Centrifugal Utility Fans

Model SFD, SFB, SWD and SWB


Direct and Belt Drive

New Model SWD with

January
2014

Models SFD, SFB, SWD and SWB


Utility Fans
Contents
Standard Construction Features .................... 4-5

Engineering Data ............................................... 16

Vari-Green Options ........................................ 6-7

Fan Identification/Model Selection.................... 18

Severe Duty Options ...................................... 8-9

SFD Dimensions and Performance ............ 17-18

Temperature Options ......................................... 10

SWD Dimensions and Performance........... 17-19

Options and Accessories .............................10-12

SFB Dimensions and Performance ............ 20-29

Typical Installations ........................................... 13

SWB Dimensions and Performance........... 30-65

Discharge Position/Dimensional Data ..........14-15

Typical Specifications ................................. 66-68

Greenheck Fan Corporation certies that the model SFD,


SFB, SWD and SWB, fans shown herein are licensed to bear
the AMCA Seal. The ratings shown are based on tests and
procedures performed in accordance with AMCA Publication
211 and comply with the requirements of the AMCA Certied
Ratings Program. The certied ratings for Model SFD, SFB
and SWB are shown on pages 15-61.

Greenheck Fan Corporation certies that the model SWB


Series 300 AF, fans shown herein are licensed to bear the
AMCA Seal. The ratings shown are based on tests and
procedures performed in accordance with AMCA Publication
211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certied Ratings Program. The
certied ratings for Model SWB Series 300 AF are shown on
pages 49-61.

SFD, SFB, SWD and SWB Series 100, 200 and 300
models are listed for electrical (UL/cUL 705)
File no. E40001
SWB Series 200 and 300 models are listed for grease
removal (UL/cUL 762) File no. MH11745
SWB Series 200 and 300 models are listed for
Emergency Smoke Control Systems File No. MH17511

High Wind Certication

Seismic Certication

Miami-DADE Notice of Acceptance (NOA)


09-0303.31 for high wind and hurricane zones

OSHPD - Ofce of Statewide Health Planning


and Development - OSP-0113-10

Florida Product Approval Number - FL12680

IBC 2006 and 2009 - International Building Code

Enjoy Greenhecks extraordinary service, before, during


and after the sale.
Greenheck offers added value to our wide selection of top performing, energy-efcient products by
providing several unique Greenheck service programs.
Our Quick Delivery Program ensures shipment of our in-stock products within 24 hours of placing
your order. Our Quick Build made-to-order products can be produced in 1-3-5-10-15- or 25 day
production cycles, depending upon their complexity.
Greenhecks free Computer Aided Product Selection program (CAPS), rated by many as the best in
the industry, helps you conveniently and efciently select the right products for the challenge at hand.
Greenheck has been Green for a long time! Our energy-saving products and ongoing corporate
commitment to sustainability can help you qualify for LEED credits.
Our 3D service allows you to download at no charge lightweight, easy-to-use AutoDesk Revit
3D drawings for many of our ventilation products.
Find out more about these special Greenheck services at greenheck.com

Models SFD, SFB, SWD and SWB


Utility Fans
Model Comparison

Models SFD and SFB


Greenheck models SFD and SFB
forward-curved utility fans have been
designed for supply, exhaust and
return air applications requiring low to
medium air volumes and pressures.
You will receive the following benefits
with these fans:
SFD fans are available in four sizes
(6, 7.5, 9 and 10) with different rpm
motors. Capacities range from 150
to 2,600 cfm (255 to 4,600 m/hr) with
static pressures to 2.5 in. wg (623 Pa).

Model SWD and SWB


Greenhecks backward-inclined
utility fans have many advantages;
higher operating efficiencies, nonoverloading horsepower curves and
higher pressure capabilities. You will
also receive the following benefits with
these fans:
SWD fans are available in seven
sizes (7 through 18) with capacities
from 100 to 5,500 cfm (170 to 9,352
m/hr) and static pressures to
2.5 in. wg (623 Pa). Model SWD
is offered exclusively with Vari-Green
electronically commutated motors
for energy efficiency and ease of
control.
SWB Series 100 in ten sizes (106
through 124) with capacities from

Maximum Volume
(cfm)

Maximum Static Pressure


(in. wg)

Relative Cost

Mixed Flow

Centrifugal

Direct

Belt

Propeller/Axial

High Temp (above 200F )

High Wind (150 mph)

Smoke Control (UL)

9
9
9 9
9
9
9
9
9 9
9 9
9 9 9 9 9 9 9
9

Grease (UL 762)

9
9
9
9

Spark Resistant

9
9
9
9

Recirculate

9
9
9
9

Reversible

Wall

Hanging

Base/Floor

Roof Curb

9
9
9
9

Impeller Type Performance

Contaminated Air

SWB

9
9
9
9

Drive
Type

Application

General/Clean Air

SWD

9
9
9
9

Supply

SFB

Indoor

SFD

Outdoor

Model

Airow

Exhaust

Mounting

Ceiling Mounted

Location

2,600

2.5

25,200

3.5

$$

5,500

2.5

$$

54,000

$$

SFB fans are available in ten sizes (9 through 30)


with capacities ranging from 360 to 25,250 cfm
(610 to 42,900 m/hr) and static pressures to
3.5 in. wg (872 Pa).
Greenheck utility fans are designed, engineered and
tested prior to shipment to provide years of smooth,
vibration-free operation with minimal maintenance.
The fan may be mounted indoors or outdoors.
All fan sizes are tested in our AMCA accredited
laboratory to ensure complete and accurate
performance ratings. All models are licensed to bear
the AMCA Air Performance seal. Performance as
cataloged is assured.
70 to 11,000 cfm (120 to 18,700 m/hr) and static
pressures to 3.0 in. wg (747 Pa).
SWB Series 200 in twelve sizes (206 through 224)
with capacities from 70 to 13,700 cfm (120 to 23,300
m/hr) and static pressures to 5.0 in. wg (1,250 Pa).
SWB Series 300 in seven sizes (327 through 349) with
capacities from 4,600 to 54,000 cfm (7,700 to 91,700
m/hr) and static pressures to 5.0 in. wg (1,250 Pa).
Greenheck utility fans are designed, engineered and
tested prior to shipment to provide years of smooth,
vibration-free operation with minimal maintenance.
Fans may be mounted indoors or outdoors.
Fans are tested in our AMCA accredited laboratory
to ensure complete and accurate performance
ratings. All models are licensed to bear the AMCA
Air Performance seal. SWB 300 Series AF fans
are licensed to bear the AMCA Sound and Air
Performance seal. Performance as cataloged
is assured.
3

Standard Construction Features

Standard Construction Features

All structural steel parts are phosphate treated and coated with Greenhecks
Permatector for a long lasting finish. Galvanized construction remains
unpainted.

Backward Inclined or Airfoil

Finish

Backward Inclined

Backward Inclined

SWB Series 100 and 200 through size 210 and all sizes of SWD have
backward-inclined non-overloading centrifugal wheels constructed of
aluminum. Series 200, sizes 212 and larger and Series 300 wheels are
constructed of steel or aluminum. Backward-inclined wheels are made
of a heavy-gauge material with single-thickness blades securely riveted
or welded to a heavy-gauge backplate and wheel cone. SWB Series 300
fans are available with aluminum airfoil wheels. Each wheel is statically and
dynamically balanced to precise tolerances.

Backward Inclined

SFD and SFB fans have forward-curved centrifugal wheels constructed of die
formed steel with blades securely riveted to a steel backplate and rim.
Each wheel is statically and dynamically balanced to precise tolerances.
Forward Curved

Wheel

SWB
100 200 300

Forward Curved

SFD SFB SWD

Painted Steel

Painted Steel or Aluminum

Housings are available in clockwise or counterclockwise rotation and are field


rotatable to the eight standard discharge positions. Side panels are bonded
to the fan housing with an airtight lock seam. Fully welded housings are also
available on SFB, SWD, and SWB Series 200 and 300 models.

Galvanized

SFD and SWB Series 100 housings are constructed of galvanized steel.
SFB and SWB Series 200 and 300 housings are constructed of steel and
coated with Permatector as standard. SWB Series 200 may also be
constructed with aluminum housings and housing supports. SWD housings
can be galvanized, painted steel, or aluminum.

Galvanized, Painted Steel,


or Aluminum

Housing

Painted Steel

Galvanized

See housing and drive frame information for specific material and coating.

Base rails have prepunched mounting holes which allow for easy installation.

9 9 9 9 9 9

Drive
Frame

SFB and SWB Series 100 and 200 drive frames are constructed of rugged,
welded and coated steel members (Series 300 drive frames are constructed
of reinforced heavy-gauge galvanized steel) supporting the shaft and
bearings to provide rigid reinforcement for the housing. SFB and SWB drive
frames are arrangement 10.
SFD drive frames are constructed of galvanized steel, bolted and available in
arrangement 4. SWD drive frames are constructed of galvanized or painted
steel, bolted and available in arrangement 4.

Fasteners

Corrosion-resistant fasteners are used to secure unit base and blower


scroll assembly.

Motor

Heavy-duty ball bearing motors are carefully matched to the fan load. Open
drip proof, totally enclosed, and explosion resistant enclosures are available
for SFD, SFB, and SWB fans.
Vari-Green motors are included with all SWD fans, and are optional for
model SFD.

Galvanized

Mounting
Holes

Painted Steel

Painted Steel

9 9 9 9 9 9

Galvanized or
Painted Steel

Housing supports are constructed of heavy-gauge steel with formed flanges


for extra strength.

Painted Steel

Housing
Supports

Galvanized

9 9 9 9 9 9

9 9 9 9 9 9

Vari-Green motor enclosures may be open drip proof or totally enclosed.

Inlet Cone Streamlined inlet cone design provides for low turbulence air intake, reducing
intake losses and sound levels.

9 9 9 9 9 9

Standard Construction Features

Belt Drive Only Features

SFB

SWB
100 200 300

10 Motor Plate

Pivoting motor plate with adjusting screws make belt tensioning a quick and easy
operation.

9 9 9 9

11 Drive
Assembly

Machined, cast iron pulleys are factory set to the required RPM and are adjustable for
final system balancing for applications with 10 hp or less motors. Sized for a minimum
of 150% of driven horsepower.

9 9 9 9

12 Fan Shaft

Precision turned, ground and polished solid steel shafts are sized so the first critical
speed is at least 25% over the maximum operating speed. Stainless steel shafts are
available on SWB Series 200 and 300 fans.

9 9 9 9

13 Bearings

Heavy-duty, self-aligning pillow block ball bearings are selected for a minimum L10 life
in excess of 100,000 hours (L50 average life of 500,000 hours) at maximum cataloged
operating conditions.

9 9 9 9

SFB and
SWB 200

7
3

13

SWD

7
8

12
13

6
4
3
1
7

11

10
6

SFD
5

3
3

SWB 100

SWB 300
2
13

13

11

12

12

11

6
8

4
4
8

10

6
10
5

Vari-Green Options

Vari-Green Motor -

SWD and SFD

Greenhecks electronically commutated (EC)


Vari-Green (VG) motor combines motor
technology, controllability and energy-efciency
into one single low maintenance unit and is the
industrys rst fully controllable motor. When combined
with Greenhecks SWD/SFD fans, most of the CFM and
static pressure ranges of a belt drive can be attained
with the benets of a direct drive.
Motor Information
HP
1/6

RPM
1725

Volts
115
115
1/4
1725
115/230
115
1/2
1725
115/230
115
3/4
1725
115/230
115
1
1725
115/230
1
1725 115/208-230
2
1725
208-230
Extended RPM Motors
1/2
2500
115
3/4
2200
115

HZ
50/60

Phase
Single

Enclosure
TENV

Single
Single

FLA
3.4
3.7
3.3/1.8
6.7
6.8/3.5
10.1
9.0/4.9
12.4
11.4/6.3
12.0/6.0
12.0

50/60

Single

50/60

Single

50/60

Single

50/60

Single

50/60
50/60
50/60
50/60

Single
Single

6.5
11.3

ODP
ODP

ODP
ODP
ODP
ODP

Vari-Green Advantages
Initial cost is similar to a belt drive
Lower operating cost
No maintenance, no belts, pulleys or bearings
Easy RPM adjustment

Features
1. Dial on Motor Control - A potentiometer (dial on
motor control) is mounted on the motor for easy
speed adjustment for system balance. Simply turn
the dial; there are no belts and pulleys to adjust.
2. Control Wire Inputs - the motor accepts a
0-10 VDC signal from Building Automation Systems,
Vari-Green Controls or other controls to adjust
motor speed.
3. Consolidated Motor with Dial and 0-10 VDC signal
- Refer to greenheck.com, Vari-Green Motor IOM for
specic information.

TEFC
TEFC

Vari-Green Motor Benets


Operates on AC power thats converted to DC
providing a more efcient motor operation as compared
to an AC operation.
The motor can attain up to 85% efciency and reduce
energy consumption.
Watt savings of 20-70% depending on RPM.
Note: As motor speed is turned down, efciency stays high

Constant Volume Life Cycle Analysis


Three Year Cost Comparison

as compared to an AC motor that decreases dramatically.

Operates cooler than a standard AC motor at lower


RPMs. A cooler motor has longer motor life and
reduces energy consumption.
80% usable RPM turndown vs. 30% on AC single
phase direct drive.
SWD and SFD fans with Vari-Green motors can
provide most of the CFM and static pressure ranges
of a comparable belt drive.
Maintenance costs are reduced as there are
no belts or bearings to replace and no pulleys
to adjust.
Direct drive fans are often preferred where
maintenance access is difcult.
Provides a solution for demand controlled ventilation
applications.

Analysis is based on
operating costs for a
period of three years
where the fans operate
continuously at 1725
rpm, 24/7, with an
energy rate of $0.10/
kWh. Maintenance on
the SQ-120 is estimated
at $65/yr.

$2000

1800
1600
1400
1200
1000
800
600
400
200
$0
Belt
Drive

VariGreen

Initial Cost
Maintenance cost over three years
Operating cost over three years

Note: Example is based


on a relative cost. Use
and installation variables
may produce different
results.

Vari-Green Options

Demand Controlled Ventilation for


Multistory Buildings

install for applications that include: venting dryers,


bathrooms, residential type kitchen space or industrial
process exhaust.

Applications requiring constant pressure or variable


volume can utilize SWD and SFD fans with Vari-Green
motors and Vari-Green
controls. Demand controlled Variable Volume
Operating Cost Analysis
ventilation systems reduce
Variable Volume vs. Constant Volume
the amount of energy used
$2,000
by decreasing the speed
1,750
of the fan when demand
1,500
is low. This in turn lessens
1,250
the amount of conditioned
1,000
air exhausted and further
750
reduces total operating
500
costs associated with air
conditioning and heating
250
in multistoried buildings
$0
Constant
Variable
such as: hotels, multifamily
Volume
Volume
complexes, institutional
Heating Cost
facilities, and high rise
Cooling Cost
commercial buildings.
Fan Operating Cost

Contact fans@greenheck.com for more information.

Example of potential savings


based on a northeast city in
the USA using Vari-Green
components for variable volume.

Vari-Green Controls
Transformer - Provides 24V power from the existing
line voltage at the fan to the Vari-Green motor and
controls. Dual voltage primary (120/240V) transformer
provided with the fan.

% of Operation

Hypothetical (Hotel Bathroom)


Variable Volume - Load Shape
100
80$$$$$$$$$$$$$$$$$$$$$$$$
60$$$$$$$$$$$$$$$$$$$$$$$$
40$$$$$$$$$$$$$$$$$$$$$$$$
20$$$$$$$$$$$$$$$$$$$$$$$$
0%$$$$$$$$$$$$$$$$$$$$$$$$
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Time of Day

Series 1

Demand controlled ventilation offers significant energy savings by


exhausting only the necessary amount of air throughout the day.

% of Operation

The Vari-Green constant


pressure control is preprogrammed and easy-to-

Daily Operating Comparison:


Variable Volume and Constant Volume

Constant Volume - Load Shape


100
80
60
40
20
0%

1 2 3 4

Series 2

5 6

7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Time of Day

Note: A standard VFD compatible motor can also function within a


variable volume system.

Institutional facilities - Schools, prisons,


multistory ofce buildings; bathrooms.
Constant Pressure Control - Outdoor
Control Vari-Green motor via static pressure on the
inlet side of the fan. Includes one duct probe and
transducer for use in:

Remote Dial - Allows for remote, manual airow


adjustments. Wall plate with dial may be mounted in a
standard 2x4 inch electrical junction box.

Multifamily structures - Apartments, condos, hotels;


residential kitchen, dryer facilities and bathrooms.

Two-Speed Control with Integral Transformer


Control allows motor RPM to be set at two independent
speeds (high or low). Meets minimum airow
requirements with the ability to bump up to high
speed in an emergency or meet maximum airow
requirements, or reset to low for energy conservation.
Speeds are selectable via either a dry contact input
which utilizes an external switching device to toggle
between speeds, or an AC digital input which allows an
AC voltage signal to be used to change speeds.

Air Quality VOC - Control a Vari-Green motor via


changes in volatile organic compounds (VOCs).
VOCs are gasses that are emitted from humans,
building materials, perfumes, foods, and furniture
off-gassing. Range is 0-2000 CO2 ppm equivalent.

Constant Pressure Control - Indoor Control Vari-Green motor via static (variable volume) or
velocity (constant CFM) pressure on the inlet or outlet
side of the fan. Optional, one or two, duct or room
probes for use in:
Multifamily structures - Apartments, condos, hotels;
dryers, residential kitchens and bathrooms.

Institutional facilities - Schools, prisons, multistory.

Institutional facilities Schools, court house,


hospitals; bathrooms, waiting rooms, cafeteria.
Commercial buildings Ofce space, conference
rooms, bathrooms, break room.
Air Quality Temperature and Humidity Control Vari-Green motor via changes in temperature,
humidity, or both. Range is 15 to 130F (-10 to 55c)
and 0 to 100% relative humidity.
Multifamily structures Apartments, condos, hotels;
bathrooms, utility rooms.
Commercial buildings Ofce buildings; ofce space,
conference rooms, utility rooms, bathrooms.
7

Applications
High Wind and Hurricane

High Wind and Hurricane SFD, SFB and SWB Series 100 and 200
Greenheck is leading the High Wind Standard for rooftop fans and ventilators. Forceful
winds and wind-borne debris are the cause of most hurricane damage. Hurricane
winds start at 75 mph and can exert
a force of 75 pounds per square foot
of pressureor over 900 pounds
on a fan and curb. Forceful winds
are not the only problem, wind-borne
debris can also cause detrimental
effects to objects and structures.
High winds and extreme forces are
the cause of most storm damage.
By analyzing calculations, computer
simulations, actual testing, and
other standardsGreenheck
Atlantic, Gulf and Pacic history of major hurricane tracks.
developed the High Wind Standard.

Protocols designed to protect against wind-borne debris and severe wind loads:
Structural
Performance Load

A static load that is 2times the design load (180 pounds per square foot pressure) is applied both positive
and negative to simulate wind force loads in each direction. Structural Performance per Dade County
Protocol TAS-202 (ASTME-330).

Large Missile
Impact Test

Large Missile Impact Testing is required when objects are located 30 feet or less from the ground.
The test is per Dade County Protocol TAS-201. The test unit is impacted three times with a piece of
lumber (2 in. x 4 in. x 6 ft.) weighing approximately nine pounds and traveling at 34mph. This simulates
wind-borne debris striking the fan.
Greenheck has gone the extra mile and worked with Miami-Dade County to design a High Velocity

Miami-Dade County Hurricane Zone standard for rooftop fans. The SFD, SFB and SWB Series 100 and 200 models are
certified and approved by the Miami-Dade Building Code Compliance office and Texas Department of
Test Protocols
Insurance for use in hurricane zones.

Miami-Dade NOA
Numbers

The certifications can be viewed on the Miami-Dade County website under the NOA numbers listed below.
Models SFD, SFB and SWB Series 100 and 200 are the first upblast aluminum/steel fans in the industry
that have received a Miami-Dade NOA for high wind (150 mph) and hurricane zones.
SFD, SFB and SWB Series 100 and 200: 09-0303.31

Texas Department
of Insurance

The certifications can be viewed on the Texas Department of Insurance Windstorm website under
TDInumberRV-71.
Structural calculations performed by a state licensed Professional Engineer (P.E.) on models SFD, SFB

State Licensed P.E. and SWB Series 100 and 200 include Finite Element Analysis (FEA) and a stamped P.E. report of the fans
compliance to ASCE 7-05 Minimum Design Loads for Buildings and Other Structures Standard and the
Calculations
Florida Building Code. The ASCE 7-05 Standard meets the IBC, Florida and Miami-Dade County codes.

Certified
Independent
Third-Party Testing

Each of the Greenheck models have been subjected to extensive testing procedures. The SFD, SFB and
SWB Series 100 and 200 have been certified by an independent third-party to the ASTM E-330 Static
Pressure Difference Standard, Florida Building Code Test Protocols TAS-202 Static Pressure Difference
and TAS-201 Large Missile Impact. All tests are video taped for documentation of test method and results.

Computational
Fluid Dynamics
(CFD)

All Greenheck high wind models have been analyzed using Computational Fluid Dynamics (CFD). CFD is
computer software designed to simulate the flow of high speed winds over the surface of objects. The
software records the force profile exerted on the fan so it can be utilized in Finite Element Analysis (FEA).

Finite Element
Analysis (FEA)

Utilizing the results from CFD analysis Greenheck can accurately predict the stress, strain, and deflection
resulting from high wind loads. Greenheck high wind units have been proven to withstand high winds
through Finite Element Analysis utilizing CFD results.

Applications
Seismic and Spark-Resistance

Seismic - SFD, SFB


and SWB Series 100 and 200

With changes in building codes and standards more equipment is being


required to be seismically certied in areas of the country not commonly
thought of as being in seismically active zones.
The International Building Code (IBC) is designed to provide model code
regulations that safeguard public health and safety in all U.S. communities.
IBC 2009 and 2012 are the latest versions adopted on state or local levels.
With this code, the standards are intended to improve the performance and
design of non-structural systems subject to seismic events.
The State of California, one of the most active seismic areas in the United
States, has the Ofce of Statewide Health Planning and
Development
(OSHPD). OSHPD regulates the design
Dev
and
an construction of healthcare facilities to ensure
they
are safe and capable of providing services to
t
the
t public after a seismic event. OSHPD developed
their
own unique certication process to incorporate
t
the
t IBC and ASCE testing standards to ensure
equipment
remains operable after a seismic event.
e

Protocols designed for seismic standards:


Seismic
Testing Criteria

All Greenheck seismically certified models have been tested using the most severe seismic event that is
found on the Spectral Response Map per IBC Figures 1613.5 (1-2). Because our testing is performed under
the worst case scenario, using the highest mapped seismic load, highest level occupancy category, worst
case site class, and highest code mandated importance factor, it allows Greenheck seismically certified
fans to be used anywhere in the United States under any conditions.

California OSHPD
Test Protocols

The California Office of Statewide Health Planning and Development (OSHPD) requires all certified models
be shake table tested in accordance with ICC ES AC-156, in which the fans are physically subjected
to the same or greater forces than they will see during a seismic event. Subjecting Greenheck model
SFD, SFB and SWB Series 100 and 200 fans to this type of testing ensures the fans will operate without
problems after a seismic event.

OSHPD Certification
No. 0113-10

The OSHPD certification numbers and supporting documents can be viewed on OSHPDs
website and ensures that the fan has been subjected to and passed rigorous testing standards.

State Licensed
P.E. Calculations

When using the fans in applications which are not covered by California OSHPD standards Greenheck
models SFD, SFB and SWB Series 100 and 200 have been certified by a third-party engineering firm to
IBC 2009, 2012 and ASCE 7-05 standards. These engineers hold professional engineers (PE) licenses in
all 50 states so no matter where your job is located you are backed by a PE signature for your state.

Certified
Independent
Third-Party Testing

All Greenheck Seismically Certified Fan models have gone through extensive testing procedures.
Greenheck models SFD, SFB and SWB Series 100 and 200 have been certified to IBC 2009, 2012, ASCE
7-05 and California OSHPD standards through both engineering calculations and shake table testing of all
models by independent third-party engineering firms.

Spark-Resistant Construction
The following AMCA Standards apply to fan
applications that may involve the handling of potentially
explosive or flammable particles, fumes or vapors.
Models SFB, SWD and SWB are available with spark
resistant construction options that meet the intent of
these AMCA Standards.
AMCA Type A - All parts in contact with the airstream
are constructed of nonferrous material (aluminum).
Models SFB, SWD and SWB do not meet AMCA
Type A spark resistant construction because the
fan shaft is steel.
AMCA Type B - The fan wheel is constructed
of nonferrous material (aluminum). A nonferrous

(aluminum) rub ring surrounds the fan shaft where it


passes through the fan housing. Available on models
SWD and SWB Series 200 and 300.
AMCA Type C - The inlet cone is constructed
of nonferrous material (aluminum). A nonferrous
(aluminum) rub ring surrounds the fan shaft where it
passes through the fan housing.
The constructions listed minimize the potential of
ferrous components making contact with each other
that may produce sparks. However, they do not
guarantee against the potential of producing sparks.
The installer must electrically ground all fan and system
components.

Applications
Emergency Smoke Control
Temperature Options
Testing
High temperature testing was
conducted at Greenhecks
Research and Development
facility with airstream
temperatures in excess of
1000F (538C). Temperatures
were monitored at the following
critical locations throughout
the tests: bearings, bearing
compartment, motor, motor
compartment, airstream and
fan housing.
Continuous Operating Temperatures
Utility fans are suitable for applications with elevated
temperature airstreams. Refer to the chart at the right
for continuous operating temperature guidelines and
optional accessories.
High Temperature/Emergency Smoke Control
The SWB Series 200 sizes 212 to 224 and Series
300 may be equipped for emergency smoke removal
applications by specifying a high temperature option.
The table below right indicates the construction
features included in the high temperature options
enabling exhaust of heat and smoke at 500F (260C)
for a minimum of 4 hours or 1000F (538C) for a
minimum of 15 minutes.
Temperature ratings for both high temperature
options were tested in accordance to UL smoke
control systems.

Options and Accessories


Wiring Pigtail - Allows direct hookup to the power
supply eliminating field wiring to the fan.
Disconnect Switches
A wide selection of
NEMA rated switches
are available for positive
electrical shutoff and
safety, including: dusttight, rainproof and
corrosion-resistant.

10

SWB
SWB
SWB
SWD
Series
Series
Series SFD, SFB
Continuous
100
200
300
Operating
Temperatures Galvanized,
and
Painted
Painted Aluminum Steel SFD SFB
Construction Steel or Galvanized Steel
Airstream
Aluminum
-20 to 200F
(-29 to 93C)

Standard
201 to 300F

(94 to 149C)

Heat Slinger/
Shaft Seal
301 to 400F

(149 to 204C)

Heat Slinger/
Shaft Seal

9 9

The maximum continuous operating temperature on the SWB is 400F.


For continuous operating temperatures between 401 and 1000F use an
Arrangement 1, 9 or 10, backward-inclined centrifugal fan model BISW.
High Temperature SWB Features
Series 200 & 300
Steel Construction
Shaft Seal
Heat Slinger

High
Temperature
Option

High
Temperature
Option with UL

9
9
9

9
9
9
9
9

Weatherhood
UL Label (Power ventilators for smoke
control systems)

Testing for Emergency Smoke Temperature and Time Guidelines


Time
Code
Class
Tested Temperature
(Hours)
IRI
500F (260C)
4.00
SBCCI

1000F (538C)

0.25

BSI

Class A

302F (150C)

5.00

BSI

Class B

482F (250C)

2.00

BSI

Class C

572F (300C)

0.50

BSI

Class D

572F (300C)

1.00

BSI

Class E

752F (400C)

2.00

MOTOR STARTERS
The fundamental function of a motor starter is to
protect the motor from damage that can occur from
overheating. With a Greenheck motor starter, you will be
provided with the best motor protection available.
Specic model components may include;
SmartStart technology, physical interface, overload
protection, disconnect, magnetic contactor,
NEMA-1,
NEMA-3R, NEMA-4 and
N
NEMA-4X steel enclosures and
pre-engineered easy system
integration. For complete
information on specic
Greenheck Motor Starter
models refer to greenheck.com,
Products, Motor Starter page.

Options and Accessories

UL/cUL 762 - SWB Series 200


and 300 models are listed for
grease removal (UL/cUL 762).
The UL/cUL 762 option includes
a weatherhood, threaded drain
connection and access door.
Indoor mounting requires
the fan to have welded scroll
construction.
Weatherhood - Available to completely cover the motor
and drive compartments; protecting the shaft, bearings,
motor and drive components from moisture and other
adverse weather conditions. Weatherhoods are vented
to provide sufficient motor cooling, designed to meet
OSHA guidelines and are easily removed for service
access. Series 300 includes an access door.
Drain Connection - Threaded drain connections can
be provided to drain moisture from the bottom of the
fan housing.
Grease Trap (SWB Only) - Aluminum trap is designed
to collect grease residue and avoid drainage onto roof
surface. Disposable grease absorbents are available for
easy maintenance.
Access Doors - Access doors provide access for
inspection and cleaning. Either bolted or hinged, quick
opening access doors are available on all models
except SFD. (Series 100bolted option only)
Welded Scroll Construction - Welded scroll
construction is available on SWD and SWB Series
200 and 300.
Aluminum Construction - Aluminum airstream option is
available on SWD and SWB Series 200.
Dampers - Gravity or motorized
parallel blade backdraft dampers
feature sturdy galvanized frames
with prepunched mounting holes,
aluminum blades with felt edges
and balanced design for minimal
resistance to airflow. Backdraft
dampers are not suitable for downblast or bottom
angular downblast discharge positions. The fan must
be supplied with a flanged outlet to install a backdraft
damper directly to the fan. Heavy-duty dampers are
available for high pressure applications on fans with
motors equal to or greater than 7 horsepower.
Extended Lube Lines - Lubrication lines with grease
fittings are extended from shaft bearings to the base
of the drive frame panel or weatherhood for easy
bearing lubrication.
Inlet box and Curb Cap - Used to minimize entry losses
when a 90 turn is required at the fan inlet. Available on
SWB Series 200.

