Catalog C: UV-1-231F

AAF-HermanNelson
Self-contained Classroom Unit Ventilators
Models AZS, AZQ, AZR Air Cooled Units
Models AED, AEQ Air-To-Air Heat Pump Units
Models ARQ, ERQ Water Source Heat Pump Units
AAF-HermanNelson
Self-contained Unit Ventilators

Comfort Conditioning For:


School Classrooms Hotel Suites
Conference Rooms Recreation Rooms

Catalog UV-1-231F / Page 2 / (6/99) AAF-HermanNelson


Table of Contents

Quality Construction Features ................................................................. 4-5

Design Features ............................................................................................. 6


Welded Frame ........................................................................................................................... 7
Draw-thru Design ..................................................................................................................... 8
Motor/Bearings Design Features ............................................................................................... 9
Damper Operation .................................................................................................................. 10
Room Air/Outdoor Air Damper ............................................................................................. 11
Temperature Controls (MicroTech DDC) ......................................................................... 12-13
Unit Mounted Control Components ...................................................................................... 14
Louvers/Ventimatic Shutter ..................................................................................................... 15
Cabinets & Filters ................................................................................................................... 16
Heat Pump Operation ............................................................................................................. 17

Details and Dimensions ........................................................................ 18-21


Models AZS, AZQ, AZR, AED, AEQ .................................................................................... 18
Models ARQ, ERQ ............................................................................................................ 19-21

Application Considerations ........................................................................ 22


Water Source Heat Pump Models ........................................................................................... 22

Specifications ......................................................................................... 23-31


Air Cooled Units AZS, AZQ, AZR .................................................................................... 23-25
Air-To-Air Heat Pumps AED, AEQ ................................................................................... 26-28
Water Source Heat Pumps ARQ, ERQ .............................................................................. 29-31

1999 AAF-HermanNelson Incorporated

The information in this catalog supersedes and


replaces previous [catalogs][bulletins] with regards to
AAF-HermanNelson Incorporated Terminal Air
Conditioning products. Illustrations cover the general
appearance of AAF-HermanNelson products at the time
of publication. AAF-HermanNelson reserves the right
to make changes in design and construction at any time
without notice.

AAF-HermanNelson Catalog UV-1-231F / Page 3 / (6/99)


Take a Close Look at the Best Unit Ventilator
Ever Built . . . For Over 80 Years!

AAF-HermanNelson
Self-contained
Unit Ventilator
In 1917, AAF-HermanNelson began making within the unit. A refrigeration cycle is employed because they lack the ability to please everyone
Unit Ventilators and has been manufacturing to remove heat from the occupied space and all the time. With the Self-contained Unit Venti-
them longer than anyone else in the industry. Unit transfer it to the outdoors where it can be dissi- lator each room is independently controlled for
Ventilators have proven to be the most energy pated into the atmosphere. With a self-contained cooling and for heating. There is no need for central
efficient systems available for maintaining the system, there is no need for a chiller, chilled water cooling or heating systems, making the Self-
required amount of ventilation and precise piping, a remote condensating unit, etc., to contained Unit Ventilator less expensive to install.
temperature control. supply cooling.
Self-contained Unit Ventilators are available with
AAF-HermanNelson Unit Ventilator systems The Self-contained Unit Ventilator is ideal for factory furnished, fully automatic modulating
have an economical first cost and an economical retrofit projects. Many older buildings have very controls. These controls adjust quickly to
life cycle cost. Sophisticated devices modulate old, outdated heating systems and most often compensate for changes in activity and occupancy
individual room control to adjust quickly to have no cooling systems. so the proper learning environment can be
changes in activity levels and temperatures. maintained.
Sudden changes in occupancy are adjusted for in Additionally, these older buildings employed a
the same manner to maintain a comfortable large amount of asbestos insulating materials that These units are also designed to provide many
temperature throughout the day. can be toxic if disturbed. Once this material is hours of free cooling using extensive outside
disturbed, it must be removed by qualified abate- air capabilities. Even in cold northern climates,
The Self-contained Classroom Unit Ventilators ment professionals. The Self-contained Unit cooling can be required year round, often when
were designed to provide optimal comfort Ventilator is the perfect solution to this dilemma the outdoor temperature is below freezing. The
levels with minimal energy consumption. This is because there is no need to make structural modi- AAF-HermanNelson Classroom Unit Ventilator
made possible by State-of-the-Art controls and fications in order to add heating or cooling. The utilizes this free cooling to maintain an
superior outside air capabilities which allow the only wall modification necessary is to cut a hole for efficient method of comfort conditioning
unit to supply free cooling a large percentage the condensing section and the outside air louver. throughout the year.
of the time.
The Self-contained Unit Ventilator is a great Whatever the application may be, there is an
The term self-contained refers to the unit choice for new installations as well. Central cooling AAF-HermanNelson Unit Ventilator to meet
design, where the entire cooling function is done or central heating systems are often undesirable the need.

Catalog UV-1-231F / Page 4 / (6/99) AAF-HermanNelson


The Quality of the Energy Saving
Unit Ventilator System

Classroom Unit Ventilators


Quality built by AAF-HermanNelson
Certified to ISO 9002 to assure the highest quality product

Outside. . .
special care and quality
for a long-lasting look of
elegance and beauty.
All AAF-HermanNelson Unit Ventilators un- 3. Final steps are the application of specially
dergo special preparation to assure long-lasting formulated Thermosetting Urethane Powder
beauty, resistance to abuse and corrosion. to the exterior. This film is then oven-cured to These
assure maximum scuff and mar resistance.
You will find AAF-HermanNelsons finish meets important steps
your most rigid expectations. Here are some of 4. Textured Thermosetting Urethane Powder which assure years
the things we do to make sure it does: is highly resistant to scratches and surface
damage, is used on the top. of reliable
1. High-quality furniture steel is carefully inspected performance
before painting. Scratches and marks that 5. Finally, they are painstakingly inspected. We
might show through the finish are removed. know the next inspector is you. We want you
to be satisfied.
2. After fabrication, the metal undergoes a 5-stage
cleaning and phosphatizing process which
removes cutting oils and forming compounds
and prepares the surface for painting. This
assures a good bonding surface and reduces the
possibility of peeling or corrosion.

AAF-HermanNelson Catalog UV-1-231F / Page 5 / (6/99)


Design Features

AAF-HermanNelson Unit Ventilators are highly engineered


to provide an extensive offering of features.

AAF-HermanNelson is the classroom leader and Motor location out of airstream (away from Access panel interlock safety switch
has over eighty years of experience in classroom hot coil) extends motor life. provided on electric heat units.
environmental control. Many features are
Large diameter, hollow fan shaft provides Capillary-type overheat thermostat
standard for AZS, AZQ, AZR, AED, AEQ, ARQ
quiet, economical performance, directly con- provides overheat protection across entire
and ERQ models. These features are as follows:
nected motor provides for easier maintenance. electric heating coil length.
Multi-tap transformer provides fan motor DDC Controller provided with stand-alone
Tamper resisting, hex socket head,
speed control through High-Medium-Low- or network operation.
positive positioning threaded fasteners
Off switch.
furnished on all access panels. Oilable sleeve bearings standard on fan
Multiple fans provide precise, smooth, quiet motor and fan shaft end bearing for quietness
Welded galvanized steel unitized chas-
performance. and long life.
sis provides rattle-resistant operation.
Antiblow-thru, room air damper prevents Institutional quality cabinet has durable,
Insulated, galvanized steel drain pan
gusts of wind from blowing into room. textured, scuff-resistant, Charcoal Bronze, baked
has welded corners and mastic coating on
enamel top surface which results in low
exterior. Rigid, double wall, insulated outdoor
reflectivity. Baked alkyd enamel paint finish
damper of welded galvanized steel.
Hand of drain pan connection is field- in choice of standard colors on all other
reversible. Nylon damper bearings assure quiet, main- exterior panels.
tenance-free operation of room air, outdoor air,
Throwaway filter is included in all units as Removable bar discharge grille permits
and face and bypass dampers.
standard (electric heat units have permanent easy cleaning of fan housings.
filters). Steam distributing coils assure more even
Adjustable leveling legs compensate for
distribution of steam and more even discharge
Single air filter; indoor and outdoor air floor irregularities.
air temperature.
utilize a common filter.
Fiberglass insulated unit back also serves
Vacuum breaker relieves vacuum in steam
Draw-thru design provides uniformed air as an outdoor air seal.
coil to allow drainage of condensate from coil
distribution across the coil with an even
which eliminates water hammer and greatly Built-in pipe tunnel for field crossover of hot
discharge air temperature.
reduces the possibility of coil freeze-up. water or chilled water piping, electrical or
Energy efficient fan motor, permanent split refrigeration tubing.
Manual air vent and drain plug is
capacitor (PSC), plug-in type fits all size units.
furnished on all water coils. Three individual front access panels
Motor has built-in, automatic reset, provided for ease of maintenance and service.
UL/CUL built to insure compliance with safety
thermal overload protection.
standards.

Catalog UV-1-231F / Page 6 / (6/99) AAF-HermanNelson


Unitized Welded Galvanized Steel Frame

Unitized welded galvanized steel frame construction


makes this the most durable Unit Ventilator you can buy.

The AAF-HermanNelson unitized frame (see


Figure 7-3) resists vibration loosening and the
chain reaction of problems this can cause. It will
be as strong and as accurately assembled in 25 years
as it is the first day of installation. This construc-
tion assures correct alignment of fan shaft and
bearings, and prevents binding of dampers.
The AAF-HermanNelson Unit Ventilator is truly
engineered and manufactured to resist abuse over
the years.

Extra Strength
Assures Long Life
The unique benefits of the welded frame construc-
tion (see Figure 7-1) combined with AAF- Figure 7-1 Figure 7-2
HermanNelsons extra-strength steel bar grilles and AAF-HermanNelson Other, Competitive
heavy-gauge metal cabinet casings, provide full Welded Chassis Fastener Type Construction
assurance of trouble-free operation and long life.

Compare
Exclusive AAF-HermanNelson unitized welded
galvanized steel chassis construction is far superior
to the typical competitive fastener assembled
construction. Loosened fasteners usually lead
to vibration rattles and sagging panels. (see
Figure 7-2)

Figure 7-3
AAF-HermanNelson
Welded Chassis

AAF-HermanNelson Catalog UV-1-231F / Page 7 / (6/99)


AAF-HermanNelson Draw-Thru Design

Draw-Thru Design Permits Safer Supply Air

Location Of Heating Element


The heating element is located away from the Figure 8-1
top of the unit, eliminating damage from pencils, The AAF-HermanNelson design
crayons, sharp-pointed objects, paper, chewing Coil heating section is safely located
gum, etc., which may be dropped through the top. Filter below foreign object Dropzone.

Outdoor
Air
Room Air

Draw-Thru Design Results In Uniform Coil Face


Velocity And Even Discharge Air Temperatures

The AAF-HermanNelson Draw-Thru principle is


one of the most significant factors that sets the
AAF-HermanNelson apart from most competitive
models. With this system, fans draw air through the
entire heat transfer element (see Figure 8-2), rather
than blowing it through highly concentrated areas
of the element (see Figure 8-3).
Coil
There are two reasons why AAF-HermanNelsons
Draw-Thru Design is so effective:

(1) Draw-thru design provides uniform discharge


Air Flow Shaded
air temperatures.
Figure 8-2
(2) Draw-Thru fans assure complete, even, heat AAF-HermanNelson Draw-Thru Design With Even Air Distribution
transfer over the entire length of the heat exchanger
for more efficient Unit Ventilator operation.

