Está en la página 1de 42

CONTROL DE VERSIN

01

Aprob

30.03.15

VERSIN 0

YBR

01.01.15

Aprob:

Fecha:

CONTROL DE VERSIN DEL DOCUMENTO

27.06.15

GIGAWATT

LEVANTAMIENTO DE OBSERVACIONES

27.03.15

GIGAWATT

EDICION INICIAL

Rev.

Fecha:

Nombre:

Descripcin:

CLIENTE

AMPLIACIN DE LA S.E.T. CHILINA 138/33


kV y 33/10 kV, ALTO SELVA ALEGRE,
AREQUIPA

Gigawatt

ESTUDIO BSICO DE INGENIERA

Ingenieros

Nombre
Prepar:

GIGAWATT

Revis:

SEAL

Fecha
27.06.15

MEMORIA DESCRIPTIVA DEL


PROYECTO

Aprob:
Cdigo :

Documento N:
GW-SEAL-001-2015

Nombre del documento : Memoria del proyecto

EBI-001_MDP

Revisin: 1
Pginas: 040

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

CONTENIDO
1.

ASPECTOS GENERALES ..................................................................................... 4


1.1.

ANTECEDENTES DEL PROYECTO ........................................................................ 4

1.2.

OBJETIVOS DEL PROYECTO ................................................................................. 5

1.3.

ALCANCES DEL PROYECTO .................................................................................. 5

1.3.1.
1.3.1.1.
1.3.1.2.
1.3.1.3.
1.3.1.4.
1.3.1.5.
1.3.1.6.
1.3.2.
1.3.3.

OBRAS ELECTROMECNICAS .......................................................................................... 5


Patio de Llaves: ...................................................................................................................... 5
En Sala de Celdas: ................................................................................................................. 6
En Sala de Control: ................................................................................................................ 7
En Sala de Celdas 10 kV Existente: .................................................................................. 8
Desmontaje electromecnico: ............................................................................................ 8
Reubicacin de Equipos de Patio: .................................................................................... 8
SISTEMA DE AUTOMATIZACIN Y COMUNICACIONES: ........................................... 8
OBRAS CIVILES: .................................................................................................................... 8

1.4.

NORMATIVA .............................................................................................................. 9

1.5.

DESCRIPCIN DEL REA DEL PROYECTO ......................................................... 9

1.5.1.
1.5.2.
1.5.3.

UBICACIN GEOGRFICA .................................................................................................. 9


CONDICIONES CLIMATOLGICAS ................................................................................. 10
VAS DE ACCESO ................................................................................................................ 10

2. CRITERIOS DE DISEO DE OBRAS ELECTROMECNICAS Y


ELCTRICAS: .............................................................................................................. 11

3.

2.1.

CONDICIONES AMBIENTALES:............................................................................ 11

2.2.

NIVELES DE TENSIN NOMINAL: ........................................................................ 11

2.3.

NIVELES DE AISLAMIENTO: ................................................................................. 12

2.4.

DISTANCIAS MNIMAS DE SEGURIDAD:............................................................. 12

2.5.

SISTEMA DE PUESTA A TIERRA: ........................................................................ 13

2.6.

DEMANDA DE POTENCIA: .................................................................................... 13

2.7.

NIVELES DE CORTOCIRCUITO: ........................................................................... 14

2.8.

CONTROL: ............................................................................................................... 14

2.9.

APANTALLAMIENTO: ............................................................................................ 14

2.10.

SERVICIOS AUXILIARES: ...................................................................................... 14

2.11.

ILUMINACIN: ........................................................................................................ 14

CRITERIOS DE DISEO DE OBRAS CIVILES: ................................................. 15


3.1.

REA DISPONIBLE: ............................................................................................... 15

3.2.

CRITERIOS PARA EL DISEO DE CIMENTACIONES: ....................................... 15

3.2.1.
3.3.

4.

Clculo de la Capacidad Portante en Suelos:................................................. 15


SISMICIDAD............................................................................................................. 15

CARACTERSTICAS GENERALES DEL PROYECTO ...................................... 17

MEMORIA DE PROYECTO

Pg. 2 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

5.

6.

4.1.

NIVELES DE TENSIN ........................................................................................... 17

4.2.

NIVEL DE AISLAMIENTO ....................................................................................... 17

4.3.

DEMANDA DE POTENCIA ..................................................................................... 18

4.4.

NIVELES DE CORTOCIRCUITO ............................................................................ 20

4.5.

MEDICIN Y CLCULO DE RESISTIVIDAD DE TERRENO ................................ 21

OBRAS ELECTROMECNICAS - EQUIPAMIENTO PROYECTADO .............. 22


5.1.

TRANSFORMADORES DE POTENCIA ................................................................. 22

5.2.

EQUIPO HBRIDO EN 138 KV ................................................................................ 23

5.3.

TRANSFORMADORES DE TENSIN DE 138 KV ................................................ 24

5.4.

PARARRAYOS EN 138 KV ..................................................................................... 24

5.5.

CELDAS EN 33 KV .................................................................................................. 24

5.6.

CELDAS METAL CLAD EN 10 KV ......................................................................... 26

5.7.

TABLEROS DE CONTROL Y PROTECCIN ........................................................ 27

5.8.

BANCO DE BATERAS, CARGADOR RECTIFICADOR Y SS.AA. ...................... 28

5.9.

REUBICACIN DE EQUIPOS EXISTENTES ......................................................... 30

5.10.

RED DE TIERRA...................................................................................................... 31

5.11.

CABLES DE ENERGA EN MEDIA TENSIN ....................................................... 31

5.12.

CABLES DE CONTROL Y ENERGA EN BAJA TENSIN .................................. 32

SISTEMA DE AUTOMATIZACIN Y COMUNICACIONES ............................... 32


6.1.
6.2.
6.3.
A.
B.
C.
D.
E.
F.
G.
H.
I.

7.

CARACTERSTICAS GENERALES DEL SISTEMA ........................................................... 32


ARQUITECTURA DEL SISTEMA DE MONITOREO Y CONTROL: ................................. 34
EQUIPAMIENTO PROYECTADO ........................................................................................... 36
UNIDAD CENTRAL DE SUBESTACION .................................................................................... 36
INTERFAZ HOMBRE MAQUINA (IHM): ..................................................................................... 37
UNIDAD DE SINCRONIZACIN DE TIEMPO (GPS):.............................................................. 38
SWITCH ETHERNET INDUSTRIAL: ........................................................................................... 38
CABLEADO Y TERMINALES DE COBRE: ............................................................................... 39
PATCH CORDS PARA FIBRA TICA: ...................................................................................... 39
PITGAILS PARA FIBRA TICA: ................................................................................................. 39
CABLE DE COBRE ETHERNET TIPO FTP: ............................................................................. 39
GABINETE METLICO: ................................................................................................................ 39

OBRAS CIVILES ................................................................................................... 40


7.1.
7.2.
7.3.
7.4.
7.5.
7.6.
7.7.
7.8.

DEMOLICIONES Y DESMONTAJES ..................................................................................... 40


CIMENTACIONES DE EQUIPOS ELECTROMECNICOS................................................ 40
POZA DE RECUPERO DE ACEITES ..................................................................................... 40
LINEA SUB TERRANEA DE MEDIA TENSIN- BUZONES ............................................. 40
SISTEMA DE CANALETAS ..................................................................................................... 41
TRATAMIENTO DE TERRENO ACCESOS DRENAJE................................................ 41
ADECUACIN DE AMBIENTE PARA SALA DE CELDAS ............................................... 41
ADECUACIN DE AMBIENTE PARA SALA DE CONTROL ............................................ 42

8.

PRESUPUESTO REFERENCIAL ........................................................................ 42

9.

PLAZO DE EJECUCIN ...................................................................................... 42

MEMORIA DE PROYECTO

Pg. 3 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

MEMORIA DESCRIPTIVA
1. ASPECTOS GENERALES
1.1. ANTECEDENTES DEL PROYECTO
El sistema elctrico Arequipa se encuentra ubicado en el Departamento de Arequipa,
abasteciendo de energa a la ciudad de Arequipa dentro del rea de demanda 09, es
uno de los sistemas ms antiguos que existen, donde el abastecimiento de energa
es por la Empresa de Generacin de Arequipa S.A. (EGASA) y el Sistema
Interconectado Nacional (SEIN), la distribucin y comercializacin lo realiza la
empresa Sociedad Elctrica del Sur Oeste S.A (SEAL).
La subestacin de Chilina, es materia de trabajo del presente proyecto, la cual ser
ampliada con la finalidad de suministrar potencia y energa elctrica en beneficio de
la ciudad de Arequipa, as como mejorar el perfil de tensin a los clientes y a la vez
atender el incremento de la demanda, evitando incumplir con las condiciones y
obligaciones de los contratos de suministro suscritos, garantizando el suministro
regular de energa elctrica con la calidad y seguridad establecidas en la Ley de
Concesiones Elctricas (LCE) y la Norma Tcnica de Calidad de Servicios Elctricos
(NTCSE).
El crecimiento de la poblacin y de la actividad comercial e industrial de la ciudad de
Arequipa, (capital de la provincia) ha producido en los ltimos aos, el incremento del
consumo de energa elctrica, que ha tenido como consecuencia la necesidad de
una mayor oferta de energa.
La S.E.T. Chilina 138/33 kV de propiedad de EGASA, entro en operacin el ao 2002
con la finalidad de abastecer la demanda requerida del sistema elctrico Arequipa.
Esta subestacin est equipada con un transformador de potencia de 60 MVA
(ONAF); 138/33 kV para inyectar energa al sistema elctrico Arequipa en 33 kV
mediante la salidas en la doble barra de Convertidor y Chilina (Parque Industrial
(Challapampa) I-II y Jess I-II).
La S.E.T. Chilina de propiedad de SEAL, cuenta con un transformador de 20/25 MVA
(ONAN/ONAF) 33/10 kV, ubicado en las instalaciones de la central trmica. Chilina,
para atender la demanda requerida en 10 kV en los distritos aledaos de la
subestacin.