Inlet and Outlet Guards - Constructed


of punched sheet metal or expanded
metal mounted in a steel frame to provide
protection for non-ducted installations.
The guards can be easily removed for fan
maintenance or inspection.
Flanged Inlet and Outlet - Flanges are available for
damper mounting or flanged duct connections. Inlet
flanges have prepunched mounting holes. Outlet
flanges are bolted on standard; welded for UL 762
applications
Companion Flange - Connects to the inlet flange and
then attaches to the ductwork. Recommended for slipfit duct connections.
External Inlet Vane Dampers (SWB and
SWD) - Available on model SWB fans,
sizes 112124 and 212224 and SWD
fans sizes 13-18. External vanes are
mounted on the inlet flange. Inlet vane
dampers feature zinc-plated steel
blade axles, stainless steel washers
and bearings. Vanes can be used for either manual or
automatic operation, with controls furnished by others.
Maximum operating temperature is 200F (93C).
Coatings - A wide variety of coatings and colors are
available for decorative to acidic applications on SFB,
SWD and SWB Series 200 and 300. All Greenheck
coatings can be found in the Performance Coatings for
Commercial and Industrial Fans publication.
Permatector is our standard coating. Typically
used for applications that require corrosion
resistance in indoor and outdoor environments.
Hi-Pro Polyester is resistant to salt water,
chemical fumes and moisture in more corrosive
atmospheres. Typically used for applications
requiring superior chemical resistance, excellent
abrasion and outdoor UV protection. This coating
exceeds protective qualities of Air Dried Heresite
and Air Dry Phenolic.
Baked Enamel Decorative Coatings are heat
cured enamels applied as electrostatic powders.
Customers can choose from 16 standard
decorative colors or color match any color.
Heat Slinger and/or Shaft Sealall belt models
and SWD - Heat slinger is an aluminum
cooling disc mounted on the fan shaft
between the inboard bearing and
the fan housing. The disc dissipates
heat conducted along the fan shaft.
The shaft seal with an aluminum rub
ring is available for applications where
contaminated or high temperature air is being handled.
11

Mounting Options

Vibration Isolators
Base-mounted neoprene or spring isolators are available to lessen mechanical vibration and assure quiet
operation. Free-standing, restrained and housed spring isolators are also available. Isolators are sized to
match the weight of each fan.

Free-Standing Open
Spring Mounts Type 3, 1-inch Deflection
Free-standing spring isolators
are unhoused laterally stable
steel springs. They provide a
minimum horizontal stiffness
of 0.8 times the rated vertical
stiffness and provide an additional 50% overload
capacity. These isolators are equipped with a topmounted adjusting bolt and an acoustical non-skid
base. Springs are color coded to indicate load capacity.

Rubber Mounts Type 2, -inch and


-inch Deflection
Neoprene mountings consist
of a steel top plate and base
plate completely embedded in
colored (oil-resistant) neoprene
for easy identification of
capacity. Neoprene mountings are furnished with a
tapped hole in the center. This enables the equipment
to be bolted securely to the rubber mount.

Restrained Spring
Mounts -

Housed Spring Mounts


Type 4B, 1-inch Deflection
Housed spring isolators consist
of steel springs assembled into
a telescoping housing with a
top-mounted adjusting bolt and
an acoustical non-skid base.
Housed spring isolators include
resilient inserts to prevent metalto-metal contact and provide snubbing for side loads.
Springs provide an additional 50% overload capacity
and are color coded to indicate load capacity.

Type 4A, 1-inch Deflection


Restrained spring isolators
consist of laterally stable, freestanding springs assembled
into a steel housing. These
assemblies are designed for
vertical and horizontal motion restraint. Restrained
spring isolators can be used for blocking during
equipment installation and are provided with leveling
bolts. Springs provide 50% overload capacity and are
color coded or identified to indicate load capacity.
Restrained spring mounts are recommended for
equipment subject to wind loading or large torquing
forces.

Direct Mount - Type A

Mounting Rails

No base required. Isolators


are attached directly to
equipment. Direct isolation
can be used if equipment
is unitary and rigid without
the use of additional
support. If there is
any doubt whether or
not equipment can be
supported directly on isolators,
use rails, bases or consult the factory.

with Isolators
Isolation mounting
rails are available with
either rubber mount,
free-standing open or
restrained spring isolators.
The isolators are mounted
between aluminum rails
that run the length of the
fan base. Isolation rails
provide easy installation on isolated
systems, and are ideal for applications
where there is a large overhung load.
Mounting rails are available
for fans up to size 36.

Equipment Supports
Models GESS and GESR equipment
supports are available for roof
mounting of utility fans up to size 36.
Equipment supports are available in
a number of lengths, widths, heights,
and can also be built for a pitched roof.
12

Typical Installations

General Clean Air


or Fume Hood
(NonGrease)

Flex

The SFD, SFB,


SWD and SWB
are designed for
applications ranging
from clean air to
contaminated air.
Typical installations
are shown below. Installations must
include a means for inspecting,
cleaning and servicing the exhaust fan.

Flex

3 Wheel
Diameters

SWB Commercial Kitchen (Grease)


Greenhecks SWB Series 200 and 300 are designed
to meet restaurant and foodservice applications.
These fans are UL and cUL Listed for grease removal
and have been tested under elevated temperature
conditions.
Due to high temperatures and grease-laden airstreams
in commercial kitchen ventilation, system designers
must be aware of governing codes and guidelines.
The National Fire Protection Association (NFPA) is
the primary source used by many local codes for
commercial kitchen ventilation systems. Local code
authorities should be consulted before proceeding with
any kitchen ventilation project.

selected. An outlet guard is strongly recommended


when the fan discharge is accessible. When an outlet
guard is not ordered with the fan, it must be provided
by the installer. An upblast discharge is recommended.
No dampers are to be used in the system.
The fan discharge must be a minimum of 40 inches
(1016 mm) above the roof line and the exhaust
duct must be fully welded to a minimum distance
of 18 inches (457 mm) above the roof surface.

Weatherhood

Inlet Box

Installation must include a means for inspecting,


cleaning and servicing the exhaust fan.
Fans selected for grease removal must include a
weatherhood, access door and 1-inch (25 mm) drain
connection. For grease applications where the fan is
mounted indoors, the welded scroll option must be

Curb Cap

Inlet box and curb cap are used when space is limited and a
90 turn is required less than 3 wheel diameters from the inlet.

Upblast Discharge
Optional
Companion
Flange

**40 in.
(1016 mm)

Weatherhood
3 Wheel
Diameters
*18 in.
(457 mm)

** Per NFPA 96 the fan discharge must be


a minumum distance of 40 in. (1016 mm)
above the roof surface.

Duct
From
Kitchen
Hood

SWB Series 200 and 300 models


are listed for grease removal (UL/
cUL 762).
File no. MH11745

*Per NFPA 96 the duct must


be all welded construction
to a minumum distance of
18 in. (457 mm) above the
roof surface.

13

SFD, SFB and SWD Discharge


Positions and Dimensional Data
CW BAU
B

CCW BAU

SFD Dimensions

Unit Size
D

A
H

CW UB
I

CCW UB
G

B
8716

(27)

(214)

SFD-7.5

114

1014

(32)

(260)

(173)

SFD-9

1516

111316

(33)

(300)

SFD-10

11516

14

914

(49)

(356)

(235)

SFB-9

D
A

SFB-10
SFB-12
SFB-15

CCW TH

CW TH
F

SFB-18

SFB-20
SFB-22
SFB-25

CCW TAD

CW TAD
C

SFB-27

E
612

F
6116

G
5316

H
9

I
7

J
514

(141)

(121)

(165)

(154)

(132)

(230)

(178)

(133)

61316

51316

734

714

614

923

812

634

(148)

(197)

(184)

(159)

(245)

(216)

(171)

734

612

81516

8516

7316

1079

912

712

(197)

(165)

(227)

(211)

(183)

(274)

(241)

(191)

71316

1034

10116

812

1234

1112

812

(198)

(273)

(256)

(216)

(324)

(292)

(216)

F
81516

G
758

H
1345

I
1014

J
8
(203)

SFB-30

A
138

B
121116

C
814

D
7

E
912

(35)

(322)

(210)

(178)

(241)

(227)

(194)

(350)

(260)

1716

1412

9516

71316

1034

10116

8916

1516

1112

914

(37)

(368)

(237)

(198)

(273)

(256)

(217)

(385)

(292)

(235)

214

16

101116

9116

1238

11916

978

1516

1314

934

(57)

(406)

(271)

(230)

(314)

(294)

(251)

(385)

(337)

(248)

21116

17916

111316

91516

131116

121116

1078

1634

1458

1058

(68)

(446)

(300)

(252)

(348)

(322)

(276)

(426)

(371)

(270)

4116

2338

151316

1314

18516

1718

1458

2213

1958

1334

(103)

(594)

(402)

(337)

(465)

(435)

(371)

(567)

(498)

(349)

4916

2512

1714

1412

20116

1834

16116

2449

2112

1478

(116)

(648)

(438)

(368)

(510)

(476)

(408)

(621)

(546)

(378)

5516

28

19116

16

2218

2034

171116

2849

2334

16

(135)

(711)

(484)

(406)

(562)

(527)

(449)

(723)

(603)

(406)

6116

301116

21116

1734

24716

2278

19916

3135

2614

1712

(154)

(779)

(535)

(451)

(621)

(581)

(497)

(803)

(667)

(445)

34

22

19

2612

2412

2078

33

2834

1878

(127)

(864)

(559)

(483)

(673)

(622)

(530)

(838)

(730)

(479)

658

3818

25

2118

29

2714

2314

3635

3158

21

(168)

(968)

(635)

(537)

(737)

(692)

(591)

(930)

(803)

(533)

All dimensions in inches (millimeters).

A
H

CW DB
G

SWD Dimensions

CCW DB
I

Unit Size

SWD-7

11516

1418

71316

1034

1018

858

1518

1112

858

(49)

(359)

(235)

(198)

(273)

(257)

(219)

(384)

(292)

(219)

SWD-8

15

1 16

14 8

9 4

13

7 16

10 4

10 8

8 8

15 8

11 2

858

(49)

(359)

(235)

(198)

(273)

(257)

(219)

(384)

(292)

(219)

SWD-10

11516

1418

914

71316

1034

1518

1112

858

(359)

(198)

(273)

1018
(257)

858

(49)

(219)

(384)

(292)

(219)

SWD-13

21116
(68)

1758

1134

978

1358

1234

1078

1658

1458

1058

(448)

(298)

(251)

(346)

(324)

(276)

(422)

(371)

(270)

SWD-15

318

1912

13116

11

1518

1418

1218

1812

1614

1158

(79)

(495)

(332)

(279)

(384)

(359)

(308)

(470)

(413)

(295)

SWD-16

312

2114

14515

12

16916

1512

1314

2038

1734

1212

(89)

(540)

(364)

(305)

(406)

(394)

(337)

(518)

(451)

(318)

SWD-18

4116

2338

151316

1314

18516

1718

1458

2238

1958

1334

(103)

(594)

(402)

(337)

(465)

(435)

(371)

(568)

(498)

(349)

CW BAD
D

CCW BAD
E

CW BH
J

(235)

All dimensions in inches (millimeters).

CCW BH
J

Images are viewed from the drive side of fan.

14

D
434

SFB Dimensions

CCW TAU

D
A

C
5916

All dimensions in inches (millimeters).

Unit Size

CW TAU
E

SFD-6

A
1116

SWB Discharge
Positions and Dimensional Data
CW BAU
B

CCW BAU

SWB Dimensions

Size

106

11516

1418

914

71316

1034

1018

858

1518

1112

858

(49)

(359)

(235)

(198)

(273)

(257)

(219)

(384)

(292)

(219)

107

15

1 16

14 8

13

7 16

10 4

10 8

8 8

15 8

11 2

858

(49)

(359)

(235)

(198)

(273)

(257)

(219)

(384)

(292)

(219)

108

11516

1418

914

71316

1034

1018

858

1518

1112

858

(49)

(359)

(235)

(198)

(273)

(257)

(219)

(384)

(292)

(219)

110

11516

1418

914

71316

1034

1518

1112

858

(359)

(198)

(273)

1018
(257)

858

(49)

(219)

(384)

(292)

(219)

113

21116
(68)

1758

1134

978

1358

1234

1078

1658

1458

1058

(448)

(298)

(251)

(346)

(324)

(276)

(422)

(371)

(270)

115

318

1912

13116

11

1518

1418

1218

1812

1614

1158

(79)

(495)

(332)

(279)

(384)

(359)

(308)

(470)

(413)

(295)

116

3 2

21 4

14 15

12

16 16

15 2

13 4

20 8

17 4

1212

(89)

(540)

(364)

(305)

(406)

(394)

(337)

(518)

(451)

(318)

118

4116

2338

151316

1314

18516

1718

1458

2238

1958

1334

(103)

(594)

(402)

(337)

(465)

(435)

(371)

(568)

(498)

(349)

120

4916

2512

1714

1412

20116

1834

1618

2412

2112

1478

(116)

(648)

(438)

(368)

(510)

(476)

(410)

(622)

(546)

(378)

124

13

5 16

15

30 16

21 16

17 4

24 16

22 8

19 16

31 2

26 4

1734

(402)

(786)

(535)

(451)

(621)

(581)

(497)

(800)

(667)

(451)

206

11516

1418

914

71316

1034

1018

858

1518

1112

858

(49)

(359)

(235)

(198)

(273)

(257)

(219)

(384)

(292)

(219)

207

11516

1418

914

71316

1034

1018

858

1518

1112

858

(49)

(359)

(235)

(198)

(257)

(219)

(384)

(292)

(219)

208

11516

1418

914

71316

1034

1018

858

1518

1112

858

(49)

(359)

(235)

(198)

(273)

(257)

(219)

(384)

(292)

(219)

210

11516

1418

914

71316

1034

1018

858

1518

1112

858

(49)

(359)

(235)

(198)

(273)

(257)

(219)

(384)

(292)

(219)

212

2516

1618

101116

1238

1158

91516

1518

1314

934

(59)

(410)

(271)

(229)

(314)

(295)

(252)

(384)

(337)

(248)

213

21116

1758

1134

978

1358

1234

1078

1658

1458

1058

(68)

(448)

(298)

(251)

(346)

(324)

(276)

(422)

(371)

(270)

215

3 8

19 2

13 16

11

15 8

14 8

12 8

18 2

16 4

1158

(79)

(495)

(332)

(279)

(384)

(359)

(308)

(470)

(413)

(295)

216

312

2114

14515

12

16916

1512

1314

2038

1734

1212

(89)

(540)

(364)

(305)

(406)

(394)

(337)

(518)

(451)

(318)

218

4116

2338

151316

1314

18516

1718

1458

2238

1958

1334

(103)

(594)

(402)

(337)

(465)

(435)

(371)

(568)

(498)

(349)

220

4916

2512

1714

1412

20116

1834

1618

2412

2112

1478

(116)

(648)

(438)

(368)

(510)

(476)

(410)

(622)

(546)

(378)

222

5316

28116

19116

16

2218

2058

171116

2834

2334

1614

(132)

(713)

(484)

(406)

(562)

(524)

(449)

(730)

(603)

(413)

224

13

5 16

15

30 16

21 16

17 4

24 16

22 8

19 16

31 2

26 4

1734

(402)

(786)

(535)

(451)

(621)

(581)

(497)

(800)

(667)

(451)

327

518

35

2314

1958

2678

25

2112

33

2834

2114

(130)

(889)

(591)

(498)

(683)

(635)

(546)

(838)

(730)

(540)

330

534

3838

2558

2158

2934

2758

2334

3658

3158

2318

(146)

(975)

(651)

(549)

(756)

(702)

(603)

(930)

(803)

(587)

333

634

4218

2838

231316

321316

30916

26116

40

34 916

(171)

(1070)

(721)

(605)

(833)

(776)

(662)

(1016)

(878)

336

71316

46516

31516

26516

36316

3334

281316

4412

3814

2714

(198)

(1176)

(795)

(668)

(919)

(857)

(732)

(1130)

(972)

(692)

340

878

5034

34716

281516

391516

37316

311116

47

42316

2958

(225)

(1289)

(875)

(735)

(1014)

(953)

(805)

(1194)

(1072)

(752)

344

1018

551316

38

311516

44116

41116

35

52

4658

32516

(257)

(1418)

(965)

(811)

(1119)

(1043)

(889)

(1321)

(1184)

(821)

349

11 8

61 16

41 16

35 8

48 16

45 8

38 16

57

51 16

35316

(289)

(1554)

(1062)

(892)

(1230)

(1146)

(976)

(1448)

(1303)

(894)

A
H

CW UB
I

CCW UB
G

(235)

CW TAU
E

CCW TAU

D
A

D
A

CCW TH

CW TH
F

CCW TAD

CW TAD
C

A
H

CW DB
G

CCW DB
I

CW BAD
D

CCW BAD
E

(273)

CW BH
J

25

(635)

CCW BH
F

Images are viewed from the drive side of fan.

13

All dimensions in inches (millimeters).

15

Engineering Data

Selection

Effects of Installation on Performance

The first consideration in any fan selection


is the amount of air to be moved and the
resistance to this air movement. Air volume
requirements are established through specific
codes or accepted industry standards. Once
the air volume is known, system resistance
can be determined by summing up the
losses through the system components.
Duct layout, duct size, coils, filters, dampers,
and fan accessories all affect system
resistance. ASHRAE Guide and Data Books
and manufacturers data on individual
system components are common sources of
information available to the system designer.

Fan ratings presented in the performance tables and curves


of this catalog are in accordance with AMCA Standard 210
Laboratory Methods of Testing Fans for Aerodynamic
Performance Rating. The AMCA test procedure utilizes an open
inlet and a straight outlet duct to assure maximum static regain.

In most applications, several fans may meet


the required airflow and system resistance
conditions. An optimum fan selection requires
evaluation of alternative fan types and fan
sizes, as they relate to initial cost, operating
cost, available space, and allowable sound
levels. The relative importance of these facts
varies with each system.

Any installation with inlet or discharge configurations that deviate


from this standard may result in reduced fan performance.
Restricted or unstable flow at the fan inlet can cause pre rotation
of incoming air or uneven loading of the fan wheel yielding large
system losses and increased sound levels. Free discharge or
turbulent flow in the discharge ductwork will also result in
system effect losses.
The examples below show system layouts and inlet and
discharge configurations which can affect fan performance.

7 MAX.

POOR

GOOD

FAIR

Two types of wheels are available:


1. Backward-inclined or airfoil wheels turn
at twice the speed of forward-curved fans
and feature:
Higher operating efficiencies
A non-overloading horsepower curve
which reaches a peak
near the middle of the normal operation
range
Stronger wheel design allowing for
operation at higher static pressures
2. Forward-curved wheels typically have
lower performance capabilities compared
to the backward inclined and contain:

FAIR

POOR

POOR

One
Impeller
Dia.

Turning
Varies

Should be at least
1/2 Impeller Dia.

POOR

FAIR

GOOD

POOR

FAIR

GOOD

Overloading type wheel (meaning that


changes in performance can result in
significant brake horsepower changes)
Forward-curved wheels have lower
sound levels
Comprehensive air performance data for these
utility fans can be found in the fan tables and
fan curves section, starting on page 18.

Not Greater than


o
60 Including Angle

POOR

16

POOR

FAIR

SFD and SWD Direct Drive

Model SWD (7 -10)


M

Model SFD

Model SWD (13 - 18)

N
N

P
P

BB

AA

K
K
C
C

JJ

L
D

E
E

E
E

LL
H

G
G
F
F

D
D

DIMENSIONAL DATA
Model
SFD
6
7.5
9
10
SWD

738

514

16

11

5/8

141116

8316

1116

9116

114

7/8

1114

5316

(187)

(133)

(406)

(279)

(16)

(373)

(208)

(27)

(230)

(152)

(32)

(22)

(286)

(132)

514

18116

1214

5/8

14516

818

1116

958

114

118

131116

638

(229)

(133)

(459)

(311)

(16)

(364)

(206)

(27)

(244)

(203

(32)

(29)

(348)

(162)

1018

614

20516

1334

5/8

1778

1038

1116

1034

10

114

138

151316

7716

(257)

(159)

(516)

(349)

(16)

(454)

(264)

(27)

(273)

(254)

(32)

(35)

(402)

(189)

1218

634

24516

1614

9/16

1938

1138

1116

1234

12

114

138

1858

812

(308)

(171)

(618)

(413)

(14)

(492)

(289)

(27)

(324)

(305)

(32)

(35)

(473)

(216)

11

9 4

23 4

21 4

12 8

11 4

8 8

11 2

16 8

16

10 8

26 58

(279)

(51)

(248)

(591)

(552)

(308)

(286)

(219)

(292)

(429)

(406)

(257)

(676)

11

9 34

23 14

21 34

12 18

11 14

8 58

11 12

16 78

16

10 18

26 58

(279)

(51)

(248)

(591)

(552)

(308)

(286)

(219)

(292)

(429)

(406)

(257)

(676)

10

11

9 34

23 14

21 34

12 18

11 14

8 58

11 12

16 78

16

10 18

26 58

(279)

(51)

(248)

(591)

(552)

(308)

(286)

(219)

(292)

(429)

(406)

(257)

(676)

13

14

10 58

25 34

23 14

13 34

14 18

10 58

14 12

19 38

17 58

12 34

31 14

(356)

(51)

(270)

(654)

(591)

(349)

(359)

(270)

(369)

(492)

(448)

(324)

(794)

15 78

11 58

27

24 12

13 34

15 58

11 58

16 78

21 18

19 12

14 18

34 34

(403)

(51)

(295)

(686)

(622)

(349)

(397)

(295)

(429)

(537)

(495)

(359)

(883)

17 12

12 34

28

25 12

13 34

17 38

12 12

18 18

22 38

20 58

15 12

38 18

15
16
18

(445)

(51)

(324)

(713)

(648)

(349)

(441)

(318)

(461)

(568)

(524)

(394)

(969)

19 14

14 18

29 12

26 78

13 34

19 516

13 34

19 78

22 38

22 58

17 18

42

(489)

(51)

(359)

(750)

(683)

(349)

(491)

(349)

(505)

(568)

(575)

(435)

(1067)

Max. Motor *Unit


Frame Size Weight
30
56
(14)

56
145T
184T

40
(18)

75
(34)

113
(51)

69

(31)

(31)

(31)

(44)

69
69
96
123
(56)

133

(60)

147

(67)

All dimensions in inches (millimeters). Weight given in pounds (kilograms)

17

SFD - Direct Drive


Model Number Code
The model number code is designed to completely identify the fan. The correct code letters must be specified to
designate the correct construction. The remainder of the model number is determined by the size and performance.

SW

10 -

AF

CW

Drive

Fan Size

Wheel Rotation

Discharge Position

B - Belt
D - Direct

06 through 49

CW - Clockwise
CCW - Counterclockwise

UB
TAU
TH
TAD
DB
BAD
BH
BAU

Airfoil Wheel
AF - (backward inclined
wheel is standard)

Wheel Type
SW - Backward-Incline
SF - Forward-Curved

SFD dimensional
drawings found on
page 17.

Series (SWB Only)

Motor HP

100 - Galvanized Construction


200 - PermatectorTM Coated
Steel Construction
300 - Galvanized and Permatector
Coated Steel Construction

4 = 1/4
3 = 1/3
5 = 1/2
7 = 3/4
10 = 1

Motor RPM
A = 1725
B = 1140
C = 860

Model SFD
Direct Drive

Motor
HP

6B

6B

1/4

1725

1/6

1140

1/2

1725

VG

7.5

1/2
5A

10

1140

1/4
4A

1/6

4C

1/4

860

5B

1/2

1140

15A

1 12

1725

3C

1/3

860

7B

3/4

1140

30A

1725

CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones

15
20
30
50
75

=
=
=
=
=

112
2
3
5
712

100
150
200
300
400

=
=
=
=
=

(Direct Drive only)

D = 1550
E = 1050
G = 1300
VG = Vari-Green

Fan
RPM

VG

TH

0.125
407
0.06
6.7
667
0.24
13.6
672
0.16
10.6
1062
0.59
20
839
0.18
9.2
1159
0.46
16.1
1806
1.64
31
1259
0.36
12.3
1713
0.86
19.4
2641
3.03
39

0.25
338
0.05
6.0
628
0.22
12.8
612
0.14
9.8
1028
0.56
18.6
748
0.15
7.8
1097
0.42
14.9
1765
1.59
29
1176
0.32
11.3
1653
0.82
18.5
2603
2.98
37

International
(See CAPS for performance)
K = 950 RPM J = 1475 RPM

0.375
232
0.03
4.7
585
0.20
12.3
549
0.13
9.4
988
0.53
16.8
645
0.12
7.0
1028
0.38
14.3
1725
1.54
28
1085
0.29
10.0
1592
0.77
17.6
2564
2.93
36

10
15
20
30
40

Model SFD
6
7.5
9
10

Static Pressure in Inches wg


0.5
0.75
1
1.25

541
0.17
11.7
467
0.10
8.6
949
0.50
15.8
487
0.09
6.6
957
0.34
13.6
1683
1.48
27
965
0.25
9.2
1528
0.72
17.0
2525
2.87
35

Upblast
Top Angular Upblast
Top Horizontal
Top Angular Downblast
Downblast
Backward Angular Downblast
Backward Horizontal
Backward Angular Upblast

Wheel Diameter
6-5/16 (160)
7-2/3 (195)
9-1/8 (232)
10-3/4 (273)
1.5

Outlet Area
0.27 (0.03)
0.33 (0.03)
0.44 (0.04)
0.57 (0.05)
2.5

424
0.13
10.5

869
0.46
14.1

775
0.38
12.7

636
0.30
11.3

782
0.26
12.3
1595
1.36
25

1502
1.24
22

1407
1.13
21

1298
1.01
21

989
0.70
19.3

1378
0.64
15.7
2444
2.73
33

1163
0.52
13.9
2362
2.60
31

2275
2.44
30

2179
2.32
29

1942
2.01
27

1621
1.62
25

Performance certified is for installation Type B - Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified
Ratings Seal applies to air performance only.

18

SWD - Vari-Green

Model SWD Wheel Diameter


7
11-3/8 (289)
8
11-3/8 (289)
10
11-3/8 (289)
13
13-1/2 (343)
15
14-3/4 (375)
16
17 (432)
18
19 (483)

SWD dimensional
drawings found on
page 17.

Model
VG
SWD Motor HP

Fan
RPM

1/4

1725

1/2

2500

1/4

1725

1/2

2500

1/4

1725

3/4

2200

1/4

1200

1/2

1550

3/4

1725

1/2

1150

3/4

1400

1725

3/4

900

1300

1725

3/4

850

950

1300

10

13

15

16

18

CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones

0.25
535
0.16
12.4
802
0.49
23
713
0.14
10.5
1092
0.4
17.6
1283
0.26
14.7
1691
0.54
21
1382
0.18
9.3
1874
0.38
13.6
2115
0.52
16
1905
0.28
10.5
2412
0.51
14
3053
0.93
19.5
2054
0.25
8.8
3173
0.72
16.1
4324
1.65
26
2880
0.39
9.8
3302
0.54
11.9
4734
1.37
20

0.5
493
0.17
11.6
778
0.5
22
630
0.15
10.2
1039
0.42
17.4
1168
0.27
13.6
1602
0.55
19.7
1191
0.19
8.9
1739
0.39
13
1995
0.53
15.6
1671
0.29
9.9
2224
0.51
13.2
2896
0.95
19
1754
0.26
8
2983
0.75
15.3
4176
1.7
24
2510
0.4
9
2964
0.55
11
4487
1.39
19.7

0.75
437
0.17
10.8
750
0.51
22
534
0.15
9.5
984
0.43
17.1
1047
0.27
12.7
1512
0.55
18.9
964
0.19
8.6
1591
0.41
12.3
1870
0.55
14.9
1416
0.29
9.2
2027
0.52
12.5
2746
0.96
18.2
1394
0.26
7
2795
0.77
14.6
4033
1.73
24
2060
0.39
8.2
2631
0.56
10.1
4240
1.41
19.2

Static Pressure in Inches wg


1
1.25
1.5
1.75
380
308
0.17
0.17
11.1
10.6
721
689
648
603
0.51
0.52
0.52
0.52
21
21
20
19.8
405
0.15
9
926
864
796
716
0.45
0.45
0.46
0.45
16.6
16.2
15.5
14.8
921
785
0.27
0.27
12
11.5
1422
1324
1226
1123
0.56
0.56
0.56
0.56
18.2
17.4
16.6
15.5

Outlet Area
0.76 (0.07)
0.76 (0.07)
0.76 (0.07)
1.03 (0.10)
1.25 (0.12)
1.52 (0.14)
1.87 (0.17)

2.25

2.5

566
0.52
19.3

523
0.52
18.8

477
0.52
18.2

625
0.45
14.2

520
0.46
14

1018
0.55
14.6

882
0.55
14.9

1427
0.41
11.5
1731
0.56
14.2

1246
0.4
11
1581
0.57
13.6

1419
0.56
12.9

1230
0.54
12.5

1818
0.52
11.8
2592
0.97
17.5

1605
0.52
11.2
2422
0.98
16.8

2252
0.98
16

2080
0.97
15.2

1906
0.96
14.7

2573
0.79
13.8
3890
1.76
23

2328
0.79
13.1
3748
1.79
22

2078
0.78
12.6
3593
1.82
21

3422
1.85
21

3241
1.85
20

2162
0.54
9.6
3994
1.43
18.4

3765
1.44
17.6

3496
1.43
17

3157
1.4
16.6

3052
1.84
19.7

2863
1.83
18.9

Performance certified is for installation Type B - Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified
Ratings Seal applies to air performance only.

