The reference title and language for this EAD is English. The applicable rules of copyright refer to the document elaborated in and published by
EOTA.
This European Assessment Document (EAD) has been developed taking into account up-to-date technical and scientific knowledge at the time
of issue and is published in accordance with the relevant provisions of Regulation (EU) No 305/2011 as a basis for the preparation and issuing of
European Technical Assessments (ETA).
EOTA 2015
3/24
Contents
1 SCOPE OF THE EAD .............................................................................................................................................5
1.1 Description of the construction product ...........................................................................................................5
1.2 Information on the intended use of the construction product...........................................................................6
1.2.1 Intended use.............................................................................................................................................6
1.2.2 Working life/Durability...............................................................................................................................6
2 ESSENTIAL CHARACTERISTICS AND RELEVANT ASSESSMENT METHODS AND CRITERIA....................7
2.1 Essential characteristics of the product ...........................................................................................................7
2.2 Assessment methods and criteria for the performance of the product in relation to essential characteristics
of the product .................................................................................................................................................11
2.2.1 Precast concrete composite wall with point connectors.........................................................................11
Basic requirement for construction works 1
2.2.1.1
Shape...........................................................................................................................................11
2.2.1.2
2.2.1.3
2.2.1.4
2.2.1.5
2.2.1.6
2.2.1.7
2.2.1.8
2.2.1.9
2.2.2.1
Shape...........................................................................................................................................14
2.2.2.2
Dimensions ..................................................................................................................................14
2.2.2.3
Material ........................................................................................................................................14
2.2.2.4
Steel failure due to tensile loading and combined pull-out and concrete cone failure ................14
2.2.2.5
2.2.2.6
2.2.2.7
2.2.2.8
2.2.2.9
EOTA 2015
4/24
2.2.3.1
2.2.3.2
2.2.3.3
EOTA 2015
5/24
s or (in absence of
EOTA 2015
6/24
Intended use
The precast concrete composite wall with point connectors is intended to be used for the construction of
external walls above or below ground and internal walls which are load bearing or non-load bearing, including
those that are subject to fire regulations.
The precast concrete composite wall with point connectors shall be subjected to static and quasi static actions
only.
1.2.2
Working life/Durability
The assessment methods included or referred to in this EAD have been written b
request to take into account a working life of the precast concrete composite wall with point connectors for
the intended use of 50 years when installed in the works provided that the is subject to appropriate
installation, see Clause 1.1. These provisions are based upon the current state of the art and the available
knowledge and experience.
When assessing the product the intended use as foreseen by the manufacturer shall be taken into account.
The real working life may be, in normal use conditions, considerably longer without major degradation
affecting the basic requirements for works1.
The indications given as to the working life of the construction product cannot be interpreted as a guarantee
neither given by the product manufacturer or his representative nor by EOTA when drafting this EAD nor by
the Technical Assessment Body issuing an ETA based on this EAD, but are regarded only as a means for
expressing the expected economically reasonable working life of the product.
The real working life of a product incorporated in a specific works depends on the environmental conditions to which that works is subject, as
well as on the particular conditions of the design, execution, use and maintenance of that works. Therefore, it cannot be excluded that in
certain cases the real working life of the product may also be shorter than the working life.