MEMORIA DE PROYECTO

Pg. 4 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

Hoy en da la demanda de la ciudad de Arequipa se ha incrementado


considerablemente por lo que, existe la necesidad de ampliar la capacidad de estas
subestaciones para atender las condiciones de operacin venideras.
1.2. OBJETIVOS DEL PROYECTO
El proyecto tiene por objetivo general la suficiente provisin de energa para atender
la creciente demanda del sistema elctrico Arequipa con estndares de calidad
segn NTCSE.
Los objetivos especficos son:
Garantizar la disponibilidad de energa para la demanda existente y futura con una
capacidad instalada de 135 MVA en 33 kV y 50 MVA en 10 kV.
Construir

infraestructura

electromecnica

civil,

que

cumpla con

los

requerimientos tcnicos y ambientales establecidos por las normativas vigentes y


opere confiablemente durante la vida til de 20 aos.
1.3. ALCANCES DEL PROYECTO
El Proyecto Ampliacin de Potencia de la Subestacin de Transformacin Chilina
138/33 kV y 33/10 kV Alto Selva Alegre-Arequipa de manera general plantea el
incremento de la capacidad instalada para disponer de una oferta de 135 MVA en
33 kV y 50 MVA en 10 kV; adicionalmente propone renovar todas las celdas de SEAL
en 33 kV cuya vida til ha sido superada y actualmente representan un riesgo para
la continuidad del suministro.
El presente proyecto se desarrollar dentro de los lineamientos tcnicos y
econmicos, que garanticen su adecuada operatividad y seguridad durante su vida
til.
Para

lograr

los

alcances fundamentales,

ser

necesario

implementar

la

infraestructura electromecnica y civil necesaria, de acuerdo al detalle siguiente:


1.3.1.

OBRAS ELECTROMECNICAS

1.3.1.1. Patio de Llaves:


Suministro e Instalacin de un transformador de potencia trifsico de 75 MVA
(ONAF), 138/33 kV.

MEMORIA DE PROYECTO

Pg. 5 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

Suministro e Instalacin de un transformador de potencia trifsico de 25 MVA


(ONAF), 33/10 kV.
Suministro e Instalacin de un transformador de servicios auxiliares 33/0.38-0.22
kV; 100 kVA.
Suministro e Instalacin de equipos hbridos, 170 kV, 750 kVp (BIL), 2000 A,
31.5 kA, equipados con interruptores de potencia, transformadores de corriente y
seccionadores con cuchilla a tierra.
Suministro e Instalacin de transformadores de tensin capacitivos monofsicos;
170 kV, 750 kVp BIL.
Suministro e Instalacin de Pararrayos de xido metlico con contador de
descargas de 120 kV, 40 kV y 12 kV.
Suministro y montaje de prtico metlico de celosa para lnea de llegada en
138 kV.
Suministro y montaje de prticos metlicos para barra en 138 kV.
Suministro y montaje de un poste metlico de 36 metros para lnea de llegada en
138 kV.
Suministro y montaje de dos postes metlicos de 21 metros para la lnea de llegada
Charcani VI en 33 kV.
Suministro e Instalacin de conductores AAAC para barra flexible.
Suministro e Instalacin de cables de energa para la acometida de 33 kV.
Suministro e Instalacin de cables de energa para la acometida de 10 kV.
Ampliacin de red de tierra profunda hacia el rea proyectada del patio de llaves.
Instalacin de red de tierra superficial, derivaciones y conexin a equipos de patio
de llaves.
Instalacin de sistema de apantallamiento mediante cable de guarda.
Instalacin del sistema de fuerza e iluminacin normal y emergencia.
1.3.1.2. En Sala de Celdas:
Suministro e Instalacin de 03 Celdas blindadas con aislamiento en gas (GIS) para
Transformador de doble barra en 33 kV.

MEMORIA DE PROYECTO

Pg. 6 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

Suministro e Instalacin de 08 Celdas blindadas con aislamiento en gas (GIS) de


Lnea de doble barra en 33 kV.
Suministro e Instalacin de 01 Celda blindada con aislamiento en gas (GIS) de
Acoplamiento transversal de doble barra en 33 kV.
Suministro e Instalacin de 02 Celdas blindadas con aislamiento en gas (GIS) de
Acoplamiento longitudinal de doble barra en 33 kV.
Suministro e Instalacin de 01 Celda blindada con aislamiento en gas (GIS) de
Medicin de doble barra en 33 kV.
Suministro e Instalacin de 01 Celda blindada con aislamiento en gas (GIS) para
Servicios Auxiliares de doble barra en 33 kV.
Instalacin del Sistema de Fuerza e Iluminacin Normal y Emergencia.
Suministro y tendido de cables de energa en 33 kV.
1.3.1.3. En Sala de Control:
Suministro e Instalacin de 02 Tableros de Proteccin de Transformadores
Suministro e Instalacin de 01 Tablero de Proteccin de Lnea.
Suministro e Instalacin de 01 Tablero de Proteccin de Barra y Registrador de
falla para las bahas 138 kV.
Suministro e Instalacin de 01 Tablero de Automatizacin y Comunicaciones.
Suministro e Instalacin de 02 Tableros para Servicios Auxiliares en AC y DC.
Suministro e Instalacin de 01 Cargador - Rectificador de Bateras en 110 Vcc.
Suministro e Instalacin de 01 Cargador - Rectificador de Bateras en 48 Vcc.
Suministro e Instalacin de Banco de Bateras Plomo - Acido para 110 Vcc.
Suministro e Instalacin de Banco de Bateras Plomo - Acido para 48 Vcc.
Suministro y tendido de cables de control y medida.
Instalacin del Sistema de Fuerza e Iluminacin Normal y Emergencia.

MEMORIA DE PROYECTO

Pg. 7 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

1.3.1.4. En Sala de Celdas 10 kV Existente:


Suministro e instalacin de 01 Celda de Remonte y Acoplamiento tipo metal clad
en 10 kV.
Suministro e Instalacin de 01 Celda de Transformador tipo metal clad en 10 kV.
Suministro e Instalacin de 01 Celda de Lnea tipo metal clad para Reserva en
10 kV
Suministro y tendido de cables de energa en 10 kV.
1.3.1.5. Desmontaje electromecnico:
Desmontaje de prtico de llegada de lnea 138 kV.
Desmontaje de torres de lnea de 138 kV y 33 kV.
Desmontaje de cables y conductores.
1.3.1.6. Reubicacin de Equipos de Patio:
Reubicacin de transformador tensin capacitivo en 138 kV.
1.3.2.

SISTEMA DE AUTOMATIZACIN Y COMUNICACIONES:


Sistema de Automatizacin y Control de la S.E.T. Chilina de acuerdo a los
requerimientos vigentes.

1.3.3.

OBRAS CIVILES:
Cimentaciones de equipos de patio y soportes de acometidas en 138 kV y 33 kV,
pozos de recupero de aceite de transformadores, etc.
Ductos, buzones y canalizaciones para redes en 10 kV, 33 kV y control.
Cerco perimtrico, accesos y otros.
Demoliciones.
Adecuacin de la sala del convertidor de frecuencia para instalar las celdas en
33 kV: Se habilitar el espacio utilizado actualmente por equipamiento de la
antigua C.T. Chilina, cuyo plan de abandono se viene gestionando.

MEMORIA DE PROYECTO

Pg. 8 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

Adecuacin del auditorio para sala de control: Se habilitar el espacio existente


para la instalacin de los tableros de medicin, control, proteccin, S.S.A.A. y
comunicaciones.

1.4.

NORMATIVA
Normas Nacionales:
-

Cdigo Nacional de Electricidad - Suministro 2011.

Reglamento Nacional de Edificaciones 2012.

Normas Tcnicas Peruanas (NTP).

Ley de Concesiones Elctricas 25844 y su Reglamento.

Norma Tcnica de Calidad de los Servicios Elctricos DS N040-2011-EM.

Reglamento de Proteccin Ambiental en las actividades elctricas DS N029-94.

Reglamento de Seguridad y Salud en el Trabajo de las Actividades Elctricas


(RSSTAE).

Normas Internacionales:
-

American National Standards Institute (ANSI)

Institute of Electrical and Electronics Engineers (IEEE)

EN Standards (European Standards)

Internacional Electrotechnical Commission (IEC)

Verband Deutscher Elecktroteckniker (VDE)

Deutsche Industrie Normem (DIN)

National Electrical Manufacturers Association (NEMA)

1.5. DESCRIPCIN DEL REA DEL PROYECTO


1.5.1.

UBICACIN GEOGRFICA
La zona de proyecto queda ubicado en el Distrito de Alto Selva Alegre, Provincia y
Departamento de Arequipa Per, entre las coordenadas UTM - Sistema WGS 84: (E)
229406.59 y (N) 8187151.34 y a una altitud promedio de 2400 msnm el cual abastece
de energa al sistema elctrico Arequipa. Asimismo a 1009 km de la ciudad de Lima.
El terreno sobre el que descansa es origen volcnico, presenta una geologa muy
errtica, Arequipa cuenta con una extensin territorial de 9.682 km2.

MEMORIA DE PROYECTO

Pg. 9 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

Figura N01: Ubicacin del Proyecto

1.5.2.

CONDICIONES CLIMATOLGICAS
Arequipa experimenta una variacin de temperatura que es notoria entre el sol y la
sombra, posee un clima predominantemente seco en invierno, otoo y primavera
debido a la humedad atmosfrica, es tambin semirido a causa de la precipitacin
efectiva y templada por la condicin trmica.
Las caractersticas climticas principales son:

1.5.3.

Temperatura mnima

8.5 C

Temperatura media

15.8 C

Temperatura mxima

23.1 C

Humedad relativa promedio

48.8%

Velocidad media del viento

4 m/s.

VAS DE ACCESO
Para llegar al rea de estudio del proyecto desde la ciudad de Lima (referencia) se
cuenta con dos medios principales de transporte como la va terrestre y va area.
A continuacin describimos las maneras de acceder al rea del proyecto:

MEMORIA DE PROYECTO

Pg. 10 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

Va terrestre:
Arequipa se conecta con Lima a travs de la carretera con una distancia de
1009 km de Lima mediante la Panamericana Sur, tiempo de llegada diecisis
horas contando; adems con otras carreteras de acceso de las regiones ms
influyentes de la zona sur de nuestro pas.
Desde Tacna: carretera asfaltada Panamericana Sur Tacna Arequipa con una
distancia 371 Km tiempo de llegada seis horas.
Desde Cusco: carretera asfaltada Cusco Juliaca Arequipa con una distancia
de 448 Km tiempo de llegada 08 horas.
Va area:
Desde la ciudad de Lima a la ciudad de Arequipa a travs del Aeropuerto
Internacional Rodrguez Balln, tiempo de viaje es de una hora y treinta mitos.

Desde la ciudad de Cusco - Arequipa en media hora.

Desde ciudad Tacna o Juliaca Arequipa en veinte minutos.

