Curso EMT

DIgSILENT PowerFactory

DIgSILENT PowerFactory EMT-Training

Introduccin

DIgSILENT PowerFactory EMT-Training

Introduccin: Transitorios en Sistemas de Potencia

Reference: IEC TR 60071-4 Computational Guide to Insulation Co-ordination and Modelling of Electrical Networks

DIgSILENT PowerFactory EMT-Training

Introduction: Transients in Power Systems

Transient event

Temporary
Overvoltages
TOV

Slow-front
overvoltages

Load rejection

Transformer energization

Line/cable energization &


re-energization

Line/cable droping

Parallel line/cable resonance

Uneven braker poles

Switching of inductive and


capacitive current

Fast-front
overvoltages

Back flashover

Direct lightning strike

Flashover in GIS

Very-fast-front
overvoltages

Reference: IEC TR 60071-4 Computational Guide to Insulation Co-ordination and Modelling of Electrical Networks

DIgSILENT PowerFactory EMT-Training

Introduccin: Simulaciones RMS vs EMT


Simulacin RMS (estabilidad):
Resuelve la red elctrica mediante ecuaciones fasoriales del
tipo [Y] * [U] = [I] .
Se usan ecuaciones diferenciales solo para la parte mecnica
de los generadores (Swing equation J

d
= Pmec Pelec
dt

Simulacin EMT (transitorios electromagnticos):


Resuelve toda la red elctrica usando nicamente ecuaciones
diferenciales del tipo [U] = [I] * [R] + [L] * d/dt( [I] ).
Representacin multifsica completa.
Resulta mas lenta que la simulacin RMS.
En PF: ajuste automtico de paso para acelerar la simulacin.
Transitorios Electromagnticos en PF: Introduccin

Introduccin: Simulaciones RMS vs EMT

Estabilidad:

V = j L I

EMT:

v=L

DIgSILENT PowerFactory EMT-Training

di
dt

I = jCV

i=C

dv
dt

DIgSILENT

Introduccin: Simulaciones RMS vs EMT


800.0

600.0

400.0

200.0

0.00

-200.0
0.00
4x555 MVA: Phase Current B in kA

0.12

0.25

0.38

Short Circuit Current with complete model (EMT-model)

[s]

Plots

0.50

Date: 4/25/2001
Annex: 1 /1

DIgSILENT PowerFactory EMT-Training

DIgSILENT

Introduccin: Simulaciones RMS vs EMT


300.0

250.0

200.0

150.0

100.0

50.00

0.00
0.00
4x555 MVA: Current, Magnitude in kA

0.12

0.25

Short Circuit Current with reduced model (Stability model)

0.38

[s]

Plots

0.50

Date: 4/25/2001
Annex: 1 /1

DIgSILENT PowerFactory EMT-Training

Introduccin: Simulaciones RMS vs EMT

Phenomen

RMS-Simulation

EMT-Simulation

Critical fault clearing time

(X)

Dynamic motor startup


Peak shaft-torque

X
0

(X)
X

Torsional oscillations
Subsynchronous resonance

X
0

X
X

Dynamic voltage stability


Self excitation of ASM

X
0

(X)
X

Oscillatory stability

((X))

AVR and PSS dynamics

(X)

Transformer/Motor inrush

(X)

HVDC dynamics
Switching Overvoltages
DIgSILENT PowerFactory EMT-Training

Modelos para
Simulaciones EMT

DIgSILENT PowerFactory EMT-Training

10

Modelos para Simulaciones EMT

Dependiendo del tipo de transitorio en consideracin,


diferente grado de detalle en los modelos resulta
requerido.
El modelo debe ser adecuado al rango de tiempo del
transitorio bajo anlisis.
Dependencia del modelo con la frecuencia debe ser
observada.

