Está en la página 1de 72

In the name of Allah, Most Gracious, Most Merciful

Impact of Distributed Generation Units


on Short-Circuit Capacity (SCC) Calculations

By : Morteza Shabanzadeh
Supervisor : Professor Mahmoud-Reza Haghi-Fam
Morteza Shabanzadeh & TMU 2013

P
Presentation
t ti
O
Outline
tli
Introduction
SCC Calculation According to IEC 60909 Standard
Impact of DGs on Fault Locating Methods
DGs Effects in Different Types of Dis. Networks
Limitation of Short-Circuit Power due to DGs

MortezaShabanzadehandTMU2013

2/72

Introduction
Short-Circuit Currents :
Initial symmetrical short-circuit current (
Peak short-circuit current (

Steady state short-circuit current (

MortezaShabanzadehandTMU2013

3/72

Introduction

MortezaShabanzadehandTMU2013

4/72

Introduction
Peak Short-Circuit Currents (

):

Ip causes high dynamic and mechanical stresses on the components.


It will
ill be
b reached
h d within
ithi 10 ms after
ft occurrence off the
th fault.
f lt
Conventional circuit breakers in the network will not be fast enough to
interrupt this current and therefore components have to be designed such
that they are able to withstand these currents.

MortezaShabanzadehandTMU2013

6/72

Introduction
Initial & Steady-state Short-Circuit Currents (
They will result in large losses

):

g
And therefore cause thermal overloading.

MortezaShabanzadehandTMU2013

6/72

Introduction
Fault level calculations are indispensable tools during the Grid Design Phase.

The purpose of short-circuit calculations is to determine:


grid components.
p
Thermal effect of fault currents on g
Mechanical stresses on grid components.
Coordination of protection devices.

MortezaShabanzadehandTMU2013

7/72

Introduction
Distribution networks are characterized by:
Max acceptable fault current (related to the switchgear)
Thermal withstand capability (of the equipment)
Mechanical withstand capability (of the equipment and constructions)

MortezaShabanzadehandTMU2013

8/72

Introduction
Main inhibiting factor for the interconnection of DGs:
Combined Isc contribution of the upstream grid and DGs should remain
below the network design value.
SCC of existing distribution network (esp. MV) is close to the design value
(little margin for the connection of DGs).

MortezaShabanzadehandTMU2013

9/72

Introduction
DGs Isc depends on :
DGs size
DGs control mode (Technology)
The number of connection points of DGs in the system

MortezaShabanzadehandTMU2013

10/72

P
Presentation
t ti
O
Outline
tli
Introduction
SCC Calculation According to IEC 60909 Standard
Impact of DGs on Fault Locating Methods
DGs Effects in Different Types of Dis. Networks
Limitation of Short-Circuit Power due to DGs

MortezaShabanzadehandTMU2013

11/72

Overview of the IEC 60909 Standard


o Basic Principles:
Equivalent Voltage Source Method
Several simplifications in calculation procedures
Isc Calculation using Vn and rated values of the equipment
Various correction factors
Network neutral is earthed

MortezaShabanzadehandTMU2013

12/72

Overview of the IEC 60909 Standard


o Short-circuit current definitions:
Initial Symmetrical Short-Circuit Current (

):

rms value of the ac symmetrical component of a prospective


short-circuit current
Initial Symmetrical Short-Circuit Power (

):
hasnophysicalmeaning

MortezaShabanzadehandTMU2013

13/72

Overview of the IEC 60909 Standard


o Short-circuit current definitions:
Peak Short-Circuit Current (

):

Max instantaneous value of the fault current.

Decaying aperiodic component (

MortezaShabanzadehandTMU2013

):

14/72

Overview of the IEC 60909 Standard


o Short-circuit current definitions:
Steady-state Short-Circuit Current (

):

The rms value of the current after the decay of the transient
components.
For far-from-generator faults :

MortezaShabanzadehandTMU2013

15/72

Overview of the IEC 60909 Standard


o Calculation of

Equivalent Voltage Source :

Voltage of an ideal source applied at the short-circuit location in positive


sequence system, whereas all other sources in the system are ignored
(short-circuited).
(short-circuited)

MortezaShabanzadehandTMU2013

16/72

Overview of the IEC 60909 Standard


o Short-circuit Impedances :

MortezaShabanzadehandTMU2013

17/72

Overview of the IEC 60909 Standard


o Short-circuit Impedances :
1) Equivalent impedance of the upstream network :

Fornetworkswithanominalvoltagehigherthan35kV,theIECStandardsuggestsRQ=0.
Inallothercases,itrecommendsRQ/XQ=0.1asasafeassumption.