2. CRITERIOS DE DISEO DE OBRAS ELECTROMECNICAS Y ELCTRICAS:


2.1. CONDICIONES AMBIENTALES:
Altitud mxima del proyecto : 2400 msnm
Temperatura mnima

: 8.5 C

Temperatura media

: 15.8 C

Temperatura mxima

: 23.1 C

Humedad relativa promedio : 48.8%

Velocidad media del viento

: 4 m/s

2.2. NIVELES DE TENSIN NOMINAL:


Los niveles de tensin de la zona de proyecto son:
- Alta tensin (Vnom)

138 kV.

- Alta tensin (Vmax)

145 kV.

- Media tensin (Vnom)

33 kV

- Media tensin (Vmax)

36 kV

MEMORIA DE PROYECTO

Pg. 11 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

2.3. NIVELES DE AISLAMIENTO:


Para

la

coordinacin

de

aislamiento

en

subestaciones

se

considera

las

recomendaciones de la Norma IEC, N 60071 Insulation Coordination, la altitud sobre


el nivel del mar de las instalaciones, el nivel de proteccin de los pararrayos, el grado
de puesta a tierra del sistema elctrico y el nivel isocerunico de la zona, a fin de corregir
los valores de servicio de la tensin en 138 kV, 33 k y 10kV.
Se presenta un resumen de los clculos:
Tabla 3.1: Niveles de Aislamiento
Tensin
Nominal
(kV)

Altura de
Instalacin

Tensin de

Tensin de

Tensin de

Diseo Asignada

Sostenimiento a

Sostenimiento al

al Equipo

Frecuencia Industrial

Impulso tipo rayo (BIL)

138

2400 msnm

170 kV

325 kVrms

750 kVp

33

2400 msnm

52 kV

95 kVrms

250 kVp

33(*)

No aplica

36 kV

70 kVrms

170 kVp

10

2400 msnm

17.5 kV

38 kVrms

95 kVp

(*) Los niveles de aislamiento indicados para los equipos instalados en celdas con aislamiento
de gas SF6.
2.4. DISTANCIAS MNIMAS DE SEGURIDAD:
Para las distancias mnimas y de seguridad se considera lo sealado por la norma IEC
60071 y el Cdigo Nacional de Electricidad.
Tabla 3.2: Distancias Mnimas de Seguridad
DESCRIPCIN

UNIDAD

VALOR

VALOR

Tensin nominal de la red

kV

138

33

Distancia mnima entre fase y tierra


Distancia mnima entre fases

m
m

1.50
1.50

0.48
0.48

Distancia mnima de trabajo horizontal

3.40

3.00

Distancia mnima de trabajo vertical

3.00

3.00

Distancia mnima de circulacin personal bajo conexiones

3.90

2.74

Distancia mnima entre la base de cualquier aislador y tierra

2.25

2.25

Distancia mnima de partes con tensin al cerco perimtrico


(Excepcin 2 CNE Suministro)

4.20

3.10

Distancia mnima de techo a lneas para pasaje de vehculos

5.65

4.49

Distancia mnima por circulacin vehicular (horizontal por maniobra)

3.30

3.30

MEMORIA DE PROYECTO

Pg. 12 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

2.5. SISTEMA DE PUESTA A TIERRA:


A partir de la obtencin de los planos de la malla profunda existente se ha evaluado la
ampliacin hacia el rea de donde se implementara las celdas de lnea y de
transformador as como tambin de los transformadores de potencia, asegurando que
las vas de acceso con posibilidad de trnsito de personal estn protegidas contra los
gradientes de potencial que pudieran generarse.
Resistividad del Terreno:
Con la aplicacin del mtodo Wenner se efectuaron las mediciones correspondientes
en el rea de ampliacin de la Subestacin Chilina. Las lecturas realizadas en cada
lugar fueron en forma longitudinal, expresados en la escala adecuada, obtenindose los
siguientes resultados:
Tabla 3.3: Resistividad del Terreno

Espaciamiento a
(m)
1
2
4
8
12

Resistividad Elctrica
Medida (.m)
1
2
32.8
55.5
48.4
44.9
61
39.9
54.2
33.9
46.5
44.3

Resistividad
Media (.m)
44.15
46.65
50.45
44.05
45.40

A partir de los valores registrados se efectuaron los clculos, con el software CYMGRD
para modelar las resistividades de las capas del suelo, obteniendo los siguientes
resultados:
2.6. DEMANDA DE POTENCIA:
La demanda para el presente estudio del Sistema Elctrico Chilina en el horizonte del
proyecto es:
Tabla 3.4: Cuadro de Demanda de Potencia

SUBESTACIN
CHILINA 138/33 KV
CHILINA 33/10 KV

MEMORIA DE PROYECTO

2015
(MW)
41.72
19.20

2016
(MW)
47.59
20.14

2017
(MW)
48.74
21.05

2027
(MW)
70.17
33.13

2037
(MW)
102.85
48.81

Pg. 13 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

2.7. NIVELES DE CORTOCIRCUITO:


Del anlisis del Sistema Elctrico se han determinado las corrientes de cortocircuito
durante el horizonte del proyecto. El equipamiento previsto deber soportar las
condiciones de falla.
Tabla 3.5: Resultados de Corto Circuito Horizonte del Proyecto

Cdigo DigSilent
CHIL138/33
CHIL138/33
CHIL33/10
CHIL33/10

Vnom
(kV)
138.0
33.0
33.0
10.0

2015
Actual
Mx. Icc
(kA)
5.32
14.53
14.45
14.66

2017-SP

2017-CP

2024-CP

2036-CP

Mx. Icc
(kA)
5.56
16.54
16.45
15.31

Mx. Icc
(kA)
6.45
19.66
19.57
24.97

Mx. Icc
(kA)
6.60
20.58
20.47
25.21

Mx. Icc
(kA)
6.84
23.69
23.71
26.72

2.8. CONTROL:
En forma general las protecciones deben poseer mando local y remoto, poseer interfaz
de comunicacin, indicadores locales de operacin, suficientes entradas y salidas para
poder implementar la lgica de protecciones.

2.9. APANTALLAMIENTO:
Se considera la ampliacin del apantallamiento contra descargas atmosfricas sobre el
patio previsto para implementacin de las celdas de lnea y de transformador as como
tambin de los transformadores de potencia. Los clculos para la determinacin de las
zonas protegidas se han realizado con el mtodo electrogeomtrico ms recomendado
en el diseo de subestaciones de potencia.
2.10. SERVICIOS AUXILIARES:
Se utilizar el sistema de servicios auxiliares de corriente alterna y continua existentes.
En el caso de corriente alterna, se dispone de una fuente de 100 kVA y 380/220V - 60Hz.
Para el caso de corriente continua existe un rectificador a 110 Vcc y 48 Vcc, con la
suficiente capacidad para alimentar las cargas adicionales de la ampliacin.

2.11. ILUMINACIN:
De acuerdo a lo establecido en el Cdigo Nacional de Electricidad Suministro 2011,
los valores de iluminacin debern ser mayores o iguales a 22 lux.

MEMORIA DE PROYECTO

Pg. 14 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

3. CRITERIOS DE DISEO DE OBRAS CIVILES:


3.1. REA DISPONIBLE:
Al tratarse de una subestacin existente, se han evaluado espacios disponibles internos
para acoger las instalaciones proyectadas.
3.2. CRITERIOS PARA EL DISEO DE CIMENTACIONES:
Para que una cimentacin tenga un comportamiento satisfactorio debe cumplir con los
dos siguientes requisitos:

La cimentacin debe ser segura contra una falla por corte del suelo que la soporta;
es decir la capacidad portante admisible del terreno debe ser superior a la carga
transmitida por la cimentacin.

3.2.1.

Clculo de la Capacidad Portante en Suelos:


La capacidad ltima del terreno se define como la mxima presin media de contacto
entre la cimentacin y el terreno tal que no se produzcan un fallo por cortante del
suelo. La capacidad portante se define como la capacidad ltima afectada por un
factor de seguridad (FS), cuyo valor suele oscilar entre 3 y 4.
La investigacin de campo se ha ejecutado de acuerdo a la Norma E-050 de Suelos
y Cimentaciones del Reglamento Nacional de Edificaciones y segn la NTP 339.162
(ASTMD 420) con el objeto de obtener el perfil estratigrfico y determinar las
caractersticas geotcnicas del terreno de fundacin. Para ello se ubic, dentro del
espacio de la Sub Estacin, una zona aparente para realizar la excavacin de la
calicata, de tal manera que permitiera realizar una observacin directa del terreno y
la obtencin de la muestra necesaria.

3.3. SISMICIDAD
Segn el Reglamento Nacional de Edificaciones (Normativa vigente actual 2006):
Norma E.030 Diseo Sismorresistente: Captulo II: Parmetros de sitio. Para la zona del
proyecto se tienen los siguientes parmetros geotcnicos:
Zonificacin (Z): clasificado como Zona 2 (sismicidad media) y calificado con
un valor de 0.3

MEMORIA DE PROYECTO

Pg. 15 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

Tabla 4.2: Cuadro de Zonificacin

Condiciones Geotcnicas (S): El suelo de fundacin pertenece a una


formacin, se trata de un suelo Intermedio. Luego en base a la Tabla N 02 del
Artculo 6, de la Norma E.030 Diseo Sismorresistente, clasificamos al terreno
de fundacin como un suelo intermedio, perfil S2, con una aceleracin del suelo
(Tp) de 0.6 y un parmetro de Sitio (S) de 1.2.
Tabla 4.3: Condiciones Geotcnicas

Categora de La Edificacin (U): Cada estructura est clasificada de acuerdo


con las categoras indicadas en la TABLA N 3. Por ser una Subestacin Elctrica
el coeficiente de uso e importancia es de 1.5, ya que se trata de una Edificacin
Esencial de categora A.
Tabla 4.4: Categora de las Edificaciones

MEMORIA DE PROYECTO

Pg. 16 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

3.4. Diseo de la Cimentacion:


Considerando que el diseo de las cimentaciones se realiza para absorber esfuerzos de
corte y flexin as como algunas verificaciones como las de punzonamiento. Adherencia
y anclaje, transmisin de esfuerzos, etc. El diseo considera las expresiones indicadas
en la norma de concreto armado comentarios en su seccin11 flexin, seccin13 corte
y torsin y seccin16 zapatas; as mismo, se deber tomar en cuenta algunas
disposiciones para el diseo ssmico como las mencionadas en la norma ACI 318 08
en su seccin 21.8 cimentaciones.
Para el anlisis de cimentaciones se emplea al programa SAFE, exportando las cargas
directamente desde el programa de anlisis y diseo de edificaciones ETABS; empleado
en el mtodo de los elementos finitos, con modelamiento de apoyos tipo resorte segn
el mdulo de balasto del terreno.
Con referencia al mdulo de balasto se tiene la siguiente tabla esfuerzo admisible
versus mdulo de balasto, la cual presenta valores en funcin a la capacidad de carga
del terreno.