DIgSILENT PowerFactory EMT-Training

11

Transformadores,
Reactores, Autotransformadores

DIgSILENT PowerFactory EMT-Training

12

Modelo de Transformador

Secuencia Positiva:
C W(HV)-W(LV),1

R Cu,HV
C W(HV)-E

X ,HV
XM

X ,LV

R Cu ,LV
C W(HV)-E

R Fe
w1 : w2

Para capacidades de acoplamiento habilitar la opcin HFParameters en la pgina EMT (elemento transformador)

DIgSILENT PowerFactory EMT-Training

13

Modelo de Transformador

Secuencia Homopolar, arrollamiento Yn

R Cu0,HV
C W(HV)-E

X 0,HV

X 0,LV

X M0

3 XE,HV

R Cu 0,LV
C W(HV)-E

w1 : w2

3 R E,HV

DIgSILENT PowerFactory EMT-Training

14

Modelo de Transformador

Sec. Homopolar, con arrollamiento D (compensacin)


X S _ LV

X S _ HV

I0

3I 0

I0
U0

I0

I0
I0

I0

I0

I0

Tipo de ncleo de menor importancia.


Corriente homopolar en vaco (ladoYn) aproximadamente igual a la
corriente de cortocircuito de secuencia positiva.

DIgSILENT PowerFactory EMT-Training

15

Modelo de Transformador

Sec. Homopolar, sin arrollamiento en D.


X S _ HV

X S _ LV
3I 0

I0
I0

U0

I0

Tipo de nucleo resulta de importancia.


El flujo de secuencia homopolar se cierra por la cuba del transformador.
Altas corrientes en vaco (hasta algunas veces la corriente nominal)

DIgSILENT PowerFactory EMT-Training

16

Modelo de Transformador

Lineal

iM

Lineal por Tramos

1/Lsat

Polinomial
polynome

iM =

M
LM

1 + M

ksat

iM,sat

linear

1/Lunsat

knee touch

knee

Flujo de Codo en p.u.

Lunsat

Reactanciamagnetizante para condicin no-saturado en p.u.

Lsat

Reactancia magnetizante para condicin saturado en p.u.

ksat

Exponente representacin polinomial (ksat). Valores tpicos: 9,13,15.

knee

A mayor valor de ksat la curva resulta mas pronunciada (aguda)


DIgSILENT PowerFactory EMT-Training

17

Modelo de Autotransformador

Secuencia Positiva
r Cu 0,HV
uHV0

RE

Transformador YNyn con


los puntos de estrella
interconectados.

x 0,LV

r Cu0,LV

x M0

N HV

(1+t) : 1

XE

Auto-Transformador:

x 0,HV

3 x E,HV

3 x E,LV

3 r E,HV

3 r E,LV

N LV

Secuencia Homopolar
R Cu0,HV
U HV0
N HV

X 0,HV

X 0,LV R Cu0,LV

X M0,HV

(1+t) : 1

3 XE

w1 : w2

N LV

U LV0

3 RE

DIgSILENT PowerFactory EMT-Training

18

Caso de Aplicacin:
Corrientes de Arranque

DIgSILENT PowerFactory EMT-Training

19

Corrientes de Arranque en Transformadores

DIgSILENT PowerFactory EMT-Training

20

10

Corrientes de Arranque en Transformadores

DIgSILENT PowerFactory EMT-Training

21

Corrientes de Arranque en Transformadores

A mayor potencia del transformador:


I_inrush / I_nominal tiende a disminuir
Mayor duracin del transitorio de energizacin
Sn < 1 MVA => I_inrush ~ 10 15 I_nominal
Sn > 1 MVA => I_inrush ~ 1 8 I_nominal
Importancia del fenmeno para:
Ajuste protecciones: corrientes de arranque pueden saturar a
los transformadores de medicin de corriente TIs.
Cadas de tensin durante el transitorio (que puede durar
varios segundos).
Sobretensiones por desconexin durante el transitorio de
arranque por interrupcin de altas corrientes.
Corrientes de arranque (Inrush)