19

SFB-9 - Belt Drive

1678
1512

658

(394)

(168)

1014

1018

(260)

(257)

2
(51)
rve

8
(203)

24
(610)

10

1978

1334

(254)

(505)

left
o

1 8
5

f th
is s
yste
m cu

(429)

(41)

se
lec
t

to

the

(349)

11516

1312 (343)

no
t

(287)

14 4 (362)
1

20 (508)

Do

Wheel Diameter = 912 (241)


Shaft Diameter = 3/4 (19)
Outlet Area = 0.454 ft2 (0.042 m2)
^Approximate Unit Weight = 120 lb. (54 kg)

cfm

All dimensions in inches (millimeters)


For additional discharge positions see page 14
^Weight shown is largest cataloged Open Drip Proof motor

Maximum BHP at given RPM = (RPM/1747)3


(Maximum KW at a given RPM = (RPM/1926)3)

Maximum RPM = 2000 and Minimum RPM = 450


Tip Speed (ft/min.) = RPM x 2.49
(Tip Speed (m/s) = RPM x 0.0126)

SFB-9
CFM

Maximum Motor Frame Size = 145T


OV

360

792

460

1013

560

1233

660

1453

760

1674

860

1894

960

2114

1060

2334

1260

2775

1360

2995

1460

3215

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
644
0.03
6.3
681
0.05
6.8
728
0.07
7.5
780
0.09
8.5
838
0.13
9.8
909
0.17
11.1
983
0.23
11.1
1059
0.30
12.0
1216
0.48
14.2
1297
0.59
15.7
1378
0.71
17.3

0.5

0.75

891
0.08
11.0
930
0.11
10.8
966
0.14
10.7
1013
0.18
10.6
1064
0.23
10.9
1118
0.28
11.5
1174
0.35
12.2
1318
0.54
14.3
1392
0.66
15.7
1468
0.79
17.2

1090
0.15
10.1
1129
0.18
10.3
1166
0.23
10.7
1207
0.28
11.1
1256
0.34
11.8
1306
0.42
12.6
1417
0.61
14.6
1482
0.72
16.1
1554
0.86
17.6

1225
0.19
10.3
1264
0.23
10.6
1303
0.28
11.0
1340
0.34
11.4
1378
0.40
12.1
1426
0.49
13.2
1528
0.69
15.7
1583
0.81
17.0
1639
0.94
18.3

Static Pressure in Inches wg


1.25
1.5
1.75

1382
0.28
11.0
1422
0.34
11.8
1461
0.40
12.6
1498
0.47
13.4
1534
0.55
14.3
1631
0.77
16.8
1682
0.89
18.1
1736
1.03
19.6

1528
0.39
13.2
1568
0.46
14.0
1608
0.54
14.9
1644
0.63
15.8
1728
0.84
18.1
1777
0.98
19.5
1827
1.13
21

1628
0.44
14.5
1667
0.52
15.4
1706
0.61
16.4
1745
0.71
17.5
1818
0.92
19.5
1866
1.06
21
1915
1.22
22

2.25

1758
0.58
17.0
1798
0.68
18.0
1837
0.78
19.1
1911
1.01
21
1949
1.14
22
1998
1.31
24

1845
0.64
18.6
1883
0.75
19.7
1923
0.86
21
1999
1.10
23

2.5

1965
0.82
21

Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

20

SFB-10 - Belt Drive

1938

(492)

914

1112

1512

812

(394)

(216)

2
(51)
mc
urve

(235)

1134

(292)

2658

yste

(298)
(279)

2214
214

1518

of t
his
s

11

(676)

(565)

16 (406)

lec
t to

the

left

(57)

(384)

se

12 (305)
ot

2038 (518)
22 (559)

1678 (429)

Do

Wheel Diameter = 1058 (270)


Shaft Diameter = 3/4 (19)
Outlet Area = 0.705 ft2 (0.065 m2)
^Approximate Unit Weight = 130 lb. (59 kg)

cfm

All dimensions in inches (millimeters)


For additional discharge positions see page 14
^Weight shown is largest cataloged Open Drip Proof motor

Maximum BHP at given RPM = (RPM/1310)3


(Maximum KW at a given RPM = (RPM/1444)3)

Maximum RPM = 1650 and Minimum RPM = 400


Tip Speed (ft/min.) = RPM x 2.78
(Tip Speed (m/s) = RPM x 0.0141)

SFB-10
CFM

Maximum Motor Frame Size = 145T

OV

600

851

790

1121

980

1390

1170

1660

1360

1930

1550

2199

1740

2469

1930

2739

2120

3008

2310

3278

2500

3548

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
526
0.05
5.6
575
0.08
6.2
633
0.13
7.1
693
0.19
8.3
760
0.27
9.9
828
0.37
11.1
898
0.50
11.4
973
0.66
12.4
1050
0.85
13.8
1128
1.08
15.3
1207
1.36
17.1

0.5

0.75

730
0.12
9.1
777
0.18
10.3
828
0.25
10.7
887
0.35
10.7
946
0.46
11.0
1009
0.60
11.7
1077
0.77
12.7
1145
0.97
13.9
1214
1.21
15.2
1285
1.48
16.9

897
0.23
10.3
944
0.32
10.3
994
0.42
10.7
1049
0.54
11.3
1109
0.70
12.1
1169
0.87
13.0
1232
1.09
14.1
1299
1.34
15.6
1368
1.63
17.4

1013
0.30
10.2
1045
0.38
10.6
1092
0.50
11.0
1142
0.63
11.6
1196
0.79
12.4
1256
0.99
13.6
1316
1.21
15.0
1376
1.46
16.5
1441
1.76
18.3

Static Pressure in Inches wg


1.25
1.5
1.75

1144
0.45
10.9
1181
0.57
11.3
1229
0.73
12.0
1279
0.89
13.1
1332
1.08
14.5
1393
1.33
16.0
1452
1.59
17.6
1512
1.90
19.4

1263
0.64
12.0
1309
0.81
13.0
1357
1.00
14.2
1407
1.20
15.6
1461
1.43
17.1
1522
1.72
18.8
1581
2.04
21

1349
0.73
13.3
1383
0.89
14.2
1430
1.09
15.5
1479
1.32
16.8
1529
1.56
18.3
1585
1.84
20
1645
2.18
22

1430
0.81
14.7
1456
0.97
15.5
1499
1.18
16.8
1546
1.43
18.1
1596
1.69
19.8
1647
1.97
22

2.25

2.5

1531
1.02
17.0
1564
1.27
18.1
1611
1.53
19.8

1603
1.17
18.7
1629
1.37
19.9

Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

21

SFB-12 - Belt Drive


2138
(543)

934

1314

1512

(394)

(229)

2
(51)
mc
urve

(248)

1358

(337)

2838

yste

(346)

13
(330)

2214
112

1518

of t
his
s

(721)

(565)

(38)

16 (406)

lec
t to

the

left

(384)

12 (305)
ot

se

2078 (530)
2212 (572)

1678 (429)

Do

Wheel Diameter = 1258 (321)


Shaft Diameter = 3/4 (19)
Outlet Area = 0.856 ft2 (0.08 m2)
^Approximate Unit Weight = 147 lb. (67 kg)

cfm

All dimensions in inches (millimeters)


For additional discharge positions see page 14
^Weight shown is largest cataloged Open Drip Proof motor

Maximum BHP at given RPM = (RPM/1111)3


(Maximum KW at a given RPM = (RPM/1225)3)

Maximum RPM = 1400 and Minimum RPM = 370


Tip Speed (ft/min.) = RPM x 3.30
(Tip Speed (m/s) = RPM x 0.0168)

SFB-12
CFM

Maximum Motor Frame Size = 145T

OV

825

964

1065

1244

1305

1525

1545

1805

1785

2086

2025

2367

2265

2647

2505

2928

2745

3208

2985

3489

3225

3769

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
455
0.07
5.7
493
0.12
6.3
533
0.18
7.1
580
0.26
8.2
632
0.36
9.6
686
0.49
11.0
747
0.67
11.8
809
0.88
13.0
873
1.13
14.5
937
1.43
16.1
1002
1.77
17.8

0.5

0.75

631
0.18
9.3
665
0.25
10.2
703
0.35
10.5
743
0.47
10.7
789
0.61
11.4
837
0.79
12.2
889
1.00
13.2
943
1.26
14.4
1001
1.56
15.8
1062
1.92
17.4

773
0.33
10.3
806
0.43
10.6
844
0.57
11.1
883
0.74
11.8
925
0.93
12.6
971
1.15
13.5
1019
1.41
14.6
1071
1.72
16.2
1124
2.08
17.8

871
0.40
10.5
897
0.52
11.0
931
0.67
11.5
969
0.85
12.2
1008
1.06
12.9
1048
1.30
14.1
1093
1.58
15.6
1140
1.90
17.1

Static Pressure in Inches wg


1.25
1.5
1.75

983
0.62
11.3
1010
0.77
11.8
1045
0.96
12.7
1083
1.19
13.9
1122
1.45
15.3
1162
1.75
16.7
1205
2.08
18.2

1061
0.71
12.0
1087
0.88
13.0
1116
1.07
14.0
1152
1.31
15.2
1190
1.59
16.6
1230
1.91
18.0

1158
0.99
14.4
1185
1.19
15.5
1217
1.44
16.6
1254
1.73
17.9
1292
2.06
19.5

2.25

2.5

1225
1.09
16.0
1251
1.32
17.0
1278
1.56
18.1
1314
1.87
19.5

1313
1.44
18.6
1340
1.70
19.8
1370
2.00
21

1373
1.56
20
1399
1.84
22

Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

22

SFB-15 - Belt Drive

2338
(594)

1058

1234

2134

(270)

(324)

(51)
curv
e

(552)

16

1458

stem

(406)

(371)

112

of th
i

(391)

2434
1658

s sy

1538

3114
(371)

(629)

1758 (448)

ele
ct
to

the

left

(38)

(422)

13 (330)

no
ts

30 (762)
3258 (829)

1878 (479)

Do

Wheel Diameter = 15 (381)


Shaft Diameter = 1 (25)
Outlet Area = 1.39 ft2 (0.129 m2)
Mounting Hole Size = 1/2 (13)
^Approximate Unit Weight = 214 lb. (97 kg)

cfm

Maximum BHP at given RPM = (RPM/720)3

All dimensions in inches (millimeters)


For additional discharge positions see page 14
^Weight shown is largest cataloged Open Drip Proof motor

(Maximum KW at a given RPM = (RPM/794)3)

Maximum RPM = 1200 and Minimum RPM = 380


Tip Speed (ft/min.) = RPM x 3.93
(Tip Speed (m/s) = RPM x 0.0200)

SFB-15
CFM

Maximum Motor Frame Size = 184T

OV

1560

1125

1860

1342

2160

1558

2460

1775

2760

1991

3060

2208

3360

2424

3660

2641

3960

2857

4260

3074

4560

3290

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
395
0.16
6.0
421
0.23
7.5
450
0.32
9.9
481
0.42
10.9
514
0.56
11.5
549
0.72
12.7
585
0.91
14.1
623
1.14
15.9
662
1.41
17.8
701
1.71
18.9
742
2.06
20

0.5
508
0.25
8.1
529
0.33
8.8
554
0.44
9.6
580
0.56
10.6
608
0.71
11.9
637
0.89
13.5
668
1.11
14.9
701
1.35
16.0
734
1.63
17.3
768
1.95
18.6
804
2.32
19.8

0.75

619
0.43
9.4
638
0.55
10.3
663
0.70
11.4
688
0.87
12.3
715
1.07
13.2
742
1.29
14.0
772
1.56
14.7
802
1.86
15.9
834
2.20
17.2
867
2.59
18.8

716
0.67
11.2
734
0.83
12.0
759
1.03
12.8
784
1.24
13.5
810
1.49
14.1
837
1.76
14.7
865
2.07
15.4
895
2.44
16.6
925
2.85
18.4

Static Pressure in Inches wg


1.25
1.5
1.75

803
0.97
13.4
822
1.17
14.0
846
1.41
14.6
871
1.68
15.0
897
1.98
15.4
924
2.31
16.3
951
2.67
17.6
980
3.09
19.2

865
1.09
15.2
884
1.32
15.6
903
1.57
16.0
928
1.87
16.5
953
2.18
17.0
979
2.54
17.7
1005
2.93
18.9
1032
3.35
20

941
1.47
17.2
959
1.74
17.5
980
2.04
17.9
1005
2.39
18.6
1030
2.76
19.3
1056
3.17
20
1082
3.63
22

2.5

2.75

1013
1.90
19.0
1031
2.22
19.4
1053
2.58
20
1078
2.98
21
1103
3.41
22
1129
3.89
23

1128
2.58
22
1147
2.98
23
1166
3.40
23
1191
3.88
24

1174
2.75
24
1192
3.17
24

Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

23

SFB-18 - Belt Drive

3078
(784)

22

1334

(349)

(451)

(51)
curv
e

1958

1734

(559)

stem

1938

(498)

42
(1067)

1914

3314
112

2238

of t
his
sy

(492)
(489)

(845)

2338 (594)
2518 (638)

ct

to

th e

(568)

left

(38)

ts
ele

18 (457)

no

35 (889)
3678 (937)

Do

cfm

Wheel Diameter = 1818 (460)


Shaft Diameter = 1 (25)
Outlet Area = 2.29 ft2 (0.213 m2)
Mounting Hole Size = 1/2 (13)
^Approximate Unit Weight = 265 lb. (120 kg)

Maximum BHP at given RPM = (RPM/614)3

All dimensions in inches (millimeters)


For additional discharge positions see page 14
^Weight shown is largest cataloged Open Drip Proof motor

(Maximum KW at a given RPM = (RPM/677)3)

Maximum RPM = 1050 and Minimum RPM = 310


Tip Speed (ft/min.) = RPM x 4.75
(Tip Speed (m/s) = RPM x 0.0241)

SFB-18
CFM

Maximum Motor Frame Size = 184T


OV

2725

1188

3150

1374

3575

1559

4000

1744

4425

1930

4850

2115

5275

2300

5700

2486

6125

2671

6550

2857

6975

3042

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
364
0.29
8.4
388
0.39
10.3
415
0.52
11.1
444
0.68
12.0
473
0.87
13.6
503
1.09
15.5
534
1.36
17.7
566
1.67
19.2
599
2.03
20
631
2.43
22
664
2.88
24

0.5
464
0.44
9.2
481
0.56
10.1
500
0.70
11.3
524
0.89
13.1
548
1.09
14.7
573
1.34
15.8
601
1.63
17.1
630
1.96
18.6
660
2.34
20
689
2.76
21
720
3.23
23

0.75
550
0.60
10.2
563
0.74
11.2
578
0.90
12.2
596
1.10
13.1
615
1.32
14.0
638
1.59
14.8
662
1.90
15.6
687
2.24
16.9
714
2.64
18.5
743
3.09
20
771
3.60
23

635
0.93
12.6
648
1.11
13.4
662
1.32
14.0
680
1.57
14.4
698
1.85
14.8
719
2.17
15.6
743
2.55
16.6
767
2.96
18.0
791
3.41
20
818
3.93
22

Static Pressure in Inches wg


1.25
1.5
1.75

712
1.33
15.5
725
1.56
15.8
738
1.81
15.9
756
2.12
16.2
774
2.46
16.7
793
2.83
17.9
817
3.28
19.4
840
3.77
21
865
4.30
23

782
1.80
17.7
795
2.08
17.8
809
2.38
18.1
826
2.75
18.7
844
3.15
19.5
863
3.58
21
886
4.10
22
909
4.67
24

836
2.03
19.5
848
2.34
19.7
861
2.68
20
875
3.04
20
893
3.47
21
911
3.94
22
929
4.43
24
951
5.02
26

2.25

898
2.60
21
910
2.97
22
923
3.35
22
938
3.78
23
956
4.28
24
974
4.81
26
992
5.38
27

943
2.86
23
957
3.26
24
970
3.67
24
982
4.11
25
998
4.61
26
1016
5.18
27
1034
5.78
29

2.5

1001
3.54
25
1013
3.99
26
1026
4.46
26
1039
4.95
27

Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

24

SFB-20 - Belt Drive

3358
(854)

1478

2334

1578

(603)

(403)

2
(51)

22
(559)

s ys
tem

2112
(546)

curv

(378)

2118
3618
(918)

of t

112

2412

(537)

his

46
(1168)

left

(38)

t to

the

(622)

ts
ele
c

1912 (495)

2558 (651)

35 (889)
37 (940)

27 8 (695)
3

n
Do

cfm

Wheel Diameter = 20 (508)


Shaft Diameter = 114 (32)
Outlet Area = 2.40 ft2 (0.223 m2)
Mounting Hole Size = 5/8 (16)
^Approximate Unit Weight = 405 lb (184 kg)

Maximum BHP at given RPM = (RPM/485)3

All dimensions in inches (millimeters)


For additional discharge positions see page 14
^Weight shown is largest cataloged Open Drip Proof motor

(Maximum KW at a given RPM = (RPM/535)3)

Maximum RPM = 950 and Minimum RPM = 270


Tip Speed (ft/min.) = RPM x 5.24
(Tip Speed (m/s) = RPM x 0.0266)

SFB-20
CFM

Maximum Motor Frame Size = 215T

OV

3275

1362

3800

1581

4325

1799

4850

2018

5375

2236

5900

2455

6425

2673

6950

2892

7475

3110

8000

3329

8525

3547

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
320
0.37
8.1
343
0.51
10.3
369
0.70
11.3
396
0.92
12.3
424
1.19
14.0
454
1.52
16.1
484
1.90
18.6
515
2.36
20
546
2.88
22
578
3.47
24
610
4.14
26

0.5
402
0.53
9.1
420
0.70
10.1
440
0.90
11.5
462
1.15
13.4
485
1.45
15.4
511
1.80
16.8
537
2.22
18.4
565
2.69
19.8
593
3.24
21
622
3.86
23
652
4.55
24

0.75

487
0.90
11.3
503
1.13
12.6
521
1.39
13.7
542
1.71
14.7
564
2.08
15.5
587
2.52
16.8
612
3.02
18.5
638
3.59
20
665
4.24
22
692
4.96
24

561
1.36
13.1
576
1.64
13.9
594
1.99
14.5
614
2.38
15.3
634
2.83
16.1
657
3.36
17.0
681
3.95
19.2
705
4.61
22
731
5.37
24

Static Pressure in Inches wg


1.25
1.5
1.75

613
1.61
14.6
628
1.91
15.0
642
2.26
15.3
661
2.68
15.5
679
3.15
16.5
700
3.70
18.0
722
4.30
19.5
745
5.00
22
769
5.77
24

676
2.19
16.7
689
2.56
16.9
704
2.98
17.3
722
3.49
18.0
741
4.04
19.3
761
4.68
21
782
5.38
23
805
6.18
25

733
2.87
18.6
747
3.30
19.0
762
3.81
19.8
780
4.41
21
799
5.05
22
819
5.79
24
840
6.59
26

2.5

2.75

788
3.64
21
801
4.15
21
818
4.76
22
836
5.44
24
854
6.18
25
875
7.02
28

877
4.89
24
890
5.51
25
904
6.20
27
922
7.02
29
940
7.89
31

911
5.26
26
925
5.92
26
938
6.61
28

Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

25

SFB-22 - Belt Drive

3634
16

2334

2758

(603)

(702)

24

1712

(610)

(445)

212
(64)
curv
e

(406)

stem

(933)

(584)

4112
112

2834

of t
his
sy

23

5212
(1334)

(1054)

2814 (718)

se
lec
t to

t he

(730)

left

(38)

20 (508)

no
t

3418 (867)
3958 (1006)

3034 (781)

Do

Wheel Diameter = 2214 (565)


Shaft Diameter = 114 (32)
Outlet Area = 3.23 ft2 (0.300 m2)
Mounting Hole Size = 5/8 (16)
^Approximate Unit Weight = 540 lb (245 kg)

cfm

Maximum BHP at given RPM = (RPM/418)3

All dimensions in inches (millimeters)


For additional discharge positions see page 14
^Weight shown is largest cataloged Open Drip Proof motor

(Maximum KW at a given RPM = (RPM/461)3)

Maximum RPM = 900 and Minimum RPM = 240


Tip Speed (ft/min.) = RPM x 5.79
(Tip Speed (m/s) = RPM x 0.0294)

SFB-22
CFM

Maximum Motor Frame Size = 215T


OV

4000

1240

4950

1534

5900

1829

6850

2123

7800

2418

8750

2712

9700

3007

10650 3301

11600 3596

12550 3890

13500 4185

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
285
0.44
8.6
315
0.71
11.3
350
1.09
14.1
388
1.60
17.2
428
2.25
21
470
3.08
24
512
4.09
27
555
5.33
30
599
6.79
34
643
8.51
38
688
10.5
42

0.5
359
0.64
10.5
385
0.96
13
410
1.37
15.9
441
1.91
19.3
475
2.61
22
511
3.47
25
550
4.53
28
590
5.80
32
631
7.30
37
672
9.04
40
714
11.1
44

0.75
419
0.83
12.8
441
1.20
15.4
467
1.68
17.9
491
2.25
20
520
2.98
23
552
3.87
26
587
4.97
30
623
6.27
34
662
7.83
38
701
9.62
42
742
11.7
46

Static Pressure in Inches wg


1.25
1.5
2

491
1.43
16.6
514
1.96
19
540
2.61
22
564
3.37
25
593
4.30
28
624
5.43
31
658
6.77
35
693
8.34
38
730
10.17
42
768
12.3
47

535
1.67
18
557
2.23
20
582
2.95
23
608
3.79
26
632
4.75
30
660
5.90
32
691
7.28
36
724
8.88
39
759
10.76
43
794
12.9
48

598
2.52
22
620
3.26
24
646
4.17
28
671
5.21
30
695
6.39
34
724
7.79
37
755
9.44
41
788
11.33
45
822
13.5
49

691
3.92
26
713
4.88
29
739
6.08
32
764
7.41
36
789
8.90
40
813
10.54
44
844
12.56
48
875
14.8
53

2.5

755
4.56
29
776
5.64
31
798
6.87
34
824
8.35
39
850
10
43
874
11.82
47
898
13.8
52

3.25

834
6.38
34
854
7.71
37
877
9.24
41

861
6.75
36
881
8.14
39

Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

26

SFB-25 - Belt Drive

4038
(1026)

1712

25

(445)

1912

212

(495)

(64)
mc
urve

(635)

3158

2614
5734

2578

4534
112

3112

(657)

(1162)

the
left
of

(1467)

this
syst
e

(803)

(667)

(38)

3118 (791)

ele
ct

to

(800)

no

36 (914)
4112 (1054)

33 8 (854)

ts

1978 (505)

Do

Wheel Diameter = 25 (635)


Shaft Diameter = 112 (38)
Outlet Area = 4.21 ft2(0.391 m2)
Mounting Hole Size = 5/8 (16)
^Approximate Unit Weight = 700 lb. (318 kg)

cfm

All dimensions in inches (millimeters)


For additional discharge positions see page 14
^Weight shown is largest cataloged Open Drip Proof motor

Maximum Motor Frame Size = 284T

OV

6000

1425

6950

1651

7900

1877

8850

2103

9800

2329

10750 2554

11700 2780

12650 3006

13600 3232

14550 3457

15500 3683

(Maximum KW at a given RPM = (RPM/335)3)

Maximum RPM = 750 and Minimum RPM = 190


Tip Speed (ft/min.) = RPM x 6.54
(Tip Speed (m/s) = RPM x 0.0332)

SFB-25
CFM

Maximum BHP at given RPM = (RPM/304)3

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
246
0.74
8.4
263
1.02
10.3
283
1.39
12.1
304
1.85
14.1
326
2.40
16.1
349
3.07
18.4
373
3.86
21
397
4.78
23
421
5.84
25
445
7.04
27
471
8.43
29

0.5
310
1.03
10.4
324
1.37
11.9
338
1.78
13.7
354
2.29
15.7
372
2.87
18.0
391
3.58
20
412
4.42
22
433
5.37
24
455
6.46
26
478
7.72
29
501
9.15
31

0.75
363
1.32
12.5
375
1.72
14.3
387
2.17
16.2
401
2.73
17.9
416
3.36
19.6
432
4.12
21
450
4.99
23
468
5.96
25
488
7.13
27
510
8.43
30
531
9.88
33

Static Pressure in Inches wg


1
1.25
1.5
2
412
1.65
14.5
419
463
2.05
2.42
15.8
17.3
431
470
508
2.57
2.95
3.34
17.3
18.6
20
444
482
518
585
3.15
3.61
4.03
4.93
19.0
20
22
25
457
495
530
593
3.86
4.32
4.83
5.76
21
22
23
26
471
508
542
605
4.65
5.19
5.70
6.79
23
24
25
27
487
522
556
617
5.57
6.16
6.73
7.89
25
26
28
29
504
537
569
629
6.62
7.22
7.88
9.07
27
28
30
32
521
553
584
643
7.79
8.48
9.13
10.51
29
31
32
34
539
570
600
657
9.09
9.86
10.58
12.04
31
33
34
36
559
588
617
671
10.62
11.37
12.18
13.68
34
35
36
39

2.5

654
6.81
29
660
7.78
30
672
9.05
32
684
10.39
34
696
11.82
36
709
13.43
39
723
15.26
42

3.25

716
8.96
33
722
10.11
35
734
11.62
36
746
13.21
39

743
9.57
35
748
10.74
36

Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

27

SFB-27 - Belt Drive

44

(1118)

19

27

(483)

2138

(543)

212
(64)
urve

2818

(686)

of t
his
sys
tem
c

3412

(714)

(876)

2812

6118
(1553)

(724)

4918
358 (1248)

33

3518 (892)
3758 (956)

el e
ct

to

the

(838)

left

(92)

4012 (1029)
46 (1168)

no
ts

2214 (565)
Do

Wheel Diameter = 2712 (699)


Shaft Diameter = 112 (38)
Outlet Area = 4.97 ft2 (0.462 m2)
Mounting Hole Size = 5/8 (16)
^Approximate Unit Weight = 845 lb. (383 kg)

cfm

All dimensions in inches (millimeters)


For additional discharge positions see page 14
^Weight shown is largest cataloged Open Drip Proof motor

(Maximum KW at a given RPM = (RPM/314)3)

Maximum RPM = 700 and Minimum RPM = 200


Tip Speed (ft/min.) = RPM x 7.20
(Tip Speed (m/s) = RPM x 0.0366)

SFB-27
CFM

Maximum BHP at given RPM = (RPM/285)3

Maximum Motor Frame Size = 286T


OV

8600

1729

9750

1961

10900 2192

12050 2423

13200 2655

14350 2886

15500 3117

16650 3349

17800 3580

18950 3811

20100 4043

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
245
1.29
11.1
264
1.75
13.1
284
2.31
15.1
305
3.02
17.3
327
3.85
19.8
349
4.83
22
372
5.97
25
395
7.27
27
418
8.76
29
441
10.40
32
465
12.40
34

0.5
297
1.72
12.5
310
2.21
14.6
327
2.84
16.7
344
3.58
19.2
363
4.46
22
382
5.47
24
403
6.64
26
424
8.02
28
446
9.59
31
468
11.30
34
490
13.30
37

0.75
345
2.17
15.1
355
2.71
17.0
368
3.38
18.9
381
4.14
21
398
5.09
23
415
6.16
25
434
7.40
27
453
8.80
29
472
10.37
32
492
12.10
35
514
14.20
39

Static Pressure in Inches wg


1
1.25
1.5
2
388
427
462
2.61
3.07
3.56
16.7
18.2
20
397
434
470
3.23
3.73
4.26
18.4
19.7
21
407
444
477
540
3.94
4.51
5.05
6.24
20
21
23
26
419
454
487
547
4.78
5.39
6.03
7.28
22
23
25
27
432
465
497
556
5.73
6.41
7.09
8.45
24
25
27
29
447
478
508
566
6.83
7.57
8.30
9.80
26
28
29
31
464
491
521
576
8.14
8.84
9.68
11.25
28
30
32
34
481
508
535
588
9.60
10.38
11.17
12.90
31
33
34
36
499
525
550
601
11.24
12.10
12.92
14.74
34
35
36
39
518
543
567
614
13.10
14.00
14.90
16.70
37
38
39
41
538
561
585
629
15.10
16.10
17.10
18.90
39
40
41
44

2.5

603
8.58
30
610
9.86
32
618
11.22
33
628
12.88
36
638
14.64
39
648
16.49
41
661
18.70
44
674
21.00
47

652
9.95
34
660
11.28
35
668
12.80
37
676
14.41
39
685
16.36
41
695
18.42
44

3.25

683
12.04
37
691
13.58
39
699
15.28
40

Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

28

SFB-30 - Belt Drive

4834
21

27

(533)

3138

3678

(797)

(937)

2338

(594)

212

(64)
em c
urve

(686)

syst

(1238)

3134

68
112

3658

of t
his

(806)

5334

(1727)

(1365)

ct

to

the

left

(38)

(930)

no

4234 (1086)
4814 (1226)

ts
el e

2212 (572)

3838 (975)
4118 (1045)

Wheel Diameter = 30 (762)


Shaft Diameter = 112 (38)
Outlet Area = 5.72 ft2 (0.531 m2)
Mounting Hole Size = 5/8 (16)
^Approximate Unit Weight = 940 lb. (426 kg)

cfm

All dimensions in inches (millimeters)


For additional discharge positions see page 14
^Weight shown is largest cataloged Open Drip Proof motor

