Intelligent
Detectors and Bases
Detectors: V-PS, V-PHS, V-HFD, V-HRD
Bases: B4U, RB4U, IB4U, SB4U
S853/
S1122
7300-1657:
0245-0248
Overview
Edwards Vigilant brand intelligent analog detectors are meticulously engineered to deliver high-performance features, superb
reliability, and unbeatable quality. With their highly stable design,
these detectors resist air movement caused by heating and air
conditioning, making them reliable performers ideally suited to
modern building interiors.
Standard Features
M85001-0592
D ATA S H E E T
Not to be used for installation purposes. Issue 2
Heat Detectors
Detector Bases
The V-Series heat detectors are capable of performing comprehensive self-diagnostics and storing the results.
Adaptor bracket
Screws
Trim ring
Connect the detector to the base by rotating the detector clockwise until it snaps into the locked position.
The head can be removed by turning it counterclockwise.
If the head must lock to the base, break away the
locking tab shown below using a pair of pliers.
Bottom of detector
Breakaway tab
Term
1
2
3
3
From
controller
or
previous
device
To next
device
SLC in (-)
SLC in (+)
Description
SLC in and SLC out (+)
SLC in (-)
Not used
Not used
Term
4
5
6
6
Description
Not used
Remote LED (+)
SLC out (-)
Remote LED (-)
LED Indication
V-Series detectors provide a bicolor status LED:
Normal: Green LED flashes
Alarm/active: Red LED flashes
Page 2 of 6
M85001-0592
D ATA S H E E T
Not to be used for installation purposes. Issue 2
Term
SLC in (+)
SLC in (-)
SLC out (+)
SLC out (-)
Description
DATA + (IN)
DATA - (IN)
DATA + (OUT)
DATA - (OUT)
AUX_RISER +
AUX_RISER SLC +
SLC -
AUX_RISER +
AUX_RISER SLC +
SLC -
TB2
TB1
Sleeping rooms: In sleeping areas, the high dBA output and temporal tone settings must be used. However, if the FACP is producing the three-tone temporal evacuation signal, then the high dBA
output and steady tone settings may be used.
Term
TB1
SLC in (+)
Description
N/O (Normally open)
COM (Common)
N/C (Normally
Closed)
DATA + (IN)
Term
SLC in (-)
SLC out (+)
SLC out (-)
Description
DATA - (IN)
DATA + (OUT)
DATA - (OUT)
Contact rating:
2.0a @ 30vdc resistive
Notes
1. Wire in accordance with NFPA 70, National Electrical Code.
2. Be sure to observe the polarity of the terminals on the terminal block
as shown in the diagram.
3. Break wire run at each terminal. Do not loop signaling circuit field
wires around terminals.
Page 3 of 6
M85001-0592
D ATA S H E E T
Not to be used for installation purposes. Issue 2
Wire size
Base diameter
Height from box
(including detector)
Maximum distance
from ceiling (wall
mount)
32 to 120F (0 to 49C)
0 to 93% RH, noncondensing at 90F (32C)
-4 to 140F (-20 to 60C)
V-PS, V-PHS, V-HRD, and V-HFD detectors
North American 2-1/2 in. (64 mm) deep 2 gang
box
Standard 4" square box 1-1/2 in. (38 mm) deep
box
European 100 mm square box
12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0,
or 0.75 sq. mm) (Sizes 16 and 18 AWG are
preferred)
6.0 in. (152 mm)
2.58 in. (66 mm)
12 in. (305 mm)
High dBA
28
41
52
48
60
66
Low dBA
High dBA
71.3
75.0
77.7
75.8
79.2
82.0
77.2
79.8
81.5
80.5
84.1
86.0
77.3
81.0
83.7
81.8
85.2
88.0
83.2
85.8
87.5
86.5
90.1
92.0
Specifications, Detectors
Air velocity
Smoke sensitivity range
ULI fixed-temp alarm rating
ULC fixed-temp alarm rating
Maximum Spacing
Rate-of-Rise
Operating voltage
Normal operating current
Alarm current
Environmental compensation
Compatible bases
Maximum distance from ceiling
wall-mounted
Storage temperature
Operating environment
Agency listings
Page 4 of 6
V-PHS
V-PS
V-HRD
0 to 5,000 ft/min (0 to 25.39 m/s)
N/A
0.67% - 3.66%
135F (57C)
N/A
140F (60C)
30 ft (9.1 m)
N/A
15F (8C)/min.
15.2 to 19.95 VDC
45 A, average
45 A, average
Automatic
B4U Standard, RB4U Relay, IB4U Isolator, SB4U Audible
V-HFD
135F (57C)
140F (60C)
50 ft (15 m) centers
N/A
12 in (305 mm)
-4 to 140F (-20 to 60C)
Temperature: 32 to 120F (0 to 49C); Humidity: 0 to 93% RH, noncondensing at 90F (32C)
Meets UL 268,
Meets UL 268,
ULC-S529-02, UL 521,
Meets UL 521, ULC-S530-M91, NFPA 72, and
ULC-S529-02, NFPA 72,
ULC-S530-M91, NFPA 72,
CAN/ULC S524-01
and CAN/ULC S524-01
and CAN/ULC S524-01
M85001-0592
D ATA S H E E T
Not to be used for installation purposes. Issue 2
Specifications, Bases
B4U Standard Base
Operating environment
Temperature
Humidity
Storage temperature range
Compatible detectors
Compatible electrical boxes
Wire size
Base diameter
Height from box (including detector)
Maximum distance from ceiling (wall
mount)
32 to 120F (0 to 49C)
0 to 93% RH, noncondensing at 90F ( 32C)
-4 to 140F (-20 to 60C)
V-PS, V-PHS, V-HRD, and V-HFD detectors
North American 2-1/2 in. (64 mm) deep 2 gang box
Standard 4 in. square box 1-1/2 in. (38 mm) deep box
European 100 mm square box
12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm) (Sizes 16 and 18 AWG are preferred)
6.0 in. (152 mm)
2.08 in. (53 mm)
2.57 in. (65 mm)
12 in. (305 mm)
Ordering Information
Model
V-PHS
V-PS
V-HRD
V-HFD
B4U
RB4U
IB4U
SB4U
AB4G-SB
GSA-LED
211-10PKG
Page 5 of 6
Description
Intelligent Analog Optical/Fixed Temperature Detector
Intelligent Analog Optical Smoke Detector
Intelligent Analog Rate-of-Rise Heat Detector
Intelligent Analog Fixed Temperature Heat Detector
Standard Base
Relay Detector Base
Isolator Detector Base
Audible (Sounder) Detector Base
Surface Box for Audible Base
Remote alarm LED, use with standard base only
Replacement optical chambers (package of 10)
M85001-0592
D ATA S H E E T
Not to be used for installation purposes. Issue 2
Contact us...
Email: edwards.fire@fs.utc.com
Web: www.vigilant-fire.com
Vigilant is an EDWARDS brand.
1016 Corporate Park Drive
Mebane, NC 27302
2013 UTC Fire & Security Americas
Corporation, Inc. All rights reserved.
Specifications subject to change
without notice. Edwards is part of UTC
Climate, Controls & Security, a unit of
United Technologies Corporation.
M85001-0592
D ATA S H E E T
Not to be used for installation purposes. Issue 2
06-27-13