22

11

Manejo de las Simulaciones


en Dominio del Tiempo

DIgSILENT PowerFactory EMT-Training

23

Manejo de las Simulaciones

Flujo Cargas
Condiciones Iniciales

Setup

Selecciones mtodo (valores RMS)


Representacin de la Red:
balanceada/desbalanceada

Definir Variables
Definir Eventos

Inicializar Simulacin
Definir/Cambiar Eventos
Continuar Simulacin
Graficar Resultados

DIgSILENT PowerFactory EMT-Training

Simulacin

24

12

Conexin de Capacitores

DIgSILENT PowerFactory EMT-Training

25

Conexin de Capacitores

DIgSILENT PowerFactory EMT-Training

26

13

Conexin de Capacitores
Circuitos LC bsicos:

Z0 =

L
C

i (t ) =

VS
sin (0 t )
Z0

0 =

1
L C

vC (t ) = VS 1 cos (0 t ) + VC 0 cos (0 t )
La corriente de arranque puede ser varias veces la corriente de pico
de frecuencia fundamental (ej. 10 veces)
La oscilacin natural de tensin,despreciando amortiguamiento, es
siempre el doble de la tensin inicial en el interruptor
DIgSILENT PowerFactory EMT-Training

27

DIgSILENT

Conexin de Capacitores

4.00

3.00

2.00

1.00

0.00

-1.00

-2.00
-0.005
-0.000
C1: Capacitor: Phase Voltage in p.u.
AC Voltage Source: Source: Phase Voltage in p.u.

0.005

0.010

[s]

0.015

-0.005
C1: Capacitor: Inrush current in p.u.

0.005

0.010

[s]

0.015

15.00

10.00

5.00

0.00

-5.00

-10.00

DIgSILENT PowerFactory EMT-Training

-0.000

28

14

Conexin de Capacitores: Amplificacin de Tensin

Amplificacin de tensin, casos mas desfavorables:


La potencia del capacitor a conectar es considerablemente
mas grande que la capacidad total del sistema de baja tensin

0.00
0.00
3.49

0.00
-1.22
3.49

Cable

T3
132.07
1.00
-0.01

0.00
0.00

T2

Qcomp

T1

132.05
1.00
-0.00

Trf-1

20.13
1.01
-150.02

0.03
-1.17
2.42

-0.00
1.22
2.42

Line

-0.03
1.17
1.22

0.03
-1.39
1.22

0.03
-1.39

Usource

Baja potencia de cortocircuito en la barra de alta tensin

DIgSILENT PowerFactory EMT-Training

29

Conexin de Capacitores: Amplificacin de Tensin

Frecuencias de resonancia dominates: 0,cir1 = S kk Qsh

0,cir 2 = ST Qc

Si ambas frecuencias son prximas puede ocurrir uan amplificacind e


la tensin: la oscilacin transitoria, iniciada por la energizacin de C sh
excita la resonancia serie del segundo circuito

U c puede alcanzar valores de hasta 4 p.u. en el cable

DIgSILENT PowerFactory EMT-Training

30

15

Conexin de Capacitores: Amplificacin de Tensin

2.00

1.00

0.00

-1.00

-2.00

-3.00
-30.00

0.00

30.00

60.00

90.00

[ms]

120.00

0.00

30.00

60.00

90.00

[ms]

120.00

0.00

30.00

60.00

90.00

[ms]

120.00

T2: Phase Voltage A in p.u.


T2: Phase Voltage B in p.u.
T2: Phase Voltage C in p.u.

4.00

2.00

0.00

-2.00

-4.00
-30.00
T3: Phase Voltage A in p.u.
T3: Phase Voltage B in p.u.
T3: Phase Voltage C in p.u.

6.00
4.00
2.00
0.00
-2.00
-4.00
-6.00
-30.00
T4: Phase Voltage A in p.u.
T4: Phase Voltage B in p.u.
T4: Phase Voltage C in p.u.