11525 2015

13050 2282

14575 2549

16100 2816

17625 3082

19150 3349

20675 3616

22200 3883

23725 4149

25250 4416

Maximum RPM = 650 and Minimum RPM = 175


Tip Speed (ft/min.) = RPM x 7.86
Maximum Motor Frame Size = 286T

OV

10000 1749

(Maximum KW at a given RPM = (RPM/263)3)

(Tip Speed (m/s) = RPM x 0.0399)

SFB-30
CFM

Maximum BHP at given RPM = (RPM/239)3

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
245
1.60
13.0
267
2.25
15.7
291
3.10
18.7
316
4.14
22
342
5.42
25
369
6.98
28
397
8.82
31
424
11.00
35
452
13.40
39
480
16.20
43
508
19.40
46

0.5
293
2.12
15.0
311
2.85
17.9
330
3.73
21
352
4.85
23
375
6.18
26
399
7.78
29
423
9.65
33
448
11.80
37
474
14.30
42
501
17.20
45
528
20.50
49

0.75
332
2.59
17.3
350
3.44
19.7
368
4.44
22
387
5.60
25
406
6.96
28
428
8.64
31
450
10.57
35
474
12.80
39
498
15.40
42
523
18.30
46
548
21.50
51

Static Pressure in Inches wg


1
1.25
1.5
2
369
403
434
3.13
3.63
4.19
18.6
20
22
383
416
446
501
3.98
4.60
5.19
6.43
21
22
24
27
401
430
459
513
5.09
5.69
6.39
7.73
24
25
27
29
419
448
474
526
6.37
7.10
7.78
9.31
27
28
30
31
437
466
492
539
7.84
8.69
9.49
11.02
30
32
33
35
456
484
510
557
9.51
10.49
11.40
13.12
33
35
36
38
477
503
529
575
11.50
12.50
13.55
15.51
36
38
39
42
499
523
547
593
13.80
14.80
15.90
18.10
40
41
43
46
521
545
566
612
16.40
17.50
18.60
21.00
43
45
46
50
545
567
588
630
19.40
20.60
21.70
24.20
47
49
51
55
569
589
610
649
22.80
23.90
25.20
27.70
52
53
55
59

2.5

3.25

562
9.15
32
573
10.79
34
586
12.74
37
600
14.86
41
616
17.32
45
634
20.20
49

606
10.56
35
617
12.37
38
629
14.38
40
642
16.73
44

638
13.16
40
649
15.20
42

Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

29

SWB-106 - Belt Drive


Series 100
1834

3.5

(219)

(508)

(248)

2
(51)

11

26 8

(279)

2114

(676)

112

15 8
1

(540)

(384)

0.0
0

16

00

1135

0.5

30

Wheel Diameter = 1138 (289)


Shaft Diameter = 3/4 (19)
Outlet Area = 0.76 ft2 (0.07 m 2 )
^Approximate Unit Weight = 135 lb. (61 kg)

1.0

25

16 8 (429)

1.5

2
1

2514 (641)
2634 (679)

65

1534 (400)

2.0

20

16 (406)

300

(38)

2.5

Do

(286)

Static Pressure (in. wg)

(292)
5

Static Pressure (Pa x 100)

1114

RPM
HP
Density 0.075 lb/ft3

3.0
7

1112

this
syst
em c
urve

934

the
left
of

20

sel
ect
to

858

no
t

(476)

670
100

200

200

300
Volume (cfm)
400

400

600

500

800

1000

Volume (m3/hr)

Maximum BHP at a given RPM = (RPM/3706)3

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

(Maximum KW at a given RPM = (RPM/4086)3)

Maximum RPM = 3000


Tip Speed (ft/min.) = RPM x 2.91
(Tip Speed (m/s) = RPM x 0.0148)

SWB-106
CFM

Maximum Motor Frame Size = 145T

OV

100

132

140

184

180

237

220

289

260

342

300

395

340

447

380

500

420

553

460

605

500

658

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
936
0.02
5.4
1023
0.02
6.0
1172
0.03
6.6
1356
0.05
7.2
1550
0.07
8.0
1749
0.09
9.1
1952
0.13
10.5
2156
0.17
12.2
2361
0.23
14.7
2567
0.29
17.9
2775
0.37
22

0.5
1273
0.04
6.8
1322
0.04
7.1
1398
0.05
7.5
1522
0.07
8.2
1681
0.09
9.0
1866
0.12
10.1
2056
0.15
11.5
2253
0.20
12.8
2452
0.26
14.2
2654
0.32
16.2
2858
0.40
22

0.75
1542
0.06
8.0
1574
0.07
8.4
1632
0.08
8.9
1712
0.10
9.4
1830
0.12
10.2
1976
0.15
11.3
2158
0.19
12.5
2344
0.23
13.7
2535
0.29
15.1
2732
0.36
16.9
2931
0.44
18.9

1799
0.11
9.8
1843
0.12
10.2
1906
0.13
10.9
1993
0.15
11.8
2113
0.18
12.8
2258
0.22
13.7
2434
0.27
14.7
2618
0.33
16.1
2806
0.40
17.8

Static Pressure in Inches wg


1.25
1.5
1.75

1999
0.14
11.5
2031
0.16
11.9
2088
0.17
12.6
2155
0.19
13.2
2253
0.22
14.0
2379
0.26
14.9
2524
0.31
16.2
2699
0.37
17.2
2883
0.44
18.9

2179
0.18
13.1
2210
0.20
13.4
2257
0.22
13.9
2318
0.24
14.5
2391
0.27
15.2
2500
0.31
16.2
2633
0.35
17.4
2779
0.42
18.8
2956
0.49
19.8

2376
0.24
14.8
2413
0.26
15.2
2470
0.29
15.9
2537
0.32
16.6
2626
0.35
17.5
2736
0.40
18.6
2879
0.46
20

2.25

2.5

2531
0.29
16.3
2561
0.31
16.7
2614
0.34
17.4
2676
0.37
18.0
2745
0.41
18.7
2852
0.45
19.9
2973
0.51
21

2676
0.34
17.9
2706
0.37
18.3
2751
0.39
18.8
2808
0.42
19.5
2876
0.46
20
2963
0.51
21

2813
0.39
19.4
2844
0.42
19.8
2880
0.45
20
2936
0.48
21
3000
0.52
22

Performance certied is for installation Type B - free inlet, ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

30

600

SWB-107 - Belt Drive


Series 100
1834

3.5

20

934

(219)

(508)

(248)

(51)

3.0

(540)

syst
em

this

05

0.5

20

2514 (641)
2634 (679)

1.0

2
1

1534 (400)

16 (406)
1678 (429)

1.5

15

1115

00

(384)

50
24

(38)

2.0

29

112

1518

the
left
of

(279)

2114

2.5

no
ts
ele
ct
to

11

2658
(676)

Do

1114
(286)

Static Pressure (in. wg)

1112

Static Pressure (Pa x 100)

(292)

RPM
HP
Density 0.075 lb/ft3

curv
e

858

(476)

60

670

Wheel Diameter = 11 8 (289)


Shaft Diameter = 3/4 (19)
Outlet Area = 0.76 ft2 (0.07 m 2 )
^Approximate Unit Weight = 135 lb. (61 kg)

0.0
0

100

200

300
400
500
Volume (cfm)

600

700

800

200

400

600

800

1000

1200

Volume (m3/hr)

Maximum BHP at a given RPM = (RPM/3706)3


(Maximum KW at a given RPM = (RPM/3851)3)

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

Maximum RPM = 2900


Tip Speed (ft/min.) = RPM x 2.91
(Tip Speed (m/s) = RPM x 0.0148)

SWB-107
CFM

Maximum Motor Frame Size = 145T

OV

140

184

200

263

260

342

320

421

380

500

440

579

500

658

560

737

620

816

680

895

740

974

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
891
0.02
4.5
1008
0.02
5.1
1184
0.04
6.0
1372
0.06
7.3
1573
0.09
8.6
1782
0.12
10.1
1994
0.17
11.8
2208
0.23
14.1
2421
0.30
16.6
2636
0.39
19.5
2852
0.50
23

0.5
1198
0.04
5.9
1264
0.04
6.2
1374
0.06
6.8
1531
0.08
7.7
1713
0.11
8.9
1900
0.15
10.6
2096
0.20
12.3
2302
0.27
14.1
2512
0.34
17.0
2723
0.44
22

Static Pressure in Inches wg


1.25
1.5
1.75

0.75

1494
0.07
7.3
1572
0.09
7.7
1686
0.11
8.4
1840
0.14
9.7
2020
0.19
11.3
2205
0.24
12.9
2394
0.30
14.7
2593
0.38
16.7
2799
0.48
19.0

1695
0.10
8.5
1759
0.12
8.8
1848
0.14
9.5
1970
0.18
10.7
2129
0.22
12.0
2308
0.28
13.5
2492
0.35
15.5
2680
0.43
17.6
2872
0.52
19.9

1877
0.13
9.8
1931
0.15
10.1
2005
0.18
10.6
2105
0.21
11.6
2238
0.26
12.7
2404
0.32
14.2
2583
0.39
16.1
2767
0.48
18.5

2088
0.19
11.3
2156
0.22
11.8
2244
0.25
12.6
2358
0.30
13.7
2493
0.36
14.9
2669
0.44
16.8
2850
0.53
19.1

2239
0.23
12.6
2299
0.26
13.0
2375
0.30
13.7
2472
0.34
14.7
2601
0.41
16.1
2751
0.48
17.5

2.25

2.5

2380
0.27
13.8
2432
0.30
14.2
2502
0.34
14.9
2593
0.39
15.9
2705
0.45
17.2
2838
0.53
18.4

2512
0.32
15.2
2559
0.35
15.6
2627
0.39
16.3
2708
0.44
17.2
2805
0.50
18.3

2684
0.40
17.0
2745
0.44
17.6
2817
0.49
18.5

Performance certied is for installation Type B - free inlet, ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

31

SWB-108 - Belt Drive


Series 100
4.0

858
(219)

20

934

(508)

(248)

(51)

3.5

26 8

(279)

2114

(676)

112
15 8
1

(540)

(38)

(384)

6
5
4
3

2.5

2.0
1.5
1.0

25 4 (641)
2634 (679)

0.5

Wheel Diameter = 1138 (289)


Shaft Diameter = 3/4 (19)
Outlet Area = 0.76 ft2 (0.07 m 2 )
^Approximate Unit Weight = 135 lb. (61 kg)

Do

1534 (400)

25

50

670

0.0
0

19

15

110

75

16 (406)
1678 (429)

23

00
28

Static Pressure (Pa x 100)

11

this
sy

(286)

to t
he
left
of

(292)

3.0
7

no
ts
ele
ct

11 4
1

Static Pressure (in. wg)

11 2
1

RPM
HP
Density 0.075 lb/ft3

stem
curv
e

1834
(476)

6
8
Volume (cfm x 100)
8

10

10 12 14 16
Volume (m3/hr x 100)

12

18

20

14

22

Maximum BHP at a given RPM = (RPM/3233)3


(Maximum KW at a given RPM = (RPM/3564)3)

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

Maximum RPM = 2800


Tip Speed (ft/min.) = RPM x 2.91
(Tip Speed (m/s) = RPM x 0.0148)

SWB-108
CFM

Maximum Motor Frame Size = 145T

OV

200

263

300

395

400

526

500

658

600

789

700

921

800

1053

900

1184

1000

1316

1100

1447

1200

1579

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
860
0.02
5.5
982
0.03
6.6
1141
0.04
7.2
1317
0.07
8.0
1504
0.09
9.1
1699
0.13
10.3
1899
0.18
12.1
2102
0.24
13.9
2308
0.32
15.6
2517
0.41
18.7
2728
0.52
23

0.5
1148
0.04
6.8
1235
0.05
7.0
1357
0.07
7.7
1506
0.10
8.6
1673
0.14
9.8
1849
0.18
11.5
2035
0.23
13.3
2227
0.30
14.7
2423
0.38
16.6
2623
0.48
18.7

0.75

1443
0.09
7.7
1551
0.11
8.2
1675
0.14
9.2
1825
0.18
10.5
1989
0.23
12.5
2162
0.29
13.9
2344
0.37
15.5
2531
0.45
17.4
2723
0.55
19.7

1635
0.12
8.7
1719
0.15
9.0
1837
0.18
9.8
1965
0.22
11.2
2119
0.28
12.9
2282
0.34
14.5
2455
0.43
16.2
2634
0.53
18.2

Static Pressure in Inches wg


1.25
1.5
1.75

1805
0.16
9.6
1872
0.19
9.8
1983
0.23
10.5
2105
0.27
11.8
2242
0.33
13.3
2396
0.40
15.0
2561
0.49
16.8
2733
0.59
18.9

2025
0.24
10.7
2117
0.28
11.1
2234
0.32
12.3
2361
0.39
13.9
2507
0.46
15.6
2662
0.54
17.4

2165
0.29
11.5
2241
0.33
12.0
2356
0.38
13.0
2478
0.44
14.6
2610
0.52
16.2
2763
0.61
18.1

2.25

2.5

2296
0.34
12.4
2364
0.39
12.9
2471
0.44
13.7
2589
0.50
14.8
2715
0.59
17.0

2419
0.40
13.5
2487
0.45
13.9
2579
0.50
14.6
2695
0.56
15.7

2603
0.51
14.8
2681
0.57
15.5
2796
0.63
16.6

Performance certied is for installation Type B - free inlet, ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

32

SWB-110 - Belt Drive


Series 100
1834

4.0

(219)

20

934

(508)

(248)

3.5

(51)

3.0

1518

(540)

(38)

(384)

5
4
3

2.0

the
le

112

2.5

1.5

ele
ct
to

(279)

2114

(676)

1.0

0.0

70

70

10

12

65

14

10

670

70

0.5

22

2514 (641)
2634 (679)

70

1534 (400)

18

16 (406)
1678 (429)

Do

26

no
ts

11

2658

Static Pressure (in. wg)

1114
(286)

Static Pressure (Pa x 100)

1112

ft o
f th
is s
yste
m

(292)

RPM
HP
Density 0.075 lb/ft3

curv
e

858

(476)

14

16

18

20

22

Volume (cfm X 100)

Wheel Diameter = 1138 (289)


Shaft Diameter = 3/4 (19)
Outlet Area = 0.76 ft2 (0.07 m 2 )
^Approximate Unit Weight = 135 lb. (61 kg)

10

15

20

25

30

35

Volume (m3/hr x 100)

Maximum BHP at a given RPM = (RPM/2665)3


(Maximum KW at a given RPM = (RPM/2938)3)

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

Maximum RPM = 2665


Tip Speed (ft/min.) = RPM x 2.91
(Tip Speed (m/s) = RPM x 0.0148)

SWB-110
CFM

Maximum Motor Frame Size = 145T

OV

500

658

650

855

800

1053

950

1250

1100

1447

1250

1645

1400

1842

1550

2039

1700

2237

1850

2434

2000

2632

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
898
0.04
8.5
1040
0.06
9.0
1192
0.09
9.7
1353
0.13
10.6
1519
0.18
12.0
1688
0.25
14.2
1859
0.33
16.0
2033
0.43
18.3
2211
0.55
21
2391
0.69
24
2571
0.86
27

0.5
1094
0.07
8.8
1218
0.10
9.2
1356
0.13
9.9
1501
0.18
10.9
1653
0.24
12.7
1813
0.31
14.3
1976
0.40
16.3
2141
0.51
18.8
2310
0.63
22
2480
0.78
25
2652
0.96
27

0.75
1264
0.10
9.0
1368
0.13
9.4
1496
0.18
10.1
1633
0.23
11.6
1776
0.30
13.0
1924
0.37
14.8
2080
0.47
17.0
2241
0.59
19.6
2404
0.72
23
2569
0.88
25

1508
0.18
9.9
1621
0.22
10.9
1750
0.28
12.1
1888
0.36
13.4
2031
0.44
15.5
2179
0.54
17.8
2332
0.67
21
2491
0.81
24
2652
0.97
26

Static Pressure in Inches wg


1.25
1.5
1.75

1635
0.23
10.5
1735
0.27
11.5
1859
0.34
12.1
1991
0.42
13.9
2130
0.51
16.2
2274
0.62
18.9
2421
0.75
22
2573
0.89
24

1849
0.33
11.4
1961
0.39
12.6
2088
0.48
14.4
2222
0.58
17.0
2362
0.70
20
2506
0.83
23
2654
0.98
24

1955
0.39
12.1
2055
0.45
13.1
2179
0.54
15.0
2309
0.65
18.2
2446
0.77
22
2588
0.91
23

2.25

2.5

2054
0.45
13.3
2153
0.52
14.0
2267
0.61
16.1
2394
0.72
19.3
2526
0.85
23

2245
0.59
15.3
2349
0.67
17.3
2474
0.79
21
2603
0.93
22

2332
0.66
16.7
2433
0.75
18.6
2551
0.87
21

Performance certied is for installation Type B - free inlet, ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

33

SWB-113 - Belt Drive


Series 100
2338

4.0
9

(51)

(362)

3114
(794)

14

24 4
3

112

16 8
5

(356)

(629)

(38)

(422)

7
6
5
4
3

Static Pressure (in. wg)

Static Pressure (Pa x 100)

(371)

14 4
1

cur
ve

8
3.0

1458

2.5
3

2.0
1.5
1.0

Wheel Diameter = 1312 (343)


Shaft Diameter = 3/4 (19)
Outlet Area = 1.03 ft2 (0.10 m2)
^Approximate Unit Weight = 175 lb. (79 kg)

no
t

10

12

90

92

10

15
20
Volume (cfm X 100)
20

30

25

40

85

Do
550
5

0.0
0

30

60

27 2 (699)
3018 (765)

1878 (479)

20

0.5

1
1

16

13 (330)

23

1758 (448)

RPM
HP
Density 0.075 lb/ft3

3.5

em

(552)

to
the
lef
to
f th
is s
yst

(270)

se
lec
t

21 4

(270)

1058

1058

(594)

30

50

Volume (m3/hr x 100)

Maximum BHP at a given RPM = (RPM/2084) 3


(Maximum KW at a given RPM = (RPM/2298)3)

All dimension in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

Maximum RPM = 2385


Tip Speed (ft/min.) = RPM x 3.53
(Tip Speed (m/s) = RPM x 0.0179)

SWB-113
CFM

Maximum Motor Frame Size = 184T

OV

700

680

900

874

1100

1068

1300

1262

1500

1456

1700

1650

1900

1845

2100

2039

2300

2233

2500

2427

2700

2621

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
767
0.05
5.4
883
0.08
6.2
1009
0.11
7.4
1144
0.16
8.8
1283
0.22
10.0
1424
0.30
11.9
1569
0.39
13.8
1714
0.51
15.9
1860
0.64
18.1
2007
0.80
20
2154
0.99
22

0.5
939
0.09
5.7
1037
0.12
6.9
1147
0.17
8.5
1266
0.22
9.5
1391
0.29
10.8
1524
0.37
12.7
1659
0.48
14.6
1799
0.60
16.8
1940
0.75
19.0
2083
0.92
21
2228
1.12
23

0.75

1168
0.17
8.3
1269
0.22
9.1
1378
0.29
10.1
1494
0.37
11.5
1617
0.46
13.3
1745
0.57
15.3
1878
0.70
17.8
2014
0.85
19.7
2153
1.03
21
2293
1.24
24

1291
0.23
9.0
1378
0.28
9.7
1480
0.36
10.7
1591
0.44
12.2
1706
0.55
13.9
1828
0.66
16.1
1953
0.80
18.2
2085
0.96
20
2219
1.15
22
2356
1.36
24

Static Pressure in Inches wg


1.25
1.5
1.75
2

1482
0.35
10.2
1576
0.43
11.3
1680
0.52
12.9
1792
0.63
14.7
1907
0.76
16.9
2029
0.91
18.7
2153
1.08
21
2284
1.27
23

1580
0.41
11.0
1665
0.50
12.0
1766
0.60
13.6
1872
0.72
15.5
1984
0.86
17.4
2101
1.02
19.2
2222
1.19
21
2347
1.40
24

1753
0.58
12.8
1846
0.68
14.3
1948
0.81
16.2
2057
0.96
17.9
2170
1.13
19.8
2288
1.31
22

1837
0.65
13.8
1922
0.77
15.2
2023
0.91
16.7
2126
1.06
18.4
2238
1.24
20
2352
1.43
23

2.25

2.5

1916
0.73
15.1
1999
0.85
15.8
2093
1.00
17.2
2194
1.16
18.9
2302
1.35
21

2073
0.94
16.4
2161
1.09
17.8
2261
1.27
19.6
2364
1.46
22

Performance certied is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the
effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

34

35

SWB-115 - Belt Drive


Series 100
2534

4.0

(546)

(295)

3.5

(51)

3.0

1 2
1

1812

(403)

(699)

(38)

(470)

5
4
3

lef
to
f th
is s
yst
em

2712

(883)

2.5
3

2.0

1.5
1.0

21 8 (537)

Wheel Diameter = 14 4 (375)


Shaft Diameter = 3/4 (19)
Outlet Area = 1.25 ft2 (0.12 m2)
^Approximate Unit Weight = 225 lb. (102 kg)

0.5
0.0
0

Do
550

12

10

88

10

15

40

2718 (689)
3114 (794)

87
21

15 (381)

70
18

20 (508)

15

no
ts
ele
ct
to
the

1578

3434

Static Pressure (in. wg)

(400)

Static Pressure (Pa x 100)

(413)

1534

cur
ve

1614

RPM
HP
Density 0.075 lb/ft3

(295)

1158

2112

1158

(654)

20
25
30
Volume (cfm X 100)

35

40

45

10

20

30
40
50
Volume (m3/hr x 100)

60

70

Maximum BHP at a given RPM = (RPM/1737)3


(Maximum KW at a given RPM = (RPM/1915)3)

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

Maximum RPM = 2187


Tip Speed (ft/min.) = RPM x 3.93
(Tip Speed (m/s) = RPM x 0.0200)

SWB-115
CFM

Maximum Motor Frame Size = 184T

OV

1000

800

1250

1000

1500

1200

1750

1400

2000

1600

2250

1800

2500

2000

2750

2200

3000

2400

3250

2600

3500

2800

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
737
0.08
6.2
843
0.11
6.9
955
0.16
8.2
1075
0.23
9.6
1196
0.32
11.1
1319
0.42
12.8
1444
0.55
14.7
1570
0.71
16.7
1698
0.89
19.0
1827
1.11
21
1956
1.35
24

0.5
879
0.13
6.7
976
0.18
7.8
1078
0.24
9.1
1184
0.31
10.3
1294
0.41
11.7
1412
0.53
13.4
1533
0.67
15.4
1654
0.84
17.6
1776
1.04
19.9
1899
1.26
22
2024
1.52
25

Static Pressure in Inches wg


1.25
1.5
1.75

0.75

1086
0.24
8.4
1183
0.32
9.6
1284
0.40
10.9
1389
0.51
12.4
1496
0.63
14.0
1609
0.78
16.0
1727
0.97
18.3
1847
1.18
20
1968
1.42
23
2090
1.69
25

1186
0.31
8.9
1276
0.39
10.1
1373
0.49
11.4
1474
0.61
13.0
1578
0.75
14.7
1685
0.91
16.7
1794
1.09
18.8
1911
1.31
21
2030
1.57
23
2150
1.86
26

1360
0.47
10.6
1455
0.58
12.0
1552
0.71
13.6
1654
0.86
15.4
1758
1.03
17.5
1864
1.23
19.4
1973
1.45
22
2088
1.71
24

1445
0.56
11.3
1530
0.67
12.5
1625
0.82
14.1
1724
0.98
16.0
1826
1.16
18.0
1931
1.37
20
2037
1.60
22
2146
1.87
24

1600
0.77
13.1
1695
0.92
14.7
1791
1.09
16.6
1891
1.29
18.7
1993
1.51
21
2098
1.76
23

2.25

2.5

1673
0.87
14.1
1759
1.02
15.3
1854
1.21
17.3
1952
1.42
19.4
2053
1.65
22
2156
1.91
24

1746
0.97
15.1
1821
1.13
16.1
1915
1.32
18.0
2010
1.55
20
2109
1.79
22

1883
1.24
17.1
1972
1.44
18.8
2067
1.67
21
2164
1.93
23

Performance certied is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

35

SWB-116 - Belt Drive


Series 100
28
(318)

(546)

(324)

12

2
(51)
10

17 4

17 2

(451)

(445)

17 2
1

(968)

30
1 2
1

2038

(445)

(762)

(38)

(518)

Static Pressure (in. wg)

Static Pressure (Pa x 100)

3818

0
0

400
5
10

10

50

72

15

20

25

30

23
20

75

3014 (769)
3238 (823)

13

Do

16 (406)

00
17

2138 (543)
2278 (581)

RPM
HP
Density 0.075 lb/ft3

no
ts
ele
ct
to
the
lef
to
f th
is s
yst
em
cur
ve

1234

2112

1212

(711)

35

40

45

50

Volume (cfm X 100)

Wheel Diameter = 17 (432)


Shaft Diameter = 1 (25)
Outlet Area = 1.52 ft2 (0.14 m2)
^Approximate Unit Weight = 241 lb. (109 kg)

20

40

60

80

Volume (m3/hr x 100)

Maximum BHP at a given RPM = (RPM/1403)3

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

(Maximum KW at a given RPM = (RPM/1547)3)

Maximum RPM = 2023


Tip Speed (ft/min.) = RPM x 4.32
(Tip Speed (m/s) = RPM x 0.0219)

SWB-116
CFM

Maximum Motor Frame Size = 184T

OV

1200

789

1560

1026

1920

1263

2280

1500

2640

1737

3000

1974

3360

2211

3720

2447

4080

2684

4440

2921

4800

3158

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.5
750
0.15
5.8
846
0.22
7.1
949
0.31
8.8
1061
0.42
10.9
1182
0.57
13.5
1306
0.76
15.4
1432
0.99
17.6
1560
1.27
20
1690
1.60
23
1821
1.99
27
1953
2.44
32

0.75

1.25

943
0.30
7.8
1039
0.40
9.6
1141
0.53
11.8
1250
0.69
13.8
1369
0.89
15.8
1491
1.14
18.0
1615
1.43
21
1742
1.78
24
1869
2.18
28
1999
2.65
32

1026
0.38
8.7
1120
0.50
10.7
1216
0.65
12.5
1320
0.82
14.1
1429
1.03
16.1
1545
1.29
18.4
1667
1.60
21
1790
1.96
25
1916
2.38
28

1192
0.60
11.5
1287
0.76
12.9
1385
0.96
14.6
1490
1.18
16.6
1599
1.45
18.9
1716
1.76
22
1837
2.14
25
1960
2.58
29

Static Pressure in Inches wg


1.5
2
2.5

1259
0.71
12.0
1352
0.88
13.3
1448
1.09
15.1
1548
1.34
17.1
1654
1.62
19.6
1764
1.94
23
1881
2.32
26
2002
2.77
30

1470
1.12
14.4
1564
1.36
15.9
1659
1.64
18.6
1758
1.96
21
1863
2.32
24
1971
2.72
27

1576
1.38
16.4
1666
1.64
17.4
1761
1.95
19.9
1857
2.30
23
1955
2.70
25

2.75

3.5

1715
1.79
18.4
1808
2.11
21
1903
2.47
23
2001
2.89
26

1762
1.93
19.5
1853
2.26
21
1948
2.64
23

1851
2.23
22
1940
2.59
22

Performance certied is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

36

55

SWB-118 - Belt Drive


Series 100
3078

4.0

(350)

(559)

(359)

(51)

(1067)

3314
1 2
1

2238

(489)

(845)

(38)

(568)

6
5
4
3

2.5

2.0
1.5

3214 (817)
34 (864)

0.0
0

99

77

13

26

60

54

45

Do

0.5

14

20

1778 (454)

2338 (594)
25 (635)

16

1.0
2

12

no
ts
ele
ct
to
the
lef
to
f th
is s

1914

(492)

42

7
Static Pressure (in. wg)

1938

(498)

Static Pressure (Pa x 100)

3.0

1958

RPM
HP
Density 0.075 lb/ft3

3.5

urv
e

1418

yst
em
c

22

1334

(784)

39

52

65

Volume (cfm X 100)

Wheel Diameter = 19 (483)


Shaft Diameter = 1 (25)
Outlet Area = 1.87 ft2 (0.17 m2)
^Approximate Unit Weight = 312 lb. (142 kg)

20

40

60

80

100

Volume (m3/hr x 100)

Maximum BHP at a given RPM = (RPM/1150)3

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

(Maximum KW at a given RPM = (RPM/1268)3)

Maximum RPM = 1660


Tip Speed (ft/min.) = RPM x 4.78
(Tip Speed (m/s) = RPM x 0.0243)

SWB-118
CFM

Maximum Motor Frame Size = 213T

OV

1500

802

1900

1016

2300

1230

2700

1444

3100

1658

3500

1872

3900

2086

4300

2299

4700

2513

5100

2727

5500

2941

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
545
0.11
5.6
628
0.16
6.5
717
0.24
7.7
808
0.34
9.1
902
0.46
10.9
997
0.62
13.1
1095
0.82
15.5
1193
1.06
17.6
1291
1.34
20
1391
1.67
22
1491
2.05
24

0.5
667
0.19
6.6
728
0.25
7.2
806
0.34
8.2
892
0.46
9.8
980
0.61
11.7
1070
0.78
14.1
1162
1.00
16.3
1256
1.25
18.6
1351
1.55
21
1447
1.90
23
1544
2.31
25

Static Pressure in Inches wg


1.25
1.5
1.75

0.75

826
0.36
7.8
887
0.45
8.9
964
0.59
10.5
1047
0.75
12.5
1135
0.95
14.6
1223
1.18
16.9
1314
1.45
19.7
1405
1.77
21
1499
2.13
23
1593
2.55
25

969
0.58
9.9
1032
0.71
11.4
1109
0.89
13.2
1191
1.11
15.2
1279
1.36
17.6
1367
1.65
19.8
1457
1.98
21
1548
2.37
23
1640
2.80
25