Disadvantages of some Competitive Blow-Thru Designs

Uneven heat transfer


Uneven discharge air temperature elements must have uniform air distribution across
Coil
Uneven air flow them for optimum element life. Coil hot spots
Premature element failure due to hot spots result in any area that has a lesser amount of air
passing over it. These hot spots reduce element
In the typical blow-thru design (see Figure 8-3), life and are the single greatest cause of premature
air is forced through limited areas of the heat electric heating element failure . . . an unnecessary Coil
transfer element. As a result, uneven heat transfer and costly maintenance problem.
takes place, which translates to uneven discharge
temperatures. The use of the AAF-HermanNelson draw-thru
design with even air distribution over the entire Air Flow Shaded
On electric heat units, there is a constant heat input coil length will greatly reduce the number of Figure 8-3
along the total coil length in the form of electric electric heating element failures, and will extend Uneven Air Distribution with
energy, when the coil is energized. Electric heating the life of the heating elements. Typical Blow-Thru Designs

Catalog UV-1-231F / Page 8 / (6/99) AAF-HermanNelson


Motor Design Features/Quiet Operation

Advantages of Easy Motor Removal AAF-HermanNelson


Should it ever be required, motor removal is fast
AAF-HermanNelson and easy. Location of the AAF-HermanNelson High Tech Fan Design
Motors and Bearings motor (see Figure 9-3) is separate from the Assures Quiet Operation
complete fan assembly (which on many unit
ventilators must be removed with the motor. See
Figure 9-2). A 14 horsepower motor is used for Designed To Assure
all applications. Quiet Operation
The AAF-HermanNelson Unit Ventilator
Figure 9-1
Brushless Motor Located Out of Air Stream is engineered, and manufactured for quiet
Motor AAF-HermanNelson direct-connection drive operation. Airflow patterns, dampers, fans,
places the motor away from the hot coil, out of housings, shafts, motors, insulation, and all
the air stream. See Figure 9-3. This also other components are thoroughly evaluated
prevents motor strain often caused by Whipping and tested to assure quiet operation.
AAF-HermanNelson Unit Ventilator motors offer
low operating current and wattage. See Figure action of unsupported fans on double extended
9-1. This can result in savings up to hundreds shafts, which can lead to early motor failure.
of dollars per year. See Figure 9-2.

This permanent, split capacitor motor features Long-Life Bearings


automatic reset thermal-overload protection, and The rotating element has only one large, sleeve-
has no brushes, contacts or centrifugal starting type end bearing and two motor bearings for
switchesthe most common cause of motor failure. smoother operation. See Figure 9-4 and 9-3.
It is safely located out of the air stream and away Should end bearing replacement ever be required,
from the overheating effect of the heating coil. location of the bearing at the end of the shaft (not
in-board like some units - see Figure 9-2) makes
Another common cause of motor failure is a lack for easy access and fast replacement.
of lubrication. Even permanently lubricated
motors are supplied with recommended lubrica- Figure 9-5
tion charts calling for lubrication every five or ten Fan Wheel
years. For this reason we recommend that
maintenance instructions of the motor manufac-
turer be clearly followed. Figure 9-4. Long-Life Bearings Fan Wheel
The AAF-HermanNelson fan wheels with
offset blades, balanced and precise dimensions
ensure smooth, quiet, consistent performance.
Coupling In-Board See Figure 9-5.
Fans Motors Bearing Fans

Low Sound Level


AAF-HermanNelson fan housings are heavy-
gauge steel, and designed to permit air to
Double-extended shaft units with motor In-board bearing, with motor located in the expand after it leaves the fan for the smoothest,
located in the air stream air stream quietest air flow. Fans are slow-speed design,
balanced statically and dynamically for quiet
operation. Large fan shafts of ground and
Figure 9-2. Competitive Designs
polished steel operate safely, well below
critical speed. Modular fan construction also
Motor
Fans contributes to equal outlet velocities for quiet
operation. These performance-engineered
features result in a quiet Unit Ventilator.

End
Bearing
Coupling
Drive shaft solidly anchored and supported on Partition
both ends with motor located out of the air stream

Figure 9-3. AAF-HermanNelson Design

AAF-HermanNelson Catalog UV-1-231F / Page 9 / (6/99)


Damper Operation

Smooth Air Flow Eliminates Turbulence And Resulting Noise


Regardless of damper positions, AAF-HermanNelson Unit Ventilators permit an even air flow through the unit . . . with no obstructions or restricted
air passages to cause turbulance, vibration and noise.

Figure 10-1 The Unit Ventilator will be Fast morning warm-up


Return Air Mode sending heated room air into using 100% recirculated
your classroom. Usually this room air.
occurs before occupancy.

Figure 10-2 The Unit Ventilator will be Unit maintaining desired


Mixed Air sending a mixture of room air room temperature.
Mode and fresh outdoor air into your
classroom. This usually occurs
intermittently all day long.

Figure 10-3 The Unit Ventilator will be Natural cooling using


Outdoor Air sending only fresh, outdoor air maximum outdoor air.
Ventilation into your classroom to cool the
Mode room, counteracting the heat
generated by the pupils, lights
and sun. This also may occur
intermittently all day long.

Catalog UV-1-231F / Page 10 / (6/99) AAF-HermanNelson


AAF-HermanNelson
Room Air/Outdoor Air Dampers

The typical classroom is cooled by outdoor air With the roll damper type unit, when both out- Insulated Double
Walled Construction
over half the time, even in cold climates. It is door and room air are admitted to the unit, both
well recognized that cooling, not heating, is the filters are used. When outdoor air is admitted Turned Metal
main thermal problem in school classrooms. for natural cooling, it must now all pass through
only one filter. This increases the resistance to air Wool Mohair
Seal
It is therefore essential that unit ventilators flow considerably and reduces the total cfm de-
efficiently deliver outdoor air when classroom livered to the classroom.
conditions call for natural cooling. You buy the
unit for its natural cooling ability. With AAF- Typical roll damper units are fitted with filters
HermanNelson Unit Ventilators, you are assured which become contaminated at different rates, Wool Mohair
of having outdoor air whenever it is needed. which prevents delivery of rated air. In addition, End Seal
at filter changing time, only half-used filters are
Wool
AAF-HermanNelson Unit Ventilators use all the often replaced an additional cost. Mohair
filter area at all times for both outdoor air and Seal Turned
Metal
return air, providing relatively constant room air Even single filter units, whose design limits the
flow at all damper positions. (See Figure 11-1). outdoor air to one half of the filter area and the
Figure 11-4
room air to the other half, have an air delivery
AAF-HermanNelson
profile similar to that shown for the roll damper
Outdoor Air Damper
unit. (See Figure 11-3).

Both the room air and outdoor air dampers have


nylon damper bearings to assure quiet, mainte-
nance free operation.

Filter (1) Positive Sealing Damper


Dampers on AAF-HermanNelson Unit Ventilators
have turned metal on the long closing edges which
Outdoor
Room Air Filter provide positive sealing by imbedding into
Air virgin wool mohair. Dampers have wool mohair
R.A./O.A.
Divider
end seals thus preventing outdoor air from
Outdoor entering. (See figure 11-4)
Figure 11-1 Air
Room
AAF-HermanNelson Design Air
Balanced Damper Design
The AAF-HermanNelson room air damper
Figure 11-3 design is free floating and prevents intermittent
Some competitors units, which utilize a singleroll Competitive Design
damper, and multiple filters, fail to deliver rated gusts of cold air from blowing directly into the
air in the outdoor air position because of vari- classroom on windy days (See figure 11-5).
able resistance to air flow within the unit (see
Figure 11-2).

Gust
AAF-HermanNelson of
Classroom Damper Features Wind
The standard AAF-HermanNelson outdoor air
Filter (2)
Room Roll damper is made of galvanized steel to inhibit
Air Damper corrosion, double wall welded construction for
Outdoor
Air rigidity and fiberglass insulation sandwiched
Filter (1) between the double wall. (See Figure 11-4)
Our outdoor damper has additional insulation Figure 11-5
Figure 11-2 on the exterior of the outside air damper blade AAF-HermanNelson
Competitive Roll Damper Design and on the outdoor air entry portion of the unit. Indoor Air Damper Design

AAF-HermanNelson Catalog UV-1-231F / Page 11 / (6/99)


AAF-HermanNelson Temperature Controls
MicroTech Direct Digital Control (DDC)

General On stand-alone units the heating setpoint is Room Air Temperature Sensors
McQuay International has developed a Direct Digital determined by the room temperature adjustment and Tenant Override
Control (DDC) package known as MicroTech, potentiometer setting. On network units this pot Room air temperature sensors are available for unit
designed specifically to provide sophisticated is inoperative and adjustment is done at the front mounting or wall mounting. Unit mounted room
temperature control of AAF-HermanNelson end computer. The cooling setpoint is determined air temperature sensors are located in a sampling
Classroom Unit Ventilators. The MicroTech DDC by adding the dead band to the heating setpoint. chamber located behind a grille in the front panel.
package can function either as a stand-alone A representative sample of room air is continuously
controller or as part of a network control from a Typical setpoint values for a heating/cooling unit drawn across the sensor in the sampling chamber
front end computer. would be 76F cooling and 70F heating. A room by the unit fans during the occupied cycle, thus
temperature above 78F will cause mechanical providing excellent room air temperature sensing.
The use of this AAF-HermanNelson MicroTech cooling to be initiated. A room temperature below No separate night setback thermostat is required for
DDC package assures a correct sequence of operation, 70F will cause heating to be initiated. When the the MicroTech DDC system. The same room air
as well as the elimination of any problems which room temperature is between 70F and 76F, no temperature sensor is used for both the occupied
may be associated with divided responsibility heating or mechanical cooling is permitted and this mode and the unoccupied mode. The unit mounted
between the unit manufacturer and the automatic is the dead band. configuration eliminates the problem of selecting
temperature control contractor. the optimum location for a wall mounted room
No energy other than fan energy is expended during air sensor.
Any stand-alone AAF-HermanNelson Unit Venti- this mode. The room temperature can be held
lator can be easily converted later to a networked between 70F and 76F during a substantial The following are the choices of room air tempera-
unit by the addition of a front end computer, portion of the school year simply by admitting more tures sensors available:
network components, communication wiring and or less outdoor air to offset the high internal heat
the simultaneous, one-time, global downloading of gains associated with school classrooms. 1. Unit Sensor with Tenant Override
a new software program into all microprocessors in This provides thermistor type temperature
the unit ventilator network. Minimum Outdoor sensing and a unit mounted tenant override
Air Potentiometer switch to allow timed override from unoccupied
Availability The minimum outdoor air pot located on the UVC to occupied mode.
MicroTech DDC packages are available for the allows user adjustment from 0% to 100% on stand-
following AAF-HermanNelson Self-contained Unit alone units. On network units the factory setting is 2. Wall Sensor with Tenant Override, Setpoint
Ventilators: 20% and any adjustment is done by the front end Adjustment, and Communications
computer with the pot on the UVC being inoperative. This provides thermistor type temperature sensing,
1. Air source heat pump with electric heat
2. Water source heat pump
3. Water source heat pump with electric heat
4. DX cooling only
5. DX cooling with electric heat
6. DX cooling with steam heat
7. DX cooling with hot water heat

MicroTech Unit Ventilator


Controller (UVC)
The brain of the HermanNelson Classroom Unit
Ventilators MicroTech DDC system is a micropro-
cessor-based board (UVC) located in the left end
compartment of the Unit Ventilator. The MicroTech
UVC utilizes digital control strategies to maintain
programmed heating, cooling and ventilation
setpoints. See Figure 12-1.

Dead Band
The AAF-HermanNelson MicroTech DDC system
utilizes separate heating and cooling setpoints. This
energy saving feature permits one-time setting of
the desired heating and cooling temperatures. This
eliminates the need to make seasonal thermostat
adjustments. The dead band is factory set at 6F. Figure 12-1. MicroTech Unit Ventilator Controller (UVC)