DIgSILENT PowerFactory EMT-Training

31

Conexin de Capacitores: Amplificacin de Tensin

Como mitigar la amplificacin de tensin:


Descargadores en el lado de baja tensin: verificar solicitacin
energtica!
Interruptores controlados (PoW CB) para el capacitor de alta
tensin o uso de resistores de pre insercin
Conectar capacitores grandes en varios pasos
Desintonizar el circuito: reubicar el banco de capacitores,
distribuir la capacidad en varios bancos
Instalar filtros en el lado de baja tensin para desintonizar el
circuito

DIgSILENT PowerFactory EMT-Training

32

16

Tensin de Recuperacin
tras el Despeje de Fallas

DIgSILENT PowerFactory EMT-Training

33

Transient Recovery Voltage (TRV)

System
characteristic at
fault location

0 2
vC (t ) = 2
V cos ( t ) cos (0 t )
0 2 m
vC (t ) Vm cos ( t ) cos (0 t )
vC (t ) Vm 1 cos (0 t )
DIgSILENT PowerFactory EMT-Training

34

17

DIgSILENT

Transient Recovery Voltage (TRV)

2,00

1,00

0,00

-1,00

-2,00
100,0

108,0
UW-3: Phase Voltage A in p.u.
UW-3: Phase Voltage B in p.u.
UW-3: Phase Voltage C in p.u.

116,0

124,0

132,0

[ms]

DIgSILENT PowerFactory EMT-Training

140,0

35

Modelos de Lneas/Cables

DIgSILENT PowerFactory EMT-Training

36

18

Modelos de Lneas

Estado Estacionario:
PI Nominal (parmetros concentrados)
PI Equivalente (parmetros distribuidos)

Estado Transitorio (Dominio del Tiempo)


PI Nominal (parmetros concentrados)
Modelos de Parmetros Distribuidos
- Constantes
- Dependientes de la Frecuencia

DIgSILENT PowerFactory EMT-Training

37

Parmetros Concentrados

G/2

C/2

G/2

C/2

Z = Z l = R l + j L l
Y =

DIgSILENT PowerFactory EMT-Training

1
1
Y l = (G l + j C l )
2
2

38

19

Parmetros Concentrados

Ventajas:
Fcil de implementar y de poco requerimiento de clculo.
Sencillo para cualquier nmero de fases y de circuitos (solo cambia
la dimensin de las matrices Z y Y.
Posibilidad de conectar varios circuitos en cascada (line routes) y
definir transposiciones complicadas.
Modelo se puede usar para estado transitorio (con limitaciones)
Desventajas:
Errores considerables si la lnea es demasiada larga ( > 150 km
para 50 Hz, > 15 km para 600 Hz).
No representa la dependencia de R y L para estudios de barridos de
frecuencia y armnicos.
Modelos de lneas en estado estacionario

39

Parmetros Distribuidos: Estado Estacionario

V
= I ( x) Z
x

I
= V ( x) Y
x

Z = R + j L

Y = G + j C

DIgSILENT PowerFactory EMT-Training

40

20

Parmetros Distribuidos: Estado Estacionario

V
= I ( x) Z
x

2V
= Z Y V ( x)
x 2

I
= V ( x) Y
x

2I
= Z Y I ( x)
x 2

Solucin del tipo:

U ( x) = K1 e x + K 2 e x
Z C I ( x) = K1 e x + K 2 e x
where

= Z Y

ZC =

Z
Y

DIgSILENT PowerFactory EMT-Training

41

Parmetros Distribuidos: Estado Estacionario

Is
Zc ,

Vs

Ir
Vr

Con condiciones de borde:

cosh l
Vr
I = 1 sinh l
r
ZC

DIgSILENT PowerFactory EMT-Training

Z C sinh l
= A B Vs
cosh l C D I s

42

21

Parmetros Distribuidos: Estado Estacionario

Z = Z C sinh l = Z l

sinh l
l

l
thg

cosh l 1 1
2

Y =
= Y l
l
Z C sinh l 2
2
DIgSILENT PowerFactory EMT-Training

43

Parmetros Distribuidos: Estado Estacionario

Ventajas:
Provee una solucin exacta para lneas con y sin transposicin en
dependencia de la frecuencia.
Modelo exacto de la lnea para estudio de barrido en frecuencia y
flujo de armnicos.

