Sales Program
Gendrive
Diesel Engines
Edition 1/15
valid from 01/2015
04
06
12
General specications
13
Engine designation
14
New products
22
28
30
32
34
36
42
44
46
Gendrive engines - 50 Hz
3D - Diesel engines for standby power
3E - Diesel engines for standby power with overload
3F - Diesel engines for data center continuous power
3H - Diesel engines for mission critical power
3C - Diesel engines for NPP standby power
3B - Diesel engines for prime power
3G - Diesel engines for grid stability power
3C - Diesel engines for prime power limited
3A - Diesel engines for continuous power
48
52
54
56
58
62
64
Gendrive engines - 60 Hz
3D - Diesel engines for standby power
3F - Diesel engines for data center continuous power
3H - Diesel engines for mission critical power
3C - Diesel engines for NPP standby power
3B - Diesel engines for prime power
3G - Diesel engines for grid stability power
3A - Diesel engines for continuous power
66
68
70
72
82
83
94
Exhaust emissions
Stationary Power Plants
Nonroad Mobile Machinery
General
Contents
General
A customer-oriented
technology leader.
MTU supplies its customers with technologicallyadvanced products that are proven in the eld.
MTUs range of products and services for
off-highway applications is extensive and includes
both standard and customized solutions.
General
MTU Gendrive
rating denition
General
MTU Gendrive
rating denition
General
MTU Gendrive
rating denition
Overview of values
Load
Load factor
10 % overload (ICXN)
Max. operating hours
(per year)
Rating denition
Load
Load factor
10 % overload (ICXN)
Max. operating hours
(per year)
Rating denition
Standby Power
(3D)
variable
85 %
no
Standby Power
with Overload (3E)
variable
85 %
yes
Data Center
Continuous Power (3F)
constant & variable
100 %
yes
Mission Critical
Power (3H)
variable
85 %
50 HZ: yes / 60 Hz: no
500 h 1)
DIN ISO 3046 - IFN
500 h 1)
DIN ISO 3046 - ICXN
unlimited 2)
DIN ISO 3046 ICXN
1000 h 1)
unlimited 3)
50 Hz: ISO 3046 - ICXN DIN ISO 3046 ICXN
60 Hz: ISO 3046 - IFN
Prime Power
(3B)
variable
75 %
yes
Grid Stability
Power (3G)
constant & variable
100 %
yes
Prime Power
Limited (3C)
variable
75 %
yes
Continuous
Power (3A)
constant & variable
100 %
yes
unlimited
DIN ISO 3046 - ICXN
1000 h 4)
DIN ISO 3046 ICXN
1000 h
DIN ISO 3046 - ICXN
unlimited
DIN ISO 3046 ICXN
NPP Standby
Power (3C)
variable
acc. to KTA&IEEE regul.
yes
Explanation of
the engine designation
Series 956
Example:
20 V 956 TB 34
Design index
Application segment
Power Denition
Turbocharged/Charge-air cooling
Series
Cylinder-conguration: V = V-engine
No. of cylinders
12 V 4000 G 63 L
Series
Cooling variants
Water-to-air charge air cooling (W2A)
Air-to-air charge air cooling (A2A)
1600/2000/4000/956
2000/4000/956
1600/2000
For more information about MTU gendrive diesel engines please visit:
www.mtu-online.com
Sales Program 2015 I Gendrive I 13
General
General
specications
New Proucts
General
New products
Frequency:
Cylinder version:
Application groups:
Frequency:
Cylinder version:
Application groups:
Frequency:
Cylinder version:
Power range:
Application groups:
Emissions:
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
14 I Gendrive I Sales Program 2015
New Proucts
General
New products
Frequency:
Cylinder version:
Power range:
Application groups:
Emissions:
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
16 I Gendrive I Sales Program 2015
Frequency:
Cylinder version:
Power range:
Application groups:
Emissions:
Frequency:
Cylinder version:
Power range:
Application groups:
Emissions:
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
18 I Gendrive I Sales Program 2015
General
New products
Frequency:
Cylinder version:
Power range:
Application groups:
Emissions:
General
New products
Frequency:
Cylinder Version:
Power range:
Application groups:
Emissions:
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
20 I Gendrive I Sales Program 2015
Gendrive engines
Standby Power (3D)
367
404
480
528
601
661
772
850
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
Standby Power - 50 Hz
x
x
x
x
x
Engine model
274
301
358
394
448
493
576
634
240
264
320
352
400
440
520
572
24
Engine
Cooling variant
300
330
400
440
500
550
650
715
25
bhp
22
kWm
19
Cooling
kWe
kVA
EU Nonroad
Stage IIIA
Emissions Standard
Rating
Typical
Generator Set
output (1)
50 Hz 1500 rpm
274 kWm - 634 kWm
A2A
A2A
A2A
A2A
A2A
A2A
A2A
A2A
x
x
x
x
x
x
x
x
6R 1600 G70F
6R 1600 G80F
8V 1600 G70F
8V 1600 G80F
10V 1600 G70F
10V 1600 G80F
12V 1600 G70F
12V 1600 G80F
1
8 19 24 22 25
reference to emission level in price list
(2) Explanation see page 82
Gendrive engines
Standby Power (3D)
852
852
982
1026
1026
1189
1194
1194
1307
1307
1313
1475
1475
1475
1656
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
A2A
W2A
A2A
A2A
W2A
A2A
A2A
W2A
A2A
W2A
A2A
A2A
A2A
W2A
A2A
x
x
x
x
x
x
x
x
x
x
Standby Power - 50 Hz
Engine
Engine model
635
635
732
765
765
887
890
890
975
975
979
1100
1100
1100
1235
25
572
572
660
688
688
800
800
800
880
880
888
1000
1000
1000
1120
22
Cooling variant
715
715
825
860
860
1000
1000
1000
1100
1100
1110
1250
1250
1250
1400
24
bhp
19
kWm
kWe
kVA
Cooling
EU Nonroad
Stage IIIA
Emissions Standard
Rating
Typical
Generator Set