1044
0.71
11.2
1102
0.86
12.5
1169
1.04
13.9
1247
1.27
15.8
1329
1.54
18.7
1417
1.85
20
1505
2.20
22
1594
2.60
24

1170
1.01
13.3
1229
1.20
14.8
1301
1.43
17.0
1379
1.72
18.4
1462
2.04
20
1550
2.42
22
1638
2.84
25

1233
1.17
14.3
1291
1.37
16.3
1352
1.60
17.9
1428
1.90
18.5
1506
2.24
20
1591
2.63
23

2.25

2.5

1349
1.55
17.0
1407
1.79
17.5
1475
2.08
18.8
1552
2.44
20
1631
2.85
23

1403
1.73
16.8
1461
1.99
17.8
1521
2.27
19.2
1596
2.64
21

1513
2.19
18.4
1572
2.49
19.7
1638
2.85
21

Performance certied is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

37

SWB-120 - Belt Drive


Series 100
3358

3.5

(51)

46

2118

3618
112

2412

(537)

(918)

(38)

(622)

1.5
3

1.0

0.0
0

1
2

47

3
4
5
Volume (cfm X 1000)

82

64

57

Do

70

0.5

13

Wheel Diameter = 21 8 (549)


Shaft Diameter = 1 (25)
Outlet Area = 2.23 ft2 (0.21 m2)
^Approximate Unit Weight = 374 lb. (170 kg)

2.0

11

27 8 (695)

35 (889)
37 (940)

RPM
HP
Density 0.075 lb/ft3

5
99

1938 (492)

2558 (651)

2.5

(1168)

Static Pressure (in. wg)

(537)

Static Pressure (Pa x 100)

21 2
(546)

2118

3.0
cur
ve

(391)

yst
em

(603)

eft
of
this
s

ot
he
l

1538

no
ts
ele
ct
t

(378)

2334

1478

(854)

10

12

Volume (m3/hr x 1000)

Maximum BHP at a given RPM = (RPM/943)3

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

(Maximum KW at a given RPM = (RPM/1040)3)

Maximum RPM = 1357


Tip Speed (ft/min.) = RPM x 5.23
(Tip Speed (m/s) = RPM x 0.0266)

SWB-120
CFM

Maximum Motor Frame Size = 215T

OV

1800

807

2250

1009

2700

1211

3150

1413

3600

1614

4050

1816

4500

2018

4950

2220

5400

2422

5850

2623

6300

2825

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
471
0.12
6.5
528
0.17
6.6
593
0.25
7.1
658
0.34
7.9
723
0.45
9.0
791
0.59
10.7
861
0.75
13.1
931
0.94
15.9
1003
1.16
17.6
1076
1.42
19.3
1151
1.73
21

0.5
591
0.22
6.5
633
0.29
6.7
686
0.38
7.3
743
0.49
8.3
807
0.62
10.0
873
0.79
12.3
937
0.98
14.4
1002
1.20
15.9
1069
1.45
17.8
1137
1.74
19.8
1207
2.06
21

0.75

728
0.42
8.0
770
0.52
8.1
820
0.64
9.1
877
0.79
10.9
937
0.97
13.0
1001
1.19
15.1
1067
1.45
16.8
1132
1.73
18.5
1196
2.04
19.3
1262
2.40
20

811
0.56
9.4
850
0.68
9.5
892
0.81
10.2
943
0.98
11.6
999
1.17
13.4
1057
1.40
15.3
1121
1.67
17.4
1186
1.98
18.5
1252
2.34
19.3
1316
2.71
21

Static Pressure in Inches wg


1.25
1.5
1.75

923
0.84
11.2
962
0.99
11.2
1006
1.17
12.4
1057
1.38
14.3
1113
1.62
16.2
1171
1.90
17.2
1234
2.23
18.1
1298
2.60
19.7

989
1.01
12.3
1028
1.18
12.4
1068
1.37
13.0
1113
1.59
15.0
1166
1.85
16.5
1222
2.15
17.0
1280
2.48
18.0
1342
2.87
20

1088
1.37
13.5
1128
1.58
13.7
1169
1.82
15.1
1217
2.09
16.4
1270
2.40
17.2
1327
2.75
18.7

2.25

2.5

1145
1.57
14.6
1184
1.80
14.9
1223
2.05
15.5
1267
2.33
16.7
1316
2.65
18.1

1237
2.02
16.4
1276
2.29
16.6
1316
2.58
17.8

1287
2.24
18.0
1326
2.53
18.2

Performance certied is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the
effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

38

SWB-124 - Belt Drive


Series 100
4058

4.0

(64)

3.0

3112

(657)

(38)

(800)

5
4
3

2.0
1.5

4534
112 (1162)

2.5

(1467)

is s

2578

5734

Wheel Diameter = 24 4 (629)


Shaft Diameter = 1 (25)
Outlet Area = 3.40 ft2 (0.32 m2)
^Approximate Unit Weight = 546 lb. (248 kg)

56

0.0
0

25

t
no
Do 4
14

60

36 (914)
4112 (1054)

0.5

89

1934 (502)

0
73

3118 (791)
3358 (854)

12

1.0

10

se
le
ct
to

(661)

Static Pressure (in. wg)

(667)

Static Pressure (Pa x 100)

26

2614

RPM
HP
Density 0.075 lb/ft3

3.5
cur
ve

(483)

yst
em

(635)

of
th

212

th
el
eft

19

(451)

25

1734

(1032)

6
8
Volume (cfm X 1000)

8
10
12
14
Volume (m3/hr x 1000)

10

16

12

18

20

Maximum BHP at a given RPM = (RPM/713) 3

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

(Maximum KW at a given RPM = (RPM/786)3)

Maximum RPM = 1225


Tip Speed (ft/min.) = RPM x 6.41
(Tip Speed (m/s) = RPM x 0.0326)

SWB-124
CFM

Maximum Motor Frame Size = 256T

OV

2800

824

3400

1000

4000

1176

4600

1353

5200

1529

5800

1706

6400

1882

7000

2059

7600

2235

8200

2412

8800

2588

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.25
413
0.19
4.9
464
0.27
6.0
517
0.38
7.5
572
0.51
9.1
629
0.66
11.0
687
0.86
12.9
746
1.09
14.7
806
1.37
16.5
867
1.69
18.0
927
2.07
20
989
2.50
23

0.5

0.75

541
0.43
6.9
588
0.56
8.3
638
0.71
9.8
691
0.91
11.6
745
1.13
13.8
800
1.38
16.4
856
1.68
17.6
913
2.03
19.0
971
2.43
21
1030
2.88
23

651
0.74
9.2
696
0.92
10.7
744
1.13
12.7
795
1.39
15.5
849
1.68
16.8
903
2.01
18.2
958
2.38
19.9
1013
2.80
22
1070
3.27
24

751
1.14
11.8
795
1.37
14.0
843
1.64
15.6
893
1.96
17.2
945
2.32
19.2
999
2.74
21
1053
3.19
23
1108
3.69
24

Static Pressure in Inches wg


1.25
1.5
1.75

843
1.62
14.4
888
1.91
15.3
935
2.24
17.3
984
2.63
19.8
1037
3.07
22
1090
3.56
24
1144
4.11
25

930
2.18
15.7
976
2.54
17.6
1024
2.94
19.9
1073
3.40
22
1125
3.92
25
1178
4.49
26

1014
2.83
18.0
1061
3.26
20
1109
3.74
22
1158
4.28
25
1210
4.87
26

2.25

2.5

1055
3.15
18.5
1097
3.59
20
1144
4.09
23
1192
4.64
25

1132
3.92
21
1177
4.44
23
1224
5.02
25

1170
4.26
21
1209
4.79
23

Performance certied is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

39

SWB-206 - Belt Drive


Series 200
(219)

(508)

(248)

2
(51)

11

4.5

10

4.0

1114

(292)

(286)

2658

11

(676)

(279)

2114
112

1518

(540)

(38)

(384)

8
7
6
5
4

3.0
3

2.5

2.0
1.5

Wheel Diameter = 1138 (289)


Shaft Diameter = 3/4 (19)
Outlet Area = 0.63 ft2 (0.06 m 2 )
^Approximate Unit Weight = 140 lb. (64 kg)

not
Do

0.0
0

121

670
1

3
4
Volume (cfm X 100)
4

0.5

2514 (641)
2634 (679)

0
229

15 4 (400)

50
17

16 (406)
1678 (429)

0
283

1.0
2

RPM
HP
Density 0.075 lb/ft3

337

3.5
Static Pressure (in. wg)

11 2

Static Pressure (Pa x 100)

9
1

system
curve

934

of thi
s

20

the l
eft

858

sele
ct to

1834
(476)

10

Volume (m3/hr x 100)

Maximum BHP at a given RPM = (RPM/3629)3

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

(Maximum KW at a given RPM = (RPM/4001)3)

Maximum RPM = 3370


Tip Speed (ft/min.) = RPM x 2.91
(Tip Speed (m/s) = RPM x 0.0148)

SWB-206
CFM

Maximum Motor Frame Size = 145T

OV

70

111

120

190

170

270

220

349

270

429

320

508

370

587

420

667

470

746

520

825

570

905

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.5
1201
0.03
6.4
1262
0.04
6.8
1350
0.05
7.4
1489
0.07
8.0
1693
0.10
9.0
1921
0.14
10.5
2169
0.19
12.1
2422
0.26
13.7
2678
0.35
15.8
2936
0.45
18.5
3196
0.58
22

1.5

1.75

1722
0.09
9.2
1786
0.11
9.8
1868
0.13
10.7
1975
0.16
11.8
2138
0.20
12.9
2341
0.26
14.2
2567
0.33
15.8
2802
0.42
17.7
3051
0.53
19.3
3303
0.67
21

2079
0.16
11.9
2137
0.19
12.5
2203
0.22
13.3
2289
0.25
14.2
2395
0.28
15.2
2540
0.34
16.4
2721
0.41
18.1
2943
0.51
19.7
3170
0.62
21

2238
0.20
13.2
2292
0.23
13.8
2355
0.26
14.5
2429
0.29
15.3
2529
0.33
16.5
2643
0.39
17.6
2817
0.46
19.2
3010
0.55
21
3234
0.67
22

Static Pressure in Inches wg


2
2.5
2.75

2435
0.27
15.0
2497
0.31
15.8
2566
0.35
16.7
2659
0.39
17.8
2767
0.44
19.0
2907
0.51
20
3087
0.60
22
3296
0.72
23

2698
0.35
17.8
2760
0.40
18.6
2825
0.45
19.4
2898
0.50
20
2998
0.55
21
3108
0.62
22
3252
0.71
24

2822
0.40
19.1
2881
0.45
19.7
2945
0.51
20
3014
0.56
21
3108
0.62
22
3213
0.68
23
3330
0.77
24

3.5

3.75

2941
0.45
20
2997
0.51
21
3059
0.57
22
3128
0.62
22
3213
0.68
23
3313
0.74
24

3165
0.56
22
3216
0.61
23
3277
0.68
24
3343
0.75
25

3272
0.62
24
3319
0.67
24

Performance certied is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

40

11

SWB-207 - Belt Drive


Series 200
1834

(248)

(51)

(292)

(286)

26 8
5

11

(676)

(279)

21 4
1

112

1518

(540)

(38)

(384)

670
0

17

50

121

30

Wheel Diameter = 1138 (289)


Shaft Diameter = 3/4 (19)
Outlet Area = 0.63 ft2 (0.06 m 2 )
^Approximate Unit Weight = 140 lb. (64 kg)

28

70
33

90

2514 (641)
2634 (679)

16 8 (429)

1534 (400)

22

16 (406)

10

Static Pressure (in. wg)

1114

Static Pressure (Pa x 100)

12

1112

curv
e

(508)

RPM
HP
Density 0.075 lb/ft3

this
syst
em

(219)

14

the
left
of

934

no
ts
ele
ct t
o

20

Do

858

(476)

6
8
Volume (cfm X 100)
10
Volume (m3/hr x 100)

10

12

15

20

Maximum BHP at a given RPM = (RPM/3099)3

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

(Maximum KW at a given RPM = (RPM/3417)3)

Maximum RPM = 3370


Tip Speed (ft/min.) = RPM x 2.91
(Tip Speed (m/s) = RPM x 0.0148)

SWB-207
CFM

Maximum Motor Frame Size = 145T

OV

200

317

280

444

360

571

440

698

520

825

600

952

680

1079

760

1206

840

1333

920

1460

1000

1587

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.5
1098
0.04
6.2
1244
0.06
7.3
1415
0.09
8.5
1591
0.13
10.0
1793
0.19
12.6
2007
0.26
16.0
2226
0.36
18.4
2449
0.47
22
2678
0.61
25
2909
0.78
28
3142
0.97
30

1
1458
0.10
9.1
1549
0.12
9.7
1687
0.16
10.7
1855
0.21
12.4
2023
0.28
15.0
2195
0.35
17.1
2395
0.45
19.5
2600
0.58
23
2815
0.73
27
3034
0.90
29
3255
1.11
32

1.5

1808
0.19
11.1
1923
0.23
12.1
2064
0.29
14.2
2230
0.37
16.5
2404
0.47
18.9
2565
0.57
21
2751
0.69
24
2951
0.85
27
3156
1.03
30

2060
0.27
13.3
2139
0.32
14.1
2259
0.38
15.5
2406
0.47
17.9
2574
0.57
21
2751
0.70
23
2911
0.83
26
3084
0.98
28
3282
1.17
31

Static Pressure in Inches wg


2.5
3
3.5

2333
0.40
15.7
2446
0.48
17.4
2577
0.57
19.5
2725
0.68
22
2898
0.81
25
3075
0.97
27
3235
1.13
29

2534
0.51
17.7
2618
0.58
19.1
2735
0.68
21
2878
0.80
24
3034
0.93
25
3208
1.11
28

2777
0.68
21
2893
0.79
23
3021
0.92
25
3168
1.06
26
3332
1.24
29

4.5

2941
0.80
22
3040
0.91
24
3158
1.04
26
3300
1.20
28

3103
0.94
24
3179
1.03
25
3295
1.17
27

3255
1.07
25
3311
1.16
26

Performance certied is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

41

SWB-208 - Belt Drive


Series 200
1834

(248)

(51)

11

2658

(279)

2114

(676)

112

1518

(540)

(38)

(384)

8
6

50

22
17

121

670
2

70

Wheel Diameter = 1138 (289)


Shaft Diameter = 3/4 (19)
Outlet Area = 0.63 ft2 (0.06 m 2 )
^Approximate Unit Weight = 140 lb. (64 kg)

90

30

2514 (641)
2634 (679)

1678 (429)

1534 (400)

33

28

16 (406)

10

Do

1114
(286)

Static Pressure (in. wg)

1112
(292)

Static Pressure (Pa x 100)

12

RPM
HP
Density 0.075 lb/ft3

stem
curv
e

(508)

this
sy

(219)

14

left
of

934

the

20

no
ts
ele
ct
to

858

(476)

6
8
10
Volume (cfm X 100)
10

15

12

14

20

25

Volume (m3/hr x 100)

Maximum BHP at a given RPM = (RPM/3242)3


(Maximum KW at a given RPM = (RPM/3574)3)

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

Maximum RPM = 3370


Tip Speed (ft/min.) = RPM x 2.91
(Tip Speed (m/s) = RPM x 0.0148)

SWB-208
CFM

Maximum Motor Frame Size = 145T

OV

250

397

370

587

490

778

610

968

730

1159

850

1349

970

1540

1090

1730

1210

1921

1330

2111

1450

2302

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.5
1125
0.04
7.0
1270
0.06
7.7
1445
0.09
8.6
1640
0.12
9.2
1852
0.18
11.2
2076
0.24
13.5
2310
0.33
15.3
2548
0.44
17.5
2790
0.57
19.9
3035
0.73
22
3282
0.91
26

0.75
1343
0.06
8.0
1451
0.09
8.3
1606
0.12
9.1
1785
0.16
10.5
1980
0.22
12.4
2189
0.29
14.1
2409
0.38
16.0
2637
0.50
18.1
2872
0.63
21
3111
0.80
23
3352
0.99
25

1.5

1610
0.11
8.8
1753
0.16
9.7
1918
0.21
11.3
2101
0.27
12.9
2298
0.34
14.6
2507
0.44
16.6
2725
0.56
18.8
2951
0.70
21
3184
0.87
24

1909
0.18
10.9
2014
0.23
11.4
2160
0.29
12.5
2323
0.37
13.8
2505
0.45
15.6
2697
0.56
17.7
2896
0.69
20
3110
0.84
22
3329
1.02
25

Static Pressure in Inches wg


2
2.5
3

2172
0.26
13.2
2240
0.30
13.1
2378
0.38
14.4
2528
0.47
14.8
2693
0.57
16.5
2874
0.69
18.6
3065
0.82
21
3263
0.98
23

2472
0.39
15.3
2575
0.47
16.2
2715
0.57
17.8
2871
0.69
17.6
3041
0.82
19.5
3222
0.97
21

2681
0.49
17.6
2755
0.56
18.1
2892
0.68
19.9
3039
0.81
18.6
3198
0.95
20

3.5

4.5

2874
0.59
19.9
2941
0.67
21
3056
0.79
22
3196
0.93
22
3350
1.09
21

3121
0.79
22
3210
0.90
22
3348
1.06
23

3289
0.91
23
3357
1.01
23

Performance certied is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the
effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

42

16

SWB-210 - Belt Drive


Series 200
1834

(51)

2658

11

(676)

(279)

2114
112

1518

(540)

(38)

17

70

12

35

2514 (641)
2634 (679)

05

1534 (400)

40
28

23

16 (406)
1678 (429)

337

(384)

10

Static Pressure (in. wg)

1114
(286)

Static Pressure (Pa x 100)

11 2
(292)

12
1

RPM
HP
Density 0.075 lb/ft3

cur
ve

(248)

to
the
lef
to
f th
is s
yst
em

(508)

14

no
ts
ele
ct

934

Do

(219)

20

858

(476)

700

0
0

12

15

18

21

24

27

Volume (cfm X 100)

Wheel Diameter = 1138 (289)


Shaft Diameter = 3/4 (19)
Outlet Area = 0.63 ft2 (0.06 m2)
^Approximate Unit Weight = 140 lb. (64 kg)

10

20

30

40

Volume (m3/hr x 100)

Maximum BHP at a given RPM = (RPM/2649)3


(Maximum KW at a given RPM = (RPM/2921)3)

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

Maximum RPM = 3370


Tip Speed (ft/min.) = RPM x 2.91
(Tip Speed (m/s) = RPM x 0.0148)

SWB-210
CFM

Maximum Motor Frame Size = 145T

OV

625

992

800

1270

975

1548

1150

1825

1325

2103

1500

2381

1675

2659

1850

2937

2025

3214

2200

3492

2375

3770

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.5
1158
0.08
6.3
1311
0.12
7.4
1480
0.17
8.6
1661
0.24
10.0
1853
0.32
11.9
2054
0.43
14.0
2258
0.56
16.5
2465
0.72
18.3
2674
0.91
20
2885
1.13
22
3096
1.39
25

1
1501
0.17
7.6
1583
0.21
8.2
1714
0.27
9.5
1872
0.35
11.0
2041
0.45
12.9
2214
0.57
15.1
2402
0.71
17.0
2594
0.89
18.7
2793
1.09
21
2996
1.33
23
3201
1.60
25

1.5
1809
0.27
9.4
1846
0.31
9.8
1936
0.38
10.7
2063
0.47
12.3
2214
0.58
14.3
2381
0.72
16.0
2550
0.88
17.6
2724
1.06
19.3
2913
1.28
21
3104
1.53
24
3300
1.82
26

2106
0.44
11.9
2143
0.50
12.4
2250
0.60
13.9
2379
0.72
15.2
2528
0.87
16.6
2694
1.05
18.3
2863
1.25
20
3034
1.47
22
3214
1.73
24

Static Pressure in Inches wg


2.5
3
3.5

2334
0.58
13.9
2371
0.65
14.3
2431
0.74
14.8
2541
0.87
15.9
2676
1.03
17.3
2825
1.21
19.0
2990
1.43
21
3159
1.68
23
3329
1.95
25

2578
0.81
15.4
2615
0.90
15.8
2704
1.03
16.7
2815
1.20
18.1
2958
1.39
19.7
3108
1.61
21
3274
1.88
23

2768
0.97
16.6
2805
1.07
17.1
2854
1.19
17.6
2964
1.37
18.8
3082
1.58
20
3229
1.81
22

4.5

2982
1.26
18.3
3019
1.38
18.8
3103
1.55
19.6
3214
1.77
21
3345
2.01
23

3148
1.45
19.5
3185
1.58
20
3235
1.73
21
3344
1.96
22

3305
1.65
21
3342
1.79
21

Performance certied is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

43

SWB-212 - Belt Drive


Series 200
2138

(394)

(244)

(51)

14
5

12

1518

(38)

0
0

Wheel Diameter = 12 2 (318)


Shaft Diameter = 1 (25)
Outlet Area = 0.85 ft2 (0.08 m 2 )
^Approximate Unit Weight = 170 lb. (77 kg)

700
5

25

10

15
20
Volume (cfm X 100)

10

22910 (582)

17

121

55
27

21 8 (543)
3

40

12 (305)

22

16 (406)
1678 (429)

326

(384)

ft o
f

(330)

(565)

the
le

112

sel
ect
to

(721)

no
t

13

2214

10

Do

28 8
3

Static Pressure (in. wg)

13
(330)

Static Pressure (Pa x 100)

1314
(337)

RPM
HP
Density 0.075 lb/ft3

this
syst
em c
urve

958

(248)

1512

934

(543)

20

30

25

30

40

50

Volume (m3/hr x 100)

Maximum BHP at a given RPM = (RPM/2372)3

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

(Maximum KW at a given RPM = (RPM/2615)3)

Maximum RPM = 3262


Tip Speed (ft/min.) = RPM x 3.21
(Tip Speed (m/s) = RPM x 0.0163)

SWB-212
CFM

Maximum Motor Frame Size = 145T

OV

600

706

850

1000

1100

1294

1350

1588

1600

1882

1850

2176

2100

2471

2350

2765

2600

3059

2850

3353

3100

3647

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.5
1022
0.08
6.0
1150
0.11
7.2
1325
0.17
8.7
1522
0.25
10.5
1732
0.36
12.8
1947
0.50
15.6
2177
0.69
18.4
2409
0.92
21
2641
1.20
23
2874
1.53
27
3108
1.91
30

1
1372
0.16
7.9
1447
0.21
8.5
1561
0.28
9.8
1728
0.38
11.7
1905
0.51
14.0
2104
0.66
16.8
2312
0.86
19.0
2524
1.10
21
2739
1.39
24
2968
1.75
27
3199
2.17
31

1.5

1710
0.33
10.4
1799
0.42
11.4
1913
0.52
13.2
2080
0.67
15.7
2255
0.84
17.6
2443
1.05
19.7
2646
1.31
22
2855
1.62
25
3067
1.98
28

1941
0.45
12.7
2005
0.56
13.6
2113
0.68
14.9
2233
0.84
16.5
2403
1.03
18.4
2578
1.26
21
2761
1.53
23
2962
1.85
26
3169
2.23
29

Static Pressure in Inches wg


2.5
3
3.5

2208
0.71
15.2
2291
0.85
16.0
2404
1.02
17.4
2538
1.22
19.2
2708
1.47
21
2883
1.76
24
3065
2.10
27

2392
0.87
16.5
2457
1.03
17.2
2564
1.21
18.4
2679
1.43
20
2830
1.69
22
3001
2.00
25

2562
1.03
17.8
2625
1.21
18.5
2712
1.41
19.5
2825
1.65
21
2944
1.91
23
3112
2.24
26

4.5

2719
1.20
19.0
2783
1.40
19.8
2851
1.62
21
2962
1.87
22
3076
2.16
24

2931
1.59
21
2995
1.83
22
3091
2.10
23

3071
1.79
23
3135
2.05
23

Performance certied is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

44

35

SWB-213 - Belt Drive


Series 200
2338

(51)

(362)

3114

14

(794)

(356)

2434
112

1658

(629)

(38)

(422)

10

11

40

10

15

20

290

Do
700

60

24

Wheel Diameter = 1334 (349)


Shaft Diameter = 1 (25)
Outlet Area = 1.03 ft2 (0.10 m 2 )
^Approximate Unit Weight = 183 lb. (83 kg)

20
20

80

18 8 (479)

15

2712 (699)
3018 (765)

13 (330)

1758 (448)

Static Pressure (in. wg)

1414

1458
(371)

Static Pressure (Pa x 100)

12

RPM
HP
Density 0.075 lb/ft3

lef
to
f th
is s
yst
em
cur
ve

(270)

no
ts
ele
ct
to
the

(552)

(270)

14

1058

2134

1058

(594)

20
25
30
Volume (cfm X 100)

35

40

60

40

45

Volume (m3/hr x 100)

Maximum BHP at a given RPM = (RPM/2002)3

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

(Maximum KW at a given RPM = (RPM/2207)3)

Maximum RPM = 2902


Tip Speed (ft/min.) = RPM x 3.53
(Tip Speed (m/s) = RPM x 0.0179)

SWB-213
CFM

Maximum Motor Frame Size = 184T

OV

1000

971

1280

1243

1560

1515

1840

1786

2120

2058

2400

2330

2680

2602

2960

2874

3240

3146

3520

3417

3800

3689

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.5
998
0.12
6.9
1134
0.18
8.2
1290
0.26
9.6
1457
0.37
11.5
1629
0.51
13.7
1807
0.68
16.4
1987
0.89
18.8
2170
1.14
21
2355
1.44
23
2541
1.79
26
2729
2.19
29

0.75
1144
0.18
7.5
1248
0.24
8.7
1384
0.33
10.2
1540
0.45
12.0
1703
0.59
14.2
1874
0.78
17.0
2048
1.01
19.0
2226
1.27
21
2407
1.58
23
2589
1.94
26
2773
2.36
30

1
1287
0.24
8.4
1358
0.31
9.2
1478
0.40
10.8
1619
0.53
12.6
1775
0.69
15.0
1938
0.88
17.3
2107
1.12
19.3
2280
1.40
21
2457
1.72
24
2636
2.10
27
2817
2.53
30

Static Pressure in Inches wg


1.5
2
2.5
3

1585
0.46
11.0
1660
0.56
12.2
1778
0.70
14.1
1913
0.87
16.3
2063
1.09
18.1
2222
1.34
20
2386
1.64
22
2555
1.99
25
2727
2.40
27

1850
0.74
14.2
1931
0.89
15.5
2051
1.08
17.1
2184
1.30
18.8
2332
1.58
21
2489
1.89
23
2650
2.26
25
2816
2.68
28

2034
0.95
15.8
2093
1.10
16.5
2181
1.29
17.9
2307
1.53
19.7
2440
1.81
22
2587
2.16
24
2744
2.54
26

2249
1.32
17.7
2318
1.52
18.8
2423
1.78
20
2550
2.07
22
2685
2.42
25
2832
2.83
27

3.5

4.5

2462
1.77
19.8
2543
2.03
21
2656
2.34
23
2784
2.69
26

2596
2.03
21
2665
2.29
22
2758
2.62
24
2884
2.99
27

2730
2.31
23
2790
2.58
24
2869
2.90
25

Performance certied is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

45

SWB-215 - Belt Drive


Series 200
2534

(296)

(546)

(295)

(51)

14
5

12

(38)

left
of
27

4
260

18

00

22

00

600

0
0

00

18

10

27 8 (689)
3114 (794)
1

2118 (537)

the

15 (381)

00
14

20 (508)

(470)

se
lec
t to

1812

(699)

112

no
t

(403)

2712

Do

(883)

10

Static Pressure (in. wg)

15 8
7

3434

Static Pressure (Pa x 100)

1534
(400)

1614
(413)

RPM
HP
Density 0.075 lb/ft3

this
sys
tem
cur
ve

1158

2112

1158

(654)

36

45

54

Volume (cfm X 100)

Wheel Diameter = 1514 (387)


Shaft Diameter = 1 (25)
Outlet Area = 1.25 ft2 (0.12 m 2 )
^Approximate Unit Weight = 231 lb. (105 kg)

20

40

60

80

Volume (m3/hr x 100)

Maximum BHP at a given RPM = (RPM/1679)3


(Maximum KW at a given RPM = (RPM/1851)3)

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

Maximum RPM = 2604


Tip Speed (ft/min.) = RPM x 3.93
(Tip Speed (m/s) = RPM x 0.0200)

SWB-215
CFM

Maximum Motor Frame Size = 184T

OV

1200

960

1550

1240

1900

1520

2250

1800

2600

2080

2950

2360

3300

2640

3650

2920

4000

3200

4350

3480

4700

3760

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.5
886
0.15
6.9
1009
0.22
8.2
1150
0.32
9.7
1301
0.45
11.5
1458
0.62
13.8
1620
0.83
16.5
1785
1.09
19.0
1951
1.41
21
2120
1.78
24
2290
2.21
26
2460
2.72
30

0.75
1024
0.21
7.5
1112
0.29
8.7
1236
0.40
10.2
1377
0.54
12.1
1525
0.72
14.3
1680
0.96
17.0
1839
1.23
19.2
2001
1.56
21
2166
1.95
24
2332
2.41
27
2500
2.93
30

1
1157
0.29
8.5
1214
0.37
9.3
1322
0.49
10.8
1449
0.64
12.7
1591
0.84
15.0
1738
1.08
17.4
1893
1.37
19.4
2050
1.72
22
2211
2.13
24
2374
2.60
27

1.5

Static Pressure in Inches wg


2
2.5
3

1421
0.56
11.2
1487
0.68
12.3
1593
0.85
14.2
1715
1.07
16.3
1852
1.33
18.2
1996
1.65
20
2145
2.02
22
2299
2.46
25
2456
2.97
28

