Documentos de Académico
Documentos de Profesional
Documentos de Cultura
By : Morteza Shabanzadeh
Supervisor : Professor Mahmoud-Reza Haghi-Fam
Morteza Shabanzadeh & TMU 2013
P
Presentation
t ti
O
Outline
tli
Introduction
SCC Calculation According to IEC 60909 Standard
Impact of DGs on Fault Locating Methods
DGs Effects in Different Types of Dis. Networks
Limitation of Short-Circuit Power due to DGs
MortezaShabanzadehandTMU2013
2/72
Introduction
Short-Circuit Currents :
Initial symmetrical short-circuit current (
Peak short-circuit current (
MortezaShabanzadehandTMU2013
3/72
Introduction
MortezaShabanzadehandTMU2013
4/72
Introduction
Peak Short-Circuit Currents (
):
MortezaShabanzadehandTMU2013
6/72
Introduction
Initial & Steady-state Short-Circuit Currents (
They will result in large losses
):
g
And therefore cause thermal overloading.
MortezaShabanzadehandTMU2013
6/72
Introduction
Fault level calculations are indispensable tools during the Grid Design Phase.
MortezaShabanzadehandTMU2013
7/72
Introduction
Distribution networks are characterized by:
Max acceptable fault current (related to the switchgear)
Thermal withstand capability (of the equipment)
Mechanical withstand capability (of the equipment and constructions)
MortezaShabanzadehandTMU2013
8/72
Introduction
Main inhibiting factor for the interconnection of DGs:
Combined Isc contribution of the upstream grid and DGs should remain
below the network design value.
SCC of existing distribution network (esp. MV) is close to the design value
(little margin for the connection of DGs).
MortezaShabanzadehandTMU2013
9/72
Introduction
DGs Isc depends on :
DGs size
DGs control mode (Technology)
The number of connection points of DGs in the system
MortezaShabanzadehandTMU2013
10/72
P
Presentation
t ti
O
Outline
tli
Introduction
SCC Calculation According to IEC 60909 Standard
Impact of DGs on Fault Locating Methods
DGs Effects in Different Types of Dis. Networks
Limitation of Short-Circuit Power due to DGs
MortezaShabanzadehandTMU2013
11/72
MortezaShabanzadehandTMU2013
12/72
):
):
hasnophysicalmeaning
MortezaShabanzadehandTMU2013
13/72
):
MortezaShabanzadehandTMU2013
):
14/72
):
The rms value of the current after the decay of the transient
components.
For far-from-generator faults :
MortezaShabanzadehandTMU2013
15/72
MortezaShabanzadehandTMU2013
16/72
MortezaShabanzadehandTMU2013
17/72
Fornetworkswithanominalvoltagehigherthan35kV,theIECStandardsuggestsRQ=0.
Inallothercases,itrecommendsRQ/XQ=0.1asasafeassumption.
MortezaShabanzadehandTMU2013
18/72
TheseEqs.arealsoapplicabletoshort
These Eqs are also applicable to shortcircuit
circuitcurrentlimitingreactors.
current limiting reactors
MortezaShabanzadehandTMU2013
19/72
Theimpedanceofoverheadlinesandcables iscalculatedfromconductorandline
geometrydataanditistypicallyknownforstandardlinetypes.
MortezaShabanzadehandTMU2013
20/72
Xd isthesubtransientreactance.
MortezaShabanzadehandTMU2013
21/72
TheimpedanceisreferredtotheHVside.
tr istheratedtransformationratiooftheunittransformer.
MortezaShabanzadehandTMU2013
22/72
MortezaShabanzadehandTMU2013
23/72
MortezaShabanzadehandTMU2013
24/72
MortezaShabanzadehandTMU2013
25/72
MortezaShabanzadehandTMU2013
26/72
Decoupled via
converter interface
Asynch.
Generator
Synch.