output (1)
50 Hz 1500 rpm
635 kWm - 1235 kWm
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
1
8 19 24 22 25
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
Gendrive engines
Standby Power (3D)
2112
2347
2635
2930
3245
3581
3822
x
x
x
x
x
x
x
x
x
x
x
x
x
x
W2A
W2A
W2A
W2A
W2A
W2A
W2A
Standby Power - 50 Hz
Engine
Engine model
1575
1750
1965
2185
2420
2670
2850
1440
1600
1800
2000
2240
2480
2640
25
Cooling variant
1800
2000
2250
2500
2800
3100
3300
22
bhp
24
kWm
19
Cooling
kWe
kVA
EU Nonroad
Stage IIIA
Emissions Standard
Rating
Typical
Generator Set
output (1)
50 Hz 1500 rpm
1575 kWm - 2850 kWm
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
1
8 19 24 22 25
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
Gendrive engines
Standby Power
with Overload (3E)
1600
1800
2100
2250
2500
2800
3000
1280
1440
1680
1800
2000
2240
2400
1420
1575
1798
1965
2200
2420
2590
1904
2112
2411
2635
2950
3245
3473
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
W2A
W2A
W2A
W2A
W2A
W2A
W2A
bhp
Engine
Engine model
kWm
25
kWe
22
Cooling variant
kVA
24
19
Cooling
EU Nonroad
Stage IIIA
Emissions Standard
Rating
Typical
Generator Set
output (1)
50 Hz 1500 rpm
1420 kWm - 2590 kWm
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
1
8 19 24 22 25
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
Gendrive engines
Data Center
Continuous Power (3F)
1600
1800
2100
2250
2500
2800
3000
1280
1440
1680
1800
2000
2240
2400
1420
1575
1798
1965
2200
2420
2590
1904
2112
2411
2635
2950
3245
3473
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
W2A
W2A
W2A
W2A
W2A
W2A
W2A
bhp
Engine
Engine model
kWm
25
kWe
22
Cooling variant
kVA
24
19
Cooling
EU Nonroad
Stage IIIA
Emissions Standard
Rating
Typical
Generator Set
output (1)
50 Hz 1500 rpm
1420 kWm - 2590 kWm
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
1
8 19 24 22 25
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
Gendrive engines
Mission Critical Power (3H)
1600
1800
2100
2250
2500
2800
3000
1280
1440
1680
1800
2000
2240
2400
1420
1575
1798
1965
2200
2420
2590
1904
2112
2411
2635
2950
3245
3473
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
W2A
W2A
W2A
W2A
W2A
W2A
W2A
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
1
8 19 24 22 25
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
bhp
Engine
Engine model
kWm
25
kWe
22
Cooling variant
kVA
24
19
Cooling
EU Nonroad
Stage IIIA
Emissions Standard
Rating
Typical
Generator Set
output (1)
50 Hz 1500 rpm
1420 kWm - 2590 kWm
Gendrive engines
NPP Standby Power (3C)
x
x
x
x
x
x
W2A
W2A
W2A
W2A
W2A
W2A
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
1
8 19 24 22 25
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
2092
2789
3487
5230
6973
8717
Engine
Engine model
1560
2080
2600
3900
5200
6500
25
1440
1920
2400
3520
4656
5820
22
Cooling variant
1800
2400
3000
4400
5820
7275
24
bhp
19
kWm
kWe
kVA
Cooling
EU Nonroad
Stage IIIA
Emissions Standard
Rating
Typical
Generator Set
output (1)
50 Hz 1500 rpm
1560 kWm - 6500 kWm
Gendrive engines
Prime Power (3B)
275
300
365
400
450
500
590
650
220
240
292
320
360
400
472
520
249
274
325
358
407
448
524
576
334
367
436
480
546
601
703
772
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
A2A
A2A
A2A
A2A
A2A
A2A
A2A
A2A
x
x
x
x
x
x
x
x
6R 1600 G10F
6R 1600 G20F
8V 1600 G10F
8V 1600 G20F
10V 1600 G10F
10V 1600 G20F
12V 1600 G10F
12V 1600 G20F
Prime Power - 50 Hz
bhp
Engine model
kWm
25
kWe
24
Engine
Cooling variant
kVA
22
19
Cooling
EU Nonroad
Stage IIIA
Emissions Standard
Rating
Typical
Generator Set
output (1)
50 Hz 1500 rpm
249 kWm - 576 kWm
1
8 19 24 22 25
reference to emission level in price list
(2) Explanation see page 82
Gendrive engines
Prime Power (3B)
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
A2A
W2A
A2A
W2A
A2A
W2A
A2A
W2A
A2A
A2A
W2A
A2A
A2A
W2A
A2A
A2A
W2A
A2A
x
x
x
x
x
x
x
x
x
x
x
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
1
8 19 24 22 25
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
Prime Power - 50 Hz
778
778
892
892
932
932
951
951
1081
1086
1086
1194
1194
1194
1341
1341
1341
1478
Engine
Engine model
580
580
665
665
695
695
709
709
806
810
810
890
890
890
1000
1000
1000
1102
25
520
520
600
600
624
624
640
640
728
728
728
800
800
800
908
908
908
1000
22
Cooling variant
650
650
750
750
780
780
800
800
910
910
910
1000
1000
1000
1135
1135
1135
1250
24
bhp
19
kWm
kWe
kVA
Cooling
EU Nonroad
Stage IIIA
Emissions Standard
Rating
Typical
Generator Set
output (1)
50 Hz 1500 rpm
580 kWm - 1102 kWm
Gendrive engines
Prime Power (3B)
1365
1600
1800
2100
2250
2500
2800
3000
1092
1280
1440
1680
1800
2000
2240
2400
1205
1420
1575
1798
1965
2200
2420
2590
1616
1904
2112
2411
2635
2950
3245
3473
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
W2A
W2A
W2A
W2A
W2A
W2A
W2A
W2A
Prime Power - 50 Hz
bhp
Engine
Engine model
kWm
25
kWe
22
Cooling variant
kVA
24
19
Cooling
EU Nonroad
Stage IIIA
Emissions Standard
Rating
Typical
Generator Set
output (1)
50 Hz 1500 rpm
1205 kWm - 2590 kWm
1
8 19 24 22 25
reference to emission level in price list
(2) Explanation see page 82
(3) Series 20V 4000 G63 without power
reduction available up to 35C / 400 m
(4) Series 12V 4000 G63 / 20V 4000 G63L