EOTA 2015
7/24
No
Essential characteristic
Assessment
method
Type of expression of
product performance
(Level, class,
description)
Shape
2.2.1.1
Description
2.2.1.2
Description
2.2.1.3
Level
Reaction to fire
2.2.1.4
Class
Resistance to fire
2.2.1.5
Class
2.2.1.6
Level
2.2.1.7
Level
2.2.1.8
Description
2.2.1.9
Description
2.2.1.10
Level
Basic requirement for construction works 6: Energy economy and heat retention
1)
11
Thermal conductivity
2.2.1.11
Level
12
Thermal resistance
2.2.1.12
Level
13
2.2.1.13
Level
EOTA 2015
8/24
Table 2: Essential characteristics of the connector and assessment methods and criteria for the performance
of the product in relation to those essential characteristics
No
Essential characteristic
Assessment
method
Type of expression of
product performance
(level, class,
description)
Shape
2.2.2.1
Description
Dimensions
2.2.2.2
Description
Material
2.2.2.3
Description
2.2.2.4
Level
2.2.2.5
Level
Splitting failure
2.2.2.6
Level
2.2.2.7
Level
2.2.2.8
Level
10
2.2.2.9
Level
11
Edge distance
2.2.2.10
Description
12
Centre spacing
2.2.2.11
Description
13
Corrosion protection
2.2.2.12
Description
Reaction to fire
2.2.2.13
EOTA 2015
Same as BWR 1
Class
9/24
Table 3: Essential characteristics of the two precast reinforced layers of concrete and methods and
assessment methods and criteria for the performance of the product in relation to those essential
characteristics
No
Essential characteristic
Assessment
method
Type of expression of
product performance
(level, class,
description)
2.2.3.1.1
Level
Yield strength Re
Tensile strength Rm
2.2.3.1.2
Level
Bendability
2.2.3.1.3
Description
2.2.3.1.4
Level
Rib spacing c
2.2.3.1.5
Description, Level
2.2.3.1.6
Description, Level
9
10
Rib height h
2.2.3.1.7
Description, Level
11
2.2.3.1.8
Description
13
14
15
16
Yield strength Re
17
Tensile strength Rm
18
19
20
Bendability
2.2.3.2.5
Description
21
2.2.3.2.6
Level
22
Rib spacing c
2.2.3.2.7
Description, Level
23
Rib in
2.2.3.2.8
Description, Level
24
Rib height h
2.2.3.2.9
Description, Level
25
2.2.3.2.10
Description
EOTA 2015
2.2.3.2.1
Level
Level
2.2.3.2.2
Level
2.2.3.2.3
Level
Level
2.2.3.2.4
Level
Level
Level
No
Essential characteristic
10/24
Assessment
method
Type of expression of
product performance
(level, class,
description)
Concrete layers
26
2.2.3.3.1
Description, Level
27
Shape
2.2.3.3.2
Description
28
2.2.3.3.3
Level
29
2.2.3.3.4
Level
30
Chloride content
2.2.3.3.5
Level
31
Alkali content
2.2.3.3.6
Level
32
2.2.3.3.7
Description
33
2.2.3.3.8
Level
34
2.2.3.3.9
Description, Level
35
Air content
2.2.3.3.10
Level
36
2.2.3.3.11
Level
37
2.2.3.3.12
Description
38
2.2.3.3.13
Description
39
Water absorption
2.2.3.3.14
Level
40
Compressive strength
2.2.3.3.15
Level
41
Reinforcement detailing
2.2.3.3.16
Description
Reaction to fire
2.2.3.4
Class
43
1)
2.2.3.5
EOTA 2015
Description
11/24
2.2 Assessment methods and criteria for the performance of the product in relation to
essential characteristics of the product
2.2.1
Shape
Exemplary drawings and figures of the shape shall be stated in the ETA.
2.2.1.2
2.2.1.3
Reaction to fire
The precast concrete composite wall with point connectors is considered to satisfy the requirements for
performance class A1 of the characteristic reaction to fire in accordance with the EC Decision 96/603/EC3,
as amended, without the need for testing on the basis of it fulfilling the conditions set out in that Decision
and its intended use being covered by that Decision.
Therefore the performance of the product is A1.
2.2.1.5
Resistance to fire
For the verification of the resistance to fire of the precast concrete composite wall with point connectors
one of the methods described in EN 13369, Clause 4.3.4.2 can be chosen.
Depending on the chosen method of verification, the product shall be classified according to EN 13501-2
or EN 1992-1-2.
2.2.1.6
Where
n
Official
EOTA 2015
number of connectors
12/24
Depending on the filling pressure the number of connectors per m 2 shall be determined.
The minimum tensile bending resistance of the precast reinforced layers of concrete shall be calculated
for the maximum centre spacing between the connectors according to EN 15498, Annex C, Clause C.4.2,
where the maximum filling pressure shall be taken from EN 14992, Annex B, figure B.1.
The characteristic value of the minimum tensile bending resistance of the reinforced layers of concrete
shall be less than the mean centric tensile strength of the used concrete strength class. Tabulated values
for the concrete strength classes and the corresponding mean centric tensile strength shall be taken from
EN 1992-1-1, Table 3.1.
