Documentos de Académico
Documentos de Profesional
Documentos de Cultura
SwitchgearTrainingCentre,Coonoor
Type2CoordinationinLow
VoltageMotorFeeders Star
DeltaStarter
by:K.Sivakumar,SwitchgearTrainingCentre,Coonoor.
MOTORDATA
S.C. INDUCTION MOTOR
100 HP, IrM(Line) = 135A; IrM(Phase) = 78A
ILR = 6 IrM
STARTING METHOD : STAR/DELTA
STARTING TIME: 8 sec.
STAR/DELTASTARTER MAINCIRCUIT
Q2
Q3
A1
B1
C1
C2
A2
B2
Q1
STAR/DELTASTARTEROPERATION
CONTACTOR SEQUENCE
CONTACTOR
START
TRANSITION
ON
STAR, Q1
MAIN, Q2
DELTA, Q3
TYPICALCURVEOFCURRENT
DURINGASTAR/DELTASTART
12 IrM
CURRENT(RMS)
8 IrM
6 IrM
ID
4 IrM
2 IrM
IY
IrM
TIME
SELECTIONOFCONTACTORS
Currents experienced by the Contactors
During Starting
During Running
Contactor
Ie(AC3)
Ib
Im
Ie(AC3)
Ib
Im
Main
IrM/3
2IrM
2IrM
IrM/3
6IrM/3
N.A.
Star
IrM/3
2IrM
N.A.
N.A.
N.A.
N.A.
Delta
N.A.
N.A.
N.A.
IrM/3
6IrM/3
6IrM/3
SELECTIONOFCONTACTORS
Currents experienced by the Contactors
During Starting
Contactor Ie(AC3)
During Running
Ib
Im
Ie(AC3)
Ib
Im
Main (A)
45
270
270
78
468
N.A.
Star (A)
Delta (A)
45
270
N.A.
N.A.
N.A.
N.A.
78
468
468
N.A.
N.A. N.A.
SelectionofMain&DeltaContactors
Main Contactor:
Required
Ie(AC3) > 78A
Im > 270A
Ib > 468A
SelectionofMain&DeltaContactors
But, the full load current of the motor is derived at
assuming certain efficiencies & power factor. In
practice, these may vary. So, whenever the motor
full load current and the contactor rating are very
close, it is better to go for the next higher size of
contactor. So, in this case too since the motor full
load current (Phase) is 78A & the contactor rating
is 80A, it is advisable to opt for the next higher
size contactor, which is 95A. So, for Main & Delta
contactors we have to select 95A Contactor (MNX
95).
SelectionofStarContactor
Star Contactor:
Required
Ie(AC3) > 45A
Im - N.A.
Ib > 270A
SelectionofContactor
So, one can go for the next higher size contactor, say,
50A.
As far the Icw ratings of the contactors both the Star
& the Main contactors will have to tolerate 270A for 8
seconds. The 50 A Star contactor, whose Icw rating as
per IS is 400 A for 10s. Then this can withstand 270 A
for 21.94 sec. But, the starting time is only 8s. So, no
problem.
Similarly, the 95A main contactor can withstand 760A
for 10s, which corresponds to 270A for 79.23s, which
is much more than the starting time. So, okay.
SelectionofOLR
Selection of OLR:
OLR to be connected in Phase Circuit to reduce cost.
Phase Current = 78A
Relays available: 66 110A (MNX-R4) &
60 100A (MNX-R5)
But, MNX-R5 cannot be mounted on to the MNX 95
contactor. So, select 66 110A (MNX-R4) OLR. Set
at 78A.
Relay operating time (minimum) for 270A (3.5 times)
is 15s. This is more than the starting time of 8s. So,
relay selected is okay.
Type2Coordination CaseStudy
SelectionofHRCFuse
Motor Full Load Current
Inrush Current @ 12IrM
Inrush Duration
Staring Current @ 2IrM
Staring Time
135A
1620A
10 milliseconds
270A
8 sec.
Fuse Selection:
Condition 1: In of Fuse shall be > 135A;
Condition 2: Operating time of fuse for Motor Inrush
Current, shall be greater than 10 m.sec.
Condition 3: Operating time of fuse for Motor Starting
Current, shall be greater than 8 sec.
Type2Coordination CaseStudy
SelectionofHRCFuse
Required
Available
160A Fuse
In > 135A
160A
300ms
1000 s
Type2Coordination CaseStudy
SelectionofHRCFuse
It is to be noted that this 160A Fuse is
suitable - only when considered
individually. In co-ordination with OLR &
Contactor, this may not be suitable. Lets
study this:
Type2Coordination CaseStudy
SelectionofHRCFuse
6 IrM
7 IrM
9 IrM
9.5 IrM
Op. time
5 IrM
8 IrM
for current 675A
810A
945A
1080A 1215A 1282A
multiples
(390A) (468A) (546A) (623A) (701A) (740A)
66-110A
OLR set @
78A
12
sec.
9 sec.
7.5
sec.
6.5
sec.
5.5
sec.
5 sec.
160A Fuse
120s
65s
30s
25s
12s
4.5s
Type2Coordination CaseStudy
SelectionofHRCFuse
Remember! we had selected 95A Contactors for
Main & Delta contactors for this motor, whose
breaking capacity is at least 760A. Now, if we
select the 160A Fuse, as can be seen from the chart,
it will allow the OLR to operate first for all faults
up to about 740A (phase current) and the fuse takes
over at about 740A (phase current), which is very
close to the ultimate breaking capacity of the
contactors. Thus, Type-2 Co-ordination is
ensured. The starter components selected are
okay.
Type2Coordination CaseStudy
Justforverification
Startercomponentsfor100HPStarDelta
Make
Switch
Fuse
L&T
200A
160A
Contactors
Main Delta
Star
95A
80A
95A
OLR
66110A
Current
Line
Phase
135A
77.9A
ThankYou
stccoonoor@LNTEBG.com
sivakumark@LNTEBG.com