(Published2007)
Thisbookgivesfullinformationofbothelectricalandnonelectrical
hazardousareatechnology
andcoversterminology,equipmentmarking,ATEX,DSEAR,Area
Classification,TypesofProtectionetc.
Clickherefordetails
Hazardousareasaredefinedbythreemaincriteria:
Thetypeofhazard
Thelikelihoodofthehazardbeingpresentinflammableconcentrations
The(auto)ignitiontemperatureofthehazardousmaterial
Thetypeofhazard(Groups)
http://www.hexagontech.co.uk/hazard_basics.htm
1/10
5/24/2015
HazardousAreaBasics
Thehazardwillbeintheformofagas,vapour,dustorfibre.
GasesandVapours
Gasesandvapoursarecategorizedintermsoftheirignitionenergyorthemaximum
experimentalsafegap(inrespectofflameproofprotection).Thiscategorization
leadstotheGasGroups:
Mining
GroupI
Methane
IIA
Propane
SurfaceIndustry
GroupII
IIB
Ethylene
IIC
Hydrogen
(Thegasesnotedinthetablearetypicalgasesforeachgroup.)
GroupIICisthemostseveregroup.Hazardsinthisgroupcanbeignitedveryeasily
indeed.
EquipmentmarkedassuitableforGroupIICisalsosuitableforIIBandIIA.
EquipmentmarkedassuitableforIIBisalsosuitableforIIAbutNOTforIIC.
Ifequipmentismarked,forexample,ExeIIT4thenitissuitableforallsubgroups
IIA,IIBandIIC.
DustsandFibres(GroupIII)
GroupIIIissubdividedintothreesubgroups:
IIIACombustibleflyings
IIIBNonconductivedust
IIICElectricallyconductivedusts
Dustsandfibresarealsodefinedintermsoftheirignitionpropertiesincludingdust
cloudignitionproperties.
BACKTOTOP
Thelikelihoodofthehazardbeingpresentin
flammableconcentrations(Zones)
http://www.hexagontech.co.uk/hazard_basics.htm
2/10
5/24/2015
HazardousAreaBasics
Thelikelihoodofthehazardbeingpresentinflammableconcentrationswillvaryfrom
placetoplace.Alocationveryclosetoanopensourceofhazardwillhaveahigh
likelihoodofaflammableatmosphere.Ontheotherhand,outsideaflangedpipe
containingaflammableliquid,thelikelihoodofaflammableatmospherebeing
presentismuchlowersinceitwillonlyoccuriftheflangeleaks.Ratherthanwork
withaninfiniterangeofpossibilities,threezonesaredefined.
GasesandVapours
Therearethreezonesforgasesandvapours:
Zone0
Zone1
Zone2
Flammableatmospherehighlylikelytobepresentmaybe
presentforlongperiodsorevencontinuously
Flammableatmospherepossiblebutunlikelytobepresent
forlongperiods
Flammableatmosphereunlikelytobepresentexceptfor
shortperiodsoftimetypicallyasaresultofaprocessfault
condition.
Zonezeroisthemostseverezone(thehighestprobabilityofflammableatmosphere
presence).Equipmentforthiszoneneedstobeverywellprotectedagainst
providingasourceofignition.
Dusts
Therearethreezonesfordusts:
Zone20
Dustcloudlikelytobepresentcontinuouslyorforlong
periods
Zone21
Dustcloudlikelytobepresentoccasionallyinnormal
operation
Dustcloudunlikelytooccurinnormaloperation,butifit
does,willonlyexistforashortperiod
(Thepresenceofdustlayersdoesnotautomaticallyleadtothedustzone.The
likelihoodofthedustlayerbeingdisturbedtocreateacloudneedstobeconsidered.
Dustlayersalsoneedcarefulconsiderationintermsofignitiontemperature.
Becausethedustlayercanmaketheequipmentunderithotterthennormal,afactor
ofsafetyisappliedtothelayerignitiontemperature.)