The precast reinforced layers of concrete shall resist to a formwork pressure of a defined rate of concreting
and the class of consistency of concrete as defined in EN 14992, Annex B, figure B.1. The maximum
centre spacing between the connectors has to be observed.
If the minimum tensile bending resistance of the precast reinforced layers of concrete is greater than the
mean centric tensile strength of the used concrete additionally reinforcement with verification according
to EN 1992-1-1 is necessary.
2.2.1.8
2.2.1.9
EOTA 2015
13/24
Thermal conductivity
The design thermal conductivity of the materials shall be obtained from tabulated values in EN ISO 10456.
The characteristic value shall be stated in the ETA.
2.2.1.12
Thermal resistance
The thermal resistance and thermal transmittance of concrete products may be calculated in accordance
with EN ISO 6946 or measured in a hot box in accordance with EN ISO 8990 or EN 1934.
The characteristic value shall be stated in the ETA.
2.2.1.13
EOTA 2015
2.2.2
Connector
14/24
Shape
Exemplary drawings and figures of the shape shall be stated in the ETA.
2.2.2.2
Dimensions
The relevant dimensions of the connector shall be determined.
The dimensions shall conform to the connector's specification.
2.2.2.3
Material
Material characteristics of the components of the connector shall be determined according to the
respective reference standards. For the stainless steel wires EN 10088-1 and EN 1993-1-4 applies. The
steel sheet shall be determined according to EN 10130.
Acceptance criteria shall conform to the respective reference standard of the component's material. The
components shall be accompanied by an inspection certificate 3.1.
Results of tensile tests to compare with the figures of the inspection certificate 3.1 are to be provided.
2.2.2.4
Steel failure due to tensile loading and combined pull-out and concrete cone failure
Due to corrugation and notches of the steel wires the characteristic resistance in case of steel failure,
NRk,s, cannot be calculated according to EOTA TR 029, Clause 5.2.2.2 but shall be assessed during
testing of combined pull-out and concrete cone failure.
The occurrence of steel failure due to tensile loading or combined pull-out and concrete cone failure
depends on the embedment depth of the steel wires and concrete strength class. The embedment depth
is equal to the thickness of the concrete layers.
Testing shall be carried out on concrete layers of different thickness. The minimum layer thickness where
combined pull-out and concrete cone failure does not occur anymore but steel failure shall be assessed
as well as the characteristic values of both failure modes.
The compressive strength of the precast reinforced layers of concrete shall be verified according to EN
12390-1, EN 12390-2 and EN 12390-3.
5 pull-out failure tests for one thickness of precast reinforced layer of concrete shall be summarized in
one test series. The mean value of steel failure at maximum load as well as for combined pull-out and
concrete cone failure shall be calculated. The 5 %-fractile value at a confidence level of 90 % shall be
determined. The 5 %-fractile value shall then be converted to a concrete compressive strength of 25
N/mm2 (cube compressive strength of C20/25):
Where
5 %-fractile value converted to C20/25
Concrete compressive strength at the day of testing
. 5 %-fractile value of the values of steel failure at maximum load
The characteristic resistance in case of combined pull-out and concrete cone failure at the corresponding
embedment depth shall be stated in the ETA.
The characteristic value of steel failure due to tensile loading shall be stated in the ETA.
EOTA 2015
2.2.2.5
15/24
2.2.2.6
Splitting failure
According to EOTA TR 029, Clause 5.2.2.6, the calculation of the characteristic splitting resistance may
be omitted if the following two conditions are fulfilled:
-
A reinforcement is present which limits the crack width to wk ~ 0.3 mm, taking into account the
splitting forces according to EOTA TR 029, Clause 7.3.
The characteristic resistance for concrete cone failure and pull-out failure is assessed for
cracked concrete.
In all other cases a minimum reinforcement is required to avoid splitting of the member. The splitting
reinforcement shall be calculated for 50 % of the tensile force of the steel wires. The necessary crosssection of the minimum reinforcement in mm 2 is determined as follows:
Where
sum of the tensile forces of the anchor bolts under tension under the design value of the
actions [N]
characteristic value of the yield point of the reinforcing steel [N/mm 2]
partial safety factor for the reinforcement according to national rules; in the absence of such
rules, the partial safety factor can be taken with 1.15 from EN 1992-1-1.
