Documentos de Académico
Documentos de Profesional
Documentos de Cultura
The next
generation
of OEM drives
Ease of use.
PC Software
MaxConnect and MaxLoader
software allows users to easily
configure parameters, real
time monitor critical VFD
and motor data, and compare
parameter sets. The PC
Software is free to download,
visit: www.eaton.com/m-max
for the latest revision.
Diagnostics
Extremely easy keypad
navigation allows you to
monitor 21 common values
during operation (MON menu).
Both Fault and Alarm status
for the previous 9 faults are
also stored along with time
(FLT menu).
Frame
Type
Local/Remote button
Allows the user to toggle
operation between the keypad,
I/O terminals, and fieldbus at
the push of a button, rather
than adding an HOA switch or
reprogramming your speed
reference and start sources.
EATON CORPORATION
Small Footprint
Extremely compact size
which can be Din rail or
panel mounted.
H1
H2
H3
W1
W2
W3
D1
D2
Weight
Lbs (kg)
FS1
6.16
(156.5)
5.79
(147.0)
5.40
(137.3)
2.58
(65.5)
1.49
(37.8)
0.17
(4.5)
3.88
(98.5)
0.27
(7.0)
1.213
(0.550)
FS2
7.68
(195.0)
7.20
(183.0)
6.69
(170.0)
3.54
(90.0)
2.46
(62.5)
0.22
(5.5)
4.00
(101.5)
0.27
(7.0)
1.543
(0.699)
FS3
10.33
(262.5)
9.93
(252.3)
9.50
(241.3)
3.94
(100.0)
2.95
(75.0)
0.22
(5.5)
4.27
(108.5)
0.27
(7.0)
2.183
(0.990)
EATON CORPORATION
M-Max Series
Efficiency.
30 Watt
Savings
13,140
$
1000
Units
in energy
Conformal Coating
Protective coating for printed
circuit boards. It protects
and insulates against moisture,
corrosion, dust, and thermal
shock.
50C (122F)
Rated to handle higher
ambient termperatures.
reduction
of 180,000 lbs.
Nema 1 enclosures
Available for all frame sizes
to meet Nema 1 and IP21
requirements. Includes
conduit entry plate.
EMC filters
Type C2 protection integrated
into the unit on 1 phase 230V
and 3 phase 480V units.
Brake chopper circuit
Integrated into 3 phase FS2
and FS3 units.
Global Acceptance
17
Equivalent to removing
cars off the road per year.
EATON CORPORATION
EATON CORPORATION
M-Max Series
36.2
Description
MMX = Base catalog number
36
MMX 1 1 AA 1D1 F 0 0
Phase
1 = Single-phase
3 = Three-phase
36
Option
0 = Full version
Enclosure Class
0 = NEMA 0 or IP20
Voltage
1 = 120V
4 = 480V
2 = 230V
5 = 575V
Software
Designation Series
AA
Output Current
1D6 = 1.6A
010 = 10A
36
36
36
EMC Filter
F = Filter
N = No filter
36
36
Product Selection
M-Max
Volts
1/4
100120V single-phase in
230V three-phase out
36
100% Continuous
Current IN (A)
Nominal Input
Current (A)
Frame
Size
Catalog Number
1.7
9.2
FS2
MMX11AA1D7N0-0
2.4
11.6
MMX11AA2D4N0-0
3/4
2.8
12.4
MMX11AA2D8N0-0
3.7
15
MMX11AA3D7N0-0
1-1/2
4.8
16.5
FS3
MMX11AA4D8N0-0
1.7
4.2
FS1
MMX12AA1D7F0-0
2.4
5.7
3/4
2.8
6.6
3.7
8.3
1-1/2
4.8
11.2
MMX12AA4D8F0-0
14.1
MMX12AA7D0F0-0
9.6
15.8
FS3
MMX12AA9D6F0-0
1.7
2.7
FS1
MMX32AA1D7N0-0
1/2
1/4
1/2
200240V single-phase in
230V three-phase out
3
1/4
200240V three-phase in
230V three-phase out
36
MMX12AA3D7F0-0
36
36
3.5
MMX32AA2D4N0-0
3.8
MMX32AA2D8N0-0
3.7
4.3
1-1/2
4.8
6.8
MMX32AA4D8N0-0
8.4
MMX32AA7D0N0-0
11
13.4
FS3
MMX32AA011N0-0
1.3
2.2
FS1
MMX34AA1D3F0-0
1.9
2.8
MMX34AA1D9F0-0
2.4
3.2
MMX34AA2D4F0-0
3/4
1
FS2
36
36
36
36
MMX34AA3D3F0-0
3.3
4.3
5.6
5.6
7.3
7.6
9.6
11.5
MMX34AA9D0F0-0
7-1/2
12
14.9
MMX34AA012F0-0
10
14
18.7
MMX34AA014F0-0
1.7
2.0
2.7
3.6
MMX35AA2D7N0-0
3.9
5.0
MMX35AA3D9N0-0
6.1
7.6
MMX35AA6D1N0-0
7-1/2
9.0
10.4
MMX35AA9D0N0-0
575V three-phase in
575V three-phase out
36
1-1/2
FS2
36
MMX32AA3D7N0-0
36
MMX12AA2D8F0-0
FS2
2.4
380480V three-phase in
460V three-phase out
36
MMX12AA2D4F0-0
2.8
1/2
36
3/4
1/2
36
MMX34AA4D3F0-0
36
MMX34AA5D6F0-0
FS3
FS3
MMX34AA7D6F0-0
MMX35AA1D7N0-0
36
36
36
36
36
Notes
Horsepower ratings are based on the use of a 240V, 460V, and 575V NEMA B, four- or six-pole squirrel cage induction motor and are for reference only.