1661
0.91
14.4
1732
1.09
15.6
1840
1.32
17.2
1961
1.59
19.0
2095
1.94
21
2238
2.33
23
2385
2.79
26

1830
1.16
15.9
1879
1.34
16.6
1958
1.58
18.0
2072
1.88
19.8
2193
2.23
22
2326
2.66
24

2020
1.61
17.9
2083
1.86
19.0
2176
2.18
21
2293
2.54
23
2416
2.98
25

3.5

4.5

2165
1.92
19.3
2213
2.17
20
2285
2.49
22
2388
2.88
24

2333
2.48
21
2396
2.81
23

2456
2.83
23

Performance certied is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

46

SWB-216 - Belt Drive


Series 200
28

1 2

2038

(762)

(38)

95

600

3
4
Volume (cfm X 1000)
4

Wheel Diameter = 1634 (425)


Shaft Diameter = 114 (32)
Outlet Area = 1.52 ft2 (0.14 m 2 )
^Approximate Unit Weight = 251 lb. (114 kg)

65

10

3014 (769)
3238 (823)

16

20
20

16 (406)

237

13

2138 (543)
2278 (581)

(518)

no
t

(445)

30
1

(968)

10

17 2
1

Static Pressure (in. wg)

38 8
1

Static Pressure (Pa x 100)

17 2
(445)

17 4
(451)

12
3

RPM
HP
Density 0.075 lb/ft3

curv
e

(51)

this
sys
tem

(324)

left
of

(546)

14

the

(318)

se
lec
t to

1234

2112

1212

(711)

10

Volume (m3/hr x 1000)

Maximum BHP at a given RPM = (RPM/1414)3


(Maximum KW at a given RPM = (RPM/1559)3)

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

Maximum RPM = 2378


Tip Speed (ft/min.) = RPM x 4.32
(Tip Speed (m/s) = RPM x 0.0219)

SWB-216
CFM

Maximum Motor Frame Size = 184T

OV

1200

789

1650

1086

2100

1382

2550

1678

3000

1974

3450

2270

3900

2566

4350

2862

4800

3158

5250

3454

5700

3750

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.5
762
0.15
5.9
848
0.22
7.1
970
0.32
8.5
1109
0.46
10.1
1256
0.65
12.2
1410
0.90
14.6
1566
1.21
17.5
1724
1.59
19.7
1884
2.05
22
2046
2.60
25
2208
3.25
28

0.75
900
0.22
6.9
959
0.31
7.6
1059
0.42
9.0
1182
0.58
10.6
1320
0.79
12.7
1462
1.04
15.1
1616
1.37
17.6
1770
1.78
19.9
1926
2.25
22
2084
2.81
25
2244
3.47
29

1.5

1072
0.40
8.4
1147
0.53
9.6
1255
0.70
11.2
1381
0.92
13.3
1520
1.20
15.7
1661
1.53
17.9
1813
1.95
20
1967
2.45
23
2123
3.04
25
2279
3.71
29

1267
0.61
10.4
1322
0.77
11.1
1400
0.96
12.7
1505
1.20
14.7
1626
1.51
16.6
1758
1.89
18.5
1900
2.34
21
2042
2.85
23
2194
3.46
26
2348
4.19
30

Static Pressure in Inches wg


2
2.5
3

1487
1.03
13.3
1543
1.25
14.4
1629
1.52
15.7
1734
1.84
17.4
1853
2.24
19.3
1985
2.73
21
2124
3.29
24
2265
3.92
27

1632
1.30
14.8
1687
1.56
15.6
1749
1.85
16.6
1841
2.20
18.3
1950
2.61
20
2069
3.11
22
2200
3.72
25
2338
4.41
28

1818
1.88
16.8
1874
2.20
17.6
1949
2.57
19.2
2042
3.01
21
2156
3.53
23
2277
4.14
26

3.5

4.5

1939
2.21
18.1
1994
2.57
18.9
2050
2.96
20
2141
3.43
22
2239
3.97
24
2355
4.60
27

2106
2.94
20
2162
3.38
21
2234
3.86
23
2326
4.43
25

2211
3.33
21
2267
3.80
22
2324
4.30
24

Performance certied is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

47

SWB-218 - Belt Drive


Series 200
3078

(359)

(51)

19 4

3314

(1067)

112
2238

(489)

(845)

(38)

(568)

8
6
4

1
3

30

87

18

10

D
555

15

0
0

90

214

11

3214 (819)
34 (864)

1778 (454)

2338 (594)
25 (635)

10

42

Static Pressure (in. wg)

1938
(492)

1958

Static Pressure (Pa x 100)

12

(498)

RPM
HP
Density 0.075 lb/ft3

this
sys
tem
curv
e

(559)

to
the
left
of

(349)

14

no
ts
ele
ct

1418

22

1334

(784)

3
4
5
Volume (cfm X 1000)

Wheel Diameter = 1858 (473)


Shaft Diameter = 114 (32)
Outlet Area = 1.87 ft2 (0.17 m2 )
^Approximate Unit Weight = 324 lb. (147 kg)

Maximum BHP at a given RPM = (RPM/1196)3

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

Maximum RPM = 2147


Tip Speed (ft/min.) = RPM x 4.78

10

12

Volume (m3/hr x 1000)

(Maximum KW at a given RPM = (RPM/1319)3)

(Tip Speed (m/s) = RPM x 0.0243)

SWB-218
CFM

Maximum Motor Frame Size = 213T

OV

2000

1070

2500

1337

3000

1604

3500

1872

4000

2139

4500

2406

5000

2764

5500

2941

6000

3209

6500

3476

7000

3743

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.5
762
0.26
10.1
862
0.37
10.1
974
0.52
11.5
1092
0.72
13.6
1218
0.97
15.7
1346
1.28
18.2
1475
1.66
21
1605
2.10
24
1737
2.63
27
1869
3.26
31
2003
3.98
34

1
963
0.49
11.3
1023
0.62
11.6
1110
0.80
12.6
1211
1.03
14.2
1322
1.32
16.4
1438
1.66
18.8
1557
2.08
21
1683
2.58
24
1810
3.15
28
1938
3.81
31
2067
4.57
35

1.5
1136
0.75
13.4
1185
0.92
13.0
1245
1.12
13.9
1327
1.36
15.2
1423
1.68
17.3
1530
2.07
19.6
1643
2.52
22
1758
3.04
25
1877
3.65
28
2002
4.37
31
2128
5.18
35

1330
1.24
15.2
1380
1.47
15.5
1443
1.74
16.8
1525
2.07
18.7
1619
2.48
21
1723
2.97
24
1834
3.54
26
1949
4.18
29
2065
4.91
32

Static Pressure in Inches wg


2.5
3
3.5

1459
1.58
17.9
1507
1.85
18.3
1557
2.15
19.1
1626
2.51
21
1709
2.92
23
1804
3.43
25
1907
4.03
27
2017
4.72
30
2131
5.49
33

1623
2.24
21
1672
2.58
22
1727
2.95
23
1800
3.41
24
1885
3.91
26
1981
4.54
28
2084
5.25
31

1730
2.65
24
1779
3.02
25
1828
3.43
25
1890
3.90
26
1967
4.45
28
2055
5.07
30

4.5

1878
3.48
27
1927
3.93
27
1979
4.42
28
2048
5.00
29

1971
3.95
29
2020
4.44
29
2069
4.96
30

2060
4.43
31
2108
4.96
32

Performance certied is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

48

SWB-220 - Belt Drive


Series 200
3358

21 8
1

(1168)

112

24 2
1

(537)

(918)

(38)

4
6
Volume (cfm X 1000)
4

10

79

507

65

Wheel Diameter = 2038 (518)


Shaft Diameter = 114 (32)
Outlet Area = 2.23 ft2 (0.21 m2 )
^Approximate Unit Weight = 389 lb. (176 kg)

75

13

35 (889)
37 (940)

16

196

1938 (492)

85
10

2558 (651)
2738 (695)

(622)

3618

10

Static Pressure (in. wg)

46

Static Pressure (Pa x 100)

2118
(537)

21 2
(546)

12
1

sys
tem
curv
e

(51)

this

(390)

RPM
HP
Density 0.075 lb/ft3

the
left
of

(603)

se
lec
t to

(378)

14

no
t

1538

2334

1478

(854)

12

14

10

16

Volume (m3/hr x 1000)

Maximum BHP at a given RPM = (RPM/1027)3


(Maximum KW at a given RPM = (RPM/1132)3)

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

Maximum RPM = 1961


Tip Speed (ft/min.) = RPM x 5.23
(Tip Speed (m/s) = RPM x 0.0266)

SWB-220
CFM

Maximum Motor Frame Size = 215T

OV

2000

897

2650

1188

3300

1480

3950

1771

4600

2063

5250

2354

5900

2646

6550

2937

7200

3229

7850

3520

8500

3812

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.5
647
0.25
8.7
731
0.36
9.2
836
0.53
10.6
951
0.76
13.0
1072
1.06
15.2
1198
1.44
17.8
1325
1.90
21
1453
2.47
24
1583
3.15
28
1714
3.97
31
1846
4.92
36

1
860
0.51
11.5
897
0.65
11.2
970
0.85
12.1
1064
1.11
13.7
1171
1.46
15.8
1285
1.88
18.4
1401
2.40
21
1525
3.04
25
1650
3.78
28
1776
4.64
32
1904
5.63
36

1.5

1065
1.00
13.4
1104
1.21
13.5
1177
1.51
14.9
1267
1.88
16.8
1370
2.35
19.4
1481
2.92
22
1594
3.59
25
1711
4.37
28
1835
5.32
32
1960
6.38
37

1206
1.39
15.9
1243
1.64
15.8
1289
1.94
16.4
1364
2.35
18.4
1454
2.84
21
1555
3.45
24
1664
4.18
26
1777
5.01
29
1892
5.96
33

Static Pressure in Inches wg


2.5
3
3.5

1367
2.10
19.0
1405
2.43
19.4
1461
2.85
21
1539
3.37
23
1630
4.00
25
1731
4.76
27
1840
5.66
30
1952
6.67
34

1480
2.58
22
1517
2.96
23
1556
3.38
23
1624
3.94
25
1706
4.58
26
1799
5.37
29
1900
6.30
32

1621
3.51
26
1658
3.98
26
1708
4.52
26
1781
5.23
28
1867
6.01
30

4.5

4.75

1717
4.08
28
1754
4.60
28
1792
5.15
28
1857
5.87
30
1935
6.70
32

1807
4.67
30
1845
5.23
31
1882
5.83
31
1932
6.52
32

1851
4.97
32
1888
5.55
32
1925
6.18
32

Performance certied is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

49

SWB-222 - Belt Drive


Series 200
3678

(584)

4112
112 (1054)
(38)

(730)

74

477

70

179

153

12

Wheel Diameter = 2258 (575)


Shaft Diameter = 114 (32)
Outlet Area = 2.74 ft2 (0.25 m2 )
^Approximate Unit Weight = 450 lb. (204 kg)

05

3418 (867)
3958 (1006)

20 (508)

10

28 4 (718)
3012 (775)
1

Do

2834

Static Pressure (in. wg)

23

5212
(1334)

10

Static Pressure (Pa x 100)

2312
(597)

2334

12

(603)

curv
e

(64)

RPM
HP
Density 0.075 lb/ft3

this
syst
em

(432)

left
of

(610)

the

2 2

(413)

14

no
ts
ele
ct
to

17

24

1614

(937)

6
8
Volume (cfm X 1000)

10

10

15

20

Volume (m3/hr x 1000)

Maximum BHP at a given RPM = (RPM/897)3


(Maximum KW at a given RPM = (RPM/989)3)

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

Maximum RPM = 1798


Tip Speed (ft/min.) = RPM x 5.82
(Tip Speed (m/s) = RPM x 0.0296)

SWB-222
CFM

Maximum Motor Frame Size = 215T

OV

2500

912

3250

1186

4000

1460

4750

1734

5500

2007

6250

2281

7000

2555

7750

2828

8500

3102

9250

3376

10000 3650

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.5
602
0.30
9.3
677
0.43
9.7
768
0.61
11.2
868
0.86
13.6
976
1.18
15.8
1085
1.60
18.4
1197
2.10
21
1310
2.71
25
1424
3.43
29
1539
4.28
32
1655
5.28
36

1
783
0.59
11.5
831
0.77
11.5
892
0.99
12.6
975
1.27
14.2
1065
1.64
16.5
1164
2.09
19.0
1267
2.66
22
1376
3.32
25
1485
4.12
29
1596
5.04
32
1708
6.10
37

1.5
949
0.93
14.3
971
1.15
13.8
1019
1.43
14.3
1080
1.75
15.6
1158
2.14
17.5
1244
2.64
20
1339
3.23
23
1439
3.95
26
1542
4.80
29
1650
5.77
33
1760
6.87
37

1099
1.56
16.6
1137
1.88
16.8
1186
2.27
17.7
1249
2.70
19.5
1326
3.22
22
1410
3.85
25
1503
4.61
27
1601
5.47
30
1703
6.51
34

Static Pressure in Inches wg


2.5
3
3.5

1226
2.01
20
1241
2.36
20
1289
2.80
21
1339
3.30
22
1405
3.85
24
1484
4.52
26
1568
5.30
28
1659
6.22
31
1756
7.25
35

1347
2.88
24
1383
3.36
24
1432
3.91
25
1487
4.53
26
1553
5.20
27
1635
6.03
30
1719
6.98
32

1452
3.42
27
1470
3.92
27
1518
4.54
27
1567
5.22
28
1628
5.95
29
1698
6.78
31
1780
7.78
34

4.5

1556
4.52
29
1598
5.18
30
1647
5.92
30
1698
6.73
31
1764
7.59
33

1648
5.16
32
1674
5.84
32
1722
6.63
33
1771
7.50
34

1735
5.82
35
1746
6.51
35
1793
7.36
35

Performance certied is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

50

12

SWB-224 - Belt Drive


Series 200
4058

(635)

(483)

(64)

2578

4534

(657)

112 (1162)
(38)

3112
(800)

65

424
0

4112 (1054)
Wheel Diameter = 2434 (629)
Shaft Diameter = 112 (38)
Outlet Area = 3.40 ft2 (0.32 m 2 )
^Approximate Unit Weight = 568 lb. (258 kg)

6
8
Volume (cfm X 1000)
10

10

15

88

15

60
13

25
11

36 (914)

33 8 (854)

4
2

1934 (502)

0
89

3158 (803)

5734
(1467)

10

Static Pressure (in. wg)

(660)

26

2614

Static Pressure (Pa x 100)

12

(667)

RPM
HP
Density 0.075 lb/ft3

to
the
left
of t
his
sys
tem
cur
ve

(451)

2 2

14

no
ts
ele
ct

19

25

1734

(1032)

12

14

20

Volume (m3/hr x 1000)

Maximum BHP at a given RPM = (RPM/749)3


(Maximum KW at a given RPM = (RPM/826)3)

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown is largest cataloged Open Drip Proof motor

Maximum RPM = 1588


Tip Speed (ft/min.) = RPM x 6.41
(Tip Speed (m/s) = RPM x 0.0326)

SWB-224
CFM

Maximum Motor Frame Size = 256T

OV

3000

882

3900

1147

4800

1412

5700

1676

6600

1941

7500

2206

8400

2471

9300

2735

10200 3000

11100 3265

12000 3529

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.5
526
0.34
7.4
594
0.50
8.5
674
0.71
10.0
760
1.00
12.4
851
1.36
14.5
946
1.82
17.1
1041
2.38
20
1139
3.07
24
1239
3.89
28
1339
4.85
31
1440
5.98
34

0.75
614
0.51
9.1
659
0.68
9.4
729
0.92
11.0
809
1.24
13.0
894
1.64
15.2
982
2.13
17.8
1076
2.73
21
1170
3.44
25
1266
4.29
29
1364
5.28
32
1463
6.43
35

1
699
0.71
12.7
726
0.89
10.4
783
1.14
11.7
856
1.49
13.5
936
1.92
15.8
1020
2.44
18.6
1108
3.08
22
1200
3.83
25
1294
4.71
29
1390
5.73
32
1486
6.90
35

1.5

861
1.37
14.5
890
1.64
13.2
945
2.01
14.7
1015
2.49
17.0
1093
3.09
19.7
1175
3.79
23
1261
4.60
27
1348
5.55
30
1440
6.65
32
1534
7.89
36

Static Pressure in Inches wg


2
2.5
3

1001
2.20
16.1
1036
2.60
16.5
1093
3.11
18.2
1162
3.74
21
1240
4.51
24
1320
5.39
27
1404
6.41
30
1490
7.57
33

1106
2.84
18.9
1126
3.22
19.1
1171
3.77
20
1230
4.45
22
1301
5.24
25
1378
6.20
27
1458
7.28
30

1221
3.95
22
1251
4.49
23
1300
5.19
24
1362
6.03
25
1433
7.01
28
1510
8.16
31

3.5

4.5

1309
4.72
25
1329
5.24
25
1369
5.98
26
1423
6.85
26
1489
7.87
28

1411
6.10
27
1438
6.80
27
1484
7.69
28

1487
6.98
29
1508
7.65
29

Performance certied is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

51

SWB-327 - Belt Drive


Series 300
4614

(762)

(545)

(106)

16

2812 (724)

sys
tem
this

to
the
left
of

4
2

48 4 (1226)
52716 (1332)

Wheel Diameter = 27 (686)


Shaft Diameter = 11116 (43)
Outlet Area = 4.19 ft2 (0.389 m 2 )
^Approximate Unit Weight = 917 lb. (417 kg)

7
72 92
6 0
57 29
1

3534 (908)

10

31

33 (838)

12

(838)

13

(89)

25
14 5
5

312 (1292)

33

10

no
ts
ele
ct

(813)

32
5078

6134
(1568)

12

(727)

Static Pressure (in. wg)

(730)

2858

Static Pressure (Pa x 100)

14

2834

RPM
HP
Density 0.075 lb/ft3

6
curv
e

4316

15

21716

10

(540)

30

2114

(1175)

76

90

8
10
12
Volume (cfm X 1000)

10

15

14

20

16

25

Volume (m3/hr x 1000)

Maximum BHP at a given RPM = (RPM/629)3

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown includes largest cataloged Open Drip Proof motor and weatherhood

(Maximum KW at a given RPM = (RPM/693)3)

Maximum RPM = 1425


Tip Speed (ft/min.) = RPM x 7.07
(Tip Speed (m/s) = RPM x 0.0359)

Maximum Motor Frame Size = 256T

SWB-327
CFM

OV

5000

1193

5900

1408

6800

1622

7700

1837

8600

2052

9500

2267

10400 2482

11300 2696

12200 2911

13100 3126

14000 3341

52

RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA

0.5
1
551
663
0.66
1.10
10.3 / 72 11.8 / 75
604
712
0.89
1.40
11.5 / 74 12.9 / 76
666
764
1.17
1.75
12.9 / 76 14 / 77
731
815
1.53
2.17
14.5 / 78 15.2 / 79
801
872
1.97
2.65
16.3 / 80 17 / 80
871
934
2.51
3.23
18.5 / 82 19.2 / 82
942
997
3.14
3.90
21 / 84
22 / 84
1014
1066
3.89
4.70
24 / 86
24 / 86
1086
1135
4.74
5.62
27 / 88
28 / 88
1160
1205
5.72
6.67
30 / 90
32 / 91
1233
1276
6.83
7.85
35 / 92
37 / 93

1.5
756
1.57
13.2 / 77
800
1.92
14.1 / 78
849
2.34
15.2 / 79
900
2.83
16.6 / 80
951
3.40
18.3 / 81
1003
4.03
20 / 83
1059
4.76
22 / 85
1121
5.59
25 / 87
1184
6.54
29 / 89
1249
7.62
33 / 91
1317
8.87
38 / 94

Static Pressure in Inches wg


2
2.5
3
3.5
841
2.08
14.9 / 79
878
953
1022
2.48
3.07
3.69
15.6 / 79 17.6 / 81 19.6 / 83
923
991
1058
1120
2.95
3.59
4.26
4.96
16.6 / 80 18.2 / 82 19.9 / 83 22 / 85
971
1037
1098
1157
3.50
4.19
4.91
5.65
18.1 / 81 19.4 / 83 21 / 84
22 / 85
1022
1085
1145
1201
4.14
4.88
5.66
6.45
19.7 / 83 21 / 84
22 / 85
24 / 86
1074
1136
1194
1248
4.86
5.67
6.50
7.35
21 / 84
23 / 85
25 / 87
26 / 88
1125
1188
1244
1297
5.66
6.56
7.45
8.35
24 / 86
26 / 87
27 / 88
29 / 89
1177
1239
1296
1348
6.55
7.53
8.51
9.47
27 / 88
28 / 89
31 / 90
32 / 91
1236
1291
1347
1400
7.55
8.60
9.66
10.7
30 / 90
32 / 91
34 / 92
35 / 92
1298
1345
1399
8.68
9.78
10.9
35 / 92
36 / 93
37 / 93
1361
1407
9.94
11.1
39 / 94
40 / 94

4.5

1179
5.67
24 / 86
1215
6.43
24 / 86
1253
7.26
25 / 87
1299
8.21
28 / 89
1347
9.27
31 / 90
1397
10.5
33 / 91

1234
6.40
26 / 88
1270
7.22
26 / 88
1307
8.11
27 / 88
1348
9.10
29 / 89
1395
10.2
32 / 91

1322
8.02
28 / 89
1358
8.97
29 / 89
1395
10.0
30 / 90

Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values
shown are for inlet LwiA sound power levels and inlet hemispherical sone levels for installation type B: Free inlet, Ducted outlet, calculated per AMCA Standard 301.
The AMCA Certified Ratings Seal applies to air performance only.

18

30

SWB-327-AF - Belt Drive


Series 300
4614

(545)

(106)

32

(1568)

5078
(89)

48 4 (1226)

Do

3534 (908)

52716 (1332)
Wheel Diameter = 27 (686)
Shaft Diameter = 11116 (43)
Outlet Area = 4.19 ft2 (0.389 m 2 )
^Approximate Unit Weight = 877 lb. (399 kg)

6
61 71
0

76

5
84

2812 (724)

13

8
96

33 (838)

3 1

47
11

(838)

13

33

(813)

(1292)

50
14

312

10

Static Pressure (in. wg)

6134

Static Pressure (Pa x 100)

28 8
(727)

28 4
(730)

RPM
HP
Density 0.075 lb/ft3

12
5

urv
e

(762)

14

ec
tt
ot
he
lef
to
f th
is s
yst
em
c

4316

ot
se
l

21716

15

(540)

30

10

2114

(1175)

6
8
10
Volume (cfm X 1000)
10

15

12

20

14

16

25

Volume (m3/hr x 1000)

Maximum BHP at a given RPM = (RPM/671)3

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown includes largest cataloged Open Drip Proof motor and weatherhood

(Maximum KW at a given RPM = (RPM/740)3)

Maximum RPM = 1450


Tip Speed (ft/min.) = RPM x 7.07
(Tip Speed (m/s) = RPM x 0.0359)

Maximum Motor Frame Size = 256T

SWB-327-AF
CFM

OV

6000

1431

6700

1599

7400

1766

8100

1933

8800

2100

9500

2267

10200 2434

10900 2601

11600 2768

12300 2935

13000 3102

RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA

0.5
664
0.86
10 / 72
719
1.07
11.1 / 74
776
1.31
12.6 / 76
834
1.59
14.2 / 77
893
1.91
16.1 / 79
953
2.28
18.3 / 81
1013
2.70
21 / 83
1074
3.17
22 / 84
1136
3.70
23 / 85
1198
4.30
24 / 86
1260
4.96
26 / 87

1
755
1.38
11.3 / 74
804
1.63
12.4 / 75
856
1.92
13.7 / 77
908
2.24
15.4 / 79
963
2.61
17.3 / 81
1019
3.03
19.2 / 82
1075
3.51
20 / 83
1133
4.03
22 / 84
1192
4.61
23 / 85
1251
5.26
24 / 87
1311
5.96
26 / 88

1.5
833
1.90
12.6 / 75
881
2.21
13.8 / 77
928
2.55
15.3 / 79
977
2.93
16.8 / 80
1028
3.35
18.1 / 82
1081
3.82
19.3 / 83
1134
4.33
21 / 84
1189
4.91
22 / 85
1245
5.54
23 / 86
1301
6.24
25 / 87
1358
7.00
26 / 88

Static Pressure in Inches


2
2.5
3
906
975
2.44
3.01
14 / 77
15.6 /79
946
1013
1075
2.80
3.41
4.04
15.3 / 79 16.6 / 80 17.4 / 81
994
1052
1112
3.21
3.85
4.52
16.8 / 80 17.4 / 81 18.2 / 82
1041
1100
1152
3.64
4.35
5.05
17.7 / 81 18.4 / 82 19.1 / 82
1089
1147
1200
4.11
4.88
5.65
18.7 / 82 19.4 / 83 20 / 83
1139
1194
1247
4.62
5.45
6.29
19.7 / 83 20 / 84
21 / 84
1190
1243
1294
5.19
6.07
6.95
21 / 84
21 / 84
22 / 85
1242
1293
1342
5.81
6.73
7.68
22 / 85
23 / 85
23 / 86
1296
1345
1392
6.49
7.46
8.46
23 / 86
24 / 86
25 / 87
1351
1398
1443
7.23
8.25
9.29
25 / 87
25 / 87
26 / 87
1406
8.04
26 / 88

wg
3.5

1169
1223
5.22
5.93
19 / 82 19.9 / 83
1208
1260
5.79
6.54
19.8 / 83 21 / 84
1247
1299
6.41
7.21
21 / 84
22 / 85
1295
1340
7.12
7.94
22 / 85
23 / 85
1343
1388
7.86
8.75
23 / 86
24 / 86
1390
1435
8.62
9.59
24 / 86
25 / 87
1438
9.46
25 / 87

4.5

1310
7.32
22 / 85
1348
8.03
22 / 85
1387
8.79
23 / 86
1429
9.63
25 / 87

1395
8.86
23 / 86
1433
9.66
24 / 87

Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the
effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown
are for inlet LwiA sound power levels and inlet hemispherical sone levels for installation type B: Free inlet, Ducted outlet, calculated per AMCA Standard 301. The AMCA
Certified Ratings Seal applies to air performance and LwiA values only.

53

SWB-330 - Belt Drive


Series 300
5034

(848)

(605)

(106)

16
6

this
sys
tem
to
the
left
of
D

79

76

35

Wheel Diameter = 30 (762)


Shaft Diameter = 11516 (49)
Outlet Area = 5.17 ft2 (0.480 m 2 )
^Approximate Unit Weight = 1088 lb. (495 kg)

11

60 664
3
47 527
9

32

54 (1372)
58316 (1478)

3812 (978)

90

3178 (810)

10

3534 (908)

(930)

12

(89)

312 (1419)

3658

10

(895)

5578

no
ts
e le
ct

3514

6814
(1734)

12

(808)

Static Pressure (in. wg)

311316

3158

Static Pressure (Pa x 100)

14

(803)

RPM
HP
Density 0.075 lb/ft3

curv
e

(587)

4316

15

231316

10

3338

2318

(1289)

10
15
Volume (cfm X 1000)
10

15

20

25

20

30

35

Volume (m3/hr x 1000)

Maximum BHP at a given RPM = (RPM/527)3

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown includes largest cataloged Open Drip Proof motor and weatherhood

(Maximum KW at a given RPM = (RPM/581)3)

Maximum RPM = 1279


Tip Speed (ft/min.) = RPM x 7.85
(Tip Speed (m/s) = RPM x 0.0399)

Maximum Motor Frame Size = 256T

SWB-330
CFM

OV

7000

1353

8000

1547

9000

1740

10000 1934

11000 2127

12000 2321

13000 2514

14000 2707

15000 2901

16000 3094

17000 3288

54

RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA

0.5
1
531
630
1.02
1.62
12.7 / 76 13.8 / 77
580
671
1.31
2.00
13.9 / 77 15 / 79
631
713
1.67
2.43
15.1 / 79 16 / 80
686
755
2.12
2.93
16.7 / 80 17.4 / 81
742
804
2.65
3.51
18.4 / 82 19 / 82
799
855
3.28
4.18
20 / 83
21 / 84
857
906
4.00
4.95
22 / 85
23 / 85
915
962
4.84
5.85
25 / 86
25 / 87
974
1018
5.79
6.87
27 / 88
28 / 88
1033
1075
6.86
8.02
30 / 90
31 / 90
1093
1132
8.07
9.31
33 / 91
34 / 92

1.5
709
2.25
15.3 / 79
748
2.69
16.3 / 80
789
3.21
17.5 / 81
831
3.80
18.7 / 82
872
4.45
19.9 / 83
914
5.19
21 / 84
961
6.02
24 / 86
1011
6.96
26 / 87
1062
8.01
28 / 89
1114
9.19
32 / 91
1170
10.5
35 / 92

Static Pressure
2
2.5
782
849
2.93
3.65
16.7 / 80 18.5 / 82
816
879
3.42
4.19
17.6 / 81 19.1 / 82
854
914
4.00
4.82
18.7 / 82 19.9 / 83
894
953
4.66
5.54
19.9 / 83 21 / 84
936
993
5.40
6.35
21 / 84
23 / 85
978
1034
6.23
7.26
23 / 85
24 / 86
1019
1076
7.13
8.27
25 / 86
26 / 88
1061
1117
8.13
9.35
27 / 88
28 / 89
1109
1159
9.25
10.5
30 / 89
31 / 90
1159
1202
10.5
11.8
33 / 91
34 / 92
1210
1252
11.9
13.3
37 / 93
39 / 94

in Inches
3
911
4.39
20 / 84
940
5.00
21 / 84
970
5.68
21 / 84
1007
6.46
23 / 85
1045
7.32
24 / 86
1085
8.30
26 / 87
1127
9.38
28 / 88
1169
10.6
30 / 90
1210
11.8
33 / 91
1252
13.2
36 / 93

wg
3.5

4.5

997
5.83
23 / 86
1026
6.58
23 / 86
1057
7.39
24 / 86
1095
8.33
25 / 87
1134
9.36
27 / 88
1174
10.5
29 / 89
1215
11.8
32 / 91
1257
13.1
35 / 92

1050
6.69
25 / 87
1079
7.50
25 /87
1109
8.38
26 / 87
1142
9.35
27 / 88
1180
10.5
29 / 89
1219
11.6
31 / 90
1259
13.0
34 / 92

1128
8.44
27 / 88
1158
9.39
27 / 89
1188
10.4
28 / 89
1224
11.6
30 / 90
1262
12.8
33 / 91

1175
9.40
29 / 90
1204
10.4
29 / 90
1234
11.5
30 / 90
1266
12.7
32 / 91

Performance certied is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values
shown are for inlet LwiA sound power levels and inlet hemispherical sone levels for installation type B: Free inlet, Ducted outlet, calculated per AMCA Standard 301.
The AMCA Certied Ratings Seal applies to air performance only.