Generator
Static
Conversion
CHP
Fuel Cell
PV
MortezaShabanzadehandTMU2013
Rotating
Conversion
Direct drive WTs
-CHP
27/72
MortezaShabanzadehandTMU2013
28/72
TypeII
Type
TypeII
TypeIII
TypeIV
MortezaShabanzadehandTMU2013
29/72
Type I
SHEP, CHP
MortezaShabanzadehandTMU2013
30/72
Type II
Small SHEP,
constant speed WTs
MortezaShabanzadehandTMU2013
31/72
Type III
DFIG
(variable speed WTs)
MortezaShabanzadehandTMU2013
32/72
LimitedovercurrentcapabilityofRotor
Statorcurrentisdominant
Crowbar protection
Crowbarprotection
RoughlyapproximatedasTypeII
Statorisdisconnectedafter30~50ms
Isc(max)<5p.u.(beforetrippingthestator)
(
) p ( f
pp g
)
MortezaShabanzadehandTMU2013
33/72
Type IV
PVs, -Turbines
variable speed WTs
MortezaShabanzadehandTMU2013
34/72
AretreatedasASynch.Machines
or
or
t isthedurationofthecontribution
(100msmaybeadoptedhereaswell)
MortezaShabanzadehandTMU2013
35/72
Case Study
PLOAD =35MVA
Type IV
PDG =17.16MW
T
Type
II
Type III
MortezaShabanzadehandTMU2013
Type I
36/72
Case Study
Type IV
Type III
Type II
Type I
MortezaShabanzadehandTMU2013
37/72
Case Study
Results
Asexpected,thecontributionofTypeIV
DGunitsismuchlowerthanallotherTypes.
Type IV
Type III
MortezaShabanzadehandTMU2013
38/72
Case Study
Results
Type II
Type I
MortezaShabanzadehandTMU2013
39/72
Case Study
Resulting fault level at the MV busbars :
Algebraic sum
Phasor sum
(with contribution of WF1 added algebraically)
MortezaShabanzadehandTMU2013
40/72
MortezaShabanzadehandTMU2013
41/72
Example (2) :
Resulting fault level in Netherland test network:
Peak Short Circuit Current (KA)
MortezaShabanzadehandTMU2013
42/72
MortezaShabanzadehandTMU2013
43/72
P
Presentation
t ti
O
Outline
tli
Introduction
SCC Calculation According to IEC 60909 Standard
Impact of DGs on Fault Locating Methods
DGs Effects in Different Types of Dis. Networks
Limitation of Short-Circuit Power due to DGs
MortezaShabanzadehandTMU2013
44/72
MortezaShabanzadehandTMU2013
45/72
MortezaShabanzadehandTMU2013
46/72
off fault
DG at d
downstream
off fault
DG at upstream
1. InverterbasedDGsinjectless shortcircuitcurrenttothefault.
2. UpstreamDGshavemorenegative effectsonfaultlocatingmethodsincomparisontodownstreamDGs.
MortezaShabanzadehandTMU2013
47/72
P
Presentation
t ti
O
Outline
tli
Introduction
SCC Calculation According to IEC 60909 Standard
Impact of DGs on Fault Locating Methods
DGs Effects in Different Types of Dis. Networks
Limitation of Short-Circuit Power due to DGs
MortezaShabanzadehandTMU2013
48/72
Radial
Loop
L
Network
MortezaShabanzadehandTMU2013
49/72
MortezaShabanzadehandTMU2013
C
Case(1)
(1)
C
Case(2)Case(3)
(2)C
(3)
50/72
BusVoltage(p.u
u.)
DGat7,VC
DGat2~7,,
5MW,PF
DGat2~7,
5MW,VC
B #
Bus#
MortezaShabanzadehandTMU2013
51/72
We can see that the more connection points of DG in the system, the lower values
of short circuit currents.
MortezaShabanzadehandTMU2013
52/72
The
h case off shared
h d sized
d DG at two connection points provides
d b
better profile
f l around
d 1.0 p.u.
MortezaShabanzadehandTMU2013
53/72
As expected,
d ffault
l currents d
decrease as the
h ffault
l llocation gets far
f away ffrom the
h grid.
d
MortezaShabanzadehandTMU2013
54/72
MortezaShabanzadehandTMU2013
55/72
MortezaShabanzadehandTMU2013
56/72
MortezaShabanzadehandTMU2013
57/72
Dispersedlylocated DGresultsinbettervoltageprofilecomparedtosinglespot
locatedDG.