MortezaShabanzadehandTMU2013

18/72

Overview of the IEC 60909 Standard


o Short-circuit Impedances :
2) Equivalent impedance of a Transformer:

TheseEqs.arealsoapplicabletoshort
These Eqs are also applicable to shortcircuit
circuitcurrentlimitingreactors.
current limiting reactors

MortezaShabanzadehandTMU2013

19/72

Overview of the IEC 60909 Standard


o Short-circuit Impedances :
3) Equivalent impedance of Lines:

Theimpedanceofoverheadlinesandcables iscalculatedfromconductorandline
geometrydataanditistypicallyknownforstandardlinetypes.

MortezaShabanzadehandTMU2013

20/72

Overview of the IEC 60909 Standard


o Short-circuit Impedances :
4) Equivalent of Synchronous Generators:

Xd isthesubtransientreactance.

MortezaShabanzadehandTMU2013

21/72

Overview of the IEC 60909 Standard


o Short-circuit Impedances :
5) Equivalent of Power Station units with Syn. Generators:

TheimpedanceisreferredtotheHVside.
tr istheratedtransformationratiooftheunittransformer.

MortezaShabanzadehandTMU2013

22/72

Overview of the IEC 60909 Standard


o Short-circuit Impedances :
6) Equivalent of Asynchronous Motors:

ILR/IrM istheratiooflockedrotor toratedcurrentofthemachine..

MortezaShabanzadehandTMU2013

23/72

Overview of the IEC 60909 Standard


o Short-circuit Impedances :
Shuntcapacitorsandnonrotatingloadsareignored.

MortezaShabanzadehandTMU2013

24/72

Overview of the IEC 60909 Standard


o Correction factors:
IEC60909introducesimpedancecorrectionfactorsfor:
Transformers(KT)
Synchronousgenerators(KG)
Powerstationunits(KS)
whichmultiplytherespectiveimpedancesinallcalculationformulae.

MortezaShabanzadehandTMU2013

25/72

Overview of the IEC 60909 Standard


o Fault level calculation in networks with DG:
o Resultingfaultlevelisthephasorsumofthemaxfaultcurrentsfrom:
UpstreamGrid
StepdownTransformer
Step down Transformer
VariousDGs
o AccordingtoIEC60909:
Thegridcontributioniseasilycontributed,but
ThecontributionofnovelDGtypesisnotaddressedinthisStandard.

MortezaShabanzadehandTMU2013

26/72

Overview of the IEC 60909 Standard


DG
Directly
coupled

Decoupled via
converter interface

Asynch.
Generator

Synch.
Generator

Static
Conversion

SCIG & DFIG


wind g
generators

CHP

Fuel Cell
PV

MortezaShabanzadehandTMU2013

Rotating
Conversion
Direct drive WTs
-CHP

27/72

Overview of the IEC 60909 Standard


o Fault level calculation in networks with DG:
1) Contributionoftheupstreamgrid

MortezaShabanzadehandTMU2013

28/72

Overview of the IEC 60909 Standard


o Fault level calculation in networks with DG:
2) ContributionoftheDGstations

TypeII
Type
TypeII
TypeIII
TypeIV

MortezaShabanzadehandTMU2013

29/72

Overview of the IEC 60909 Standard


o Fault level calculation in networks with DG:
2) ContributionoftheDGstations
Type I :Synch.Generatorsdirectlycoupledtothegrid

Type I
SHEP, CHP

MortezaShabanzadehandTMU2013

30/72

Overview of the IEC 60909 Standard


o Fault level calculation in networks with DG:
2) ContributionoftheDGstations
Type II :ASynch.Generatorsdirectlycoupledtothegrid

Type II
Small SHEP,
constant speed WTs

MortezaShabanzadehandTMU2013

31/72

Overview of the IEC 60909 Standard


o Fault level calculation in networks with DG:
2) ContributionoftheDGstations
Type III:DFIG,withpowerconvertersintherotorcircuit

Type III
DFIG
(variable speed WTs)