Units are to be selected such that the motor current is less than or equal to the MMX rated continuous output current.
For 208V, 380V, or 415V applications, select the unit such that the motor current is less than or equal to the MMX rated continuous output current.
For MMX11_, MMX32_, and MMX35_, there are no options for units with lters.
36
36
36
Volume 6Solid-State Motor Control CA08100007EApril 2011 www.eaton.com
EATON CORPORATION
M-Max Series
V6-T36-9
36
36.2
Accessories
Ratings
Specications
Description
Description
36
Description
36
Module is plugged onto the front of the drive to provide: upload/download of all parameters, MMX-COM-PC
direct link to a PC via USB interface for parameter assignment via MaxConnect software, and
copying of parameters for a series of devices or when exchanging devices. No PC required
36
36
36
36
Catalog Number
Kits
Description
Catalog Number
MMX-IP21-FS1
MMX-IP21-FS2
MMX-IP21-FS3
36
36
36
Catalog Number
MMX-NET-XA
XMX-NET-CO-A
XMX-NET-PS-A
XMX-NET-PD-A
XMX-NET-DN-A
36
36
36
Line Reactors
Description
36
36
Undervoltage protection
Connection to power
Overtemperature
protection
Yes
36
Output voltage
0 to Vin
Continuous output
current
36
36
Output frequency
0 to 320 Hz
Frequency resolution
0.01 Hz
Yes
Motor underload
protection
Yes
Initial output current (IH) Current 2 x IN for 2 seconds in every 20-second period
Torque depends on motor
36
Control Characteristics
Frequency control (V/Hz) open loop or sensorless vector control
1.5 to 16 kHz; default 6 kHz
36
Frequency reference
36
30 to 320 Hz
Acceleration time
0 to 3000 sec
36
Reference scaling
Deceleration time
0 to 3000 sec
Braking torque
36
36
K64-000988-8091
230V Series
1 hp, 240V
K64-000988-0120
400V Series
2 hp, 240V
K64-000988-0180
575V Series
3 hp, 240V
K64-000988-0250
Ambient Conditions
36
Ambient operating
temperature
36
Storage temperature
Relative humidity
36
Air quality
Altitude
Vibration
Shock
36
K64-000989-2091
External fault
1 hp, 240V
K64-000989-4091
Fieldbus communication
2 hp, 240V
K64-000989-8091
3 hp, 240V
K64-000989-0120
36
1 hp, 480V
K64-000989-2091
PID controller
K64-000989-4091
Skip frequencies
36
2 hp, 480V
3 hp, 480V
K64-000989-4091
5 hp, 480V
K64-000989-8091
K64-000989-0180
36
10 hp, 480V
K64-000989-0250
1 hp, 575V
K64-000989-2091
Enclosure class
36
2 hp, 575V
K64-000989-8091
36
3 hp, 575V
K64-000989-8091
5 hp, 575V
K64-000989-4091
Notes
Exception: 115V single-phase in, 230V three-phase out.
Only three-phase FS2 and FS3 drives are equipped with brake chopper circuit.
36
K64-000989-0180
10 hp, 575V
K64-000989-0180
36
Notes
Type 1 kit provides conduit entry plate.
Additional input and output reactors are available. Consult Eaton representative for a complete listing.
