High-pressure sodium vapour lamps: various designs
Low-pressure sodium vapour lamps: tubular

Comparison of lamp names (examples)

The Lighting Handbook

Internat.
name from

Manufacturer names

LIS (ZVEI)

Osram

Philips

GE

Sylvania

A 60
QR-CBC
QPAR
TC-S
TC-T
TC-L
T16
T26
HME
HIT
HIT-CE
HST

A
DECOSTAR S
HALOPAR
DULUX S
DULUX T
DULUX L
FH, FQ
L
HQL
HQI-T
HCI-T
NAV-T

A
Masterline
PAR
PL-S
PL-T
PL-L
TL5 HE, HO
TLD
HPL
MHN-T
CDM-T
SON-T, SDW-T

A1
Precise MR
PAR
BIAX S
BIAX T
BIAX L
F T5
F
H
ARC/T, KRC/T
CMH/T
Lucalox T

Normal
Superia
Hi-Spot
Lynx CF-S
Lynx CF-T
Lynx CF-L
F
HSL
HSI-T
SHP-T, SHP-TS

Chapter 4 / 17

18 / Chapter 4
ww, nw
ww, nw
ww, nw
ww, nw
ww, nw
ww, nw
ww, nw
ww, nw
ww, nw
ww, nw
ww, nw
ww, nw
ww, nw
ww, nw
ww, nw
ww, nw

80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80

Colour
Colour rendition
temperature
index Ra
G5
G5
G5
G5
G5
G5
G5
G5
G5
2 GX 13
2 GX 13
2 GX 13
2 GX 13
G 13
G 13
G 13

Base

1,200
1,900
1,750
2,600
3,300
3,100
4,300
4,450
6,150
1,800
3,200
4,000
5,000
1,350
3,350
5,200

Luminous
flux in lm
(at 25 C)

25
42
66

13,000
13,000
13,000

Lamp
service life
in h

magnetic VVG

System
power
in W
1618
24
27
3133
3941
46
54
61
ca. 88
26
4547
60
66
1920
36
5457

System
power
in W
1620,000
1620,000
1620,000
1620,000
1620,000
1620,000
1620,000
1620,000
1620,000
12,000
12,000
12,000
12,000
1620,000
1620,000
1620,000

84
87
74
93
93
76
90
81
82
69
71
67
76
68
89
93

Lamp
max. system luservice life minous efficiency
in h
in lm/W

electronic EVG

24.06.2004
8:49 Uhr

The Lighting Handbook

Fluorescent lamps
T 16 14 W
T 16 21 W
T 16 24 W
T 16 28 W
T 16 35 W
T 16 39 W
T 16 49 W
T 16 54 W
T 16 80 W
T 16-R 22 W
T 16-R 40 W
T 16-R 55 W
T 16-R 60 W
T 26 18 W
T 26 36 W
T 26 58 W

Lamp name

04_LAMPEN_uk.qxd
Seite 18

Characteristic values of the major lamps

80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80

Base

G 24 d-1/q-1
G 24 d-1/q-1
G 24 d-2/q-2
GX 24 d-1/q-1
GX 24 d-2/q-2
GX 24 d-3/q-3
GX 24 q-3
GX 24 q-4
GX 24 q-5
2G8
GX24q-6
2G8
2G8
2 G 11
2 G 11
2 G 11
2 G 11
2 G 11
2 G 11

Colour
Colour rendition
temperature
index Ra

Compact fluorescent lamps


TC-D/TC-DEL 10 W
ww, nw
TC-D/TC-DEL 13 W
ww, nw
TC-D/TC-DEL 18 W
ww, nw
TC-T/TC-TEL 13 W
ww, nw
TC-T/TC-TEL 18 W
ww, nw
TC-T/TC-TEL 26 W
ww, nw
TC-TEL/-TELI 32 W
ww, nw
TC-TEL/-TELI 42 W
ww, nw
TC-TELI 57 W
ww, nw
TC-TELI 60 W
ww, nw
TC-TELI 70 W
ww, nw
TC-TELI 85 W
ww, nw
TC-TELI 120 W
ww, nw
TC-L 18 W
ww, nw
TC-L 24 W
ww, nw
TC-L 36 W
ww, nw
TC-L 40 W
ww, nw
TC-L 55 W
ww, nw
TC-L 80 W
ww, nw

Lamp name

The Lighting Handbook

600
900
1,200
900
1,200
1,800
2,400
3,200
4,300
4,000
5,200
6,000
9,000
1,200
1,800
2,900
3,500
4,800
6,000

Luminous
flux in lm
(at 25 C)
8,000
8,000
8,000
8,000
8,000
8,000

8,000
8,000
8,000

15
17
23
17
23
31

25
30
42

Lamp
service life
in h

magnetic VVG

System
power
in W
12
14
1820
14
1820
28
3536
4647
62
65
75
92
128
19
2527
3439
45
5561
85

System
power
in W
10,000
10,000
10,000
10,000
10,000
10,000
10,000
10,000
10,000
20,000
10,000
20,000
20,000
10,000
10,000
10,000
10,000
10,000
10,000

50
64
66
64
66
64
68
69
69
62
70
65
70
63
72
85
77
87
71

Lamp
max. system luservice life minous efficiency
in h
in lm/W

electronic EVG

04_LAMPEN_uk.qxd
24.06.2004
8:50 Uhr
Seite 19

Characteristic values of the major lamps

Chapter 4 / 19

90
90
90
90
90
90
90
90
90
90
90
90

Low-voltage halogen lamps


QT 12 35 W
ww
QT 12 50 W
ww
QR CBC 51 35 W (860) ww
QR CBC 51 50 W (860) ww
QR 111 75 W (845)
ww
QR 111 100 W (845)
ww

High-voltage halogen lamps


QT-DE 12 150 W L 114,2 ww
QT-DE 12 300 W
ww
QT-DE 12 500 W
ww
QT 32 100 W matt
ww
QT 32 150 W matt
ww
QT 32 250 W matt
ww
R7s
R7s
R7s
E 27
E 27
E 27

GY 6.35
GY 6.35
GU 5.3
GU 5.3
G 53
G 53

Special
Special
Special

Base

2,200
5,000
9,500
1,430
2,400
4,000

600
930
*70014,000
*95014,000
*1.70030,000
*2.80048,000

3,500
6,000
12,000

Luminous
flux in lm
(at 25 C)

1,500
2,000
2,000
2,000
2,000
2,000

4,000
4,000
4,000
4,000
3,000
3,000

Lamp
service life
in h

magnetic VVG

System
power
in W
55
85
165

System
power
in W
60,000
60,000
60,000

14
16
19
14
16
16

16
18
16
18
10
10

64
71
73

Lamp
max. system luservice life minous efficiency
in h
in lm/W

electronic EVG

8:50 Uhr

The Lighting Handbook

20 / Chapter 4

24.06.2004

*Axial luminous intensity in cd.

80
80
80

Colour
Colour rendition
temperature
index Ra

Induction lamps
LMG-IHf 55 W (QL 55 W) ww, nw
LMG-IHf 85 W (QL 85 W) ww, nw
LMG-IHf 165 W (QL 165 W) ww, nw

Lamp name

04_LAMPEN_uk.qxd
Seite 20

Characteristic values of the major lamps

ww, nw
ww, nw
ww, nw
ww, nw, tw
nw, tw
nw
ww, nw
ww, nw
ww
ww, nw
ww, nw
nw, tw
nw, tw
ww, nw
ww, nw, tw
ww, nw
ww, nw
ww, nw, tw

Base
Luminous
flux in lm
(at 25 C)
6,000
6,000
6,000
6,000
6,000
6,000
6,000
6,000
9,000
9,000
6,000
6,000
6,000
6,000
6,000
7,000
12,000
6,000

Lamp
service life
in h

magnetic VVG

System
power
in W

80, 70
E 27
4,9005,000
8296
80, 70
E 27
7,3008,100 112115
80, 70
E 27
10,50012,500 168177
90, 60, 70 E 40
17,00255,000 275285
90, 60, 70 E 40
20,50043,000 400460
60
E 40
95,000 10501065
80
G 12
5,2005,500
8296
80
G 12
13,000 168177
80
G8.5/G12
3,400
4446
80
G8.5/G12
6,4006,600
8296
80
G 12
14,000 168177
90, 60, 70 E 40
19,00021,000 275285
90, 60, 70 E 40
25,00042,000 400460
90, 80
RX 7s
5,0006,000
8296
90, 80, 70 RX 7s
11,250 168177
90, 80
RX 7s
5,7007,000
8995
90, 80
RX 7s 13,50014,200 168177
90, 80, 70 Fc 2
20,000 275285

Colour
Colour rendition
temperature
index Ra

Metal halide lamps


HIE 70 W
HIE 100 W
HIE 150 W
HIE 250 W
HIE 400 W
HIE 1000 W
HIT 70 W (quartz)
HIT 150 W (quartz)
HIT/HIT-TC 35 W (ceramic)
HIT/HIT-TC 70 W (ceramic)
HIT 150 W (ceramic)
HIT 250 W
HIT 400 W
HIT-DE 70 W (quartz)
HIT-DE 150 W (quartz)
HIT-DE 70 W (ceramic)
HIT-DE 150 W (ceramic)
HIT-DE 250 W

Lamp name

The Lighting Handbook

6,000
6,000

6,000
6,000
912,000
912,000
612,000
6,000
6,000
715,000
1215,000

172

8083
172
4245
8083
172
8083
172
8083
172

63
72
74
93
93
90
69
77
80
83
83
76
91
75
66
79
80
72

Lamp
max. system luservice life minous efficiency
in h
in lm/W

electronic EVG

8083

System
power
in W

04_LAMPEN_uk.qxd
24.06.2004
8:50 Uhr
Seite 21

Characteristic values of the major lamps

Chapter 4 / 21

22 / Chapter 4
60, 20
60, 20
80
80
80
60, 20
60, 20

High-pressure sodium vapour lamps


HSE 250 W
ww
HSE 400 W
ww
HST 35 W (SDW-T)
ww
HST 50 W (SDW-T/TG)
ww
HST 100 W (SDW-T/TG) ww
HST 250 W
ww
HST 400 W
ww
E 40
E 40
PG 12-1
PG 12-1/G12
PG 12-1/G12
E 40
E 40

E 40
E 40

Base

22,00032,000
36,00054,000
1,300
2,300
4,800
23,00033,000
37,00056,500

13,000
22,000

Luminous
flux in lm
(at 25 C)

275285
440450
4142
66
114116
275
440450

266270
425
10,000
10,000
10,000
10,000
10,000
10,000
10,000

8,000
8,000

Lamp
service life
in h

magnetic VVG

System
power
in W

System
power
in W

112
120
31
34
42
116
123

48
51

Lamp
max. system luservice life minous efficiency
in h
in lm/W

electronic EVG

24.06.2004
8:50 Uhr

The Lighting Handbook

40
40

Colour
Colour rendition
temperature
index Ra

High-pressure mercury vapour lamps


HME 250 W
ww, nw
HME 400 W
ww, nw

Lamp name

04_LAMPEN_uk.qxd
Seite 22

Characteristic values of the major lamps

04_LAMPEN_uk.qxd

24.06.2004

8:50 Uhr

Seite 23

Energy efficiency of luminaires


Most of the electrical power is consumed in the lamp and its
control gear. In order to clarify the power consumption of the
ballast/lamp system, the European Union has adopted the
energy classification system (Directive 2000/55/EU on energy
efficiency requirements for ballasts for fluorescent lamps).
The EEI (Energy Efficiency Index) classifies ballasts into seven
categories:
Class

Ballasts

A1
A2
A3
B1
B2
C

Dimmable electronic ballasts


Reduced-loss electronic ballasts
Electronic ballasts
Magnetic ballasts, very low loss (low-loss ballast)
Magnetic ballasts, low loss (low-loss ballast)
Magnetic ballasts, moderate loss (conventional
ballast)
Magnetic ballasts, very high loss (conventional
ballast)

Sales of class D ballasts have been prohibited since 21 May


2002; class C ballasts must be taken off the market by
21 November 2005 at the latest.

Example for T26 36 W 840:

The Lighting Handbook

EEI
A1
A2
A3
B1
B2
C
D

19 W (25 % dimming is equivalent to 50 % A3)


36
38
41
43
45
45
Chapter 4 / 23

* see chapter 5

LUXMATE connection
LUXMATE Basic*
LUXMATE Emotion*
LUXMATE Professional*

Additional emergency lighting


function (DC mode)

not possible

yes
linear

1 or 3100 %
Fluctuations
plus/minus
no
no
Luminaire group; all luminaires
on one control line

Analog (110 V)

yes
logarithmic **

0.1100 % (depends on lamp)


none
Interchangeable polarity
yes
yes
Individual luminaires or
luminaire groups

Digital (DALI)

** matches visual perception

LDE (PCA Excel one4all)

LMB
DALI ONLY
LDE

Dimming level can be set by customer 1 or 370 % ( PCA Excel one4all )


uniform surface illumination possible in emergency lighting mode, dimming-level
memory with automatic recall in emergency lighting mode ( PCA Excel one4all)

yes
logarithmic **

1 or 3100 %
none
Interchangeable polarity
yes
yes, only PCA Excel one4all
Luminaire group; all luminaires
on one control line

Digital (DSI)

24.06.2004
8:50 Uhr

The Lighting Handbook

24 / Chapter 4

Visual comfort
Stable and flicker-free lamp operation
Dimming curve

Dimming range in AC mode


Dimming level tolerance
Control line
Zero-power switching
Status report & logging
Addressing

Functionality

Properties

04_LAMPEN_uk.qxd
Seite 24

Properties of dimmable electronic


ballasts

04_LAMPEN_uk.qxd

24.06.2004

69 W

Power consumption as a

function of dimmer setting

compared with conventional


ballasts 20 % to 88 %
at 1 % dimming level (off)

55 W
45 W
35 W
25 W

8W

8W

8W

100 % 75 % 50 % 25 %
Conventional ballast Controlled by LUXMATE Dimmer setting

in (%)

90
80
70
60
50

1%

Additional emergency lighting function


with PCA Excel one4all
(central power supply)
Set-DC

Energy saving using Set-DC


100

Seite 25

Energy saving at normal operation


Set-AC

Power consumption 20 % to 88 %

558 W

8:50 Uhr

Saving:
up to 70 %,
at 10 % luminous flux
reduced use of
group batteries and
central installations

potential
energy saving
of 52 %

AC-mode
DC-mode

40
30
20 further potential
energy saving of 27 %
10
0
59

53

9:00

48

10:00

43

11:00

39

35

12:00

30

13:00

28

22

14:00

Power requirement of a
traditional
raditional freestanding luminaire

17

15:00

12

Power (W)
10 at 230 V DC

16:00

Potential energy savings


using daylight sensors
and presence detectors
up to 70 %
compared
with
constant light
e.g. freestanding
luminaire
using
SensControl

sufficient daylight

cloud cover

increasing daylight

absent

absent

The Lighting Handbook

Power requirement of a freestanding


luminaire using SensControl

decreasing daylight

Chapter 4 / 25

00_INHALTSVER_uk.qxd

24.06.2004

10:21 Uhr

Seite 2

05_LUXMATELM_uk.qxd

24.06.2004

9:40 Uhr

Chapter 5

Lighting and room management,


emergency lighting
LUXMATE lighting management . . . . . . . . . . . . . . . . .
2
Dimming with LUXMATE Basic . . . . . . . . . . . . . . . . . .
3
LUXMATE Basic system overviews . . . . . . . . . . . . . . . 4 9
Dimming and switching with LUXMATE Emotion
LUXMATE EMOTION system overviews + optional
integration of ONLITE Local Check . . . . . . . . . . . . . . 10 13
LUXMATE Professional system overview (selection) . . . 14 15
ONLITE emergency lighting system
(applicable to U.K.) . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 25

Seite 1

05_LUXMATELM_uk.qxd

24.06.2004

9:40 Uhr

Seite 2

Luxmate lighting management


The intelligent control system for individual rooms
and throughout buildings

Function

Applications

Room management systems


LUXMATE Professional (based on LUXMATE bus system)
Artificial light/daylight/blinds
Conference rooms
Interfaces to media technology
Office buildings
Integration of ONLITE
Shopping malls
emergency lighting system
Museums
Interface to building management Industry
system and central maintenance
Customized operating systems
Lighting control systems
LUXMATE EMOTION (based on DALI)
Lighting scenes
Shops
Timer
Health & Care
RGB dimming software
Wellness
ACTIVE LIGHT lighting concepts Control rooms
Flexibility of individual
Offices
addressing/grouping
In the home

In the home
Small offices &
surgeries
Commercial
premises
The Lighting Handbook

LUXMATE Basic (based on DSI)


Daylight-based
Infrared remote control unit
Standard switch components
No addressing, group dimming
Zero-power switching and
dimming

1000 %

1000 %

LED

STARLFEX
optical fibre
QT engines

On/Off, dimming, daylightdependent dimming

* number can be increased using DSI-V amplifier, ** DALI versions available on request

3 x 100/148* DSI-TLE** Momentary-action switch,


light sensor

DSI-TLC** Momentary-action switch,


On/Off, dimming, daylightlight sensor, presence detector dependent dimming

On/Off, dimming, D/ID


Balanced Lighting

On/Off, dimming, 3 lighting


scenes per output

Balanced Lighting

2 x 25/73*

Momentary-action switch,
remote control unit

DSI-IRBLC Momentary-action switch,


remote control unit

DSI-2IR

On/Off, dimming, D/ID

On/Off, dimming

On/Off, dimming, 1 scene

On/Off, dimming

Function

2 x 25/73*

2 x 25/73*

DSI-BLC** Momentary-action switch

2 x 25/73*

Momentary-action switch
Momentary-action switch

DSI-TD**
DSI-TS

100/148*

Momentary-action switch,
presence detector

Operation

25/73*

DSI-T**

Output
module

25/73*

Number
possible

24.06.2004

DALI TE one4all
105 VA/150 VA

PWM converter LED


K210 one4all
25 W

T16/T26 1001 % DSI electronic ballast


TC 1003 %
(LMB)

DALI TE one4all
105 VA/150 VA

Low-voltage halogen 1000 %


incandescent lamps

Dimmable
fluorescent lamps

PDAX 500 VA
PDAS 1,000 VA
phase dimmer

Dimming range Control gear/


dimmer

General purpose lamps 1000 %


PAR lamps, Halogen
incandescent lamps

Lamps

Dimming with LUXMATE Basic (no addressing required)

The Lighting Handbook

05_LUXMATELM_uk.qxd
9:40 Uhr
Seite 3

Chapter 5 / 3

DALI-TD

Arguments for your customers

Absolutely flicker-free dimming

Simple to operate using conventional momentary-action light switches

throughout

Hence ensures standardised design of light switches and sockets

Any number of momentary-action light switches can be connected in parallel

* available on request

Alternative:
Connect terminals
T and T together with
a jumper if a single
momentary-action
switch is used.