Catalog UV-1-231F / Page 12 / (6/99) AAF-HermanNelson


AAF-HermanNelson Temperature Controls MicroTech DDC . . . (Continued)

an LED unit mode indicator, a tenant override Modulating Control Valves system. The MicroTech DDC system uses the same
switch to allow timed override from unoccupied Steam valves are 2-way, normally open, angle room air sensor for both occupied (day) and unoc-
to occupied mode, and a setpoint offset adjust- pattern. Hot water and chilled/hot water (2-pipe) cupied (night) control which eliminates the usage of
ment potentiometer which allows the user to valves can be either 2-way or 3-way and are normally a separate night setback thermostat.
increase or decrease the current control setpoint open to the coil. Chilled water valves can be either
by 3F. A thermometer is provided along with a 2-way or 3-way and are normally closed to the coil. Steam and hot water units provide convective heat
communications port. See Figure 13-2. during the unoccupied cycle but remain under the
control of the room air sensor to prevent convective
LED Mode and Fault Indicator End-of-Cycle Valves overheating during the unoccupied cycle. When
A yellow LED is on the UVC board and a green Any unit with a steam coil that is Face & Bypass convective heat is insufficient to maintain the
LED on the wall mounted room air temperature Damper controlled also has a 2-position, 2-way, unoccupied heating setpoint, the unit fan motor is
sensors. Both LEDs emulate the UVC status by End-of-Cycle valve to shut off steam flow at the end energized until the room air temperature exceeds the
flashing at predetermined intervals to indicate: of the heating cycle. unoccupied heating setpoint.
Occupied Mode, Unoccupied Mode, Tenant Over-
ride Mode and Fault Conditions. Any unit with a hot water coil that is Face & Bypass With the MicroTech DDC system, the outdoor air
Damper controlled that also has a separate cooling damper remains closed during the unoccupied cycle.
Damper Actuators coil has a 2-position, 3-way, End-of-Cycle Valve to shut
The damper actuators are compact electric/ hydraulic off the hot water flow at the end of the heating cycle. Network Unit
type, factory-mounted, wired and adjusted. On No additional control wiring is required on
shutdown, the outdoor air damper will be closed Any two coil unit with a chilled water coil that is Face MicroTech Network units since the occupied/
and the face and bypass damper (when used) will be & Bypass Damper Controlled has a 2-position, 3- unoccupied changeover is accomplished via the
returned to the full face position allowing air thru way, End-of-Cycle Valve to shut off the chilled network communication wiring. MicroTech offers
the coil. See Figure 13-1. water flow at the end of the cooling cycle. a choice of 26 unique time schedules. Each Unit
Ventilator controller in the network can be assigned
Master/Slave Control its own time schedule or any number of unit venti-
The MicroTech DDC system has the capability of lators can be assigned to the same time schedule.
providing Master/Slave Control for up to a total of
6 Stand Alone Units. Master/Slave control for Stand Alone Units
network units is not required since the network Occupied/unoccupied changeover on Stand Alone
inherently allows all units in a given space to have the units can be accomplished: manually by a unit
same programmed setpoints if desired. mounted day-night switch in each unit, automati-
cally by a unit mounted time clock in each unit, or
The master unit provides the control input to the automatically by a remote mounted time clock
slaves that designates room heating and cooling which operates a unit mounted day-night relay in
setpoints (occupied and unoccupied), minimum each unit.
outdoor air damper position setpoint, and the
operating mode (occupied, unoccupied, or tenant The unit mounted time clock has a 24-hour dial
Figure 13-1. Damper Actuator override). with skip-a-day feature and battery back-up. The
time clock utilizes the unit line voltage power supply.
The object of Master/Slave control is to maintain a
uniform temperature throughout the space. This The remote mounted time clock can be furnished by
requires that each unit in the Master/Slave configu- others or by AAF-HermanNelson. The AAF-
ration has its own room air temperature sensor to HermanNelson time clocks are 120 volt, 24 hour
enable it to maintain the room heating or cooling with skip-a-day or 7 day and with or without reserve
setpoints dictated to it by the master unit. Commu- power. It is common practice to have more than one
nications for the Master/Slave configuration are by zone which requires a separate remote time clock
parallel wiring between the master and each slave unit. for each zone. The remote mounted time clocks
function is to energize or de-energize an external
The Master/Slave configuration requires only one (24 volt or 120 volt) control circuit which operates
day/night (occupied/unoccupied) changeover the unit mounted day-night relay in each unit in the
device and it is for the master unit only. zone. The control circuit must be deenergized by the
remote time clock during occupied cyle and
Night Setback Control General energized during unoccupied cycle.
AAF-HermanNelson offers various night control
Figure 13-2. Modulating Control Valve options to enhance the basic Unit Ventilator control

AAF-HermanNelson Catalog UV-1-231F / Page 13 / (6/99)


AAF-HermanNelson
Unit Mounted Control Components
Access
4 Motor 8 5 Door 6* 7*
9*
11*
3 10*

1
Compressor
Compartment

2
12

13 *Accessible Thru Access Door

Figure 14-1. Front View With Access Panels Removed

Figure 14-1 shows the location of the standard and dampers in response to the Unit Ventilator Controller 9. Holiday Switch (Accessory)
optional AAF-HermanNelson control items. The (UVC). Factory mounted, wired and adjusted. This device is furnished with the time clock, avail-
following is a general description of these components. able as an accessory. It permits manual changeover
4. Sampling chamber to unoccupied (night) control for extended or oth-
1. MicroTech Unit Ventilator Controller This enclosure houses the room air sensor when- erwise unscheduled periods. The switch must be
This is a factory mounted microprocessor-based ever a unit mounted sensor is specified. Room air manually returned to the normal (automatic con-
Direct Digital Control (DDC) device which is is continuously drawn through the sampling trol) position at the end of the holiday
capable of stand-alone control or network control chamber to ensure fast, accurate response to period for the unit to operate on the automatic
from a front end computer. The controller can temperature changes within the room. temperature control sequence.
support sixteen (16) inputs and sixteen (16)
outputs. Each input supports either analog sensing 5. Defrost timer 9. Day/Night Switch
and/or binary contact closure. Each output When the unit is in the heating mode, the out- This manual switch may be used in lieu of auto-
consists of a binary contact closure to operate door coil may operate at temperatures low enough matic unoccupied (night) control or remote
controlled devices. The controller will provide to cause frost to form on the outdoor coil. The unoccupied control. It permits manual changeover
status of either the outputs or the inputs upon unit has an automatic defrost cycle which operates to unoccupied control, but must be manually
request from a personal computer connected at a factory set interval of 90 minutes, but only if returned to the Day position for unit to operate
either to a network or an individual controller. the outdoor coil surface termperature is below on the automatic control sequence.
The controller contains self-diagnostic capability 28F (-2C). The timer is field adjustable for a 30
to maintain constant reliability. The controller or 45 minute interval. 10. Unit Main Power On-Off Switch
provides heating and cooling control in response Disconnects main power to unit for servicing the
to various inputs as well as the room sensor which 6. High-Medium-Low-Off unit or when unit is to be shut down for an
may be either unit mounted or wall mounted. Motor Speed Switch extended period.
Damper actuators are precisely positioned by Allows user to select the fan speed desired.
means of step-and-wait parameters built into The Off position shuts unit down completely. 11. Emergency Electric Heat Switch
control software. Two-position functions such as Should the reverse cycle heating system become
DX cooling and electric heating are also initiated 7. Tenant Override Switch inoperative, this device allows the unit to be manu-
by the controller. Room temperature adjustment, Allows the user to manually override the units ally switched to emergency electric heat. This will
unoccupied temperature offset and outdoor air occupied mode for up to a preprogrammed two permit the electric resistance heaters to operate as
damper minimum position are all adjustable at the hours.The tenant override value is resettable from needed regardless of outdoor temperature.
controller. In a network system, these three adjust- a personal computer connected either to a network
ments are not operative and are done as part of the or an individual controller. The tenant override 12. Right End Compartment
network control plan. switch can also be part of the wall room sensor. Class 1 wiring required.

The controller provides a visual means of fault 8. Time Clock (Accessory) 13. Left End Compartment
detection with the use of status LED on board. This device automatically cycles unit through Class 2 wiring required.
occupied and unoccupied modes in accordance
2. Room Temperature Adjustments with a user programmed time schedule. Program-
This item controls the room temperature setpoint. ming instructions are included. Time clocks have
battery backup so they will not require resetting if Not furnished with network units since the
3. Damper Actuator(s) electric power is interrupted. Located in front of function is handled through the communication
These devices position the outdoor and room air the room air fan motor. network.

Catalog UV-1-231F / Page 14 / (6/99) AAF-HermanNelson


Horizontal and Vertical Blade Louvers

Figure 15-1 see Figure 15-2). The double break design provides The core of the louver can be removed without
Water Source positive water impingement and entrapment but disturbing the frames weathertight seal that was
Heat Pump is slightly more restrictive than the horizontal made during installation.
Horizontal design louver.
Blade Louver Heavy-duty lattice grilles are also available for
The Air Cooled Unit and Air-to-Air Heat Pump either vertical or horizontal blade louvers. Grilles
Figure 15-2
Water Source
uses a vertical blade louver which is split horizontally can be furnished in unpainted, clear anodized or
Heat Pump to separate outside air intake to exhaust air from the painted heavy-gauge aluminum. The horizontal
Vertical Blade outdoor coil (see Figure 15-3). All louvers can be and vertical lines of the grilles are designed to line
Louver furnished unpainted, clear anodized aluminum, or up with the louver blades to present an aesthetic
painted with a color selected by the architect. They are appearance.
Figure 15-3
alloy AQ 5005, suitable for color anodizing by others.
Air Cooled
and Air-to-Air It is strongly recommended that an AAF-
Heat Pump AAF-HermanNelson Unit Ventilator louvers can HermanNelson louver be utilized because it is integral
Vertical Blade be used with panel wall, stud wall or masonry wall to the unit performance. Louvers made by other
Louver construction. All louvers contain weep holes manufacturers may be too restrictive or cause excessive
located in the exterior side of the weathertight recirculation of condenser air. Either of these con-
Two styles of louvers are available for AAF- frame to allow for removal of moisture such as ditions could have a serious negative effect on unit
HermanNelson Self-contained Unit Ventilators. rainwater or condensate overflow. performance and possibly cause unit malfunction.
The first style is an architectural design with Louvers by other manufacturers must always by
multiple break type horizontal blades (WSHP A wire mesh bird screen is factory installed on the tested and approved by AAF-HermanNelson prior
only, see Figure 15-1). The second style is a roomside of the louver and both horizontal and to their application with AAF-HermanNelson
vertical design with double break type aluminum vertical blade louvers have a demountable feature Self-contained Unit Ventilator products to ensure
blades which are split horizontally (WSHP only, to allow access to the unit from outside the building. satisfactory unit performance.

Ventimatic Shutter
considerable energy savings. In the heating mode, louvers on the same wall, equal pressure will keep
the unit ventilator brings in only the minimum excess air from entering through the unit ventila-
required percent of outside air. The Ventimatic tor. Same wall location also minimizes short cir-
shutter, in turn, exhausts a minimum amount. In cuiting of airflow that can occur with opposite wall
the cooling mode, when conditions allow, the unit locations. (See Figure 15-6)
Outdoor Bird Ventimatic ventilator brings in outdoor air for full natural
Louver Screen Shutter cooling: The Ventimatic shutter responds by Steel Interior

Figure 15-4. Ventimatic Shutter Assembly exhausting an equal amount. (See Figure 15-5) Wall Grille
(Optional)

As Directed 7" Cement


The Ventimatic shutter is a continuously variable, by Architect Mortar

gravity actuated, room exhaust vent which operates 3


4" Approx.

in direct response to positive static air pressure. Steel Shutter


Mounting Plate
Figure 15-5 Figure 15-6
(See Figure 15-5) Outdoor air which is introduced Installation Installation of
Bird Steel Baffle Not less
by the unit ventilator must leave the room in some Screen Leaf Support than 9" of Ventimatic Interior Wall Grille
(2 Req'd)
way. In some states, exhaust vents are required by Flexible Glass Fabric
Shutter to
Drain Silicone Impregnated Horizontal
law or code to accomplish this. The Ventimatic Holes Shutter Leaf (2 Req'd) The Ventimatic shutter is normally mounted on
Blade Wall
Shutter solves the problem. (See Figure 15-4) Cement 3
4" Approx. an exterior louver. Large units generally employ
Mortar Exhaust
Note: All dimensions approximated. Louver two Ventimatic shutters to insure adequate exhaust
The operation of the Ventimatic shutter is air capacity. The two shutters are mounted side-
inherently silent. The shutter flaps are made of When using the Ventimatic shutter exhaust by-side on the same outdoor louver. The size and
temperature resistant, glass fabric that is impreg- system it is important that the Ventimatic shutter appearance of the louver used for the unit
nated with silicone rubber for flexibility and long and the unit ventilator wall louvers be mounted ventilator and for the Ventimatic shutter should
life. This fabric retains its original properties down on the same wall. This will neutralize the effect of be identical. Applying the Ventimatic shutter in
to - 50F. The Ventimatic shutters ability to wind pressure that could force excess air into the this manner presents an architecturally coordi-
exhaust only the amount of air required results in unit ventilators wall intake louver. By locating the nated installation.

AAF-HermanNelson Catalog UV-1-231F / Page 15 / (6/99)


Cabinets & Filters

Tamper Resistant Access


Hex head (Allen wrench) front panel fasteners Hex Head
deter unauthorized access to interior of unit. (See Discharge Grille Mounting Fasteners
Figure 16-1) Bracket(s)

Removable Discharge Grille Discharge


Facilitates cleaning of fans and fan housings. Grille
(See Figure 16-1)
Screen

Sectionalized Access Panels


All Self-contained Units are furnished with three Sheet
individual front panels. This feature permits Metal
opening of only the required panel. No cumber- Screws

some full length panels to contend with.


