Calculation Package for Reinforced Concrete Slab based on ACI-318 Chapter 13 & PCA Comments

Project :
Customer :
Location :
Structure :

TABLE OF CONTENTS
Chapter No. 1 => General Information of the Structural System
1.1 Code Notation
1.2 Plate Model Assumptions and Considerations for Analysis

Chapter No. 2 => Model Assumptions & Criteria


2.1 Sketch(s) of the Model
2.2 Design Loads & Material Properties considered
2.3 Thickness of the Slab & Cover
2.4 Mechanical Elements from Staad Pro

Chapter No. 3 => Reinforced Concrete Design


3.1 Defining Steel Reinforcement for "Mx" @ Central Strip
3.2 Defining Steel Reinforcement for "My" @ Central Strip
3.3 Defining Steel Reinforcement for "Mx" @ Lateral Strip
3.4 Defining Steel Reinforcement for "My" @ Lateral Strip

Chapter No. 4 => Design Conclusions


4.1 The Steel Reinforcement based on calculations
4.2 Sketch for Reinforcement

Version 1.0.0
Date
Designed
Revised
Approved

:
:
:
:

16-mar-16
JR
JR
JR

Calculation Package for Reinforced Concrete Slab based on ACI-318 Chapter 13 & PCA Comments
Project :
Customer :
Location :
Structure :

CHAPTER No. 1; GENERAL INFORMATION OF THE STRUCTURAL SYSTEM


1.1

Version 1.0.0
Date
Designed
Revised
Approved

:
:
:
:

16-mar-16
JR
JR
JR

Version 1.0.0

Calculation Package for Reinforced Concrete Slab based on ACI-318 Chapter 13 & PCA Comments
Project :
Customer :
Location :
Structure :

Date
Designed
Revised
Approved

:
:
:
:

16-mar-16
JR
JR
JR

1.2 Plate Model Assumptions and Considerations for Analysis

1.2.1 Quadratic Stress distribution assumed for Bending

1.2.2 Sign Conventions for Plate Axis

1.2.3 Sign Conventions for Plate Moments

1.2.4 Sign Conventions for Plate Stresses

1.2.5 Sign Conventions for Stress caused by Mx

1.2.6 Sign Conventions for Stress caused by My

1.2.7 Sign Conventions for Out of Plane Shear Stresses SQX and SQY

Version 1.0.0

Calculation Package for Reinforced Concrete Slab based on ACI-318 Chapter 13 & PCA Comments
Project :
Customer :
Location :
Structure :

Date
Designed
Revised
Approved

CHAPTER No. 2; MODEL ASSUMPTIONS & CRITERIA


2.1 Sketch(s) of the Model
2.1.1 Slab Length 1 =>

5.50 m

2.1.2 Slab Length 2 =>

7.50 m

2.2 Design Loads & Material Properties considered


The Material Specifiations will be as shown below, unless otherwise noted.
2.2.1 Slab

Material Spec : Reinforced Concrete

f'c :

250 kg/cm2

2.2.2 Reinforced Steel

Material Spec : ASTM A615

fy :

4,200 kg/cm2

2.2.3 Reinforced Steel Wire Mesh

Material Spec : ASTM A185

fy :

5,000 kg/cm2

The Design Loads will be as shown below, unless otherwise noted.


2.2.4 Dead Load
DL :

100 kg/m2

2.2.5 Live Load


LL :

500 kg/m2

2.2.6 Required Strength


920 kg/m2
[U] :

:
:
:
:

16-mar-16
JR
JR
JR

Version 1.0.0

Calculation Package for Reinforced Concrete Slab based on ACI-318 Chapter 13 & PCA Comments
Project :
Customer :
Location :
Structure :

Date
Designed
Revised
Approved

:
:
:
:

16-mar-16
JR
JR
JR

2.3 Thickness of the Slab & Cover


The minimum thickness will be the maximum of the shown below.
2.3.1 Thickness 1 :

9 cm

[ACI 9.5 c]

2.3.2 Thickness 2 :

9 cm

[ACI 9.5 c]

2.3.3 Thickness 3 :

10 cm

[ACI 9.5.3.2 b]

2.3.4 Thickness 4 :

8 cm

The minimum cover will be in accordance with the specifications shown below.