25

40

SWB-330-AF - Belt Drive


Series 300
5034

urve

stem
c
this
sy

ft o
f

he
le

02
11

56

38 2 (978)

51

54 (1372)
58316 (1478)

2
81

3178 (810)

9
70 4
64

3534 (908)

3
96

(930)

5
130
13

(1419)

(89)

RPM
HP
Density 0.075 lb/ft3

12

3658

3 2
1

to
t

3514
(895)

5578

10

Static Pressure (in. wg)

6814
(1734)

12

13

no
ts
ele
ct

(106)

Do

(605)

Static Pressure (Pa x 100)

(808)

(848)

14

15

31 16

4316

31 8
(803)

231316

10

(587)

3338

2318

(1289)

Wheel Diameter = 30 (762)


Shaft Diameter = 11516 (49)
Outlet Area = 5.17 ft2 (0.480 m 2 )
^Approximate Unit Weight = 998 lb. (454 kg)

10
15
Volume (cfm X 1000)
10

20

20

25

30

40

Volume (m3/hr x 1000)

Maximum BHP at a given RPM = (RPM/563)3

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown includes largest cataloged Open Drip Proof motor and weatherhood

(Maximum KW at a given RPM = (RPM/621)3)

Maximum RPM = 1305


Tip Speed (ft/min.) = RPM x 7.85
(Tip Speed (m/s) = RPM x 0.0399)

Maximum Motor Frame Size = 256T

SWB-330-AF
CFM

OV

8000

1547

8800

1702

9600

1856

10400 2011

11200 2166

12000 2321

12800 2475

13600 2630

14400 2785

15200 2940

16000 3094

RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA

0.5
631
1.23
11.7 / 75
678
1.49
13 / 76
726
1.79
14.1 / 78
775
2.14
15.6 / 79
825
2.53
17.3 / 81
875
2.97
19.2 / 82
925
3.46
21 / 84
976
4.02
24 / 86
1027
4.64
26 / 87
1079
5.32
27 / 88
1131
6.07
28 / 89

1
709
1.91
12.9 / 76
752
2.22
14 / 77
795
2.58
15.3 / 79
840
2.97
16.8 / 80
886
3.42
18.5 / 82
933
3.92
20 / 83
980
4.48
23 / 85
1028
5.09
24 / 86
1077
5.76
26 / 87
1127
6.50
27 / 88
1176
7.31
28 / 89

Static Pressure in Inches


1.5
2
2.5
3
779
839
901
957
2.61
3.31
4.05
4.81
14.2 / 77 15.5 / 79 16.9 / 80 18.4 / 82
818
878
933
988
2.98
3.76
4.53
5.34
15.4 / 79 16.7 / 80 18 / 81 19.6 / 83
858
918
970
1020
3.40
4.24
5.08
5.93
16.6 / 80 18 / 81 19.5 / 83 21 / 84
900
957
1010
1056
3.85
4.75
5.68
6.57
18 / 81 19.5 / 83 21 / 84
21 / 84
944
997
1049
1097
4.35
5.32
6.29
7.29
19.6 / 83 21 / 84
22 / 85
22 / 85
987
1039
1088
1136
4.91
5.92
6.96
8.01
22 / 84
22 / 85
23 / 85
23 / 86
1033
1082
1129
1175
5.51
6.58
7.68
8.79
23 / 86
23 / 86
24 / 86
24 / 86
1079
1126
1172
1215
6.18
7.31
8.46
9.64
24 / 86
24 / 86
25 / 87
25 / 87
1125
1171
1215
1257
6.92
8.09
9.30
10.5
26 / 87
26 / 87
26 / 87
27 / 88
1172
1217
1259
1300
7.72
8.95
10.2
11.5
27 / 88
27 / 88
27 / 88
28 / 89
1220
1263
1303
8.59
9.87
11.2
28 / 89
29 / 89
29 / 89

wg
3.5

4.5

1039
6.18
21 / 83
1071
6.81
21 / 84
1103
7.49
22 / 85
1139
8.25
23 / 86
1180
9.08
24 / 86
1219
9.92
25 / 87
1258
10.8
26 / 88
1298
11.8
27 / 88

1119
7.72
22 / 85
1150
8.45
23 / 85
1182
9.24
24 / 86
1219
10.1
25 / 87
1260
11.1
26 / 87
1299
12.0
27 / 88

1195
9.43
24 / 86
1227
10.3
25 / 87
1259
11.2
25 / 87
1297
12.2
27 / 88

1238
10.4
25 / 87
1269
11.3
25 / 87
1301
12.3
26 / 88

Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the
effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown
are for inlet LwiA sound power levels and inlet hemispherical sone levels for installation type B: Free inlet, Ducted outlet, calculated per AMCA Standard 301. The AMCA
Certified Ratings Seal applies to air performance and LwiA values only.
55

SWB-333 - Belt Drive


Series 300
55916

56 8 (1432)
60916 (1538)

41916 (1056)
Wheel Diameter = 33 (838)
Shaft Diameter = 11516 (49)
Outlet Area = 6.26 ft2 (0.582 m 2 )
^Approximate Unit Weight = 1231 lb. (560 kg)

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown includes largest cataloged Open Drip Proof motor and weatherhood

87

76

4
2

3178 (810)

3834 (984)

95

(1016)

(89)

no
t

312 (1543)

40

10

63
11
97
10

(1894)

(813)

6034

3814

74916

12

Do

(889)

Static Pressure (in. wg)

35

(878)

Static Pressure (Pa x 100)

34916

curv
e

6
14

this
syst
em

(106)

RPM
HP
Density 0.075 lb/ft3

left
of

(665)

the

(848)

16

se
lec
t to

(635)

4316

20

26316

15

3338

10

25

(1175)

64
2
56
50 1
44 9
5

10
15
20
Volume (cfm X 1000)
10

20

30

25

40

Volume (m3/hr x 1000)

Maximum BHP at a given RPM = (RPM/445)3


(Maximum KW at a given RPM = (RPM/491)3)

Maximum RPM = 1163


Tip Speed (ft/min.) = RPM x 8.64
(Tip Speed (m/s) = RPM x 0.0439)

Maximum Motor Frame Size = 256T

SWB-333
CFM

OV

7500

1198

9000

1437

10500 1677

12000 1916

13500 2156

15000 2396

16500 2635

18000 2875

19500 3115

21000 3354

22500 3594

56

RPM
BHP
Sones / LwiA
RPM
BHP
Sones
RPM
BHP
Sones / LwiA
RPM
BHP
Sones
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA

0.5
440
0.96
10 / 71
489
1.32
11.7 / 74
547
1.81
14.1 / 77
606
2.42
16.8 / 80
666
3.17
19.8 / 83
727
4.08
23 / 85
789
5.16
26 / 87
852
6.44
29 / 89
916
7.94
33 / 91
981
9.67
38 / 93
1046
11.6
42 / 95

Static Pressure in Inches


1
1.5
2
2.5
3
535
615
686
756
821
1.61
2.31
3.09
3.94
4.86
11.3 / 74 13 / 76 14.9 / 78 17.8 / 81 21 / 83
576
650
717
779
836
2.09
2.87
3.71
4.62
5.57
13.1 / 76 14.7 / 78 16.1 / 79 17.6 / 81 19.7 / 83
619
690
753
811
867
2.68
3.57
4.49
5.43
6.47
15.3 / 78 16.8 / 80 18 / 81 19.2 / 82 21 / 83
666
733
794
849
901
3.36
4.41
5.41
6.46
7.53
17.8 / 81 19 / 82
20 / 83
21 / 84
23 / 85
721
778
836
890
940
4.21
5.34
6.50
7.64
8.81
20 / 83
21 / 84
23 / 85
24 / 86
25 / 87
779
826
880
932
980
5.23
6.40
7.72
9.00
10.3
23 / 85
24 / 86
25 / 87
27 / 88
28 / 88
838
882
927
976
1023
6.44
7.70
9.05
10.5
11.9
26 / 87
27 / 88
29 / 89
30 / 89
31 / 90
898
940
978
1023
1067
7.83
9.21
10.6
12.1
13.7
30 / 90
31 / 90
32 / 91
34 / 91
35 / 92
958
998
1035
1070
1114
9.42
10.9
12.4
14.0
15.7
34 / 92
36 / 92
36 / 93
37 / 93
38 / 93
1019
1058
1093
1127
1161
11.3
12.9
14.5
16.1
17.8
39 / 94
39 / 94
40 / 94
41 / 95
42 / 95
1081
1117
1152
13.3
15.1
16.8
43 / 95
43 / 96
45 / 96

wg
3.5

4.5

895
6.60
23 / 85
919
7.55
22 / 85
950
8.66
24 / 86
987
10.0
27 / 87
1026
11.6
30 / 89
1067
13.3
32 / 91
1110
15.3
36 / 92
1154
17.4
39 / 94

951
7.68
26 / 87
968
8.65
25 / 86
999
9.86
26 / 87
1031
11.2
28 / 88
1070
12.9
31 / 90
1109
14.7
33 / 91
1151
16.8
37 / 93

1004
8.80
31 / 89
1018
9.83
28 / 88
1044
11.1
27 / 88
1075
12.5
29 / 89
1111
14.2
32 / 90
1150
16.1
35 / 92

1068
11.1
31 / 90
1088
12.3
29 / 89
1118
13.9
30 / 90
1150
15.6
33 / 91

Performance certied is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values
shown are for inlet LwiA sound power levels and inlet hemispherical sone levels for installation type B: Free inlet, Ducted outlet, calculated per AMCA Standard 301.
The AMCA Certied Ratings Seal applies to air performance only.

30

50

SWB-333-AF - Belt Drive


Series 300
55916

(106)

38 4
1

(1894)

6034

(813)

3 2 (1543)
1

Wheel Diameter = 33 (838)


Shaft Diameter = 11516 (49)
Outlet Area = 6.26 ft2 (0.582 m 2 )
^Approximate Unit Weight = 1166 lb. (530 kg)
All dimensions in inches (millimeters)
For additional discharge positions see page 15
^Weight shown includes largest cataloged Open Drip Proof motor and weatherhood

10
15
Volume (cfm X 1000)
10

86

69

56 8 (1432)
3

60916 (1538)

6
55 07
2

Do

38

94

10

3178 (810)

4
82

3834 (984)
41916 (1056)

RPM
HP
Density 0.075 lb/ft3

11

(89)

(1016)

40

10

74916

(889)

Static Pressure (in. wg)

35

(878)

Static Pressure (Pa x 100)

12

34916

10
is s
yst
em
cur
ve

(665)

lef
to
f th

(848)

14

no
ts
ele
ct
to
the

4316

20

26316

15

(635)

3338

25

(1175)

20

20

25

30

40

Volume (m3/hr x 1000)

Maximum BHP at a given RPM = (RPM/482)3


(Maximum KW at a given RPM = (RPM/531)3)

Maximum RPM = 1186


Tip Speed (ft/min.) = RPM x 8.64
(Tip Speed (m/s) = RPM x 0.0439)

Maximum Motor Frame Size = 256T

SWB-333-AF
CFM

9000

OV

1437

10000 1597

11000 1757

12000 1916

13000 2076

14000 2236

15000 2396

16000 2555

17000 2715

18000 2875

19000 3035

RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA

0.5
541
1.25
12.3 / 75
584
1.52
14.3 / 77
628
1.84
16.5 / 79
674
2.21
18.9 / 82
719
2.65
21 / 83
766
3.14
22 / 84
812
3.70
24 / 86
859
4.33
26 / 87
907
5.03
28 / 88
954
5.82
30 / 90
1002
6.67
32 / 91

Static Pressure
1
1.5
2
2.5
613
679
742
801
2.01
2.79
3.61
4.42
14.1 / 77 16.3 / 79 19.4 / 81 21 / 82
652
714
772
828
2.36
3.21
4.09
5.01
16.1 / 79 17.7 / 80 20 / 82
24 / 83
692
751
805
858
2.75
3.67
4.62
5.61
17.8 / 81 19.2 / 82 21 / 83
25 / 84
734
789
841
890
3.20
4.19
5.21
6.25
19.4 / 82 21 / 83
22 / 84
25 / 85
776
829
878
925
3.69
4.77
5.86
6.96
21 / 83
22 / 84
24 / 85
26 / 87
820
870
916
962
4.23
5.41
6.56
7.74
23 / 85
24 / 86
26 / 87
28 / 88
864
911
957
999
4.84
6.09
7.33
8.59
25 / 86
26 / 87
27 / 88
30 / 89
909
954
997
1039
5.52
6.83
8.17
9.49
27 / 88
28 / 88
29 / 89
31 / 90
954
998
1039
1079
6.28
7.65
9.08
10.5
29 / 89
30 / 90
31 / 90
33 / 91
1000
1042
1082
1120
7.13
8.54
10.0
11.6
31 / 90
32 / 91
33 / 91
34 / 92
1046
1086
1125
1161
8.07
9.51
11.1
12.7
33 / 91
34 / 92
36 / 92
37 / 93

in Inches wg
3
3.5

881
5.91
25 / 85
909
6.62
31 / 86
938
7.33
31 / 87
969
8.10
31 / 88
1005
8.94
31 / 89
1041
9.85
32 / 90
1078
10.8
33 / 91
1117
11.9
35 / 91
1157
13.0
36 / 92

956
7.63
31 / 87
985
8.44
39 / 89
1015
9.27
37 / 89
1046
10.2
35 / 90
1081
11.1
34 / 91
1117
12.2
36 / 91
1154
13.3
37 / 92

4.5

1003
8.55
31 / 89
1029
9.58
38 / 90
1058
10.5
43 / 91
1088
11.4
41 / 91
1119
12.5
39 / 92
1154
13.6
39 / 92

1072
10.6
36 / 90
1099
11.7
43 / 91
1128
12.7
46 / 92
1158
13.8
44 / 93

1139
12.8
42 / 92
1167
14.0
50 / 93

Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the
effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown
are for inlet LwiA sound power levels and inlet hemispherical sone levels for installation type B: Free inlet, Ducted outlet, calculated per AMCA Standard 301. The AMCA
Certified Ratings Seal applies to air performance and LwiA values only.

57

SWB-336
SWB- - - Belt Drive
Series
Series
300
61

(735)

(106)

Wheel Diameter = 3612 (927)


Shaft Diameter = 2316 (56)
Outlet Area = 7.66 ft2 (0.712 m 2 )
^Approximate Unit Weight = 1530 lb. (695 kg)

this
sy
1

1
0
0

10

73

64

54
2
376 430 474

51

10

5918 (1502)
63516 (1608)

10

3178 (810)

0
81

41 2 (1054)
45516 (1151)
1

92

(1130)

to t
he
left
of

(1705)

(89)

10

312
4412

(1067)

6718

no
ts
ele
ct

42

8234
(2102)

12

Do

(983)

Static Pressure (in. wg)

(972)

381116

Static Pressure (Pa x 100)

14

3814

RPM
HP
Density 0.075 lb/ft3

stem
curv
e

(848)

16

25

4316

20

281516

15

(692)

3338

10

2714

(1549)

15
20
Volume (cfm X 1000)
20

30

25

30

40

50

Volume (m3/hr x 1000)

Maximum BHP at a given RPM = (RPM/376)3

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown includes largest cataloged Open Drip Proof motor and weatherhood

(Maximum KW at a given RPM = (RPM/415)3)

Maximum RPM = 1051


Tip Speed (ft/min.) = RPM x 9.56
(Tip Speed (m/s) = RPM x 0.0486)

Maximum Motor Frame Size = 286T

SWB-336
CFM

OV

7500

979

9500

1240

11500 1501

13500 1762

15500 2023

17500 2284

19500 2545

21500 2806

23500 3067

25500 3328

27500 3590

58

RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA

0.5
362
0.86
10.7 / 71
405
1.25
11.9 / 73
456
1.77
13.7 / 76
513
2.46
16.2 / 79
572
3.35
19.1 / 82
631
4.45
22 / 85
692
5.79
26 / 87
754
7.41
29 / 89
817
9.33
33 / 91
881
11.6
38 / 93
944
14.2
43 / 96

1
454
1.54
10.8 / 73
490
2.06
12.6 / 75
531
2.74
14.6 / 78
575
3.56
17.1 / 80
623
4.54
19.9 / 82
680
5.80
23 / 85
738
7.30
27 / 87
796
9.07
30 / 90
855
11.1
34 / 92
916
13.5
39 / 94
976
16.3
45 / 96

1.5
532
2.33
12.9 / 76
561
2.94
14.1 / 77
597
3.73
16.1 / 79
638
4.72
18.7 / 81
680
5.89
21 / 84
727
7.21
24 / 86
778
8.80
27 / 88
835
10.7
31 / 90
892
13.0
35 / 92
951
15.5
40 / 94
1010
18.4
46 / 96

Static Pressure
2
2.5
606
3.24
16.1 / 79
625
685
3.90
4.95
15.9 / 79 18.7 / 82
656
712
4.76
5.91
17.8 / 81 19.3 / 82
694
745
5.87
7.07
20 / 83
21 / 84
734
784
7.20
8.52
22 / 85
24 / 85
777
825
8.75
10.2
25 / 86
27 / 87
823
867
10.4
12.2
28 / 88
30 / 89
870
913
12.4
14.3
32 / 90
33 / 91
926
959
14.8
16.6
37 / 92
38 / 93
983
1014
17.4
19.4
42 / 95
43 / 95
1041
20.5
47 / 96

in Inches wg
3
3.5

745
6.09
22 / 84
764
7.09
21 / 83
794
8.35
22 / 85
830
9.88
25 / 86
869
11.7
28 / 88
910
13.8
31 / 90
953
16.2
35 / 92
999
18.7
40 / 94
1045
21.5
44 / 95

813
8.34
23 / 85
841
9.70
24 / 86
873
11.3
26 / 87
911
13.2
29 / 89
951
15.4
33 / 91
992
18.0
37 / 92
1035
20.8
41 / 94

4.5

863
9.70
26 / 87
885
11.1
25 / 87
915
12.8
27 / 88
951
14.8
31 / 90
989
17.1
34 / 91
1030
19.8
38 / 93

911
11.1
30 / 89
926
12.5
28 / 88
957
14.3
29 / 89
988
16.4
32 / 90
1026
18.8
35 / 92

970
14.1
31 / 90
996
15.9
31 / 90
1026
18.0
33 / 91

Performance certied is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values
shown are for inlet LwiA sound power levels and inlet hemispherical sone levels for installation type B: Free inlet, Ducted outlet, calculated per AMCA Standard 301.
The AMCA Certied Ratings Seal applies to air performance only.

35

SWB-336-AF - Belt Drive


Series 300
61

(106)

(983)

42
(1067)

6718

79
8
69

1
7

5918 (1502)
63516 (1608)

46

51

3178 (810)

58

4112 (1054)
45516 (1151)

(89)

(1130)

87

4412

(1705)

312

(2102)

47
10 06
10

8234

10

Static Pressure (in. wg)

381116

38 4
(972)

Static Pressure (Pa x 100)

12
1

RPM
HP
Density 0.075 lb/ft3

25

(735)

14

20

(848)

4316

(692)

281516

15

33 8
3

10

2714

(1549)

0
0

10

15

20

25

30

Volume (cfm X 1000)

Wheel Diameter = 3612 (927)


Shaft Diameter = 2316 (56)
Outlet Area = 7.66 ft2 (0.712 m 2 )
^Approximate Unit Weight = 1445 lb. (657 kg)

10

20

30

40

50

Volume (m3/hr x 1000)

Maximum BHP at a given RPM = (RPM/408)3

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown includes largest cataloged Open Drip Proof motor and weatherhood

(Maximum KW at a given RPM = (RPM/450)3)

Maximum RPM = 1047


Tip Speed (ft/min.) = RPM x 9.56
(Tip Speed (m/s) = RPM x 0.0485)

Maximum Motor Frame Size = 286T

SWB-336-AF
CFM

OV

12000 1566

13000 1697

14000 1827

15000 1958

16000 2088

17000 2219

18000 2349

19000 2480

20000 2610

21000 2741

22000 2872

RPM
BHP
Sones / LwiA
RPM
BHP
Sones
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA

0.5
1
1.5
521
583
639
1.80
2.80
3.82
14.6 / 78 16.1 / 79 18.2 / 81
553
612
666
2.10
3.18
4.27
16.2 / 79 17.7 / 81 19.9 / 82
586
642
693
2.44
3.61
4.77
18 / 81 19.6 / 82 21 / 83
620
673
723
2.84
4.06
5.31
20 / 83
22 / 84
22 / 84
654
705
752
3.28
4.56
5.89
22 / 84
23 / 85
24 / 85
688
737
782
3.77
5.10
6.53
24 / 85
24 / 86
25 / 86
722
770
813
4.32
5.70
7.21
25 / 86
26 / 87
27 / 87
757
802
845
4.92
6.35
7.92
27 / 87
28 / 88
28 / 88
792
836
876
5.58
7.06
8.69
28 / 88
29 / 89
30 / 89
827
869
909
6.31
7.85
9.53
30 / 89
31 / 90
32 / 90
862
903
941
7.10
8.71
10.4
32 / 90
33 / 91
34 / 91

Static Pressure
2
2.5
693
744
4.89
6.00
21 / 82
24 / 84
716
766
5.41
6.58
22 / 83
25 / 85
742
788
5.96
7.20
23 / 84
26 / 85
769
813
6.57
7.87
24 / 85
26 / 86
796
839
7.23
8.59
25 / 86
27 / 87
825
866
7.93
9.37
27 / 87
29 / 88
854
893
8.69
10.2
28 / 88
30 / 89
884
922
9.50
11.1
30 / 89
31 / 90
915
952
10.4
12.0
31 / 90
33 / 91
946
981
11.3
13.0
33 / 91
35 / 92
977
1012
12.3
14.1
35 / 92
37 / 93

in Inches
3
792
7.06
26 / 85
812
7.80
28 / 86
833
8.48
30 / 87
856
9.21
31 / 88
879
9.99
31 / 88
905
10.8
31 / 89
932
11.7
32 / 90
959
12.7
34 / 91
986
13.7
35 / 92
1016
14.8
37 / 92
1045
15.9
38 / 93

wg
3.5

4.5

856
8.93
30 / 87
876
9.79
34 / 88
897
10.6
37 / 89
920
11.4
37 / 90
942
12.3
36 / 90
968
13.3
37 / 91
995
14.3
37 / 92
1021
15.4
38 / 92

917
11.0
34 / 89
937
12.0
40 / 90
959
12.9
44 / 91
981
13.9
43 / 92
1003
14.9
42 / 92
1029
16.0
42 / 93

976
13.3
40 / 91
996
14.4
47 / 92
1017
15.4
50 / 93
1040
16.5
48 / 93

1032
15.8
45 / 93

Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the
effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown
are for inlet LwiA sound power levels and inlet hemispherical sone levels for installation type B: Free inlet, Ducted outlet, calculated per AMCA Standard 301. The AMCA
Certified Ratings Seal applies to air performance and LwiA values only.
59

SWB-340 - Belt Drive


Series 300
661316

this
sys
tem
curv
e

to
the
left
of
5

10

40

10

0
0

62

54

46

87

Wheel Diameter = 4014 (1022)


Shaft Diameter = 2316 (56)
Outlet Area = 9.31 ft2 (0.865 m 2 )
^Approximate Unit Weight = 1709 lb. (777 kg)

62116 (1576)
6614 (1683)

49516 (1253)

4
2

3178 (810)

69

4512 (1156)

2
79

(1194)

RPM
HP
Density 0.075 lb/ft3

93

(89)

no
ts
ele
ct

(1819)

10

312

47

(1168)

7158

12

Static Pressure (in. wg)

46

89316
(2265)

14
Static Pressure (Pa x 100)

42 8
(1083)

(106)

42 16
(1072)

(810)

4 16

25

(848)

31 8

16

(752)

20

33 8
3

15

2958

10

(1697)

15
20
25
Volume (cfm X 1000)
20

30

40

30

35

50

60

Volume (m3/hr x 1000)

Maximum BHP at a given RPM = (RPM/321)3

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown includes largest cataloged Open Drip Proof motor and weatherhood

(Maximum KW at a given RPM = (RPM/354)3)

Maximum RPM = 936


Tip Speed (ft/min.) = RPM x 10.54
(Tip Speed (m/s) = RPM x 0.0535)

Maximum Motor Frame Size = 286T

SWB-340
CFM

OV

12500 1342

14250 1530

16000 1718

17750 1906

19500 2094

21250 2282

23000 2470

24750 2658

26500 2846

28250 3034

30000 3222

60

RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA

0.5
391
1.80
10.3 / 71
428
2.32
12.6 / 74
466
2.95
15.2 / 77
506
3.72
18.1 / 79
547
4.63
19.9 / 82
589
5.70
23 / 84
631
6.94
26 / 86
673
8.37
29 / 88
716
9.98
32 / 90
758
11.8
35 / 91
801
13.8
38 / 93

1
460
2.85
12.4 / 74
488
3.51
14.8 / 76
521
4.25
16.7 / 78
555
5.12
18.5 / 80
592
6.14
21 / 82
629
7.31
24 / 85
668
8.65
27 / 87
708
10.2
30 / 88
749
11.9
33 / 90
790
13.9
36 / 91
832
16.1
39 / 93

Static Pressure in Inches


1.5
2
2.5
3
521
575
625
671
3.92
5.06
6.29
7.56
13.9 / 76 15.6 / 78 17.3 / 80 19.4 / 81
547
599
646
691
4.70
5.93
7.22
8.61
15.8 / 78 17.4 / 79 19 / 81
20 / 82
575
625
670
712
5.60
6.95
8.34
9.76
17.8 / 80 19.4 / 81 21 / 83
22 / 84
603
652
697
738
6.63
8.10
9.60
11.1
19.9 / 81 22 / 83
23 / 84
24 / 85
636
680
724
764
7.75
9.40
11.0
12.7
22 / 83
24 / 85
25 / 85
26 / 86
670
710
751
791
9.02
10.8
12.6
14.4
25 / 86
26 / 86
27 / 87
28 / 87
706
744
780
818
10.5
12.4
14.3
16.3
28 / 87
29 / 88
30 / 88
31 / 89
743
778
813
846
12.1
14.1
16.2
18.3
30 / 89
31 / 89
32 / 90
33 / 90
781
814
847
879
14.0
16.1
18.2
20.5
33 / 90
34 / 91
35 / 91
36 / 92
819
851
881
912
16.0
18.2
20.5
22.8
36 / 92
37 / 92
39 / 92
40 / 93
860
889
918
18.3
20.6
23.0
40 / 93
41 / 93
42 / 94

wg
3.5

4.5

733
10.0
22 / 83
754
11.3
23 / 84
776
12.7
25 / 86
802
14.4
27 / 87
828
16.2
29 / 88
855
18.2
32 / 89
882
20.4
35 / 91
910
22.7
38 / 92

793
12.9
24 / 85
813
14.4
26 / 86
837
16.1
28 / 88
863
18.0
31 / 89
889
20.1
33 / 90
917
22.4
36 / 91

829
14.5
26 / 86
850
16.1
27 / 87
871
17.8
29 / 88
896
19.9
32 / 89
922
22.1
34 / 91

885
17.9
29 / 88
905
19.7
31 / 89
928
21.8
33 / 90

Performance certied is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values
shown are for inlet LwiA sound power levels and inlet hemispherical sone levels for installation type B: Free inlet, Ducted outlet, calculated per AMCA Standard 301.
The AMCA Certied Ratings Seal applies to air performance only.