(See Figure 16-1)
Hex Head
Fasteners
The convenient 12" wide front panels at each Hex Head
end provide access to piping compartments, Fasteners
temperature control components and High-Me- Front Access Panel
dium-Low-Off switch. Unlike units that have full
length front panels, the 12" wide front panels
Figure 16-1
can be removed without disturbing the normal
operating mode of the unit. The center
front panel is normally only removed for filter
Fan Shaft
maintenance and discharge grille removal.
Bearing
(See Figures 16-1 and 16-3)

Filters 12" Left Front


All units are furnished with AAF throw-away Access Panel
filters. Additional, permanent wire mesh and
renewable media filters are available. The one- Figure 16-2
piece filter design makes filter changeout quick
and easy. (See Figure 16-3)

Throwaway Filters feature Amerglas media. Motor


They are designed to be used once, then discarded.

Permanent filters are metal filters that may be 12" Left Front
Access Panel
removed, cleaned and re-used innumberable
times. (See Figure 16-3)

Renewable Filters consist of frame and renew- Structural


able Amerglas media. (See Figure 16-4) Frame
Filter
With AAF-HermanNelsons single filter design,
filter changeout takes only seconds. Change only one
filter instead of multiple filtersno hidden filters. Figure 16-3

With one-piece filter design, the mixture of


outdoor air and room air passes through the 12" Right Front
single unit filter. With all air being handled Access Panel
by one filter there is no possibility of uneven Figure 16-4
dust loading which is an inherent danger of Renewable Media
units with separate filters for room air and Filter Renewable Media
outdoor air.

Catalog UV-1-231F / Page 16 / (6/99) AAF-HermanNelson


Heat Pump Operation

Air-To-Air Heat Pump Units Models AED, AEQ


General The electric heat elements can also be energized the heat pump heating cycle is resumed. This cycle
manually by the emergency heat switch. This occurs every 90 minutes if defrost is required. The
The AAF Model AED and AEQ units are air-to-air
feature is included to provide emergency heat in 90-minute timer can be field adjusted to either
heat pumps and not dependent upon a central-
the case of a compressor malfunction. Once the 45-minute or 30-minute cycles if necessary.
ized heating system. Heat pumps extract heat from
malfunction is repaired, the emergency heat switch
cold outside air, amplify it, and transfer it to the
should be replaced in the normal position to However, regardless of the cycle time, defrost will
occupied space. This process drastically reduces
allow regular heat pump operation to resume. not occur unless the outdoor coil sensor deter-
the need for electric resistance heating, thus
mines the coil temperature is too low.
conserving precious fossil fuels and minimizing
energy costs. Defrost cycle
The heat pump cycle is designed to extract as much Condensate removal
The heat pump cycle for the Models AED and free heat out of the air as possible. The Model Heat pumps can generate condensate while
AEQ units are designed to supply all the heating AED and AEQ units are furnished with a defrost heating which must be disposed of properly.
needs of the occupied space regardless of outdoor cycle to melt away any frost which may form on Condensate is produced mainly during the defrost
temperature. Optimal energy savings is obtained the outdoor coil that could hinder normal heat cycle when refrigerant is reversed through the
when outdoor temperatures range from 65F pump operation. outdoor coil to melt the frost or ice that is present.
to 30F (18C to -1C). However, considerable The Model AEQ is supplied with a drain
savings can be realized by operating the heat pump A coil mounted sensor is used to activate this connection that can be attached to the buildings
cycle when subzero temperatures exist. defrost cycle. The defrost cycle is factory set to internal collection system for disposal.
energize every 90 minutes depending on the A self-contained condensate disposal system is also
When the outdoor temperature is below 20F condition of the outdoor coil. If the sensor offered for the AED Model. Condensate is
(-71C), the electric resistance heaters are able to determines the coil is too cold, it signals the transferred to a compartment that contains an
be energized. They will be energized only if the reversing valve to reverse the flow of refrigerant electric element designed to completely boil
room temperature setpoint cannot be satisfied by sending hot gas through the frosted coil. This awayall heat pump condensate. This system
the heat pump cycle alone. Should electric heat process occurs for a maximum of ten minutes. accomplishes condensate disposal while simulta-
become necessary, it is energized in stages. This neously adding much needed humidity to the
eliminates wide temperature swings that would During the defrost cycle, if the room requires heat occupied space.
occur if an unnecessary amount of electric heat is to satisfy the thermostat setpoint, the electric
energized. Once the room temperature setpoint is resistance heaters are energized. These heaters are The Model AED and AEQ Self-contained Air-
satisfied, the electric heaters are de-energized in brought on in stages until the desired room to-Air Heat Pump Unit Ventilators can provide
stages until the desired room temperature can temperature is obtained. Once the coil is defrosted, the lowest energy usage of any Self-contained Unit
be maintained. the electric heat elements are de-energized and Ventilator available.

Water Source Heat Pump Units Models ARQ, ERQ


General The ARQ and ERQ Models have outstanding are heating. Cooling will occur in rooms that have
The ARQ and ERQ Models are Self-contained ventilation characteristics allowing up to 100% direct sunshine or a large number of occupants.
Water Source Heat Pump Unit Ventilators. They outside air to be introduced to the space. It con- Heating may be required in rooms with no sun
are economical units which cool by removing heat tains a built-in refrigeration section that elimi- such as north facing rooms and in unoccupied
from the room and transferring this heat to a nates the need for chillers and outdoor condens- spaces.
water loop. Heating is accomplished by drawing ing units making the ARQ and ERQ Models eco-
heat out of the water loop and transferring it to nomical for new or retrofit construction. There are times, however, when every unit will
the room as warm air. Refrigerant is used to require heating or every unit will require
amplify this process allowing greater heat transfer Heating Cooling Process cooling. For this situation, water source heat
for more efficient heating and cooling. Water source heat pumps are a very efficient pumps usually include a cooling tower to reject
method of heating and cooling. When one unit excessive or unwanted heat. They will also
The ARQ and ERQ Models are designed and is rejecting heat into the water loop, another unit employ a central boiler for supplemental heat or
built to serve commercial and industrial applications is drawing heat from the water loop. The units separate unit mounted electric resistance heating
such as schools, hospitals, office buildings and other are installed on a closed water loop using inter- coils to add heat when the loop water tempera-
buildings with large conference rooms and common connecting pipe. With a water source heat pump ture becomes too low to extract heat.
areas. This unit is available in six sizes, ranging from system it is possible, and even desirable, to have
2 to 412 tons (7 to 15.8 kW) cooling capacity. many units cooling at the same time that others

AAF-HermanNelson Catalog UV-1-231F / Page 17 / (6/99)


Details and Dimensions
Air Cooled Models AZS, AZQ, AZR, AED, AEQ
Area For Electric Wiring Table 18-1. AZS, AZQ, AZR, AED, AEQ
1" (25mm) L 1" (25mm)
512"
Wall Sleeve Location (140mm)
DIMENSIONS IN INCHES (MM)
Top 638" UNIT ROOM PROJ.
1218" (162mm)
C SIZE A L C END PANEL AMOUNT
View (314mm) 5"
(127mm) IN WALL
26" DEPTH
(711mm)
1112" Room Projection 0 1658 (422) 1138 (289)
(292mm) 1658"
(422mm)
24 86 84 3 (76) 1958 (498) 838 (213)
Area For Condensate
30 (2184) (2134) 514 (133) 2178 (557) 618 (156)
Hinged Door (Control Access)
Floor Drain (See Note 4) 1138 (289) 28 (711) 0
1" A 1"
(25mm) (25mm) 0 1658 (422) 1138 (289)
End End
Panel Panel 36 98 96 3 (76) 1958 (498) 838 (213)
Front 40 (2489) (2434) 514 (133) 2178 (557) 618 (156)
30"
View (762mm) 1138 (289) 28 (711) 0
0 1658 (422) 1138 (289)
44 110 108 3 (76) 1958 (498) 838 (213)
48 (2794) (2743) 514 (133) 2178 (557) 618 (156)
Removable
Decorator Panels 54 1138 (289) 28 (711) 0
Application Considerations
LOUVER LOUVER STEEL LINTEL
(NOTE 2) (NOTE 2) (BY OTHERS)
28"
(711mm)
STEEL LINTEL 1658"
(BY OTHERS) 1658" LOUVER C
(NOTE 2) (422mm)
(422mm)

CAULK PERIMETER
CAULK PERIMETER)
1658"
SEE
(422mm)
NOTE 1 WALL
28"
28" WALL SLEEVE
28" (711mm)
(711mm) 3" (76mm)
(711mm) SLEEVE
WALL 3" (76mm)
3"
SLEEVE
(76mm)

3" (76mm)
3" (76mm) 3" (76mm)
FLOOR
FLOOR (INCLUDING CARPET) FLOOR
CAULK
PERIMETER

Figure 18-1 Figure 18-2 Figure 18-3


Full Recess Partial Recess No Recess (SEE NOTE 5)
Notes:
 Horizontal splitter (by others) must be installed whenever there is any space  Louvers may be recessed a maximum of 2" (51mm) from the exterior face of the wall.
beween the wall sleeve and the louver. It is also necessary to seal the ends of  Drain must be flush with floor to allow unit installation and removal. Unit drain
the wall opening. tube is 78" (22mm) O.D. copper.
 The top and two sides of the louver must be caulked watertight. Do not caulk  A field supplied air seal should be applied to the exterior perimeter of the wall
bottom edge of louver. Refer to installation instructions in IM 502 for details. sleeve when unit is installed with no recess.

Unit Cross Section AZS, AZQ, AZR, AED, AEQ


OUTDOOR INDOOR OUTDOOR INDOOR
16 58" 16 58"
(422mm) (422mm)
 

 
Condenser
   RACEWAY FOR FACTORY WIRING
Discharge Air
30" 30"  ELECTRIC HEAT CONTROL BOX
(762mm)
28" (762mm) 28"  EVAPORATOR COIL
(711mm)
 (711mm)
  ELECTRIC HEATING COIL
       CONDENSING COIL
Condenser  OUTDOOR FANS
Supply Air
 INDOOR FANS
Outside
Air

28" 28"
(711mm) (711mm)

Figure 18-4. Cooling Mode Figure 18-5. Heat Pump/Heating Mode

Catalog UV-1-231F / Page 18 / (6/99) AAF-HermanNelson


Details and Dimensions
Water Source Heat Pump Models ARQ, ERQ
Component Location and Dimensions (1658 Deep)
3
4"
(19mm) 1 6" 4
11" 17-12"
(152mm)
(279mm) (445mm)

6-14"
(159mm)
Top View 16-58"
(422mm)
11-12" 11-12"
(292mm) (292mm)

2
Return Water 34" (19mm) FPT
5
3
E F Supply Water 4" (19mm) FPT
3

5 6
G

30"
7 (762mm)
5"
(127mm) H
3" 13-14" 8
(76mm) (337mm)

7
8" (22mm) O.D. 22-12" (572mm)
11" Copper Drain
1" (279mm) 23" (584mm) 1"
Left-hand Standard Field Reversible 14"
278" 3" (25mm) A (25mm) (356mm)
(73mm) (76mm)

Left End View Front View Right End View

Table 19-1
Piping & Wall Thermostat Wiring: ARQ-024, 030 ARQ-036, 040 ARQ-048, 054
 Bottom entry within 11" x 1112" (279 mm x 292 mm) area. ERQ-024, 030 ERQ-036, 040 ERQ-048, 054
Electrical Main Power & Control Wiring:
IN. MM IN. MM IN. MM
 Bottom entry within 6" x 1112" (152 mm x 292 mm) area.
 1" (25.4 mm) and 2" (51 mm) knockouts in main junction box for main A 86 2184 98 2489 110 2794
power wiring. B 48 1219 60 1524 72 1829
Component Location: D 55 1397 67 1702 79 2007
 Hinged 24" x 1434" (610 mm x 375 mm) access door.
 Fan motor E 5 1 5 132 5 1 5 132 7 178
 Electrical control box F 3 1 4 83 3 1 4 83 3 1 4 83
 Compressor compartment G 101516 278 101516 278 17 432
 Compressor H 14 356 14 356 8 203

Unit Cross Section ARQ, ERQ





 RACEWAY FOR FACTORY WIRING


 ELECTRICAL JUNCTION BOX
30" (762mm)  AIR-TO-REFRIGERANT COIL
  (OPTIONAL) ELECTRIC HEAT/COIL
  (BOILERLESS ONLY)
 WATER-TO-REFRIGERANT COIL
BRAZED PLATE HEAT EXCHANGER
LOCATED IN LEFT END COMPARTMENT
Outdoor Air
Return Air

16 58" (422mm)
or
21 78" (557mm)

AAF-HermanNelson Catalog UV-1-231F / Page 19 / (6/99)


Details and Dimensions Water Source Heat Pump Models ARQ, ERQ (Continued)

Outdoor Air Arrangement 1658" (422mm) deep units

Figure 20-2. Closed Pipe Tunnel (1658 Deep)


7" (178mm) 1658"
19" 3
(483mm) (422mm)
1" (25mm)

1
30" 8 8"
3 (206mm)
(762mm)
1 28" x D
(711mm x D)
7
1312" D 17 8" If wall is chased, wall
(343mm) (454mm) opening for outdoor
2 air MUST BE WITHIN
29" THE 28" x D (711mm
(737mm) x D) AREA.
612" 4"
Outdoor Air Opening
(165mm) (102mm)

1" (25mm) 1" (25mm) Air Seal


Right End View Resilient Insulation 4" 112" Left End View
17" (102mm)
(Without End Panel) (165mm) 6" and Air Seal 812"
(38mm) (Without End Panel)
(152mm) (216mm)
25" (635mm) C 13"
(330mm)

Rear View (Without End Panels)

Table 20-1
Piping & Wall Thermostat Wiring: ARQ-024, 030 ARQ-036, 040 ARQ-048, 054
Rear entry field cut in 4" x 1778" (102 mm x 454 mm) area. ERQ-024, 030 ERQ-036, 040 ERQ-048, 054
Electrical Main Power & Control Wiring: IN. MM IN. MM IN. MM
Rear entry field cut in 4" x 6" (102 mm x 152 mm) area. C 48 1219 60 1524 72 1829
D 55 1397 67 1702 79 2007
Component Location:
Four 78" (22 mm) diameter holes in back for anchoring unit to wall.

