TX3 Aperio Door Controller Installation Quick Reference

Inputs 1 to 8

Outputs 1 to 6
SW1

Inputs 1 to 8 are general purpose inputs.

Aperio Hub Settings and Connections

SW1 sets the Telephone Access controller


networkSwitch
address. Use
Tamper
DIP switches 1 to 5 to set the network address. DIP switches 6, 7
and 8 should remain at the factory set values.

Set DIP switches 1 to 4 on S101 to a unique RS-485

address.
Set DIP switch 8 on S101 to ON if the Aperio hub is

INPUT 1

INPUT 8

on the end of the RS-485 bus.

SW2

OUTPUT 7

JW4

hubs on the RS-485 network.

NO NC

OUTPUT 1

OUTPUT 2

JW6

terminal on the MD-1113.

DIP

D0
RED

ON

GREEN

1 2 3 4 5 6 7 8 9 10

INT

Aperio
USB connection
Hub 1

TERM
UP
DOWN
A4
A3
A2
A1
A0

OUTPUT 6

Outputs 7 and 8
Outputs 7 and 8 are programmable and provide:

P6 - P5 +OFF
BAT-

INPUT

BAT+

JW1 OPEN
JW2 OPEN
- S +

SW2
Aperio
Hub 3

Ribbon cable
connects to P3
on main board
ON

ON/OFF
A BSwitch
SW1

SW2 sets the Card Access controller RS-485 network address and
determines how the IP module get its IP address (if installed).

Use DIP switches 1 to 6 to set the RS-485 network address.


A B

Connection for
front door LEDs

Address 1

Red

12 V BATTERY

P5, P6. Battery connections.


P7. AC, Trouble and Alarm LEDs.

Jumpers

MD-1113 Module

JW1, JW2. Leave open. Short only when updating


firmware.
JW3, JW4, JW5. Leave open. Not used.

Aperio
Hub 1

A B

JW1 OPEN
JW2 OPEN

S101
DIP 6 OFF
DIP 7 OFF
DIP 8 OFF

Aperio
Hub 2

Aperio
Hub 3

A B

A B

S101
DIP 6 OFF
DIP 7 OFF
DIP 8 OFF

S101
DIP 6 ON
DIP 7 ON
DIP 8 ON

Connect the last controller on the network to the RS-485 input


terminal. Refer to LT-980 section 3.3.5 for end of line resistors to
be used on the first and last nodes of network. The RS-485
terminal consists of + (positive), - (negative), and S (Shield)
connections.
Aperio
Hub 3

A B

A B

A B

S101
DIP 6 ON
DIP 7 ON
DIP 8 ON

S101
DIP 6 OFF
DIP 7 OFF
DIP 8 OFF

S101
DIP 6 OFF
DIP 7 OFF
DIP 8 ON

JW1 OPEN
JW2 OPEN

JW6. JW6 is not used and by default is open.


Version 0.11
LT-1164

Aperio
Hub 2

Aperio Door Controller Installation Quick Reference

OFF

The RS-485 connection consists of an input and output terminal.


Connect the RS-485 output terminal to the RS-485 input terminal
of the next controller.

16 Guage
Wire

MD-1113 Module

RS-485

Aperio hubs on both ends of RS-485 bus.


Aperio
Hub 1

ON

software.

Connecting the Aperio Hubs to the MD-1113 RS-485 Network Terminal


MD-1113 on one end and an Aperio hub on the other end of
the RS-485 network bus.

Address 4

Set DIP switch 8 ON to get IP address from TX3 Configurator

P3. Connector for MD-1113 Module Board.


P4. Connector for MD-921 IP Module board.

Address 3

Set DIP switch 8 OFF to get IP address from DHCP server.

Ground
Terminal

optional

Address 2

S101
DIP 6 OFF
DIP 7 OFF 1
8
1
8
1
8
1
DIP 8 ON
Keep DIP switch 7 at the factory set value

Power terminals for 16


Vac transformer (PS-4 or
PS-4P)

USB. Computer connection for firmware download and


configuration.

output of 1 A. For example, if output 7 provides 700 mA,


then output 8 provides 300 mA.

S +

Connections

a maximum output of 700 mA each, for a combined total

S101
DIP 6 OFF
DIP 7 OFF
DIP 8 OFF

OUTPUT

Black

J100

12 Vdc

P7
Aperio
Hub 2

P1

RS-485

Thermal Kit

8-24VDC

30 Vac rated \ 1 amp

NO

MD-1113

RS-485 terminals for connecting


to multiple TX3 controllers

S101

OUTPUT 5

ALARM

JW 1

S101
DIP 6 ON
DIP 7 ON
DIP 8 ON

EXT

30 Vdc \ 3 amp

NO NC

TROUBLE

Connection to 12V
battery
backup Module
MD-1113

A B

ANTENNA

OUTPUT 4

LEDs

JW 5

NO NC

RS-485 terminals for Aperio


Hubs (see figures below)

terminal on the MD-1113.