Conventional momentaryaction light switch


Preset/Dia

Lamp control gear

APD

D1
D2
TEL

up to 25 DSI transformers
up to 25 DALI transformers*

or

D1
D2

up to 25 DSI phase dimmers


up to 25 DALI phase dimmers*

or

LV halogen incandescent
lamps max. 70/105/150/210 VA

max. 2 m 2

Incandescent lamps/
HV halogen incandescent lamps max. 300 VA

L'
N
N
L

10
9

12
11

Lamps

up to 25 DSI electr. ballasts


up to 25 DALI electr. ballasts*
Fluorescent lamps T26/T16
TC-L/TC-DEL/TC-TEL
L
N
D1
PCA
D2

Dimming range 1 or 3100 % light level


Lamps can be started at any dimming level
Suitable for all major lamp types
Easy to install
Insensitive to mains fluctuations and interference
Components can be delivered separately or pre-fitted in the luminaire
Dimming-level memory

Momentary-action switch control


L module with input for preset light level
N
D1
T
T
D2
DSI-TD
Preset/Dia

Control line
e.g. NYM 2 x 1.5 mm2, max. length 100 m

Control units

24.06.2004

The Lighting Handbook

4 / Chapter 5
Programming instructions for preset light level (Dia):
Set brightness level required using
momentary-action switch
Press the Preset/Dia switch for at
least 5 seconds

User control units


Mains 230 V/50 Hz

Conventional double
momentary-action
light switch
On/Off
Dimming

L
N
PE

05_LUXMATELM_uk.qxd
9:40 Uhr
Seite 4

LUXMATE Basic DSI-TD or DALI-TD

Dimming using conventional momentary-action light switches and


with dimming-level memory
(DALI-TD available on request)

up to 5 ceilingmounted
IRED IR sensors

one must be set as master,


the others as slaves

Convenient operation using infrared remote control unit


Remote control unit comes complete with wall bracket
Horizontal/vertical transmission characteristics
Can run three lighting scenes

Arguments for your customers

up to 7 IRS
channels can
be used

IRS IR remote
control unit
max. range
10 m at
500 lux

max.
length 50 m

LDSI-2IR infrared control module IR1


N
IR2
TT
D2 D1
T
D1
T If more than one DSI module is used, D2

Control units
Group 1

D1
D2

L'
N
N
L

12
11
10
9

max.
length 2 m
87
65
43
21

Fluorescent lamps T26/T16


TC-L/TC-DEL/TC-TEL

Lamps

L'
N
N
L

LV halogen incandescent lamps 70/105/150/


210 VA
max.
DSI transformer
length 2 m
87
65
D1
4
3
D2
21

D1
D2

DSI phase dimmer

DSI electronic ballast


12
L
11
N
10
D1
9
D2
Incandescent lamps/HV halogen incandescent lamps
max. 300 VA

Group 2

Lamp control gear

Individual dimming of five luminaire groups


Easy to install
Components can be delivered separately or pre-fitted in the luminaire
Up to eight modules per infrared circuit

DSI control lines, max. length 50 m

SI transformer

DSI phase dimmer

DSI electronic ballast


L
N
D1
D2

D1
D2

Lamps

Up to 5 luminaire groups for each installation

Lamp control gear

24.06.2004

* Single-switch control

N 230 V/50 Hz

User control units

Group 2

Group 1

L
N
PE

The Lighting Handbook

max. 25 PCA, PHD, TEL

05_LUXMATELM_uk.qxd
9:40 Uhr

LUXMATE Basic IR

Dimming of luminaires by infrared remote control unit

Chapter 5 / 5

Seite 5

max. 25 PCA, PHD, TEL

05_LUXMATELM_uk.qxd

24.06.2004

9:40 Uhr

Seite 6

LUXMATE Basic Daylight DSI-TLC or DALI-TLC


Daylight-based control
for small rooms

(DALI-TLC available on request)

Applications

Single and team offices


Areas near windows in shopping centres
Classrooms
Corridors and passageways

0%

50 %

500 lx
artificial light
daylight

Arguments for your customers


Dims the lighting from 1001 %, based exactly on the daylight
available
Accurate window-light sensor rather than error-prone roomlight sensor
Energy savings of up to 75 %
Brightness level can be changed at any time using momentaryaction dimmer switches
Economically priced short pay-back period
Long lamp service life
Option to connect presence detector

6 / Chapter 5

The Lighting Handbook

See page 8 for sensor positioning!

LSD
light sensor

Control line
e.g. NYM 2 x 1.5 mm 2
max. length 100 m

DALI-TLC

Lamp control gear

PCA

Group I

10
9

12
11

up to 25 DSI electronic ballasts/Group II


up to 25 DALI electr. ballasts/Group II
12
L
11
N
D1
10
PCA
D2
9
Group II

L
N
D1
D2

up to 25 DSI electronic ballasts/Group I


up to 25 DALI electr. ballasts/Group I

Lamps

Fluorescent lamps T26/T16


TC-L/TC-DEL/TC-TEL

Fluorescent lamps T26/T16


TC-L/TC-DEL/TC-TEL

24.06.2004

Motion sensor/
Presence detector

On/Off
Dimming

Light-sensor line
e.g. NYM 2 x 1.5 mm2, max. length 100 m

Control units

DSI-TLC daylight-based control module


installed in luminaire/recessed into ceiling
L N
Se2 Se1
T1 T2
D2 D1
T3 T4
D4 D3
PD in
DSI-TLC

User control units


L Mains 230 V/50 Hz
N
PE

Daylight-based control
for small rooms

Conventional double
momentary-action
light switch G I G II

The Lighting Handbook

05_LUXMATELM_uk.qxd
9:40 Uhr

LUXMATE Basic Daylight DSI-TLC or DALI-TLC


(DALI-TLC available on request)

Chapter 5 / 7

Seite 7

05_LUXMATELM_uk.qxd

24.06.2004

9:40 Uhr

Seite 8

LUXMATE Basic Daylight DSI-TLE or DALI-TLE


Daylight-based control
for large rooms

(DALI-TLE available on request)

Applications
Open-plan offices
Manufacturing bays, warehouses, sports halls and gymnasiums
Supermarkets etc.
0%

50 %

80 %

Vertical sensor positioning


5m

4m

3 m 2.5 m

2m

1m
0m

1m

4m
5m
6m

Window height = 2.5 m


Horizontal sensor positioning
5m

4m

3m

2.5 m

2m

1m

0m
3m
2m
1m
0m
1m
2m
3m

Window width = 4.0 m

8 / Chapter 5

The Lighting Handbook

3m

Arguments for your customers: see


page 6!

2m

L
N
PE

Dimming using
conventional double
momentary-action
light switch

Control line
e.g. NYM 2 x 1.5 mm 2
max. length 250 m

Control units

DSI-TLE
DSI-TLE
DALI-TLE Se I II III
daylightbased
control
module
for 3 groups,
Auto/Man Down
installed in
L N On/Off Up
switch
cabinet
Insert jumper
between Up/Down
for single
momentaryaction switch

Light-sensor line
e.g. NYM 2 x 1.5 mm 2
max. length 250 m

Alternative: Connect the Up and


Down terminals together with a
jumper when using a single
momentary-action switch.

LSD light sensor


mounted on ceiling

User control units

Lamp control gear

Lamps

up to 100 DSI electr. ballasts/Group I, II, III


up to 64 DALI electr. ballasts/Group I, II, III 12
L
11
N
D1
10
PCA
D2
9
Group III

Fluorescent lamps T26/T16


TC-L/TC-DEL/TC-TEL

up to 100 DSI electr. ballasts/Group I, II, III Fluorescent lamps T26/T16


TC-L/TC-DEL/TC-TEL
up to 64 DALI electr. ballasts/Group I, II, III
12
L
11
N
D1
10
PCA
D2
9
Group II

up to 100 DSI electr. ballasts/Group I, II, III Fluorescent lamps T26/T16


TC-L/TC-DEL/TC-TEL
up to 64 DALI electr. ballasts/Group I, II, III
12
L
11
N
D1
10
PCA
D2
9
Group I

24.06.2004

On/Off
Automatic/Manual

Conventional
serial switch

The Lighting Handbook

05_LUXMATELM_uk.qxd
9:40 Uhr

LUXMATE Basic Daylight DSI-TLE or DALI-TLE

Daylight-based control for large rooms

Chapter 5 / 9

Seite 9

10 / Chapter 5
1

10
1

1RUK, 4A2)
4RUKS, 4 x 16A3)

ANAS

1
1

Control
unit

DALI
loads
1

Calling up/changing scenes


Download/upload via RS 232
interface
Addressing, scenes, shows, time entries

On/Off, dimming,

On/Off, dimming,
16 x 16 room-based lighting scenes
static or Active Light
Timed lighting scenes

EMOTION
Touch

Momentaryaction switch1)
Motion sensor1)
EMOTION
Touch
PC software

Function

Operation

24.06.2004

The Lighting Handbook

Dimming/
Control gear/
switching range dimmer
General-purpose
1000 %
EMOTION-APDX
lamps, PAR lamps,
500 VA, 1,000 VA
Halogen incandesSDK-AN-06, 1,400 VA
cent lamps
SDK-AB-05, 1,200 VA
Low-voltage halogen 1000 %
DALI TE one4all
incandescent lamps
105 VA, 150 VA
Discharge lamps
HIT 100 %
Electronic/
SDW-T 100 % conventional ballast
HS 30, 50, 100 %
HM 50, 100 %
Induction lamps
QL 100 %
Switchable
100 %
fluorescent lamps
Dimmable
T16/T26 1001 % DALI electronic ballast
fluorescent lamps TC 1003 %
(LDE-DO)

Lamps

(2 x 64 DALI addresses, 2 x 99 DALI loads)

Dimming and switching with LUXMATE Emotion + optional integration of ONLITE Local Check

05_LUXMATELM_uk.qxd
9:40 Uhr
Seite 10

1000 %
100 %

70 %

STARFLEX QT
STARFLEX HIT

Escape-sign
luminaires (T, TC)
Emergency
luminaires (T, TC)
3

1
1
1
1
1
1

ANAS
4RUKS, 4 x 16A
4RUKS, 4 x 16A
ANAS
ANAS

3) available on request
4) details in ONLITE product brochure
5) includes bus supply, EMOTION BV bus supply not required

dimmable transf. 110 V


electronic ballast 150 W
conventional ballast 250 W
colour wheel
dimming wheel
Emergency lighting electr.
ballast (Local Check)
DALI electronic ballast +
emergency lighting
electronic ballast
(Local Check NT1-NT3)

LED K210/K211 25 W

1) via EMOTION SDED, 5 DALI loads


2) not for Discharge lamps, otherwise can only be used
as contactor relay

Depends on
wattage4)

1000 %

LED

The Lighting Handbook

9:40 Uhr

Local Check
Controller3)
PC software

6) with ONLITE Local Check power supply and printer


7) with ONLITE Local Check power supply and GSM module

Download/upload via RS 232


interface
Configuration data, test log book

24.06.2004

ONLITE SB 128 Non-maintained/maintained mode can


Local Check
be set for each luminaire
Random test function
Controller5)
Programmable function test/duration test
Test log book function (printable6))
Alarm output (buzzer, relay contact 24 V,
GSM, SMS7))

05_LUXMATELM_uk.qxd

Chapter 5 / 11

Seite 11

05_LUXMATELM_uk.qxd

24.06.2004

9:40 Uhr

Seite 12

LUXMATE EMOTION Lighting control system


Operation/supply
L Mains 230 V/50 Hz
N
PE

EMOTION Touch
COM T 1 T 2 COM T 3

COM T 4

L
N

max. 0.25 m,
cable included in supply
DA DA DA DA

LSD*
LM-CS(X)*
light sensor control point

COM T 1 T 2 T 3 T 4

EKXP installation box


(please order separately)

DA DA DA DA
L
N

EMOTIONSDED
DA DA (5 DALI loads)

Line 1:
DALI control line
e.g. NYM 2 x 1.5 mm 2
max. length 300 m
max. 64 users (addresses)
99 DALI loads

DA DA

Line 2:
DALI control line
e.g. NYM 2 x 1.5 mm 2
max. length 300 m
max. 64 users (addresses)
99 DALI loads

ONLITE SB 128
LOCAL CHECK controller,
integral bus supply

Use EMOTION BV bus supply if


ONLITE not included in system

Cable lengths of DALI control line


Conductor cross-sections
DALI control line

Cable length

2
2
2
2

116
174
232
300

x
x
x
x

0.50
0.75
1.00
1.50

mm 2
mm 2
mm 2
mm 2

m
m
m
m

Switching lamps using LUXMATE EMOTION


Lamp type

Safe installed load


EMOTION 1 RUK

EMOTION 4RUKS

A, PAR, QT
T16/T26 with low-loss ballast
(parallel p.f. corrected)
TC with low-loss ballast
(parallel p.f. corrected)
T16/T26/TC with electr. ballast
LV with transformer
HIT, SDW-T, HS, HM

500 W
250 W

4 x 2,000 W
4 x 920 W

250 W

4 x 800 W

30A for 0.5 s max.


30A for 0.5 s max.

4 x 10 A
4 x 10 A
4 x 800 W

12 / Chapter 5

DA DA

05_LUXMATELM_uk.qxd

24.06.2004

9:40 Uhr

Lighting/emergency lighting

L
N
DA
DA
DA
DA

Fluorescent lamps T26/T16 12


TC-L/TC-DEL/TC-TEL 11

DALI electronic ballast (1 DALI load)


K
K'
EMOTION-1RUK
(10 DALI loads)

10
9

e.g. HIT luminaires

K1
K 1'
L
K2
N
K 2'
DA
K3
DA
EMOTION 4RUKS K 3'
K4
(1 DALI load)
K 4'
L
L'
N
N
DA
DA
Incandescent lamps/
Emotion APD (1 DALI load) HV halogen incandescent lamps
max. 2 m
DA
DA

DA
DA

DALI-TE (1 DALI load)

LV halogen incandescent lamps


R
G
B

LED luminaires

DALI LED converter


(1 DALI load)
LN

0/110 V units
e.g. STARFLEX
fibre optics
(1 DALI load)

DA
DA
EMOTION ANAS
(1 DALI load)
L
N
DA
DA

TECTON trunking
PROTON TEC*
SPIRIT TEC

L
N
DA
DA DALI-DSI*

D1
D2
D1
D2

25 DSI luminaires
25 DSI luminaires

L
N
DA
DA Locally supplied emergency luminaire
LOCAL CHECK NT1-NT3
(3 DALI loads)
DA
DA
L
N

Escape-sign luminaire
LOCAL CHECK
(1 DALI load)

* available on request

Chapter 5 / 13

Seite 13

05_LUXMATELM_uk.qxd

24.06.2004

9:40 Uhr

LUXMATE Professional (selection)


Commissioning/user control units
LM-PFC
Installation-specific
operation
LM-CG/LM-EG
Multi-room solution
LM-MPA/LM-CPA
Single-room solution

B 1 , B 2 , L, N

LM-CS(X)
control point

RS-232 link to AV system


ASCII plain text protocol
B 1, B 2

B 1 , B 2 , L, N

LM-IRB

IRED

IRS
B1, B2, L, N
24VDC
24VAC

LM-SI03

B1, B2 L, N
230
VAC

L, N

B1, B2

LM-SDED
LM-SWED

Bus

For dimming and


switching individual
luminaire groups

Mains
DSI- or
DALI control line
Sensor cable

Room management/central control/automation


Screen
B1, B2

B1, B2

LM-RV

Blinds
Motor 1
K1

B1, B2

LM-2LSE

Partition
switch

L, N

B1 , B2

B1 , B2

LM-2FSE
L, N

Window

LM-2JSM

L, N

L, N

Motor 1

Blinds
Motor 2

B1, B2

LM-ZSM
L, N

Motor 2

Timer control

LM-iZSQ
L, N

Sequence
automation

Window

B1, B2

LM-BVS35
L, N

14 / Chapter 5

Seite 14

05_LUXMATELM_uk.qxd

24.06.2004

9:40 Uhr

Lighting management
HIT/HST/HME lamps

LM-2RUK
L, N

K', K

B1 , B2

L, N

Electronic/conventional ballast for


discharge lamps

Switching

LM-DSI
L, N
B1 , B 2

up to 10 DSI electronic ballasts


D 1 , D2

D 1 , D2
L, N

Fluorescent lamps

DSI dimming
up to 10 DSI electronic ballasts
up to 10 DALI electronic ballasts
LM-2TL
LM 2TL DALI

L, N
D1, D2

L, N

D1, D2

B1 , B2

D1, D2

Fluorescent lamps
LSD
option to connect a daylight sensor
to the LM-STL or LM-2TL/DALI
up to 10 DSI electronic ballasts
up to 10 DALI electronic ballasts

D 1 , D2
L, N

Daylight-based dimming (DSI or DALI)


D1, D2

DALI-PCA

Fluorescent lamps

DALI-APD

Incandescent lamps/
HV halogen incandescent lamps

DALI-TEL

LV halogen incandescent lamps

D1, D2

LM-DALI
L, N

D1, D2

B1 , B 2

up to 64 ballasts in
16 groups

D1, D2

D1, D2

DALI LED converter

LED luminaires

DALI dimming

ONLITE interface, emergency lighting

LM DALI-S

SB 128
local check
CTP

Local check
repeater

locally supplied LOCAL CHECK


emergency luminaire
LOCAL CHECK
escape-sign
luminaire

ONLITE interface for emergency lighting/local supply

Chapter 5 / 15

Seite 15

05_LUXMATELM_uk.qxd

24.06.2004

9:40 Uhr

Seite 16

ONLITE emergency lighting system


(applicable to U.K.)
EMERGENCY LIGHTING

Standby
lighting

Emergency lighting

anti-panic
lighting

for escape
routes and
rooms

for workplaces with


particular risk

Types of Zumtobel Staff emergency


luminaires

16 / Chapter 5

central test:
Monitoring
of up to
4x64 luminaires by
e-DALI; function test and duration test are programmable
Test log book listing

Group or
central
battery
Central
monitoring
Automatic
testing
Test log
book listing

The Lighting Handbook

local check:
Autotest, not
monitored

local solo:
Local battery
Function
display
Manual
test, not
monitored

ONLITE central

ONLITE local

05_LUXMATELM_uk.qxd

24.06.2004

9:40 Uhr

Routine Testing and Maintenance of Emergency Lighting


It is important that equipment is properly tested and maintained if it is
to function correctly when required in an emergency. All emergency
lighting should be regularly checked and maintained by a competent
person in accordance with manufacturers recommendations. The following table shows the routine testing of emergency lighting equipment
that should take place.
Daily

Visually check that all maintained lamps are operating


and that all system healthy indicators on Central Power
Supply Systems (Central Battery Systems) are illuminated.
Check that any system fault recorded is given urgent
attention and record all corrective actions in the log
book provided.

Monthly Check all luminaries and other emergency lighting


equipment is in a good condition, all lamps and light
controllers are clean, undamaged and not blackened.
Briefly test all emergency lighting equipment by simulating a failure of the normal lighting supply. The test
should not exceed a quarter of the equipment rated
duration. Check that all equipment functions correctly.
Check that, upon restoring the mains supply, all supply
healthy indicators are again illuminated.
Six
Carry out the inspection and testing as described in
monthly
the monthly test schedule, but conduct a test of the
equipment for one third of its rated duration.
Annually* A full system test should be conducted by a competent
service engineer including a full rated duration test of
the system.
Compliance of the installation and system with the
requirements of BS5266/BSEN 1838 should be considered and documented.

The Lighting Handbook

The results of all testing and any necessary corrective action should
be recorded in a log record held on site which shall be available if
required, for inspection by any authorised person.
* The publication of prEN50172 will change the requirements of
BS5266 Part1. prEN50172 changes the requirements for the first
three years of self-contained luminaires to be annual full duration
tests.

Chapter 5 / 17

Seite 17

05_LUXMATELM_uk.qxd

24.06.2004

9:40 Uhr

Seite 18

Risk Assessment Checklist for Emergency Lighting


Installations
Risk assessment of the following parameters to provide the required
level of emergency lighting when the occupants of premises evacuate in
an emergency could mean the difference between life and death.

6.g),
6.h)

6.j

6.d),
6.e), 7

18 / Chapter 5

Does Not Comply

Where artificial lighting is


installed, is emergency lighting
fitted on the escape routes and
in open areas?
Is emergency lighting and fire
safety signage on the existing
escape routes adequate to
permit occupants to reach a
place of safety within 23
minutes?
Is emergency lighting installed
in all open areas
of greater than 60m2
If there are special risks e.g.
flammable materials used in
processes, or areas having
restricted access, is emergency
lighting fitted?

