Grid Stations Visit ( Date : 13 / 11 / 2014 )

Syed Adeel Shaukat (AM GSM West) Emp # 80013189

Jacob Lines Grid Station


Visited Jacob Lines G/S and carried out hazard identification in 11 kV and 132 kV yards.
Registered entry in security book and control room log book. First got information about
emergency exits and assembly point. A few trench covers were found missing in 11kV yard
but temporary arrangement has been made. In 132kV yard, Wall of a room was found
dangerously cracked; this is a serious safety hazard as the scrap location is right beside the
cracked wall. Some transformer control cable trenches were also uncovered.
A major issue that I observed was the concrete base of red phase cable riser of Trafo # 1 is
cracked. As the load on this cable termination is severe therefore it is a major safety hazard.

Baloch Colony Grid Station


Next visited Baloch G/S and repeated the same procedure. Then observed safety hazards. In
11kV yard, few trench covers were missing. In 132kV yard, Almost all of the control cable
trench covers are unavailable. This is a serious safety hazard to the control cables as well
because they are prone to damage. Power cable trench broken and also covers were also
missing at some points. In 132kV yard some fire hazards were present; an empty cable drum
and dry bushes.

Gulistan-e-Johar Grid Station


Next visited Johar G/S and repeated the same entry procedure. Then visited the whole grid
station. Trench covers were missing in 11kV yard. Then arranged forced shutdown of Trafo #
1 for rack-out issue of switch # 1. Made entry in log book for shutdown and tool box talk by
supervisor. After arranging of shutdown by SBO, locked the 132kV isolator and racked out
the incoming switch # 6. Then opened front plate of switch # 1 and manually racked out the
switch. Hazard was identified as charged spring mechanism, it was discharged. Mr. Qaiser
suggested as a safe method it was safer to discharge the spring after closing the front plate.
Then opened the back plate of the incoming switch # 6 and gang incharge discharged busbar
and cable. Then racked in the incoming trolley. After that gave clearance of the shutdown.

Gulistan-e-Johar

Baloch Colony

Jacob Lines

GRID

HAZARD NATURE

DETAIL

CONTROL

LOCATION (11kV
yard)

Missing Trench Covers

Place trench covers, make temporary


arrangement, or avoid walking over
trench

EQUIPMENT (11kV
SWITCHGEAR)

Live Equipment

Do not enter unnecessarily, avoid


horse play

LOCATION (132kV
yard)

No Fencing

Properly demarcate live equipment


with hazard signs

LOCATION (132kV
yard)

No Demarcation of Scrap
and Usable item

Sort out both items and properly


barricade scrap

LOCATION (SCRAP
yard)

Cracked wall

Arrange for civil repairs, avoid going


close to wall when in scrap yard

EQUIPMENT (132kV
cable riser)

Cracked base

Arrange for civil repairs

LOCATION (11kV
yard)

Missing Trench Covers

LOCATION (132kV
yard)

Broken & Missing Trench


Covers

Place trench covers, make temporary


arrangement, or avoid walking over
trench & arrange for civil repairs

LOCATION (132kV
yard)

Empty Oil Drum

Fire Hazard, place in scrap yard

LOCATION (132kV
yard)

Dry cut bushes

Dispose off at a safe place, preferably


out of grid station area

EQUIPMENT (11kV
SWITCHGEAR)

Live Equipment

Do not enter unnecessarily, avoid


horse play

LOCATION (11kV
yard)

Missing Trench Covers

Place trench covers, make temporary


arrangement, or avoid walking over
trench

11 kV Voltage Hazard

Take Shutdown of Transformer, Lock


the isolator, Rack out Incoming, check
with LLT & discharge the charging
voltage

Spring Mechanism Hazard

Discharge the spring before working


on mechanism

Injury Hazard

Keep Fingers away from edges of


trolley

ACTIVITY (11kV
Trolley Rack Out
Issue)
ACTIVITY (11kV
Trolley Rack Out
Issue)
ACTIVITY (11kV
Incoming Rack In)