Verificacin De Esfuerzos
Para el presente estudio, el suelo a una profundidad de 1.35 m se indica un esfuerzo
admisible del 8.3 Tn/m, siendo este dato importante para el anlisis de la cimentacin.
La verificacin de los resultados obedece a las combinaciones segn el reglamento que
exige, se crea una combinacin de SERVICIO con el fin de comprobar los esfuerzos del
terreno y esfuerzos en la estructura segn las dimensiones geomtricas de las zapatas
asignadas.

4.

CARACTERSTICAS GENERALES DEL PROYECTO

4.1.

NIVELES DE TENSIN
Los niveles de tensin en la zona de proyecto son:

4.2.

- Alta tensin

: 138 kV

- Media tensin

: 33 kV y 10 kV

NIVEL DE AISLAMIENTO
Para la coordinacin de aislamiento en subestaciones se considera las
recomendaciones de la Norma IEC, N 71 Insulation Coordination, la altitud sobre
el nivel del mar de las instalaciones, el nivel de proteccin de los pararrayos, el grado

MEMORIA DE PROYECTO

Pg. 17 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

de puesta a tierra del sistema elctrico y el nivel isocerunico de la zona, a fin de


corregir los valores de servicio de la tensin en 138 kV, 33 kV y 10 kV.
Se presenta un resumen de los clculos:

Tensin
Nominal
(kV)

Altura de
Instalacin

Tensin de

Tensin de

Tensin de

Diseo Asignada

Sostenimiento a

Sostenimiento al

al Equipo

Frecuencia Industrial

Impulso tipo rayo (BIL)

138

2400 msnm

170 kV

325 kVrms

750 kVp

33

2400 msnm

52 kV

95 kVrms

250 kVp

33(*)

No aplica

36 kV

70 kVrms

170 kVp

10

2400 msnm

17.5 kV

38 kVrms

95 kVp

(*) Los niveles de aislamiento indicados para los equipos instalados en celdas con
aislamiento de gas SF6.
4.3.

DEMANDA DE POTENCIA
La subestacin Chilina inyecta energa al Sistema Elctrico Arequipa en conjunto con
la S.E. Socabaya, y ms adelante con los aportes de la S.E. Parque Industrial y S.E.
Jess.
El horizonte de proyeccin para la evaluacin de la demanda ser de 20 aos; tal
como lo establece la Resolucin Directoral N 009-2013-EF/63.1 Contenidos
Mnimos Especficos Para Estudios De Pre inversin A Nivel De Perfil De Proyectos
De Inversin Pblica En Sistemas De Transmisin De Energa Elctrica.
De acuerdo a las proyecciones el Sistema Elctrico Arequipa requerir el ao 2017
184.94 MW, el ao 2027 275.72 MW y al final del perodo de evaluacin 386.79 MW.
Estos requerimientos exigen que la capacidad de la S.E. Chilina 138/33 kV deba
incrementarse garantizando el suministro con estndares de calidad.

MEMORIA DE PROYECTO

Pg. 18 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

PROYECCIN DE MXIMA DEMANDA


COINCIDENTE (MW)TOTAL

2034 355.0
2035 368.7
2036 382.7

2036

2035

2034

2033 341.9

0.0
2033

2032 328.9

50.0

2032

2031 316.5

2031

2030 304.6

100.0

2030

2029 293.2

150.0

2029

2028 282.3

200.0

2028

2026 261.5
2027 271.7

2027

2025 251.8

250.0

2026

2024 242.5

300.0

2025

2023 233.2

350.0

2024

2022 224.3

2023

2021 215.3

400.0

2022

2020 206.1

2021

2019 197.3

450.0

2020

2018 188.9

TOTAL
PROYECCIN DE MXIMA
DEMANDA COINCIDENTE (MW)
SE AREQUIPA
Aos: 2014 - 2036
SISTEMA ELECTRICO AREQUIPA

2019

2017 180.9

147.3
162.9
177.1
184.9
193.0
201.3
210.2
219.4
228.3
237.2
246.5
255.9
265.6
275.7
286.4
297.3
308.6
320.5
333.0
345.9
359.1
372.8
386.8

2018

2016 173.0

2.98
3.86
4.06
4.06
4.06
4.06
4.06
4.06
4.06
4.06
4.06
4.06
4.06
4.06
4.06
4.06
4.06
4.06
4.06
4.06
4.06
4.06
4.06

2017

2015 159.0

SE AREQUIPA

2016

2014 144.3

AT

2015

MT

2014

AO

TOTAL
SE AREQUIPA

Fuente: Equipo Consultor

Tabla N01: Proyeccin de la Demanda del Sistema Elctrico Arequipa.


SUBESTACIN
CHILINA 138/33 Kv

2015

41.72
47.59
48.74
49.40
53.92
54.59
55.30
59.11
62.57
65.76
66.58
69.29
70.17
73.96
76.45
79.75
83.26
87.73
91.02
92.56
95.86
102.85

2016
2017
2018
2019
2020
2021
2022
2023
2024
2025
2026
2027
2028
2029
2030
2031
2032
2033
2034
2035

PROYECCIN DE MXIMA DEMANDA COINCIDENTE


(MW)
Aos: 2015 - 2036
120.00

100.00

80.00

60.00

40.00

20.00

0.00

2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
2025
2026
2027
2028
2029
2030
2031
2032
2033
2034
2035

AO

CHILIN A 138/33 Kv

2036
Fuente: Equipo Consultor

Tabla N02: Proyeccin de la Demanda de la SET Chilina 138/33 kV.

De los anlisis de flujo y bajo el cumplimiento de los estndares de calidad de

MEMORIA DE PROYECTO

Pg. 19 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

determina que la S.E. Chilina 138/33 kV deber atender la demanda, segn el grfico
anterior. El ao 2017 48.74 MW, el ao 2027 70.17 MW y al final del perodo
102.85 MW.
En el caso de las cargas alimentadas en 10 kV desde la S.E. Chilina se observa
tambin que el ao 2017 se necesitarn 21.1 MW, el ao 2027 33.1 MW y al final del
perodo 48.8 MW.
PROYECCIN DE MXIMA
DEMANDA NO COINCIDENTE SET
SUBESTACIN
CHILINA

2033
2034
2035

2036

2035

2034

2033

2032

2032

0.0

2031

2031

2030

2030

10.0

2029

2029

2028

2028

20.0

2027

2027

2026

2025
2026

30.0

2025

2024

2024

2023

40.0

2023

2022

2022

2021

50.0

2021

2020

2020

2019

2019

2018

60.0

2018

2017

2017

2016

2016

2015

PROYECCIN DE MXIMA DEMANDA NO COINCIDENTE


(MW)
Aos: 2014 - 2036

2015

18.3
19.2
20.1
21.1
22.0
23.0
24.1
25.2
26.4
27.6
28.9
30.3
31.7
33.1
34.7
36.3
37.9
39.7
41.5
43.4
45.1
46.9
48.8

2014

2014

AO

CHILINA

2036
Fuente: Equipo Consultor

Tabla N03: Proyeccin de Demanda de la Subestacin Chilina de 33/10 kV.

4.4.

NIVELES DE CORTOCIRCUITO
De acuerdo al Estudio de Cortocircuito, se observa que las corrientes de falla ms
elevadas se registran en la barra de 10 kV, alcanzado valores de hasta 26.76 kA.
Por lo tanto, por razones de normalizacin los nuevos equipos a instalarse tendrn
los siguientes niveles de Corriente de Cortocircuito normalizados de acuerdo a IEC:
- Nivel de 138 kV

: 31.5 kA

- Nivel de 33 kV

: 31.5 kA

- Nivel de 10 kV

: 31.5 kA

MEMORIA DE PROYECTO

Pg. 20 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

Cdigo DigSilent
SANT138
SOCA138
CONV138
PINDU138C
JESUS138
SOCA33
CONV33
CONV33B
PQIB33
CHIL33
JESUS33
CHALL33
Cono_Norte_33
LAMB33
LAZA33
PAUC33
PORO33
RPLA33
MOLY33
CERVE33
ACERS33
CHIL10
CHIL10B
CONO_NORTE_10

Corriente de
Cortocircuito
Vnom (kV)
Mxima Mnima
(kA)
(kA)
138.00
11.31
9.82
138.00
15.88
11.99
138.00
6.84
5.98
138.00
8.50
7.45
138.00
10.72
9.24
33.00
19.92
10.99
33.00
23.69
18.74
33.00
23.69
18.74
33.00
21.82
19.25
33.00
23.71
18.56
33.00
20.37
18.88
33.00
19.08
15.72
33.00
7.06
6.14
33.00
9.84
8.71
33.00
15.78
13.65
33.00
0.00
0.00
33.00
11.61
9.77
33.00
15.34
13.31
33.00
16.34
14.66
33.00
15.75
14.45
33.00
17.61
16.39
10.00
26.72
21.88
10.00
26.72
21.88
10.00
9.00
7.67

AO 2036
AVENIDA
MXIMA DEMANDA MNIMA DEMANDA
3
1
2-t
3
1
2-t
(kA)
(kA)
(kA)
(kA)
(kA)
(kA)
10.26 11.06 10.84 9.82 10.68 10.46
12.92 15.55 15.11 11.99 14.57 14.22
6.13 6.64 6.25 5.98 6.51 6.13
7.79 8.37 8.02 7.45 8.08 7.73
9.71 10.51 10.25 9.24 10.11 9.85
19.60 11.12 17.77 19.04 10.99 17.26
19.11 21.18 20.04 18.74 20.84 19.73
19.11 21.18 20.04 18.74 20.84 19.73
19.77 21.39 20.01 19.25 20.95 19.58
18.92 21.14 19.87 18.56 20.80 19.58
19.89 19.36 19.30 19.39 19.02 18.88
16.00 18.17 16.71 15.72 17.90 16.50
6.71 6.92 6.17 6.66 6.89 6.14
8.81 9.61 9.28 8.71 9.53 9.20
13.96 14.79 13.79 13.76 14.63 13.65
0.00 0.00 0.00 0.00 0.00 0.00
9.90 11.28 10.01 9.77 11.17 9.92
13.50 14.76 13.77 13.31 14.58 13.63
16.00 14.88 15.24 15.66 14.66 14.96
15.36 15.06 14.70 15.06 14.84 14.45
17.21 16.99 16.72 16.82 16.71 16.39
25.65 0.00 22.07 25.44 0.00 21.88
25.65 0.00 22.07 25.44 0.00 21.88
8.90 0.00 7.69 8.88 0.00 7.67