The Lighting Handbook

Complies

ICEL B55266Pt1
1008
Clause
Section
Ref
Ref

Not Applicable

E1 Assessment of Escape Routes

05_LUXMATELM_uk.qxd

24.06.2004

9:40 Uhr

The Lighting Handbook

11

Complies

ICEL B55266Pt1
1008
Clause
Section
Ref
Ref

Does Not Comply

E2 Assessment of Existing Emergency Lighting


Luminaires and Escape Route Signs

Are the existing luminaires clean,


undamaged and are all lamps intact,
operational and unblackened?
Are luminaire housings on escape
routes fire retardant in accordance
with BS5266?
ICEL Registered products automatically comply, for others refer to
original equipment manufacturer.

9.4

6.10.2

9.3

9.1

Do the luminaires operate for the


required emergency duration? The
minimum duration is 1 hour, however in premises where evacuation
is not immediate, following a normal
mains failure, 3 hours is required.
Note: After fully discharging the
system allow 24 hours to recharge
before re-occupying the building.

9.2

6.10.1

9.3

9.2

Are the fittings sited in their correct


operating environment, e.g. for
temperature and I.P. rating?
Are the luminaires of the correct
system type (e.g. Non maintained/
maintained/combined)?

Chapter 5 / 19

Seite 19

05_LUXMATELM_uk.qxd

24.06.2004

9:40 Uhr

Seite 20

6g),8

6.j),4

Do the sign legends comply with the


Health and Safety (Safety Signs and
Signals) Regulations 1996?
5.6,.6.9.3 Are there signs that clearly show the
emergency escape routes from any
position within the premises?
5.6
Are all exits marked and directions
of travel indicated?

6.9.3

8.1

5.6

20 / Chapter 5

Are the signs illuminated internally


or from an external source when the
normal lighting supply fails?
Is the size of each sign correct for
the viewing distances?

The Lighting Handbook

Complies

ICEL B55266Pt1
1008
Clause
Section
Ref
Ref

Does Not Comply

E3 Assessment of Fire Safety Signs

05_LUXMATELM_uk.qxd

24.06.2004

9:40 Uhr

9.1

6.7

Are the luminaires positioned at


all points of emphasis

ICEL
1006

Near stairs, such that all reads


receive direct light?

ICEL
1006

Near changes of level?

ICEL
1006

Near each change of direction?

ICEL
1006

Near each intersection of


corridors?

ICEL
1006

To illuminate Exit doors?

ICEL
1006

Near each piece of fire fighting


equipment or manual call point?

ICEL
1006

Outside and near to each final


exit to a point of safety?

ICEL
1006

Near each first aid point?

6.c),
9.1

5.3.2

Does Not Comply

Complies

ICEL B55266Pt1
1008
Clause
Section
Ref
Ref

Not Applicable

E4 Siting of Luminaires

Are luminaires sited along the


permanently unobstructed
escape routes at the correct
spacings, positioned to achieve
the required minimum level of
illuminance of 0.2 Lux?

6.d), 5.2,5.3 + Are luminaires sited along


9.1 BS5266Pt7/ escape routes which may
BSEN1838 become obstructed, positioned
to achieve a minimum level of
illuminance of 1 Lux?

The Lighting Handbook

6.c),9.1

5.2 +
Are luminaires sited along the
BS5266Pt7/ escape routes which may be
BSEN1838 utilized by the very young,
elderly, disabled or partially
sighted, positioned to achieve
a level of illuminance of at least
1 Lux (possibly significantly
higher, depending on the degree
of impairment?

Chapter 5 / 21

Seite 21

05_LUXMATELM_uk.qxd

24.06.2004

9:40 Uhr

Seite 22

6.j),9.1

9.1

Does Not Comply

Complies

ICEL B55266Pt1
1008
Clause
Section
Ref
Ref

Not Applicable

E4 Siting of Luminaires (continued)

5.3.3 + Are luminaires in the open


BS5266Pt7/ areas of greater than 60 m2, at
BSEN1838 the correct spacing to achieve
the illuminance of 0.5 Lux minimum?
6.3
Are a minimum of 2 luminaires
contributing to the emergency
illumination in each lighting
compartment on the escape
route, to ensure that the area is
not plunged into darkness if a
luminaire fails?

ICEL
1006

6.8.3

Lift cars?

ICEL
1006

6.8.5

Toilet facilities and other open


tiled areas exceeding 8 m2
floor area and all toilets for the
disabled?

ICEL
1006

6.8.4

Escalators?

ICEL
1006

6.8.4

Motor generator, control or plant


rooms?

ICEL
1006

6.8.7

Covered car parks along


pedestrian routes?

ICEL
1006

Near each first aid point?

6.e),7

Are high risk areas illuminated


at 10 % of normal illuminance
or at least 1.5 Lux, in an emergency, with a response time
of 0.5 seconds or less?

22 / Chapter 5

The Lighting Handbook

Are additional luminaires


provided in the following
locations

05_LUXMATELM_uk.qxd

24.06.2004

9:40 Uhr

App.D

12.4

9.4

6.10.1

9.4

6.10.2

Complies

ICEL B55266Pt1 Section not applicable


1008
Clause
Section
Ref
Ref

Does Not Comply

E5 Self-Contained Emergency Luminaires and Sign

Are the batteries being charged


(indicator lamp on)?
Do the luminaires comply with all
relevant product standards for
escape routes?
ICEL marked luminaires automatically comply. In particular ICEL
signifies fire retardant housings and
verified photometric data.

9.6

The Lighting Handbook

App.D

12.4

Complies

ICEL B55266Pt1 Section not applicable


1008
Clause
Section
Ref
Ref

Does Not Comply

E6 Central Power Supply Systems (Central Battery Systems)

Do the Central Power Supply


Systems (Central Battery Systems)
comply with prEN 50171 or does a
competent person declare the
systems are working correctly?
Is the battery charger functioning
correctly?

Chapter 5 / 23

Seite 23

05_LUXMATELM_uk.qxd

24.06.2004

9:40 Uhr

Seite 24

6.2

9.6

Complies

Does Not Comply

8.2.13

Does Not Comply

Not Applicable

ICEL B55266Pt1
1008
Clause
Section
Ref
Ref

Complies

E7 Wiring of Luminaires

Are luminaires permanently


wired?
Are the non maintained luminaires fed from the same final
sub-circuit as the local lighting?
(A qualified electrician can usually check by removing the local
lighting fuse and verifying the
emergency lighting operation)

8.3.5.2. + Is the volt drop to Central


IEE Regs Battery luminaires within 10%
of the nominal voltage and are
luminaires connected in fire
protected cable as defined in
BS5266?

E8 Records and Documentation


ICEL B55266Pt1
1008
Clause
Section
Ref
Ref

Has a risk assessment verification


certificate been provided?

10

11.3

Are the entries made in the log book


correct?

10

3.3

Are up-to-date drawings available


and correct?

24 / Chapter 5

The Lighting Handbook

App.E

05_LUXMATELM_uk.qxd

24.06.2004

9:40 Uhr

10
10

The Lighting Handbook

App. D

Not Applicable

Complies

ICEL B55266Pt1
1008
Clause
Section
Ref
Ref

Does Not Comply

E9 Routine Maintenance

Is a procedure in place to
rectify test failures and provide
spares?
8.3.3, 12.4 Is a regime of regular testing
set up?
12.4

Are routine tests completed


according to the requirements
in BS5266?
Central Power Supply Systems
(Central Battery Systems).
Where applicable, are the battery electrolyte levels and specific
gravities satisfactory?

Chapter 5 / 25

Seite 25

00_INHALTSVER_uk.qxd

24.06.2004

10:21 Uhr

Seite 2

06_QUICKPLAN_uk.qxd

24.06.2004

9:43 Uhr

Chapter 6

Quickplan calculating the number of


luminaires required
The five steps of lighting design . . . . . . . . . . . . . . . . .
PANOS HF/HG 175/200/250 2-lamp . . . . . . . . . . . . .
PANOS HM 175/200/250 2-lamp . . . . . . . . . . . . . . . .
PANOS LF/LG 175/200/250 2-lamp . . . . . . . . . . . . . .
PANOS LM 175/200/250 2-lamp . . . . . . . . . . . . . . . .
QUARTOS CQF 1-/2-lamp . . . . . . . . . . . . . . . . . . . . .
MIRAL/MIREL RAS/RES BWS 2-/3-/4-lamp . . . . . . .
MIREL FEC/FED 1-/4-lamp M625 . . . . . . . . . . . . . . . .
RTX II C bzw. D 1-/2-lamp . . . . . . . . . . . . . . . . . . . . .
MELLOW LIGHT IV louvre (surface-mounted/recessed)
MELLOW LIGHT IV grid-mesh controller (surfacemounted/recessed) . . . . . . . . . . . . . . . . . . . . . . . . . . .
LIGHT FIELDS recessed M625 . . . . . . . . . . . . . . . . . .
LIGHT FIELDS surface-mounted . . . . . . . . . . . . . . . . .
LIGHT FIELDS A-ID . . . . . . . . . . . . . . . . . . . . . . . . . . .
LA TRAVE KC T16 2-lamp . . . . . . . . . . . . . . . . . . . . .
LA TRAVE KC T16 3-lamp . . . . . . . . . . . . . . . . . . . . .
CLARIS MSD-ID 1-/2-lamp . . . . . . . . . . . . . . . . . . . . .
AERO USN/UGN-ID 2-lamp . . . . . . . . . . . . . . . . . . . . .
OREA GZ-ID 2-lamp . . . . . . . . . . . . . . . . . . . . . . . . . .
SPHEROS D-ID/C-ID T16 EVG 1-/2-lamp . . . . . . . . . .
TECTON(-I) + RW T16 1-/2-lamp . . . . . . . . . . . . . . . .
TECTON(-I) + RW T16 1-/2-lamp . . . . . . . . . . . . . . . .
TECTON-IP louvre T16 1-/2-lamp . . . . . . . . . . . . . . . .
ZX/XR/XT 1-/2-lamp T26 . . . . . . . . . . . . . . . . . . . . . .
COPA I 250 W . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COPA I 400 W . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COPA D 32/42/57/85 W . . . . . . . . . . . . . . . . . . . . . .
COPA D 70/150 W . . . . . . . . . . . . . . . . . . . . . . . . . .
COPA D 250 W QT . . . . . . . . . . . . . . . . . . . . . . . . . .
COPA A-B HIT/HST 1-/2-lamp . . . . . . . . . . . . . . . . . .
COPA A-B HIT/HST 1-lamp . . . . . . . . . . . . . . . . . . . . .
COPA A-N HME 1-lamp . . . . . . . . . . . . . . . . . . . . . . .
COPA A-B, A-T, A-ASY HST 1-lamp . . . . . . . . . . . . . . .
COPA A-ASY HIT/HST 1-lamp . . . . . . . . . . . . . . . . . . .
FZ/FT/IFP/TOL-TBC 1-lamp, 58 W . . . . . . . . . . . . . . .
FZ/FT/IFP/TOL-TBC 1-lamp, 36 W . . . . . . . . . . . . . . .
FZ/FT/IFP/TOL 2-lamp, 58 W . . . . . . . . . . . . . . . . . . .
FZ/FT/IFP/TOL 2-lamp, 36 W . . . . . . . . . . . . . . . . . . .
CHIARO FTR390/FTR680 1-/2-lamp . . . . . . . . . . . . . .
RAIN 1-/2-lamp . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41

Seite 1

06_QUICKPLAN_uk.qxd

24.06.2004

9:43 Uhr

Seite 2

The five steps of lighting design


The lighting design process can be simplified into five steps:

Determine lighting REQUIREMENTS


(see chapter on Recommended values for indoor lighting)

SELECT lamps and luminaires


(see Lamps and Luminaires chapters)

Calculate NUMBER of luminaires required


(using the Quickplan graphs below)

POSITION the luminaires


(axial spacing values are noted in the Quickplan diagrams)

ANALYSE the results (technical lighting


features, costs)
(for costs see Economic efficiency calculation chapter)

Efficiency method
The Quickplan graphs have been calculated using the efficiency
method.
The following formulae can be used to give an approximate
figure for the mean illuminance and the number of luminaires
required.
n z L WF B
A

n=

Em = mean illuminance
z = number of lamps per luminaire
L = luminous flux of the lamp
B = utilization factor (= LB R )
LB = luminaire efficiency
R = room utilization factor

Em A
z L WF B
n = number of luminaires
WF = maintenance factor
A = floor area

Standard UGR values and maintained luminance levels for


luminance limit angle (e.g. 65 or 75) all around the
luminaire
Correction factors for dark rooms and different ceiling heights
(no. of luminaires x factor)
Maintenance factor uses an assumed value (graphs calculated
using MF = 0.8)
Uniformity: max. luminaire spacing to achieve a uniformity
greater than or equal to 0.7

The Lighting Handbook

Em =

140
130
120
110
100
90
80
70
60
50
40
30
20
10
40

60

100

120

Floor area m2

80

140

160

2/32 W TC-T (250)

2/26 W TC-D (250)

2/18 W TC-D (200)

180

200

86
80
72
66
60
54
48
42
36
30
24
18
12
6

300 lx

up to 50 m2
1.2
1.4
1.6

Axial spacing up to 2.9 m (2/13, 2/18),


up to 2.8 m (2/26, 2/32)

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.78
2,000 h
1 year
2 years

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.1
Ceiling
Floor area

24.06.2004

20

2/13 W TC-D (175)


2/18 W TC-D (200)
2/26 W TC-D (250)
2/32 W TC-T (250)

UGR_axial UGR_transv.
65
17.3
17.3
< 1000 cd/m2
17.0
17.0
< 1000 cd/m2
15.8
15.8
< 200 cd/m2
16.2
16.2
< 200 cd/m2

2/13 W TC-D (175)

PANOS HF/HG 175/200/250 2-lamp


X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

Ceiling height: 3 m

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:43 Uhr

Chapter 6 / 3

Seite 3

20

40

60

100

120

Floor area m2

80

140

160

180

2/26 W TC-DEL (250)

2/18 W TC-DEL (200)

200

86
80
72
66
60
54
48
42
36
30
24
18
12
6

300 lx

up to 50 m2
1.2
1.4
1.6

Axial spacing up to 3.1 m/2.9 m (2/26 W)

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.78
2,000 h
1 year
2 years

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.1
Ceiling
Floor area

24.06.2004

The Lighting Handbook

4 / Chapter 6
2/13 W TC-D (175)
2/18 W TC-D (200)
2/26 W TC-D (250)

UGR_axial UGR_transv.
65/75
17.6
17.6
75< 200 cd/m2
18.6
18.6
75< 1000 cd/m2
16.0
16.0
65< 1000 cd/m2

2/13 W TC-DEL (175)

PANOS HM 175/200/250 2-lamp


X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

Ceiling height: 3 m

500 lx

140
130
120
110
100
90
80
70
60
50
40
30
20
10

06_QUICKPLAN_uk.qxd
9:43 Uhr
Seite 4

140
130
120
110
100
90
80
70
60
50
40
30
20
10
40

60

100

120

Floor area m2

80

140

160

180

2/32 W TC-T (250)

2/26 W TC-D (250)

2/18 W TC-D (200)

200

86
80
72
66
60
54
48
42
36
30
24
18
12
6

300 lx

up to 50 m2
1.2
1.4
1.6

Axial spacing up to 3.7 m (2/18 W), up to


4 m (2/13 W, 2/26 W), up to 4.4 m (2/32 W)

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.78
2,000 h
1 year
2 years

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.1
Ceiling
Floor area

24.06.2004

20

2/13 W TC-D (175)


2/18 W TC-D (200)
2/26 W TC-D (250)
2/32 W TC-T (250)

UGR_axial UGR_transv.
75
21.2
21.2
< 200 cd/m2
20.5
20.5
< 1000 cd/m2
21.7
21.7
< 200 cd/m2
24.5
23.5

2/13 W TC-D (175)

PANOS LF/LG 175/200/250 2-lamp


X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

Ceiling height: 3 m

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:43 Uhr

Chapter 6 / 5

Seite 5

20

40

60

100

120

Floor area m2

80

140

160

180

2/32 W TC-TEL (250)

2/26 W TC-DEL (250)

2/18 W TC-DEL (200)

200

86
80
72
66
60
54
48
42
36
30
24
18
12
6

300 lx

up to 50 m2
1.2
1.4
1.6

Axial spacing up to 4 m (2/13 W, 2/18 W),


up to 4.7 m (2/26 W,2/32 W)

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.78
2,000 h
1 year
2 years

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.1
Ceiling
Floor area

24.06.2004

The Lighting Handbook

6 / Chapter 6
2/13 W TC-DEL (175)
2/18 W TC-DEL (200)
2/26 W TC-DEL (250)
2/32 W TC-TEL (250)

UGR_axial UGR_transv.
75
20.9
20.9
20.7
20.7
< 1000 cd/m2
22.1
22.1
22.7
21.9

2/13 W TC-DEL (175)

PANOS LM 175/200/250 2-lamp


X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

Ceiling height: 3 m

500 lx

140
130
120
110
100
90
80
70
60
50
40
30
20
10

06_QUICKPLAN_uk.qxd
9:43 Uhr
Seite 6

60

80

100

120

140

160

200

up to 50 m2
1.2
1.4
1.6

Axial spacing up to 4 m (1/42 W, 2/32 W),


up to 3.7 m (2/26 W)

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.78
2,000 h
1 year
2 years

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.1
Ceiling
Floor area

24.06.2004

Floor area m2

180

18

24

30

2/32 W

2/26 W

1/42 W

10

40

UGR_axial UGR_transv.
65
17.5
17.5
< 1000 cd/m2
16.1
16.1
< 200 cd/m2
18.5
18.5
< 1000 cd/m2

36

300 lx

12

20

CQF 1/42 W TC-T


CQF 2/26 W TC-D
CQF 2/32 W TC-T

Ceiling height: 3 m

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

QUARTOS CQF 1-/2-lamp

20

30

40

50

60

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:44 Uhr

Chapter 6 / 7

Seite 7

10

15

20

20

RAS/RES 2/54 W T16


RAS/RES 3/80 W T16
RAS/RES 4/54 W T16
RAS/RES 4/80 W T16

Ceiling height: 3 m

40

60

100

120

Floor area m2

80

UGR_axial UGR_transv.
16.4
19.5
14.6
18.0
15.8
19.3
16.2
19.7

140

160

180

4/80 W

4/54 W
3/80 W

2/54 W

MIRAL/MIREL RAS/RES - BWS 2-/3-/4-lamp

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

200

12

15

18

300 lx

up to 50 m2
1.2
1.4
1.6

Continuous row spacing up to 3.8 m

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.78
6,000 h
1 year
2 years

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.1
Ceiling
Floor area

24.06.2004

The Lighting Handbook

8 / Chapter 6

25

30

500 lx

06_QUICKPLAN_uk.qxd
9:44 Uhr
Seite 8

20

FEC 1/54 W T16


FEC 2/28 W T16
FEC 2/35 W T16
FEC 2/49 W T16
FEC 4/14 W T16

Ceiling height: 3 m

40

60

100

65
< 1000 cd/m2
< 1000 cd/m2
< 1000 cd/m2
< 1000 cd/m2
< 1000 cd/m2

120

Floor area m2

80

UGR_axial UGR_transv.
17.7
17.9
16.3
15.7
14.6
14.0
15.4
14.8
16.1
15.5

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

140

MIREL FEC/FED 1-/4-lamp M625

160

180

2/49 W

2/35 W

2/28 W

1/54 W
4/14 W

200

12

18

24

30

36

300 lx

up to 50 m2
1.2
1.4
1.6

Continuous row spacing up to 4.3 m


(1/54 W) or 4.7 m

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.78
6,000 h
1 year
2 years

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.1
Ceiling
Floor area

24.06.2004

10

20

30

40

50

60

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:44 Uhr

Chapter 6 / 9

Seite 9

10

20

30

40

20

RTX2 1/35 W + D
RTX2 1/49 W + D
RTX2 1/54 W + D
RTX2 2/35 W + D
RTX2 2/54 W + D

Ceiling height: 3 m

40

60

100

65
< 200 cd/m2
< 200 cd/m2
< 200 cd/m2
< 1000 cd/m2
< 1000 cd/m2

Floor area m2

80

UGR_axial UGR_transv.
15.3
15.8
16.4
16.8
17.6
18.1
17.2
17.8
18.6
19.2

120

140

RTX II C or D 1-/2-lamp
X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

160

180

2/54 W

2/35 W

1/54 W

1/49 W

1/35 W

200

12

18

24

30

36

300 lx

up to 50 m2
1.2
1.4
1.6

Continuous row spacing up to 4.3 m


1-lamp, up to 4 m 2-lamp

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.78
6,000 h
1 year
2 years

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.1
Ceiling
Floor area

24.06.2004

The Lighting Handbook

10 / Chapter 6

50

60

500 lx

06_QUICKPLAN_uk.qxd
9:44 Uhr
Seite 10

20

40

60

100

120

Floor area m2

80

UGR_axial UGR_transv.
65
ML IV A AC 2/35 T16
13.7
13.0
< 1000 cd/m2
ML IV A AC 2/49 T16
14.4
14.1
< 1000 cd/m2
ML IV A AC 2/54 T16
15.3
14.9
< 1000 cd/m2
ML IV B EC 1/55 TC-L M625
16.4
14.8
< 1000 cd/m2
ML IV B EC 2/24 T16 M625
16.7
14.7
< 1000 cd/m2
ML IV A EC 2/54 T16 M625
16.4
16.2
< 1000 cd/m2