36
36
Switching frequency
36
36
Output Ratings
36
36
Specication
Overcurrent protection
Description
Catalog Number
36
Overvoltage protection
Programmable Parameters
36
Input Ratings
Control method
36
36
Specication
Protections
36
36
36.2
36
36
36
36
36
36
36
36
36
36
36
36
36
V6-T36-10
EATON CORPORATION
EATON CORPORATION
M-Max Series
V6-T36-11
36
36
36
36
36
36.2
Dimensions
Standards
I/O Specications
Reliability
Pretested components:
standard
Computerized testing:
standard
Conformal-coated boards
Includes:
RS-485 interface
36
W2
36
36
36
H2
H3
36
36
Factory Preset
Description
36
+10V
Maximum load 10 mA
AI1
Analog signal in 1
Freq. reference P)
36
36
36
36
36
36
AUTOGEN
Ref
Current
36
36
Analog
OUT
36
36
GND
24V
Frame Type
H1
H2
H3
W1
W2
W3
D1
D2
GND
FS1
DI1
Digital input 1
Start forward P)
6.16
(156.5)
5.79
(147.0)
5.40
(137.3)
2.58
(65.5)
1.49
(37.8)
0.17
(4.5)
3.88
(98.5)
DI2
Digital input 2
Start reverse P)
FS2
7.68
(195.0)
7.20
(183.0)
6.69
(170.0)
3.54
(90.0)
2.46
(62.5)
0.22
(5.5)
10
DI3
Digital input 3
Preset speed P)
FS3
RS-485 signal A
FB communication
10.33
(262.5)
9.93
(252.3)
9.50
(241.3)
3.94
(100.0)
2.95
(75.0)
0.22
(5.5)
RS-485 signal B
FB communication
AI2
Analog signal in 2
PI actual value P)
GND
13
GND
14
DI4
Digital input 4
Preset speed B1 P)
15
DI5
Digital input 5
Fault reset P)
16
DI6
Digital input 6
Disable PI contr. P)
18
AO
Analog output
Output frequency P)
Active = READY
20
DO
22
RO11
23
RO12
24
RO21
25
RO22
36
26
RO23
36
Note
P) Parameter-selectable function.
36
36
D1
W1
36
36
36
D2
W3
H1
Terminal
36
36
M-Max Drives
50C rated
150% for one minute/
10 mm
200% for two seconds/
20 sec.
Eaton Electrical Services
and Systems: national
network of AF drive
specialists
36
36
36
36
36
36.2
Relay out 1
Active = RUN P)
Relay out 2
Active = FAULT
P)
36
0.27
(7.0)
1.213 (0.550)
36
4.00
(101.5)
0.27
(7.0)
1.543 (0.699)
36
4.27
(108.5)
0.27
(7.0)
2.183 (0.990)
36
36
36
36
36
W3
W2
36
36
P)
Weight
Lbs (kg)
36
36
36
36
W1
36
Frame Type
W1
W2
W3
FS1
36
8.14
(206.7)
3.77
(95.7)
2.99
(75.9)
3.98
(101.2)
5.41
(137.5)
FS2
36
9.90
(251.5)
4.72
(120.0)
3.97
(100.8)
4.94
(125.5)
5.68
(144.2)
FS3
12.26
(311.5)
5.12
(130.1)
4.36
(110.8)
5.33
(135.3)
6.32
(160.5)
36
36
36
36
36
36
36
V6-T36-12
EATON CORPORATION
EATON CORPORATION
M-Max Series
V6-T36-13
10
Parameter Guide
Appendix A
All Parameters
When first switching on or after activating the default settings (S4.2 = 1) parameter P1.1 must
be set to 0 for access to all parameters.
Parameter Selection
Access
PNU
ID
P1.1
115
P1.2
540
P1.3
1472
ro/rw
Designation
Value Range
Page
FS
(P1.3)
rw
0 = All parameters
1 = Only quick configuration
parameters
65/64
rw
Application
0 = Basic
1 = Pump drive
2 = Fan drive
3 = High load
65
rw
0 = EU
1 = USA
65
ro/rw
Designation
Value Range
Page
FS
(P1.3)
RUN
User
Setting
Analog Input
Access
PNU
ID
P2.1
379
rw
(microswitch S2)
0 = 010V/020 mA
1 = 210V/420 mA
66
P2.2
380
rw
100.00 to 100.00%
66
P2.3
381
rw
100.00 to 100.00%
66
100
P2.4
378
rw
0.010.0s
66
0.1
P2.5
390
rw
(microswitch S3)
Like P2.1
67
P2.6
391
rw
100.00 to 100.00%
67
P2.7
392
rw
100.00 to 100.00%
67
100
P2.8
389
rw
0.010.0s
67
0.1
150
RUN
User
Setting
EATON CORPORATION
M-Max Series
11
Digital Input
Access
PNU
ID
P3.1
300
P3.2
RUN
ro/rw
Designation
Value Range
Page
FS
(P1.3)
rw
Start/stop logic
70
0 = Deactivated
1 = Activated via control signal
terminal 8 (DI1)
2 = Activated via control signal
terminal 9 (DI2)