without power reduction available up to
30C / 400 m
Gendrive engines
Grid Stability Power (3G)
1600
1800
2100
2250
2500
2800
3000
1280
1440
1680
1800
2000
2240
2400
1420
1575
1798
1965
2200
2420
2590
1904
2112
2411
2635
2950
3245
3473
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
W2A
W2A
W2A
W2A
W2A
W2A
W2A
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
1
8 19 24 22 25
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
bhp
Engine
Engine model
kWm
25
kWe
22
Cooling variant
kVA
24
19
Cooling
EU Nonroad
Stage IIIA
Emissions Standard
Rating
Typical
Generator Set
output (1)
50 Hz 1500 rpm
1420 kWm - 2590 kWm
Gendrive engines
Prime Power Limited (3C)
22
25
kVA
kWe
kWm
bhp
275
300
365
400
450
500
590
650
220
240
292
320
360
400
472
520
249
274
325
358
407
448
524
576
334
367
436
480
546
601
703
772
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
A2A
A2A
A2A
A2A
A2A
A2A
A2A
A2A
x
x
x
x
x
x
x
x
6R 1600 G40F
6R 1600 G50F
8V 1600 G40F
8V 1600 G50F
10V 1600 G40F
10V 1600 G50F
12V 1600 G40F
12V 1600 G50F
24
Engine model
19
Engine
Cooling variant
Cooling
EU Nonroad
Stage IIIA
Emissions Standard
Rating
Typical
Generator Set
output (1)
50 Hz 1500 rpm
249 kWm - 576 kWm
1
8 19 24 22 25
reference to emission level in price list
(2) Explanation see page 82
Gendrive engines
Continuous Power (3A)
x
x
x
x
x
x
x
x
x
x
x
x
x
A2A
W2A
A2A
W2A
A2A
A2A
A2A
W2A
A2A
W2A
W2A
W2A
W2A
x
x
x
x
x
x
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
1
8 19 24 22 25
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
Continuous Power - 50 Hz
691
691
878
878
892
951
966
966
1189
1757
2193
2682
2950
Engine
Engine model
515
515
655
655
665
709
720
720
887
1310
1635
2000
2200
25
460
460
592
592
600
640
648
648
800
1184
1500
1820
2000
22
Cooling variant
575
575
740
740
750
800
810
810
1000
1480
1875
2275
2500
24
bhp
19
kWm
kWe
kVA
Cooling
EU Nonroad
Stage IIIA
Emissions Standard
Rating
Typical
Generator Set
output (1)
50 Hz 1500 rpm
515 kWm - 2200 kWm
Cooling
275
300
365
400
450
500
550
600
710
710
800
800
925
925
1000
1000
1200
1200
1250
344
375
456
500
563
625
688
750
888
888
1000
1000
1156
1156
1250
1250
1500
1500
1563
312
343
408
448
511
561
613
668
780
780
890
890
1010
1010
1115
1115
1310
1310
1371
418
460
547
601
685
752
822
896
1046
1046
1194
1194
1354
1354
1495
1495
1757
1757
1839
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
A2A
A2A
A2A
A2A
A2A
A2A
A2A
A2A
A2A
W2A
A2A
W2A
A2A
W2A
A2A
W2A
A2A
W2A
A2A
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Engine
Engine model
bhp
kWm
20
kVA
kWe
19
Emissions Standard
Rating
Standby Power - 60 Hz
Typical
Generator Set
output (1)
60 Hz 1800 rpm
312 kWm - 1371 kWm
Cooling variant
Gendrive engines
Standby Power (3D)
6R 1600 G70S
6R 1600 G80S
8V 1600 G70S
8V 1600 G80S
10V 1600 G70S
10V 1600 G80S
12V 1600 G70S
12V 1600 G80S
12V 2000 G45
12V 2000 G45
12V 2000 G85
12V 2000 G85
16V 2000 G45
16V 2000 G45
16V 2000 G85
16V 2000 G85
18V 2000 G85
18V 2000 G85
18V 2000 G76S
19 3 20 7
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
48 I Gendrive I Sales Program 2015
Cooling
kWe
kVA
kWm
bhp
1600
1750
2100
2300
2550
2550
2800
3250
2000
2188
2625
2875
3188
3188
3500
4063
1736
1910
2280
2500
2740
2740
3010
3490
2328
2561
3058
3353
3674
3674
4036
4680
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
W2A
W2A
W2A
W2A
W2A
W2A
W2A
W2A
Engine
Engine model
20
19
Emissions Standard
Rating
Standby Power - 60 Hz
Typical
Generator Set
output (1)
60 Hz 1800 rpm
1736 kWm - 3490 kWm
Cooling variant
Gendrive engines
Standby Power (3D)
19 3 20 7
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
Typical
Generator Set
output (1)
Cooling
kVA
kWm
bhp
1400
1600
1850
2100
2300
2550
2800
1750
2000
2313
2625
2875
3188
3500
1520
1736
2020
2280
2490
2740
3010
2038
2328
2709
3058
3339
3674
4036
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
W2A
W2A
W2A
W2A
W2A
W2A
W2A
kWe
Engine
Engine model
20
19
Emissions Standard
Rating
60 Hz 1800 rpm
1520 kWm - 3010 kWm
Cooling variant
Gendrive engines
Data Center
Continuous Power (3F)
19 3 20 7
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
Typical
Generator Set
output (1)
Cooling
kVA
kWm
bhp
1600
1750
2100
2300
2550
2550
2800
3250
2000
2188
2625
2875
3188
3188
3500
4063
1736
1910
2280
2500
2740
2740
3010
3490
2328
2561
3058
3353
3674
3674
4036
4680
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
W2A
W2A
W2A
W2A
W2A
W2A
W2A
W2A
kWe
Engine
Engine model
20
19
Emissions Standard
Rating
60 Hz 1800 rpm
1736 kWm - 3490 kWm
Cooling variant
Gendrive engines
Mission Critical Power (3H)
19 3 20 7
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
Typical
Generator Set
output (1)
Cooling
1925
2575
3250
1680
2240
2800
2253
3004
3755
x
x
x
W2A
W2A
W2A
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
19 3 20 7
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical
generator efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
1540
2060
2600
Engine
Engine model
bhp
kWm
20
kVA
kWe
19
Emissions Standard
Rating
60 Hz 1800 rpm
1680 kWm 2800 kWm
Cooling variant
Gendrive engines
NPP Standby Power (3C)
Typical
Generator Set
output (1)
Cooling
313
344
413
456
519
563
625
688
800
800
919
919
1038
1038