Desventajas:
Mayor requerimiento de clculo.
Modelo deben adaptarse para su uso en estado transitorio (ya que
el valor de Z y de Y dependen de la frecuencia).

Modelos de lneas en estado estacionario

44

22

Parmetros Distribuidos: Dominio del Tiempo

Se tiene del estado estacionario:

U r Z C I r = (U s + Z C I s ) e l
U s Z C I s = (U r + Z C I r ) e l
Z C = Z C ( ) =

R + j L
G + j C

= ( ) = ( ) + j ( ) =

(R +

j L) (G + j C )

B. se necesitan algunas restricciones para dominio del tiempo

DIgSILENT PowerFactory EMT-Training

45

Parmetros Distribuidos Constantes

Si las prdidas de la lnea son despreciables:

ZC = ZC ( ) =

v=

R + j L
L

G + j C
C

(R + j L) (G + j C ) j

L C = j

1
L C

DIgSILENT PowerFactory EMT-Training

46

23

Parmetros Distribuidos Constantes

En dominio del tiempo luego de la transformada inversa de Fourier:

us ( t ) = Z C is ( t ) + [ur ( t ) + Z C ir ( t )]
u r ( t ) = Z C ir ( t ) + [u s ( t ) + Z C is ( t )]

DIgSILENT PowerFactory EMT-Training

47

Parmetros Distribuidos Dependientes de la Frecuencia

V r Z c ( ) I r = (V s + Z c ( ) I s ) A( )
A( ) = e l
Aproximacin mediante racionales:

Aapp (s ) = e s min k

Z c app (s ) = k

(s + z1 ) (s + z2 ) (s + zn ) = k1 + k2 + + km
(s + p1 ) (s + p2 ) (s + pm ) (s + p1 ) (s + p2 )
(s + pm )

(s + z1 ) (s + z2 ) (s + zn ) = k + k1 + k2 k n
(s + p1 ) (s + p2 ) (s + pn ) 0 (s + p1 ) (s + p2 ) (s + pn )

DIgSILENT PowerFactory EMT-Training

48

24

Frequency Dependent Distributed Parameters Model

DIgSILENT PowerFactory EMT-Training

49

Parmetros Distribuidos Dependientes de la Frecuencia

Parmetros Distribuidos Constantes:


Simple y rpido, se puede usar para transitorios en los cuales solo un
rango pequeo de frecuencias es de inters.
Aplicaciones:
Line Switching (generalmente suficiente)
Impulsos atmosfricos

Parmetros distribuidos dependientes de la frecuencia:


Mas complejo y mas lento. Necesario en caso de que un amplio rango
de frecuencias sea de inters.
Aplicaciones:
Transitorios con corrientes de retorno por tierra
Line switching (mas exacto)

Modelos de lneas en estado transitorio

50

25

DIgSILENT

Comparacin Modelos de Lnea

1.00

0.00

-1.00

-2.00
-0.001

0.00
L-3-1: Phase Voltage A/Terminal j in p.u.
L-3-1: Phase Voltage A/Terminal j in p.u.
L-3-1: Phase Voltage A/Terminal j in p.u.