Zone22
http://www.hexagontech.co.uk/hazard_basics.htm
3/10
5/24/2015
HazardousAreaBasics
BACKTOTOP
The(auto)ignitiontemperatureofthehazardous
material(TemperatureClasses)
Aswellasconsideringtheprotectionagainstelectricalarcsandsparksignitinga
flammableatmosphere,considerationneedstobegiventothesurfacetemperature
ofequipment.(Mostelectricalapparatusdissipatessomeheat!)Flammable
materialsarecategorizedaccordingtotheirignitiontemperature.Again,ratherthan
workwithaninfiniterange,sixtemperatureclassesaredefinedasfollows:
TClass
Hazardswhichwillnotigniteattemperaturesbelow:
T1
T2
T3
450C
300C
200C
T4
T5
T6
135C
100C
85C
ThebiggertheTnumbertheloweristhetemperature.
TheTemperatureclassificationwillbemarkedonitemsofequipment.Ifthe
hazardousareainwhichyouareinstallingequipmenthasgasesorvapourswitha
lowautoignitiontemperaturethenyouwillneedequipmentwithabiggerTNumber
soastoensurethatanyhotsurfacesontheequipmentwillnotignitethehazard.
Forexample,ifahazardhasanautoignitiontemperatureof180C,thenitwouldbe
safetouseequipmentwhichismarkedT6orT5orT4.Itwouldnotbesafetouse
equipmentmarkedT3orT2orT1asthisequipmentcouldexhibitsurface
temperatureswhicharehotenoughtoignitethehazardousatmosphere.
Don'tforgetthat,unlessthecertificationdocumentsstateotherwise(inwhichcase
therewillbeanadditiontotheTClassificationcodeontheequipmentlabelsuchas
T4(60CAmb))theequipmentisonlycertifiedinambienttemperaturesupto40C.
Ifexposedtohighertemperaturestherearetwopossibledangers.FirstthestatedT
Classtemperaturemaybeexceededandsecondlysafetycomponentswithinthe
equipmentcouldfailtoanunsafecondition.Ifyouexpectequipmenttobesubjected
totemperaturesabove40C(suchasindirectsunshineorinaroofspace)you
shouldinstallequipmentwhichiscertifiedforahigherambienttemperature.
http://www.hexagontech.co.uk/hazard_basics.htm
4/10
5/24/2015
HazardousAreaBasics
BACKTOTOP
ProtectingElectricalApparatustomakeitsuitableforuse
inhazardousareas
Electricalapparatusforuseinhazardousareasneedstobedesignedand
constructedinsuchawaythatitwillnotprovideasourceofignition.Thereareten
recognizedtypesofprotectionforhazardousareaelectricalapparatus.Eachtypeof
protectionachievesitssafetyfromignitionindifferentwaysandnotallareequally
safe.InadditiontotheequipmentbeingsuitablefortheGasGroupandthe
TemperatureClassrequired,thetypeofprotectionmustbesuitableforthezonein
whichitistobeinstalled.Thedifferenttypesofprotectionandthezonesforwhich
theyaresuitableareasfollows:
Forinformationonequipmentmarking,clickhere(opensnewpage)
TypesofProtectionforGas/VapourHazards
SeealsoinformationonTypesofProtection,Clickhere(opensnewpage)
Equipment
Code
Exia
Exib
Intrinsicsafety'ia'
Intrinsicsafety'ib'
Suitablefor
zones...
0,1,2
1,2
Equipment
Category...