1156
1156
1375
1375
284
312
371
408
465
511
561
608
710
710
810
810
915
915
1010
1010
1191
1191
381
418
498
547
624
685
752
815
952
952
1086
1086
1227
1227
1354
1354
1597
1597
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
A2A
A2A
A2A
A2A
A2A
A2A
A2A
A2A
A2A
W2A
A2A
W2A
A2A
W2A
A2A
W2A
A2A
W2A
x
x
x
x
x
x
x
x
x
x
x
x
x
Prime Power - 60 Hz
250
275
330
365
415
450
500
550
640
640
735
735
830
830
925
925
1100
1100
Engine
Engine model
bhp
kWm
20
kVA
kWe
19
Emissions Standard
Rating
60 Hz 1800 rpm
284 kWm - 1191 kWm
Cooling variant
Gendrive engines
Prime Power (3B)
6R 1600 G10S
6R 1600 G20S
8V 1600 G10S
8V 1600 G20S
10V 1600 G10S
10V 1600 G20S
12V 1600 G10S
12V 1600 G20S
12V 2000 G45
12V 2000 G45
12V 2000 G85 (2)
12V 2000 G85 (2)
16V 2000 G45
16V 2000 G45
16V 2000 G85
16V 2000 G85
18V 2000 G85
18V 2000 G85
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
19 3 20 7
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
Typical
Generator Set
output (1)
Cooling
1250
1575
1750
2000
2313
2625
2875
3188
3500
1105
1390
1520
1736
2020
2280
2490
2740
3010
1482
1864
2038
2328
2709
3058
3339
3674
4036
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
W2A
W2A
W2A
W2A
W2A
W2A
W2A
W2A
W2A
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
19 3 20 7
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
Prime Power - 60 Hz
1000
1260
1400
1600
1850
2100
2300
2550
2800
Engine
Engine model
bhp
kWm
20
kVA
kWe
19
Emissions Standard
Rating
60 Hz 1800 rpm
1105 kWm - 3010 kWm
Cooling variant
Gendrive engines
Prime Power (3B)
Typical
Generator Set
output (1)
Cooling
kVA
kWm
bhp
1400
1600
1850
2100
2300
2550
2800
1750
2000
2313
2625
2875
3188
3500
1520
1736
2020
2280
2490
2740
3010
2038
2328
2709
3058
3339
3674
4036
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
W2A
W2A
W2A
W2A
W2A
W2A
W2A
kWe
Engine
Engine model
20
19
Emissions Standard
Rating
60 Hz 1800 rpm
1520 kWm - 3010 kWm
Cooling variant
Gendrive engines
Grid Stability Power (3G)
19 3 20 7
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
Typical
Generator Set
output (1)
Cooling
656
656
688
688
769
769
894
894
988
1019
1019
1300
1375
1625
1875
2219
2563
2875
580
580
620
620
685
685
790
790
870
900
900
1140
1190
1420
1680
1950
2230
2490
778
778
831
831
919
919
1059
1059
1167
1207
1207
1529
1596
1904
2253
2615
2990
3339
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
A2A
W2A
A2A
W2A
A2A
W2A
A2A
W2A
W2A
A2A
W2A
W2A
W2A
W2A
W2A
W2A
W2A
W2A
x
x
x
x
x
x
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
19 3 20 7
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
Continuous Power - 60 Hz
525
525
550
550
615
615
715
715
790
815
815
1040
1100
1300
1500
1775
2050
2300
Engine
Engine model
bhp
kWm
20
kVA
kWe
19
Emissions Standard
Rating
60 Hz 1800 rpm
580 kWm - 2490 kWm
Cooling variant
Gendrive engines
Continuous Power (3A)
Rating
Emissions Standard
50 Hz
50 Hz
2000
2188
2625
2875
2112
2347
2635
2930
1736
1910
2280
2500
2328
2561
3058
3353
W2A
W2A
W2A
W2A
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
1 19 3 20 7 24
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical
generator efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
Cooling variant
24
x
x
x
x
1600
1750
2100
2300
1575
1750
1965
2185
1440
1600
1800
2000
20
1800
2000
2250
2500
19
kVA
kWe kWe kVA
50 Hz 50 Hz 60 Hz 60 Hz
60 Hz
60 Hz
Cooling
Engine
Engine model
Rating
Emissions Standard
50 Hz
50 Hz
20
24
kVA
kWe kWe kVA
50 Hz 50 Hz 60 Hz 60 Hz
275
300
365
400
450
500
590
800
1000
1250
1600
1600
1800
2100
2100
2250
2250
249
274
325
358
448
524
576
709
890
1102
1420
1420
1575
1798
1798
1965
1965
x
x
x
x
x
x
x
x (3) x (4)
x (3) x (4)
x (3) x (4)
x
x
x (3), (5) x (4), (5)
x (5) x (4), (5)
x
x (3), (5) x (4), (5)
x
x (3), (5) x (4), (5)
220
240
292
320
360
400
472
640
800
1000
1280
1280
1440
1680
1680
1800
1800
250
275
330
365
415
450
500
650
910
1000
1400
1400
1600
1850
1850
2100
2100
313
344
413
456
519
563
625
813
1138
1250
1750
1750
2000
2313
2313
2625
2625
334
367
436
480
601
703
772
951
1194
1478
1904
1904
2112
2411
2411
2635
2635
284
312
371
408
511
561
608
716
998
1097
1520
1520
1736
2020
2020
2280
2280
381
418
498
547
685
752
815
960
1338
1471
2038
2038
2328
2709
2709
3058
3058
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
(1) The quoted typical kVA / kWe ratings are based on typical generator
efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
68 I Gendrive I Sales Program 2015
A2A
A2A
A2A
A2A
A2A
A2A
A2A
A2A
A2A
A2A
W2A
W2A
W2A
W2A
W2A
W2A
W2A
x (4)
x (4)
x (4)
19
Cooling variant
60 Hz
60 Hz
Cooling
x
x
x
x
x
x
x
x
x
x
Engine
6R 1600 B30S
6R 1600 B40S
8V 1600 B30S
8V 1600 B40S
10V 1600 B40S
12V 1600 B30S
12V 1600 B40S
12V 2000 B76
16V 2000 B76
18V 2000 B76
12V 4000 G23/G43
12V 4000 G23/G43
12V 4000 G63/G83
16V 4000 G23/G43
16V 4000 G23/G43
16V 4000 G63/G83
16V 4000 G63/G83
1 19 3 20 7 24
reference to emission level in price list
(2)
(3)
(4)
(5)
50 / 60 Hz 1500/1800 rpm
249 kWm 2280 kWm
Engine model
1420
1950
1904
2615
24
W2A
W2A
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
1 19 3 20 7 24
reference to emission level in price list
(1) The quoted typical kVA / kWe ratings are based on typical
generator efciencies.