MortezaShabanzadehandTMU2013

32/72

Overview of the IEC 60909 Standard


o Fault level calculation in networks with DG:
2) ContributionoftheDGstations
Type III:DFIG,withpowerconvertersintherotorcircuit

LimitedovercurrentcapabilityofRotor
Statorcurrentisdominant
Crowbar protection
Crowbarprotection
RoughlyapproximatedasTypeII

Statorisdisconnectedafter30~50ms
Isc(max)<5p.u.(beforetrippingthestator)
(
) p ( f
pp g
)

MortezaShabanzadehandTMU2013

33/72

Overview of the IEC 60909 Standard


o Fault level calculation in networks with DG:
2) ContributionoftheDGstations
Type IV:Powerconverterinterfacedunits,withorwithoutrotatinggenerator

Type IV
PVs, -Turbines
variable speed WTs

MortezaShabanzadehandTMU2013

34/72

Overview of the IEC 60909 Standard


o Fault level calculation in networks with DG:
2) ContributionoftheDGstations
Type IV:Powerconverterinterfacedunits,withorwithoutrotatinggenerator

AretreatedasASynch.Machines
or
or
t isthedurationofthecontribution
(100msmaybeadoptedhereaswell)

MortezaShabanzadehandTMU2013

35/72

Case Study

PLOAD =35MVA
Type IV

PDG =17.16MW

T
Type
II
Type III

MortezaShabanzadehandTMU2013

Type I

36/72

Case Study

Type IV

Type III

Type II

Type I
MortezaShabanzadehandTMU2013

37/72

Case Study
Results

Asexpected,thecontributionofTypeIV
DGunitsismuchlowerthanallotherTypes.

Type IV

Type III

MortezaShabanzadehandTMU2013

38/72

Case Study

Results

Type II

Type I

MortezaShabanzadehandTMU2013

39/72

Case Study
Resulting fault level at the MV busbars :

Algebraic sum

Phasor sum
(with contribution of WF1 added algebraically)

MortezaShabanzadehandTMU2013

40/72

DGs short-circuit current Simulation


DGs
Technical Softwares to simulate DGs Protection behavior:
DIgSILENTPowerFactory
PSCAD
ATPEMTP

MortezaShabanzadehandTMU2013

41/72

Example (2) :
Resulting fault level in Netherland test network:
Peak Short Circuit Current (KA)

MortezaShabanzadehandTMU2013

42/72

Solutions for fault level reduction


1. Increasethedesignmaximumfaultlevel
2. Reducetheprospectiveshortcircuitcurrentofthegrid
Reconfigurationofthenetwork
Increasetheshortcircuitimpedanceofthetransformers
Reducetheprospectiveshort
Reduce the prospective shortcircuit
circuitcurrentoftheDG
current of the DG
3.ReducetheprospectiveshortcircuitcurrentoftheDG
Selectequipmentwithincreasedshortcircuitimpedance
Installationofcurrentlimitingreactors
Installation of current limiting reactors
Connectionviapowerelectronicsconverters
4.Activelimitationoftheshortcircuitcurrent

MortezaShabanzadehandTMU2013

43/72

P
Presentation
t ti
O
Outline
tli
Introduction
SCC Calculation According to IEC 60909 Standard
Impact of DGs on Fault Locating Methods
DGs Effects in Different Types of Dis. Networks
Limitation of Short-Circuit Power due to DGs

MortezaShabanzadehandTMU2013

44/72

Impact of DGs on Fault Locating Methods


o Effect of DG on Impedance Measurement Based Method :

Single-line diagram of network

MortezaShabanzadehandTMU2013

DG unit placed at upstream

DG unit placed at downstream

45/72

Impact of DGs on Fault Locating Methods


o Simulation Result :
Scenario (1): Synchronous DG = 30 MW
Scenario (2): Inverter based DG = 5 MW

single-phase to ground fault

MortezaShabanzadehandTMU2013

46/72

Impact of DGs on Fault Locating Methods


o Simulation Result :

off fault

Calculation error with DG at downstream of fault

DG at d
downstream

off fault

DG at upstream

Calculation error with DG at upstream of fault

1. InverterbasedDGsinjectless shortcircuitcurrenttothefault.
2. UpstreamDGshavemorenegative effectsonfaultlocatingmethodsincomparisontodownstreamDGs.