Ceiling height: 3 m

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

140

180

EC 2/54 W

160

AC 2/54 W

AC 2/35 W
AC 2/49 W

EC 1/55 W

EC 2/24 W

200

12

15

18

MELLOW LIGHT IV Louvre (surface-mounted/recessed) 300 lx

up to 50 m2
1.2
1.4
1.6

Continuous row spacing up to 4 m,


axial spacing up to 4.7 m (2/24 W)

Uniformity

Clean medium-sized room (T16)


Lamp operation
Cleaning of luminaires
Room maintenance

MF= 0.8
6,000 h
1 year
1 year

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.1
Ceiling
Floor area

24.06.2004

10

15

20

25

30

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:44 Uhr

Chapter 6 / 11

Seite 11

40

60

80

100

120

Floor area m

140

160

180

200

12

AB 2/49 W

AB 2/54 W

AB 2/35 W

15

EB 2/54 W

EB 1/55 W

EB 2/24 W

20

UGR_axial UGR_transv.
18.9
16.1
19.4
16.7
20.3
17.5
20.4
19.1
20.0
18.6
19.8
19.9

18

300 lx

10

15

20

ML IV A AB 2/35 W T16
ML IV A AB 2/49 W T16
ML IV A AB 2/54 W T16
ML IV B EB 1/55 W TC-L M625
ML IV B EB 2/24 W T16 M625
ML IV B EB 2/54 W T16 M625

Ceiling height: 3 m

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

MELLOW LIGHT IV Grid-mesh controller


(surface-mounted/recessed)
up to 50 m2
1.2
1.4
1.6

Continuous row spacing up, axial spacing


up to 5.4 m/4.7 m (2/54 W EB)

Uniformity

Clean medium-sized room (T16)


Lamp operation
Cleaning of luminaires
Room maintenance

MF= 0.8
6,000 h
1 year
1 year

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.1
Ceiling
Floor area

24.06.2004

The Lighting Handbook

12 / Chapter 6

25

30

500 lx

06_QUICKPLAN_uk.qxd
9:44 Uhr
Seite 12

20

L-FIELD 2/24 W T16


L-FIELD 2/28 W T16
L-FIELD 2/35 W T16
L-FIELD 4/14 W T16

Ceiling height: 3 m

40

60

100

120

Floor area m2

80

UGR_axial UGR_transv.
65
15.4
15.3
14.4
14.3
65< 1000 cd/m2
14.5
14.4
65< 1000 cd/m2
14.5
14.2
65< 1000 cd/m2

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

140

LIGHT FIELDS Recessed M625

160

180

2/35 W

2/28 W

4/14 W

2/24 W

200

12

18

24

30

36

300 lx

up to 50 m2
1.2
1.4
1.6

Continuous row spacing up to 3.7 m (2/28 W,


2/35 W), axial spacing up to 3.4 m (2/24 W, 4/14 W)

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.77
6,000 h
1 year
2 years

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.1
Ceiling
Floor area

24.06.2004

10

20

30

40

50

60

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:44 Uhr

Chapter 6 / 13

Seite 13

10

20

30

40

20

L-FIELDS A 2/28 W
L-FIELDS A 2/35 W
L-FIELDS A 4/14 W

Ceiling height: 3 m

40

60

100

120

Floor area m2

80

UGR_axial UGR_transv.
65
14.4
14.4
65< 1000 cd/m2
14.5
14.4
65< 1000 cd/m2
14.5
14.2
65< 1000 cd/m2

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

140

LIGHT FIELDS Surface-mounted

160

180

2/35 W

2/28 W

4/14 W

200

12

18

24

30

36

300 lx

up to 50 m2
1.2
1.4
1.6

Continuous row spacing up to 3.7 m (2/28 W,


2/35 W), axial spacing up to 3.4 m (4/14 W)

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.77
6,000 h
1 year
2 years

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.1
Ceiling
Floor area

24.06.2004

The Lighting Handbook

14 / Chapter 6

50

60

500 lx

06_QUICKPLAN_uk.qxd
9:44 Uhr
Seite 14

20

40

60

100

120

Floor area m2

80

140

160

2/49 W

180

200

12

up to 50 m2
1.2
1.4
1.6

Continuous row spacing up to 3.7 m (2/49 W,


2/54 W), axial spacing up to 3.1 m (4/24 W)

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.75
4,000 h
1 year
1 year

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.25
Ceiling
Floor area

24.06.2004

10

20

2/54 W

18
4/24 W

30

30

UGR_axial UGR_transv.
65
<13
<13
< 1000 cd/m2
<13
<13
< 1000 cd/m2
<13
<13
< 1000 cd/m2

36

300 lx

24

L-FIELDS A-ID 2/49 W


L-FIELDS A-ID 2/54 W
L-FIELDS A-ID 4/24 W

Ceiling height: 3 m

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

LIGHT FIELDS A-ID

40

50

60

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:44 Uhr

Chapter 6 / 15

Seite 15

10

20

20

40

60

100

120

Floor area m2

80

140

160

2/35 W

180

2/54 W

200

12

18

30

30

36

24

UGR_axial UGR_transv.
55/65
<13
<13
55< 1000 cd/m2
<13
<13
65< 1000 cd/m2

300 lx

40

2/35 W T16
2/54 W T16

Ceiling height: 3 m

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

LA TRAVE KC T16 2-lamp

up to 50 m2
1.2
1.4
1.6

Continuous row spacing up to 3.1 m

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.75
4,000 h
1 year
1 year

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.25
Ceiling
Floor area

24.06.2004

The Lighting Handbook

16 / Chapter 6

50

60

500 lx

06_QUICKPLAN_uk.qxd
9:44 Uhr
Seite 16

10

20

40

60

100

120

140

160

180

200

up to 50 m2
1.2
1.4
1.6

Continuous row spacing up to 4.2 m

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.75
4,000 h
1 year
1 year

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.25
Ceiling
Floor area

24.06.2004

Floor area m2

80

3/54 W

12

20
3/35 W

18

30

30

UGR_axial UGR_transv.
55/65
<13
<13
55< 1000 cd/m2
<13
<13
65< 1000 cd/m2

36

300 lx

24

3/35 W T16
3/54 W T16

Ceiling height: 3 m

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

LA TRAVE KC T16 3-lamp

40

50

60

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:44 Uhr

Chapter 6 / 17

Seite 17

10

20

20

40

60

100

Floor area m2

80

140

160

180

2/35 W

200

12

18
2/28 W

30

30

1/35 W

1/28 W

36

24

UGR_axial UGR_transv.
65
<13
<13
< 1000 cd/m2
<13
<13
< 1000 cd/m2
<13
<13
< 1000 cd/m2
<13
<13
< 1000 cd/m2

300 lx

40

1/28 W T16
1/35 W T16
2/28 W T16
2/35 W T16

Ceiling height: 3 m

120

CLARIS MSD-ID 1-/2-lamp


X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

up to 50 m2
1.2
1.4
1.6

Continuous row spacing up to 3.9 m


1-lamp, up to 4.4 m 2-lamp

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.77
4,000 h
1 year
1 year

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.25
Ceiling
Floor area

24.06.2004

The Lighting Handbook

18 / Chapter 6

50

60

500 lx

06_QUICKPLAN_uk.qxd
9:44 Uhr
Seite 18

20

2/28 W T16
2/54 W T16

Ceiling height: 3 m

40

60

100

120

Floor area m2

80

UGR_axial UGR_transv.
65
<13
<13
< 1000 cd/m2
<13
<13
< 1000 cd/m2

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

140

AERO USN/UGN-ID 2-lamp

160

180

2/54 W

2/28 W

200

12

18

24

30

36

300 lx

up to 50 m2
1.2
1.4
1.6

Continuous row spacing up to 5.6 m

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.75
4,000 h
1 year
1 year

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.25
Ceiling
Floor area

24.06.2004

10

20

30

40

50

60

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:44 Uhr

Chapter 6 / 19

Seite 19

10

20

40

60

100

120

Floor area m2

80

140

160

180

200

12

20
2/54 W

18

30

30

36

24

UGR_axial UGR_transv.
<13
<13

300 lx

40

2/54 W T16

Ceiling height: 3 m

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

OREA GZ-ID 2-lamp

up to 50 m2
1.2
1.4
1.6

Continuous row spacing up to 5.6 m

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.75
4,000 h
1 year
1 year

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.25
Ceiling
Floor area

24.06.2004

The Lighting Handbook

20 / Chapter 6

50

60

500 lx

06_QUICKPLAN_uk.qxd
9:44 Uhr
Seite 20

20

1/35 W T16
1/54 W T16
2/28 W T16
2/35 W T16
2/54 W T16

Ceiling height: 3 m

40

60

100

65/75
65< 1000 cd/m2
65< 1000 cd/m2
65< 1000 cd/m2
65< 1000 cd/m2
75< 1000 cd/m2

120

Floor area m2

80

UGR_axial UGR_transv.
<13
<13
<13
<13
<13
<13
<13
<13
14.6
13.5

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

140

160

180

2/54 W

2/35 W

2/28 W

1/54 W

1/35 W

SPHEROS D-ID/C-ID T16 Electronic ballast 1-/2-lamp

200

12

18

24

30

36

300 lx

up to 50 m2
1.2
1.4
1.6

Continuous row spacing up to 4.2 m

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.77
4,000 h
1 year
1 year

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.25
Ceiling
Floor area

24.06.2004

10

20

30

40

50

60

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:44 Uhr

Chapter 6 / 21

Seite 21

10

20

30

40

20

40

60

100

120

Floor area m2

80

UGR_axial UGR_transv.
TECTON 1/54 W T16 + RW
25.1
22.9
TECTON 1/54 W T16+PK+RW 25.5
20.9
TECTON 2/54 W T16 + RW
25.8
25.0
TECTON-I 2/54 W T16 + R
24.5
24.5

Ceiling height: 3 m

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

140

TECTON(-I) + RW T16 1-/2-lamp

160

180

2/54 W
-I 2/54 W

1/54 W

1/54 W+PK

200

12

18

24

30

36

300 lx

up to 50 m2
1.2
1.4
1.6

Axial spacing up to 5.6 m/4.8 m (-I 2/54 W +R)

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.80
6,000 h
1 year
1 year

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.1
Ceiling
Floor area

24.06.2004

The Lighting Handbook

22 / Chapter 6

50

60

500 lx

06_QUICKPLAN_uk.qxd
9:44 Uhr
Seite 22

20

40

60

100

120

Floor area m2

80

140

2/80 W

160

180

-I 2/80 W

200

12

up to 50 m2
1.2
1.4
1.6

Axial spacing up to 5.6 m/4.8 m (-I 2/80 W +R)

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.80
6,000 h
1 year
1 year

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.1
Ceiling
Floor area

24.06.2004

10

20

1/80 W

18
1/80 W+PK

30

30

36

300 lx

24

UGR_axial UGR_transv.
TECTON 1/80 W T16 + RW
25.4
23.2
TECTON 1/80 W T16+PK+RW 25.8
21.2
TECTON 2/80 W T16 + RW
26.1
25.3
TECTON-I 2/80 W T16 + R
24.8
24.8

Ceiling height: 3 m

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

TECTON(-I) + RW T16 1-/2-lamp

40

50

60

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:44 Uhr

Chapter 6 / 23

Seite 23

10

20

20

40

60

120

Floor area m2

80

140

160

180

2/80 W

2/54 W

1/80 W

200

12

18

1/54 W

30

30

36

24

UGR_axial UGR_transv.
19.4
18.8
19.7
19.2
21.2
20.5
21.5
20.9

300 lx

40

TECTON-IP 1/54 W T16


TECTON-IP 1/80 W T16
TECTON-IP 2/54 W T16
TECTON-IP 2/80 W T16

Ceiling height: 3 m

100

TECTON-IP Louvre T16 1-/2-lamp

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

up to 50 m2
1.2
1.4
1.6

Axial spacing up to 4.4 m

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.80
6,000 h
2 years
2 years

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.1
Ceiling
Floor area

24.06.2004

The Lighting Handbook

24 / Chapter 6

50

60

500 lx

06_QUICKPLAN_uk.qxd
9:44 Uhr
Seite 24

20

ZX 1/58 W T26
ZX 2/58 W T26
ZX 1/58 W T26 + XR
ZX 2/58 W T26 + XR
ZX 1/58 W T26 + XT
ZX 2/58 W T26 + XT

Ceiling height: 3 m

40

60

100

120

Floor area m2

80

UGR_axial UGR_transv.
26.7
22.3
25.8
19.2
23.6
22.0
25.5
22.3
< 13
20.3
18.9
21.4

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

140

1/58 W

180

2/58 W+XT

2/58 W

1/58 W+XT

160

2/58 W+XR

1/58 W+XR

ZX/XR/XT 1-/2-lamp T26

200

12

18

24

30

36

300 lx

up to 50 m2
1.2
1.4
1.6

Axial spacing at Rh = 6 m up to 16 m (ZX)/


14 m (XR)/6.5 m (XT)

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.80
6,000 h
1 year
1 year

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.1 for
(XR,XT)/1.25 for (ZX)
Ceiling
Floor area

24.06.2004

10

20

30

40

50

60

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:44 Uhr

Chapter 6 / 25

Seite 25

100

150

200

250

300

Floor area m2

350

400

450

500

12

1/250 W HSE

1/250 W HIE

15

18

50

UGR_axial UGR_transv.
65
1/250W HIE RAB 19000lm TST
15.2
15.2
< 1000 cd/m2
1/250W HSE RAB 25000lm TST 16.2
16.2
< 1000 cd/m2

Ceiling height: 6 m

300 lx

10

15

20

COPA I 250 W
X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

MF=0.79 (HIE)
4000 h
1 year
1 year

Axial spacing up to 5 m (TST)

Uniformity

Clean large room


Lamp operation
Cleaning of lumi. (IP65)
Room maintenance

Maintenance factor (MF)

Correction factors
Dark room (50/40/20): 1.1

MF=0.83 (HSE)
8,000 h
3 years
3 years

24.06.2004

The Lighting Handbook

26 / Chapter 6

25

30

500 lx

06_QUICKPLAN_uk.qxd
9:44 Uhr
Seite 26

50

100

150

250

300

Floor area m2

200

350

400

1/400 W

450

HSE**

1/400 W HSE*

500

MF=0.70 (HIE)
2000 h
1 year
1 year

* (Colour rendition class Ra > 60)


** (Colour rendition class Ra > 20)

Axial spacing up to 8.3 m

Uniformity

Clean large room


Lamp operation
Cleaning of lumi. (IP65)
Room maintenance

Maintenance factor (MF)

Correction factors
Dark room (50/40/20): 1.1

MF=0.83 (HSE)
8,000 h
3 years
3 years

24.06.2004

10

9
1/400 W HIE

15

15

18

300 lx

12

UGR_axial UGR_transv.
65/75
1/400W HIE RAB 36000 lm
17.5
17.5
75< 1000 cd/m2
1/400W HSE RAB 36000 lm*
17.6
17.4
75< 1000 cd/m2
1/400W HSE RAB 47000 lm** 16.0
16.0
65< 1000 cd/m2

Ceiling height: 6 m

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

COPA I 400 W

20

25

30

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:44 Uhr

Chapter 6 / 27

Seite 27

60

80

100

120

140

Floor area m

160

180

200

18

24

30

1/85 W RKF/RKID

1/57 W RKF/RKID

1/42 W RKF/RKID

1/32 W RKF/RKID

36

10

40

75< 1000 cd/m2


65< 1000 cd/m2
65< 1000 cd/m2

65 / 75
65< 200 cd/m2
75< 200 cd/m2

12

20

UGR_axial UGR_transv.
15.1
15.1
17.3
17.3
23.2
23.2
20.5
20.5
17.6
17.6
17.5
17.5

300 lx

20

30

40

COPA D 1/32W RKF/RKID


COPA D 1/42W RKF/RKID
COPA D 1/57W RKF
COPA D 1/57W RKID
COPA D 1/85W RKF
COPA D 1/85W RKID

Ceiling height: 4 m

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

COPA D 32/42/57/85 W

up to 50 m2
1.2
1.4

Axial spacing up to 5 m, up to 5.4 m


(42 W RKF), up to 5.7 m (42 W RKID,
57 W RKF, RKID )

Uniformity

Clean medium-sized room


Lamp operation
Cleaning of luminaires (IP65)
Room maintenance

MF= 0.78
2,000 h
1 year
2 years

over 50 m2
1.1
1.2

Maintenance factor (MF)

height
5m
6m

Correction factors
Dark room (50/40/20): 1.1
Ceiling
Floor area

24.06.2004

The Lighting Handbook

28 / Chapter 6

50

60

500 lx

06_QUICKPLAN_uk.qxd
9:44 Uhr
Seite 28

10

20

40

60

100

120

140

160

180

200

up to 50 m2
1.2
1.4

Axial spacing up to 4 m

Uniformity

Clean medium-sized room


Lamp operation
Cleaning of luminaires (IP65)
Room maintenance

MF= 0.77 (HCI)


2,000 h
1 year
2 years

over 50 m2
1.1
1.2

Maintenance factor (MF)

height
5m
6m

Correction factors
Dark room (50/40/20): 1.1
Ceiling
Floor area

24.06.2004

Floor area m

80

1/150 W HIT

15

15

1/70 W HIT

18

300 lx

12

UGR_axial UGR_transv.
55/65
COPA D 1/70W (6400 lm)
18.0
18.0
65 < 1000 cd/m2
COPA D 1/150W (14000 lm)
20.9
20.9
75 < 1000 cd/m2