1G
2G
Exic
IntrinsicSafety'ic'
3G
Exd
Flameproofprotection
1,2
2G
Exp
Purge/pressurizedprotection
1,2
2G
Expx
Purge/pressurizedprotection
'px'
1,2
2G
1,2
2G
3G
1,2
1,2
2G
2G
0,1,2
1G
Description
Exe
Exm
Purge/pressurizedprotection
'py'
Purge/pressurizedprotection
'pz'
Increasedsafety
Encapsulation
Exma
Encapsulation
Expy
Expz
http://www.hexagontech.co.uk/hazard_basics.htm
5/10
5/24/2015
HazardousAreaBasics
Exmb
Encapsulation
1.2
2G
Exmc
Exo
Exq
Encapsulation
Oilimmersion
Sand/powder(quartz)filling
2
1,2
1,2
3G
2G
2G
Exn
Exs
Typenprotection
Specialprotection
2
Normally1and2
3G
EquipmentcomplyingwithEuropean(CENELEC)standardswillfrequentlybearthe
codeEEx(asopposedtoEx)ButnotethattheuseofEExisbeingphasedout,and
equipmentdesignedandcertifiedtothelatesteditionsoftheEuropeanStandards
willbecodedEx...(asopposedtoEEx...).
Ingeneral,theEuropeanstandardsforhazardousareaelectricalequipmentare
technicallyidenticaltotheIEC(InternationalElectrotechnicalCommission)
standards.Equipmentmanufacturersoftenhhavetheirequipmentdesignscertifiedto
boththeEuropeanandIECrequirementssothattheycanmarkettheirequipment
worldwide.Thisdoes,unfortunatelymaketheequipmentlabellingplatemore
complex.
TypesofProtectionforEquipmentforDustHazardLocations
Equipment
Code
tDA20
tDB20
iaD
Protectionbyenclosure
Protectionbyenclosure
IntrinsicSafety
Suitablefor
Zones...
20,21,22
20,21,22
20,21,22
Equipment
Category..
1D
1D
1D
maD
tDA21
tDB21
ibD
mbD
pD
Encapsulation
Protectionbyenclosure
Protectionbyenclosure
IntrinsicSafety
Encapsulation
Pressurization
20,21,22
21,22
21,22
21,22
21,22
21,22
1D
2D
2D
2D
2D
2D
tDA22
tDB22
Protectionbyenclosure
Protectionbyenclosure
22
22
3D
3D
icD
IntrinsicSafety
22
3D
Description
http://www.hexagontech.co.uk/hazard_basics.htm
6/10
5/24/2015
HazardousAreaBasics
BACKTOTOP
EquipmentProtectionLevelsEPL
From2007onwards,theIECTechnicalStandardsintheseriesIEC60079,andin
particularIEC60079Part14,haverecognisedthattheremaybeoccasionswhereit
isnecessarytoincrease,abovethenormallevels,theprotectionagainstignition
sources.Thisconceptallowsforconsiderationofrisk(ieconsequencesofan
explosion)asopposedtojusttheprobabilityofaflammableatmosphereexisting
theconventionalselectioncriteriabetweenthetypesofprotectionandthezoneof
use.
ThreeEquipmentProtectionLevelsarespecifiedasshowninthetablebelow.
InnormalcircumstancestheeffectoftheseEPLswillbetoretainthenormal
zone/equipmentprotectionrelationship.If,however,theriskisconsideredespecially
severe,thentherequiredEPLforthezonemaybeincreased.Similarly,iftheriskis
deemedtobeespeciallysmallornegligible,theEPLmaybereducedfromthenorm.
ThefollowingtwotablesshowthenormalrelationshipbetweenEPLandzone,and
theEPLawardedtoeachtypeofprotection.