3 = Activated via control signal
terminal 10 (DI3)
4 = Activated via control signal
terminal 14 (DI4)
5 = Activated via control signal
terminal 15 (DI5)
6 = Activated via control signal
terminal 16 (DI6)
70
rw
403
404
rw
Like P3.2
70
P3.4
412
rw
Reverse
Like P3.2
70
P3.5
405
rw
Like P3.2
70
P3.6
406
rw
Like P3.2
71
P3.7
414
rw
Fault reset
Like P3.2
71
P3.8
407
rw
Run enable
Like P3.2
71
P3.9
419
rw
Fixed frequency,
binary value B0
Like P3.2
71
P3.10
420
rw
Fixed frequency,
binary value B1
Like P3.2
72
P3.11
421
rw
Fixed frequency,
binary value B2
Like P3.2
72
P3.12
1020
rw
PID controller,
deactivate
Like P3.2
72
P3.13
1400
(Not used)
P3.14
1401
rw
External brake,
feedback signal (N/O)
Like P3.2
72
P3.15
1402
rw
Change acceleration/
deceleration time (acc2/dec2)
Like P3.2
72
P3.16
1403
rw
Stop acceleration/deceleration
time
Like P3.2
72
P3.17
1404
rw
Like P3.2
72
P3.18
1405
rw
Like P3.2
72
P3.19
1406
rw
Motor potentiometer,
decrease value
Like P3.2
72
EATON CORPORATION
Access
User
Setting
P3.3
Parameter Guide
Appendix A
Appendix A
ro/rw
Designation
Value Range
Page
FS
(P1.3)
1407
rw
Motor potentiometer,
set value to zero
Like P3.2
72
P3.21
1408
rw
Like P3.2
72
P3.22
1409
rw
Like P3.2
73
P3.23
1410
rw
Like P3.2
73
P3.24
1411
rw
Counter, reset
Like P3.2
73
P3.25
1412
rw
Like P3.2
73
P3.26
1413
rw
Like P3.2
73
P3.27
1414
rw
Like P3.2
73
P3.28
1415
rw
Like P3.2
73
P3.29
1416
rw
065535
73
P3.30
1417
rw
065535
73
P3.31
1418
rw
DI1 logic
(control signal terminal 8)
0 = N/O
1 = N/C
73
P3.32
1419
rw
DI2 logic
(control signal terminal 9)
Like P3.31
73
P3.33
1420
rw
DI3 logic
(control signal terminal 10)
Like P3.31
74
P3.34
1421
rw
DI4 logic
(control signal terminal 14)
Like P3.31
74
P3.35
1422
rw
DI5 logic
(control signal terminal 15)
Like P3.31
74
P3.36
1423
rw
DI6 logic
(control signal terminal 16)
Like P3.31
74
P3.37
1480
rw
Manual mode
Like P3.2
74
ro/rw
Designation
Value Range
Page
FS
(P1.3)
PNU
ID
P3.20
RUN
User
Setting
Analog Output
Access
PNU
ID
P4.1
307
rw
0 = Deactivated
1 = Output frequency (Hz)
2 = Output current (A)
3 = Torque (%)
4 = PID controller (%)
75
P4.2
310
rw
0 = 0V
1 = 2V (live-zero)
75
P4.3
1456
rw
AO, gain
0.00200.00%
75
100.00
P4.4
1477
rw
0.0010.00s
75
0.0
152
151
RUN
User
Setting
EATON CORPORATION
M-Max Series
13
Appendix A
Digital Output
PNU
ID
P5.1
313
P5.2
314
RUN
Designation
Value Range
rw
RO1 Signal
(Relay 1 Output)
0 = Deactivated
76
1 = READY
2 = RUN
3 = FAULT
4 = Error message (inverted)
5 = ALARM
6 = REV
7 = Output frequency
8 = Motor controller active
9 = Zero frequency
10 = Frequency monitoring 1
11 = Frequency monitoring 2
12 = PID monitoring
13 = Overtemperature signal
14 = Overcurrent control active
15 = Overvoltage control active
16 = PLC Sequence control active
17 = PLC sequence control, single step
completed
18 = PLC sequence control, program cycle
completed
19 = PLC sequence control, pause
20 = Counter, value 1 reached
21 = Counter, value 2 reached
22 = RUN message active
23 = Analog min reference error
24 = LOG function fulfilled
25 = PID controller, actual value
monitoring
26 = External brake actuated
27 = Current monitoring
28 = Fieldbus, remote output
77
rw
RO2 signal
(relay output 2)
Like P5.1
Page
FS
(P1.3)
ro/rw
Access
User
Setting
ro/rw
Designation
Value Range
Page
FS
(P1.3)
1458
rw
DO logic
(control signal terminal 13)
0 = N/O
1 = N/C
79
P5.10
1331
rw
RO1 logic
(control signal terminal 22, 23)
Like P5.9
79
P5.11