8-24VDC terminals on J100.

OUTPUT 3

P4

Connect the B terminal on J100 to the negative (-)


Connect power (8-24 Vdc, 250 mA) to the GND and

NO NC

AC

JW2

Connect the A terminal on J100 to the positive (+)

Outputs 7 and 8
IP Module Interface

hubs on the RS-485 network.

NO NC

O u ttpu
p u t s 1 to 6

JW3

Set DIP switch 7 on S101 to ON for one of the Aperio

GND

OUTPUT 8

Inputs 1 to 8

Set DIP switch 6 on S101 to ON for one of the Aperio

D1

NC

12V

12V

Outputs 1 to 6 are relay contact programmable normally open


(NO) or normally closed (NC) outputs. Any power supply
connected to these outputs cannot exceed:

Ground Terminal
The Card Access system is equipped with a 16 gauge electrical
wire attached to the panel chassis Ground Terminal. Do not
disconnect this wire.
Attach the end of the supplied wire to a suitable grounding wire
16 gauge or thicker. Attach the other end to the cold water
ground.

for more information see LT-1160 Aperio Door Controller System Manual
available on CD, USB flash drive, or website WWW.MIRCOM.COM

TX3 Aperio Door Controller Installation Quick Reference

The following figure shows the various controller connections

Aperio Hub 1

Aperio Hub n

TX3 Aperio Door Controller


Installation Quick Reference
IMPORTANT
This document is for reference only and does not replace the existing documentation. For more detailed
information refer to the documentation on the CD, the USB flash drive, or Mircom website
(www.mircom.com).

RS-485 Network for Aperio Hubs


Maximum network bus length: 3,000 feet
Use 22 AWG wire

Installation Prerequisites
OUTPUTS 1 to 6

INPUTS 1 to 8

Relay contact, 2 amps

General purpose inputs


General
purpose input

General
purpose input

1 pair
22 AWG

General
purpose input

1 pair
22 AWG

1 pair
22 AWG

Ensure there is a provision for a ground circuit. The Aperio Door Controller assembly must be grounded by a qualified

electrician. An improperly grounded unit can result in equipment malfunction and void the warranty.
Use the latest Aperio Door Controller System controller firmware. Mircom periodically updates panel firmware and

Configurator Software to add features and correct any minor inconsistencies. For information about the latest firmware
or software visit the Manuals and Downloads section of the Mircom website at www.mircom.com.

Aperio Door
Controller

Basic Wiring

3 wires
22 AWG

1. Turn the controller power switch to OFF.


2. Connect the Aperio hub network bus to the RS-485 terminal on the MD-1113 Module board.
3. Connect any inputs and outputs.
1 pair
22 AWG

1 pair
18 AWG
1 pair
22 AWG

General
purpose input

General
purpose input

OUTPUTS 7 to 8

22 AWG

Programmable outputs
Combined 1 amp output
12 Vdc
500 mA

Power
transformer
16VAC/40VA
PS-4 or PS-4P

Power
transformer
AC or DC Door
strike supply

Configure the system using the Configurator software using a USB or modem connection. Verify the following:
Ensure that the controller and all connected devices and components are fully operational.

Ensure the Configurator software is set with the correct controller RS-485 network address.
120 VAC
60HZ

Wiring requirements
Install all transformers outside the Lobby Control Unit enclosure.
Unless specified otherwise, all wiring is a maximum length of 1000 ft. The RS-485 wiring maximum length is 4000 ft.
All units use the PS-4P transformer for the power supply. The door strike power supply depends on the door strike

Version 0.11
LT-1164

Before Starting the Configuration

Ensure the controller DIP Switches are set with a unique RS-485 network address.

Single Panel Wiring

power requirements.

5. Set SW2 to a unique RS-485 network address.


6. Turn the controller power switch to ON (a correctly wired controller will show a green AC LED).

RS-485 Network
for TX3 devices

Electrical room

4. Connect the controller supply.

Ensure that your PC is set with the correct date and time.

To Start the Configuration


1. Connect the PC to the controller using the USB port or modem connection.
2. Launch the Configurator and select the correct controller you are connecting to (on the basis of name, panel label, panel
model, and network address).
3. Click Connect. The connection icon appears in the Configurator tool bar.
4. Ensure that the panel is configured with the correct date and time.
5. Configure the Aperio Door Controller using the instructions in the LT-1160 Installation and Operation Manual.
for more information go to the CD, USB flash drive, or website and read the LT-1160 Aperio Door Controller System Manual
WWW.MIRCOM.COM