Ceiling height: 4 m

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

COPA D 70/150 W

20

25

30

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:44 Uhr

Chapter 6 / 29

Seite 29

60

80

100

120

140

Floor area m

160

180

200

18

1/250 W QT

24

30

36

10

40

UGR_axial UGR_transv.
65
17.8
17.8
< 1000 cd/m2

12

20

COPA D 1/250 W QT

Ceiling height: 4 m

300 lx

20

30

40

COPA D 250 W QT
X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

up to 50 m2
1.2
1.4

Axial spacing up to 4.5 m

Uniformity

Clean medium-sized room


Lamp operation
Cleaning of luminaires (IP65)
Room maintenance

MF= 0.76
1,000 h
1 year
2 years

over 50 m2
1.1
1.2

Maintenance factor (MF)

height
5m
6m

Correction factors
Dark room (50/40/20): 1.1
Ceiling
Floor area

24.06.2004

The Lighting Handbook

30 / Chapter 6

50

60

500 lx

06_QUICKPLAN_uk.qxd
9:44 Uhr
Seite 30

50

100

150

COPA A-B 1/250W HIT (20000 lm)


COPA A-B 1/250W HST (23000 lm)
COPA A-B 2/250W HIT (40000 lm)
COPA A-B 1/250W HST (46000 lm)

Ceiling height: 6 m

250

300

Floor area m2

200

UGR_axial UGR_transv.
25.8
25.1
26.6
25.6
27.3
27.3
22.6
31.6

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

350

COPA A-B HIT/HST 1-/2-lamp

400

450

2/250 W HIT

2/250 W HST

1/250 W HST

1/250 W HIT

500

12

15

18

300 lx

MF=0.80 (HIT)
2,000 h
1 year
2 years

MF=0.81 (HST)
14,000 h
1 year
2 years

Axial spacing up to: 7,5 m HST, up to 8.3 m


2/250 W HIT, up to 9 m 1/250 W HIT

Uniformity

Clean large room


Lamp operation
Cleaning of lumi. (IP65)
Room maintenance

Maintenance factor (MF)

Correction factors
Dark room (50/40/20): 1.1

24.06.2004

10

15

20

25

30

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:44 Uhr

Chapter 6 / 31

Seite 31

10

15

20

50

100

150

COPA A_B 1/400 W HIT (32000 lm) *


COPA A_B 1/400 W HST (48000 lm) **

Ceiling height: 6 m

250

300

Floor area m2

200

UGR_axial UGR_transv.
25.8
25.1
26.6
25.6

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

350

COPA A-B HIT/HST 1-lamp

400

450

1/400 W HST

1/400 W HIT

500

12

15

18

300 lx

MF=0.67 (HIT)
1,000 h
1 year
2 years

* (Colour rendition class Ra > 90)


** (Colour rendition class Ra > 20)

Axial spacing up to 9 m

Uniformity

Clean large room


Lamp operation
Cleaning of lumi. (IP65)
Room maintenance

Maintenance factor (MF)

Correction factors
Dark room (50/40/20): 1.1

MF=0.81 (HST)
14,000 h
1 year
2 years

24.06.2004

The Lighting Handbook

32 / Chapter 6

25

30

500 lx

06_QUICKPLAN_uk.qxd
9:44 Uhr
Seite 32

150

200

250

300

350

450

500

Axial spacing up to 9 m

Uniformity

Clean large room


Lamp operation
Cleaning of luminaires (IP65)
Room maintenance

Maintenance factor (MF)


MF= 0.80
2,000 h
1 year
2 years

Correction factors
Dark room (50/40/20): 1.1

24.06.2004

Floor area m2

400

18

24

1/400 W HME

1/250 W HME

30

10

100

UGR_axial UGR_transv.
27.0
25.2
29.0
27.7

36

300 lx

12

50

COPA A_B 1/250 W HME (13000 lm)


COPA A_B 1/400 W HME (22000 lm)

Ceiling height: 6 m

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

COPA A-N HME 1-lamp

20

30

40

50

60

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:44 Uhr

Chapter 6 / 33

Seite 33

50

100

COPA A-B 1/600 W HST


COPA A-T 1/600 W HST
COPA ASY 1/600 W HST

Ceiling height: 6 m

150

250

300

Floor area m2

200

350

400

450

A-T 1/600 W HST


A-B 1/600 W HST
A-ASY 1/600 W HST

UGR_axial UGR_transv.
32.7
31.2
22.6
27.7
-

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

COPA A-B, A-T, A-ASY HST 1-lamp

500

300 lx

MF= 0.83
10,000 h
2 years
2 years

Axial spacing up to 6.3 m (ASY), up to


7.5 m (A-B)

Uniformity

Clean large room


Lamp operation
Cleaning of luminaires (IP65)
Room maintenance

Maintenance factor (MF)

Correction factors
Dark room (50/40/20): 1.1

24.06.2004

The Lighting Handbook

34 / Chapter 6

10

500 lx

06_QUICKPLAN_uk.qxd
9:44 Uhr
Seite 34

50

100

150

COPA A-ASY 1/250 W HIT (20000 lm)


COPA A-ASY 1/250 W HST (27000 lm)
COPA A-ASY 1/400 W HIT (32000 lm)
COPA A-ASY 1/400 W HST (48000 lm)

Ceiling height: 6 m

250

300

Floor area m2

200

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

350

400

450

1/400 W HIT

1/250 W HST

1/400 W HST

1/250 W HIT

COPA A-ASY HIT/HST 1-lamp

500

12

15

18

300 lx

Clean large room


Lamp operation
Cleaning of luminaires (IP65)
Room maintenance

Maintenance factor (MF)


MF=0.81 (HST)
14,000 h
2 years
2 years

Correction factors
Dark room (50/40/20): 1.1

24.06.2004

10

15

20

25

30

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:44 Uhr

Chapter 6 / 35

Seite 35

60

80

100

120

Floor area m2

140

160

180

200

10

40

12

24

30

20

TOL-TBC 1/36 W

IFP 1/36 W
FZ 1/36 W
FT 1/36 W

36

18

20

UGR_axial UGR_transv.
22.0
17.3
19.4
15.2
22.7
18.4
19.8
19.5

300 lx

30

40

FZ 1/36W T26
FT 1/36W T26
IFP 1/36W T26
TOL 1/36W T26 TBC

Ceiling height: 3 m

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

FZ/FT/IFP/TOL-TBC 1-lamp, 36 W

up to 50 m2
1.2
1.4
1.6

Continuous row spacing up to 5.8 m (TOLTBC), 7.8 m (IFP-PC) or 8.5 m (FZ, FT)

Uniformity

Clean medium-sized room


Lamp operation
Cleaning of luminaires
Room maintenance

MF= 0.78
6,000 h
1 year
2 years

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.25 (1.1 for TOL-TBC)
Ceiling
Floor area

24.06.2004

The Lighting Handbook

36 / Chapter 6

50

60

500 lx

06_QUICKPLAN_uk.qxd
9:44 Uhr
Seite 36

20

FZ 1/58W T26
FT 1/58W T26
IFP-PC 1/58W T26
TOL 1/58W T26 TBC

Ceiling height: 3 m

40

60

100

120

Floor area m2

80

UGR_axial UGR_transv.
22.8
18.1
20.2
16.0
23.5
19.2
21.2
20.6

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

140

FZ/FT/IFP/TOL-TBC 1-lamp, 58 W

FZ FT

160

180

TOL-TBC

IFP-PC

200

12

18

24

30

36

300 lx

up to 50 m2
1.2
1.4
1.6

Continuous row spacing up to 5.8 m (TOLTBC), 7.8 m (IFP-PC) or 8.5 m (FZ, FT)

Uniformity

Clean medium-sized room


Lamp operation
Cleaning of luminaires
Room maintenance

MF= 0.78
6,000 h
1 year
2 years

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.25 (1.1 for TOL-TBC)
Ceiling
Floor area

24.06.2004

10

20

30

40

50

60

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:44 Uhr

Chapter 6 / 37

Seite 37

10

20

20

40

60

100

120

Floor area m2

80

140

FZ 2/36 W

30

160

180

IFP 2/36 W

TOL 2/36 W

UGR_axial UGR_transv.
23.2
18.6
20.8
16.8
24.1
19.5
19.8
19.5

40

FZ 2/36W T26
FT 2/36W T26
IFP 2/36W T26
TOL 2/36W T26 TBC

Ceiling height: 3 m

FT 2/36 W

FZ/FT/IFP/TOL 2-lamp, 36 W

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

200

12

18

24

30

36

300 lx

up to 50 m2
1.2
1.4
1.6

Continuous row spacing up to 5.8 m (TOLTBC), 7.4 m (IFP-PC) or 7.9 m (FZ, FT)

Uniformity

Clean medium-sized room


Lamp operation
Cleaning of luminaires
Room maintenance

MF= 0.78
6,000 h
1 year
2 years

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.25 (1.1 for TOL-TBC)
Ceiling
Floor area

24.06.2004

The Lighting Handbook

38 / Chapter 6

50

60

500 lx

06_QUICKPLAN_uk.qxd
9:44 Uhr
Seite 38

20

FZ 2/58W T26
FT 2/58W T26
IFP 2/58W T26
TOL 2/58W T26 TBC

Ceiling height: 3 m

40

60

100

120

Floor area m2

80

UGR_axial UGR_transv.
24.0
19.4
21.6
17.6
24.9
20.3
21.2
20.6

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

140

160

TOL 2/58 W

180

IFP 2/58 W
FZ 2/58 W

FT 2/58 W

FZ/FT/IFP/TOL 2-lamp, 58 W

200

12

15

18

300 lx

up to 50 m2
1.2
1.4
1.6

Continuous row spacing up to 5.8 m (TOLTBC), 7.4 m (IFP-PC) or 7.9 m (FZ, FT)

Uniformity

Clean medium-sized room


Lamp operation
Cleaning of luminaires
Room maintenance

MF= 0.78
6,000 h
1 year
2 years

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.25 (1.1 for TOL-TBC)
Ceiling
Floor area

24.06.2004

10

15

20

25

30

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:44 Uhr

Chapter 6 / 39

Seite 39

60

80

100

120

Floor area m2

140

160

180

200

18

24

30

36

6
40

22+40 W

1/55 W

10

2/40 W

1/40 W

42

48

54

12

20

UGR_axial UGR_transv.
20.3
20.3
20.7
20.7
20.6
20.6
19.8
19.4

300 lx

20

30

40

50

60

FTR 1/40W T16-R


FTR 1/55W T16-R
FTR 1/22W+40W T16-R
FTR 2/40W T16-R

RCeiling height: 3 m

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

CHIARO FTR390/FTR680 1-/2-lamp

up to 50 m2
1.2
1.4
1.6

Axial spacing up to 4.5 m, up to


5 m 2/40 W

Uniformity

Clean medium-sized room


Lamp operation
Luminaire maintenance
Room maintenance

MF= 0.76
6,000 h
1 year
2 years

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.25
Ceiling
Floor area

24.06.2004

The Lighting Handbook

40 / Chapter 6

70

80

90

500 lx

06_QUICKPLAN_uk.qxd
9:44 Uhr
Seite 40

40

100

120

140

2/36 W

20

60

Floor area m2

80

160

180

2/54 W

200

12

up to 50 m2
1.2
1.4
1.6

Continuous row spacing up to 8 m

Uniformity

Clean medium-sized room


Lamp operation
Cleaning of luminaires
Room maintenance

MF= 0.78
6,000 h
1 year
2 years

over 50 m2
1.1
1.2
1.3

Maintenance factor (MF)

height
4m
5m
6m

Correction factors
Dark room (50/40/20): 1.25
Ceiling
Floor area

24.06.2004

10

20

1/80 W

18

1/58 W

30

36

30

UGR_axial UGR_transv.
26.3
21.3
28.7
24.2
25.2
19.2
28.4
21.8

300 lx

24

RAIN 1/58 W T 26
RAIN 1/80 W T 16
RAIN 2/36 W T 26
RAIN 2/54 W T 16

Ceiling height: 3 m

X=4H Y=8H / S=0.25H / Reflection factors 70/50/20

RAIN 1-/2-lamp

40

50

60

500 lx

The Lighting Handbook

06_QUICKPLAN_uk.qxd
9:44 Uhr

Chapter 6 / 41

Seite 41

00_INHALTSVER_uk.qxd

24.06.2004

10:21 Uhr

Seite 2

07_BELSAN_uk.qxd

24.06.2004

9:46 Uhr

Seite 1

Chapter 7

Lighting refurbishment
Arguments for refurbishing lighting systems . . . . . . . . 3 4
Collecting data for lighting refurbishment . . . . . . . . . .
5
Illuminance measurement . . . . . . . . . . . . . . . . . . . . .
5
Data-collection sheet for lighting refurbishment . . . . . . 6 17

07_BELSAN_uk.qxd

24.06.2004

9:46 Uhr

Seite 2

07_BELSAN_uk.qxd

24.06.2004

9:46 Uhr

Seite 3

Arguments for refurbishing lighting systems


1. Reduced operating costs
1.1. Energy savings
Efficiency of the luminaires improved from about 35 % to more
than 80 % (e.g. opal diffuser luminaire to louvre luminaire)
Lower power consumption of ballasts
Energy audit for 58 W fluorescent lamps
Lamp diameter
38 mm
Ballast
convent.
Lamp power
65 W
Dissipated power
12 W
Total power
77 W
Extra power consumption 40 %

26 mm
convent.
58 W
12 W
70 W
27 %

26 mm 26 mm
low-loss electronic
58 W
50 W
8W
5W
66 W
55 W
20 %

Energy audit for 36 W fluorescent lamps


Lamp diameter
38 mm
Ballast
convent.
Lamp power
40 W
Dissipated power
9W
Total power
49 W
Extra power consumption 36 %

26 mm
convent.
36 W
9W
45 W
25 %

26 mm 26 mm
low-loss electronic
36 W
32 W
6W
4W
42 W
36 W
17 %

Using available daylight: potential energy savings of up to 70 %


Blinds control: prevents buildings getting too hot
Air-conditioned rooms: a reduction in the connected load means
a reduction in heat load and hence less air-conditioning power
(The heat load generated by a light output of 1 kW requires
about 3 kW of cooling power)
1.2. Savings in lamp replacement costs

The Lighting Handbook

The lamp lifetime of fluorescent lamps is extended by more


than 50 % when operated with an electronic ballast
(to 16,000 20,000 h)

Chapter 7 / 3

07_BELSAN_uk.qxd

24.06.2004

9:46 Uhr

Seite 4

1.3. Savings in maintenance costs


No need to buy a starter when using electronic ballasts
Modular design of luminaires and tool-free installation make
it easier and hence cheaper to replace components
No more spare-parts problems, so lower maintenance costs
(motto: complete refurbishment better than constant repairs)

2. Improved ergonomics
Applying ergonomic principles to lighting brings the following
proven benefits:
Growth in output
Fewer mistakes and lower stoppage rates
Reduced number of accidents
The lower thermal load of refurbished lighting systems produces
a more pleasant room environment, improved working conditions
and thus a greater willingness to work.

3. Reliability and safety


Do the luminaires meet the electrotechnical requirements
(e.g. ENEC mark of conformity)?
Do the luminaires comply with stipulated safety measures and
requirements in the room (IP XX, FF/D, Ex)?

4 / Chapter 7

The Lighting Handbook

Does the lighting meet photometric requirements (e.g. lighting


level, glare limitation, etc.)?

07_BELSAN_uk.qxd

24.06.2004

9:46 Uhr

Seite 5

Collecting data for the lighting refurbishment


The data-collection sheets help you to compile all the relevant
information for making an inventory of your existing lighting
systems.
They provide a basis for a photometric comparison and system
costing.

Illuminance measurement
The average illuminance is the arithmetic mean of the point
illuminance levels measured in a defined grid using a luxmeter
under precisely defined conditions.
Meters: designation and accuracy
L: highest accuracy; 3 % limit of error
A: high accuracy; 5 % limit of error
B: moderate accuracy; 10 % limit of error (minimum
requirement)
Measurement conditions
Avoid daylight/light from other sources (measure separately
and deduct)
Check mains voltage and ambient temperature
Use new, suitably aged lamps (discharge lamps 100 h)
Measurement grid and measurement height

The Lighting Handbook

Workplaces = 0.75 m, sports facilities = 1.0 m


Thoroughfares, stairs, indoor car parks = 0.03 m
Cylindrical illuminance = 1.2 m
Measurement grid: coincident rectangles; separation about 1 m
Measurement grid not coincident with luminaire position grid

Chapter 7 / 5

07_BELSAN_uk.qxd

24.06.2004

9:46 Uhr

Seite 6

Data collection sheet for lighting refurbishment


Project

Contact

Address

Tel
Fax

Activities in room

Old system Option 1

Option 2

Luminaire type A
Number of luminaires
Number of lamps per luminaire
Type of ballast
System power per luminaire
including ballast (W)
Illuminance

Luminaire type B
Number of luminaires
Number of lamps per luminaire
Type of ballast
System power per luminaire
including ballast (W)
Illuminance

Total connected load in kW


ON period each day (h)
Working days per year
Annual ON period (h)
Power consumption in kWh/a

Annual savings in kWh


Power costs per kWh
Annual power costs in kWh

Annual savings
6 / Chapter 7

The Lighting Handbook

Basic power price kW/year

07_BELSAN_uk.qxd

24.06.2004

Room length

9:46 Uhr

Reflection: Wall

Seite 7

Room width

Ceiling

Room height

Floor

u = Emin =
Emean

Uniformity
Emean =

lx

Emin

lx

The Lighting Handbook

Room sketch:

Costs

Old system Option 1

Option 2

Cleaning per luminaire/year


Lamp replacement (incl. lamp)

Chapter 7 / 7

07_BELSAN_uk.qxd

24.06.2004

9:46 Uhr

Seite 8

Data collection sheet for lighting refurbishment


Project
Address

Contact
Tel
Fax

Activities in room

Old system Option 1

Option 2

Luminaire type A
Number of luminaires
Number of lamps per luminaire
Type of ballast
System power per luminaire
including ballast (W)
Illuminance

Luminaire type B
Number of luminaires
Number of lamps per luminaire
Type of ballast
System power per luminaire
including ballast (W)
Illuminance

Total connected load in kW


ON period each day (h)
Working days per year
Annual ON period (h)
Power consumption in kWh/a

Annual savings in kWh


Power costs per kWh
Annual power costs in kWh

Annual savings
8 / Chapter 7

The Lighting Handbook

Basic power price kW/year

07_BELSAN_uk.qxd

24.06.2004

Room length

9:46 Uhr

Reflection: Wall

Seite 9

Room width

Ceiling

Room height

Floor

u = Emin =
Emean

Uniformity
Emean =

lx

Emin

lx

The Lighting Handbook

Room sketch:

Costs

Old system Option 1

Option 2

Cleaning per luminaire/year


Lamp replacement (incl. lamp)

Chapter 7 / 9

07_BELSAN_uk.qxd

24.06.2004

9:46 Uhr

Seite 10

Data collection sheet for lighting refurbishment


Project
Address

Contact
Tel
Fax

Activities in room

Old system Option 1

Option 2

Luminaire type A
Number of luminaires
Number of lamps per luminaire
Type of ballast
System power per luminaire
including ballast (W)
Illuminance

Luminaire type B
Number of luminaires
Number of lamps per luminaire
Type of ballast
System power per luminaire
including ballast (W)
Illuminance

Total connected load in kW


ON period each day (h)
Working days per year
Annual ON period (h)
Power consumption in kWh/a

Annual savings in kWh


Power costs per kWh
Annual power costs in kWh

Annual savings
10 / Chapter 7

The Lighting Handbook

Basic power price kW/year

07_BELSAN_uk.qxd

24.06.2004

Room length

9:46 Uhr

Reflection: Wall

Seite 11

Room width

Ceiling

Room height

Floor

u = Emin =
Emean

Uniformity
Emean =

lx

Emin

lx

The Lighting Handbook

Room sketch:

Costs

Old system Option 1

Option 2

Cleaning per luminaire/year


Lamp replacement (incl. lamp)

Chapter 7 / 11

07_BELSAN_uk.qxd

24.06.2004

9:46 Uhr

Seite 12

Data collection sheet for lighting refurbishment


Project
Address

Contact
Tel
Fax

Activities in room

Old system Option 1

Option 2

Luminaire type A
Number of luminaires
Number of lamps per luminaire
Type of ballast
System power per luminaire
including ballast (W)
Illuminance