MortezaShabanzadehandTMU2013

47/72

P
Presentation
t ti
O
Outline
tli
Introduction
SCC Calculation According to IEC 60909 Standard
Impact of DGs on Fault Locating Methods
DGs Effects in Different Types of Dis. Networks
Limitation of Short-Circuit Power due to DGs

MortezaShabanzadehandTMU2013

48/72

DGs Effects in Different Types of Dis


DGs
Dis. Networks
o Three types of distribution systems:

Radial
Loop
L
Network

MortezaShabanzadehandTMU2013

49/72

DGs Effects in Different Types of Dis


DGs
Dis. Networks
A. Radial

MortezaShabanzadehandTMU2013

C
Case(1)
(1)

C
Case(2)Case(3)
(2)C
(3)

50/72

DGs Effects in Different Types of Dis


DGs
Dis. Networks
A. Radial
DGat7,PF

BusVoltage(p.u
u.)

DGat7,VC
DGat2~7,,
5MW,PF
DGat2~7,
5MW,VC

B #
Bus#

MortezaShabanzadehandTMU2013

51/72

DGs Effects in Different Types of Dis


DGs
Dis. Networks
A. Radial
Isc (KA)

We can see that the more connection points of DG in the system, the lower values
of short circuit currents.

MortezaShabanzadehandTMU2013

52/72

DGs Effects in Different Types of Dis


DGs
Dis. Networks
B. Loop

The
h case off shared
h d sized
d DG at two connection points provides
d b
better profile
f l around
d 1.0 p.u.

MortezaShabanzadehandTMU2013

53/72

DGs Effects in Different Types of Dis


DGs
Dis. Networks
B. Loop
Isc (KA)

As expected,
d ffault
l currents d
decrease as the
h ffault
l llocation gets far
f away ffrom the
h grid.
d

MortezaShabanzadehandTMU2013

54/72

DGs Effects in Different Types of Dis


DGs
Dis. Networks
C. Network

MortezaShabanzadehandTMU2013

34.5 kV network type test system

55/72

DGs Effects in Different Types of Dis


DGs
Dis. Networks
C. Network

MortezaShabanzadehandTMU2013

56/72

DGs Effects in Different Types of Dis


DGs
Dis. Networks
C. Network

MortezaShabanzadehandTMU2013

57/72

DGs Effects in Different Types of Dis


DGs
Dis. Networks

Dispersedlylocated DGresultsinbettervoltageprofilecomparedtosinglespot
locatedDG.
If
Ifadistributionsystemhasastronggridconnection,faultcurrentsmaynot
di t ib ti
t
h
t
id
ti
f lt
t
t
significantlyincreasewiththeadditionofDG.
AnumberofDGhavingaunitarypowerfactorcontrolshouldbelocatedalong
g
yp
f
g
distributionsystemsothatbettervoltageprofileisobtained.

MortezaShabanzadehandTMU2013

58/72

P
Presentation
t ti
O
Outline
tli
Introduction
SCC Calculation According to IEC 60909 Standard
Impact of DGs on Fault Locating Methods
DGs Effects in Different Types of Dis. Networks
Limitation of Short-Circuit Power due to DGs

MortezaShabanzadehandTMU2013

59/72

Limitation of Short-Circuit Power due to DGs


Fault Current Limiters (FCL
FCL) :
The most important requirements of an FCL are
1) Limitation of peak current (Ip) within 10ms.
(The minimum opening time of the circuit breakers is much longer
, and therefore they are not able to protect the components)

2) Ratio between nominal current and limited short-circuit current.

3) Low impedance and low losses in normal situation.

MortezaShabanzadehandTMU2013

60/72

Limitation of Short-Circuit Power due to DGs


The most important types of FCL :
1. Choke coil
p
2. Superconductors
3. Semiconductors
4. Magnetic fault current limiter
5. Is Limiter

MortezaShabanzadehandTMU2013

61/72

Limitation of Short-Circuit Power due to DGs


The most important types of FCL :
1. Choke coil
g ) impedance
p
((high)
simple and robust
voltage drop & losses during normal operation
big size

MortezaShabanzadehandTMU2013

62/72

Limitation of Short-Circuit Power due to DGs


The most important types of FCL :
2. Superconductors
use the relationship between the resistance and temperature to limit Ip, Ik.
R = 0 (when they are cooled below their critical temperature)
During fault, due to losses their temperature will increase and FCL will get a much higher R.