ESTIAJE
MXIMA DEMANDA MNIMA DEMANDA
3
1
2-t
3
1
2-t
(kA)
(kA)
(kA)
(kA)
(kA)
(kA)
10.56 11.31 11.09 10.25 11.05 10.83
13.25 15.88 15.40 12.90 15.53 15.10
6.39 6.84 6.47 6.13 6.64 6.25
7.95 8.50 8.15 7.78 8.36 8.01
9.96 10.72 10.46 9.70 10.51 10.25
19.92 11.19 18.03 19.59 11.12 17.76
21.18 23.69 22.40 19.10 21.17 20.03
21.18 23.69 22.40 19.10 21.17 20.03
20.31 21.82 20.41 19.76 21.38 20.01
21.00 23.71 22.26 18.92 21.13 19.87
20.37 19.73 19.69 19.88 19.40 19.32
17.01 19.08 17.59 16.00 18.17 16.71
6.89 7.06 6.31 6.71 6.92 6.17
9.08 9.84 9.52 8.99 9.77 9.46
15.08 15.78 14.84 13.95 14.79 13.79
0.00 0.00 0.00 0.00 0.00 0.00
10.25 11.61 10.30 10.13 11.50 10.22
14.22 15.34 14.36 13.50 14.75 13.77
16.34 15.08 15.50 15.99 14.87 15.24
15.75 15.31 14.99 15.36 15.05 14.69
17.61 17.25 17.01 17.21 16.98 16.71
26.72 0.00 22.99 25.65 0.00 22.07
26.72 0.00 22.99 25.65 0.00 22.07
9.00 0.00 7.78 8.90 0.00 7.69

Tabla N04: Resultados de Corto Circuito - Ao 2036 con proyecto Sistema Elctrico Arequipa

En la siguiente tabla se muestra el incremento de la corriente de corto circuito en


los aos evaluados y en el rea del proyecto.

Cdigo DigSilent
CHIL138/33
CHIL138/33
CHIL33/10
CHIL33/10

Vnom
(kV)
138.0
33.0
33.0
10.0

2015
Actual
Mx. Icc
(kA)
5.32
14.53
14.45
14.66

2017-SP

2017-CP

2024-CP

2036-CP

Mx. Icc
(kA)
5.56
16.54
16.45
15.31

Mx. Icc
(kA)
6.45
19.66
19.57
24.97

Mx. Icc
(kA)
6.60
20.58
20.47
25.21

Mx. Icc
(kA)
6.84
23.69
23.71
26.72

Tabla N05: Cuadro de resumen de mximas corrientes de corto circuito S.E.T. Chilina

4.5.

MEDICIN Y CLCULO DE RESISTIVIDAD DE TERRENO


Medicin de la Resistividad por el Mtodo Wenner
Con la aplicacin del mtodo Wenner se efectuaron las mediciones
correspondientes en el rea de ampliacin de la Subestacin Chilina. Las lecturas
realizadas en cada lugar fueron en forma longitudinal, expresados en la escala
adecuada, obtenindose los siguientes resultados:

MEMORIA DE PROYECTO

Pg. 21 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

Espaciamiento
a (m)
1
2
4
8
12

Resistividad Elctrica
Medida (.m)
1
32.8
48.4
61
54.2
46.5

2
55.5
44.9
39.9
33.9
44.3

Resistividad
Media (.m)
44.15
46.65
50.45
44.05
45.40

Tabla N06: Medidas realizadas de la resistividad del terreno.

5.

OBRAS ELECTROMECNICAS - EQUIPAMIENTO PROYECTADO


En general, el suministro electromecnico para la subestacin ser el apropiado
para soportar las condiciones previstas en el rea del proyecto, el cual comprende
el equipamiento que garantizar la operacin de la subestacin en su tiempo de vida
til, cumpliendo con las recomendaciones especificadas por las normas vigentes
como el Cdigo Nacional de Suministro - 2011, la Comisin Electrotcnica
Internacional (IEC), Instituto Nacional de Estndares Americanos (ANSI),
requerimientos de Normas Nacionales e Internacionales relacionadas.
Todos los equipos han sido previstos con caractersticas tcnicas que permitirn su
integracin con un sistema de automatizacin y comunicaciones bajo los estndares
y normas vigentes.

5.1.

TRANSFORMADORES DE POTENCIA
Se instalarn transformadores de potencia de 02 devanados cuyas caractersticas se
detallan a continuacin:
Transformador N 01 de 138/33 kV
TRANSFORMADOR TRIFASICO DE 138/33 kV
ITEM

UNIDAD

Enfriamiento

DESCRIPCIN
ONAF

Potencia AT

MVA

75

Nivel de Tensin AT

kV

138

Nivel de Tensin MT

kV

Grupo de Conexin

33
YNd11

TRANSFORMADOR DE CORRIENTE DE 138 kV


ITEM
Tensin de diseo de equipo
Nivel bsico de aislamiento

UNIDAD

DESCRIPCIN

kV

170

kVp

750

TRANSFORMADOR DE CORRIENTE DE 33 kV
ITEM

MEMORIA DE PROYECTO

UNIDAD

DESCRIPCIN

Pg. 22 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

Tensin de diseo de equipo


Nivel bsico de aislamiento

kV

52

kVp

250

PARARRAYOS DE 33 kV
ITEM

UNIDAD

DESCRIPCIN

Tensin Nominal del Pararrayo

kV

40

Corriente de Descarga

kA

10

Clase de Descarga

Transformador N 02 de 33/10 kV
TRANSFORMADOR TRIFASICO DE 33/10 kV
ITEM

UNIDAD

Enfriamiento

DESCRIPCIN
ONAF

Potencia AT

MVA

25

Nivel de Tensin AT

kV

33

Nivel de Tensin MT

kV

10

Grupo de Conexin

YNd11

TRANSFORMADOR DE CORRIENTE DE 33 kV
ITEM

UNIDAD

Tensin de diseo de equipo


Nivel bsico de aislamiento

DESCRIPCIN

kV

52

kVp

250

TRANSFORMADOR DE CORRIENTE DE 10 kV
ITEM

UNIDAD

DESCRIPCIN

kV

17.5

kVp

95

Tensin de diseo de equipo


Nivel bsico de aislamiento

PARARRAYOS DE 33 kV
ITEM

UNIDAD

DESCRIPCIN

Tensin Nominal del Pararrayo

kV

40

Corriente de Descarga

kA

10

Clase de Descarga

5.2.

EQUIPO HBRIDO EN 138 KV


Se instalarn 02 equipos hbridos, cuyas caractersticas tcnicas se detallan a
continuacin:

ITEM

UNIDAD

DESCRIPCION

kV

170

kVp

750

Corriente nominal en servicio continuo

2000

Corriente de corte nominal en cortocircuito

kA

31.5

Tensin de diseo del equipo


Nivel Bsico de Aislamiento (BIL)

MEMORIA DE PROYECTO

Pg. 23 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

Incluye:
Interruptor de Potencia Tripolar
Transformadores de Corriente
Seccionadores con Cuchilla a Tierra

5.3.

TRANSFORMADORES DE TENSIN DE 138 KV


Se instalarn 03 transformadores de tensin monofsica en el lado de 138 kV, el cual
se utilizara para la baha de la Lnea proveniente de la SET Santuario, contarn con
02 ncleos para proteccin y 01 para medicin, cuyas caractersticas tcnicas se
detallan a continuacin:
ITEM

UNIDAD

Tensin de diseo del equipo

kV

170
1383 / 0.103 / 0.103 kV, 3P;
30 VA
1383 / 0.103 / 0.103 kV, 3P;
30 VA
1383 / 0.103 / 0.103 kV, 3P;
30 VA

Ncleo de Proteccin
Ncleo de Proteccin
Ncleo de Medicin
Nivel Bsico de Aislamiento (BIL)

5.4.

DESCRIPCION

kVp

750

PARARRAYOS EN 138 KV
Se instalarn 06 pararrayos de xido metlico (03 en la celda de lnea y 03 en celdas
de transformacin) segn se detalla en los planos electromecnicos, cuyas
caractersticas son las siguientes:

ITEM

UNIDAD

DESCRIPCIN

Tensin de diseo del equipo

kV

170

Tensin Nominal del Pararrayo

kV

120

Corriente de Descarga

kA

10

Clase de Descarga

5.5.

CELDAS EN 33 KV
Las Celdas en Media Tensin Aisladas en Gas (GIS) sern diseadas de acuerdo a
las Normas de Fabricacin internacionales, se instalarn las siguientes celdas:

MEMORIA DE PROYECTO

Pg. 24 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

01 Celda blindada con aislamiento en gas (GIS) de Transformador de doble


barra en 33 kV, con el siguiente equipamiento:
DESCRIPCIN
02 Seccionadores de barra 36 kV, 170kVp (BIL), 2000 A, 31.5 kA
01 Interruptores de Potencia 36 kV, 170kVp (BIL), 2000 A, 31.5 kA
03 Transformador de Corriente 36 kV, 170kVp (BIL)

08 Celdas blindadas con aislamiento en gas (GIS) de Lnea de doble barra en


33 kV, con el siguiente equipamiento:
DESCRIPCIN
02 Seccionadores de barra 36 kV, 170kVp (BIL), 1250 A, 31.5 kA
01 Interruptores de Potencia 36 kV, 170kVp (BIL), 1250 A, 31.5 kA
03 Transformador de Corriente 36 kV, 170kVp (BIL)
01 seccionador de lnea con puesta a tierra 36 kV, 170kVp (BIL), 1250 A, 31.5 kA
03 Transformadores de tensin 36 kV, 170kVp (BIL)
03 Pararrayos 40 kV (RT), 10 kA, CI2

01 Celda blindada con aislamiento en gas (GIS) de Acoplamiento Transversal


de doble barra en 33 kV, con el siguiente equipamiento:
DESCRIPCIN
02 Seccionadores de barra 36 kV, 170kVp (BIL), 2500 A, 31.5 kV
01 Interruptores de Potencia 36 kV, 170kVp (BIL), 2500 A, 31.5 kA
03 Transformadores de Corriente 36 kV, 170kVp (BIL)