The kVA gures are calculated with a 0.8 power factor.
Typical deductions for fan drive power and generator efciency is applied
for calculation and serves as guideline only.
1757
2193
Engine
Engine model
x
x
1625
2219
20
1310
1635
1188 1300
1492 1775
Cooling variant
1485
1865
19
kVA
kWe kWe kVA
50 Hz 50 Hz 60 Hz 60 Hz
60 Hz
50 Hz
60 Hz
Cooling
50 Hz
Emissions Standard
Rating
Engine
Cylinder data
Bore/Stroke
Cyl. displac. Total displac.
mm (in)
l (cu in)
l (cu in)
Series 1600 Gx0 (50/60 Hz) fuel consumption optimized,
exhaust emission optimized (TA-Luft), India CPCB (ARAI) Stage I and
Stage II, EU Nonroad Stage IIIA, NEA Singapore for ORDE,
US EPA Nonroad Tier 3 compliant, US EPA Nonroad Tier 3 Stationary,
US EPA Nonroad Tier 2 compliant, US EPA Tier 2 Stationary
6R 1600 Gx0 - A2A
122/150
1.75
10.5
6 Cyl./In-Line
(4.8/5.9)
(107)
(641)
Dimensions, max
LxWxH
mm (in)
Mass, max
(dry)
kg (lbs.)
1272
(2804)
122/150
(4.8/5.9)
1.75
(107)
14.0
(854)
1519
(3349)
122/150
(4.8/5.9)
1.75
(107)
17.5
(1068)
1827
(4028)
122/150
(4.8/5.9)
1.75
(107)
21.0
(1282)
2145
(4729)
Engines
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
Cylinder data
Bore/Stroke
Cyl. displac. Total displac.
mm (in)
l (cu in)
l (cu in)
Series 2000 Gx5 (50 / 60 Hz) - fuel consumption optimized,
exhaust emission optimized (TA-Luft), India CPCB (ARAI) Stage I,
US EPA Nonroad Tier 2 compliant, US EPA Tier 2 Stationary
12V 2000 Gx5 - A2A
130/150
1.99
23.9
12 Cyl./90V
(5.1/5.9)
(121)
(1458)
12V 2000 Gx5 - W2A 130/150
1.99
23.9
12 Cyl./90V
(5.1/5.9)
(121)
(1458)
Dimensions, max(1)
LxWxH
mm (in)
Mass, max(1)
(dry)
kg (lbs.)
2490
(5490)
2570
(5665)
130/150
(5.1/5.9)
130/150
(5.1/5.9)
1.99
(121)
1.99
(121)
31.8
(1947)
31.8
(1947)
3150
(6835)
3180
(7010)
130/150
(5.1/5.9)
130/150
(5.1/5.9)
1.99
(121)
1.99)
(121)
35.8
(2185)
35.8
(2185)
3500
(7715)
3580
(7893)
Engine
(1) Series 2000: Dimensions and masses refer to engines with water-to-air
charge air cooling; Engines with air-to-air charge air-cooling and integrated
40C - radiators and fan = Length + 650 mm (12/16V) + 850 mm (18V)
Engines
Engine
Cylinder data
Bore/Stroke
Cyl. displac. Total displac.
mm (in)
l (cu in)
l (cu in)
Series 2000 Gx6 (50 / 60 Hz) - fuel consumption optimized,
exhaust emission optimized (TA-Luft), NEA Singapore for ORDE,
US EPA Nonroad Tier 2 compliant, US EPA Nonroad Tier 2 Stationary
12V 2000 Gx6 - A2A
135/156
2.23
26.76
12 Cyl./90V
(5.3/6.15)
(136)
(1633)
16V 2000 Gx6 - A2A
135/156
2.23
35.68
16 Cyl./90V
(5.3/6.15)
(136)
(2177)
18V 2000 Gx6 - A2A 135/156
2.23
40.14
18 Cyl./90V
(5.3/6.15)
(136)
(2450)
Dimensions, max
LxWxH
mm (in)
Mass, max
(dry)
kg (lbs.)
2670
(5586)
3125
(6889)
3360
(7408)
2950
(6503)
3350
(7386)
35.68
(2177)
Engines
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
Engine
Cylinder data
Bore/Stroke Cyl. displac.
Total displac.
mm (in)
l (cu in)
l (cu in)
Series 4000 Gx3 (50 / 60 Hz) - fuel consumption optimized,
exhaust emission optimized (TA-Luft), NEA Singapore for ORDE,
US EPA Nonroad Tier 2 compliant, US EPA Nonroad Tier 2 Stationary
12V 4000 Gx3 - W2A 170/210
4.77
57.2
12 Cyl./90 V
(6.7/8.3)
(291)
(3491)
16V 4000 Gx3 - W2A 170/210
4.77
76.3
16 Cyl./90 V
(6.7/8.3)
(291)
(4655)
20V 4000 Gx3 - W2A 170/210
4.77
95.4
20 Cyl./90 V
(6.7/8.3)
(291)
(5822)
Series 4000 Ex3 (50 / 60 Hz) - fuel consumption optimized
12V 4000 Ex3 - W2A 170/210
4.77
57.2
12 Cyl./90 V
(6.7/8.3)
(291)
(3491)
16V 4000 Ex3 - W2A 170/210
4.77
76.3
16 Cyl./90 V
(6.7/8.3)
(291)
(4655)
20V 4000 Ex3 - W2A 170/210
4.77
95.4
20 Cyl./90 V
(6.7/8.3)
(291)
(5822)
Specications are subject to change without notice. All dimensions are
approximate for complete information refer to installation drawing.