Catalog UV-1-231F / Page 20 / (6/99) AAF-HermanNelson


Details and Dimensions Water Source Heat Pump Models ARQ, ERQ (Continued)

Outdoor Air Arrangement 2178" (566mm) deep units

Figure 21-1. Partial Adaptor Back (2178" Deep)


7"
11 (178mm) 21-78" (556mm)
Piping Area 19" 5-14" (133mm)
(483mm) 2-12" (64mm) 3-34" (95mm)

30" 2 10"
14-12" (762mm) 11
(368mm) 14-12"
(368mm)
1" (25mm)
13-12" 17-78"
(343mm) 4 1" Outdoor Air 1"
12" (305mm) x C (454mm)
(25mm) 12" Opening (25mm) 14"
Area For (305mm)
Outdoor Air (356mm)
4"
(102mm)
1"
(25mm) 1" 3"
Right End View 6-12"
6" (25mm)
4"
(76mm) Left End View
(165mm) 17" Air Seal
(Without End Panel) (165mm) 1-12"
(Without End Panel)
23" (534mm) C 11" (38mm)
(279mm)
Rear View (Without End Panels)

Figure 21-2. Full Adaptor Back (2178" Deep) Piping Tunnel


Outdoor Air [1-34" x 11-34"
Duct Collar (44 x 298mm)]
1
[5- 4" (133mm) x B] 5-14" Isolated from
7" Outdoor Air
Arrangement H (133mm) B 3-14"
(178mm)
1 19" 11 (83mm) 21-78" (556mm)
4" (6.4mm) 1" (25mm)
(483mm)

1" 30" 2
(25mm) (762mm) 11 11-34"
(298mm) 1-34" (44mm)
27-12" Outdoor Air
(699mm) Opening
13-12" 17-78"
27-12" (699mm) (343mm) 4 1" 1" (454mm)
x C area for (25mm) (25mm)
Outdoor Air 14"
Arrangement G 6-12" 4" (356mm)
(165mm) (102mm)
1"
(25mm) 1" 3"
6" 4"
(25mm) Air Seal (76mm)
17"
(165mm) 1-12"
23" (534mm) C 11" (38mm)
(279mm)

Right End View Left End View


(Without End Panel) Rear View (Without End Panels) (Without End Panel)

Piping & Wall Thermostat Wiring: Table 21-1


Bottom entry within 11" x 1112" (279 mm x 292 mm) area. Dimensions
Rear entry field cut in 4" x 1778" (102 mm x 454 mm) area. Unit Size
C D
Electrical Main Power & Control Wiring:
Bottom entry within 6" x 1112" (152 mm x 292 mm) area. 024 & in. 48 55
4 Rear entry field cut in 4" x 6" (102 mm x 152 mm) area. 030 mm 1219 1397
1" (25.4 mm) and 2" (51 mm) knockouts in main junction box for main 036 & in. 60 67
power wiring. 042 mm 1524 1702
Component Location: 048 & in. 72 79
6 Hinged 24" x 1434" (610 mm x 375 mm) access door. 060 mm 1829 2007
7 Fan motor
Electrical control box
Compressor compartment
Compressor
11 Four 78" (22 mm) diameter holes in back for anchoring unit to wall.
12 Hinged 12" x 1434" (305mm x 375mm) access door (Optional.)

AAF-HermanNelson Catalog UV-1-231F / Page 21 / (6/99)


Application Considerations
Water Source Heat Pump Models ARQ, ERQ

1658" (422mm) Deep Unit


Figure 22-1. Standard Unit Figure 22-2. Chased Wall Unit Figure 22-3. Chased Wall Unit
Standard Intake Louver Location Top of Intake Louver up to Top of Intake Louver up to
21" (533mm) Above Floor 28" (711mm) Above Floor
(With Adapter Back Available as an Accessory) (With Adapter Back Available as an Accessory)

Lintel Lintel
(by others) (by others)

Intake
Louver
Not Less
Lintel Intake Than 3"
(by others) Louver (76mm)
Not Less
Than 3"
(76mm)

Not More Not More


Than 21" Than 21"
Intake (533mm)
(533mm)
Louver
112" (38mm) 112" (38mm)
112" (38mm) Floor Line Floor Line
Floor Line

Cement Cement
Cement Mortar Mortar
Mortar Pitch Away Pitch Away
Pitch Away Important! Gasket sealing Important! Gasket sealing
Important! Gasket sealing From Unit From Unit
From Unit surface is required. surface is required.
surface is required.

2178" (556mm) Deep Unit

Figure 22-4. Pipe Passage Unit Figure 22-5. Full Adapter Back Unit Figure 22-6. Window Intake Unit
Standard Intake Louver Location Top of Intake Louver up to Window Intake Louver
(With Adapter Back Available as an Accessory) 28" (711mm) Above Floor (With Adapter Back Available as an Accessory)
(With Adapter Back Available as an Accessory)

Window Sash

Intake
Louver Goose Neck Duct
(by others)

Lintel Duct Collar


(by others) (AAF)

Intake
Louver
Lintel
(by others) Important!
Gasket
sealing
surface is
required.

Not More
Than 28"
Intake (711mm)
Louver

Not More 112" (38mm) Floor Line Floor Line Floor Line
Than 12"
(305mm)

Cement
Mortar
Pitch Away Important! Gasket sealing
From Unit surface is required.

Catalog UV-1-231F / Page 22 / (6/99) AAF-HermanNelson


Specifications
Air Cooled Units
Models AZS, AZQ, AZR

General Furnish and install where shown on be statically and dynamically balanced. Motor shall scrolls for re-evaporator on the hot condenser coil.
plans, a complete self-contained, air cooled, be permanent split capacitor (PSC) plug-in type The equipment manufacturer is to be fully respon-
heating and cooling unit ventilator. This unit shall located out of the airstream and have an internal sible for the integrity of the refrigerant piping
meet capacities, airflow and configuration as thermal overload device (auto-reset). Fan speeds and the entire refrigeration circult, including
shown on unit schedule. shall be controlled by High-Med-Low-Off switch. compressor. Condenser and evaporator coils shall
Fan/coil arrangement shall be draw-thru be fully assembled and tested prior to shipment.
Each standard unit must be listed by Underwriters design for uniform coil face velocity and discharge The motor compressor unit shall be vibration
Laboratories Inc. (U.L.) as complying with all air temperature. isolated internally and externally and shall be
safety standards. connected in such a manner as to prevent trans-
Fan motors and controls shall have each hot line mission of vibration to other components within
The units shall ship fully assembled with the protected by factory installed cartridge type fuse(s) the section.
exception of the end panels which shall be pack- The unit manufacturer shall provide one (1) spare
aged separately to allow easy access for piping and motor for each size and type of motor furnished Single-phase only: Single-phase units shall
electrical rough-in. (Option: Wall sleeves shall be as part of a unit ventilator, except units having have permanent split capacitor (PSC) compressor
shipped in advance of unit for rough-in.) double extended shaft motors shall be provided motor with start assist consisting of a compressor
with one (1) spare fan board assembly for each start capacitor and compressor start relay.
Unit construction All internal sheet metal unit size.
parts subject to corrosion must be made of galva- Units with three-phase power: Shall
nized steel. The entire frame must be welded All components of the fan/motor assembly shall utilize three-phase compressors for balanced
construction to provide strength and rigidity. be removable from the front of the unit. The electrical compressor loads.
Frames assembled with sheet metal fasteners are motor and fan shaft shall have sleeve type bearings
not acceptable. with precision tolerances and shall not require The condenser coil shall be constructed of copper
oiling more than once annually. tubes mechanically expanded to embossed alumi-
Cabinets Exterior cabinet panels shall be num plate fins. The unit shall be so designed as to
constructed of heavy-gauge steel and every exposed Condenser fans and motors The fan allow access to the entering side of the condenser
corner must be welded and ground smooth for board and fan housings shall be constructed of coil for cleaning without opening the sealed
appearance and durability. All surfaces shall be galvanized steel. The fan motor and fan shaft shall refrigeration circuit. The evaporator coil shall be
cleaned and phosphatized, then painted with an have permanently lubricated ball bearings. Motor constructed of copper tubing having embossed
oven baked powder paint. Top surface shall be shall be permanent split capacitor (PSC) type. Fan aluminum plate fins mechanically bonded thereto
Charcoal Bronze textured powder paint to resist wheels shall be forward curved centrifugal type. and shall be positioned above an insulated galva-
scratching and hide fingerprints. Front access nized steel drain pan.
panels and top access door shall be supplied with Outdoor/room air dampers Each unit
tamper resistant fasteners. shall be provided with separate room air and out- Refrigerant (R-22) shall be metered by a thermo-
door air dampers. The room air damper shall be static expansion valve in lieu of capillary tubing
Removable discharge grille shall be constructed of constructed of aluminum and counterbalanced to achieve evaporator performance and to protect
continuous, round edged, steel bars to provide a against back pressure. Outdoor air damper shall the compressor from floodback of liquid refrigerant.
10-degree vertical deflection. be two-piece, double wall construction with 12" The refrigerant section shall be adequately
(13mm) thick, 1.5 lbs. (.68 kg) density fiberglass insulated to prevent sweating.
Adjustable side deflection vanes shall be provided insulation sandwiched between welded galvanized-
beneath the discharge grille to give optimal steel blades. Outdoor air damper shall have The unit shall be furnished and wired with
lateral air distribution. additional foam insulation on the exterior of the compressor thermal/current overload and high
blades and end partitions. Dampers shall be pressure cutout. Gauge ports shall be provided to
(Option: A 1 4" (6mm) mesh screen shall be fitted with blended mohair seals along all sealing allow reading of refrigerant pressures at the
provided beneath the discharge grille to protect edges. Damper bearings shall be made of nylon or suction and discharge of the compressor.
against objects being dropped through the other material which does not require lubrication. Compressor shall be equipped with internal
discharge grille.) pressure relief valve to protect against excessive
Refrigeration system The refrigeration pressure buildup.
Room air fans and motor The motor and section shall be constructed of galvanized steel and
fan assembly shall be low speed design and shall shall include a factory sealed, factory piped assembly [Optional] Electric coils Heating elements
be double inlet, forward curved centrifugal type consisting of a hermetically sealed compressor with shall be of the open wire type. Electric heat shall
with maximum fan speed of 1100 rpm. Fan wheels an integral crankcase heater, a condenser coil, be controlled in [two] [three] stages. A capillary
shall be constructed of dark, high density, injec- condenser fan and motor, and an evaporator coil. type high limit thermostat shall be provided to
tion molded polypropylene having high impact No condensate drain piping system shall be disconnect the heating elements through backup
strength, chemical resistance and thermal stabil- required as the cooling condensate is to be contactors if an overheat condition is detected.
ity. Assembly shall be direct drive type and shall disposed of by directing it into the condenser fan A front panel interlock switch shall be furnished

AAF-HermanNelson Catalog UV-1-231F / Page 23 / (6/99)