Luminaire type B
Number of luminaires
Number of lamps per luminaire
Type of ballast
System power per luminaire
including ballast (W)
Illuminance

Total connected load in kW


ON period each day (h)
Working days per year
Annual ON period (h)
Power consumption in kWh/a

Annual savings in kWh


Power costs per kWh
Annual power costs in kWh

Annual savings
12 / Chapter 7

The Lighting Handbook

Basic power price kW/year

07_BELSAN_uk.qxd

24.06.2004

Room length

9:46 Uhr

Reflection: Wall

Seite 13

Room width

Ceiling

Room height

Floor

u = Emin =
Emean

Uniformity
Emean =

lx

Emin

lx

The Lighting Handbook

Room sketch:

Costs

Old system Option 1

Option 2

Cleaning per luminaire/year


Lamp replacement (incl. lamp)

Chapter 7 / 13

07_BELSAN_uk.qxd

24.06.2004

9:46 Uhr

Seite 14

Data collection sheet for lighting refurbishment


Project
Address

Contact
Tel
Fax

Activities in room

Old system Option 1

Option 2

Luminaire type A
Number of luminaires
Number of lamps per luminaire
Type of ballast
System power per luminaire
including ballast (W)
Illuminance

Luminaire type B
Number of luminaires
Number of lamps per luminaire
Type of ballast
System power per luminaire
including ballast (W)
Illuminance

Total connected load in kW


ON period each day (h)
Working days per year
Annual ON period (h)
Power consumption in kWh/a

Annual savings in kWh


Power costs per kWh
Annual power costs in kWh

Annual savings
14 / Chapter 7

The Lighting Handbook

Basic power price kW/year

07_BELSAN_uk.qxd

24.06.2004

Room length

9:46 Uhr

Reflection: Wall

Seite 15

Room width

Ceiling

Room height

Floor

u = Emin =
Emean

Uniformity
Emean =

lx

Emin

lx

The Lighting Handbook

Room sketch:

Costs

Old system Option 1

Option 2

Cleaning per luminaire/year


Lamp replacement (incl. lamp)

Chapter 7 / 15

07_BELSAN_uk.qxd

24.06.2004

9:46 Uhr

Seite 16

Data collection sheet for lighting refurbishment


Project
Address

Contact
Tel
Fax

Activities in room

Old system Option 1

Option 2

Luminaire type A
Number of luminaires
Number of lamps per luminaire
Type of ballast
System power per luminaire
including ballast (W)
Illuminance

Luminaire type B
Number of luminaires
Number of lamps per luminaire
Type of ballast
System power per luminaire
including ballast (W)
Illuminance

Total connected load in kW


ON period each day (h)
Working days per year
Annual ON period (h)
Power consumption in kWh/a

Annual savings in kWh


Power costs per kWh
Annual power costs in kWh

Annual savings
16 / Chapter 7

The Lighting Handbook

Basic power price kW/year

07_BELSAN_uk.qxd

24.06.2004

Room length

9:46 Uhr

Reflection: Wall

Seite 17

Room width

Ceiling

Room height

Floor

u = Emin =
Emean

Uniformity
Emean =

lx

Emin

lx

The Lighting Handbook

Room sketch:

Costs

Old system Option 1

Option 2

Cleaning per luminaire/year


Lamp replacement (incl. lamp)

Chapter 7 / 17

00_INHALTSVER_uk.qxd

24.06.2004

10:21 Uhr

Seite 2

08_WIRTSCHAF_uk.qxd

24.06.2004

9:48 Uhr

Chapter 8

Economic efficiency calculation


Economic efficiency calculation . . . . . . . . . . . . . . . . .
2
Maintenance of lighting systems . . . . . . . . . . . . . . . . .
3
Environmental conditions . . . . . . . . . . . . . . . . . . . . . .
3
Table for lamp lumens maintenance factor (LLMF)
and lamp survival factor (LSF) . . . . . . . . . . . . . . . . . .
4
Table for luminaire maintenance factor (LMF) . . . . . . .
5
Table for room surface maintenance factor (RSMF) . . .
6
Table of burning hours . . . . . . . . . . . . . . . . . . . . . . . .
7
Economic analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 13

Seite 1

08_WIRTSCHAF_uk.qxd

24.06.2004

9:48 Uhr

Seite 2

Economic efficiency calculation


A short pay-back period is usually the most important consideration when designing lighting systems.
The pay-back period calculation using the following forms is
based on a static calculation method. This is a theoretical
approach that delivers a guide value very quickly and is
perfectly adequate for an initial estimate.
Dynamic calculation models involving depreciation and interest
payments are left to the financial experts and fall outside the
scope of this handbook.
Static calculation model
Extra expenditure Investment costs
Annual saving in operating costs

Definition of terms used in the economic analysis sheets


on page 8 onwards
(3) System power of luminaire Lamp wattage + power dissipation in control gear.
(5) Annual burning hours Total of the daily lamp ON hours over
the year. The table of burning hours (page 7) provides help for
daylight-dependent systems.
(13) Maintenance factor A reference maintenance factor of
0.67 can be assumed (3-year maintenance interval, clean
environment). The system-specific maintenance factor must be
found in order to calculate the number of luminaires required.
It is given by the product of lamp lumens maintenance factor,
lamp survival factor, luminaire maintenance factor and room
surface maintenance factor. These factors can be found from
the tables on pages 37. The maintenance factor must be
documented in the design process together with the basic
conditions.
(18) Cost of lamp replacement Cost of complete job of
replacing the lamps, including the costs of the lamp and
additional costs such as step ladders, weekend overtime
payments or loss of production.
(19) Cost of luminaire cleaning Cost of the complete job of
cleaning the luminaire plus replacing faulty components in
the lighting system including parts costs.
(20) Cost of room cleaning Labour costs for cleaning room
surfaces and restoring the reflection characteristics to their
new condition.
(21) Energy costs per kWh Estimate a mixed price for high and
low tariff. Include energy standing charges in the working price.

The Lighting Handbook

Pay-back time =

08_WIRTSCHAF_uk.qxd

24.06.2004

9:48 Uhr

Maintenance of lighting systems


160 %
140 %
120 %
100 %

Example:
Luminaire maintenance: every year
Room surface maintenance: every 3 years
Lamp replacement: every 3 years
Faulty lamp replacement: immediately

80 %
60 %
40 %
20 %
0.0

0.5

1.0

1.5
2.0
years

2.5

3.0

3.5

Maintenance factor (MF) = LLMF x LSF x LMF x RSMF


(see factor tables on the following pages)

Environmental conditions
The following table contains the recommended maximum
maintenance interval for the type of environment.
Environment Max. maintenance Work areas
type
interval
Clean (C)
3 years
Clean rooms, computer
centres, electronic-component
assembly areas, hospitals*)
Normal (N)
2 years
Offices, shops, schools,
laboratories, restaurants,
warehouses, assembly bays
Dirty (D)
1 year
Steel works, chemical plants,
foundries, welding shops,
grinding shops, woodworking

The Lighting Handbook

*) Sometimes shorter maintenance intervals are required for hygiene


reasons.

From CIE publication 97 Maintenance of indoor electric lighting


systems, dated 1995, ISBN 3 900 734 34 8

Chapter 8 / 3

Seite 3

4 / Chapter 8
LLMF
LSF
LLMF
LSF
LLMF
LSF
LLMF
LSF
LLMF
LSF
LLMF
LSF
LLMF
LSF
LLMF
LSF
LLMF
LSF
LLMF
LSF
LLMF
LSF

100
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

1,000
0.93
0.50
0.98
0.91
0.94
1.00

1,500
0.89
0.03
0.97
0.84
0.91
1.00
0.80
0.99
0.95
0.98
0.94
0.97
0.85
0.98
0.85
0.88
0.83
0.93
0.65
0.90
0.77
0.96
0.98
1.00

0.78
0.95
0.94
0.98
0.93
0.96
0.83
0.94
0.80
0.84
0.80
0.89
0.62
0.85
0.75
0.93
0.97
0.99
0.89
0.90
0.88
0.80

0.88
0.50
0.88
0.50

0.74
0.72
0.58
0.72
0.72
0.83
0.96 0.96 0.95 0.95 0.94
0.97 0.96 0.93 0.91 0.88

0.70
0.50
0.90
0.96
0.89
0.90

0.76
0.80
0.60
0.78
0.73
0.88
0.97
0.98

0.72
0.64
0.91
0.97
0.90
0.94

0.74
0.75
0.92
0.98
0.91
0.95

0.76
0.85
0.92
0.98
0.92
0.96
0.83
0.50

Manufacturers figures from April 2003. Assumes the use of the latest ballast technology.
For other manufacturers or lamp types, please contact relevant lamp manufacturer.

0.83
1.00
0.96
0.99
0.95
0.98
0.88
0.98
0.89
0.91
0.88
0.97
0.70
0.94
0.80
0.98
0.98
1.00

2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000

0.95
0.50
0.89
1.00
0.97
0.99
0.96
0.99
0.97
0.92
0.99
0.99
0.94
0.96
0.93
0.99
0.78
0.98
0.90
0.99
1.00 1.00 0.99 0.99
1.00 1.00 1.00 1.00

500
0.97
0.98
0.99
0.99
0.97
1.00

24.06.2004

The Lighting Handbook

LLMF burning hours


Incandescent lamp
CIE 1997
Low-voltage halogen lamp
Philips Capsuline Pro
Single-phosphor fluorescent lamp
CIE 1997
Triphosphor fluorescent lamp T26
Osram LUMILUX
Triphosphor fluorescent lamp T16
Osram FH, FQ
Compact fluorescent lamp
Osram DULUX
Metal halide lamp Ceramic
Osram HCI-150 W/WDL
Metal halide lamp Quartz
Osram HQI-E 250 W/D
Metal halide lamp Quartz
Osram HQI-E 400 W/D
Mercury vapour lamp
Philips HPL 250/400 W
Sodium vapour lamp
Philips SON(-T) PIA Plus 100400 W

08_WIRTSCHAF_uk.qxd
9:48 Uhr
Seite 4

Table for lamp lumens maintenance factor


(LLMF) and lamp survival factor (LSF)

0.5
N
D

1.0
N
D

1.5
N
D

2.0
N
D

2.5
N
D

3.0
N
D

0.93 0.89 0.83 0.89 0.81 0.72 0.84 0.74 0.64 0.80 0.69 0.59 0.77 0.64 0.54 0.74 0.61 0.52
0.92 0.87 0.83 0.88 0.82 0.77 0.85 0.79 0.73 0.83 0.77 0.71 0.81 0.75 0.68 0.79 0.73 0.65
0.96 0.93 0.91 0.94 0.90 0.86 0.92 0.88 0.83 0.91 0.86 0.81 0.90 0.85 0.80 0.90 0.84 0.79

Reflector enclosed above


(no self-cleaning effect)

Enclosed IP2X

Dust-proof IP5X

Indirect luminaires
0.92 0.89 0.85 0.86 0.81 0.74 0.81 0.73 0.65 0.77 0.66 0.57 0.73 0.60 0.51 0.70 0.55 0.45
From CIE publication 97 Maintenance of indoor electric lighting systems, dated 1995, ISBN 3 900 734 34 8

0.95 0.91 0.88 0.90 0.86 0.83 0.87 0.83 0.79 0.84 0.80 0.75 0.82 0.76 0.71 0.79 0.74 0.68

0.95 0.92 0.88 0.93 0.89 0.83 0.91 0.87 0.80 0.89 0.84 0.78 0.87 0.82 0.75 0.85 0.79 0.73

Reflector exposed above


(self-cleaning effect)

Luminaire cleaning interval


in years
Environment type
Luminaire type
Bare batten luminaires

The Lighting Handbook

08_WIRTSCHAF_uk.qxd
24.06.2004
9:48 Uhr

Table for luminaire maintenance factor (LMF)

Chapter 8 / 5

Seite 5

Direct
0.99 0.97 0.96 0.98 0.96 0.95 0.97 0.96 0.93 0.96 0.95 0.94 0.96 0.95 0.94 0.96 0.95 0.94
Direct/Indirect 0.95 0.90 0.86 0.94 0.88 0.85 0.90 0.86 0.83 0.89 0.85 0.81 0.87 0.84 0.79 0.86 0.82 0.78
Indirect
0.92 0.87 0.83 0.88 0.82 0.77 0.86 0.79 0.74 0.84 0.77 0.70 0.81 0.74 0.68 0.78 0.72 0.65
From CIE publication 97 Maintenance of indoor electric lighting systems, dated 1995, ISBN 3 900 734 34 8

Large
K = 5.0

Direct
0.98 0.97 0.96 0.98 0.96 0.95 0.97 0.96 0.95 0.96 0.95 0.94 0.96 0.95 0.94 0.96 0.95 0.94
Direct/Indirect 0.95 0.90 0.86 0.92 0.88 0.85 0.90 0.86 0.83 0.89 0.85 0.81 0.87 0.84 0.79 0.86 0.82 0.78
Indirect
0.92 0.87 0.83 0.88 0.82 0.77 0.86 0.79 0.74 0.84 0.77 0.70 0.81 0.74 0.67 0.78 0.72 0.64

24.06.2004

The Lighting Handbook

6 / Chapter 8

Medium
K = 2.5

Room cleaning interval


in years
0.5
1.0
1.5
2.0
2.5
3.0
Environment type
C
N
D
C
N
D
C
N
D
C
N
D
C
N
D
C
N
D
Room size/ Illumination
Room index type
Small
Direct
0.97 0.96 0.95 0.97 0.94 0.93 0.96 0.94 0.92 0.95 0.93 0.90 0.94 0.92 0.89 0.94 0.92 0.88
K = 0.7
Direct/Indirect 0.94 0.88 0.84 0.90 0.86 0.82 0.89 0.83 0.80 0.87 0.82 0.78 0.85 0.80 0.75 0.84 0.79 0.74
Indirect
0.90 0.84 0.80 0.85 0.78 0.73 0.83 0.75 0.69 0.81 0.73 0.66 0.77 0.70 0.62 0.75 0.68 0.59

08_WIRTSCHAF_uk.qxd
9:48 Uhr
Seite 6

Table for room surface maintenance factor (RSMF)

310
310
310
310
258
258

24-h shift working,


Process monitoring/control

Double shift,
6 days/week

Single shift,
6 days/week

Single shift,
5 days/week

10
10

10
10

16
16

Hours/day
24
24

No
Yes

No
Yes

No
Yes

24.06.2004

From CIE publication 97 Maintenance of indoor electric lighting systems, dated 1995, ISBN 3 900 734 34 8

2.58
1.55

3.10
1.76

4.96
3.72

Daylight-dependent control Burning hours per lamp and year


1,000 hours
No
8.76
Yes
7.30

Daylight-dependent control: the lamps switch on automatically when there is too little daylight available.
Data is based on the assumption that there is sufficient available daylight for half the year.

On period
Days in use/year
365
365

Working mode/shift type

The Lighting Handbook

08_WIRTSCHAF_uk.qxd
9:48 Uhr

Table of burning hours

Chapter 8 / 7

Seite 7

08_WIRTSCHAF_uk.qxd

24.06.2004

9:48 Uhr

Seite 8

Economic analysis
Building project
Option 1
Luminaire type

Option 2

(1)

Luminaire data
Number of lamps per luminaire

(2)

System power of luminaire (W)

(3)

Operating data
Service life of system (y)

(4)

Annual burning hours see page 7

(5)

Lamp replacement interval (y)

(6)

Luminaire cleaning interval (y)

(7)

Room cleaning interval (y)

(8)

Number of luminaires
Lamp lumens maintenance factor see page 4

(9)

Lamp survival factor see page 4

(10)

Luminaire maintenance factor see page 5

(11)

Room surface maintenance factor see page 6

(12)

Maintenance factor (9) x (10) x (11) x (12)

(13)

Number of luminaires

(14)

Cost of one luminaire

(15)

Cost of one lamp

(16)

Installation costs per luminaire

(17)

8 / Chapter 8

The Lighting Handbook

Itemised investment costs

08_WIRTSCHAF_uk.qxd

24.06.2004

9:48 Uhr

Option 1

Option 2

Itemised operating costs


Cost of lamp replacement

(18)

Cost of luminaire cleaning

(19)

Cost of room cleaning

(20)

Energy costs per kWh

(21)

Investment costs
Luminaire costs (14) x (15)

(22)

Lamp costs (14) x (2) x (16)

(23)

Installation costs (14) x (17)

(24)

Investment costs (22) + (23) + (24)

(25)

Operating costs
Room cleaning costs (20) x (4)  (8)

(26)

Luminaire cleaning costs (19) x (4)  (7)

(27)

Lamp replacement costs (18) x (4)  (6)

(28)

Energy costs (14) x (3) x (4) x (5) x (21)  1000

(29)

Operating costs (26) + (27) + (28) + (29)

(30)

Annual operating costs (30)  (4)

(31)

The Lighting Handbook

Pay-back period* =

(25) Option 2 (25) Option 1


(31) Option 1 (31) Option 2

Pay-back period* =

years

years

* excludes depreciation and interest

Chapter 8 / 9

Seite 9

08_WIRTSCHAF_uk.qxd

24.06.2004

9:48 Uhr

Seite 10

Economic analysis
Building project
Option 1
Luminaire type

Option 2

(1)

Luminaire data
Number of lamps per luminaire

(2)

System power of luminaire (W)

(3)

Operating data
Service life of system (y)

(4)

Annual burning hours see page 7

(5)

Lamp replacement interval (y)

(6)

Luminaire cleaning interval (y)

(7)

Room cleaning interval (y)

(8)

Number of luminaires
Lamp lumens maintenance factor see page 4

(9)

Lamp survival factor see page 4

(10)

Luminaire maintenance factor see page 5

(11)

Room surface maintenance factor see page 6

(12)

Maintenance factor (9) x (10) x (11) x (12)

(13)

Number of luminaires

(14)

Cost of one luminaire

(15)

Cost of one lamp

(16)

Installation costs per luminaire

(17)

10 / Chapter 8

The Lighting Handbook

Itemised investment costs

08_WIRTSCHAF_uk.qxd

24.06.2004

9:48 Uhr

Option 1

Option 2

Itemised operating costs


Cost of lamp replacement

(18)

Cost of luminaire cleaning

(19)

Cost of room cleaning

(20)

Energy costs per kWh

(21)

Investment costs
Luminaire costs (14) x (15)

(22)

Lamp costs (14) x (2) x (16)

(23)

Installation costs (14) x (17)

(24)

Investment costs (22) + (23) + (24)

(25)

Operating costs
Room cleaning costs (20) x (4)  (8)

(26)

Luminaire cleaning costs (19) x (4)  (7)

(27)

Lamp replacement costs (18) x (4)  (6)

(28)

Energy costs (14) x (3) x (4) x (5) x (21)  1000

(29)

Operating costs (26) + (27) + (28) + (29)

(30)

Annual operating costs (30)  (4)

(31)

The Lighting Handbook

Pay-back period* =

(25) Option 2 (25) Option 1


(31) Option 1 (31) Option 2

Pay-back period* =

years

years

* excludes depreciation and interest

Chapter 8 / 11

Seite 11

08_WIRTSCHAF_uk.qxd

24.06.2004

9:48 Uhr

Seite 12

Economic analysis
Building project
Option 1
Luminaire type

Option 2

(1)

Luminaire data
Number of lamps per luminaire

(2)

System power of luminaire (W)

(3)

Operating data
Service life of system (y)

(4)

Annual burning hours see page 7

(5)

Lamp replacement interval (y)

(6)

Luminaire cleaning interval (y)

(7)

Room cleaning interval (y)

(8)

Number of luminaires
Lamp lumens maintenance factor see page 4

(9)

Lamp survival factor see page 4

(10)