For further information consult your MTU distributor/dealer.
78 I Gendrive I Sales Program 2015
Dimensions, max
LxWxH
mm (in)
Mass, max
(dry)
kg (lbs.)
6200
(13670)
7700
(16975)
9640
(21255)
7300
(16100)
8800
(19400)
10750
(23700)
Engines
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
Sales Program 2015 I Gendrive I 79
GRA-0577
Engine
Cylinder data
Bore/Stroke
Cyl. displac.
mm (in)
l (cu in)
Series 956 TB34 (50 Hz) - fuel consumption optimized
12V 956 TB34 - W2A 230/230
9.56
12 Cyl./60 V
(9.1/9.1)
(583)
16V 956 TB34 - W2A 230/230
9.56
16 Cyl./60 V
(9.1/9.1)
(583)
20V 956 TB34 - W2A 230/230
9.56
20 Cyl./60 V
(9.1/9.1)
(583)
Total displac.
l (cu in)
Dimensions, max
LxWxH
mm (in)
Mass, max
(dry)
kg (lbs.)
114.7
(7000)
152.9
(9331)
191.2
(11688)
13850
(30535)
17350
(38250)
20850
(45965)
Engines
Cooling Variants
A2A: air-to-air charge air cooling (TD)
W2A: water-to-air charge air cooling (TB)
Explanation emission
optimization (TA-Luft)
Series 1600
TA-Luft optimized NOx < 1500 mg / m3N
Series 2000
TA-Luft optimized NOx < 1000 mg / m3N
TA-Luft optimized NOx < 1500 mg / m3N
TA-Luft optimized NOx < 2000 mg / m3N / 7% O2
Series 4000
TA-Luft optimized NOx < 1700 mg/m3N
Exhaust emissions
Stationary Power Plants
CO
mg/m3N
300
300
Dust
mg/m3N
20
20
Emissions
Plant RTI
MW
<3
3
Exhaust emissions
Stationary Power Plants
Fuel/type of operation
Compression ignition
(diesel-/dual fuel)
RTI > 5 MW
Spark ignition (gas
engines) RTI > 1 MW
NOx
mg/m3N
500
600
500
250
500
Plant RTI
MW
2 20
20 100
> 100
NOx
mg/m3N
1500*
1000
600
CO
mg/m3N
650
650
650
NMHC
mg/m3N
150
150
150
Dust
mg/m3N
100
100
100
* for rated speeds below 1200 rpm, a limit of 1900 mg/m3N applies
Emissions
France
Diesel engines
Exhaust emissions
Stationary Power Plants
Austria
Planned emission limits for stationary combustion engines.
Diesel engines
Plant RTI
MW
Emergency
power (<50h)
< 750
750
NOx
mg/m3N
2500
CO
mg/m3N
650
Dust
mg/m3N
80
1000
250
150
150
20
20
Italy
Diesel engines
Plant RTI
MW
<3
>3
NOx
mg/m3N
4000
200
CO
mg/m3N
650
650
HC*
mg/m3N
600
600
SO2
mg/m3N
500
500
Dust
mg/m3N
130
130
* butane - heptane
Dust
mg/m3N
50
Emissions
NOx
mg/m3N
250
Exhaust emissions
Stationary Power Plants
Diesel engines
For new, non-emergency diesel engines, the following limits
shall apply:
Cyl. displ.
MY
Vh,z < 10 l
Pn 2237 kW
Vh,z < 10 l
as of
2007
2007 2010
as of
2011
as of
2007
Pn > 2237 kW
10 l Vh,z
< 30 l
NOx
HC
CO
g/kWh
g/kWh
g/kWh
like EPA-Nonroad (Tier 2 to Tier 4
acc. to MY and Power)
9.2
1.3
11.4
PM
g/kWh
Date
2003
20072)
1)
0.54
> For new diesel engines for emergency use and for re pump
engines less stringent emission limits apply (no exhaust after
treatment)
2)
NOx
0.501)
0.23
0.07
0.03
VOC
1.00
0.45
0.02
0.01
CO
6.0
2.7
0.1
0.05
lbm/MW-hr
g/kWh
lbm/MW-hr
g/kWh
> Particulate emissions not higher than those for natural gas with
a sulphur content of 1 grain/100 scf (i.e. PM < 0.5 mg/kWh)
Japan
Diesel engines
Cyl.
mm
< 400
400
NOx
ppm
(13% O2)
950
1200
NOx
mg/m3N
(5% O2)
3900
4900
Particulates
mg/m3N
(13% O2)
100*
100*
Particul.
mg/m3N
(5% O2)
200
200
Emissions
Exhaust emissions
Stationary Power Plants
India
INDIA CPCB (ARAI) Stage I
Diesel engines up to 800 kW 1) for generator drive must comply
with the following emission limits since November 2004:
NOx
g/kWh
9.2
CO
g/kWh
3.5
PM
g/kWh
0.3
Smoke limit
1/m
0.7
kW
Pn 19
> 19 Pn
up to 75
> 75 Pn
up to 800
1)
NOx + HC
CO
PM
Smoke limit
(light absorbtion
coefzient m1)
g / kWh
g /kWh
g /kWh
7.5
4.7
3.5
3.5
0.3
0.3
0.7
0,7
4.0
3.5
0.2
0.7
NMHC
mg/m3N
100
100
CO
mg/m3N
150
150
PM
mg/m3N
75
75
CO
mg/m3N
400
400
PM
mg/m3N
200
200
Rated net
power (Pn)
NOx
ppmv
710
360
NOx
ppmv
3890
1970
NMHC
mg/m3N
267
267
Emissions
1)
HC
g/kWh
1.3
> Test cycle: ISO 8178-4, D2, smoke limit at rated power
> As of January 2005 all diesel gensets upto 1000 kVA must have
acoustic enclosure, with noise below 75dBA at distance of
1 meter, at 75% load.