02 Celdas blindadas con aislamiento en gas (GIS) de Acoplamiento


Longitudinal de doble barra en 33 kV, con el siguiente equipamiento:
DESCRIPCIN
02 Seccionadores de barra 36 kV, 170kVp (BIL), 2500 A, 31.5 kV
01 Interruptores de Potencia 36 kV, 170kVp (BIL), 2500 A, 31.5 kA
03 Transformadores de Corriente 36 kV, 170kVp (BIL)
01 seccionador de lnea 36 kV, 170kVp (BIL), 2500 A, 31.5 kA

MEMORIA DE PROYECTO

Pg. 25 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

02 Celdas blindadas con aislamiento en gas (GIS) de Transformador de doble


barra en 33 kV, con el siguiente equipamiento:
DESCRIPCIN
02 Seccionadores de barra 36 kV, 170kVp (BIL), 1250 A, 31.5 kV
01 Interruptores de Potencia 36 kV, 170kVp (BIL), 1250 A, 31.5 kA
03 Transformadores de Corriente 36 kV, 170kVp (BIL)

01 Celda blindada con aislamiento en gas (GIS) para Servicios Auxiliares de


doble barra en 33 kV, con el siguiente equipamiento:
DESCRIPCIN
02 Seccionadores de barra 36 kV, 170kVp (BIL), 630 A, 31.5 kV
01 Interruptores de Potencia 36 kV, 170kVp (BIL), 630 A, 31.5 kA
03 Transformadores de Corriente 36 kV, 170kVp (BIL)

01 Celda blindad con aislamiento en gas (GIS) de Medicin de doble barra en


33 kV, con el siguiente equipamiento:

DESCRIPCIN
06 Transformadores de tensin 36 kV, 170kVp (BIL)
06 Seccionadores fusibles

5.6.

CELDAS METAL CLAD EN 10 KV


01 Celda Metal Clad de Transformador en 10 kV, con el siguiente
equipamiento:
DESCRIPCIN
01 Interruptor extrable 17.5 kV, 95 kVp (BIL), 2000 A, 31.5 kA
03 transformadores de Corriente 17.5 kV, 95 kVp (BIL)
03 Transformadores de Tensin 17.5kV, 95 kVp (BIL)

MEMORIA DE PROYECTO

Pg. 26 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

01 Celda Metal Clad de Lnea para reserva en 10 kV, con el siguiente


equipamiento:
DESCRIPCIN
01 Interruptor extrable 17.5 kV, 95 kVp (BIL), 1250 A, 31.5 kA
03 transformadores de Corriente 17.5 kV, 95 kVp (BIL)
01 Seccionador de Puesta a Tierra 17.5 kV, 95 kVp (BIL)

01 Celda Metal Clad de Acoplamiento - Remonte en 10 kV, con el siguiente


equipamiento:
DESCRIPCIN
01 Interruptor extrable 17.5 kV, 95 kVp (BIL), 2000 A
03 transformadores de Corriente 17.5 kV, 95 kVp (BIL)

5.7.

TABLEROS DE CONTROL Y PROTECCIN


Los Tableros de Control proyectados sern diseados segn Normas de Fabricacin
indicadas en la Tabla de Datos Tcnicos. Se instalarn:
01 Tablero de Proteccin y Medicin del Transformador de Potencia de 02
Devanados de 75 MVA con el siguiente equipamiento:
DESCRIPCIN
01 Medidor Electrnico Multifuncin (138 kV)
01 Equipo de Control y Proteccin (IED) Principal del Transformador con
Display Grfico de Control (HMI)
01 Equipo de Control y Proteccin (IED) Respaldo (138 kV) con HMI
01 Equipo de Control y Proteccin (IED) Respaldo (33 kV) con HMI
01 Switch Ethernet Industrial 8TX+4FX
Borneras de Prueba de Tensin y Corriente

01 Tablero de Proteccin y Medicin del Transformador de Potencia de 02


Devanados de 25 MVA con el siguiente equipamiento:
DESCRIPCIN
01 Medidor Electrnico Multifuncin (33 kV)
01 Equipo de Control y Proteccin (IED) Principal del Transformador con
Display Grfico de Control (HMI)
01 Equipo de Control y Proteccin (IED) Respaldo (33 kV) con HMI

MEMORIA DE PROYECTO

Pg. 27 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

01 Equipo de Control y Proteccin (IED) Respaldo (10 kV) con HMI


01 Switch Ethernet Industrial 8TX+4FX
Borneras de Prueba de Tensin y Corriente

01 Tablero de Proteccin y Medicin de Lnea en 138 kV con el siguiente


equipamiento:
DESCRIPCIN
01 Medidor Electrnico Multifuncin
01 Equipo de Control y Proteccin (IED) Principal
01 Equipo de Control y Proteccin (IED) Respaldo
01 Switch Ethernet Industrial 8TX+4FX
Borneras de Prueba de Tensin y Corriente

01 Tablero de Proteccin de barra y registrador de fallas para las bahas en


138 kV con el siguiente equipamiento:
DESCRIPCIN
01 Equipo de Control y Proteccin (IED) Principal
01 Equipo de Control y Proteccin (IED) Respaldo
01 Registrador de fallas
01 Switch Ethernet Industrial 8TX+4FX
Borneras de Prueba de Tensin y Corriente

5.8.

BANCO DE BATERAS, CARGADOR RECTIFICADOR Y SS.AA.


Se requiere de los sistemas de tensin auxiliar en 110 Vcc

y 48 Vcc para el

funcionamiento del sistema de control, mando, automatizacin y comunicaciones.


Bancos de Bateras para 110 Vcc con las siguientes caractersticas:
ITEM

UNIDAD

Tipo de Batera

Plomo Acido

Tensin nominal

Vcc

110

Capacidad nominal

A-h

250

55

Vcc

Nmero de celdas por banco


Tensin nominal por celda

MEMORIA DE PROYECTO

DESCRIPCIN

Pg. 28 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

Bancos de Bateras para 48 Vcc con las siguientes caractersticas:


ITEM

UNIDAD

Tipo de Batera

DESCRIPCIN
Plomo Acido

Tensin nominal

Vcc

48

Capacidad nominal

A-h

125

Vcc

12

Nmero de celdas por banco


Tensin nominal por celda

01 Cargador Rectificador 110 Vcc con las siguientes caractersticas:


ITEM

UNIDAD

DESCRIPCIN

En Corriente Alterna
Tipo

Trifsico

Tensin Nominal

Vac

380/220

Hz

60

Tensin Nominal

Vcc

110

Corriente Nominal

Acc

94

+10%, -15%

Frecuencia
En Corriente Continua

Rango de variacin de la tensin

01 Cargador Rectificador 48 Vcc con las siguientes caractersticas:


ITEM

UNIDAD

DESCRIPCIN

En Corriente Alterna
Tipo
Tensin Nominal

Trifsico
Vac

380/220

Hz

60

Tensin Nominal

Vcc

48

Corriente Nominal

Acc

50

+10%, -15%

Frecuencia
En Corriente Continua

Rango de variacin de la tensin

01 Tablero de Servicios Auxiliares 380-220 Vac con el siguiente


equipamiento:
DESCRIPCIN
Analizador de redes para suministro Normal (Transformador) y de Emergencia
(Generador)
Conmutadores manuales (iluminacin)

MEMORIA DE PROYECTO

Pg. 29 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

Interruptores termomagnticos, principal ( Red normal y de emergencia) y de


salida (cargas preferentes y no preferentes)
Sealizacin de cargas preferentes (red normal)
Equipo de transferencia automtica del grupo generador
Conectores y Accesorios

01 Tablero de Servicios Auxiliares 110Vcc y 48 Vcc con el siguiente


equipamiento:
DESCRIPCIN
Voltmetro digital
Ampermetro digital
Conmutador manual (Iluminacin)
Interruptores termomagnticos, principal y de salida
Conectores y Accesorios

01 Transformador de Servicios Auxiliares:


ITEM

UNIDAD

Tipo

Trifsico

Tensin Nominal Primaria

kV

33

Tensin Nominal Secundaria

kV

380 - 220

kVA

100

Hz

60

Potencia Nominal
Frecuencia

5.9.

DESCRIPCIN

REUBICACIN DE EQUIPOS EXISTENTES


Estos equipos en la actualidad estn en operacin en la subestacin, con la
ampliacin del mismo estos equipos sern reubicados.
Transformadores de tensin en 138 kV:
Se reubicaran 3 transformadores de tensin monofsica en 138 kV que en la
actualidad estn en operacin, el cual ser reutilizado en la ampliacin de la barra
138 kV, cuyas caractersticas tcnicas se detallan a continuacin:

MEMORIA DE PROYECTO

Pg. 30 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

ITEM
Tensin de diseo del equipo

UNIDAD
kV

Ncleo de Proteccin
Ncleo de Medicin

5.10.

145
1383 / 0.103 / 0.103 kV, 3P;
30 VA
1383 / 0.103 / 0.103 kV, 3P;
30 VA
1383 / 0.103 / 0.103 kV, 3P;
30 VA

Ncleo de Proteccin

Nivel Bsico de Aislamiento (BIL)

DESCRIPCION

kVp

750

RED DE TIERRA
Red de Tierra Profunda:
Se ampliar la red de tierra profunda, para ello se usar conductor de cobre recocido
de 120 mm2 y varillas de cobre de 16 mm dimetro por 2.40 m de longitud instalados
a lo largo de la malla en pozos de puesta a tierra y de prueba.
Red de Tierra Superficial:
Se implementar un sistema de tierra superficial que estar conectado mediante
soldadura de proceso exotrmico a la malla profunda proyectada. Esta red superficial
permitir conectar las partes metlicas de los equipos, infraestructura civil a la malla
profunda. La conexin de todos los equipos de patio de llaves y sala de control ser
con conductor de cobre recocido de 95 mm2.

5.11.