In all other cases the characteristic minimum reinforcement to avoid splitting of the layers shall be stated
in the ETA.
2.2.2.7
2.2.2.8
2.2.2.9
2.2.2.10
Edge distance
The minimum edge distance shall be determined by calculation of the failure modes, see Clause 2.2.2.5,
2.2.2.8 and 2.2.2.9.
The minimum edge distance of the connector at the corresponding embedment depth of the steel wires
shall be stated in the ETA.
EOTA 2015
2.2.2.11
16/24
Centre spacing
The centre spacing between the steel wires is defined by the shape of the connector, see Clause 2.2.2.1.
The maximum centre spacing between the connectors shall be determined by calculation of the resistance
to filling pressure, see Clause 2.2.1.7.
The centre spacing between the steel wires shall be given in the ETA.
The centre spacing between the connectors shall be in accordance with Clause 2.2.1.7.
2.2.2.12
Corrosion protection
The stainless steel wires shall meet the requirements given in EN 1993-1-4 and EN 10088-1.
Reaction to fire
The connector is considered to satisfy the requirements for performance class A1 of the characteristic
reaction to fire in accordance with the EC Decision 1996/603/EC4, as amended, without the need for
testing on the basis of it fulfilling the conditions set out in that Decision and its intended use being covered
by that Decision.
Therefore the performance of the product is A1.
EOTA 2015
2.2.3
17/24
2.2.3.1.1
2.2.3.1.2
Strength properties
The tensile test shall be carried out in accordance with EN ISO 15630-1, Clause 5. Tensile strength, Rm,
yield strength, Re, ratio tensile strength to yield strength,
, and total elongation at maximum load,
Agt, shall be determined according to EN 10080, Clause 7.2.3.
Acceptance criteria regarding the strength properties shall be in accordance with EN 10080,
Clause 8.1.3.1. In the product specification, the lower limit of the statistical tolerance interval applies in
regard to
-
Type B5
Type C2
Where
Characteristic value of the ratio tensile strength to yield strength
NOTE
2.2.3.1.3
Bendability
According to EN 10080, Clause 7.2.6 the bent and re-bend test shall be performed according to
EN 15630-1.
Acceptance criteria are defined in EN 10080, Clauses 7.2.6.2 and 7.2.6.3.
2.2.3.1.4
2.2.3.1.5
Rib spacing
Assessment according to EN ISO 15630-1, Clause 10.
The characteristic value for rib spacing shall be within the ranges given in EN 10080, Table 7.
EOTA 2015
2.2.3.1.6
18/24
Rib inclination
Assessment according to EN ISO 15630-1, Clause 10.
The characteristic value for rib inclination shall be within the ranges given in EN 10080, Table 7.
2.2.3.1.7
Rib height
Assessment according to EN ISO 15630-1, Clause 10.
The characteristic value for rib height shall be within the ranges given in EN 10080, Table 7.
2.2.3.1.8
2.2.3.2
2.2.3.2.1
2.2.3.2.2
2.2.3.2.3
2.2.3.2.4
Strength properties
See Clause 2.2.3.1.2.
2.2.3.2.5
Bendability
Assessment and declaration according to EN ISO 15630-2, Clause 6.
2.2.3.2.6
2.2.3.2.7
Rib spacing
See Clause 2.2.3.1.5.
2.2.3.2.8
Rib inclination
See Clause 2.2.3.1.6.
2.2.3.2.9
Rib height
See Clause 2.2.3.1.7.
2.2.3.2.10
EOTA 2015
2.2.3.3
19/24
Concrete layers
2.2.3.3.1
2.2.3.3.2
Shape
Exemplary drawings and figures of the shape shall be stated in the ETA.
2.2.3.3.3
2.2.3.3.4
2.2.3.3.5
Chloride content
Assessment according to EN 206-1, Clause 5.2.7.
Depending on the usage of the concrete requirements of EN 206-1, Table 10 shall be fulfilled.
2.2.3.3.6
Alkali content
According to EN 206-1, Clause 5.2.2, the potential reactivity of the aggregates with the alkalis of the raw
material shall be taken under consideration when selecting the appropriate cement.