Specifications Air Cooled Units (Continued)
Models AZS, AZQ, AZR
to de-energize the electric resistance heating by the unit ventilator manufacturer. Valve shall (.68 kg) minimum density, 1" (25mm) thick glass
element when center front panel is opened. be field installed and piped by the installing fiber insulation and felt type material affixed to
contractor.] the interior surfaces to dampen the compressor
[Optional] Hot water coil Coil shall be sound. Unit shall have attenuating loops in
aluminum plate fin and copper tube construction. OR both the suction and discharge lines to reduce
Coil shall be suitable for 150 psi working mechanical vibration.
pressure. Coil shall be provided with an accessible [Option: Coil shall be controlled by a modulating
manual air vent at the high point of the coil and a face and bypass damper. Coil shall have a 2-way, [Optional] Acoustical package The
threaded drain plug at the low point of the coil. 2-position, end-of-cycle valve to shut off steam compressor shall be mounted on neoprene
when heating is no longer required. Valve and coil compressor isolators for external vibration isolation.
Contractor shall provide all necessary balancing supply shall have union connections. Valve shall Sound attenuating loops and seamless flexible
valves, shutoff valves and union connections in be factory wired by the unit ventilator manufac- bronze hose vibration absorbers shall be furnished
both the supply and return piping connections to turer. Valve shall be field installed and piped by in both the suction and discharge lines to reduce
permit removal of the unit from the wall sleeve the installing contractor.) mechanical vibration.
for servicing.
[Optional] Up-feed piping. Compressor enclosure panels shall be 16-gauge
[Option: Coil shall be controlled by a 3-way minimum and crossbroken for additional rigidity
(optional 2-way) modulating control valve and [Option: Up-feed piping stub-up within the unit to dampen vibration. Complete interior of
shall be factory wired by the unit ventilator end compartment requires the installing contractor compressor compartment shall be lined with a
manufacturer. Valve shall be field installed and to furnish union connection at the floor line in multi-functional material that serves as a sound
piped by the installing contractor.] the supply and return lines with shutoff valves barrier, an absorber of sound and also must act as
below the floor line. This is required to permit a decoupler to the compressor enclosure. This
OR unit installation and removal for servicing.] multi-functional material shall have a mylar coating
on the face to act as a sound reflector and to
[Option: Coil shall be controlled by a modulating [Option: Up-feed piping stub-up shall be brought increase the strength of the material. Damping
face and bypass damper. Coil shall have a 3-way, up external to the unit within a removable 6", material shall be textured foam type.
2-position, end-of-cycle valve to shut off water flow (152mm) wide end panel. The shutoff valves and
when heating is no longer required. Valve and coil union connections shall be located within the 6" The exterior of the compressor compartment shall
return shall have union connections. Valve shall (152mm) wide end panel.] be coated with a high density damping material
be factory wired by the unit ventilator manufac- to eliminate impact noise and vibration. The right
turer and shall be field installed and piped by the Filter Filter shall be one-piece design located end panel, right-hand front panel, 36" (914mm)
installing contractor.] to provide filtration of the outdoor air/return of the right-hand end of the center front panel and
airflow. Separate filters for outdoor air and return the hinged top access door shall be coated with a high
(Optional) Steam coil Coil shall be alumi- air are not acceptable. Throwaway filter shall be density material to eliminate noise and vibration.
num plate fin and copper tube construction. Coil factory furnished initially installed in the unit.
shall be double tube (DT) steam distributing, [Option: If the unit has no right-hand end panel
freeze resistant type. Coil shall be pitched to [Option: Furnish _____________ extra set(s) of and has a cabinet abutting the right end, adhesive
insure complete condensate removal for freeze throwaway filters.] backed high density damping material shall be
protection and elimination of water hammer. furnished for field installation by the Installing
[Option: Furnish one set of wire mesh permanent contractor.]
Contractor shall provide all necessary shutoff valves filters as final filter.]
and union connections in both the supply and Temperature controls The unit ventilator
return piping connections to permit removal of [Option: Furnish one set of renewable (metal manufacturer shall provide factory installed,
the unit from the wall sleeve for servicing. frame with glass fiber media) filters as final filter.] calibrated, and tested temperature controls. Units
that are capable of providing up to 100% outside
A pressure equalizing device (vacuum breaker) shall [Option: Furnish _____________ roll(s) of air shall provide a microprocessor-based Direct
be factory installed to prevent the retention of renewable filter media.] Digital Control (DDC) that can monitor condi-
condensate in the coil. The installing contractor tions and automatically adjust unit operations to
shall connect the device to the return line beyond Acoustical treatment The compressor shall maintain these requirements. This DDC control
the trap using the tubing provided. Steam trap be mounted on neoprene compressor isolators for shall have the following tenant adjustments: (1)
shall be furnished and field installed by the external vibration isolation. Compressor enclosure room temperature setpoint, (2) minimum percent
installing contractor. panels shall be 16-gauge minimum and outdoor air setting, and (3) unoccupied setpoint
crossbroken for additional rigidity to dampen (offset). An LED status/fault indicator shall be
[Option: Coil shall be controlled by a 2-way, vibration. Compressor enclosure panels and unit furnished for inspection and a communications
modulating control valve and shall be factory wired front panel (compressor end) shall have 112 lbs. port shall be incorporated to allow manipulation

Catalog UV-1-231F / Page 24 / (6/99) AAF-HermanNelson


Specifications Air Cooled Units (Continued)
Models AZS, AZQ, AZR
by a remote PC. The remote PC shall be able to to the 100% outdoor air position and shall of the [vertical blade] [horizontal blade] type and
access and change pertinent operating aind remain fully open. shall be divided in half horizontally across the lou-
room conditions from a remote location. The ver to prevent condenser air recirculation. A 12"
microprocessor-based control must be capable of [Optlonal] Night control with unit day/ (13mm) square mesh bird screen shall be provided
communicating to a local IBM-compatible PC night switch (stand-alone units only) on the backside of the wall intake louver. All lou-
using the RS-232 protocol. When using this Each unit (except slaves) shall be furnished with a vers shall be 28" (711mm) high by 214"(57mm)
remote PC, the unit must be capable of reacting unit mounted day/night switch to permit manual thick and suitable for both masonry and panel wall
to changes made by the remote PC. The remote indexing from day to night mode. For units with construction. The frame of the louver shall have
PC must also be able to access all pertinent 100% O.A. capability, the unoccupied offset weep holes along the bottom. Lintels shall be pro-
operating and room conditions. temperature setpoint(s) shall be in force when vided by the contractor above the louver opening.
indexed to the night mode. The outdoor air
Room temperature sensor damper shall remain closed at all times during the (Optional: Heavy-duty lattice grille horizontal and
and tenant override options night mode. vertical lines shall line up with the louver blades
to present an aesthetic appearance. Grille shall be
Unit-mounted Units shall have a tempera- [Optional] Night control with unit-mounted fabricated from mill finish aluminum. The standard
ture sensor located in a sampling chamber to time clock Each unit shall be furnished with aluminum allow shall be [unpainted] [painted]
allow a constant circulation of room air to flow a unit-mounted, field programmed time clock for [clear anodized].)
across the sensing device. The sampling chamber day/night changeover. This clock shall have a
shall be designed in such a manner that will battery backup that will provide up to 150 hours
ensure rapid and accurate sensing of room air. of operation during a power outage. A unit-
[Option: A unit mounted tenant override device mounted holiday switch shall be furnished to
shall be supplied.] allow manual changeover to unoccupied control for
extended or otherwise unscheduled periods.
Wall-mounted sensor Units shall have a
temperature sensor with status LED funnished for Wall sleeve The galvanized steel, one-piece
mounting to the wall. [Option: In addition, a wall sleeve shall be set In a wall opening and butted
tenant override switch shall be furnished as part up directly against the intake louver. Where it is
of the wall mounted sensor.] not possible to butt the wall sleeve against the wall
intake louver, the contractor shall fabricate and
Wall-mounted sensor with tenant over- install a horizontal sheet metal baffle between
ride and setpoint adjustment A sensor louver and wall sleeve to provide an airtight
with integral tenant override and status LED shall separation between condenser discharge and
be furnished with the unit ventilators. This sensor return air. The wall sleeve is to be permanently
shall also contain a manually adjustable tempera- fastened in place and shall be suitably sealed,
ture setting allowing the controller setpoint to be caulked or grouted by the contractor around the
increased or decreased by 3F (2C). entire perimeter to prevent air leakage.

Wall sensor with setpoint adjustment The wall sleeve shall be fitted with an electrical
Units shall have a sensor furnished with a manu- junction box containing a main on-off switch.
ally adjustable temperature setting allowing the All field wiring connections shall be made in this
controller setpoint to be increased or decreased wall sleeve junction box.
by 3F (2C).
(It shall be the installing contractors responsibility
[Optlonal] Ventilation lockout relay to make the final load side power wiring connec-
Units that are not on network control shall be tions between the wall sleeve junction box and the
furnished with a [24V] [120V] ventilation lock- unit terminal block (including the wiring going
out relay to permit closing the outdoor damper to the electric heating elements.The wall sleeve
during normal occupied operation. Outdoor air shall be cartoned separately and shipped to the
damper shall close when the relay is energized by jobsite preceding the unit ventilator. Junction box
a [24V] [120V] signal. shall ship separately for field installation.)

[Optional] Exhaust fan interlock relay Wall intake Louver The louver shall be sup-
Each unit shall be furnished with an exhaust fan plied by the unit manufacturer and shall be of
interlock relay. When energized by a [24V] [120V] heavy-gauge (unpainted, painted, or clear anod-
external signal, the outdoor air damper shall move ized) aluminum construction. The louver shall be

AAF-HermanNelson Catalog UV-1-231F / Page 25 / (6/99)


Specifications
Air-to-Air Heat Pump Units
Models AED, AEQ
General Furnish and install where shown on be permanent split capacitor (PSC) with speeds required as the cooling condensate is to be
plans, a complete self-contained, air-to-air heat controlled by High-Off-Low switch. Fan/coil disposed of by directing it into the condenser fan
pump unit ventilator. This unit shall meet capaci- arrangement shall be draw-thru design for scrolls for re-evaporator on the hot condenser coil.
ties, airflow and configuration as shown on unit uniform coil face velocity and discharge air The equipment manufacturer is to be fully respon-
schedule. temperature. sible for the integrity of the refrigerant piping and
the entire refrigeration circult, including compres-
Each standard unit must be listed by Underwriters Motors shall be permanent split capacitor (PSC), sor. Condenser and evaporator coils shall be fully
Laboratories Inc. (U.L.) as complying with all plug-in type located out of the airstream and have assembled and tested prior to shipment. The
safety standards. an internal thermal overload device (auto-reset). motor compressor unit shall be vibration isolated
internally and externally and shall be connected
The units shall ship fully assembled with the Fan motors and controls shall have each hot line in such a manner as to prevent transmission of
exception of the end panels which shall be pack- protected by factory installed cartridge type fuse(s) vibration to other components within the section.
aged separately to allow easy access for piping and The unit manufacturer shall provide one (1) spare
electrical rough-in. (Wall sleeves shall be shipped motor for each size and type of motor furnished Single-phase only: Single-phase units shall
in advance of unit for rough-in.) as part of a unit ventilator, except units having have permanent split capacitor (PSC) compressor
double extended shaft motors shall be provided motor with start assist consisting of a compressor
Unit construction All internal sheet metal with one (1) spare fan board assembly for each start capacitor and compressor start relay.
parts subject to corrosion must be made of galva- unit size.
nized steel. The entire frame must be welded Units with three-phase power: Shall utilize
construction to provide strength and rigidity. All components of the fan/motor assembly shall three-phase compressors for balanced electrical
Frames assembled with sheet metal fasteners are be removable from the front of the unit. The compressor loads.
not acceptable. motor and fan shaft shall have sleeve type bear-
ings with precision tolerances and shall not require The condenser coil shall be constructed of copper
Cabinets Exterior cabinet panels shall be oiling more than once annually. tubes mechanically expanded to embossed alumi-
constructed of heavy-gauge steel and every exposed num plate fins. The unit shall be so designed as to
corner must be welded and ground smooth for Condenser fans and motors The fan allow access to the entering side of the condenser
appearance and durability. All surfaces shall be board and fan housings shall be constructed of coil for cleaning without opening the sealed
cleaned and phosphatized, then painted with an galvanized steel. The fan motor and fan shaft shall refrigeration circuit. The evaporator coil shall be
oven baked enamel. Top surface shall be Charcoal have permanently lubricated ball bearings. Motor constructed of copper tubing having embossed
Bronze textured baked enamel to resist scratching shall be permanent split capacitor (PSC) type. Fan aluminum plate fins mechanically bonded thereto
and hide fingerprints. Front access panels and top wheels shall be forward curved centrifugal type. and shall be positioned above an insulated
access door shall be supplied with tamper resis- galvanized steel drain pan.
tant fasteners. Outdoor/room air dampers Each unit
shall be provided with separate room air and out- Refrigerant (R-22) shall be metered by a thermo-
Removable discharge grille shall be constructed of door air dampers. The room air damper shall be static expansion valve in lieu of capillary tubing
continuous, round edged, steel bars to provide a constructed of aluminum and counterbalanced to achieve evaporator performance and to protect
10-degree vertical deflection. Adjustable side against back pressure. Outdoor air damper shall the compressor from floodback of liquid refrigerant.
deflection vanes shall be provided beneath the be two-piece, double wall construction with 12" The refrigerant section shall be adequately
discharge grille to give optimal lateral air (13mm) thick, 1.5 lbs. (.68 kg) density fiberglass insulated to prevent sweating.
distribution. insulation sandwiched between welded
galvanized-steel blades. (Option: Cold weather The unit shall be furnished and wired with
(Option: A 1 4" (6mm) mesh screen shall be outdoor air damper shall have additional foam compressor thermal/current overload and high
provided beneath the discharge grille to protect insulation on the exterior of the blades and end pressure cutout. Gauge ports shall be provided to
against objects being dropped through the partitions.) Dampers shall be fitted with blended allow reading of refrigerant pressures at the
discharge grille.) mohair seals along all sealing edges. Damper bear- suction and discharge of the compressor.
ings shall be made of nylon or other material which Compressor shall be equipped with internal
Room air fans and motor The motor and does not require lubrication. pressure relief valve to protect against excessive
fan assembly shall be low speed design and shall pressure buildup.
be double inlet, forward curved centrifugal type Refrigeration system The refrigeration
with maximum fan speed of 1100 rpm. Fan wheels section shall be constructed of galvanized steel and Electric coils Heating elements shall be of
shall be constructed of dark, high density, injec- shall include a factory sealed, factory piped assem- the open wire type. Electric heat shall be controlled
tion molded polypropylene having high impact bly consisting of a hermetically sealed compressor in [two] [three] stages. A capillary type high limit
strength, chemical resistance and thermal stability. with an integral crankcase heater, a condenser coil, thermostat shall be provided to disconnect the
Assembly shall be direct drive type and shall be condenser fan and motor, and an evaporator coil. heating elements through backup contactors if an
statically and dynamically balanced. Motor shall No condensate drain piping system shall be overheat condition is detected. A front panel