1332
rw
RO2 logic
(control signal terminal 24, 25, 26)
Like P5.9
79
P5.12
1459
rw
DO, on delay
0.00320.00s
79
0.00
P5.13
1460
rw
DO, off-delay
0.00320.00s
79
0.00
P5.14
1461
rw
RO1, on delay
0.00320.00s
79
0.00
P5.15
1424
rw
RO1, off-delay
0.00320.00s
79
0.00
P5.16
1425
rw
RO2, on delay
0.00320.00s
79
0.00
P5.17
1426
rw
RO2, off-delay
0.00320.00s
79
0.00
ro/rw
Designation
Value Range
Page
FS
(P1.3)
PNU
ID
P5.9
RUN
Access
PNU
ID
RUN
P6.1
125
rw
80
P6.2
117
rw
80
P6.3
101
rw
Minimum frequency
0.00P6.4 Hz
81
0.00
P6.4
102
rw
Maximum frequency
P6.3320.00 Hz
81
60.00
P6.5
103
rw
0.13000s
81
3.0
P6.6
104
rw
0.13000s
81
3.0
505
rw
Start function
0 = Ramp, acceleration
1 = Flying restart circuit
82
P5.3
312
rw
DO signal
(digital output 1)
Like P5.1
77
P5.4
315
rw
Frequency monitoring 1
0 = Deactivated
1 = 0.00P5.5 Hz
2 = P5.5P6.4 Hz
77
P6.8
506
rw
Stop function
0 = Free coasting
1 = Ramp, deceleration
82
P6.9
500
rw
S ramp
0.0
316
rw
Frequency monitoring 1,
reference value
0.00P6.4 Hz
78
0.00
0.00 = Linear
0.110.0s (S-shaped)
82
P5.5
P5.6
346
rw
Frequency monitoring 2
0 = Deactivated
1 = 0.00P5.7 Hz
2 = P5.7P6.4 Hz
78
P6.10
717
rw
0.1010.00s
83
0.50
P6.11
718
rw
0.0060.00s
83
30.00
P6.12
719
rw
0 = Ramp, acceleration
1 = Flying restart circuit
2 = According to P6.7
83
P5.7
347
rw
Frequency monitoring 2,
reference value
0.00P6.4 Hz
78
0.00
P5.8
1457
rw
Current monitoring
0.00P7.2A
79
0.00
EATON CORPORATION
User
Setting
Drives Control
P6.7
Parameter Guide
Appendix A
153
154
User
Setting
EATON CORPORATION
M-Max Series
15
Appendix A
Motor
Access
PNU
ID
RUN
ro/rw
Designation
Value Range
Page
FS
(P1.3)
P6.13
731
rw
0 = Deactivated
1 = Activated
83
P6.14
1600
rw
0 = Deactivated
1 = Activated
83
RUN
ro/rw
Designation
Value Range
Page
FS
(P1.3)
P7.1
113
rw
0.2 x Ie2 x Ie
(see motor rating plate)
87
Ie
P7.2
107
rw
Current limit
0.2 x Ie2 x Ie
87
1.5 x Ie
87
0.301.00
(see motor rating plate)
87
rw
P7.4
120
rw
84
P7.5
110
rw
180500V
(see motor rating plate)
87
84
P7.6
111
rw
30320 Hz
(see motor rating plate)
87
60.00
P6.4 +P6.4 Hz
84
0.00
P6.16
1474
rw
0 = Deactivated (no)
1 = Activated (yes)
84
P6.17
1427
rw
P6.18
1428
rw
rw
0.13000s
84
10.0
P6.20
503
rw
0.13000s
84
10.0
P6.21
526
rw
0.00P6.4 Hz
84
0.00
0.00P6.4 Hz
REV blocked
0 = Deactivated
1 = Activated
rw
Access
502
1429
84
84
0.00
0
PNU
ID
RUN
ro/rw
Designation
Value Range
Page
FS
(P1.3)
P8.1
700
rw
0 = Deactivated
1 = Alarm
2 = Fault, stop according to P6.8
88
P8.2
727
rw
Undervoltage error
Like P8.1
88
P8.3
703
rw
Ground fault
Like P8.1
88
P8.4
709
rw
Stall protection
Like P8.1
89
P8.5
713
rw
Underload protection
Like P8.1
89
P8.6
704
rw
Like P8.1
89
705
rw
20 to 100C
89
40
P6.24
509
rw
0.00P6.25
85
0.00
P8.7
P6.25
510
rw
P6.24P6.4 Hz
85
0.00
P8.8
706
rw
0.0150%
89
40
P6.26
511
rw
0.00P6.27
85
0.00
P6.27
731
rw
P6.26P6.4 Hz
85
0.00
P8.9
707
rw
1200 min
89
45
P6.28
513
rw
0.00P6.29
85
0.00
P8.10
1430
rw
0.010.0s
91
0.5
P6.29
514
rw
P6.28P6.4 Hz
85
0.00
P8.11
1473
(Not used)
P6.30
759
rw
110
85
P8.12
714
rw
10.0150%
91
60.0
P6.31
1481
rw
85
P8.13
715
rw
10.0150%
91
10.0
85
0 = Deactivated
1 = Activated
85
P6.32
P6.33
1482
1483
rw
rw
User
Setting
Protective Functions
P6.19
rw
30020000 min1
112
rw
User
Setting
P7.3
P6.23
16
ID
184
1334
Access
PNU
P6.15
P6.22
Parameter Guide
Appendix A
P8.14
733
rw
Fieldbus error
Like P8.1
92
P8.15
734
rw
Like P8.1
92
User
Setting
Note
Factory settings dependent on specic drive selected.