To prevent damaging alkali-silica reactions precautions with proven suitability shall be taken.
2.2.3.3.7
2.2.3.3.8
2.2.3.3.9
2.2.3.3.10
Air content
Assessment according to EN 12350-7.
The characteristic minimum value of the air content shall be stated in the ETA.
2.2.3.3.11
2.2.3.3.12
EOTA 2015
2.2.3.3.13
20/24
2.2.3.3.14
Water absorption
Assessment according to the test method given in EN 13369, Annex G.
The characteristic value shall be stated in the ETA.
2.2.3.3.15
Compressive strength
The concrete strength shall be verified according to EN 12390-1, EN 12390-2 and EN 12390-3.
Declaration according to EN 206-1, Table 7.
2.2.3.3.16
Reinforcement detailing
Requirements of EN 14992 shall be fulfilled.
Requirements of TR 029, Clause 5.2.2.4, d) for a shell spalling factor
shall be fulfilled.
Reaction to fire
The precast reinforced layer of concrete are considered to satisfy the requirements for performance class
A1 of the characteristic reaction to fire in accordance with the EC Decision 96/603/EC6, as amended,
without the need for testing on the basis of it fulfilling the conditions set out in that Decision and its intended
use being covered by that Decision.
Therefore the performance of the product is A1.
EOTA 2015
21/24
No
Subject/type of
control
Criteria,
if any
Minimum
number of
samples
Minimum
frequency
of control
Equipment
inspection
Materials
inspection
Inspection certificate
Check if material properties
of the steel components
to EN 10204 (to be
stated in the ETA
furnished by supplier
correspond to the material of components)
properties stated in the
100% compliance to
material properties
stated in ETA
Process
inspection
EOTA 2015
Every
production
unit
Per batch
Every
component
No
Subject/type of
control
Finished product
inspection
22/24
Criteria,
if any
Minimum
number of
samples
Minimum
frequency
of control
No
Subject/type of
control
Test or control
method
Criteria,
if any
Minimum number
of samples
Minimum
frequency of
control
It shall be ascertained that, in accordance with the test plan, the manufacturing
plant of the single product manufacturer, in particular personnel and equipment,
and the factory production control are suitable to ensure a continuous and orderly
manufacturing of the precast concrete composite wall with point connectors
according the European Technical Assessment.
EOTA 2015
It shall be verified that the system of factory production control and the specified
manufacturing process are maintained taking account of the test plan.
1/year
23/24
REFERENCE DOCUMENTS
As far as no edition date is given in the list of standards thereafter, the standard in its current version at the time
of issuing the European Technical Assessment, is of relevance.
EN 1992-1-1 (12.2004)
EN 1992-1-1/AC (01.2008)
EN 1992-1-1/AC (11.2010)
Eurocode 2: Design of concrete structures - Part 1-1: General rules and rules
for buildings
EN 1992-1-2 (12.2004)
EN 1992-1-2/AC (07.2008)
Eurocode 2: Design of concrete structures - Part 1-2: General rules Structural fire design
EN 1993-1-4 (10.2006)
Eurocode 3 - Design of steel structures - Part 1-4: General rules Supplementary rules for stainless steels
EN 206-1+A1 (07.2004)
+A2 (06.2005)
EN 1934 (03.1998)
EN 10080 (05.2005)
EN 10088-1 (06.2005)
EN 10130 (12.2006)
Cold rolled low carbon steel flat products for cold forming Technical delivery conditions
EN 10204 (10.2004)
EN 12350-7 (04.2009)
EN 12354-1 (04.2000)
EN 12390-1 (09.2012)
EN 12390-2 (04.2009)
EN 12390-3 (02.2009)
EN 12390-3 /AC (08.2011)
EN 13369 (04.2013)
EN 13501-2+A1 (09.2009)
EN 14992+A1 (06.2012)
EN 15498 (04.2008)
EOTA 2015
24/24
Steel for the reinforcement and prestressing of concrete - test methods - Part
1: Reinforcing bars, wire rod and wire
Steel for the reinforcement and prestressing of concrete - Test methods Part 2: Welded fabric
EOTA TR 029
EOTA 2015