40

SWB-340-AF - Belt Drive


Series 300
661316

(848)

(810)

(106)

5 7

4258
(1083)

89 16
3

46

71 8
5

(2265)
(89)

Wheel Diameter = 40 4 (1022)


Shaft Diameter = 2316 (56)
Outlet Area = 9.31 ft2 (0.865 m 2 )
^Approximate Unit Weight = 1579 lb. (718 kg)

Do

10

58

49

43

62116 (1576)
6614 (1683)

67

3178 (810)

74

4512 (1156)
49516 (1253)

8
84

(1194)

RPM
HP
Density 0.075 lb/ft3

94

47

(1168)

(1819)

312

10

Static Pressure (in. wg)

42316

Static Pressure (Pa x 100)

12

(1072)

15

10

he
lef
to
f th
is s
yst
em
cur
ve

(752)

14

4316

el
ec
tt
ot

3178

ot
s

3338

25

2958

20

(1697)

15
20
Volume (cfm X 1000)

25

30

35

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown includes largest cataloged Open Drip Proof motor and weatherhood

10

20

30

40

50

Volume (m3/hr x 1000)

Maximum BHP at a given RPM = (RPM/344)3


(Maximum KW at a given RPM = (RPM/379)3)

Maximum RPM = 949


Tip Speed (ft/min.) = RPM x 10.54
(Tip Speed (m/s) = RPM x 0.0535)

SWB-340-AF
CFM

OV

15000 1611

16500 1772

18000 1933

19500 2094

21000 2255

22500 2416

24000 2577

25500 2738

27000 2900

28500 3061

30000 3222

RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA

Maximum Motor Frame Size = 286T


Static Pressure in Inches
0.5
1
1.5
2
2.5
3
480
535
586
632
678
720
2.44
3.65
4.89
6.20
7.48
8.79
13.3 / 74 14.6 / 76 16 / 77 17.3 / 78 18.5 / 79 18.9 / 80
518
568
616
660
701
743
2.98
4.30
5.63
7.03
8.48
9.88
15.6 / 77 16.5 / 78 17.9 / 79 19.3 / 80 19.7 / 81 20 / 81
557
602
647
689
730
767
3.60
5.02
6.48
7.95
9.50
11.1
17.6 / 79 18.7 / 80 20 / 81
21 / 82
21 / 82
21 / 82
597
638
679
720
759
795
4.33
5.83
7.43
8.99
10.6
12.3
20 / 81
21 / 82
22 / 83
22 / 83
22 / 83
23 / 84
637
674
714
752
789
824
5.16
6.75
8.45
10.2
11.9
13.6
23 / 83
24 / 84
23 / 84
23 / 84
24 / 84
24 / 85
677
712
749
784
820
853
6.10
7.79
9.58
11.4
13.2
15.1
25 / 85
25 / 85
25 / 85
25 / 85
25 / 86
25 / 86
717
750
784
818
852
885
7.16
8.94
10.8
12.8
14.7
16.7
27 / 87
27 / 87
26 / 87
26 / 87
26 / 87
27 / 88
758
789
820
853
884
916
8.34
10.2
12.2
14.3
16.4
18.4
28 / 88
28 / 88
28 / 88
28 / 88
29 / 88
30 / 89
798
829
857
888
919
948
9.66
11.7
13.7
15.9
18.1
20.3
31 / 90
31 / 90
30 / 90
31 / 90
32 / 90
32 / 90
839
869
896
924
11.1
13.2
15.4
17.6
34 / 91
34 / 91
33 / 91
34 / 91
880
908
935
12.7
14.9
17.2
37 / 93
37 / 93
37 / 93

wg
3.5

4.5

782
11.3
21 / 82
806
12.6
22 / 83
830
14.0
23 / 84
858
15.4
25 / 86
886
17.0
27 / 87
916
18.6
29 / 88
947
20.4
31 / 90

819
12.8
21 / 83
842
14.2
22 / 84
865
15.7
24 / 85
889
17.3
26 / 86
918
18.9
28 / 88
947
20.7
30 / 89

876
15.8
24 / 85
899
17.4
25 / 86
923
19.1
27 / 87
947
20.9
29 / 89

931
19.1
27 / 87

Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the
effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown
are for inlet LwiA sound power levels and inlet hemispherical sone levels for installation type B: Free inlet, Ducted outlet, calculated per AMCA Standard 301. The AMCA
Certified Ratings Seal applies to air performance and LwiA values only.

61

SWB-344 - Belt Drive


Series 300
7338

(895)

(119)

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown includes largest cataloged Open Drip Proof motor and weatherhood

left
of t
his
sys
tem
the

t to
ele
c

no
ts
0

46

39

Wheel Diameter = 4412 (1130)


Shaft Diameter = 2716 (62)
Outlet Area = 11.39 ft2 (1.06 m 2 )
^Approximate Unit Weight = 2127 lb. (967 kg)

58

53

70516 (1786)
75 (1905)

66

3634 (933)

73

50 (1270)
5378 (1368)

(1321)

7
84
2
79

312 (2003)
(89)

52

10

5012
(1283)

7878

9858
(2505)

12

Static Pressure (in. wg)

4718
(1197)

4658

Static Pressure (Pa x 100)

14

(1184)

RPM
HP
Density 0.075 lb/ft3

curv
e

(970)

16

30

41116

25

3514

10

(821)

38316

20

32516

15

(1864)

10

10

20

20
30
Volume (cfm X 1000)
30

40

50

40

60

70

Volume (m3/hr x 1000)

Maximum BHP at a given RPM = (RPM/271)3


(Maximum KW at a given RPM = (RPM/299)3)

Maximum RPM = 847


Tip Speed (ft/min.) = RPM x 11.65
(Tip Speed (m/s) = RPM x 0.0592)

Maximum Motor Frame Size = 324T

SWB-344
CFM

OV

15000 1316

17000 1492

19000 1668

21000 1843

23000 2019

25000 2194

27000 2370

29000 2546

31000 2721

33000 2897

35000 3072

62

RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA

Static Pressure
0.5
1
1.5
2
2.5
350
413
468
517
563
2.12
3.38
4.67
6.06
7.55
10.7 / 72 12.5 / 74 14.6 / 76 16.6 / 78 17.7 / 80
381
436
490
537
580
2.70
4.12
5.54
7.02
8.60
12.7 / 74 14.6 / 76 16.9 / 78 17.7 / 80 19.2 / 81
413
463
513
559
600
3.39
4.95
6.54
8.15
9.81
14.9 / 76 17.1 / 78 18.7 / 80 19.4 / 81 21 / 82
446
492
537
582
622
4.23
5.89
7.67
9.42
11.2
17.6 / 79 20 / 80
20 / 81
21 / 83
23 / 84
481
522
563
605
645
5.21
6.99
8.91
10.9
12.8
21 / 81
22 / 82
22 / 83
24 / 84
25 / 86
516
554
592
629
668
6.35
8.26
10.3
12.4
14.5
23 / 83
23 / 84
24 / 85
26 / 86
28 / 87
551
585
621
657
692
7.67
9.69
11.9
14.1
16.4
25 / 85
26 / 86
27 / 87
29 / 88
30 / 88
586
619
652
685
718
9.18
11.3
13.6
16.0
18.4
28 / 87
29 / 88
30 / 88
31 / 89
32 / 89
622
653
684
715
746
10.9
13.2
15.6
18.0
20.6
31 / 89
32 / 90
33 / 90
34 / 90
35 / 91
658
688
716
746
775
12.8
15.2
17.7
20.4
23.0
35 / 91
36 / 91
36 / 91
37 / 92
38 / 92
695
723
749
777
804
15.0
17.5
20.1
22.9
25.7
38 / 92
38 / 92
39 / 93
40 / 93
41 / 93

in Inches wg
3
3.5

621
10.3
21 / 83
639
11.6
23 / 84
659
13.1
25 / 85
682
14.7
27 / 87
704
16.6
29 / 88
727
18.6
31 / 89
751
20.9
33 / 90
775
23.3
36 / 91
804
25.8
39 / 92
832
28.6
42 / 94

660
12.0
23 / 84
677
13.4
24 / 85
694
14.9
26 / 86
716
16.7
28 / 87
738
18.7
30 / 88
761
20.9
32 / 89
784
23.3
34 / 91
807
25.9
37 / 92
831
28.7
40 / 93

4.5

712
15.3
25 / 86
730
17.0
27 / 87
748
18.8
29 / 88
770
20.9
31 / 89
792
23.2
33 / 90
815
25.7
35 / 91
838
28.4
38 / 92

745
17.2
27 / 87
763
19.0
28 / 88
780
21.0
30 / 88
800
23.1
32 / 89
822
25.6
34 / 91
844
28.2
37 / 92

794
21.1
29 / 88
811
23.2
31 / 89
829
25.4
33 / 90

Performance certied is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values
shown are for inlet LwiA sound power levels and inlet hemispherical sone levels for installation type B: Free inlet, Ducted outlet, calculated per AMCA Standard 301.
The AMCA Certied Ratings Seal applies to air performance only.

50

80

SWB-344-AF - Belt Drive


Series 300
7338

(895)

(119)

47 8
(1197)

9858

5012

(2505)

7878
312

52

(1283)

(2003)

Wheel Diameter = 44 2 (1130)


Shaft Diameter = 2716 (62)
Outlet Area = 11.39 ft2 (1.06 m 2 )
^Approximate Unit Weight = 1997 lb. (908 kg)

10

15
20
25
30
Volume (cfm X 1000)

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown includes largest cataloged Open Drip Proof motor and weatherhood

42

Do

71

53 8 (1368)

70516 (1786)
75 (1905)

49

3634 (933)

3
2

7
62
0
57

50 (1270)

5
3

0
79

(1321)

7
4

860

(89)

10

Static Pressure (in. wg)

46 8
(1184)

Static Pressure (Pa x 100)

12
1

RPM
HP
Density 0.075 lb/ft3

10

yst
em
cur
ve

(970)

15

14

41116

no
ts
ele
ct
to
the
lef
to
f th
is s

3514

30

(821)

38316

25

32516

20

(1864)

20

35

40

40

45

60

Volume (m3/hr x 1000)

Maximum BHP at a given RPM = (RPM/291)3


(Maximum KW at a given RPM = (RPM/321)3)

Maximum RPM = 860


Tip Speed (ft/min.) = RPM x 11.65
(Tip Speed (m/s) = RPM x 0.0592)

Maximum Motor Frame Size = 324T

SWB-344-AF
CFM

OV

15000 1316

17000 1492

19000 1668

21000 1843

23000 2019

25000 2194

27000 2370

29000 2546

31000 2721

33000 2897

35000 3072

RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA

Static Pressure
0.5
1
1.5
2
2.5
376
433
484
532
2.03
3.26
4.56
5.86
10.1 / 71 11.8 / 72 13.9 / 75 15.5 / 77
411
463
511
555
597
2.56
3.94
5.38
6.85
8.32
12 / 73 13.7 / 75 15.6 / 77 16.8 / 78 18.2 / 79
447
494
539
581
621
3.20
4.74
6.29
7.93
9.57
14.3 / 76 15.8 / 77 17.2 / 78 18.6 / 79 19.9 / 81
485
528
570
609
646
3.97
5.64
7.34
9.09
10.9
16.9 / 78 18 / 79 19.2 / 80 21 / 81
22 / 82
524
562
601
639
674
4.87
6.66
8.54
10.4
12.3
19.5 / 81 20 / 81
22 / 82
23 / 83
24 / 84
563
598
634
670
703
5.92
7.83
9.87
11.9
13.9
22 / 83
23 / 83
24 / 84
26 / 85
26 / 85
602
634
668
701
734
7.12
9.16
11.3
13.5
15.7
25 / 85
26 / 85
27 / 86
27 / 86
27 / 86
642
672
703
734
765
8.50
10.66
12.9
15.3
17.6
28 / 87
29 / 88
29 / 87
29 / 87
29 / 87
682
711
739
769
797
10.1
12.4
14.7
17.2
19.8
31 / 89
31 / 89
31 / 89
31 / 89
30 / 89
722
750
775
803
831
11.8
14.2
16.7
19.4
22.1
33 / 90
33 / 90
33 / 90
33 / 90
33 / 90
762
789
813
839
13.8
16.3
19.0
21.7
35 / 92
35 / 92
35 / 92
35 / 92

in Inches wg
3
3.5

659
11.2
21 / 82
682
12.7
23 / 83
707
14.4
24 / 84
736
16.1
26 / 85
765
17.9
27 / 87
795
20.0
29 / 88
826
22.3
31 / 89
858
24.8
33 / 90

694
12.9
22 / 82
717
14.5
23 / 83
740
16.3
25 / 85
766
18.2
26 / 86
795
20.2
28 / 87
823
22.4
29 / 88
854
24.8
31 / 90

4.5

750
16.4
24 / 84
773
18.3
25 / 85
797
20.4
27 / 86
823
22.6
28 / 88
851
24.9
30 / 89

804
20.3
26 / 86
827
22.5
27 / 87
851
25.0
29 / 88

833
22.3
26 / 86
856
24.7
28 / 88

Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the
effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown
are for inlet LwiA sound power levels and inlet hemispherical sone levels for installation type B: Free inlet, Ducted outlet, calculated per AMCA Standard 301. The AMCA
Certified Ratings Seal applies to air performance and LwiA values only.

63

SWB-349 - Belt Drive


Series 300
80516

(1397)

8618

All dimensions in inches (millimeters)


For additional discharge positions see page 15
^Weight shown includes largest cataloged Open Drip Proof motor and weatherhood

curv
e

Wheel Diameter = 49 (1245)


Shaft Diameter = 2716 (62)
Outlet Area = 13.8 ft2 (1.28 m 2 )
^Approximate Unit Weight = 2433 lb. (1106 kg)

49

45

13

57

71

73 16 (1875)
7812 (1994)

3634 (933)

5412 (1384)
5838 (1483)

62

(1448)

67

(89)

76

312 (2188)
57

10

this
sys
tem

(2751)

55

108516

12

Static Pressure (in. wg)

(1313)

Static Pressure (Pa x 100)

51 16

51 16
(1303)

10

14
11

RPM
HP
Density 0.075 lb/ft3

to
the
left
of

(119)

no
ts
ele
ct

(970)

(984)

40

(894)

16

30

41116

25

38 16

3834

20

35316

15

(2040)

10

20

20
30
40
Volume (cfm X 1000)
40
60
Volume (m3/hr x 1000)

50

80

Maximum BHP at a given RPM = (RPM/231)3


(Maximum KW at a given RPM = (RPM/255)3)

Maximum RPM = 769


Tip Speed (ft/min.) = RPM x 12.83
(Tip Speed (m/s) = RPM x 0.0652)

Maximum Motor Frame Size = 324T

SWB-349
CFM

OV

20000 1449

22500 1630

25000 1811

27500 1992

30000 2173

32500 2355

35000 2536

37500 2717

40000 2898

42500 3079

45000 3260

64

RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA

Static Pressure
0.5
1
1.5
2
2.5
339
391
440
483
523
3.08
4.76
6.44
8.20
10.1
13 / 74 14.7 / 76 16.7 / 78 18.8 / 80 20 / 81
368
415
461
503
541
3.91
5.77
7.65
9.57
11.5
15.1 / 77 17.1 / 78 19.1 / 80 21 / 82
21 / 83
399
442
483
524
561
4.92
6.92
9.03
11.1
13.3
17.6 / 79 19.7 / 80 22 / 82
23 / 83
23 / 84
431
470
508
546
582
6.11
8.26
10.6
12.9
15.2
20 / 81
23 / 82
24 / 84
24 / 84
25 / 86
464
499
534
568
604
7.51
9.80
12.3
14.8
17.3
24 / 83
26 / 84
26 / 85
26 / 86
28 / 87
497
529
562
594
626
9.13
11.6
14.2
16.9
19.7
28 / 86
28 / 86
28 / 87
29 / 87
31 / 88
530
560
591
621
650
11.0
13.6
16.3
19.2
22.2
29 / 87
29 / 88
30 / 88
32 / 89
34 / 90
564
592
620
648
676
13.1
15.9
18.8
21.8
24.9
32 / 89
33 / 90
34 / 90
35 / 91
37 / 91
598
625
650
677
703
15.5
18.5
21.5
24.7
27.9
35 / 91
36 / 91
38 / 92
39 / 92
40 / 93
632
657
681
707
731
18.2
21.3
24.5
27.8
31.2
39 / 93
41 / 93
42 / 93
42 / 94
43 / 94
666
690
713
736
760
21.2
24.5
27.9
31.3
34.9
44 / 94
44 / 94
45 / 95
46 / 95
46 / 95

in Inches
3
560
12.1
21 / 83
577
13.7
23 / 84
595
15.5
25 / 85
616
17.5
27 / 87
637
19.8
30 / 88
658
22.4
33 / 90
680
25.1
35 / 91
703
28.1
38 / 92
730
31.3
41 / 93
756
34.8
44 / 94

wg
3.5
595
14.1
23 / 84
611
15.9
24 / 85
628
17.7
26 / 86
647
19.9
29 / 88
668
22.4
31 / 89
689
25.1
34 / 90
710
28.0
36 / 91
732
31.3
39 / 92
754
34.7
42 / 93

4.5

643
18.1
26 / 86
660
20.2
28 / 87
676
22.4
30 / 89
696
25.0
32 / 90
717
27.9
35 / 91
738
31.0
37 / 92
760
34.4
40 / 93

690
22.6
29 / 88
706
25.0
31 / 89
724
27.7
33 / 90
744
30.7
36 / 91
765
34.0
38 / 92

718
25.2
31 / 89
734
27.7
32 / 90
751
30.4
34 / 91

Performance certied is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values
shown are for inlet LwiA sound power levels and inlet hemispherical sone levels for installation type B: Free inlet, Ducted outlet, calculated per AMCA Standard 301.
The AMCA Certied Ratings Seal applies to air performance only.

60

100

SWB-349-AF - Belt Drive


Series 300
80516

(1303)

(1313)

108516

55

(2751)

(1397)

8618
312

57

(2188)

(89)

5
72

42

67

Do

73 16 (1875)
7812 (1994)

48

3634 (933)

61

53

5412 (1384)
5838 (1483)

780

(1448)

10

10
Static Pressure (in. wg)

511116

Static Pressure (Pa x 100)

51 16

RPM
HP
Density 0.075 lb/ft3

yst
em
cur
ve

(119)
12

20

15

is s

(984)

the
lef
to
f th

(970)

14

41116

ot
se
lec
tt

3834

40

(894)

38316

30

35316

25

(2040)

13

Wheel Diameter = 49 (1245)


Shaft Diameter = 2716 (62)
Outlet Area = 13.8 ft2 (1.28 m 2 )
^Approximate Unit Weight = 2298 lb. (1045 kg)
All dimensions in inches (millimeters)
For additional discharge positions see page 15
^Weight shown includes largest cataloged Open Drip Proof motor and weatherhood

0
0

10

20

20
30
Volume (cfm X 1000)
40

40

50

60

80

Volume (m3/hr x 1000)

Maximum BHP at a given RPM = (RPM/248)3


(Maximum KW at a given RPM = (RPM/273)3)

Maximum RPM = 780


Tip Speed (ft/min.) = RPM x 12.83
(Tip Speed (m/s) = RPM x 0.0652)

Maximum Motor Frame Size = 324T

SWB-349-AF
CFM

OV

20000 1449

22000 1594

24000 1739

26000 1884

28000 2028

30000 2173

32000 2318

34000 2463

36000 2608

38000 2753

40000 2898

RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA
RPM
BHP
Sones / LwiA

Static Pressure
0.5
1
1.5
2
2.5
365
413
457
499
537
2.93
4.56
6.27
7.99
9.74
12.4 / 73 13.7 / 75 15.5 / 77 17.5 / 79 18.9 / 80
391
437
478
517
555
3.54
5.31
7.13
9.06
10.9
13.7 / 75 15.2 / 76 17.1 / 78 18.8 / 80 20 / 81
419
461
501
537
572
4.24
6.18
8.11
10.2
12.3
15.6 / 77 17 / 78 18.9 / 80 20 / 81
21 / 82
448
486
524
559
592
5.04
7.10
9.20
11.4
13.6
17.7 / 79 19.1 / 80 20 / 81
22 / 82
23 / 83
477
512
547
581
613
5.96
8.14
10.4
12.7
15.1
20 / 81
21 / 82
22 / 82
24 / 83
25 / 84
506
539
572
604
635
7.00
9.30
11.8
14.2
16.6
23 / 83
23 / 83
24 / 84
26 / 85
27 / 86
536
565
597
628
658
8.17
10.6
13.2
15.8
18.3
25 / 85
26 / 85
27 / 86
28 / 86
30 / 87
566
594
623
652
681
9.48
12.0
14.7
17.5
20.2
27 / 86
28 / 87
29 / 87
31 / 88
32 / 88
596
623
650
678
705
10.9
13.6
16.4
19.3
22.3
30 / 88
31 / 88
32 / 89
33 / 89
33 / 89
626
652
676
703
729
12.5
15.4
18.3
21.3
24.5
33 / 89
34 / 90
35 / 90
35 / 90
34 / 90
656
681
704
730
754
14.3
17.3
20.3
23.5
26.7
36 / 91
37 / 91
36 / 91
36 / 91
36 / 91

in Inches wg
3
3.5

589
12.9
21 / 82
607
14.3
23 / 83
624
15.9
24 / 84
644
17.5
26 / 85
665
19.2
29 / 87
686
21.0
30 / 87
709
23.0
32 / 88
732
25.2
33 / 89
755
27.5
34 / 90
779
30.0
36 / 91

639
16.4
24 / 84
656
18.1
26 / 85
673
19.9
28 / 86
693
21.8
29 / 87
714
23.8
30 / 88
735
25.9
32 / 89
757
28.1
33 / 89

4.5

686
20.4
27 / 85
703
22.3
28 / 86
721
24.4
29 / 87
740
26.6
31 / 88
761
28.8
32 / 89

714
22.7
27 / 86
731
24.7
28 / 87
748
27.0
30 / 87
766
29.3
31 / 88

757
27.2
29 / 87
775
29.6
30 / 88

Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the
effects of appurtenances (accessories). The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown
are for inlet LwiA sound power levels and inlet hemispherical sone levels for installation type B: Free inlet, Ducted outlet, calculated per AMCA Standard 301. The AMCA
Certified Ratings Seal applies to air performance and LwiA values only.
65

Page Header
Specifications
Model SFD Direct
Drive Utility Fans
Supply, exhaust or return air
fans shall be of the direct
drive utility fan type, in AMCA
Arrangement 4 with a singlewidth, single-inlet housing, in
clockwise or counterclockwise
rotation as specified.
The housing shall be constructed of heavy-gauge
galvanized steel with lock formed seams permitting no
air leakage. The housing shall be easily rotated in the
field to any of the eight standard discharge positions.
Housing supports and drive frame shall be constructed
of heavy-gauge galvanized steel to minimize vibration
and rigidly support the motor and wheel.

The fan wheel shall be of the forward-curved type and


shall be constructed of heavy-gauge aluminum. Wheels
shall be statically and dynamically balanced. The wheel
cone and fan inlet cone shall be carefully matched for
maximum performance and operating efficiency. Motors
shall be heavy-duty ball bearing type matched to the
fan load and furnished at the specified voltage, phase
and enclosure.
All fans shall bear the AMCA Air Performance seal.
Utility fans shall be model SFD (with forwardcurved wheels) as manufactured by Greenheck Fan
Corporation of Schofield, Wisconsin, USA.

Model SWB Series 100, 200 and


300 Belt Drive Utility Fans
Supply, exhaust and return air fans shall
be of the belt-driven utility fan type in
AMCA Arrangement 10 with a singlewidth, single-inlet housing, in clockwise or
counterclockwise rotation as specified.
The housing shall be constructed of heavygauge galvanized steel on Series 100
Series 200
Series 100
Series 300
models and includes an airtight lock seam.
Series 200 and 300 models shall have a heavyWheels shall be statically and dynamically balanced.
gauge painted steel housing or optional aluminum
The wheel cone and fan inlet cone shall be carefully
housing on Series 200. Housing shall have an airtight
matched for maximum performance and operating
lock seam or optional welded seam. The housing shall
efficiency.
be field rotatable to any of the eight standard discharge
positions. To prevent vibration and to rigidly support
Motors shall be heavy-duty ball bearing type matched
the shaft and bearings, Series 100 and 200 drive frame
to the fan load and furnished at the specified voltage,
and bearing supports shall be constructed of welded
phase and enclosure. The fan shaft shall be ground and
steel members coated with Permatector and Series
polished solid steel mounted in heavy-duty pillow block
300 shall be constructed of reinforced heavy-gauge
ball bearings. Bearings shall be selected for a minimum
galvanized steel.
L10 life in excess of 100,000 hours (L50 average life of
500,000
hours) at maximum cataloged operating speed.
The fan wheel shall be of the non-overloading
Drives
shall
be sized for a minimum of 150% of driven
backward-inclined, centrifugal type. The fan wheel shall
horsepower.
Pulleys shall be of the fully machined cast
be constructed of heavy-gauge aluminum on Series
iron
type,
keyed
and securely attached to the fan and
200 fans sizes 206-210 and all Series 100 fans. Series
motor
shafts.
The
motor pulley shall be adjustable for
200 and 300 wheels shall be constructed of heavyfinal
system
balancing
for applications with 10 hp or
gauge steel with optional aluminum on Series 200 fans
less
motors.
size 212 and larger and all Series 300 sizes. Series
300-AF fans shall have an aluminum backward-inclined
airfoil wheel.

66

All fans shall bear the AMCA Air Performance seal.


Utility fans shall be model SWB (with backwardinclined wheels) as manufactured by Greenheck Fan
Corporation in Schofield, Wisconsin, USA.

SWB- Specifications
Series
Model SFB Belt
Drive Utility Fans
Supply, exhaust and return
air fans shall be of the
belt driven utility fan type
in AMCA Arrangement 10
with a single-width, singleinlet housing, in clockwise
or counterclockwise
rotation as specified.
The housing shall be
constructed of heavygauge steel with airtight lock formed seams. The
housing shall be easily rotated in the field to any of the
eight standard discharge positions. Housing supports
and drive frame shall be constructed of welded steel
members to prevent vibration and to rigidly support the
shaft and bearings.
Model SFB fan wheels shall be of the forward-curved
type, constructed of heavy-gauge steel with uniform
stamped steel blades.

Model SWD Direct


Drive Utility Fans
Supply, exhaust, and return air
fans shall be of the direct-driven
utility fan type in AMCA
Arrangement 4 with a single
width, single inlet housing, in
clockwise or counterclockwise
rotation as specied.
The housing shall be constructed
of galvanized steel, painted steel, or aluminum with
welded or air tight lock formed seams. Housings shall
be eld rotatable to any of the eight standard discharge
positions. Housing supports and drive frame shall be
constructed of heavy-gauge galvanized or painted steel
to minimize vibration and rigidly support the motor and
wheel.
The fan wheel shall be of the non-overloading backward
inclined, centrifugal fan type and constructed of
heavy-gauge aluminum. Wheels shall be statically
and dynamically balanced. The wheel cone and fan

Wheels shall be statically and dynamically balanced.


The wheel cone and fan inlet cone shall be carefully
matched for maximum performance and operating
efficiency.
Motors shall be heavy-duty, ball bearing type, matched
to the fan load and furnished at the specified voltage,
phase and enclosure. The fan shaft shall be ground
and polished solid steel mounted in heavy-duty, sealed,
pillow block ball bearings. Bearings shall be selected
for a minimum L10 life in excess of 100,000 hours
(L50 average of 500,000 hours) at maximum cataloged
operating speed. Drives shall be sized for a minimum of
150% of driven horsepower. Pulleys shall be of the fully
machined cast iron type, keyed and securely attached
to the fan and motor shafts. The motor pulley shall be
adjustable for final system balancing.
All fans shall bear the AMCA Air Performance seal.
Utility fans shall be model SFB (with forwardcurved wheels) as manufactured by Greenheck Fan
Corporation of Schofield, Wisconsin, USA.

inlet cone shall be carefully matched for maximum


performance and operating efciency.
The motor shall be an electronic commutation (EC)
type motor specically designed for fan applications.
AC induction type motors are not acceptable. Other
examples of unacceptable motors are: Shaded Pole,
Permanent Split Capacitor (PSC), Split Phase, Capacitor
Start and 3 phase induction type motors. Motors shall
be permanently lubricated with heavy-duty ball bearings
to match the fan load and prewired to the specic
voltage and phase. The motor shall be controllable
down to 20% of full speed (80% turndown). Speed shall
be controlled by either potentiometer dial mounted on
the motor or by a 0-10 VDC signal. The motor shall be a
minimum of 85% efcient at all speeds.
Fan performance shall be based on tests conducted
in accordance with AMCA Standard 210 for air moving
devices, and fans shall be licensed to bear the AMCA
Certied Ratings Seal for air performance.
Utility fans shall be model SWD (with backward inclined
wheels) as manufactured by Greenheck Fan Corporation
in Schofield, Wisconsin, USA.

67

Vari-Green Specifications
Vari-Green Motor
Motor to be an electronic commutation (EC) motor
specically designed for fan applications. AC
induction type motors are not acceptable. Examples
of unacceptable motors are: Shaded Pole, Permanent
Split Capacitor (PSC), Split Phase, Capacitor Start
and 3phase induction type motors. Motors shall be
permanently lubricated with heavy-duty ball bearings to match the fan load and
prewired to the specic voltage and phase. Internal motor circuitry shall convert AC
power supplied to the fan to DC power to operate the motor. Motor shall be speed
controllable down to 20% of full speed (80% turndown). Speed shall be controlled
by either a potentiometer dial mounted on the motor or by a 0-10 VDC signal. Motor
shall be a minimum of 85% efcient at all speeds.

Vari-Green Controls
Constant Pressure
Greenhecks Constant Pressure system shall be a complete package designed to
regulate fan speed based on demand while maintaining a constant static pressure.
System shall include fan with Vari-Green Motor, Vari-Green Constant Pressure
control, transformer, and pressure tap. Vari-Green Constant Pressure control shall
have the transducer integrated with a touch button control panel. Control shall have
a run mode and a program mode preventing unwanted changes when in run mode.
Transformer shall be factory-supplied to provide power to the Vari-Green Constant
Pressure controller. System shall include a self-sealing aluminum pressure tube with
-inch connection. Fan shall be centrifugal direct drive type in upblast, downblast,
or inline conguration with controllable EC Vari-Green motor.

Remote Dial
Remote dial shall be a Vari-Green control specically designed to provide
0-10 VDC signal to Greenhecks Vari-Green Motor.

2-Speed
2-Speed control shall be a Vari-Green Control specically designed to allow the
Vari-Green Motor to operate at two distinct speeds. 2-Speed Control shall include
two dials that may be set at any point between 0 and 10 VDC and an integral
transformer capable of reducing 115/230 volt AC power to 24 volt AC power.

Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and
in the Library under Warranties.
Prepared to Support
Green Building Efforts

P.O. Box 410 Schofield, WI 54476-0410 Phone (715) 359-6171 greenheck.com

00.F&V.1020 R3 1-2014 SP
Copyright 2014 Greenheck Fan Corp.