0.00

0.00

0.00

DIgSILENT PowerFactory EMT-Training

[s]

0.01

51

Sobretensiones

DIgSILENT PowerFactory EMT-Training

52

26

Sobretensiones

Descarga Atmosfrica (externas)


Impacto directo de rayo
Impacto sobre hilo de guarda
Descarga inversa (Back flashover)
Sobretensiones inducidas, etc.
Sobretensiones de Maniobra (internas)
Energizacin y recierre de lneas
Interrupcin de (pequenas) corrientes inductivas y/o capacitivas
Interrupcin de corrientes de falla
Incepcin de fallas
Sobretensiones Sostenidas (internas)
Rechazo de carga, efecto Ferranti

DIgSILENT PowerFactory EMT-Training

53

Sobretensiones

DIgSILENT PowerFactory EMT-Training

54

27

Sobretensiones por
Maniobras en Lneas

DIgSILENT PowerFactory EMT-Training

55

Cierre y Recierre de Lneas

Interruptor I y II no pueden cerrar en forma simultnea.


Por lo tanto, la onda de tensin que viaja por la lnea se duplica al
alcanzar el final de la lnea abierta.
La sobretensin puede ser > 2 pu debido a:
Fuente A no es infinita (=> reflexiones)
Carga atrapada en la lnea
Los polos del interruptor no cierran simultneamente.
Distintas velocidades de propagacin ( velocidad de la
secuencia homopolar menor que la positiva).

Sobretensiones de maniobra

56

28

Reduccin de Sobretensiones de Cierre

Interruptores con resistencia de preinsercin de 1 o 2 pasos (con 8


o 10 ms de retardo).
Cierre controlado (interruptor cierra cuando la tensin es la misma
en ambos contactos).
Uso de descargadores a ambos extremos de la lnea.
Descargadores de suspensin a lo largo de la lnea.

Sobretensiones de maniobra

57

Comportamiento estadstico

La amplitud depende del instante de cierre de los interruptores (cruce


por cero, pico, etc. de la forma de onda).
Dispersin del cierre de los polos del interruptor.

Mxima sobretensin de maniobra posible:


Baja probabilidad de ocurrencia
La coordinacin del aislamiento no sera econmicamente viable para
este valor mximo.
Coordinacin del aislamiento:
Interesa una distribucin estadstica de las sobretensiones de
maniobra.

Sobretensiones de maniobra

58

29

Interruptores Estadsticos

total

=t

cierre

+t

dispersin

Distribucin Normal
(o Gaussiana)

f (T ) =

1 t T

exp

2
2
1

T=

1 n
Ti
n i =1

1
n

(T T )
n

i =1

Sobretensiones de maniobra

Distribucin Uniforme del tiempo


de cierre y dispersin

f (T ) =

1
2 3

T=

1 n
Ti
n i =1

1
n

(T T )
n

i =1

59

Implementacin con DPL

Sobretensiones de maniobra

60

30

Sobretensiones de Origen
Atmosfrico
(Externas)

DIgSILENT PowerFactory EMT-Training

61

Descargas Atmosfricas

Impacto directo sobre el conductor de fase (mas bien raro)

Descarga inversa (Back-flashover )


Impacto sobre el hilo de guardia o la estructura de la torre
que con el aumento de la tensin termina contorneando al
aislador descargndose en el conductor de fase.

Tensiones inducidas por impacto en la cercanas de lneas.

Sobretensiones de origen atmosfrico

62

31

Formas de Onda Estandard

Acc. IEC Publ.60-1, VDE 0432-2:


Impulso de Tensin : T1 = 1,2 s 30% ; T2 = 50 s 20%
Impulso de Corriente : T1 = 8 s; T2 = 20 s
DIgSILENT PowerFactory EMT-Training

63

Impulso Biexponencial

u( t ) = U 0 e t / 2 e t / 1

Pendiente en el origen distinta de cero


El valor de pico del impulso no es directamente Uo.
Sobretensiones de origen atmosfrico

64

32

Impulso Heidler
n

I
i( t ) = 0 1 n e t /

t
1 +
1
1 -> proporcional al tiempo de frente
-> proporcional al tiempo de cola
I0 -> valor de pico de la onda
n -> ajuste de la mxima pendiente del frente de la onda.( n
aumenta, punto de max. pendiente se acerca al pico)
Pendiente en el origen distinta de cero
Sobretensiones de origen atmosfrico

65

33