Catalog UV-1-231F / Page 26 / (6/99) AAF-HermanNelson


Specifications Air-to-Air Heat Pump Units (Continued)
Models AED, AEQ
interlock switch shall be furnished to de-energize sound. Unit shall have attenuating loops in both PC shall be able to access and change pertinent
the electric resistance heating element when the suction and discharge lines to reduce operating aind room conditions from a remote
center front panel is opened. mechanical vibration. location. The microprocessor-based control must
be capable of communicating to a local IBM-
Defrost control and defrost condensate [Optional] Acoustical package compatible PC using the RS-232 protocol. When
disposal Defrost control shall be of the The compressor shall be mounted on neoprene using this remote PC, the unit must be capable of
time-temperature type. Defrost cycle shall be compressor isolators for external vibration isolation. reacting to changes made by the remote PC.
initiated only at the factory set interval of 90 Sound attenuating loops and seamless flexible The remote PC must also be able to access all
minutes and only when the coil surface temperature bronze hose vibration absorbers shall be furnished pertinent operating and room conditions.
is below 28F (-2C). Defrost timer shall be field in both the suction and discharge lines to reduce
adjustable for 30-minute or 45-minute intervals. mechanical vibration. Units that have 20% maximum outdoor capability
Unit shall include a thermostatically controlled shall be furnished with a room thermostat that is
electric resistance heater for defrost condensate Compressor enclosure panels shall be 16- [unit] [wall] mounted and shall be [manual]
drain pan. Heater shall be energized at 38F (3C) gauge minimum and crossbroken for additional [automatic] changeover type. The mechanical
5F (3C) outdoor air temperature. Defrost rigidity to dampen vibration. Complete interior cooling cycle shall be locked out whenever the
condensate shall be piped into a building drain of compressor compartment shall be lined outdoor air termperature is below 50F (10C).
system. [Option: Unit shall not require a heating with a multi-functional material that serves
condensate drain. A built-in method of heating as a sound barrier, an absorber of sound and Room temperature sensor
condensate disposal shall be used which provides also must act as a decoupler to the compressor and tenant override options
room humidification.] enclosure. This multi-functional material
shall have a mylar coating on the face to act as a Unit-mounted Units shall have a tempera-
Emergency electric heat switch An sound reflector and to increase the strength of ture sensor located in a sampling chamber to
emergency electric heat switch shall be furnished the material. Damping material shall be textured allow a constant circulation of room air to flow
to allow the unit to provide electric resistance foam type. across the sensing device. The sampling chamber
heating regardless of outdoor air temperature in shall be designed in such a manner that will
case of compressor malfunction. The exterior of the compressor compartment shall ensure rapid and accurate sensing of room air.
be coated with a high density damping material [Option: A unit mounted tenant override device
Filter Filter shall be one-piece design located to eliminate impact noise and vibration. The right shall be supplied.]
to provide filtration of the outdoor air/return air- end panel, right-hand front panel, 36" (914mm)
flow. Separate filters for outdoor air and return air of the right-hand end of the center front panel Wall-mounted sensor Units shall have a
are not acceptable. Throwaway filter shall be and the hinged top access door shall be coated temperature sensor with status LED furnished for
factory furnished initially installed in the unit. with a high density material to eliminate noise and mounting to the wall. [Option: In addition, a
vibration. tenant override switch shall be furnished as part
[Option: Furnish _____________ extra set(s) of of the wall mounted sensor.]
throwaway filters.] [Option: If the unit has no right-hand end panel
and has a cabinet abutting the right end, adhesive Wall-mounted sensor with tenant over-
[Option: Furnish one set of wire mesh permanent backed high density damping material shall be ride and setpoint adjustment A sensor
filters as final filter.] furnished for field installation by the installing with integral tenant override and status LED shall
contractor.] be furnished. This sensor shall also contain a
[Option: Furnish one set of renewable (metal manually adjustable temperature setting allowing
frame with glass fiber media) filters as final filter.] Temperature controls The unit ventilator the controller setpoint to-be increased or decreased
manufacturer shall provide factory installed, by 3F (2C).
[Option: Furnish _____________ roll(s) of calibrated, and tested temperature controls. Units
renewable filter media.] that are capable of providing up to 100% outside Wall sensor with setpoint adjustment
air shall provide a microprocessor-based Direct Units with 100% O.A. capability shall have a
Acoustical treatment The compressor shall Digital Control (DDC) that can monitor sensor furnished with a manually adjustable
be mounted on neoprene compressor isolators for conditions and automatically adjust unit temperature setting allowing the controller
external vibration isolation. Compressor enclosure operations to maintain these requirements. This setpoint to be increased or decreased by
panels shall be 16-gauge minimum and DDC control shall have the following tenant 3F (2C).
crossbroken for additional rigidity to dampen adjustments: (1) room temperature setpoint, (2)
vibration. Compressor enclosure panels and unit minimum percent outdoor air setting, and (3) [Accessory] Ventilation lockout relay
front panel (compressor end) shall have 112 lbs. unoccupied setpoint (offset). An LED status/fault Units that are not on network control shall be
(.68 kg) minimum density, 1" (25mm) thick glass indicator shall be furnished for inspection and a furnished with a [24V] [120V] ventilation lock-
fiber insulation and felt type material affixed to communications port shall be incorporated to out relay to permit closing the outdoor damper
the interior surfaces to dampen the compressor allow manipulation by a remote PC. The remote during normal occupied operation. Outdoor air

AAF-HermanNelson Catalog UV-1-231F / Page 27 / (6/99)


Specifications Air-to-Air Heat Pump Units (Continued)
Models AED, AEQ
damper shall close when the relay is energized by jobsite preceding the unit ventilator. Junction box
a [24V] [120V] signal. shall ship separately for field installations.)

[Accessory] Exhaust fan interlock relay Wall Intake Louver The louver shall be sup-
Each unit shall be furnished with an exhaust plied by the unit manufacturer and shall be of
fan interlock relay. When energized by a [24V] heavy-gauge (unpainted, painted, or clear anodized)
[120V] external signal, the outdoor air damper aluminum construction. The louver shall be of the
shall move to the maximum outdoor air position [vertical blade] [horizontal blade] type and shall
and shall remain fully open. be divided in half horizontally across the louver
to prevent condenser air recirculation. A 12"
[Accessory] Night control with unit day/ (13mm) square mesh bird screen shall be provided
night switch (stand-alone units only) on the backside of the wall intake louver. All louvers
Each unit (except slaves) shall be furnished with a shall be 28" (711mm) high by 214"(57mm) thick
unit mounted day/night switch to permit manual and suitable for both masonry and panel wall con-
indexing from day to night mode. The unoccu- struction. The frame of the louver shall have weep
pied offset temperature setpoint(s) shall be in force holes along the bottom. Lintels shall be provided
when indexed to the night mode. The outdoor by the contractor above the louver opening.
air damper shall remain closed at all times during
the night mode. (Optional: Heavy-duty lattice grille horizontal and
vertical lines shall line up with the louver blades
[Accessory] Night control with to present an aesthetic appearance. Grille shall
unit-mounted time clock Each unit be fabricated from mill finish aluminum. The
shall be furnished with a unit-mounted, standard aluminum allow shall be [unpainted]
field programmed time clock for day/ [painted] [clear anodized].)
night changeover. This clock shall have a battery
backup that will provide up to 150 hours of
operation during a power outage. A unit-
mounted holiday switch shall be furnished to
allow manual changeover to unoccupied control
for extended or otherwise unscheduled periods.

Wall sleeve The galvanized steel, one-piece


wall sleeve shall be set in a wall opening and butted
up directly against the intake louver. Where it is
not possible to butt the wall sleeve against the wall
intake louver, the contractor shall fabricate and
install a horizontal sheet metal baffle between louver
and wall sleeve to provide an airtight separation
between condenser discharge and return air. The
wall sleeve is to be permanently fastened in place
and shall be suitably sealed, caulked or grouted by
the contractor around the entire perimeter to
prevent air leakage.

The wall sleeve shall be fitted with an electrical


junction box containing a main on-off switch.
All field wiring connections shall be made in this
wall sleeve junction box.