Luminaire maintenance factor see page 5

(11)

Room surface maintenance factor see page 6

(12)

Maintenance factor (9) x (10) x (11) x (12)

(13)

Number of luminaires

(14)

Cost of one luminaire

(15)

Cost of one lamp

(16)

Installation costs per luminaire

(17)

12 / Chapter 8

The Lighting Handbook

Itemised investment costs

08_WIRTSCHAF_uk.qxd

24.06.2004

9:48 Uhr

Option 1

Option 2

Itemised operating costs


Cost of lamp replacement

(18)

Cost of luminaire cleaning

(19)

Cost of room cleaning

(20)

Energy costs per kWh

(21)

Investment costs
Luminaire costs (14) x (15)

(22)

Lamp costs (14) x (2) x (16)

(23)

Installation costs (14) x (17)

(24)

Investment costs (22) + (23) + (24)

(25)

Operating costs
Room cleaning costs (20) x (4)  (8)

(26)

Luminaire cleaning costs (19) x (4)  (7)

(27)

Lamp replacement costs (18) x (4)  (6)

(28)

Energy costs (14) x (3) x (4) x (5) x (21)  1000

(29)

Operating costs (26) + (27) + (28) + (29)

(30)

Annual operating costs (30)  (4)

(31)

The Lighting Handbook

Pay-back period* =

(25) Option 2 (25) Option 1


(31) Option 1 (31) Option 2

Pay-back period* =

years

years

* excludes depreciation and interest

Chapter 8 / 13

Seite 13

00_INHALTSVER_uk.qxd

24.06.2004

10:21 Uhr

Seite 2

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

Chapter 9

Technical information
Ceiling Brightness Impression . . . . . . . . . . . . . . . . .
2
Ceiling Illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
Luminance Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
Protection classes . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
Degrees of protection . . . . . . . . . . . . . . . . . . . . . . . . . 5 7
Fire protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 9
Chemical effects on materials . . . . . . . . . . . . . . . . . . . 10 12
Short-circuit protection and loading of circuits . . . . . . . 13 20
Low-voltage installations . . . . . . . . . . . . . . . . . . . . . . 21 23

Seite 1

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

Ceiling Brightness Impression


The LG3 criteria have always required that the ceiling is relatively well illuminated, but under the Category System for
Downlighters, the market defaulted to luminaire selection with
no emphasis on other qualitative criteria.
The LG3 Addendum solved this by banning the Category System
and setting a target for illuminating the ceiling to at least 30 %
of the task illuminance. The use of an illuminance ratio in lux on
the ceiling is crude but easy to calculate, however difficult to
measure.
The intention is unequivocal: To maintain the brightness of the
ceiling within certain limits to avoid the so called cave effect.
Zumtobel Staff recognise that many luminaire types, especially
those with Dual Components that emit some light at high
angles, actually in themselves contribute to the Brightness
Impression.
In consequence we have developed an application programme
that can calculate the CBI Ceiling Brightness Impression for
any luminaire (of any manufacture).
The CBI application uses the algorithms from the standard Glare
Calculation and the output data is presented for each luminaire
type for crosswise and endwise viewing. The basis of the calculation is to take notional room sizes in ratios of h value just as
the Glare calculation. Then for a regular array of luminaires it
first calculates for varying room reflectance the illuminance on
the ceiling. It converts this to brightness. Then it takes each luminaire and calculates the brightness subtended at the viewers
eye. This is weighted by the solid angle so distance and elevation is accounted for. Any luminaires proximate to the viewer
that exceed 2,000 cd/m2 are excluded, as these are considered
to be glaring and not contributing to the overall brightness impression.

The Lighting Handbook

A typical luminaire CBI chart is shown below, for a Mellow IV


Recessed luminaire. As would be known such a luminaire would
only achieve about 20 % task illuminance on the ceiling, but
when you account for the additive effect of luminaires in the
space the overall brightness average calculate back to lux equivalency, easily achieves a CBI or Ceiling Brightness Impression
exceeding 30.

Seite 2

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

Ceiling Illuminance
Surface Dual Component
Luminaries
Directly illuminate ceiling and
walls
Provide measureable brightness
Provide increased
brightness impression

The Lighting Handbook

Fully recessed Dual


Component Luminaires
Directly illuminate walls
Do not directly illuminate
ceiling
Create apparent brightness
Provide increased
brightness impression

Chapter 9 / 3

Seite 3

4 / Chapter 9
Make and Model
LG Flatron 915FT Plus
Nokia 500Xa 15" FDP
Compaq TFT 5005 15" FPD
LG Flatron LCD 575 MS 15" FPD
NEC Multisync LCD1760NX
Samsung Syncmaster 700 IFT 17" CRT
NEC Multisync 1810X
Nocia Pro 800+ 18" FPD
Dell Ultrasharp 1504FP
Ilyama LS902UT Visionmaster 1451
Ilyama TXA 3813MT 15" FPD
Compaq 7500 PE1163T
Toshiba Tecra 8000 LAPTOP
Samsung Syncmaster 700 TFT 17" FP
LG Studioworks 5000 LC 15" FPD
Samsung 15" FPD
LG Studioworks 880 LC 18" FPD
Dell D828L 14" CRT
Samsung Syncmaster 753s
Samsung Syncmaser 550s 15" CRT
AOC 4NLR 14" CRT

Date of mnfr.
Dec-02
Jun-99
Oct-00
Nov-00
Apr-03
Nov-99
Oct-99
Oct-99
Nov-02
Feb-02
Feb-02
Feb-02
Jan-99
Feb-99
Feb-99
Dec-99
Dec-99
Dec-97
Oct-01
Oct-01
Jan-95
I
I
I
I
I
I
I
I
I
I
II
I
I
I

Class
I
I
I
I
I
I

Increasing
tolerance
to reflections

24.06.2004

The Lighting Handbook

Lmax (cd/m2)
positive
Type
9500 CRT
4900 FDP
4400 FPD
3800 FPD
3700 FPD
3700 CRT
3500 FPD
3500 FPD
3200 FPD
3100 CRT
2700 FPD
2200 CRT
2000 LAPTOP 1
1900 FPD
1800 FPD
LG3 Limit
1700 FPD
2
1,500 cd/m 1400 FPD
1400 CRT
1300 CRT
1200 CRT
900 CRT

09_ELEKTROTECH_uk.qxd
9:51 Uhr

Luminance Limit
Modern computer screens are increasingly tolerant to reflections.
BS EN 29241-7 Ergonomic requirements for office work with
visual display terminals.

Seite 4

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

Protection classes
Zumtobel Staff luminaires are classified into the following
protection classes a measure intended to afford protection against electric shock.
Class I luminaires
Class I is not identified by a symbol; the luminaire is intended to be connected to a protective earth conductor
which bears the mark. Most Zumtobel Staff luminaires
are designed in accordance with protection class I unless
otherwise stated.
Class II luminaires
Class II luminaires have total insulation but no protective
earth terminal. The Zumtobel Staff range includes protection class II luminaires, for instance moisture-proof batten
luminaires and moisture-proof diffuser luminaires.
Class III luminaires
Class III identifies luminaires that are intended for operation
with a protective extra low voltage (50 V max.).
Zumtobel Staff architectural luminaires include class III
luminaires, e.g. PRIO low-voltage spotlights.
Protection class I
Protection class II
Protection class III

Degrees of protection
Degrees of protection indicate the following properties
of equipment:

The Lighting Handbook

The quality of its protection against direct contact


Its sealing against ingress of solid foreign bodies
(dust, stones, sand, etc.)
Its sealing against the ingress of water

Chapter 9 / 5

Seite 5

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

The type of protection is defined by two degrees of protection in


accordance with IEC 529:
Degree of shock-hazard protection and protection against
ingress of solid foreign bodies (1st digit)
Degree of protection against the ingress of water (2nd digit)
For example IP 23:
IP

INGRESS PROTECTION
Protection against ingress of solid foreign bodies
having a < 12 mm (medium-sized solid bodies),
insertion of fingers or objects.
Protection against ingress of water falling at any angle up to 60 from
vertical. There must be no adverse effect (spray water).

Degrees of protection for technical luminaires


Protection against ingress of solid foreign bodies as per
first digit
IP 0X
IP 1X
IP 2X
IP 3X
IP 4X
IP 5X
IP 6X

Unprotected against ingress of solid foreign bodies


Protection against solid bodies > 50 mm
Protection against solid bodies > 12 mm
Protection against solid bodies > 2.5 mm
Protection against solid bodies > 1 mm
Dust-protected (limited ingress of dust)
Dust-tight (no ingress of dust)

IP X5
IP X6
IP X7
IP X8

No special protection
Drip-proof protection against water drops
Protection against water drops up to 15 from the vertical
Rainproof protection against spray water up to 60
Splash-proof protection against spray water from all
directions
Jet-proof protection against jets of water
Protection against heavy seas (conditions on ship decks)
Watertight protection against immersion (pressure and
time specified)
Protection against immersion under pressure (with
instructions from manufacturer)

6 / Chapter 9

The Lighting Handbook

Protection against moisture as per second digit


IP X0
IP X1
IP X2
IP X3
IP X4

Seite 6

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

Applications for luminaires with increased protection


Damp locations
Bakeries
Manure sheds
Animal-feed preparation facilities
Industrial kitchens
Boiler rooms
Commercial workshops
Granaries
(Deep-freeze) cold storage
Pump houses
Sculleries
Laundries
Wet locations

IP X1
IP X1
IP X1
IP X1
IP X1
IP 20
IP X1
IP X1
IP X1
IP X1
IP X1

The following generally


applies:
IP X5: for cleaning using
water jets
IP X4: in rinsing areas

Beer or wine cellars


Shower cubicles
Meat processing facilities
Electroplating facilities
Greenhouses
Dairies
Workshops using wet processes
Car wash areas
Agricultural facilities

IP X4
IP X4
IP X5
IP X4
IP X4
IP X4
IP X4
IP X4

The following generally


applies:
IP X5: for cleaning using
water jets

The Lighting Handbook

Beer or wine cellars


IP 44
Shower cubicles
IP 44
Stores, storerooms for hay,
straw, feedstuff
IP 44
Intensive stock farming
IP 44
Animal sheds
IP 44
Adjoining rooms of animal sheds IP 44
Facilities with increased fire risk
Workrooms
Woodworking
Sawmills
Paper processing
Textile processing
Treatment and fabrication
Gymnasia and sports halls

IP 50
IP 50
IP 50
IP 50
IP 50
IP 50

Badminton courts
Squash courts
Indoor tennis courts
Gymnasia and sports halls

IP 20
IP 20
IP 20
IP 20

The following generally


applies:
IP X5: for cleaning using
water jets
IP 54+FF: when increased
fire risk

ballproof luminaires
ballproof luminaires with
all-round cover; maximum
mesh size 60 mm
Chapter 9 / 7

Seite 7

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

Fire protection
Luminaire identification marking
The following criteria must be taken into account:
Position of normal use
Fire behaviour of environment and mounting surfaces
Minimum clearance from combustible substances and materials
Luminaires with thecmark
Luminaires which carry thecmark must be constructed so
that the temperature on the mounting surface does not exceed
130 C during abnormal operation, and does not exceed 180 C
in the event of a ballast fault. Luminaires with this mark are
suitable for direct mounting on parts of buildings made of noncombustible, flame-retardant or normally flammable building
materials according to DIN 4102.

/Umark
Luminaires with the
Both marks regulate the surface temperatures of luminaires.
External surfaces on which readily flammable substances such
as dust or fibrous materials may accumulate when luminaires
are installed as prescribed must not exceed specific temperatures. The d luminaire mark was withdrawn in 1999.
A validity transition period allows the d mark to be used until
01. 08. 2005. TheUmark introduced in EN 60598 has applied
since 01.08.1998. The d mark limits the temperature on
horizontal surfaces to 95 C during normal operation and 115 C
in the event of a ballast fault. Temperatures must not exceed
220 C on vertical surfaces. In order to fulfil the criteria of
theUmark, the surface temperature on horizontal surfaces
must not exceed 90 C. The maximum temperature in the event
of a fault is 115 C, the same as for the d mark. The temperature must not exceed 150 C on vertical surfaces.
Luminaires with theQmark
Luminaires which carry theQmark are intended for installation
in furniture. They are designed so that in the event of a ballast
fault, flame-retardant and normally flammable materials as specified in DIN 4102 cannot be ignited, e.g. in corners of wooden
furniture. The materials may be painted, veneered or varnished.

8 / Chapter 9

The Lighting Handbook

mark
Luminaires with the
Luminaires which carry the q mark are intended for mounting
in or on furniture made of materials whose flammability is not
known. They are designed so that in normal operation any
mounting surface or other adjacent furniture surfaces do not
exceed a temperature of 95 C.

Seite 8

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

The Lighting Handbook

Fire protection: Place of use Mark Requirements

Chapter 9 / 9

Seite 9

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

Chemical effects on materials


No material is resistant to
all chemical influences.
The effects of chemicals vary
widely and take up entire
volumes of resistance tables.
The table on the opposite page
can therefore only give a brief
overview of effects of some
frequently occurring chemicals
and is subject to the following
conditions:
The chemical substance
listed in the table is a basic
material and not part of a
chemical compound.
The ambient temperature
is 22 C.
A great many complaints could
be avoided if due consideration were given during the
planning stage to the situation
in which the luminaire is going
to be used.
What are the key factors?

2. Applications
The following applications are
just a few examples of situations in which material
damage may occur:
Chemical and petrochemical industry
Foodstuffs industry (cheese
production, dairies, meat
processing, breweries)
Agriculture
Fishing industry
Kitchens and industrial
cooking facilities
Car wash facilities
Production facilities and
workshops using a high
level of oil and grease
3. Chemical composition
The chemical composition
should be discussed with
every operator.
4. Degree of saturation of
chemical substances

1. Luminaire materials

10 / Chapter 9

5. Ambient temperature
Depending on the type and
composition of the substances,
chemical reactions will take
place over a range of temperatures. We should be glad to
provide further advice if you
have any questions or doubts
about the resistance of any
materials.

The Lighting Handbook

A luminaire consists of several


parts having different functions
and which are therefore made
from different materials (base
plate, cover, seal, closures,
cable inlets, etc.).

Seite 10

09_ELEKTROTECH_uk.qxd

The Lighting Handbook

Chemical substance in question

24.06.2004

Stainless Alusteel minium

Acetic acid up to 5 %
Acetic acid up to 30 %
Acetone
Alcohol up to 30 %
Alcohol, concentrated
Aliphatic
hydrocarbons
Ammonia 25 %
Aniline
Aromatic
hydrocarbons
Battery acid
Beer
Benzene
Blood
Bromic acid
Carbon dioxide
Carbon monoxide
Carbon tetrachloride
Caustic soda solution 2 %
Caustic soda solution 10 %
Chloroform
Chlorophenol
Diesel oil, crude oil
Dioxan
Ether
Ethyl acetate (ester)
Glycerine
Glycol
Glysantin
Hydrochloric acid
up to 20 %
above 20 %
Hydrogen peroxide
up to 40 %
over 40 %

9:51 Uhr

Poly- Polymeth- Polyester acrylate..carbonate

= resistant, = resistant to limited extent, = not resistant

Chapter 9 / 11

Seite 11

09_ELEKTROTECH_uk.qxd

Chemical substance in question

24.06.2004

Stainless Alusteel minium

Ketones
Lime milk
Lysol
Methylene chloride
Methanol
Metal salts and their
aqueous solutions
Naphtha (cleaners naphtha)
Petrolium ether
Pyridine
Phenol
Nitric acid
up to 10 %
up to 20 %
above 20 %
Sea water
Soap-suds
Soda
Sodium chloride solution
Sulphuretted hydrogen
Sulphuric acid
up to 50 %
up to 70 %
above 70 %
Sulphurous acid
up to 5 %
Synthetic detergents
Turpentine
Water up to 60 C
Xylene

9:51 Uhr

Poly- Polymeth- Polyester acrylate..carbonate

12 / Chapter 9

The Lighting Handbook

= resistant, = resistant to limited extent, = not resistant

Seite 12

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

Short-circuit protection and loading of circuits


Miniature circuit breakers
Trip characteristic

Range

B
C
D

over 3 ln to 5 ln
over 5 ln to 10 ln
over 10 ln to 20 ln

Maximum number of fluorescent lamps per


miniature circuit breaker
Number of fluorescent lamps with conventional or
low-loss ballast for different lamp circuits
shunt p.f. correction

twin-lamp

Trip characteristic
Rated current A
TC 9/11 W
TC-D 13 W
TC-D 18 W
TL + TC-L 18 W
TC-L 24 W
TC-D + T 26 W
TL + TC-L 36 W
TL 58 W
TC 9/11 W
TC-D 13/18 W
TC 18 W
TC-L 18/24 W
TC-D + -T 26 W
TL + TC-L 36 W
TL 58 W
TC-L 24 W
TC-D + -T 26 W
TL + TC-L 18 W
TC + TC-L 36 W
TL 58 W

inductive

10

62

47 27

30

23 14 71 71

32

32 20

60

54 46 28

16 100

75 43

48

37 23 114 114

51

51 32

96

86 74 46

20 125

94 53

60

46 28 144 144

64

64 41

120 106 92 56

25 156 115 66

75

57 36 179 179

79

79 51

150 132 114 72

10

62

47 27

30

23 14 99 99

44

44 27

60

54 46 28

16 100

75 43

48

37 23 159 159

71

71 44

96

86 74 46

20 125

94 53

60

46 28 201 201

89

89 56

120 106 92 56

25 156 115 66

75

57 36 250 250

110

110 71

150 132 114 72

Loading of automatic circuit breakers for metal halide


lamps Maximum recommended number of electronic
ballasts per automatic circuit breaker

The Lighting Handbook

Electronic ballasts for HIT/HIT-DE/HIE and


HIT-CE/HIT-TC-CE/HIT-DE-CE/HIE-CE metal halide lamps,
non-dimming (TRIDONIC PCI series):
C10
1.5
mm2

C13
1.5
mm2

C16
1.5
mm2

C20
2.5
mm2

B10
1.5
mm2

B13
1.5
mm2

B16
1.5
mm2

B20
2.5
mm2

1/20 W HI

24

33

42

48

12

15

19

19

1/35 W HI

16

22

28

32

10

13

13

1/70 W HI

10

18

26

30

10

13

13

1/150 W HI

14

20

20

Chapter 9 / 13

Seite 13

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

Loading of automatic circuit breakers for electronic ballasts


for fluorescent and compact fluorescent lamps Maximum
recommended number of electronic ballasts per automatic
circuit breaker
Electronic ballasts for T16 fluorescent lamps, non-dimming
(TRIDONIC PC T5 PRO series):

1/14 W
2/14 W
3/14 W
4/14 W
1/21 W
2/21 W
1/28 W
2/28 W
1/35 W
2/35 W
1/24 W
2/24 W
1/39 W
2/39 W
1/54 W
2/54 W
1/49 W
2/49 W
1/80 W