Exhaust emissions
Stationary Power Plants
EU Stage II
Net Power (P)
kW
130 P < 560
75 P < 130
37 P < 75
18 P < 37
HC
g / kWh
1.0
1.0
1.3
1.5
CO
g / kWh
3.5
5.0
5.0
5.5
NOx
g / kWh
6.0
6.0
7.0
8.0
PM
g / kWh
0.2
0.3
0.4
0.8
Japan Tier I
Net Power (P)
HC
CO
NOx
PM
kW
130 P < 560
75 P < 130
37 P < 75
19 P < 37
8 P < 19
g / kWh
1.0
1.0
1.3
1.5
1.5
g / kWh
3.5
5.0
5.0
5.0
5.0
g / kWh
6.0
6.0
7.0
8.0
9.0
g / kWh
0.2
0.3
0.4
0.8
0.8
Smoke
opacity
%
40
40
40
40
US Tier II
CO
g / kWh
3.5
3.5
3.5
3.5
5.0
5.0
5.5
6.6
8.0
NMHC + NOx
g / kWh
6.4
6.4
6.4
6.6
6.6
7.5
7.5
7.5
7.5
PM
g / kWh
0.2
0.2
0.2
0.2
0.3
0.4
0.6
0.8
0.8
Emissions
Exhaust emissions
Nonroad Mobile Machinery
EU - Nonroad-Directive 97/68/EC
(as amended by 2012/46/EC)
Diesel engines
Power Pn
kW
Stage II
18 Pn < 37
37 Pn < 75
75 Pn < 130
130 Pn 560
Stage IIIA
19 Pn < 37
37 Pn < 75
75 Pn < 130
130 Pn 560
Stage IIIB
19 Pn < 37
37 Pn < 75
75 Pn < 130
130 Pn 560
Stage IV
56 Pn < 130
130 Pn < 560
NOx
HC
g/kWh
g/kWh
NOx + NMHC
CO
g/kWh
Particul.
g/kWh
Date*
8.0
7.0
6.0
6.0
1.5
1.3
1.0
1.0
5.5
5.0
5.0
3.5
0.8
0.4
0.3
0.2
2001
2004
2003
2002
7.5
4.7
4.0
4.0
7.5
4.7
4.0
4.0
5.5
5.0
5.0
3.5
0.6
0.4
0.3
0.2
2007
2008
2007
2006
4.7
3.3
3.3
2.0
4.7
0.19
0.19
0.19
5.0
5.0
5.0
3.5
0.025
0.025
0.025
0.025
2013
2012
2012
2011
0.4
0.4
0.19
0.19
5.0
3.5
0.025
0.025
10/2014
2014
Emissions
Emissions
* Date for placing on the market, type approval one year earlier
Exhaust emissions
Nonroad Mobile Machinery
Japan
Limits for Special Motor Vehicles of the Ministry of Transport (MOT):
Power Pn
kW
Tier I
19 Pn < 37
37 Pn < 75
75 Pn < 130
130 Pn 560
Tier II
19 Pn < 37
37 Pn < 56
56 Pn < 75
75 Pn < 130
130 Pn 560
NOx
HC
g/kWh
g/kWh
NOx + NMHC
CO
g/kWh
Particul.
g/kWh
Smoke
%
Date*
Oct. ...
8.0
7.0
6.0
6.0
5.5
5.0
5.0
3.5
1.5
1.3
1.0
1.0
0.8
0.4
0.3
0.2
40
40
40
40
2004
2004
2004
2004
6.0
4.0
4.0
3.6
3.6
5.0
5.0
5.0
5.0
3.5
1.0
0.7
0.7
0.4
0.4
0.4
0.3
0.25
0.2
0.17
40
35
30
25
25
2007
2008
2008
2007
2006
* Date for placing on the market, type approval one year earlier
Power Pn
kW
NOx
HC
g/kWh
g/kWh
NOx + NMHC
Japan NRMM Stage III
19 Pn < 37
4.0
5.0
37 Pn < 56
4.0
5.0
56 Pn < 75
0.4
5.0
75 Pn < 130
0.4
5.0
130 Pn 560
0.4
3.5
CO
g/kWh
Particul.
g/kWh
Smoke
%
Date*
Oct. ...
0.7
0.7
0.19
0.19
0.19
0.03
0.025
0.02
0.02
0.02
25
25
25
25
25
2016
2016
2015
2015
2014
Emissions
* The date for imported machines and vehicles (and those in contiuous production)
may vary.
Exhaust emissions
Nonroad Mobile Machinery
Diesel engines
Power Pn
kW
Tier 1
Pn > 560
Tier 2
19 Pn < 37
37 Pn < 75
75 Pn < 130
130 Pn 225
225 Pn 450
450 Pn 560
Pn > 560
Tier 3
19 Pn < 37
37 Pn < 75
75 Pn < 130
130 Pn 560
Pn > 560
Tier 4 interim
19 Pn < 37
37 Pn < 56
56 Pn < 130
130 Pn 560
Pn > 560
Tier 4 interim Pn > 900
Tier 4
19 Pn < 37
37 Pn < 56
56 Pn < 130
130 Pn 560
Pn > 560
Tier 4 - Genset
Pn > 560
NOx
HC
g/kWh
g/kWh
NOx + NMHC
CO
g/kWh
Particul.