If
Ifadistributionsystemhasastronggridconnection,faultcurrentsmaynot
di t ib ti
t
h
t
id
ti
f lt
t
t
significantlyincreasewiththeadditionofDG.
AnumberofDGhavingaunitarypowerfactorcontrolshouldbelocatedalong
g
yp
f
g
distributionsystemsothatbettervoltageprofileisobtained.
MortezaShabanzadehandTMU2013
58/72
P
Presentation
t ti
O
Outline
tli
Introduction
SCC Calculation According to IEC 60909 Standard
Impact of DGs on Fault Locating Methods
DGs Effects in Different Types of Dis. Networks
Limitation of Short-Circuit Power due to DGs
MortezaShabanzadehandTMU2013
59/72
MortezaShabanzadehandTMU2013
60/72
MortezaShabanzadehandTMU2013
61/72
MortezaShabanzadehandTMU2013
62/72
low losses
very fast response (Ip can be limited quite well)
very expensive
are still in development stage (not commercially available yet)
MortezaShabanzadehandTMU2013
63/72
MortezaShabanzadehandTMU2013
64/72
Based on the fact that a coil, or transformer, has a very low impedance when it is in saturation
At the moment a fault occurs the large fault current forces the coil out of saturation, implying a much
higher impedance.
reliable operation
gradual and smooth change of impedance
good limiting capabilities (R8)
commercially available
large
g dimensions
high price
MortezaShabanzadehandTMU2013
65/72
MortezaShabanzadehandTMU2013
66/72
5. Is Limiter
very fast
good R-ratio
small size
low losses
after each operation fuses have to be replaced;
This
h implies
l
:
relatively high costs
longer interruption times
incorrect operation
MortezaShabanzadehandTMU2013
67/72
Limitation of Short-Circuit
Short Circuit Power due to DGs
SelectionofFCL
FCL:
Thegoaloftheprocedureistofindaconfigurationforwhich
Ctot isaslowaspossible(i.e.findingmin[Ctot]):
MortezaShabanzadehandTMU2013
68/72
Limitation of Short-Circuit
Short Circuit Power due to DGs
SelectionofFCL
FCL:
10
10stepproceduretoselectthebestFCL:
d
l
h b FCL
Step1. Createalistofpossiblefaultlocations;
Step2. Foreachofthepossiblefaultlocations,
conductashortcircuitcalculationusingIEC(60)909;
co
duc a s o c cu ca cu a o us g
(60)909;
Step3. Removethefaultlocationsforwhichnopeakfault
currentproblemoccurs;
Step4. Foreachoftheremainingfaultlocations:
Determinetheprobabilityofafaulttooccur;
St 5 Selectthefaultlocationwiththehighestfault
Step5.
S l t th f lt l ti
ith th hi h t f lt
occurrenceprobability.
Step6.Calculatethetotalcostsofafaultatthislocation,
withoutaddingfaultcurrentlimiting.
MortezaShabanzadehandTMU2013
Step7.Determinepossiblefaultcurrentlimiterlocations;
Step8.Foreach(combination)ofthelocations:calculate
thetotalcostsofafault,usingthetwodifferent
e o a cos s o a au , us g e o d e e
typesoffaultcurrentlimitersatthelocation(s);
Step9.Selectthesituationwiththelowesttotalcosts
causedbyafaultandpermanentlyaddthefault
currentlimiter.
St 10 R
Step10.Removethefaultlocationfromthelistand
th f lt l ti f
th li t d
restartfromstep2,repeatinguntilthereisno
faultlocationleftinthelist
69/72
Limitation of Short-Circuit
Short Circuit Power due to DGs
CHP
SelectionofFCL
FCL:
CHP
ArealnetworkinthesouthwesternpartoftheNetherlands
MortezaShabanzadehandTMU2013
70/72
Limitation of Short-Circuit
Short Circuit Power due to DGs
SelectionofFCL
FCL:
Theresultsaccordingto10stepprocedure:
MortezaShabanzadehandTMU2013
71/72
those who
th
h struggle
t l in
i our cause,
we will surely guide them to our ways;
and Allah is with those who do good.
AL ANKABOOT (69)
AL-ANKABOOT
(6 )
MortezaShabanzadehandTMU2013
72/72