low losses
very fast response (Ip can be limited quite well)
very expensive
are still in development stage (not commercially available yet)

MortezaShabanzadehandTMU2013

63/72

Limitation of Short-Circuit Power due to DGs


The most important types of FCL :
3. Semiconductors
use semiconductor switches
good controllability
fast response
losses in the semiconductors

MortezaShabanzadehandTMU2013

64/72

Limitation of Short-Circuit Power due to DGs


The most important types of FCL :
4. Magnetic fault current limiter

Based on the fact that a coil, or transformer, has a very low impedance when it is in saturation

At the moment a fault occurs the large fault current forces the coil out of saturation, implying a much
higher impedance.

reliable operation
gradual and smooth change of impedance
good limiting capabilities (R8)
commercially available
large
g dimensions
high price
MortezaShabanzadehandTMU2013

65/72

Limitation of Short-Circuit Power due to DGs


The most important types of FCL :
5. Is Limiter
consists of two conductors in parallel.
The main conductor carries the nominal current
(up to 5kA).
After tripping the parallel fuse limits Ip in a very short time
( 1 ms).
(<
)

MortezaShabanzadehandTMU2013

66/72

Limitation of Short-Circuit Power due to DGs

The most important types of FCL :

5. Is Limiter
very fast
good R-ratio
small size
low losses
after each operation fuses have to be replaced;
This
h implies
l
:
relatively high costs
longer interruption times
incorrect operation

MortezaShabanzadehandTMU2013

67/72

Limitation of Short-Circuit
Short Circuit Power due to DGs

SelectionofFCL
FCL:
Thegoaloftheprocedureistofindaconfigurationforwhich
Ctot isaslowaspossible(i.e.findingmin[Ctot]):

thecostsofrepairing orreplacing componentswhichhavebeen


destroyedbecauseoftohighfaultcurrents,butalsothecostsof
customerminuteslost.

MortezaShabanzadehandTMU2013

68/72

Limitation of Short-Circuit
Short Circuit Power due to DGs
SelectionofFCL
FCL:
10
10stepproceduretoselectthebestFCL:
d
l
h b FCL
Step1. Createalistofpossiblefaultlocations;
Step2. Foreachofthepossiblefaultlocations,
conductashortcircuitcalculationusingIEC(60)909;
co
duc a s o c cu ca cu a o us g
(60)909;
Step3. Removethefaultlocationsforwhichnopeakfault
currentproblemoccurs;
Step4. Foreachoftheremainingfaultlocations:
Determinetheprobabilityofafaulttooccur;
St 5 Selectthefaultlocationwiththehighestfault
Step5.
S l t th f lt l ti
ith th hi h t f lt
occurrenceprobability.
Step6.Calculatethetotalcostsofafaultatthislocation,
withoutaddingfaultcurrentlimiting.

MortezaShabanzadehandTMU2013

Step7.Determinepossiblefaultcurrentlimiterlocations;
Step8.Foreach(combination)ofthelocations:calculate
thetotalcostsofafault,usingthetwodifferent
e o a cos s o a au , us g e o d e e
typesoffaultcurrentlimitersatthelocation(s);
Step9.Selectthesituationwiththelowesttotalcosts
causedbyafaultandpermanentlyaddthefault
currentlimiter.
St 10 R
Step10.Removethefaultlocationfromthelistand
th f lt l ti f
th li t d
restartfromstep2,repeatinguntilthereisno
faultlocationleftinthelist

69/72

Limitation of Short-Circuit
Short Circuit Power due to DGs

CHP

SelectionofFCL
FCL:

CHP

The rated Ipeak ofthesubstationis50kA


TheratedI
of the substation is 50kA

ArealnetworkinthesouthwesternpartoftheNetherlands

MortezaShabanzadehandTMU2013

70/72

Limitation of Short-Circuit
Short Circuit Power due to DGs

SelectionofFCL
FCL:
Theresultsaccordingto10stepprocedure:

MortezaShabanzadehandTMU2013

71/72

those who
th
h struggle
t l in
i our cause,
we will surely guide them to our ways;
and Allah is with those who do good.
AL ANKABOOT (69)
AL-ANKABOOT
(6 )

MortezaShabanzadehandTMU2013

72/72

También podría gustarte