g/kWh
as of
MY*
9.2
1.3
11.4
0.54
2000
7.5
7.5
6.6
6.6
6.4
6.4
6.4
7.5
7.5
6.6
6.6
6.4
6.4
6.4
5.5
5.0
5.0
3.5
3.5
3.5
3.5
0.6
0.4
0.3
0.2
0.2
0.2
0.2
2004
2004
2003
2003
2001
2002
2006
5.0
5.0
3.5
0.4
0.3
0.2
2008
2007
2006
no further reduction
4.7
4.7
4.0
4.0
4.0
4.0
no further reduction
7.5
4.7
3.4
2.0
3.5
Genset
0.67
7.5
4.7
0.19
0.19
0.4
5.5
5.0
5.0
3.5
3.5
0.3
0.03
0.02
0.02
0.1
2008
2012
2012
2011
2011
0.4
3.5
0.1
2011
4.7
4.7
0.4
0.4
3.5
4.7
4.7
0.19
0.19
0.19
5.5
5.0
5.0
3.5
3.5
0.03
0.03
0.02
0.02
0.04
2013
2013
2014
2014
2015
0.67
0.19
3.5
0.03
2015
* Optional for Tier 3/4: 37-56 kW - PM = 0.3 g/kWh as of 2008; 56-560 kW.- Phase in/Phase out
98 I Gendrive I Sales Program 2015
Emissions
Exhaust emissions
Nonroad Mobile Machinery
India
Proposed is the adoption of the EU-Nonroad-limits. Stage II as of
2007, stage III A as so 2011.
CO
g/kWh
PM
g/kWh
Date
8.00
6.60
6.50
6.50
5.00
5.00
1.0
0.85
0.85
0.85
0.70
0.54
Oct. 2008
Oct. 2008
Oct. 2007
Oct. 2007
Oct. 2007
Oct. 2007
8.00
6.60
5.50
5.00
5.00
3.50
0.80
0.80
0.60
0.40
0.30
0.20
April 2011
April 2011
April 2011
April 2011
April 2011
April 2011
75 Pn < 130
130 Pn < 560
Pn < 560
CO
g/kWh
PM
g/kWh
5.0
3.5
0.3
0.2
Emissions
Pn < 8
8 Pn < 19
19 Pn < 37
37 Pn < 75
75 Pn < 130
130 Pn < 560
NOx
HC
g/kWh
g/kWh
Bharat Stage II (CEV)
9.20
1.30
9.20
1.30
9.20
1.30
9.20
1.30
9.20
1.30
9.20
1.30
Bharat Stage II (CEV)
HC + NOx [g/kWh]
7.50
7.50
7.50
4.70
4.00
4.00
NOx
HC
g/kWh
g/kWh
NOx + NMHC
6.0
1.0
6.0
1.0
MTU ValueCare
Keep going.
ValueService
Extensive global service and support to help maximize
performance and uptime.
Reliable, expert assistance is essential to achieving and maintaining high
levels of performance and unconditional reliability throughout an MTU
engines lifecycle. ValueService is a full line of maintenance, repair and
service solutions designed to help maximize the performance and uptime
of MTU engines. From scheduled and unscheduled maintenance and
repair to technical documentation to product training, MTU provides
comprehensive support, customized to meet your unique needs.
ValueSpares
Genuine spare parts and top-quality consumables designed
specifically for MTU engines.
To keep your MTU engines running at optimum efficiency, choose from
a full line of genuine ValueSpares parts and consumables. Theyre
designed, tested and approved specifically for MTU engines. Whether its
spare parts or filters, oils and coolants, only MTU can guarantee genuine
quality, with parts and consumables that are designed to work seamlessly
with your MTU product. ValueSpares products help you get maximum
performance and value from your equipment. And for your convenience,
putting our parts and consumables to work is easy. ValueSpares products
are available worldwide from a single source through our MTU service
network.
ValueExchange
Remanufactured parts and engines engineered with the same high
quality standards as new products.
Whether replacing a single component or an entire engine, quality is
essential. When you choose ValueExchange products, you get genuine
MTU quality, speed and peace of mind while lowering costs.
ValueExchange provides a full range of genuine remanufactured
MTU parts and engines all engineered to ensure robust, reliable
performance. A rigorous reconditioning process ensures the same high
standards of performance, service life and quality as new products
including design and model-related updates. As a result, genuine
ValueExchange products feature similar technological advancements
as new products. And for added confidence, we back our products with
a full manufacturers warranty.
Service Network
Local support.
Worldwide.
Notice
Conversion table
1 kW
= 1.360 PS
1 kW
= 1.341 bhp
1 HP
= 1.014 PS
1 oz
= 28.35 g
1 lb
= 453.59 g
1 short ton = 907.18 kg
1 lb/HPh
= 447.3 g/PSh
1 lb/HPh
= 608.3 g/kWh
1 gal/HPh(US) = 4264 g/kWh
1 kWh
= 860 kcal
1 cal
= 4.187 J
= 9.80665 m/s2
= 3.14159
= 2.71828
1 lb
1 short ton
1 ft lb
1 ft/min
pDiesel
1 lb/sqin
1 mm HG
=
=
=
=
=
=
=
1 BTU
= 1.055 kJ
1 mm WS
1 inch
1 sq. inch
1 cu. inch
1 foot
1 sq. foot
1 land mile
1 naut. mile
1 GB Gallon
1 US Gallon
1 US Barrel
= 2.540 cm
= 6.542 cm2
= 16.387 cm3
= 3.048 dm
= 9.290 dm2
= 1.609 km
= 1.853 km
= 4.546 l
= 3.785 l
= 0.159 m3
= 42 US Gallons
T (K)
t (C)
t (C)
1 foot
1 yard
1 land mile
1 naut. mile
=
=
=
=
=
=
=
16 oz
2000 lbs
1.356 Nm
0.00508 m/s
0.83 kg/l
0.069 bar (1 psi)
1.333 mbar
(133.3 Pa)
0.0981 mbar
(9.81 Pa)
t (C) + 273.15
5/9 x (t (F) -32)
5/4 x t (R)
12 inches
3 feet
5280 feet
6080 feet
Energy:
Power:
Force:
Pressure:
MEP (bar)
1 J = 1 Ws = 1 VAs = 1 Nm
1 W = 1 VA = 1 Nm/s
1 N = 1 kgm/s2
1 Pa = 1 N/m2 (1 bar = 105 Pa)
= Pcyl(kW) x 1200
n(1/min) x Vcyl(l)
Torque (Nm) = Pges(kW) x 30000
n(1/min) x
www.mtu-online.com
Subject to change. | 3190171 | Edition 01/15 | ENC 2015-01 | Printed in Germany on chlorine-free bleached paper.