It shall be the installing contractors responsibility


to make the final load side power wiring connec-
tions between the wall sleeve junction box and the
unit terminal block (including the wiring going
to the electric heating elements.)(The wall sleeve
shall be cartoned separately and shipped to the

Catalog UV-1-231F / Page 28 / (6/99) AAF-HermanNelson


Specifications
Water Source Heat Pump Units
Models ARQ, ERQ
General Furnish and install where shown on molded polypropylene having high impact Refrigeration system The refrigeration
plans, with unit capacities and characteristics as strength, chemical resistance and thermal stability. section shall be constructed of galvanized steel and
listed in schedule for self-contained water source Assembly shall be statically and dynamically shall include a factory sealed compressor, a
heat pump console units. balanced. Fan housings shall be of steel construc- water-to-refrigerant coil, and air-to refrigerant coil
tion. Fan shaft shall be 114" (32mm) diameter, and reversing valve. The reversing valve shall have
This unit shall be listed by Underwriters Labora- hollow steel with 114" (32mm) end bearing. Fan a replaceable external solenoid coil which is
tories Inc. (U.L.). Units shall bear the U.L. and and motor assembly shall be direct drive type. energized only when space heating is required. The
cUL labels. equipment manufacturer is to be fully responsible
Motor speed shall be controlled by factory for the integrity of the refrigerant piping and the
The unit shall be furnished with a main power furnished and mounted multi-tap transformer entire refrigeration circuit, including compressor,
on-off switch. through High-Off-Low switch. water-to-refrigerant coil and air-to-refrigerant coil,
shall be fully assembled and tested prior to shipment.
Cabinet Cabinet shall have all welded galva- Fan/coil arrangement shall be draw-thru
nized steel frame with an oven baked powder paint design for uniform coil face velocity and discharge The motor compressor unit shall be vibration
finish. Color selected by architect from air temperature In addition to providing the isolated internally and externally and shall be
manufacturers color chart. Top surface shall have kinetic energy for optimum air distribution. connected in such a manner as to prevent trans-
an oven baked textured Charcoal Bronze finish to mission of vibration to other components within
provide superior durability, scuff resistance and low Motors shall be permanent split capacitor (PSC), the section.
reflectivity in lieu of smooth enamel. Front access plug-in type designed specifically for unit ventila-
panels and top access door shall be supplied with tor operation. Motors shall be located out of the Single phase only: Single phase units shall have
tamper resistant hex socket head threaded fasteners. airstream and have an internal thermal overload permanent split capacitor (PSC) compressor
Opening or removing the unit left- or right-hand device (auto-reset). motor with start assist consisting of a compressor
front panels shall not affect unit operation in start capacitor and compressor start relay.
order to facilitate testing and servicing. Internal Fan motors and controls shall have each hot line
sheet metal parts shall be constructed of galvanized protected by factory Installed cartridge type fuse(s). The water-to-refrigerant coil shall be of either the
steel to inhibit corrosion. The unit manufacturer shall provide one (1) spare coaxial type with a copper convoluted inner tube
motor for each size and type of motor furnished and a steel outer shell or stainless steel plate heat
Unit discharge grille shall be constructed of as part of a unit ventilator, except units having exchanger. Either type shall be constructed to be
continuous round edged steel bars to provide double extended shaft motors shall be provided suitable for 300 lbs. (2069 kPa) water working
10-degres vertical deflection. Adjustable side with one (1) spare fan board assembly for each pressure and 450 lbs. (3104 kPa) refrigerant pressure.
deflection vanes shall be provided beneath the unit size.
discharge grille to provide optimum lateral air Refrigerant (R-22) shall be metered by a thermo-
distribution. Cabinet depth shall not exceed 1658" All components of the fan/motor assembly shall static expansion valve In lieu of capillary tubing
(422mm) [2178" (566mm) if adapter back is used]. be removable from the front of the unit. The to achieve balanced evaporator performance and
[Option: A 1 4" (6mm) mesh screen shall be motor and fan shaft shall have sleeve type bearings to protect the compressor from floodback of liquid
provided beneath the discharge grille to protect with precision tolerances and shall not require refrigerant.
against objects being dropped through the oiling more than once annually.
discharge grille.] The refrigerant section shall be adequately insu-
Outdoor/room air dampers Each unit lated to prevent sweating. The unit shall be
Unit shall have glass fiber blanket insulation. This shall be provided with separate room air and furnished and wired with the following safety
shall act as an outdoor air seal on 1658 (422mm) outdoor air dampers. The room air damper devices: compressor thermal/current overloads and
deep units. Units that are 2178" (566mm) deep shall be constructed of aluminum and counter- high pressure cutout switch. Gauge ports shall be
shall also have glass fiber blanket insulation on balanced against back pressure to close by wind provided to allow reading of refrigerant pressures
those adapter back parts which come In contact pressure, thereby preventing outdoor air from at the suction and discharge of the compressor.
with outdoor air. Units that are 2178" (566mm) blowing directly into the room. Outdoor air
deep shall have a vinyl foam air seal which shall damper shall be two-piece, double wall Condensate Pan Insulated drain pan shall
go around the perimeter of the wall opening for construction with 1/2" (13mm) thick, 1.5 lbs. (.68 be constructed of galvanized steel and shall be
the wall intake louver. kg) density fiberglass insulation sandwiched positioned beneath the air-to-refrigerant coil.
between welded between 20 gauge galvanized- Drain connection shall be field reversible for left-
Fan and Motor The motor and fan steel blades for rigidity and to inhibit corrosion. or right-hand drain line.
assembly shall be low speed designed to assure [Option: Cold weather outdoor air damper shall
maximum quietness and efficiency. Fans shall have additional foam insulation on the exterior Filter Filter shall be one-piece type. Throw-
double inlet, forward curved centrifugal type with surfaces of the damper blade and on the ends of away filter shall be factory furnished initially
maximum fan speed of 800 rpm. Fan wheels shall the outdoor air chamber.] installed in the unit.
be constructed of dark, high density, injection

AAF-HermanNelson Catalog UV-1-231F / Page 29 / (6/99)


Specifications Water Source Heat Pump Units (Continued)
Models ARQ, ERQ
[Option: Furnish _____________ extra set(s) of outside of the compressor compartment through PC must also be able to access all pertinent
throwaway filters.] the refrigerant tubing to the refrigerant coils. operating and room conditions.

[Option: Furnish one set of wire mesh permanent Compressor enclosure panels shall be heavy-gauge Room temperature sensor
filters as final filter.] and crossbroken for additional rigidity to dampen and tenant override options
vibration. Complete interior of compressor
[Option: Furnish one set of renewable (metal compartment shall be lined with a Unit-mounted Units shall have a tempera-
frame with glass fiber media) filters as final filter.] multi-functional material that serves as a sound ture sensor located in a sampling chamber to
barrier, an absorber of sound and a decoupler to allow a constant circulation of room air to flow
[Option: Furnish _____________ roll(s) of the compressor enclosure. This multi-functional across the sensing device. The sampling chamber
renewable filter media.] material shall have a mylar coating on the face to shall be designed in such a manner that will
act as a sound reflector and to increase the strength ensure rapid and accurate sensing of room air.
(Optional] Bollerless systems Units shall of the material. Damping material shall be [Option: A unit mounted tenant override device
utilize reverse cycle operation for heating until the textured foam type. shall be supplied.]
water loop temperature drops below 60F (16C),
at which time the unit switches over to electric The exterior of the compressor compartment shall Wall-mounted sensor Units shall have a
resistance heating. Heating elements shall be of be coated with a high density damping material temperature sensor with status LED furnished for
the open wire type. Units have up to three stages to minimize impact noise and vibration. The right mounting to the wall. [Option: In addition, a
of electric heat. A capillary tube type high limit end panel, right-hand front panel, 3 feet (914mm) tenant override switch shall be furnished as part
thermostat shall be provided to disconnect the of the right-hand end of the center front panel of the wall mounted sensor.)
heating elements through backup contactors if an and the hinged top access door shall be coated with
overheat condition is detected. a high density material to eliminate noise and vibration. Wall-mounted sensor with tenant over-
ride and setpoint adjustment A sensor
A front panel interlock switch shall be furnished VentiMatic shutter (room exhaust) with integral tenant override and status LED
to de-energize the electric resistance heating coil Where indicated, the unit ventilator manufacturer shall be furnished with the unit ventilators.
whe the center front socess panel is opened. shall provide an in-room air relief VentiMatic This sensor shall also contain a manually
shutter mounted on a separate wall intake louver adjustable temperature setting allowing the
An emergency electric heat switch shall be furnished to prevent excessive static pressure build-up In the controller setpoint to be increased or decreased
to allow the unit to be manually switched to electric room. The VentiMatic shutter shall be constructed by 3F (2C).
resistance heating in case the reverse cycle heating of galvanized steel with shutter dampers of woven
system becomes inoperative. This shall permit the glass fabric impregnated with silicone rubber. Wall sensor with setpoint adjustment
electric resistance heaters to operate as needed re- Units shall have a sensor furnished with a manu-
gardless of loop water temperature. Temperature controls The unit ventilator ally adjustable temperature setting allowing the
manufacturer shall provide factory installed, controller setpoint to be increased or decreased
Acoustical treatment The compressor shall calibrated, and tested temperature controls. Units by 3F (2C).
be mounted on neoprene compressor isolators for that are capable of providing up to 100% outside
external vibration isolation. Compressor enclosure air shall provide a microprocessor-based DDC [Accessory] Ventilation lockout relay
panels shall be 16-gauge minimum and control that can monitor conditions and automati- Units that are not on network control shall be fur-
crossbroken for additional rigidity to dampen cally adjust unit operations to maintain these nished with a [24V] [120V] ventilation lockout
vibration. Compressor enclosure panels and unit requirements. The control sequence shall be on relay to permit closing the outdoor damper dur-
front panel (compressor end) shall have 112 lbs. the basis of [ASHRAE II]. This DDC controller ing normal occupied operation. Outdoor air
(.68 kg) minimum density, 1" (25mm) thick glass shall have the following tenant adjustments: (1) damper shall close when the relay is energized by
fiber insulation and felt type material affixed to room temperature setpoint, (2) minimum percent a [24V] [120V] signal.
the interior surfaces to dampen the compressor outdoor air setting, and (3) unoccupied setpoint
sound. Unit shall have attenuating loops in both (offset). An LED status/fault indicator shall be [Accessory] Exhaust fan interlock relay
the suction and discharge lines to reduce furnished for inspection and a communications Each unit shall be furnished with an exhaust
mechanical vibration. port shall be incorporated to allow manipulation fan interlock relay. When energized by a [24V]
by a remote PC. The remote PC shall be able to [120V] external signal, the outdoor air damper
[Optional] Acoustical package access and change pertinent operating aind shall move to the 100% outdoor air position and
The compressor shall be mounted on room conditions from a remote location. The shall remain fully open.
neoprene compressor isolators for external microprocessor-based control must be capable of
vibration isolation. Sound attenuating loops and communicating to a local IBM-compatible PC [Accessory] Night control with unit day/
seamless flexible bronze hose vibration absorbers using the RS-232 protocol. When using this night switch (stand-alone units only)
shall be furnished in both the suction and discharge remote PC, the unit must be capable of reacting Each unit (except slaves) shall be furnished with a
lines to reduce mechanical vibration to the to changes made by the remote PC. The remote unit mounted day/night switch to permit manual

Catalog UV-1-231F / Page 30 / (6/99) AAF-HermanNelson


Specifications Water Source Heat Pump Units (Continued)
Models ARQ, ERQ
indexing from day to night mode.The unoccu- shall be provided around the perimeter of the louver
pied offset temperature setpoint(s) shall be in force where required.] Lintels shall be provided by the
when indexed to the night mode. The outdoor contractor above the wall intake louver opening.
air damper shall remain closed at all times during
the night mode. (Optional: Heavy-duty lattice grille horizontal and
vertical lines shall line up with the louver blades
[Accessory] Night control with unit day/ to present an aesthetic appearance. Grille shall
night relay Each unit (except slaves) shall be fabricated from mill finish aluminum. The standard
have a factory installed relay for day/night aluminum allow shall be [unpainted] [painted]
changeover. This relay shall have a [24V] [115V] [clear anodized].)
holding coil that, when energized by an external
source, shall be automatically indexed to the
night mode, placing the unoccupied temperature
setpoints in force. The outdoor air damper
shall remain closed at all times during the
night mode.

[Accessory] Night control with


unit-mounted time clock Each unit shall
be furnished with a unit-mounted, field pro-
grammed time clock for day/night changeover.
This clock shall have a battery backup that will
provide up to 150 hours of operation during a
power outage. A unit-mounted holiday switch
shall be furnished to allow manual changeover to
unoccupied control for extended or otherwise
unscheduled periods.

Wall sleeve The galvanized steel, one-piece


wall sleeve shall be set in a wall opening and butted
up directly against the intake louver.

The wall sleeve shall be fitted with an electrical


junction box containing a main on-off switch.
All field wiring connections shall be made in this
wall sleeve junction box.

It shall be the installing contractors responsibility


to make the final load side power wiring connec-
tions between the wall sleeve junction box and the
unit terminal block (including the wiring going
to the electric heating elements.)(The wall sleeve
shall be cartoned separately and shipped to the
jobsite preceding the unit ventilator. Junction box
shall ship separately for field installations.)

Wall intake louver The wall intake louver


shall be supplied by the unit manufacturer and
shall be of heavy-gauge [unpainted] [painted]
[clear anodized] aluminum construction. The
louver shall be of the [horizontal] [vertical] blade
type with weep holes along the face of the bottom
edge of the louver frame. A 12" (13mm) square
mesh bird screen shall be provided on the back of
the wall intake louver. [Option: A four-side flange

AAF-HermanNelson Catalog UV-1-231F / Page 31 / (6/99)


Contact Your Local AAF-HermanNelson Representative Today!

The information in this catalog supersedes and replaces previous [catalogs][bulletins] with regards to AAF-HermanNelson Incorporated Terminal Air
Conditioning products. Illustrations cover the general appearance of AAF-HermanNelson products at the time of publication. AAF-HermanNelson reserves the right to make
changes in design and construction at any time without notice.

4900 Technology Park Boulevard Auburn, New York 13021-9030 USA (315) 253-2771 1999 AAF-HermanNelson
Catalog UV-1-231F / Page 32 / (6/99)