155
156
EATON CORPORATION
M-Max Series
17
Appendix A
PID Controller
Fixed Frequencies
Access
PNU
ID
P9.1
163
RUN
ro/rw
Designation
Value Range
Page
FS
(P1.3)
rw
PID controller
0 = Deactivated
1 = Activated for drive control
2 = Activated for external application
93
P9.2
118
rw
0.01000.0%
93
100.0
P9.3
119
rw
0.00320.00s
93
10.00
P9.4
167
rw
0.0100.0%
93
0.0
P9.5
332
rw
93
P9.6
334
rw
0 = Fieldbus
1 = AI1
2 = AI2
94
P9.7
336
rw
0.0100.0%
94
0.0
P9.8
337
rw
0.0100.0%
94
100.0
P9.9
340
rw
0 = Not inverted
1 = Inverted
94
Access
User
Setting
ro/rw
Designation
Value Range
Page
FS
(P1.3)
124
rw
0.00P6.4 Hz
99
6.00
105
rw
0.00P6.4 Hz
99
12.00
P10.3
106
rw
0.00P6.4 Hz
99
18.00
P10.4
126
rw
0.00P6.4 Hz
99
24.00
P10.5
127
rw
0.00P6.4 Hz
99
30.00
P10.6
128
rw
0.00P6.4 Hz
99
36.00
P10.7
129
rw
0.00P6.4 Hz
99
48.00
P10.8
130
rw
0.00P6.4 Hz
99
60.00
P10.9
1436
rw
0 = Deactivated
1 = Program cycle, execute once
2 = Execute program cycle continuously
3 = Execute program cycle in steps
4 = Execute program cycle continuously
in steps
100
P10.10
1437
rw
0255
100
P10.11
1438
rw
010000s
101
P10.12
1439
rw
010000s
101
P10.13
1440
rw
010000s
101
PNU
ID
P10.1
P10.2
RUN
P9.10
132
rw
0.0010.0s
94
0.00
P9.11
1431
rw
0.0010.0s
94
0.0
P10.14
1441
rw
010000s
101
P10.15
1442
rw
010000s
101
P9.12
1016
rw
0.00P6.4 Hz
94
0.00
P10.16
1443
rw
010000s
101
P9.13
1018
rw
0.0100.0%
94
25.0
P10.17
1444
rw
010000s
101
P9.14
1017
rw
03600s
94
30
P10.18
1445
rw
010000s
101
P9.15
1433
rw
0.0100.0%
95
0.0
P9.16
1434
rw
0.0100.0%
95
0.0
P9.17
1435
rw
0.0100.0%
95
3.0
P9.18
1475
rw
0.132.7
95
1.0
P9.19
1476
rw
0.132.7
95
1.0
P9.20
1478
rw
0.00100.0%
95
100.0
Parameter Guide
Appendix A
EATON CORPORATION
157
158
User
Setting
EATON CORPORATION
M-Max Series
19
Appendix A
V/Hz-Characteristic Curve
Braking
Access
PNU
ID
RUN
ro/rw
Designation
Value Range
Page
FS
(P1.3)
P11.1
108
rw
0 = Linear
1 = Squared
2 = Configurable
105
Access
User
Setting
PNU
ID
RUN
ro/rw
Designation
Value Range
Page
FS
(P1.3)
P12.1
507
rw
DC braking, current
0.2 x Ie2 x Ie
110
P12.2
516
rw
0.00600.00s
110
Ie
0.00
0.0010.00 Hz
111
1.50
P11.2
602
rw
Cut-off frequency
30.00320.00 Hz
106
60.00
P12.3
515
rw
P11.3
603
rw
Output voltage
106
100.00
P12.4
508
rw
0.00600.00s
112
0.00
P12.5
504
rw
Brake chopper
114
P12.6
1447
rw
114
P12.7
1448
rw
0.00320.00s
115
0.20
P12.8
1449
rw
0.00P6.4 Hz
115
1.50
P12.9
1450
rw
0.00P6.4 Hz
115
1.00
P12.10
1451
rw
0.00P6.4 Hz
115
1.50
P12.11
1452
rw
0.00P7.2 A
115
0.00
P11.4
604
rw
0.00P11.2 Hz
107
60.00
P11.5
605
rw
0.00P11.3%
107
100.00
P11.6
606
rw
Output voltage at 0 Hz
0.0040.00%
107
0.00
P11.7
109
rw
Torque increase
0 = Deactivated
1 = Enabled
107
P11.8
600
rw
Control mode
107
P11.9
601
rw
Carrier frequency
1.516.0 kHz
109
6.0
P11.10
522
rw
Sine-wave filter
(constant carrier frequency)
0 = Deactivated
1 = Enabled
109
Parameter Guide
Appendix A
EATON CORPORATION
159
160
User
Setting
EATON CORPORATION
M-Max Series
21
Appendix A
Logic Function
FS
(P1.3)
PNU
ID
RUN
ro/rw
Designation
Value Range
P13.1
1453
rw
LOG function,
selection input A
0 = Deactivated
117
1 = READY
2 = RUN
3 = FAULT
4 = Error message (inverted)
5 = ALARM
6 = REV
7 = Output frequency = frequency setpoint
8 = Motor controller active
9 = Zero frequency
10 = Frequency monitoring 1
11 = Frequency monitoring 2
12 = PID monitoring