T16
T16
T16
T16
T16
T16
T16
T16
T16
T16
T16
T16
T16
T16
T16
T16
T16
T16
T16

C10
1.5
mm2
46
46
30
30
46
46
44
18
46
20
46
30
30
18
30
14
30
18
18

C13
1.5
mm2
80
80
46
46
80
78
78
28
80
30
80
50
40
28
46
20
46
28
28

C16
1.5
mm2
80
80
50
50
86
80
80
30
80
30
80
50
50
30
50
24
50
30
30

C20
2.5
mm2
140
140
64
64
98
100
90
36
140
44
140
64
60
36
80
30
58
36
36

B10
1.5
mm2
23
23
15
15
23
23
22
9
23
10
23
15
15
9
15
7
15
9
9

B13
1.5
mm2
40
40
23
23
40
39
39
14
40
15
40
25
20
14
23
10
23
14
14

B16
1.5
mm2
40
40
25
25
43
40
40
15
40
15
40
25
25
15
25
12
25
15
15

B20
2.5
mm2
70
70
32
32
49
50
45
18
70
22
70
32
30
18
40
15
29
18
18

1/18 W
2/18 W
3/18 W
4/18 W
1/36 W
2/36 W
1/58 W
2/58 W

T26
T26
T26
T26
T26
T26
T26
T26

14 / Chapter 9

C10
1.5
mm2
46/46
30/44
32/
20/
32/46
20/20
32/32
14/14

C13
1.5
mm2
80/80
46/80
46/
30/
48/80
30/30
46/46
20/20

C16 C20
1.5
2.5
mm2 mm2
104/140 110/140
68/140 84/140
66/ 80/
40/ 44/
70/140 84/140
40/42 44/44
66/66 80/80
26/26 30/30

B10
1.5
mm2
23/23
15/22
16/
10/
16/23
10/10
16/16
7/7

B13
1.5
mm2
40/40
23/40
23/
15/
24/40
15/15
23/23
10/10

B16
1.5
mm2
52/70
34/70
33/
20/
35/70
20/21
33/33
13/13

B20
2.5
mm2
55/70
42/70
40/
22/
42/70
22/22
40/40
15/15

The Lighting Handbook

Electronic ballasts for T26 fluorescent lamps, non-dimming


(TRIDONIC PC E011/PC T8 PRO series):

Seite 14

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

Electronic ballasts for T16 fluorescent lamps, Basic


dimming/Dali dimming (TRIDONIC PCA T5 ECO/PCA T5 EXCEL
one4all series):

1/14 W
2/14 W
3/14 W
4/14 W
1/21 W
2/21 W
1/28 W
2/28 W
1/35 W
2/35 W
1/24 W
2/24 W
1/39 W
2/39 W
1/54 W
2/54 W
1/80 W

T16
T16
T16
T16
T16
T16
T16
T16
T16
T16
T16
T16
T16
T16
T16
T16
T16

C10
1.5
mm2
30
22
16
16
30
22
32
16
32
16
22
22
22
14
22
14
10

C13
1.5
mm2
50
32
26
24
50
32
50
22
50
22
32
32
32
22
32
22
20

C16
1.5
mm2
70
44
34
34
70
44
72
30
70
30
44
46
44
28
44
28
30

C20
2.5
mm2
80
50
42
38
76
50
80
34
80
34
50
52
50
34
50
34
30

B10
1.5
mm2
15
11
8
8
15
11
16
8
16
8
11
11
11
7
11
7
5

B13
1.5
mm2
25
16
13
12
25
16
25
11
25
11
16
16
16
11
16
11
10

B16
1.5
mm2
35
22
17
17
35
22
36
15
35
15
22
23
22
14
22
14
15

B20
2.5
mm2
40
25
21
19
38
25
40
17
40
17
25
26
25
17
25
17
15

Electronic ballasts for T26 fluorescent lamps, Basic


dimming/Dali dimming (TRIDONIC PCA T8 ECO/PCA T8 EXCEL
one4all series):

The Lighting Handbook

1/18 W
2/18 W
3/18 W
4/18 W
1/30 W
2/30 W
1/36 W
2/36 W
1/58 W
2/58 W

T26
T26
T26
T26
T26
T26
T26
T26
T26
T26

C10
1.5
mm2
30
20
12
12
30
10
30
10
20
10

C13
1.5
mm2
50
30
18
16
50
20
50
20
30
20

C16
1.5
mm2
80
40
24
24
70
30
70
30
40
30

C20
2.5
mm2
80
46
30
28
76
30
76
30
46
30

B10
1.5
mm2
15
10
6
6
15
5
15
5
10
5

B13
1.5
mm2
25
15
9
8
25
10
25
10
15
10

B16
1.5
mm2
40
20
12
12
35
15
35
15
20
15

B20
2.5
mm2
40
23
15
14
38
15
38
15
23
15

Chapter 9 / 15

Seite 15

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

Electronic ballasts for TC-L compact fluorescent lamps,


Basic dimming/Dali dimming (TRIDONIC PCA TCL ECO/
PCA TCL EXCEL one4all series):

1/18 W
2/18 W
1/24 W
2/24 W
1/36 W
2/36 W
1/40 W
2/40 W
1/55 W
2/55 W
1/80 W

TC-L
TC-L
TC-L
TC-L
TC-L
TC-L
TC-L
TC-L
TC-L
TC-L
TC-L

C10
1.5
mm2
30
30
30
30
80
20
30
14
20
10
18

C13
1.5
mm2
50
50
50
50
80
30
50
20
30
14
28

C16
1.5
mm2
80
80
80
80
80
40
80
26
40
20
30

C20
2.5
mm2
80
80
80
80
100
40
80
30
40
22
36

B10
1.5
mm2
15
15
15
15
40
10
15
7
10
5
9

B13
1.5
mm2
25
25
25
25
40
15
25
10
15
7
14

B16
1.5
mm2
40
40
40
40
40
20
40
13
20
10
15

B20
2.5
mm2
40
40
40
40
50
20
40
15
20
11
18

Electronic ballasts for TC-L compact fluorescent lamps,


non-dimming (TRIDONIC PC PRO FSD series):

TC-L
TC-L
TC-L
TC-L
TC-L
TC-L
TC-L
TC-L
TC-L
TC-L
TC-L

16 / Chapter 9

C13
1.5
mm2
50
50
50
50
80
30
50
20
30
14
28

C16
1.5
mm2
80
80
80
80
80
40
80
26
40
20
30

C20
2.5
mm2
80
80
80
80
100
40
80
30
40
22
36

B10
1.5
mm2
15
15
15
15
40
10
15
7
10
5
9

B13
1.5
mm2
25
25
25
25
40
15
25
10
15
7
14

B16
1.5
mm2
40
40
40
40
40
20
40
13
20
10
15

B20
2.5
mm2
40
40
40
40
50
20
40
15
20
11
18

The Lighting Handbook

1/18 W
2/18 W
1/24 W
2/24 W
1/36 W
2/36 W
1/40 W
2/40 W
1/55 W
2/55 W
1/80 W

C10
1.5
mm2
30
30
30
30
80
20
30
14
20
10
18

Seite 16

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

Electronic ballasts for TC-DEL/TEL compact fluorescent


lamps, non-dimming (TRIDONIC PC PRO series):

1/13 W TC-DEL/
TC-TEL
2/13 W TC-DEL/
TC-TEL
1/18 W TC-DEL/
TC-TEL
2/18 W TC-DEL/
TC-TEL
1/26 W TC-DEL/
TC-TEL
2/26 W TC-DEL/
TC-TEL
1/32 W TC-TEL
2/32 W TC-TEL
1/42 W TC-TEL
2/42 W TC-TEL
1/57 W TC-TEL

C10
1.5
mm2

C13
1.5
mm2

C16
1.5
mm2

C20
2.5
mm2

B10
1.5
mm2

B13
1.5
mm2

B16
1.5
mm2

B20
2.5
mm2

80

80

80

100

40

40

40

50

80

80

80

100

40

40

40

50

80

80

80

100

40

40

40

50

30

50

80

80

15

25

40

40

30

50

80

80

15

25

40

40

32
30
16
30
16
20

50
50
22
50
22
30

80
80
30
80
30
30

80
80
44
80
44
44

16
15
8
15
8
10

25
25
11
25
11
15

40
40
15
40
15
15

40
40
22
40
22
22

The Lighting Handbook

Electronic ballasts for TC-DEL/TEL compact fluorescent


lamps, Basic dimming/Dali dimming (TRIDONIC PCA ECO/
PCA EXCEL one4all series):

1/13 W TC-DEL/
TC-TEL
2/13 W TC-DEL/
TC-TEL
1/18 W TC-DEL/
TC-TEL
2/18 W TC-DEL/
TC-TEL
1/26 W TC-DEL/
TC-TEL
2/26 W TC-DEL/
TC-TEL
1/32 W TC-TEL
2/32 W TC-TEL
1/42 W TC-TEL
2/42 W TC-TEL

C10
1.5
mm2

C13
1.5
mm2

C16
1.5
mm2

C20
2.5
mm2

B10
1.5
mm2

B13
1.5
mm2

B16
1.5
mm2

B20
2.5
mm2

40

60

80

80

20

30

40

40

28

40

60

64

14

20

30

32

30

50

70

76

15

25

35

38

22

32

46

68

11

16

23

34

30

50

70

76

15

25

35

38

22
26
10
26
10

32
38
18
38
18

46
50
24
50
24

56
58
28
58
28

11
13
5
13
5

16
19
9
19
9

23
25
12
25
12

28
29
14
29
14

Chapter 9 / 17

Seite 17

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

Loading of automatic circuit breakers for high-pressure


lamps Maximum recommended number of ballasts per
automatic circuit breaker
Conventional ballasts for HIT/HIT-DE/HIE metal halide
lamps, uncompensated
Lamp values
Number of ballasts per automatic circuit breaker
W V A
C10 C16 C20 C25 B10 B16 B20 B25
35 230 0.53 11
18
23
29
9
15
18
23
70 230 0.98 7
11
14
17
5
8
9
12
150 230 1.8
4
6
7
9
2
4
5
6
250 230 3
2
3
4
5
1
2
3
4
400 230 3.5
2
3
4
5
1
2
2
3

Conventional ballasts for HST/HST-DE/HSE high-pressure


sodium vapour lamps, uncompensated
Lamp values
Number of ballasts per automatic circuit breaker
W V A
C10 C16 C20 C25 B10 B16 B20
50 230 0.77 9
14
18
22
6
10
13
70 230 1
7
11
14
17
5
8
10
100 230 1.2
6
9
11
14
4
6
8
150 230 1.8
4
6
7
9
2
4
5
250 230 3
2
3
4
5
1
2
3
400 230 4.4
1
2
3
4
1
1
2

B25
16
12
10
7
4
2

Conventional ballasts for HME high-pressure mercury


vapour lamps, uncompensated

18 / Chapter 9

B25
20
15
10
5
2
1

The Lighting Handbook

Lamp values
Number of ballasts per automatic circuit breaker
W V A
C10 C16 C20 C25 B10 B16 B20
50 230 0.6
10
15
18
23
8
13
16
80 230 0.8
6
9
11
14
6
10
12
125 230 1.15 4
6
7
9
4
7
9
250 230 2.15 2
3
3
4
2
3
4
400 230 3.25 1
2
3
3
1
2
2
700 230 5.4
1
1
1
2

1
1

Seite 18

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

Conventional ballasts for HIT/HIT-DE/HIE metal halide


lamps, compensated
Lamp
values
W V
35 230
70 230
150 230
250 230
400 230

ComNumber of ballasts per automatic circuit breaker


pensation C10 C16 C20 C25 B10 B16 B20
6 F 22
36
45
50
11
18
23
12 F 12
18
23
29
8
13
16
20 F 7
11
14
17
5
8
10
32 F 5
7
9
11
3
5
6
35 F 3
5
7
8
2
4
5

B25
27
20
12
8
6

Conventional ballasts for HST/HST-DE/HSE high-pressure


sodium vapour lamps, compensated
Lamp
values
W V
50 230
70 230
100 230
150 230
250 230
400 230

ComNumber of ballasts per automatic circuit breaker


pensation C10 C16 C20 C25 B10 B16 B20
10 F 16
24
31
38
11
17
22
12 F 12
18
23
29
8
13
16
12 F 10
16
20
25
7
11
14
20 F 7
11
14
17
5
8
10
36 F 5
7
9
11
3
5
6
45 F 3
4
5
7
2
3
4

B25
27
20
17
12
8
5

Conventional ballasts for HME high-pressure mercury


vapour lamps, compensated

The Lighting Handbook

Lamp
values
W V
50 230
80 230
125 230
250 230
400 230
700 230

ComNumber of ballasts per automatic circuit breaker


pensation C10 C16 C20 C25 B10 B16 B20 B25
7 F 19
31
39
49
10
15
18
23
8 F 12
19
24
30
6
9
11
14
10 F 7
12
15
19
4
6
7
9
18 F 4
6
7
9
2
3
3
4
25 F 2
4
5
6
1
2
2
2
40 F 1
2
2
3

1
1
1

Chapter 9 / 19

Seite 19

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

Loading of automatic circuit breakers for low-voltage


halogen incandescent lamps Maximum recommended
number of transformers per automatic circuit breaker
Magnetic transformers for QT/QR/QR-CB(C) halogen
incandescent lamps (TRIDONIC TMBx/OMTx series):
Power
20 W
35 W
50 W
70 W
80 W
105 W
150 W
210 W
300 W

C10
58
41
21
15
14
8
4
23
12

C16
93
65
35
24
22
13
6
45
23

B10
29
20
10
7
7
4
2
1
n.r.

B16
46
32
17
12
11
6
3
2
1

n.r. = not recommended

Magnetic transformers for QT/QR/QR-CB(C) halogen


incandescent lamps (TRIDONIC TMAx/TMDx series):
Power
20 W
35 W
40 W
50 W
60 W
70 W
80 W
105 W

C10
42
35
26
23
21
16
13
9

C16
67
56
43
37
33
26
21
14

B10
21
17
13
11
10
8
6
4

B16
33
28
21
18
16
13
10
7

Magnetic transformers for QT/QR/QR-CB(C) halogen


incandescent lamps (TRIDONIC OGT series):
Power
250 W
300 W
500 W

C10
34
2
1

C16
56
34
12

B10
12
1
n.r.

B16
23
12
n.r.

20 / Chapter 9

The Lighting Handbook

n.r. = not recommended

Seite 20

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

Low-voltage installation
Service life and luminous flux

Multiplication factor for relative operating values

The service life and luminous flux of low-voltage halogen lamps


are extremely voltage dependent. Voltage changes on the line
side are transferred to the secondary side in the same ratio.
A 1 V overvoltage
is insignificant for
a 230 W halogen
4
lamp. For a 12 V
halogen lamp,
3
however, this
represents an
2
overvoltage of
8 % which re1 = duces the average
100%
service life of the
0.8
0.6
halogen lamp,
0.4
e.g. from 3,000
0.3
hours to approx.
0.2
1,200 hours.

50

30

6
5

20

Lh

10
8
6

4
2

1=
100%
0.8
0.7
0.6
0.5
0.4
0.3
0.2

Lh

0.15
60 %

80 %

100 % 120 %

0.1
0.08
0.06
0.04
0.03
0.02

140 %

= luminous flux
Lh = service life

Voltage as % of nominal voltage

Operation at rated load


Magnetic transformers should be operated at rated load as far as
possible so as to avoid any rise in the secondary voltage which
can result in a reduction in lamp service life (5 % overvoltage
corresponds to 30 % shorter life).
Conductor cross-sections and voltage drop

The Lighting Handbook

Because the voltages are small, large currents flow on the


secondary side. If conductors are long and have small crosssections, this can result in considerable voltage drops. Crosssections must be chosen so that the voltage drop across the
conductor between transformer and lamp does not exceed 5 %.

Chapter 9 / 21

Seite 21

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

Required conductor cross-sections in mm2 as a function of


transformer rating and cable length (one-way line length) for
magnetic transformers:
Transformer
rating

20 VA
50 VA
1OO VA
150 VA
200 VA

Cable length in m

up to 2 m up to 4 m
1.5
1.5
1.5
1.5
1.5
2.5
2.5
4
4
4

up to 6 m
1.5
1.5
4
6
6

up to 8 m
1.5
2.5
4
6
10

up to 10 m up to 12 m
1.5
1.5
2.5
4
6
6
10
10
10
16

Installation
The distance between transformer and lamps must be as short
as possible (minimum distance, however, is approx. 30 cm) in
order to avoid the relatively large conductor cross-sections.
On the other hand, there is often unwanted humming, especially
when lighting is adjusted; therefore the transformer must be
installed out of earshot if possible.

Transformer

22 / Chapter 9

The Lighting Handbook

Wherever possible, cables must be laid in a star configuration


and be of equal length to ensure that all lamps receive the same
voltage.

Seite 22

09_ELEKTROTECH_uk.qxd

24.06.2004

9:51 Uhr

Transformers and light regulation


Only approved safety transformers should be used. The ambient
temperature must not exceed 50 C max. Please note that transformers for use in areas which present fire risks must carry the
appropriate conformity mark (e.g. ,
, ,
).
Phase control
Halogen lamps are operated with a magnetic transformer.
Reverse phase control
Halogen lamps are operated with an electronic transformer in
the high-frequency range. Important: do not exceed maximum
conductor length.
Safety measures when operating low-voltage
halogen lamps
Low-voltage halogen lamps generate a huge amount of heat.
In the case of recessed luminaires, make sure there is adequate
heat removal and that the safety distances from combustible
materials are observed.
The necessary safety distances from the illuminated surface
also apply when using spotlights. These are identified by the
following symbol and details of the relevant distance in metres:

The Lighting Handbook

Chapter 9 / 23

Seite 23

00_INHALTSVER_uk.qxd

24.06.2004

10:21 Uhr

Seite 2

10_NOTIZEN_uk.qxd

24.06.2004

10:51 Uhr

The Lighting Handbook

Personal Notes

Chapter 10

Seite 1

10_NOTIZEN_uk.qxd

24.06.2004

10:51 Uhr

Seite 2

Chapter 10

The Lighting Handbook

Personal Notes

10_NOTIZEN_uk.qxd

24.06.2004

10:51 Uhr

The Lighting Handbook

Personal Notes

Chapter 10

Seite 3

10_NOTIZEN_uk.qxd

24.06.2004

10:51 Uhr

Seite 4

Chapter 10

The Lighting Handbook

Personal Notes

10_NOTIZEN_uk.qxd

24.06.2004

10:51 Uhr

The Lighting Handbook

Personal Notes

Chapter 10

Seite 5

10_NOTIZEN_uk.qxd

24.06.2004

10:51 Uhr

Seite 6

Chapter 10

The Lighting Handbook

Personal Notes

00_INHALTSVER_uk.qxd

24.06.2004

10:10 Uhr

United Kingdom

Norway

Zumtobel Staff Lighting Ltd.

Zumtobel Staff Belysning AS

Unit 4 - The Argent Centre,

Industriveien 11

Pump Lane

1481 Hagan

Hayes/Middlesex UB3 3BL

Tel: +47/(0)670/62230

Tel. +44/(0)20 8589 1800

Fax: +47/(0)670/62269

Fax +44/(0)20 8756 4800

Email: firmapost@zumtobelstaff.no

Email: enquiries@uk.zumtobelstaff.co.at
www.zumtobelstaff.co.uk

Sweden
Zumtobel Staff AB

USA and Canada

Norr Mlarstrand 8

Zumtobel Staff Lighting

11220 Stockholm

3300 Route 9W

Tel: +46/(0)8/6511480

Highland, New York 1258-2630

Fax: +46/(0)8/265605

Tel. +1/(0)845/691 62 62

E-mail: info@zumtobelstaff.se

Fax +1/(0)845/691 62 89
www.zumtobelstaff.us

Head offices
Zumtobel Staff GmbH

Australia and New Zealand

Schweizer Strasse 30

Zumtobel Staff (Australia) Pty. Ltd.

Postfach 72

2 Wella Way

A-6851 Dornbirn, AUSTRIA

Somersby, NSW 2250

Tel. +43/(0)5572/390-0

Tel. +61/(2)4340 3200

Fax +43/(0)5572/22 826

Fax +61/(2)4340 2108


Email: info@zumtobelstaff.com.au

Zumtobel Staff GmbH & Co. KG

www.zumtobelstaff.com.au

Grevenmarschstr. 74-78
D-32657 Lemgo, GERMANY
Tel. +49/(0)5261/2 12-0
Fax +49/(0)5261/2 12-7777
www.zumtobelstaff.de
www.zumtobelstaff.com