Anchor Bolt Capacity

According to ACI 318M-05


Appendix D

Introduction
Batasan maximum fc yang diatur dalam ACI 318 adalah 70 MPa
untuk cast-in anchor dan 55 MPa untuk post-installed anchor
Load combination menggunakan Ultimate Strength Design
Strength reduction factor ()
Tension
0.80
Shear
0.75

General Requirement for Strenght of anchor

1.
2.
3.
4.

1.
2.
3.

Tension
Steel Strength of Anchor in Tension
Concrete Breakout Strength of Anchor
Pullout Strength in Anchor
Concrete Side-Face Blow Out
Shear
Steel Strength of Anchor in Shear
Concrete Breakout Strength of Anchor
Concrete Pryout Strength of Anchor

Steel Strenght of Anchor in Tension


Kapasitas Anchor Bolt dihitung berdasarkan
rumus berikut :
NSA = n.Ase.futa
n
Asa
futa

: jumlah anchor
: area of anchor bolt
: min (1.9fya or 860 MPa)

Concrete Breakout Strength of Anchor in Tension

Rumus kapasitas breakout strength adalah sebagai berikut


Single Anchor :

Group Anchor :

Concrete Breakout Strength of Anchor in Tension


Dimana
ANC
ANCO
Nb
ed,N
c,N
cp,N
ec,N

:
: projected concrete failure area of single anchor
group
: projected concrete failure area of single anchor
with an edge distance equal to 1.5hef
: basic concrete breakout strength of single anchor
in tension
: modification factor for edge effect
: modification factor for no cracking effect on
service load
: modification factor for post installed anchor. For
cast in taken 1.0
: modification factor for anchor group loaded
eccentrically in tension

Concrete Breakout Strength of Anchor in Tension


Perhitungan Nb

Concrete Breakout Strength of Anchor in Tension


Calculate ANCO

Concrete Breakout Strength of Anchor in Tension


Calculate AN

Concrete Breakout Strength of Anchor in Tension


Calculate AN jika jarak ke pinggir anchor bolt kurang dari 1.5hef

Pull out strength of anchor in tension


Nominal Pullout Strength

For concrete indicate no cracking

Concrete Side-Face Blow Out in Tension


Single bolt capacity

Group bolt capacity

Steel Strength Anchor in Shear


Capacity of Single Bolt :

Concrete Breakout Strength Anchor in Shear


Capacity of Single Bolt :

Capacity of Group Bolt :

Concrete Breakout Strength of Anchor in Shear


Dimana
AVC
AVCO
Vb
ed,V
c,V
ec,V

:
: projected concrete failure area of single anchor
group
: projected concrete failure area of single anchor
with an edge distance equal to 1.5hef
: basic concrete breakout strength of single anchor
in shear
: modification factor for edge effect
: modification factor for no cracking effect on
service load
: modification factor for anchor group loaded
eccentrically in tension

Concrete Breakout Strength of Anchor in Shear


Perhitungan Vb :

Concrete Breakout Strength of Anchor in Shear


Calculate AVCO

Concrete Breakout Strength of Anchor in Shear


Calculate AVC

Calculate AVC on edge

Concrete Breakout Strength of Anchor in Shear


Calculate AVC on group of anchor

Concrete Breakout Strength of Anchor in Shear


Calculate AVC if distance bolt to edge is very deep

Concrete Pryout Strength Anchor in Shear


Capacity of Single Bolt :

Capacity of Group Bolt :

Shear and Tension Interaction

Kesimpulan
Selain dengan kedalaman anchor, jarak antar anchor dan jarak anchor
ke pinggir beton mempengaruhi kapasitas tension dan shear dari
anchor.