13 = Overtemperature signal
14 = Overcurrent control active
15 = Overvoltage control active
16 = PLC sequence control active
17 = PLC sequence control, single step
completed
18 = PLC sequence control, program cycle
completed
19 = PLC Sequence control, pause
20 = Counter, value 1 reached
21 = Counter, value 2 reached
22 = RUN message active
23 = Analog min. reference error
24 = LOG function fulfilled
25 = PID controller, actual value
monitoring
26 = External brake actuated
27 = Current monitoring
28 = Fieldbus, remote output
1454
rw
Like P13.1
118
P13.3
1455
rw
0 = A AND B
1 = A OR B
2 = A XOR B
118
EATON CORPORATION
Access
User
Setting
PNU
ID
RUN
ro/rw
Designation
Value Range
Page
FS
(P1.3)
P14.1
1347
rw
0.2 x Ie2 x Ie
(see motor rating plate)
119
Ie
P14.2
1352
rw
Current (2PS)
0.2 x Ie2 x Ie
119
1.5 x Ie
119
0.301.00
(see motor rating plate)
119
P14.3
1350
rw
P14.4
1351
rw
P14.5
1348
rw
180500V
(see motor rating plate)
119
P14.6
1349
rw
30320 Hz
(see motor rating plate)
119
60.00
P14.7
1343
rw
0.00P14.8 Hz
119
0.00
P14.8
1344
rw
P14.7320.00 Hz
119
60.00
P14.9
1345
rw
0.13000s
119
3.0
P14.10
1346
rw
0.13000s
119
3.0
P14.11
1355
rw
0 = Linear
1 = Squared
2 = Configurable
120
P14.12
1354
rw
0 = Deactivated
1 = Activated
120
P14.13
1353
rw
0 = Deactivated
1 = Alarm
2 = Fault, stop according to P6.8
120
P14.14
1469
rw
20 to 100C
120
40
P14.15
1470
rw
0.0150%
120
40.0
P14.16
1471
rw
1200 min
120
45
User
Setting
P13.2
Parameter Guide
Appendix A
) (2PS)
Note
Factory settings dependent on specic drive selected.
161
162
EATON CORPORATION
M-Max Series
23
Appendix A
System Parameters
Access
PNU
ID
RUN
Parameter Guide
Appendix A
ro/rw
Designation
Value Range
Page
FS
(P1.3)
Access
User
Setting
PNU
ID
RUN
ro/rw
Designation
Value Range
Page
FS
(P1.3)
Unit Counter
S1.1
833
ro
API SW ID
123
S3.1
827
ro
MWh counter
MWh
124
S1.2
834
ro
API SW version
123
S3.2
828
ro
Operating days
00000 days
124
S1.3
835
ro
Power SW ID
123
S3.3
829
ro
Operating hours
024 h
124
S1.4
836
ro
Power SW version
123
S3.4
840
ro
00000 days
124
S1.5
837
ro
Application ID
123
S3.5
841
ro
024 h
124
S1.6
838
ro
Application revision
123
S3.6
842
ro
Fault/alarm counter
124
S1.7
839
ro
System load
123
User Set
rw
Display contrast
015
124
ro
Communication status
In xx.yyy format
xx = Number of error messages
(064)
yyy = number of correct messages
(0999)
123
rw
124
ro
Password
00009999
124
0000
Communication
S2.1
808
User
Setting
S2.2
809
rw
Fieldbus protocol
0 = FB disabled
1 = Modbus RTU
123
S2.3
810
rw
Slave address
1255
123
S2.4
811
rw
Baud rate
0 = 300
1 = 600
2 = 1200
3 = 2400
4 = 4800
5 = 9600
6 = 19200
7 = 38400
8 = 57600
123
S2.6
813
rw
Parity type
124
S2.7
814
rw
Communication timeout
0 = Not used
1 = 1s
2 = 2s
255 = up to 255s
124
S2.8
815
rw
0 = Not used
1 = Resets parameter S2.1
124
S4.1
830
S4.2
831
S4.3
832
Note
These parameters are overwritten with the bus-specic parameters when a eldbus connection (for example, CANopen) is used.
The parameter values described in the manual of the eldbus interface then apply.
EATON CORPORATION
163
164
EATON CORPORATION
M-Max Series
25
Appendix A
Parameters marked with M (Monitor) are values currently being measured, variables
calculated from these measured values, or status values from control signals.
The M parameters cannot be edited (only display values).