CABLES DE ENERGA EN MEDIA TENSIN


Se utilizar cables del tipo N2XSY para las diferentes acometidas e interconexiones
entre las instalaciones nuevas y existentes el cual pasamos a detallar a continuacin:
Cables del tipo N2XSY de 35 kV de 300 mm2 en 03 ternas para la salida en 33 kV
del transformador de potencia de 75 MVA hacia la celda GIS de llegada ubicado
en la sala de celdas.
Cables del tipo N2XSY de 240 mm2 en una terna para la lnea en 33 kV
proveniente de la central Charcani VI hacia la barra convertidor existente en la
sala de Chilina.
Cable del tipo N2XSY 35 kV de 300 mm2 en 02 ternas para la interconexin de las
nuevas barras con las barras existentes de Convertidor.
Cable del tipo N2XSY de 35 kV de 300 mm2 una terna para la alimentacin del

MEMORIA DE PROYECTO

Pg. 31 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

transformador proyectado.
Cable del tipo N2XSY de 35 kV de 300 mm2 de una terna para la alimentacin del
transformador existente.
Cable del tipo N2XSY de 35 kV de 150 mm2 de una terna salida para las lneas
(San Lzaro I-II).
Cables del tipo N2XSY 35 kV de 50 mm2 para la alimentacin del transformador
de servicios auxiliares.
Cables del tipoN2XSY 15 kV de 300 mm2 03 ternas desde el transformador de 25
MVA hacia la celda metal clad de llegada en 10 kV.
La conexin de los cables ser con el uso de terminales autocontrables de tipo
interior y/o exterior, de acuerdo a las necesidades del mismo. Su instalacin ser en
canaletas y ductos, de acuerdo a los diseos que pueden observarse en los planos
correspondientes.
5.12.

CABLES DE CONTROL Y ENERGA EN BAJA TENSIN


Para los circuitos de control y medida se utilizarn cables apantallados del tipo
N2XSY o similar de 1 kV de distintos calibres, conforme a las necesidades
requeridas, los cuales sern instalados en canaletas y bandejas cumpliendo con las
normas tcnicas.
Para los circuitos de alimentacin en baja tensin se utilizarn cables tipo NYY de
1 kV de distintos calibres acorde a las necesidades requeridas, los cuales sern
instalados en canaletas, tuberas y/o bandejas.

6.

SISTEMA DE AUTOMATIZACIN Y COMUNICACIONES


El sistema de automatizacin y comunicaciones propuestas considera su
implementacin hasta el Nivel 3 (Subestacin).

6.1.

CARACTERSTICAS GENERALES DEL SISTEMA


Se aplicar el modelo de arquitectura en base al estndar IEC 61850, en el cual los
protocolos estn basados en comunicaciones sobre redes Ethernet y los modelos
son del tipo cliente-servidor, permitiendo, adems, las comunicaciones horizontales
entre los distintos equipos (IEDs).
La arquitectura a implementar ser abierta, modular y flexible, de manera que pueda
ser expandida fcilmente.

MEMORIA DE PROYECTO

Pg. 32 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

Se deben seleccionar sistemas state of the art, con capacidades avanzadas


adaptadas a la operacin de subestaciones con la habilidad de ser integradas con
otros sistemas. Ser importante la capacidad de acomodar futuras expansiones, con
la facilidad de ser actualizadas a sistemas ms complejos.
El equipamiento de la arquitectura propuesta deber tener las siguientes
caractersticas:
Una arquitectura muy flexible, que permite una adaptacin a las necesidades
especficas de la subestacin.
Una arquitectura modular y con procesamiento distribuida, que permite una
ampliacin futura sin impacto en el funcionamiento de la parte en servicio.
Una arquitectura abierta que hace una utilizacin de estndares del mercado
en todos los niveles (hardware, software, base de datos y comunicaciones), lo
que permite una conexin e integracin con equipos de distintos fabricantes.
Utilizacin y configuracin sencillas soportada en interface grfica, verstil y de
fcil operacin para que personal sin conocimiento de computacin pueda
operarlo fcilmente, tras recibir un entrenamiento bsico.
Gran facilidad de comunicacin e integracin con otros sistemas de varios
fabricantes.
Inteligencia distribuida, uso de software estndar; ambiente Windows;
robustez; criterio de sobredimensionamiento de la capacidad de procesamiento
en todos los niveles, para permitir un crecimiento funcional y de hardware sin
degradacin del comportamiento, conforme al alcance de suministro.
La mantencin o modificacin de los componentes del sistema, no debe
ponerlo fuera de servicio.
El sistema debe ser capaz de reinicializarse rpidamente, independientemente
de la intervencin del operador, despus de una interrupcin o prdida de la
tensin de alimentacin y enclavamiento del sistema operacional.
Toda la informacin relevante debe ser almacenada en memoria no voltil, para
protegerla en caso de prdida de la fuente de energa;

MEMORIA DE PROYECTO

Pg. 33 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

Debe ser posible gerenciar y reprogramar las aplicaciones en lnea, aun cuando
las tareas principales estn siendo ejecutadas, los eventos estn siendo
registrados, las mediciones siendo almacenadas, etc.

6.2.

ARQUITECTURA DEL SISTEMA DE MONITOREO Y CONTROL:


Siguiendo los modelos de los sistemas de control, desde el punto de vista del control
y automatizacin de subestaciones elctricas; por lo general se definen 4 niveles de
automatizacin, considerado el nivel 0 como el inferior y el 3 como el superior.

El primer nivel (nivel 0):

Es el nivel de Patio o nivel de Procesos, en el cual se encuentran los equipos de


campo, como lo son interruptores y seccionadores. Estos equipos, por lo general,
poseen el mando del control en cada uno de ellos. El control de la operacin de este
nivel se puede realizar desde cada uno de los equipos o desde los circuitos de cada
una de las celdas, de acuerdo a la lgica de control y enclavamientos que posea cada
circuito.

El segundo nivel (nivel 1):

Es el nivel de Baha o IEDs, est conformado por equipos especializados en controlar


y proteger la operacin de los equipos de campo. En este nivel, el control de la
operacin es dado desde el propio IED o desde los tableros en los cuales se
encuentre instalado el IED, en dichos tableros se poseen pulsadores, botones y rels
auxiliares que en conjunto realizan las funciones de control, enclavamientos,
regulacin (opcional), proteccin y medicin de las seales de campo.

MEMORIA DE PROYECTO

Pg. 34 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

El tercer nivel (nivel 2):

Es el nivel de Subestacin, en el cual desde un sistema SCADA HMI, se realizan las


funciones de control, supervisin y adquisicin de datos de toda la Subestacin. En
este nivel el control de la operacin se realiza desde el Software SCADA
implementado y el control y la seguridad de las maniobras a efectuarse es
resguardada bajo el control de cada uno de los operadores y supervisores del sistema
SCADA.

El cuarto nivel (nivel 3):

Es el nivel de Centro de Control SCADA, en este nivel se concentra la informacin


de los sistemas SCADA HMI implementados en el tercer nivel, en este nivel es
primordial el medio de comunicacin establecido entre el Centro de Control SCADA
con los sistemas SCADA HMI de cada subestacin, pues la confiabilidad del sistema
ser controlada y supervisada desde este nivel.
6.2.1.

MODELO DE DATOS Y SERVICIOS

Segn se define en la parte 7 de la norma IEC 61850. Deber ejecutarse el modelado


de los elementos que se puede encontrar en una subestacin, con el objetivo de
conseguir el requisito fundamental de perdurabilidad en el tiempo. El modelado
utilizar los nodos lgicos como bloque principal para componer la informacin de los
sistemas de automatizacin de subestaciones.

Figura N02: Arquitectura del sistema de automatizacin y comunicacin.

MEMORIA DE PROYECTO

Pg. 35 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

6.3.
6.3.1.

EQUIPAMIENTO PROYECTADO
TABLERO DE AUTOMATIZACIN Y COMUNICACIN
El equipamiento proyectado en este Nivel, deber estar integrado en un tablero o
gabinete metlico autosoportado.
La alimentacin de los equipos deber efectuarse (de ser necesaria) a travs de
convertidores AC/CC, los cuales formarn parte de estos equipos, no aceptndose
otras formas de bajar el nivel de tensin, como por ejemplo el uso de resistencias en
serie.
Todos los equipos debern incluir el Software de configuracin y parametrizacin del
mismo y deber ser compatible para la integracin del SCADA. As tambin debern
proporcionarse las licencias de uso respectivos. Este tablero contiene:
A.

UNIDAD CENTRAL DE SUBESTACION

La unidad central se comunicar con los equipos de proteccin, control y medicin


(Nivel 1) de la subestacin mediante el protocolo de comunicaciones del estndar
IEC 61850, por medio de una interfaz de red Ethernet 100 - Base FX o TX, segn
corresponda. Deber tener adems funciones de Gateway.
Las funciones principales que deber cumplir la unidad central son:
Gestin de las comunicaciones con los diferentes equipos de proteccin,
control y medida distribuidos.
Mdulo de ejecucin de las funciones automticas y lgicas programables
centrales del sistema.
Gestin de las comunicaciones con el nivel superior (Nivel 3 - Telemando y
Telecontrol).
Gestin de las comunicaciones locales y remotas con la consola de operacin
(IHM Interfaz Hombre Mquina).
Auto supervisin y autodiagnstico permanente.
Las caractersticas principales que deber cumplir la unidad central de subestacin
son:
Debe estar orientada a soluciones escalables y distribuidas;
Debe permitir la implementacin de soluciones redundantes a nivel de la UCS

MEMORIA DE PROYECTO

Pg. 36 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

o a nivel de la red LAN.


Sincronizacin a travs de GPS;
Deber soportar comunicaciones por radio, mdem y otros medios;
Deber garantizar comunicaciones con varios centros de mando;
Administra, supervisa y controlar de manera independiente una gran cantidad
de controladores de baha, IEDs, Unidades de Medida, etc.
Garantizar comunicaciones con varios RTUs (Unidades Terminales Remotas),
IEDs y rels de proteccin de terceros.
B.

INTERFAZ HOMBRE MAQUINA (IHM):

El IHM permitir obtener las funciones de centro local en la subestacin, desde donde
ser posible el control y registro de los parmetros elctricos, tales como corrientes,
tensiones, potencia activa, potencia reactiva, factor de potencia, etc., tambin deber
supervisar la instalacin realizando, al mismo tiempo, la gestin de las
comunicaciones.
Las funciones principales que deber cumplir el IHM:
Adquisicin de Datos
Procesamiento de Alarmas
Generador de Informacin
Registro Cronolgico
Diagramas

Esquemticos

de

Posiciones

incluyendo

mens

pop-up

"zooming", "decluttering", "panning" y ejecucin de control


La configuracin del Sistema y los Datos del Sistema sern archivados en una
extensa Base de Datos. El sistema debe garantizar el almacenamiento y la
integridad de todos los datos, en caso de falta de energa
Reconfiguracin en-lnea del Sistema, soportado por un modo de ingeniera
sencillo al usuario, en un entorno grfico.
Privilegios de Operador.
Funciones Automticas Programables
Las caractersticas principales que deber cumplir el IHM son:

MEMORIA DE PROYECTO

Pg. 37 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

Interfaz Hombre-Mquina totalmente grfico en entorno multi-ventana, con


utilizacin de mens controlados por ratn, con la consiguiente reduccin del
uso del teclado, asegurando mejoras drsticas en la simplificacin de
operacin. Utilizacin y configuracin sencillas soportada en interface grfica,
verstil y de fcil operacin para que personal sin conocimiento de computacin
pueda operarlo fcilmente, tras recibir un entrenamiento bsico.
Interconectividad de equipos de diferentes suministradores, con una drstica
reduccin de costos con la evolucin en el campo de la Industria de los
ordenadores.
La configuracin del Sistema y los Datos del Sistema sern archivados en una
Base de Datos extensa.
Reconfiguracin en-linea del Sistema, soportado por un modo de ingeniera
sencillo al usuario y en un entorno grfico.
C.