2.4 Mechanical Elements from Staad Pro (Moments & Shear Stress)
2.4.1a Mechanical Elements "Mx" for Central Strip
Location
(m)

0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00

Plate ID

L/C

76
77
78
79
80
81
82
83
84
85
86

4
4
4
4
4
4
4
4
4
4
4

2.4.1b Mechanical Elements "My" for Central Strip

Mx

Lx

Ly

Thk

Location

(Ton-m)

(m)

(m)

(m)

(m)

-0.20
-0.29
-0.36
-0.38
-0.39
-0.38
-0.34
-0.24
-0.11
-0.02
0.01

1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10

0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00

Plate ID

L/C

10
25
40
55
70
85
100
115
130
145
160

4
4
4
4
4
4
4
4
4
4
4

My

Lx

Ly

(Ton-m)

(m)

(m)

Thk
(m)

0.19
0.24
0.30
0.33
0.34
0.32
0.29
0.22
0.14
0.08
0.04

1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10

Version 1.0.0

Calculation Package for Reinforced Concrete Slab based on ACI-318 Chapter 13 & PCA Comments
Project :
Customer :
Location :
Structure :

2.4.2a Mechanical Elements "Mx" for Lateral Strip


Location
(m)

0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00

Plate ID

L/C

76
77
78
79
80
81
82
83
84
85
86

4
4
4
4
4
4
4
4
4
4
4

Mx

Lx

Ly

Thk

Location

(Ton-m)

(m)

(m)

(m)

(m)

-0.20
-0.29
-0.36
-0.38
-0.39
-0.38
-0.34
-0.24
-0.11
-0.02
0.01

1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10

0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00

SQx

Lx

Ly

Thk

Location

(m)

(m)

(m)

(m)

-0.05
1.00
1.00
0.48
1.00
1.00
0.55
1.00
1.00
0.58
1.00
1.00
0.59
1.00
1.00
0.59
1.00
1.00
0.58
1.00
1.00
0.41
1.00
1.00
0.07
1.00
1.00
-0.09
1.00
1.00
-0.08
1.00
1.00
## ##
0.1
2.4.4 Quick Review of Slab Thickness based on shear

0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10

0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00

0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00

Plate ID

L/C

106
107
108
109
110
111
112
113
114
115
116

4
4
4
4
4
4
4
4
4
4
4

16-mar-16
JR
JR
JR

Plate ID

L/C

10
25
40
55
70
85
100
115
130
145
160

4
4
4
4
4
4
4
4
4
4
4

My

Lx

Ly

(Ton-m)

(m)

(m)

Thk
(m)

0.19
0.24
0.30
0.33
0.34
0.32
0.29
0.22
0.14
0.08
0.04

1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10

Thk

2.4.3b Mechanical Elements "SQy"

(Kg-cm2)

(m)

:
:
:
:

2.4.2b Mechanical Elements "My" for Lateral Strip

2.4.3a Mechanical Elements "SQx"


Location

Date
Designed
Revised
Approved

Plate ID

L/C

9
24
39
54
69
84
99
114
129
144
159

4
4
4
4
4
4
4
4
4
4
4

SQy

Lx

Ly

(Kg-cm2)

(m)

(m)

(m)

-0.09
0.54
0.60
0.63
0.63
0.63
0.62
0.45
0.11
0.20
-0.21
## ##
0.2

1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10

[ACI 11.3]
Vc :
:

8.38 Kg/cm2
0.75

Vc :

6.29 Kg/cm2
0.63 Kg/cm2

Vu :

[ACI 9.3.2.3]

Vc > Vu

[Satisfactory]

2.4.5 The Minimum Steel Reinforcement will comply with specification shown below.
As

min

1.80 cm2

But never less than :

1.40 cm2

Version 1.0.0

Calculation Package for Reinforced Concrete Slab based on ACI-318 Chapter 13 & PCA Comments
Project :
Customer :
Location :
Structure :

Date
Designed
Revised
Approved

:
:
:
:

16-mar-16
JR
JR
JR

CHAPTER No. 3; REINFORCED CONCRETE DESIGN


3.1 Defining Steel Reinforcement due to Mechanical Elements "Mx" @ Central Strip
Location

Depth "d"

Mux

(m)

(cm)

(Ton-m)

0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00

7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5

-0.20
-0.29
-0.36
-0.38
-0.39
-0.38
-0.34
-0.24
-0.11
-0.02
0.01

0.0159
0.0226
0.0282
0.0303
0.0308
0.0299
0.0268
0.0192
0.0088
0.0016
0.0008

As min

As cal

(cm2)

(cm2)

1.80
1.80
1.80
1.80
1.80
1.80
1.80
1.80
1.80
1.80
1.80

0.71
1.01
1.26
1.35
1.37
1.33
1.19
0.86
0.39
0.07
0.03

Vrs #
4
4
4
4
4
4
4
4
4
4
4

Calc Sp @

Real Sp @

(cm)

(cm)

70
70
70
70
70
70
70
70
70
70
70

25
25
25
25
25
25
25
25
25
25
25

Calc Sp @

Real Sp @

(cm)

(cm)

70
70
70
70
70
70
70
70
70
70
70

25
25
25
25
25
25
25
25
25
25
25

Calc Sp @

Real Sp @

(cm)

(cm)

70
70
70
70
70
70
70
70
70
70
70

25
25
25
25
25
25
25
25
25
25
25

Conclusion

As real
(cm2)

Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs

#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4

@25
@25
@25
@25
@25
@25
@25
@25
@25
@25
@25

cm
cm
cm
cm
cm
cm
cm
cm
cm
cm
cm

5.08
5.08
5.08
5.08
5.08
5.08
5.08
5.08
5.08
5.08
5.08

3.2 Defining Steel Reinforcement due to Mechanical Elements "My" @ Central Strip
Location

Depth "d"

Muy

(m)

(cm)

(Ton-m)

0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00

7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5

0.19
0.24
0.30
0.33
0.34
0.32
0.29
0.22
0.14
0.08
0.04

0.0154
0.0192
0.0234
0.0259
0.0266
0.0256
0.0225
0.0175
0.0114
0.0061
0.0028

As min

As cal

(cm2)

(cm2)

1.80
1.80
1.80
1.80
1.80
1.80
1.80
1.80
1.80
1.80
1.80

0.69
0.86
1.04
1.16
1.19
1.14
1.01
0.78
0.51
0.27
0.13

Vrs #
4
4
4
4
4
4
4
4
4
4
4

Conclusion

As real
(cm2)

Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs

#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4

@25
@25
@25
@25
@25
@25
@25
@25
@25
@25
@25

cm
cm
cm
cm
cm
cm
cm
cm
cm
cm
cm

5.08
5.08
5.08
5.08
5.08
5.08
5.08
5.08
5.08
5.08
5.08

3.3 Defining Steel Reinforcement due to Mechanical Elements "Mx" @ Lateral Strip
Location

Depth "d"

Mux

(m)

(cm)

(Ton-m)

0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00

7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5

-0.20
-0.29
-0.36
-0.38
-0.39
-0.38
-0.34
-0.24
-0.11
-0.02
0.01

0.0159
0.0226
0.0282
0.0303
0.0308
0.0299
0.0268
0.0192
0.0088
0.0016
0.0008

As min

As cal

(cm2)

(cm2)

1.80
1.80
1.80
1.80
1.80
1.80
1.80
1.80
1.80
1.80
1.80

0.71
1.01
1.26
1.35
1.37
1.33
1.19
0.86
0.39
0.07
0.03

Vrs #
4
4
4
4
4
4
4
4
4
4
4

Conclusion

As real
(cm2)

Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs

#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4

@25
@25
@25
@25
@25
@25
@25
@25
@25
@25
@25

cm
cm
cm
cm
cm
cm
cm
cm
cm
cm
cm

5.08
5.08
5.08
5.08
5.08
5.08
5.08
5.08
5.08
5.08
5.08

Version 1.0.0

Calculation Package for Reinforced Concrete Slab based on ACI-318 Chapter 13 & PCA Comments
Project :
Customer :
Location :
Structure :

Date
Designed
Revised
Approved

:
:
:
:

16-mar-16
JR
JR
JR

3.4 Defining Steel Reinforcement due to Mechanical Elements "My" @ Lateral Strip
Location

Depth "d"

Muy

(m)

(cm)

(Ton-m)

0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00

7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5

0.19
0.24
0.30
0.33
0.34
0.32
0.29
0.22
0.14
0.08
0.04

0.0154
0.0192
0.0234
0.0259
0.0266
0.0256
0.0225
0.0175
0.0114
0.0061
0.0028

As min

As cal

(cm2)

(cm2)

1.80
1.80
1.80
1.80
1.80
1.80
1.80
1.80
1.80
1.80
1.80

0.69
0.86
1.04
1.16
1.19
1.14
1.01
0.78
0.51
0.27
0.13

Vrs #
4
4
4
4
4
4
4
4
4
4
4

Calc Sp @

Real Sp @

(cm)

(cm)

70
70
70
70
70
70
70
70
70
70
70

25
25
25
25
25
25
25
25
25
25
25

Conclusion

(cm2)

Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs
Vrs

#4
#4
#4
#4
#4
#4
#4
#4
#4
#4
#4

@25
@25
@25
@25
@25
@25
@25
@25
@25
@25
@25

cm
cm
cm
cm
cm
cm
cm
cm
cm
cm
cm

CHAPTER No. 4; DESIGN CONCLUSIONS


4.1 The Steel Reinforcement based on calculations will be as follow:
4.1.1 Steel Reinforcement @ Mx Central Strip

: Vrs #4 @25 cm

4.1.2 Steel Reinforcement @ My Central Strip

: Vrs #4 @25 cm

4.1.3 Steel Reinforcement @ Mx Lateral Strip

Vrs #4 @25 cm

4.1.4 Steel Reinforcement @ My Lateral Strip

Vrs #4 @25 cm

4.2 Sketch for Reinforcement


Vrs #4 @25 cm

10 cm

As real

JUST BOTTOM

5.08
5.08
5.08
5.08
5.08
5.08
5.08
5.08
5.08
5.08
5.08

Calculation Package for Reinforced Concrete Slab based on ACI-318 Chapter 13 & PCA Comments
Project :
Customer :
Location :
Structure :

Version 1.0.0
Date
Designed
Revised
Approved

:
:
:
:

16-mar-16
JR
JR
JR

También podría gustarte