Parameter Values Currently Being Measured
Access
PNU
ID
RUN
ro/rw
Designation
Value Range
Page
FS
(P1.3)
User
Setting
Display Values
M1.1
ro
Output frequency
Hz
125
0.00
M1.2
25
ro
Hz
125
0.00
M1.3
ro
125
M1.4
ro
Motor current
125
0.00
M1.5
ro
Motor torque
% (calculated value)
125
0.0
M1.6
ro
Motor power
% (calculated value)
125
0.0
M1.7
ro
Motor voltage
125
0.0
M1.8
ro
125
0.0
M1.9
ro
Unit temperature
F (C)
125
M1.10
ro
Motor temperature
% (calculated value)
125
M1.11
13
ro
Analog input 1
125
0.0
M1.12
14
ro
Analog input 2
125
0.0
M1.13
26
ro
Analog output 1
125
0.0
M1.14
15
ro
Digital input 13
125
M1.15
16
ro
Digital input 46
126
M1.16
17
ro
Digital output
126
M1.17
20
ro
126
0.0
M1.18
21
ro
PID feedback
126
0.0
M1.19
22
ro
126
0.0
M1.20
23
ro
PID output
126
0.0
M1.21
1480
ro
126
EATON CORPORATION
165
EATON CORPORATION
M-Max Series
27
28
EATON CORPORATION
EATON CORPORATION
M-Max Series
29
30
EATON CORPORATION
EATON CORPORATION
M-Max Series
31
Demo Overview
Mode Navigation
BACK
To change the mode (REF, MON, PAR, FLT), hit the RESET
untill the screen clears and the left mode arrow begins to flash.
Use the up/down arrows to switch between modes, select OK
to enter the new mode.
REF
MON
PAR
FLT
Example Starting Point
REF
MON
PAR
FLT
M 1.1
BACK
RESET
0.00
REF
MON
PAR
FLT
REF
MON
PAR
FLT
OK
REF
MON
PAR
FLT
P 1.1
0
Monitor Navigation
MON allows you to
display 21 different
values. The monitor
mode also displays the
units of the value. You
can scroll through all of
the different monitored
values by pressing the
up and down arrows.
Press the OK button
to view the selected
value. In the monitor
mode, values can not
be altered.
M 1.2
OK
0.00
OK
OK
OK
0.00
Hz
Example
Starting
Point
REF
MON
PAR
FLT
Hz
M 1.1
0.00
Hz
M 1.21
0.00
EATON CORPORATION
M-Max Series
32
Parameter Navigation
Display Overview
PAR mode allows you to view and alter all of the parameters within the
drive. When you enter parameter mode you will be starting at parameter
P1.1. The up/down arrows allow you to scroll one parameter at a time.
The right/left arrows allow you to jump from parameter group to group.
P 1.3
P 2.3
P 3.3
BACK/RESET
LOC/REM
P 1.2
REF
MON
PAR
FLT
Example
Starting
Point
P 2.2
P 1.1
P 3.2
P 2.1
P 3.1
0.00
S 4.3
P 1.3
S 4.2
P 2.8
P 1.2
Start button
This will only start the drive
when in LOC of keypad mode
a READY indication is also
needed for the drive to start.
P 2.7
Parameter Modification
Navigate to the Parameter value you would like to alter, press OK.
The value will flash. The up/down arrows will adjust the value.
Press OK again to select the new value. The display will now flash
the parameter number and new value.
Starting
Point
REF
MON
PAR
FLT
OK
P 3.1
OK
P 3.1
1
33
EATON CORPORATION
Directional Arrows
Stop button
OK
3
Example
Demo Overview
EATON CORPORATION
M-Max Series
34
Demo Overview
Eaton has created an online learning center for the M-Max VFD.
The learning center is meant to serve two purposes:
Training guide
It allows the user to interface with a virtual M-Max VFD and
demo unit. We have written scripts for multiple modules of the
learning center that help walk the user through a step by step
explanation of how the VFD and demo case operates. An brief
explanation of those sections are below.
DISPLAY
DISPLAY
DISPLAY
DISPLAY
OVERVIEW
OVERVIEW
OVERVIEW
OVERVIEW
A close up look at the drives
keypad and display along with
explanations of all of the
functions.
35
EATON CORPORATION
DEFAULT
DEFAULT
DEFAULT
DEFAULT
I/O
I/O
I/O
I/O
DEMO
DEMO
DEMO
DEMO
A step by step review of the
demo cases default program.
Teaching guide
The online learning center is a great tool for sales and
customers to use during group training sessions. It helps both
the class instructor and the trainees follow along as you walk
them through proper operation of the VFD and demo.
BASIC
BASIC
BASIC
BASIC
KEYPAD
KEYPAD
KEYPAD
KEYPAD
NAV
NAV
NAV
NAV
A step by step review of some
basic keypad navigation and
parameter changes.
UN-DIRECTED
UN-DIRECTED
UN-DIRECTED
UN-DIRECTED
Allows the user to interface
with the online demo in an
unscripted, "trial by error",
scenario.
Eaton Corporation
Electrical Sector
1111 Superior Ave.
Cleveland, OH 44114
United States
877-ETN-CARE (877-386-2273)
Eaton.com
2011 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. TR04002001E
June 2011