UNIDAD DE SINCRONIZACIN DE TIEMPO (GPS):

El sistema deber contar con una unidad de sincronismo, autnoma, por difusin
horaria (Broadcast) utilizando padrn GPS de alta precisin.
Deber incorporar un receptor de GPS con antena activa para instalacin en el
exterior y cabo con conectores para la conexin de la antena al receptor. El sistema
de sincronismo tendr una unidad de procesamiento, modelo NET con procesador
de red snack TCP/IP, (S) NTP. Adems de la sincronizacin temporal por SNTP, el
sistema implementar tambin la sincronizacin por IRIG-B.
D.

SWITCH ETHERNET INDUSTRIAL:

El switch o conmutador es el dispositivo digital lgico de interconexin de las redes


de control. Su funcin es interconectar dos o ms segmentos de red, de manera
similar a los puentes de red, pasando datos de un segmento a otro de acuerdo con
la direccin MAC de destino de las tramas en la red. Adems de la funcin de
conmutacin, deber tener integrada la funcin de conversin de medios de cobre a
fibra ptica multimodo o monomodo segn la necesidad.
El switch Ethernet de la unidad principal estar compuesto de un determinado
nmero de puertos de comunicaciones. Los puertos sern tanto de cobre - usando el
conector RJ45 -, como de fibra ptica (multimodo u monomodo), usando los
conectores MT-RJ o LC.

MEMORIA DE PROYECTO

Pg. 38 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

Asimismo, los switchs a los que se conectarn los equipos del Nivel 1 en nuestro
caso IEDs, y medidores multifuncin, tambin sern de funciones similares a las
especificadas anteriormente.
Las caractersticas de cada Switch en particular se describen en las Tablas de Datos
Tcnicos correspondientes.
E.

CABLEADO Y TERMINALES DE COBRE:

Todos los conductores que interconectan los equipos de terreno al SAS, as como
los conductores de alimentacin CA y CC deben ser blindados. Los conductores
deben ser de cobre flexible, clase de aislacin 0,6/1 kV.
F.

PATCH CORDS PARA FIBRA TICA:

Los cordones suministrados deben cumplir las especificaciones que satisfagan su


calidad y operacin en entornos industriales y debern ser de tipo multimodo u
monomodo segn sea el caso. Deben ser con terminaciones MT-RJ o LC dplex
(contrastar el puerto del Switch). El fabricante debe indicar en su oferta las
caractersticas de todos los patch cords requeridos. Para lograr rendimientos pticos
de

acuerdo

cada

aplicacin

debern

tomarse

en

consideracin

las

recomendaciones de las normas ITU-T G.652 a ITU-T G.655.


Los Patch cords de fibra, deben ser originales de fbrica. No se acepta tecnologa
epxica.
G.

PITGAILS PARA FIBRA TICA:

Debern ser de materiales de alta calidad y adecuadamente ensamblados con


conectores MT-RJ o LC de acuerdo a la necesidad. Los cordones suministrados
deben cumplir las especificaciones que satisfagan su calidad y operacin en entornos
industriales y debern ser de tipo multimodo u monomodo segn sea el caso.
H.

CABLE DE COBRE ETHERNET TIPO FTP:

Para la comunicacin Ethernet en cobre se utilizarn cables FTP, ("Foiled Twisted


Pair") o tambin denominado ScTP ("Screened UTP") con la finalidad de eliminar las
interferencias.
El fabricante debe indicar en su oferta las caractersticas de los cables requeridos en
la construccin del sistema.
I.

GABINETE METLICO:

Los gabinetes indicados son metlicos, electrificados y equipados con borneras

MEMORIA DE PROYECTO

Pg. 39 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

terminales, estn basados en un gabinete para uso interior.


7.
7.1.

OBRAS CIVILES
DEMOLICIONES Y DESMONTAJES
De acuerdo al diseo planteado y la infraestructura fsica existente, existe la
necesidad reutilizar espacios existentes disponibles y/o reas de la subestacin,
siendo pertinente realizar demoliciones y desmontajes que podrn observarse en los
planos correspondientes.
Dentro ellos se encuentran:

7.2.

Demolicin de elementos de concreto

Demolicin de pavimento de concreto en patio de llaves

Demolicin de muros

Desmontaje de cerco de malla metlica

CIMENTACIONES DE EQUIPOS ELECTROMECNICOS


Sern emplazados en el patio de llaves y albergarn a los EQUIPOS ELECTRICOS
correspondientes, estas estructuras sern de concreto armado.

7.3.

Pararrayos.

Equipos Hbridos.

Transformador de tensin.

Prtico de barras.

Transformadores de potencia.

POZA DE RECUPERO DE ACEITES


El pozo de recupero de aceite se disea teniendo como principal consideracin las
caractersticas geomtricas de la estructura (el criterio para el volumen de aceite), la
carga actuante y la capacidad portante del terreno.

7.4.

LINEA SUB TERRANEA DE MEDIA TENSIN- BUZONES


DUCTOS
Son elementos que sirven para el traslado de cables de energa de 10 y 33 KV. Estar
suministrado e instalado por tubera PVC-SAP, las tuberas se enterrarn a una

MEMORIA DE PROYECTO

Pg. 40 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

profundidad mnima de 0.90 m. Sobre la clave de las mismas, las tuberas reposaran
sobre una cama de arena de 0.10 m., previo movimiento de tierras en la lnea
subterrnea de media tensin
BUZONES
Emplazados de acuerdo a los planos, estas estructuras sern de concreto armado,
sern ubicados de acuerdo al cambio de direccin y distancias apropiadas para el
mantenimiento de los cables de energa en 33 y 10 kV. Adems se proyecta la
construccin de una caseta sobre el buzn junto a la sala de celdas para el transporte
a desnivel de cables hacia la plataforma metlica.
7.5.

SISTEMA DE CANALETAS
Emplazados en el patio de llaves, estas estructuras sern de concreto armado,
presentan variadas dimensiones, segn sean stas para albergar cables de control
o de energa y la cantidad de las mismas, todas ellas presentan tapas removibles y
alcayatas de soporte para los cables correspondientes, el tipo de canaleta y alcayata
sern de acuerdo a los detalles establecidos en los planos correspondientes y sus
respectivas especificaciones tcnicas.

7.6.

TRATAMIENTO DE TERRENO ACCESOS DRENAJE


En el tratamiento de terrenos y accesos estn incluidos los tratamientos de terreno
en subestacin, la va de acceso (trabajos preliminares y movimiento de tierras).
Asimismo se presenta reparacin de losa de concreto en el patio de llaves producto
de las nuevas cimentaciones proyectadas y el relleno con grava de 15 cm para la
zona ampliada del patio de llaves, se enlaza una cuneta a la existente De acuerdo a
los detalles establecidos en los planos correspondientes.

7.7.

ADECUACIN DE AMBIENTE PARA SALA DE CELDAS


Se adecuar un ambiente que actualmente alberga un convertidor de frecuencia para
la instalacin de las celdas GIS de forma que se dividir este ambiente en dos niveles;
un primer nivel para la sala de cables, cuya finalidad ser albergar las alcayatas por
las cuales sern soportados los cables de control y energa para su distribucin en
los diferentes tableros. Este primer nivel, contar con iluminacin y ventilacin
natural.
La Sala de celdas se ubicar en el segundo nivel; para lo cual se instalar una

MEMORIA DE PROYECTO

Pg. 41 de 42

AMPLIACIN DE LAS S.E.T. CHILINA 138/33KV Y 33/10KV,


ALTO SELVA ALEGRE - AREQUIPA

plataforma metlica con perfiles de acero A36 para las columnas, vigas y entramado
metlico, tomando como soporte las vigas y muros existentes para su anclaje de
acuerdo a los planos correspondientes, para el diseo de la plataforma metlica se
consider una carga viva de 1000 kg/m2 y una carga muerta de 250kg/m2 para
garantizar el sostenimiento de las celdas GIS, adems la estructura metlica contara
con columnas arriostradas en las vigas las cuales minimizaran las deformaciones
laterales. Los trabajos de adecuacin tambin comprenden los pintados de las
paredes existentes y pintado de la estructura metlica.
7.8.

ADECUACIN DE AMBIENTE PARA SALA DE CONTROL


Se adecuar un ambiente que actualmente sirve como auditorio para la sala de
control; este ambiente cuenta con dos niveles, la cual en el primer nivel se utilizar
para la instalacin de los tableros de control, proteccin y medicin. Para este
ambiente se proyecta la demolicin del piso y la implementacin de una canaleta de
cables, adems de la demolicin de los muros para la implementacin de una puerta
y una ventana que dotaran al ambiente de iluminacin natural, los trabajos de
adecuacin tambin comprenden la construccin de un piso acabado adecuado y el
pintado de las paredes y techos para el nuevo ambiente.

8.

PRESUPUESTO REFERENCIAL
El Valor Referencial para la Ejecucin de las Obras, que comprende el Suministro,
Transporte, Montaje Pruebas y Puesta en Servicio para las Obras Electromecnicas,
Civiles, Automatizacin y Comunicaciones, es de S/. 29991,539.86 (Veintinueve
Millones Novecientos Noventa y Un Mil Quinientos Treinta y Nueve con 86/100
Nuevos Soles) incluidos el Impuesto General a las Ventas (IGV).
Complementariamente se estima que la inversin total, incluyendo el expediente
tcnico y la supervisin de obra asciende a 31940,989.95 (Treinta y Un Millones
Novecientos Cuarenta Mil Novecientos Ochenta y Nueve con 95/100 Nuevos Soles)
incluido el Impuesto General a las Ventas (IGV).

9.

PLAZO DE EJECUCIN
El tiempo estimado para la ejecucin de las obras es de 450 das calendarios (15
meses). No considera el plazo para la elaboracin del expediente tcnico.

MEMORIA DE PROYECTO

Pg. 42 de 42

También podría gustarte