EquipmentProtectionLevel
(EPL)
Ga
NormalApplicableZone(s)
0(and1and2)
Gb
Gc
1(and2)
2
EquipmentCode
Exia
Exib
Exic
Description
Intrinsicsafety'ia'
Intrinsicsafety'ib'
IntrinsicSafety'ic'
EPL
Ga
Gb
Gc
Exd
Flameproofprotection
Gb
Exp
Expx
Expy
Expz
Purge/pressurizedprotection
Purge/pressurizedprotection'px'
Purge/pressurizedprotection'py'
Gb
Gb
Gb
Gc
Exe
Increasedsafety
http://www.hexagontech.co.uk/hazard_basics.htm
Purge/pressurizedprotection'pz'
Gb
7/10
5/24/2015
HazardousAreaBasics
Exm
Exma
Exmb
Exo
Exq
Exn
Encapsulation
Encapsulation
Encapsulation
Oilimmersion
Sand/powder(quartz)filling
Typenprotection
Exs
Specialprotection
Gb
Ga
Gb
Gb
Gb
Gc
Refertoequipment
markingand
documentation
Fordusthazards,theEPLsareasfollows:
EquipmentProtectionLevel
(EPL)
NormalApplicableZone(s)
Da
Db
20(and21and22)
21(and22)
Dc
22
BACKTOTOP
Standards
Therearevariousstandardswhichgivedetailsofhazardousarearequirements.In
themain,theIECstandardsarenowparallelvotedbyCENELEC(Europe).New
standardsarebeingintroducedatabewilderingrateanditisalwaysworthchecking
against,forexample,theBSIwebsite.(SeeUsefulLinksPage)
ItisimportantforequipmentdesignerstodesigntothelatesteditionofATEX
harmonisedstandardstheuptodatelistcanbefoundontheECATEXwebsite.
(SeeUsefulLinksPage)
Gradually,thetechnicalstandardsforthetechnologyforgas/vapourhazardsand
thosefordusthazardsarebeingincorporatedintothesameseries.ForexampleIEC
6007910coversareaclassificationIEC60079101dealswithgas/vapourhazards
andIEC60079102dealswithdusthazards.Similarnumberingwillapplyforother
aspectssuchasinstallation.
Toplevelstandard
EN11271Explosiveatmospheres:Explosionpreventionandprotection.Part1:
Basicconceptsandmethodology
http://www.hexagontech.co.uk/hazard_basics.htm
8/10
5/24/2015
HazardousAreaBasics
StandardsforEquipment
IEC60079ELECTRICALAPPARATUSFOREXPLOSIVEGASATMOSPHERES
Part0Generalrequirements
Part1Constructionandtestofflameproofenclosuresofelectricalapparatus
Part2Electricalapparatustypeofprotectionp
Part3Sparktestapparatusforintrinsicallysafecircuits
Part4Methodoftestforignitiontemperature
Part5Powderfillingq
Part6Oilimmersiono
Part7Increasedsafetye'
Part11Constructionandtestofintrinsicallysafeandassociatedapparatus
Part15Electricalapparatusforexplosivegasatmospheres,typeofprotectionn
Part18Encapsulationm
Part25Intrinsicallysafesystems
Part26Specialrequirementsforconstructiontestandmarkingofzone0electrical
apparatus
Part27Fieldbusintrinsicallysafeconcept(FISCO)
StandardsforInstallationetc.(gasesandvapours)
IEC60079ELECTRICALAPPARATUSFOREXPLOSIVEGASATMOSPHERES
Part10Classificationofhazardousareas
Part14Installation(andselection)ofequipmentinhazardousareas
Part17Inspectionandmaintenanceofequipment
Notethatthe60079seriesofstandardswillgraduallyaddressdusthazardsaswell
asgas/vapourhazards.Thestandardnumberwillhaveanadditionalsuffix1or2.
Thus,forexample,6124114(seebelow)willbereplacedby60079142[installation
forequipmentindusthazards],with60079141dealingwithinstallationsin
gas/vapourhazards.
StandardsforDustHazardEquipmentandInstallation
IEC61241ELECTRICALAPPARATUSFORUSEINTHEPRESENCEOF
COMBUSTIBLEDUST
Part0GeneralRequirements
http://www.hexagontech.co.uk/hazard_basics.htm
9/10
5/24/2015
HazardousAreaBasics
Part1ProtectionbyenclosuretD
Part21Methodsfordeterminingtheminimumignitiontemperatureofdusts
Part22Methodfordeterminingtheresistivityofdustinlayers
Part23Methodfordeterminingminimumignitionenergyofdustairmixtures
Part4TypeofprotectionpD
Part10Classificationofareaswherecombustibledustsareormaybepresent
Part11ProtectionbyintrinsicsafetyiD
Part14Selectionandinstallation
Part17Inspectionandmaintenance
Part18ProtectionbyencapsulationmD